LG ASNW096FE, ASUW126FUG0, ASNW126F1G0, ASNW126FE, ASNW126F2G0 Service Manual

...
LG
Room Air Conditioner
SERVICE MANUAL
LG
MODELS: ASNW096F1G0
ASNW096FE/V/GG0 ASNW126F1G0 ASNW126FE/V/GG0 ASUW126FUGO ASNW126F2G0(A12AW2-NF6) ASUW126FUGO(A12AWU-UF6)
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name.................................................................................................................................3
Safety Precautions ...........................................................................................................................4
Dimensions .....................................................................................................................................10
Installation.......................................................................................................................................12
Flaring work and connection of piping.........................................................................................15
Checking the drainage and forming the pipings .........................................................................18
Air purging ......................................................................................................................................19
Test running ....................................................................................................................................22
Functions.........................................................................................................................................23
Operation.........................................................................................................................................27
Disassembly....................................................................................................................................40
Troubleshooting Guide ..................................................................................................................42
Schematic Diagram ........................................................................................................................62
Product Specifications ..................................................................................................................68
Exploded View ................................................................................................................................69
Replacement Parts List ..................................................................................................................71
Service Manual 3
LG Model Name
LG Model Name
2006
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 0~9 LG Model De
* ARTCOOL COLOR (SF)
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
1 Kiss E Red V Silver G Gold
Ex.F → SF Chassis
4 Room Air Conditioner
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Installation
Do not use damaged power cords, plugs, or a loose sock­et.
• There is risk of fire or electric
shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• There is risk of fire or electric shock.
Always use the power plug and socket with the ground terminal.
• There is risk of electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Do not modify or extend the power cord.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Service Manual 5
Safety Precautions
Operation
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the con­denser and evaporator.
For installation, always con­tact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, prod­uct failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furnishings.
Take care to ensure that power cords could not be pulled out or damaged during operation.
• There is risk of fire or electrical shock.
Do not place anything on the power cord.
• There is risk of fire or electric shock.
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
• There is risk of fire or electrical shock.
6 Room Air Conditioner
Safety Precautions
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
• There is risk of fire or electrical shock.
Do not place a heater or other appliances near the power cable.
• There is risk of fire and electric shock.
Do not allow water to run into electric parts.
• It may cause There is risk of fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustibles near the air conditioner.
• There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
• Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on. DO NOT use the telephone or turn switches on or off.
• There is risk of explosion or fire.
Unplug the unit if strange sounds, odors, or smoke comes from it.
• There is risk of electrical shock or fire
Stop operation and close the window in storm or hurricane. If possible, remove the air conditioner from the window before the hurricane arrives.
• There is risk of property dam­age, failure of product, or elec­tric shock.
Thinner
Wax
Service Manual 7
Safety Precautions
Installation
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.
When the product is soaked (flooded or submerged), con­tact an Authorized Service Center.
• There is risk of fire or eletric shock.
Ventilate the product from time to time when operating it together with a stove, etc.
• There is risk of fire or electrical shock.
Unplug the appliance before performing cleaning or main­tenance.
• There is risk of electrical shock.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
• There is risk of product damage or failure, or unintended opera­tion.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
• This could result in personal injury and product damage.
Always check for gas (refriger­ant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leak­age.
90˚
8 Room Air Conditioner
Safety Precautions
Operation
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the air condi­tioner.
Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evapora­tor fins, could cause product malfunction or inefficient opera­tion.
Do not direct airflow at room occupants. (Don't sit in the draft.)
This could damage your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, sol­vents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
There is risk of personal injury and failure of product.
Service Manual 9
Safety Precautions
Always insert the filter secure­ly. Clean the filter every two weeks or more often if neces­sary.
A dirty filter reduces the efficien­cy of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the unit.
It is not sanitary and could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the air conditioner.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of bat­teries.
There is risk of fire or explosion
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn or explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
The chemicals in batteries could cause burns or other health hazards.
Disuse
10 Room Air Conditioner
Dimensions
Dimensions
Pipe Hole
Fix Hole
Hanger Hole
H
W
D
W mm 600
H mm 600
D mm 146(143)
Model
Dimension
INDOOR
Indoor Unit
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Service Manual 11
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
DIM unit
W mm 770
H mm 545
D mm 245 L1 mm 285 L2 mm 64 L3 mm 518 L4 mm 10 L5 mm 100
Dimensions
Outdoor Unit
OUTDOOR
12 Room Air Conditioner
Installation
Installation
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in
front of the unit.
Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or
rain exposure, make sure that heat radiation from the con­denser is not restricted.
Ensure that the space around the back and sides is more
than 30cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the weight of the air conditioner into account and select
a place where noise and vibration are minimum.
Select a place where the warm air and noise from the air
conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof struc­ture and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
More than 20cm
More
than 50cm
More than 1.5m
More
than 50cm
Capacity is based on standard length and maxi­mum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
5k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30 3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
If piping length is more than 5m
Selection of the Best Location
Piping Length and Elevation
More than 30cm
More than 30cm
More than 60cm
More than 60cm
More than 70cm
Service Manual 13
Installation
Preparing Work for Installation
Open panel front
1. Pull the upper part of the front panel.
2. Lift up the panel.
3. To detach the front panel, remove the two screws at the lower part.
4. Detach the front panel from the body.
5. To detach the panel, disconnect the connector at the upper part.
Cover pipe and cover side remove
1. Please remove the screw of the center tuning cover.
2. Pull up the side cover of desired connecting direction, then cover side is separated.
3. Pick the pipe hole of the side cover.
CAUTION: After removing the pipe hole, cut the burr for safety.
When making pipe path through rear wall, you dont need to pick the pipe hole.
NOTICE
Drain hose junction
1. Remove the rubber stopple in the desired drain direc­tion.
2. Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.
Panel Front
Connector
Pipe hole
Side cover
Adhesive
Only the
Only the
desired direction
desired direction
Drain hose
Connecting
part
rubber cap
14 Room Air Conditioner
Installation
Fixing Indoor Unit
Drill the piping hole with a ø50mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Drill a Hole in the Wall
5-7mm
(0.2~0.3")
Indoor
WALL
Outdoor
Plastic anchors
INSTALLATION GUIDE MAP
10mm
INSTALLATION GU
INSTAIIATION GUIDE MAP
Plastic anchors
INSTALLATION GUIDE MAP
INSTALLATION GUIDE MAP
Hanger hole
(Rear side of
the product)
3. Make a hole with a diameter of 6mm and depth of 30-35mm by piercing a screw point.
5. Drive the fore plastic anchors into drilled points.
7. Hang the hole of product at the upper screws, and remove the map. (Falling attention)
9. Check the fixed product with light power.
1. Attach an Installation guide map on the desired surface.
2. Look at suited horizon by horizontal meter on the horizontal setting line, and fix lightly the map by adhesive tape.
4.
Drill the pierted part as a diameter of 50mm for connecting piping. (In case of piercing rear surface)
6.
First, Drive the two points of the upper parts by screws. (Leave 10mm for hanging the product)
8. Drive the lower parts after facing the hole of product with plastic anchors, and fix completely the upper screws.
10.
In case of nothing wrong, connect the pipe and the wire. (Refer to installation manual)
I
NSTALLATION GUIDE MAP
Horizontality
Service Manual 15
Flaring work and connection of piping
Flaring work and connection of piping
Flaring work
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the follow­ing procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Preparing the indoor unit's piping and drain hose for instal­lation through the wall.
Route the indoor tubing and the drain hose in the direction of rear left or right
Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
Carry out flaring work using flaring tool as shown below.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direc­tion as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Pipe
Reamer
Point down
Flare nut
Copper tube
Drain hose
mm inch mm
Ø6.35 1/4 0~0.5 Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5 Ø15.88 5/8 0~1.0 Ø19.05 3/4 1.0~1.3
Outside diameter A
Connection of piping -- Indoor
Copper
pipe
Slanted Uneven Rough
90°
16 Room Air Conditioner
Flaring work and connection of piping
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Indoor unit tubing Flare nut Pipes
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear piping hous-
ing section with vinyl tape.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
CAUTION: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage fur­niture or floors. *Foamed polyethylene or equivalent is recom­mended.
Connecting cable
Gas side piping
Liquid side piping
Drain hose
Loop
CAUTION: Installation Information For right piping. Follow the instruction below.
Good case
Press on the upper side of clamp and unfold the tub­ing to downward slowly.
Service Manual 17
Flaring work and connection of piping
Bad case
Following bending type from left to right may cause damage to the turbing.
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Connection of the pipes-Outdoor
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
18 Room Air Conditioner
Checking the drainage and forming the pipings
Checking the drainage and forming the pipings
Checking the drainage Form the piping
To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the indoor
unit without any leakage and goes out the drain exit.
Form the piping by wrapping the connecting portion of the indoor unit with insulation mate­rial and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using sad­dle or equivalent.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap
to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.
Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Service Manual 19
Air purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and block cap-
illary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
Do a leak test of all joints of the tubing(both indoor and out­door) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been complet­ed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leak test
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
Air Purging
Air purging
Air purging with vacuum pump
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
20 Room Air Conditioner
Air purging
Evacuation
Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
(1) Remove the caps from the 2-way and 3-way valves. (2) Remove the service-port cap from the 3-way valve. (3) To open the 2-way valve turn the valve stem counter-
clockwise approximately 90°, wait for about 2~3 sec, and close it.
(4) Apply a soap water or a liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Soap water method
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Required time for evacuation when 30 gal/h vacuum
pump is used
10 min. or more 15 min. or more
If tubing length is less than 10m (33 ft)
if tubing length is longer than 10m (33 ft)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Service Manual 21
Air purging
1. First, Check the side cover assembly exactly, and fix the power cord in the bottom groove of cover side left.
2. Assemble connecting lead wire with controller, fix the upper part of panel front, and match the lower part of panel front.
3. Screw up panel front, and suspend the hook of panel front in the groove.
Panel Front
Connector
Panel Front Assembly
22 Room Air Conditioner
Test running
Test Running
1. Check that all tubing and wiring have been properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote controller
1. Remove the battery cover by pulling it according to the arrow direction.
2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
3. Reattach the cover by
pushing it back into position.
Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
Remove the batteries from the remote control if the system is not going to be used for a long time.
Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is con­veyed to the hose, secure the unit with an anti­vibration bushing.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake tempera­ture and the discharge is more than 8°C(46°F) (Cooling) or (Heating).
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pres­sure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
NOTICE
NOTICE
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A 35°C (95°F) 8.5~9.5kg/cm
2
G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
PUMP DOWN