LG ARUV080BTS4 INSTALLATION MANUAL

www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.your set and retain it for future reference.
P/NO : MFL67221415
220-240 V3~ 50Hz / 220 V3~ 60Hz
ENGLISH
2
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
IMPORTANT SAFETY INSTRUC­TIONS
READ ALL INSTRUCTIONS BEFORE USING THE AP­PLIANCE.
Always comply with the following precautions to avoid dangerous situ­ations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in haz­ards to you and others.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Have all electric work done by a licensed electrician according to "Elec­tric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is per-
formed improperly, electric shock or fire may result.
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric
shock, or fire.
• Always ground the product.
- There is risk of fire or electric shock.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Do not store or use flammable gas or combustibles near the air condi­tioner.
- There is risk of fire or failure of product.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Prepare for strong wind or earthquake and install the unit at the speci­fied place.
- Improper installation may cause the unit to topple and result in injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• When installing and moving the air conditioner to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the
refrigerant cycle may malfunction and the unit may be damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is
shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
• Ventilate before operating air conditioner when gas leaked out.
- It may cause explosion, fire, and burn.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed securely, dust or water may
enter the outdoor unit and fire or electric shock may result.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
- Consult the dealer regarding the appropriate measures to prevent the
safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
Operation
• Do not damage or use an unspecified power cord.
- There is risk of fire, electric shock, explosion, or injury.
• Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Do not touch the power switch with wet hands.
- There is risk of fire, electric shock, explosion, or injury.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious not to touch the sharp edges when installing.
- It may cause injury.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
• Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
!
!
!
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehu­midifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
3
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Use power cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Keep the unit away from children. The heat exchanger is very sharp.
- It can cause the injury, such as cutting the finger. Also the damaged fin may re-
sult in degradation of capacity.
• When installting the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
-
The inverter equipment, private power generator, high-frequency medical equipment, or radio communication equipment may cause the air condi­tioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs med­ical treatment or image broadcasting.
• Do not install the product where it is exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser
and evaporator fins, could cause product malfunction or inefficient operation.
Operation
• Do not use the air conditioner in special environments.
-
Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
• Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
• Make the connections securely so that the outside force of the cable may not be applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property
damage, product failure, or personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
- A bad connection may cause water leakage.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
-
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspending it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
• Safely dispose of the packing materials.
-
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
-
Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
• Turn on the power at least 6 hours before starting operation.
- Starting operation immediately after turning on the main power switch can re-
sult in severe damage to internal parts. Keep the power switch turned on dur­ing the operational season.
• Do not touch any of the refrigerant piping during and after operation.
- It can cause a burn or frostbite.
• Do not operate the air conditioner with the panels or guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not directly turn off the main power switch after stopping operation.
- Wait at least 5 minutes before turning off the main power switch. Otherwise it
may result in water leakage or other problems.
Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the indoor unit PCB.
• Use a firm stool or ladder when cleaning or maintaining the air conditioner.
- Be careful and avoid personal injury.
• Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
- There are sharp and moving parts that could cause personal injury.
TABLE OF CONTENTS
2 TIPS FOR SAVING ENERGY 2 IMPORTANT SAFETY INSTRUCTIONS
4 INSTALLATION PROCESS 4 OUTDOOR UNITS INFORMATION 6 ALTERNATIVE REFRIGERANT R410A 6 SELECT THE BEST LOCATION 6 INSTALLATION SPACE
6 Individual Installation
7 LIFTING METHOD 7 INSTALLATION
7 The location of the Anchor bolts 7 Foundation for Installation 8 Preparation of Piping 9
Plumbing materials and storage methods
10 REFRIGERANT PIPING INSTALLATION
10 Precautions on Pipe connection / Valve operation
10
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
10 Preparation Work 11 Pipe Drawing Out during Single / Series connection 11 Refrigerant piping system 12 Pipe Connection Method between outdoor unit/indoor unit 15 Refrigerant charging 15 Distribution Method 16 Branch pipe Fitting 17 Leak Test and Vacuum drying 18 Vacuum Mode 18 Thermal insulation of refrigerant piping 19 Penetrations
19 ELECTRICAL WIRING
19 Caution 20 Control box and connecting position of wiring 20 Communication and Power Cables 21 Wiring of main power supply and equipment capacity 21 Field Wiring 23 Checking the setting of outdoor units 23 Automatic Addressing 24 Group Number setting 24 Cool & Heat selector 24 Static pressure compensation mode 25 Night Low Noise Function 25 Overall defrost mode 25 Setting the ODU address 26 Snow removal & rapid defrost 26 Target pressure adjusting 27 Self-Diagnosis Function
29 CAUTION FOR REFRIGERANT LEAK
29 Introduction 29 Checking procedure of limiting concentration
30 INSTALLATION GUIDE AT THE SEASIDE
!
ENGLISH
4
ENGLISH
INSTALLATION PROCESS
The foundation must be level even
Outdoor unit foundation work
Avoid short circuits and ensure sufficient space is allowed for service
Installation of outdoor unit
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
2
) there
must be no drop in pressure.
Airtight test
Multiple core cable must not be used. (suitable cable should be selected)
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness, cleanness and tightness
Refrigerant piping work
Check model name to make sure the fitting is made correctly
Installation of indoor unit
Take account of gradient of drain piping
Sleeve and insert work
Make connection clearly between outdoor, indoor, remote controller and option.
Preparation of contract drawings
Indicate clearly who will be responsible for switch setting.
Determination of division work
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Vacuum drying
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order
Transfer to customer with explanation
Preheat the crank case with the electrical heater for more than 6 hours.
CAUTION
• The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrants such change.
• The thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)
!
CAUTION
Notes : * We can guarantee the operation only within 130%
Combination. If you want to connect more than 130% combination, please contact us and discuss the requirement like below.
• If the operation of indoor unit is more than 130%, the airflow is operated as low in the all indoor units.
• The number of ( ) means the number of Max. connectable indoor units, when the connected capacity of indoor units is in the table above.
Combination Ratio(50~200%)
Outdoor Number Connection Ratio
Single outdoor units 200%
Double outdoor units 160%
Triple outdoor units 130%
!
OUTDOOR UNITS INFORMATION
Power Supply : 220-240 V3~ 50Hz / 220 V3~ 60Hz Model Name : ARUN***BTE4
Number of outdoor units 1 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit Dimensions mm Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
8 10 12 ARUN080BTE4 ARUN100BTE4 ARUN120BTE4 ARUN080BTE4 ARUN100BTE4 ARUN120BTE4
(920×1,680×760)×1 (920×1,680×760)×1 (920×1,680×760)×1
202 × 1 208 × 1 208 × 1
7.5 7.5 7.5
9.52 (3/8) 9.52 (3/8) 12.7 (1/2)
19.05 (3/4) 22.2 (7/8) 28.58 (1 1/8) 13(20) 16(25) 20(30)
Number of outdoor units 1 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit Dimensions mm Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
14 16 18 20 ARUN140BTE4 ARUN160BTE4 ARUN180BTE4 ARUN200BTE4 ARUN140BTE4 ARUN160BTE4 ARUN180BTE4 ARUN200BTE4
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1
245 × 1 245 × 1 280 × 1 280 × 1
10.5 10.5 10.5 10.5
12.7 (1/2) 12.7 (1/2) 15.88 (5/8) 15.88 (5/8)
28.58 (1 1/8) 28.58 (1 1/8) 28.58 (1 1/8) 28.58 (1 1/8) 23(35) 26(40) 29(45) 32(50)
Number of outdoor units 2 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
22 24 26 28 ARUN220BTE4 ARUN240BTE4 ARUN260BTE4 ARUN280BTE4 ARUN120BTE4 ARUN120BTE4 ARUN140BTE4 ARUN160BTE4 ARUN100BTE4 ARUN120BTE4 ARUN120BTE4 ARUN120BTE4 (920×1,680×760)×2 (920×1,680×760)×2 (1,240×1,680×760)×1 (1,240×1,680×760)×1
+ (920×1,680×760)×1 + (920×1,680×760)×1
208 × 2 208 × 2 245 × 1 + 208 × 1 245 × 1 + 208 × 1
7.5 × 2 7.5 × 2 10.5 + 7.5 10.5 + 7.5
15.88 (5/8) 15.88 (5/8) 19.05 (3/4) 19.05 (3/4)
28.58 (1 1/8) 34.9 (1 3/8) 34.9 (1 3/8) 34.9 (1 3/8) 35(44) 39(48) 42(52) 45(56)
Number of outdoor units 2 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
30 32 34 36 ARUN300BTE4 ARUN320BTE4 ARUN340BTE4 ARUN360BTE4 ARUN180BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN120BTE4 ARUN120BTE4 ARUN140BTE4 ARUN160BTE4
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×2 (1,240×1,680×760)×2 + (920×1,680×760)×1 + (920×1,680×760)×1 280 × 1 + 208 × 1 280 × 1 + 208 × 1 280 × 1 + 245 × 1 280 × 1 + 245 × 1
10.5 + 7.5 10.5 + 7.5 10.5 × 2 10.5 × 2
19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
34.9 (1 3/8) 34.9 (1 3/8) 34.9 (1 3/8) 41.3 (1 5/8) 49(60) 52(64) 55(64) 58(64)
Number of outdoor units 2 Outdoor Unit 3 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg
Refrigerant Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
38 40 42 44 ARUN380BTE4 ARUN400BTE4 ARUN420BTE4 ARUN440BTE4 ARUN200BTE4 ARUN200BTE4 ARUN180BTE4 ARUN200BTE4 ARUN180BTE4 ARUN200BTE4 ARUN140BTE4 ARUN140BTE4
ARUN100BTE4 ARUN100BTE4
(1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×2
+ (920×1,680×760)×1 + (920×1,680×760)×1
280 × 2 280 × 2 280 × 1 + 245 × 1 280 × 1 + 245 × 1
+ 208 × 1 + 208 × 1
10.5 × 2 10.5 × 2 (10.5 × 2) + 7.5 (10.5 × 2) + 7.5
19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.3 (1 5/8) 41.3 (1 5/8) 41.3 (1 5/8) 41.3 (1 5/8) 61(64) 64 64 64
5
ENGLISH
Model Name : ARUV***BTS4
Number of outdoor units 3 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg
Refrigerant Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
46 48 50 52 ARUN460BTE4 ARUN480BTE4 ARUN500BTE4 ARUN520BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN160BTE4 ARUN180BTE4 ARUN200BTE4 ARUN200BTE4 ARUN100BTE4 ARUN100BTE4 ARUN100BTE4 ARUN120BTE4
(1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×2 + (920×1,680×760)×1 + (920×1,680×760)×1 + (920×1,680×760)×1 + (920×1,680×760)×1
280 × 1 + 245 × 1 280 × 2 + 208 × 1 280 × 2 + 208 × 1 280 × 2 + 208 × 1
+ 208 × 1
(10 × 2) + 7.5 (10 × 2) + 7.5 (10 × 2) + 7.5 (10 × 2) + 7.5
19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.3 (1 5/8) 41.3 (1 5/8) 41.3 (1 5/8) 41.3 (1 5/8) 64 64 64 64
Number of outdoor units 3 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
54 56 5860
ARUN540BTE4 ARUN560BTE4 ARUN580BTE4 ARUN600BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4 ARUN140BTE4 ARUN160BTE4 ARUN180BTE4 ARUN
200BTE4 (1,240×1,680×760)×3 (1,240×1,680×760)×3 (1,240×1,680×760)×3 (1,240×1,680×760)×3 280 × 2 + 245 × 1 280 × 2 + 245 × 1 280 × 3 280 × 3
10 x 3 10 x 3 10 x 3 10 x 3
19.05 (3/4) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.3 (1 5/8) 41.3 (1 5/8) 41.3 (1 5/8) 41.3 (1 5/8) 64 64 64 64
Number of outdoor units 1 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit Dimensions mm Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
16 18 20 ARUV160BTS4 ARUV180BTS4 ARUV200BTS4 ARUV160BTS4 ARUV180BTS4 ARUV200BTS4
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1
225 × 1 260 × 1 260 × 1
6 6.5 6.5
12.7(1/2) 15.88(5/8) 15.88(5/8)
28.58(1 1/8) 28.58(1 1/8) 28.58(1 1/8) 26(40) 29(45) 32(50)
Number of outdoor units 1 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit Dimensions mm Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
8 10 12 14 ARUV080BTS4 ARUV100BTS4 ARUV120BTS4 ARUV140BTS4 ARUV080BTS4 ARUV100BTS4 ARUV120BTS4 ARUV140BTS4
(920×1,680×760)×1 (920×1,680×760)×1 (920×1,680×760)×1 (920×1,680×760)×1
180 × 1 180 × 1 190 × 1 190 × 1
55 5 5
9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2)
22.2(7/8) 22.2(7/8) 28.58(1 1/8) 28.58(1 1/8) 16(25) 16(25) 20(30) 23(35)
Number of outdoor units 2 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
22 24 26 28 ARUV220BTS4 ARUV240BTS4 ARUV260BTS4 ARUV280BTS4 ARUV120BTS4 ARUV120BTS4 ARUV140BTS4 ARUV160BTS4 ARUV100BTS4 ARUV120BTS4 ARUV120BTS4 ARUV120BTS4 (920×1,680×760)×2 (920×1,680×760)×2 (920×1,680×760)×2 (1,240×1,680×760)×1
+ (920×1,680×760)×1
180 × 1 + 190 × 1 190 × 2 190 × 2 225 × 1 + 190 × 1
5 × 2 5 × 2 5 × 2 6 + 5
15.88(5/8) 15.88(5/8) 19.05(3/4) 19.05(3/4)
28.58(1 1/8) 34.9(1 3/8) 34.9(1 3/8) 34.9(1 3/8) 35(44) 39(48) 42(52) 45(56)
Number of outdoor units 2 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
30 32 34 36 ARUV300BTS4 ARUV320BTS4 ARUV340BTS4 ARUV360BTS4 ARUV180BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV120BTS4 ARUV120BTS4 ARUV140BTS4 ARUV160BTS4
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×2 + (920×1,680×760)×1 + (920×1,680×760)×1 + (920×1,680×760)×1 260 × 1 + 190 × 1 260 × 1 + 190 × 1 260 × 1 + 190 × 1 260 × 1 + 225 × 1
6.5 + 5 6.5 + 5 6.5 + 5 6.5 + 6
19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
34.9(1 3/8) 34.9(1 3/8) 34.9(1 3/8) 41.3(1 5/8) 49(60) 52(64) 55(64) 58(64)
Number of outdoor units 2 Outdoor Unit 3 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg
Refrigerant Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
38 40 42 44 ARUV380BTS4 ARUV400BTS4 ARUV420BTS4 ARUV440BTS4 ARUV200BTS4 ARUV200BTS4 ARUV180BTS4 ARUV200BTS4 ARUV180BTS4 ARUV200BTS4 ARUV140BTS4 ARUV140BTS4
ARUV100BTS4 ARUV100BTS4
(1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×1 (1,240×1,680×760)×1
+ (920×1,680×760)×2 + (920×1,680×760)×2
260 × 2 260 × 2 260 × 1 + 190 × 1 260 × 1 + 190 × 1
+ 180 × 1 + 180 × 1
6.5 × 2 6.5 × 2 6.5 + ( 5 × 2) 6.5 + ( 5 × 2)
19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
41.3(1 5/8) 41.3(1 5/8) 41.3(1 5/8) 41.3(1 5/8) 61(64) 64 64 64
Number of outdoor units 3 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg
Refrigerant Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
46 48 50 52 ARUV460BTS4 ARUV480BTS4 ARUV500BTS4 ARUV520BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV160BTS4 ARUV180BTS4 ARUV200BTS4 ARUV200BTS4 ARUV100BTS4 ARUV100BTS4 ARUV100BTS4 ARUV120BTS4
(1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×2 + (920×1,680×760)×1 + (920×1,680×760)×1 + (920×1,680×760)×1 + (920×1,680×760)×1 260 × 1 + 225 × 1 260 × 2 + 180 × 1 260 × 2 + 180 × 1 260 × 2 + 190 × 1
+ 180 × 1
6.5 + 6 + 5 (6.5 × 2) + 5 (6.5 × 2) + 5 (6.5 × 2) + 5
19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
41.3(1 5/8) 41.3(1 5/8) 41.3(1 5/8) 41.3(1 5/8) 64 64 64 64
Number of outdoor units 3 Outdoor Unit Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions mm
Net Weight kg Refrigerant
Precharged amount
kg
Pipe Connctions
Liquid mm (inch)
Gas mm (inch)
Number of maxmum connectable indoor units
54 56 5860
ARUV540BTS4 ARUV560BTS4 ARUV580BTS4 ARUV600BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV200BTS4 ARUV140BTS4 ARUV160BTS4 ARUV180BTS4 ARUV
200BTS4 (1,240×1,680×760)×2 (1,240×1,680×760)×3 (1,240×1,680×760)×3 (1,240×1,680×760)×3 + (920×1,680×760)×1 260 × 2 + 190 × 1 260 × 2 + 225 × 1 260 × 3 260 × 3
(6.5 × 2) + 5 (6.5 × 2) + 6 6.5 × 3 6.5 × 3
19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
41.3(1 5/8) 41.3(1 5/8) 41.3(1 5/8) 41.3(1 5/8) 64 64 64 64
INSTALLATION SPACE
Individual Installation
During the installation of the unit, consider service, inlet, and outlet acquire the minimum space as shown in the figures below.
Category
Installation Space
Case 1
(10mmSide Space49mm)
Case 2
(Side Space49mm)
4 sides
are
walls
A10 B300 C10 D500
A50 B100 C50 D500
A10 B300 C10 D500 E20
A50 B100 C50 D500 E100
A10 B300 C10 D500 E20 F600
A50 B100 C50 D500 E100 F500
A10 B300 C10 D300 E20 F500
A50 B100 C50 D100 E100 F500
A10 B500 C10 D500 E20 F900
A50 B500 C50 D500 E100 F600
Only 2
sides
are
walls
A10 B300
A200 B300 E400
Limita-
tions on
the
height
of the
wall
(Refer
to 4 side
walls)
A
C
B
D
A E
B
D
A
C
B
D
E
C
AE
B
D
A
C
B
D
E
C
A E
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A E
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A E
B
F
C
D
AE
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
B
AE
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
h2
h1
1500
A
B
500
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
240 or more
50 or more
45° or
more
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet side must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than the limit, there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1.
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1500
- h2 = B(Actual height) - 500
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
6
ENGLISH
ALTERNATIVE REFRIGERANT R410A
The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also consid­ered during the installation. R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0.
SELECT THE BEST LOCATION
Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors by noise from unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sul­fur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to pre­vent any person or animal from accessing the outdoor unit.
• If installation site is area of heavy snowfall, then the following direc­tions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of
sunshine in case of installing the product at a place With a high hu­midity in winter (near beach, coast, lake, etc.) (Ex : Rooftop where there is always sunshine.)
CAUTION
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
!
7
ENGLISH
• Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always remove snow for operation.
- The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the product. (If width of the frame is wider than that of the product, snow may accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
CAUTION
Be very careful while carrying the product.
Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
• Do not touch heat exchanger fins with your bare hands. Other­wise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate chil­dren to death.
• When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall.
• Use 2 belts of at least 8 m long.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
Hoist the unit making sure it is being lifted at its center of gravity.
• When carrying the suspended, unit pass the ropes under the unit and use the two suspension points each at the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
!
LIFTING METHOD
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm under the Unit’s legs before being fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
At least 100mm
At least 100m
m
At least 100mm
At least 100mm
At least 100mm
At least 100mm
Center of the Unit
For outdoor units should not be supported only by the corner supports.
Center of the Unit
Chassis A(mm) B(mm)
UX2 920 792 UX3 1240 1102
INSTALLATION
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation sta­tus. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200mm).
At least 200mm
Locking points for
transportation ropes
Forklift Carrying Hole
Forklift Carrying Guide
Unit : mm
6565
At least 65At least 65
730
760
Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you re­move burrs in order to avoid to let burrs drop in the tubing.
Flaring work
- Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the flared section and do flar­ing work again.
Indoor unit [kW(Btu/h]
Pipe " A "
Gas Liquid Gas Liquid
<5.6(19,100) 1/2" 1/4" 0.5~0.8 0~0.5 <16.0(54,600) 5/8" 3/8" 0.8~1.0 0.5~0.8 <22.4(76,400) 3/4" 3/8" 1.0~1.3 0.5~0.8
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Flare shape and flare nut tightening torque
Precautions when connecting pipes
- See the following table for flare part machining dimensions.
- When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first. (Use ester oil or ether oil.)
-
See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
- After all the piping has been connected, use nitrogen to perform a gas leak check.
Pipe size
Tightening
torque(N·m)
A(mm) Flare shape
Ø9.52 38±4 12.8-13.2
Ø12.7 55±6 16.2-16.6
Ø15.88 75±7 19.3-19.7
CAUTION
• Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks are present
.
• When loosening a flare nut, always use two wrenches in combination, When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare(inner and outer faces) with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as the initial tightening.
Union
!
8
ENGLISH
Unit : mm
200
75
75
200
100
The corner part must be fixed firmly. Otherwise, the support for the
installation may be bent.
Get and use M10 Anchor bolt.Put Cushion Pad between the outdoor unit and ground support for
the vibration protection in wide area.
Space for pipes and wiring (Pipes and wirings for bottom side)H-beam supportConcrete support
CAUTION
• Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit Base Pan before fixing the bolt. It may cause the unstable state of the outdoor settlement, and may cause freezing of the heat exchanger resulting in abnormal operations.
• Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit before welding. Not removing Pal­let(Wood Support) causes hazard of fire during welding.
WARNING
• Install where it can sufficiently support the weight of the out­door unit. If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake. If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment of the water flowing out of the outdoor unit in operation), and the passages of the pipe and wiring, when making the ground support.
• Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet. The tube or pipe may freeze and the water may not be drained.
Pallet(Wood Support)
- Remove before Installation
!
!
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
- Use the accessory piping kit or the pipes purchased locally.
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5m longer than the pipe length.
Pipe
Reamer
Point down
Copper
tube
90
Slanted Uneven Rough
Preparation of Piping
2
90
45
2
A
R=0.4~0.8
9
ENGLISH
Opening shutoff valve
1 Remove the cap and turn the valve counter clockwise with the
hexagon wrench.
2 Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3 Make sure to tighten the cap securely.
Insulation of shutoff valve
1 Use the heat insulation material for the refrigerant piping which has
an excellent heat-resistance (over 120°C).
2 Precautions in high humidity circumstance:
This air conditioner has been tested according to the "ISO Condi­tions with Mist" and confirmed that there is not any default. How­ever, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according to the fol­lowing procedure:
- Heat insulation material to be prepared... EPDM (Ethylene Propy­lene Diene Methylene)-over 120°C the heat-resistance tempera­ture.
- Add the insulation over 10mm thickness at high humidity environ-
ment.
Closing shutoff valve
1 Remove the cap and turn the valve clockwise with the hexagon
wrench.
2 Securely tighten the valve until the shaft contacts the main body seal.
3 Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
Shutoff
valve
size
Tightening torque N·m(Turn clockwise to close)
Shaft
(valve body)
Cap
(Valve lid)
Service
port
Flare
nut
Gas line piping
attached to unit
Closed Opened
Hexagonal
wrench
Ø6.35
6.0±0.6
5.0±0.0
4mm
17.6±2.0
12.7±2
16±2
-
Ø9.52 38±4
Ø12.7 10.0±1.0 20.0±2.0 55±6
Ø15.88 12.0±1.2
5mm
25.0±2.5
75±7
Ø19.05 14.0±1.4 110±10
Ø22.2
30.0±3.0 8mm -
Ø25.4 25±3
Plumbing materials and storage methods
Pipe must be able to obtain the specified thickness and should be used with low impurities. Also when handling storage, pipe must be careful to prevent a frac­ture, deformity and wound. Should not be mixed with contaminations such as dust, moisture.
Refrigerant piping on three principles
Drying Cleanliness Airtight
Should be no moisture
inside
No dust inside.
There is no refrigerant
leakage
Items
Moisture
Dust
Leakage
Cause
failure
- Significant hydroly­sis of refrigerant oil
- Degradation of re­frigerant oil
- Poor insula’tion of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Degradation of re­frigerant oil
- Poor insulation of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Gas shortages
- Degradation of re­frigerant oil
- Poor insulation of the compressor
- Do not cold and warm
Coun-
termea-
sure
-
No moisture in the pipe
- Until the connec­tion is completed, the plumbing pipe entrance should be strictly controlled.
- Stop plumbing at rainy day.
- Pipe entrance should be taken side or bottom.
-
When removal burr after cutting pipe, pipe entrance should be taken down.
- Pipe entrance should be fitted cap when pass through the walls.
- No dust in the pipe.
- Until the connec­tion is completed, the plumbing pipe entrance should be strictly controlled.
- Pipe entrance should be taken side or bottom.
- When removal burr after cutting pipe, pipe entrance should be taken down.
- Pipe entrance should be fitted cap when pass through the walls.
- Airtightness test should be.
- Brazing operations to comply with standards.
- Flare to comply with standards.
- Flange connections to comply with standards.
Nitrogen substitution method
Welding, as when heating without nitrogen substitution a large amount of the oxide film is formed on the internal piping.
The oxide film is a caused by clogging EEV, Capillary, oil hole of accu­mulator and suction hole of oil pump in compressor.
It prevents normal operation of the compressor. In order to avoid this problem, Welding should be done after replacing
air by nitrogen gas. When welding plumbing pipe, the work is required.
Regulator
Nitrogen gas Pressure 0.02MPa less
Auxiliary valve
Taping (Should not contain air)
Welding Point
Note) should not block the outlet side. When the internal pressure in pipe is abo ve the atmospheric pressure, pinhole is o ccurred and it is a leakage cause.
Oxide scale
Nitrogen
Indoor unit
Fastening band (accessory)
Refrigerant piping
Thermal insulator (accessory)
- Pipe connections can be done on the front side or on the side accord­ing to the installation environments.
- Be sure to let 0.2kgf/cm
2
Nitrogen flow in the pipe when welding.
- If Nitrogen was not flown during welding, many oxidized membranes may form inside the pipe and disturb the normal operations of valves and condensers.
Nitrogen Direction
Preparation Work
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or Bottom pipe drawing outs.
CAUTION
• Do not give damage to the pipe/base during the Knock Out work.
• Proceed to pipe work after removing burr after Knock Out work.
• Perform sleeve work to prevent damage to the wire when con­necting wires using knock Outs.
!
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Remove leakage prevention cap
• Remove the leakage prevention cap attached to the outdoor unit service valve before pipe work.
• Proceed the leakage prevention cap removal as follows:
- Verify whether the liquid/gas pipes are locked.
- Extract remaining refrigerant or air inside using the service port.
- Remove the leakage prevention cap
10
ENGLISH
1 Always use the nitrogen.(not use oxygen, carbon dioxide, and
a Chevron gas): Please use the following nitrogen pressure
0.02MPa Oxygen – Promotes oxidative degradation of refrig­erant oil. Because it is flammable, it is strictly prohibited to use Carbon dioxide – Degrade the drying characteristics of gas Chevron Gas – Toxic gas occurs when exposed to direct
flame. 2 Always use a pressure reducing valve. 3 Please do not use commercially available antioxidant.
The residual material seems to be the oxide scale is ob-
served. In fact, due to the organic acids generated by oxida-
tion of the alcohol contained in the anti-oxidants, ants nest
corrosion occurs. (causes of organic acid
alcohol + copper
+ water + temperature)
CAUTION
!
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the branching pipes, and the refrigerant pipe coming out of the outdoor unit is divided at the end to connect to each indoor unit. Flare connec­tion for the indoor unit, and welding connection for the outdoor pipe and the branching parts.
- Use hexagonal wrench to open/close the valve.
CAUTION
• Please block the pipe knock outs of the front and side panels
after installing the pipes. (Animals or foreign objects may be brought in to damage wires.)
• ARUV***BTS4 models do not have Refrigerant charging port.
!
WARNING
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body
if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas leak-
age after the work.
!
REFRIGERANT PIPING INSTALLATION
Left Side
Pipe Draw
Out
Right Side Pipe Draw Out
Front Pipe Draw Out
Refrigerant Pipe
Nitrogen
Nitrogen Direction
Direction
Taping
Regulator
Valve
Nitrogen
Service Port
Liquid pipe
Gas pipe
Refrigerant
Charging Port
Removal Area for Liquid/Gas pipe bottom side connections.
Service Port
Liquid pipe
Gas pipe
Leakage Prevention Cap
Refrigerant Charging Port
11
ENGLISH
Pipe Drawing Out during Single / Series connection
Method of drawing out pipes on the front side
- Proceed with the pipe work as shown in the below figure for front side pipe drawing out.
Method of drawing out pipes on the bottom side
- Drawing out common pipe through side panel
Liquid pipe Gas pipe
Remove only liquid/gas pipe Knock out
Y branch method
Combination of Y branch/header Method
Header Method
: Outdoor Unit: 1st branch (Y branch) : Indoor Units
: Outdoor Unit: 1st branch (Y branch) : Y branch: Indoor Unit: Header: Sealed piping
: Outdoor Unit: 1st branch: Indoor Units: Sealed piping
: Outdoor Unit: 1st branch (Y branch) : Indoor Units: Downward Indoor Unit: Connection branch
pipe between Outdoor units: ARCNN31
: Connection branch
pipe between Outdoor units: ARCNN21
l 40m (90 m : Conditional application)*
h 40m
H 110m
L150m (200 m : Conditional application)*
Indoor Unit
l 40m
h 40m
H 110m
L200m
Refrigerant piping system
1 Outdoor Units
Y branch method
Combination of Y branch/ header Method
: Outdoor Unit: 1st branch(Y branch): Y branch: Indoor Unit: Connection branch pipe
between Outdoor units: ARCNN31
: Connection branch pipe
between Outdoor units: ARCNN21
: Header: Sealing
Series Outdoor Units (2 Units ~ 3 Units)
h * : See Table 4
h * : See Table 4
h * : See Table 4
Pipe Knock
Out for
Liquid/Gas pipes
H 110m
L150m (200 m : Conditional application)*
l 40m (90 m : Conditional application)*
h 40m
Slave2
Slave1
10m or
less
h1
H 110m
h 40m
Slave2
10m or
less
Slave1
G
F
H 110m
Master
ODU Capacity
Master ≥ Slave1 ≥ Slave 2
L150m (200 m : Conditional application)
l 40m (90 m : Conditional application)
ODU Capacity Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
A
Master
B
D
Slave2
CC
L150m (200 m : Conditional application)*
l 40m (90 m : Conditional application)*
C
Slave1
A
Master
H
I
C
h 40m
C
(Table 2) Refrigerant pipe diameter from outdoor unit to first branch. (A)
(Table 3) Refrigerant pipe diameter from first branch to last branch (B,C,D)
Upward
Outdoor unit
total capacity
Standard Pipe
Diameter
Increased Pipe Diameter
When equivalent pipe length is 90m
or more from ODU to farthest IDU
When level difference is
50m or more
HP
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
8
Ø 9.52(3/8) Ø 19.05(3/4) Ø 12.7(1/2) Ø 22.2(7/8) Ø 12.7(1/2) not increased
10
Ø 9.52(3/8) Ø 22.2(7/8) Ø 12.7(1/2) Ø 25.4(1) Ø 12.7(1/2) not increased
12 ~ 14
Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) not increased Ø 15.88(5/8) not increased
16
Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) Ø 31.8(1-1/4) Ø 15.88(5/8) not increased
18 ~ 22
Ø 15.88(5/8) Ø 28.58(1-1/8) Ø 19.05(3/4) Ø 31.8(1-1/4) Ø 19.05(3/4) not increased
24
Ø 15.88(5/8) Ø 34.9(1-3/8) Ø 19.05(3/4) not increased Ø 19.05(3/4) not increased
26 ~ 34
Ø 19.05(3/4) Ø 34.9(1-3/8) Ø 22.2(7/8) Ø 38.1(1-1/2) Ø 22.2(7/8) not increased
36 ~ 60
Ø 19.05(3/4) Ø 41.3(1-5/8) Ø 22.2(7/8) not increased Ø 22.2(7/8) not increased
Downward indoor unit
total capacity [kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0 (54,600) Ø9.52(3/8) Ø15.88(5/8)
22.4 (76,400)
Ø9.52(3/8) Ø19.05(3/4) < 33.6 (114,700) Ø9.52(3/8) Ø22.2(7/8) < 50.4 (172,000) Ø12.7(1/2) Ø28.58(1-1/8) < 67.2 (229,400) Ø15.88(5/8) Ø28.58(1-1/8)
< 72.8(248,500) Ø15.88(5/8) Ø34.9(1-3/8) < 100.8(344,000) Ø19.05(3/4) Ø34.9(1-3/8) < 173.6(592,500) Ø19.05(3/4) Ø41.3(1-5/8)
(Table 4) Conditional Application
WARNING
In case of pipe diameter B connected after first branch is bigger than the main pipe diameter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio 120% is connected to
24HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(Gas pipe), Ø15.88(liquid pipe)
2)
Pipe diameter B after first branch according to 120% indoor unit ombination(80.6kW) : Ø34.9(gas pipe), Ø19.05(liquid pipe)
Therefore, pipe diameter B connected after first branch would be Ø34.9(gas pipe) / Ø15.88(liquid pipe) which is same with main pipe diameter.
!
Condition Example
1
Diameter of pipes be­tween first branch and the last branch should be in­creased by one step, ex­cept pipe diameter B,C,D is same as Diameter A
40 m‹B+C+D+e≤90 m
B, C, D Change a
diameter
2
While calculating whole re­frigerant pipe length, pipe B,C,D length should be cal­culated twice.
A+Bx2+Cx2+Dx2
+a+b+c+d+e
1 000 m
3
Length of pipe from each indoor unit to the closest branch
a,b,c,d,e≤40 m
4
Length of pipe from out­door unit to the farthest indoor unit 5 (A+B+C+D+e)] - [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] ≤40 m
(A+B+C+D+e)-
(A+a) 40 m
• To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
Ø6.35’Ø9.52, Ø9.52’Ø12.7, Ø12.7’Ø15.88, Ø15.88’Ø19.05, Ø19.05
Ø22.2, Ø22.2’Ø25.4,
Ø25.4
Ø28.58, Ø28.58’Ø31.8,
Ø31.8
Ø34.9, Ø34.9’Ø38.1
l
h 40m
H 110m
L
Indoor Unit
12
ENGLISH
Pipe Connection Method between outdoor unit/indoor unit
Header Method
: Outdoor Unit: Header branch: Indoor Units: Sealing: Connection branch pipe
between Outdoor units: ARCNN31
: Connection branch pipe
between Outdoor units: ARCNN21
h See Table 2 A : Refrigerant pipe diameter from outdoor unit to first branch E : Refrigerant pipe diameter for outdoor unit capacity
(Slave 1+ Slave 2)
F : Refrigerant pipe diameter for outdoor unit capacity
(Slave 2)
h * : See Table 4
Level Difference
(Outdoor unit Outdoor unit)
5m
Max length from first branch to
each outdoor unit (L1, L2, L3)
Less than 10m
(equivalent length of piping 13m)
WARNING
Increased Pipe Diameter(table 2)
- When pipe length is 90m or more from ODU to 1st branch
- When level difference is 50m or more
!
Y branch
Method
Combination of Y
branch/header
Method
Header
Method
Max pipe
length
Outdoor Unit
Indoor Unit
Longest
pipe
length(L)
A+B+C+D+e≤150 m
(200 m: Conditional
application)*
A+B+b≤150 m A+C+e≤150 m
(200 m: Conditional
application)*
A+f≤200 m
Equivalent
pipe length
175 m
(225 m: Conditional
application)*
175 m
(225 m: Conditional
application)*
225 m
Total pipe
length
1,000 m 1,000 m
1,000 m
Max
difference
in height
Outdoor Unit
Indoor Unit
Difference in
height(H)
110 m 110 m
110 m
Indoor Unit
Indoor Unit
Difference in
height(h)
40 m 40 m
40 m
Longest pipe
length after
1st branch
Pipe
length(l)
40 m
(90 m: Conditional
application)*
40 m
(90 m: Conditional ap-
plication)*
40 m
(Table 1) Limit Pipe length
Master
L2
L3
Indoor
Unit
h 40m
- .
1st branch
l 40m
Slave2
Slave1
H 110m
Slave1
Master
B
C
C
h 40m
H1
L1
10m or
less
Refrigerant pipe diameter from outdoor unit to first branch
C
Slave2
ODU Capacity Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
Slave2
Slave1
Master
L200m
l 40m
D
C
C
C
13
ENGLISH
WARNING
Pipe length after header branching (a~f) It is recommended that difference in length of the pipes con-
nected to the Indoor Units is minimized. Performance difference between Indoor Units may occur.
!
Outdoor unit Connection
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2) < 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8) < 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4) < 28.0(95,900) Ø9.52(3/8) Ø22.2(7/8)
WARNING
• In case of pipe diameter B connected after first branch is bigger than the main pipe diameter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio 120% is connected to
24HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(Gas pipe), Ø15.88(liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor unit combination(80.6kW) : Ø34.9(gas pipe), Ø19.05(liquid pipe)
Therefore, pipe diameter B connected after first branch would be Ø34.9(gas pipe) / Ø15.88(liquid pipe) which is same with main pipe diameter.
[Example] Do not choose the main pipe diameter by downward indoor unit total capacity but its outdoor unit model name. Do not let the connection pipe from branch to branch exceed the main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 22 HP (61.6 kW)
outdoor unit to 130% of its system capacity (80.1 kW) and branching 7k (2.2kW) indoor unit at the 1st branch.
1) Main pipe diameter(22 HP outdoor unit): Ø28.58(gas pipe), Ø15.88(Liquid pipe)
2) Pipe diameter between 1st and 2nd branch (77.9kW indoor units) : Ø34.9(Gas pipe), Ø19.05(Liquid pipe) in conformity with downward indoor units.
Since the main pipe diameter of 22HP outdoor unit is Ø28.58(gas pipe), Ø15.88(Liquid pipe) is used as the main pipe and the connection pipe between 1st and 2nd branch.
!
CAUTION
• Bending radius should be at least twice the diameter of the pipe.
• Bend pipe after 500 mm or more from branch(or header). Do not bend U type. It may cause Performance unsatisfactory or noise.
• If want U type, bending R is more than 200 mm.
!
Pipe Connection Method/Precautions for Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between outdoor units.
- Please refer to the below connection examples to install pipe connec­tions between outdoor units.
- If the distance between the outdoor units becomes more than 2m, apply Oil Traps between the gas pipes.
- If the outdoor unit is located lower than the main pipe, apply Oil Trap.
Pipe connection between outdoor units (General Case)
The maximum pipe length after the first branching between the outdoor units is 10m or less
Pipes between outdoorunits are2mor less
Examples of Wrong Pipe Connections
2m or less
Pipes between outdoorunits are2mor longer
Oil Trap
Oil Trap Oil Trap
2m or less
2m or less
2m or less
0.2m or more
2m or longer
2m or longer2m or longer
500mm or more
500mm or more
If the main pipe is higher than the outdoor units, oil is accumulated in the outdoor unit.
If there are differences in the height between the outdoor units, oil is accumulated in the lower outdoor unit.
Oil Trap
h
h
0.2m
Toward indoor unit
Toward indoor unit
Oil Trap
(Example 3)
The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correction Factor) value of indoor unit.
Total liquid pipe : Ø25.4 mm
Additional charge(kg)
Total liquid pipe : Ø22.2 mm
Total liquid pipe : Ø19.05 mm
Total liquid pipe : Ø15.88 mm
Total liquid pipe : Ø12.7 mm
Total liquid pipe : Ø9.52 mm
Total liquid pipe : Ø6.35 mm
CF value of indoor unit
=
+
+
+
+
+
+
x 0.480(kg/m)
x 0.354(kg/m)
x 0.266(kg/m)
x 0.173(kg/m)
x 0.118(kg/m)
x 0.061(kg/m)
x 0.022(kg/m)
Amount refrigerant of Indoor units Example) 4Way Ceiling Cassette 14.5kW -1ea, Ceiling concealed
Duct 7.3kW-2ea, Wall Mounted 2.3kW-4ea CF = 0.64 × 1 + 0.26 × 2 + 0.24 × 4 = 2.12 kg
Attach the additional refrigerant table of IDU.
CAUTION
Use only 2-series of indoor unit. Ex) ARNU***2 Do not connect Hydrokit with Multi V IV Models.
!
14
ENGLISH
Toward indoor unit
Toward indoor unit
Pipe inclination (2° or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
- Apply Oil Trap as shown below when the length of the pipe between the outdoor units is more than 2m. Otherwise, the unit may not oper­ate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
2m
2m
2m
0.2m Oil Trap
(Example 2)
- When connecting the pipes between the outdoor units, the accumu­lation of oil in the slave outdoor unit should be avoided. Otherwise, the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
h
Toward indoor unit
(Example 2)
15
ENGLISH
WARNING
• Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
If the above equation can not be satisfied, then follow the follow­ing steps.
• Selection of air conditioning system: select one of the next
- Installation of effective opening part
- Reconfirmation of Outdoor Unit capacity and piping length
- Reduction of the amount of refrigerant
- Installation of 2 or more security device (alarm for gas leakage)
• Change Indoor Unit type
:
installation position should be over 2m from the floor (Wall
mounted type Cassette type)
• Adoption of ventilation system
: choose ordinary ventilation system or building ventilation sys­tem
• Limitation in piping work
: Prepare for earthquake and thermal stress
Gas pipe
Liquid pipe
Manifold GaugeLow pressure side HandleHigh pressure side Handle
!
WARNING
• Pipe to be vacuumed : gas pipe, liquid pipe
• If the refrigerant amount is not exact, it may not operate
properly.
• If additionally bottled refrigerant amount is over 10%, condenser
burst or insufficient indoor unit performance may be caused.
!
Refrigerant charging
Volume of the room at which Indoor Unit of
the least capacity is installed
Total amount of refrigerant in the system
0.44 (kg / m3)
- Ensure that the branch pipes are attached vertically.
Slave
Master
Header
Slave
Master
Slave
Master
Slave
Master
Slave
Master
Slave
Master
1st
1st
1st
Main pipe
Distribution
2nd
2nd
3rd
3rd
Main pipe
Distribution
Slave
Master
1st
3rd
3rd main pipe distribution
2nd
Horizontal Distribution
Vertical Distribution
The others
Distribution Method
• Header should be insulated with the insulator in each kit.
• Joints between branch and pipe should be sealed with the tape in­cluded in each kit.
• Any cap pipe should be insulated using the insulator provided with each kit and then taped as described above.
Y branch pipe
Models Gas pipe Liquid pipe
ARBLN
01621
I.D19.05
O.D15.88
I.D12.7
I.D15.88
I.D12.7
I.D15.88
I.D15.88
I.D12.7
292
281
74
70
I.D12.7
O.D9.52
I.D6.35
I.D9.52
I.D.9.52
I.D.6.35
I.D9.52
I.D.6.35
292
281
74
70
1
1
ARBLN
03321
I.D25.4
413
390
83
I.D15.88
I.D19.05
I.D12.7
I.D12.7I.D19.05I.D15.88I.D19.05I.D22.2
I.D28.58
O.D25.4
I.D22.2
O.D19.05
O.D19.05
I.D22.2
I.D25.4
70 80 11 0
1
2
3
3 1 2
70
I.D9.52
I.D12.7
53.6D.I25.9D.I
I.D9.52
I.D12.7
I.D6.35
I.D12.7
332
321
74
ARBLN
07121
376 404
96
I.D34.9
O.D31.8
I.D22.2
O.D22.2
I.D28.58
I.D31.8
O.D19.05
I.D28.58
120 90 120
I.D31.8
2.22D.I85.82D.I
I.D19.05
I.D15.88
I.D12.7
I.D19.05
I.D15.88
2
3
1
2
1 3
25.9D.I25.9D.I7.21D.O
I.D15.88 I.D19.05
I.D12.7
I.D12.7
I.D19.05
I.D15.88I.D12.7
I.D19.05
O.D12. 7I.D6.35
I.D15.88
371 394
83
11 0 70
2
3
3 2
ARBLN
14521
120 90 120
471 517
125
120 13 0
I.D19.05
I.D15.88
I.D12.7
I.D19.05
I.D22.2
I.D41.3 I.D38.1
I.D41.3
O.D34.9
I.D34.9
I.D34.9
I.D22.2
I.D28.58
I.D28.58I.D38.1
I.D41.3
I.D34.9
I.D38.1
O.D22.2
O.D38.1
O.D15.88
O.D28.58
90
2
3
3
3
2
2
3
416 444
96
O.D15.88 I.D9.52
I.D12.7
O.D12. 7 I.D6.35
I.D9.52
I.D15.88 I.D19.05
I.D22.2
I.D22.2
I.D19.05
I.D15.88
I.D12.7
I.D15.88
I.D19.05
I.D22.2
O.D19.0 5
80
11 0 11 0
2
3
1
2 3 3
ARBLN
23220
O.D.28.58
I.D.22.2
115
X2
100
O.D15.88
I.D12.7
70
O.D.22.2
I.D.15.88I.D.19.05
120
O.D.38.1
I.D.34.9
I.D.28.58 O.D.44.48
X2
175
I.D31.8 I.D.53.98 I.D.25.4
I.D.44.48
I.D.44.48
I.D38.1I.D41.3
I.D.44.48
I.D38.1I.D41.3
I.D.53.98
420 490
134
1
2
3
32
3 3
3
3
2
O.D.19.05 I.D.12.7
I.D.15.88
O.D12.7 I.D6.35
I.D9.52
X2
110 110
I.D25.4 I.D22.2
I.D.19.05
I.D.19.05I.D.22.2
I.D.25.4
I.D.25.4
I.D.22.2
346 379
96
2
3 32
3
[unit:mm]
16
ENGLISH
• When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connec­tion then cap pipes should be fitted to the surplus branches.
• Fit branch pipe lie in a horizontal plane.
Horizontal plane
View from point B in the direction of the arrow
Y branch
Header
A
B
A
B
To Branch Piping or Indoor UnitTo Outdoor Unit
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting sec­tion should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
To Outdoor UnitTo Indoor Unit
• The indoor unit having larger ca­pacity must be installed closer to than smaller one.
• If the diameter of the refrigerant piping selected by the proce­dures described is different from the size of the joint, the connecting section should be cut with a pipe cutter.
Pipe cutter
• When the number of pipes to be connected is smaller than the number of header branches, in­stall a cap to the unconnected branches.
Branch pipe Fitting
Horizontal plane
Within +/- 10°
A
Viewed from point A in direction of arrow
Tape
(field supply)
Facing
downwards
Within ± 3° Within ± 3°
Facing
upwards
Insulate the header using the insulation material attached to the branch pipe kit as shown in the figure.
Tape
Insulator
Insulator of field pipe
Insulator for cap pipe
Insulator
(included with kit)
Liquid and gas pipe joints
Insulator for field piping
C
Cap pipe
Tape
B
Pinched pipe
17
ENGLISH
[unit:mm]
Leak test Leak test should be made by pressurizing nitrogen gas to 3.8
MPa(38.7kgf/cm
2
). If the pressure does not drop for 24 hours, the sys­tem passes the test. If the pressure drops, check where the nitrogen leaks. For the test method, refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid pipe, gas pipe and high/low pressure common pipe)
The test result can be judged good if the pressure has not be reduced after leaving for about one day after completion of nitrogen gas pres­surization.
Indoor unit
Nitrogen gas cylinder
Slave 1 outdoor unit Master outdoor unit
Liquide pipe
Gas pipe
Liquide pipe
Gas pipe
Liquid side
Gas side
Close
Close
Close
Close
Leak Test and Vacuum drying
Header
Models Gas pipe Liquid pipe
4 branch
ARBL054
120
150
360
120
ID15.88
ID12.7
ID12.7
ID15.88
ID15.88
ID19.05
120
120
150
360
ID9.52
ID9.52
ID6.35
ID6.35
ID9.52
ID12.7
7 branch
ARBL057
540
ID15.88
ID19.05
120
150
120
ID15.88
ID12.7
ID15.88
ID12.7
ID15.88
ID19.05
540
ID9.52
ID12.7
120
150
120
ID6.35
ID9.52
ID9.52
ID12.7
4 branch
ARBL104
120
150
400
160
ID15.88
ID12.7
ID19.05
ID15.88
ID22.2
ID28.58ID25.4
120
120
150
360
ID9.52
ID9.52
ID6.35
ID6.35
ID9.52
ID12.7
7 branch
ARBL107
120
150
160
580
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
120
150
700
120
ID6.35
ID9.52
ID9.52
ID6.35
ID9.52ID12.7
10 branch
ARBL1010
120
150
160
760
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
120
150
160
760
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
10 branch
ARBL2010
120
150
182
775
ID19.05
ID15.88
ID15.88
ID12.7
ID28.58
ID31.8 ID34.9
120
150
107
60*9=540
700
ID6.35
ID9.52
ID19.05ID15.88
ID9.52
ID6.35
NOTE
!
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is checked, apply the following correction factor
There is a pressure change of approximately 0.1 kg/cm2(0.01 MPa) for each 1°C of temperature difference.
Correction= (Temp. at the time of pressurization – Temp. at the time
of check) X 0.1 For example: Temperature at the time of pressurization (3.8 MPa) is 27 °C 24 hour later: 3.73 MPa, 20°C In this case the pressure drop of 0.07 is because of tem­perature drop And hence there is no leakage in pipe oc­curred.
CAUTION
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must be at higher position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
!
WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flamma­ble gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
!
Vacuum Vacuum drying should be made from the service port provided on the outdoor
unit’s service valve to the vacuum pump commonly used for liquid pipe, gas pipe and high/low pressure common pipe. (Make Vacuum from liquid pipe, gas pipe and high/low pressure common pipe with the service valve closed.) * Never perform air purging using refrigerant.
• Vacuum drying: Use a vacuum pump that can evacuate to -100.7kPa (5 Torr, -755mmHg).
- Evacuate the system from the liquid and gas pipes with a vacuum
pump for over 2 hrs and bring the system to -100.7kPa. After main­taining system under that condition for over 1 hr, confirm the vacuum gauge rises. The system may contain moisture or leak.
- Following should be executed if there is a possibility of moisture re-
maining inside the pipe. (Rainwater may enter the pipe during work in the rainy season or over a long period of time) After evacuating the system for 2 hrs, give pressure to the system to
0.05MPa(vacuum break) with nitrogen gas and then evacuate it again with the vacuum pump for 1hr to -100.7kPa(vacuum drying). If the system cannot be evacuated to -100.7kPa within 2 hrs, repeat the steps of vacuum break and its drying. Finally, check if the vacuum gauge does not rise or not, after maintaining the system in vacuum for 1 hr.
Slave 1 outdoor unit Master outdoor unit
Vacuum pump
Close
Close
Close
Close
Scale Use a graviometer. (One that can measure down to 0.1kg). If you are unable to prepare such a high-precision gravimeter you may use a charge cylinder.
Liquide pipe
Gas pipe
Liquide pipe
Gas pipe
Liquid side
Gas side
Indoor unit
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant poly­ethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When in­sulation work is insufficient, there is a possibility of condensation drip, etc. Pay special attention to insulation work to ceiling plenum.
Heat insulation materialPipe Outer covering(Wind the connection part and cutting part of heat in-
sulation material with a finishing tape.)
Heat insulation
material
Adhesive + Heat - resistant poly-
ethylene foam + Adhesive tape
Outer
covering
Indoor Vinyl tape
Floor ex-
posed
Water-proof hemp cloth +
Bronze asphalt
Outdoor
Water-proof hemp cloth +
Zinc plate + Oily paint
NOTE
!
When using polyethylene cover as covering material, asphalt roof­ing shall not be required.
Bad example
Thermal insulation of refrigerant piping
• Do not insulate gas or low pressure pipe and liquid or highpres­sure pipe together.
• Be sure to fully insulate connecting portion.
These parts are not insulated.
Liquid pipeGas pipePower lines
Finishing tape
Insulating material
Communication lines
A
C
D
E
B
F
A
Good example
Liquid pipeGas pipePower lines
Insulating material
Communication lines
Communication lines
Separation
Power lines
E
D
D
B
A
C
18
ENGLISH
NOTE
!
Always add an appropriate amount of refrigerant. (For the refrigerant addi­tional charge) Too much or too little refrigerant will cause trouble. To use the Vacuum Mode (If the Vacuum mode is set, all valves of Indoor units and Outdoor units will be opened.)
WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flamma­ble gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
!
WARNING
When installing and moving the air conditioner to another site, recharge after perfect evacuation.
- If a different refrigerant or air is mixed with the original refriger­ant, the refrigerant cycle may malfunction and the unit may be damaged.
!
This function is used for creating vacuum in the system after compres­sor replacement, ODU parts replacement or IDU addition/replacement.
Vacuum mode setting method
Vacuum mode off method
CAUTION
ODU operation stops during vacuum mode. Compressor can't operate.
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“SVC” Push the ‘’ button
Select the Function using ‘’, ‘’ Button : :
“Se3” Push the ‘’ button
Start the vacuum mode : “VACC”
ODU V/V open
ODU EEV open
IDU EEV open
Dip switch off and push the reset button on Master unit PCB
!
Vacuum Mode
DIP SWITCH 7-Segment
SW01C ( : confirm)
SW02C ( : backward
: forward)
SW04C
( X : cancel)
SW01D (reset)
SW03C (
ȭ
ȯ
Ɨ
19
ENGLISH
A
B
E
B
I
A
B
D
C
1m1m
D
F
G
B
G
D
B
H
I
J
A
Penetrations
SleeveHeat insulating materialLaggingCaulking materialBandWaterproofing layerSleeve with edgeLagging materialMortar or other incombustible caulkingIncombustible heat insulation material
When filling a gap with mortar, cover the penetration part with steel plate so that the insulation material will not be caved in. For this part, use incom­bustible materials for both insulation and covering. (Vinyl covering should not be used.)
Inner wall (concealed) Outer wall Outer wall (exposed)
Floor (fireproofing)
Penetrating portion on fire limit and boundary wall
Roof pipe shaft
Caution
- Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guid­ance of each electric power company.
-
Install the Outdoor Unit communication cable away from the power
source wiring so that it is not affected by electric noise from the power source. (Do not run it through the same conduit.)
- Be sure to provide designated grounding work to Outdoor Unit.
- Give some allowance to wiring for electrical part box of Indoor and
Outdoor Units, because the box is sometimes removed at the time of service work.
- Never connect the main power source to terminal block of communi-
cation cable. If connected, electrical parts will be burnt out.
- Use 2-core shield cable for communication cable.(O mark in the figure
below) If communication cable of different systems are wired with the same multiplecore cable, the resultant poor transmitting and re­ceiving will cause erroneous operations. ( mark in the figure below)
- Only the communication cable specified should be connected to the
terminal block for Outdoor Unit communication.
CAUTION
Be sure to correct the outdoor unit to earth. Do not connect ground wire to any gas pipe, liquid pipe, lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
!
WARNING
Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with regulations and this installation manual. If power supply circuit has a lack of capacity or electric work defi­ciency, it may cause an electric shock or fire.
!
ELECTRICAL WIRING
2-Core Shield Cable
Multi-Core Cable
Remote control
Remote control
Remote control
Remote control
Indoor
Unit
Outdoor Unit
Outdoor Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Outdoor Unit
Outdoor Unit
Remote control
Remote control
Indoor
Unit
Indoor
Unit
Remote control
Remote control
Indoor
Unit
Indoor
Unit
Master Slave1 Slave2
Remote controller
Remote controller
Indoor
Unit
Indoor
Unit
Remote controller
Outdoor Unit
Outdoor Unit
Remote controller
Indoor
Unit
Indoor
Unit
Master Slave1 Slave2
Master Slave1 Slave2
Outdoor Unit
Remote controller
Remote controller
Indoor
Unit
Indoor
Unit
Remote controller
Remote controller
Indoor
Unit
Indoor
Unit
Master Slave1 Slave2
Outdoor Unit
2-Core Shield Cable
Multi-Core Cable
UX3
UX2
WARNING
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
!
Communication and Power Cables
Communication cable
- Types : shielding cable
- Cross section : 1.0~1.5mm
2
- Maximum allowable temperature: 60°C
- Maximum allowable cable length: under 1000m
Remote control cable
- Types : 3-core cable
Central control cable
Separation of communication and power cables
- If communication and power cables are run alongside each other then there is a strong likelihood of operational faults developing due to in­terference in the signal wiring caused by electrostatic and electro­magnetic coupling. The tables below indicates our recommendation as to appropriate spacing of communication and power cables where these are to be run side by side
NOTE
!
• The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m the figures will have to be recalculated in direct proportion to the additional length of cable involved.
• If the power supply waveform continues to exhibit some distor­tion the recommended spacing in the table should be increased.
- If the cable are laid inside conduits then the following point must also be taken into account when grouping various cable together for introduction into the conduits
- Power cable(including power supply to air conditioner) and communication cables must not be laid inside the same
- In the same way, when grouping the power wires and com­munication cables should not be bunched together.
Product type Cable type Diameter
ACP&AC Manager 2-core cable (Shielding cable)
1.0~1.5mm
2
AC Smart 2-core cable (Shielding cable)
1.0~1.5mm
2
Simple central controller 4-core cable (Shielding cable)
1.0~1.5mm
2
Current capacity of power cable Spacing
100V or more
10A 300mm 50A 500mm
100A 1000mm
Exceed 100A 1500mm
20
ENGLISH
CAUTION
When the 400 volt power supply is applied to “N” phase by mistake, check damaged parts in control box and replace them.
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Round pressure terminal
Power cable
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
- When connecting cable which is the same thickness, do as shown in the figure below.
- For wiring, use the designated power cable and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may break them.
!
CAUTION
• Use the 2-core shield cables for communication cables. Never use them together with power cables.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never in­stall a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2%. If it is greater the units lifespan will be reduced.
!
Control box and connecting position of wiring
- Remove all of the screws at front panel and remove the panel by pulling it forward.
- Connect communication cable between main and sub outdoor unit through the terminal block.
- Connect communication cables between outdoor unit and indoor units through the terminal block.
- When the central control system is connected to the outdoor unit, a dedicated PCB must be connected between them.
- When connecting communication cable between outdoor unit and in­door units with shielded cable, connect the shield ground to the earth screw.
Main PCB
Front Panel
Noise Filter
External PCB
Take care of the
phase sequence of
3-phase 3-wire
power system
21
ENGLISH
CAUTION
If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the apparatus must be carried out by a qualified person.
!
Wiring of main power supply and equipment capacity
- Use a separate power supply for the Outdoor Unit and Indoor Unit.
- Bear in mind ambient conditions (ambient temperature,direct sun­light, rain water,etc.) when proceeding with the wiring and connec­tions.
- The cable size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
- Specific wiring requirements should adhere to the wiring regulations of the region.
- Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.
- Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
CAUTION
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct ca­pacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.
!
WARNING
• Follow ordinance of your governmental organization for techni­cal standard related to electrical equipment, wiring regulations and guidance of each electric power company.
• Make sure to use specified cables for connections so that no external force is imparted to terminal connections. If connec­tions are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
!
Field Wiring
Single outdoor unit
L
N
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Outdoor Unit]
[Indoor Units]
Power supply
3 Phase 3 Wires
Power supply
1Phase 2Wires
(Main Switch)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
R S T
Switch
ELCB
ELCB
Master Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
34 34 34
[Heat Pump] Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’ terminal for day contact, it is not the point to make ground connection.
WARNING
• Indoor Unit ground wires are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, mo­mentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Run­ning the product in reversed phase may break the compressor and other parts.
!
Series outdoor units
When the power source is connected
In series between the units.
R S T
Switch
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
(Main Switch)
[Slave]
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
R
T
S
Commu
(2 W
mmunication Line
(2Po(2
[
]
L
N
ELCB
ELCB
Power supply
3 Phase 3 Wires
Power supply
1Phase 2Wires
- Outdoor: 220-240 V3~ 50Hz / 220 V3~ 60Hz
- Indoor: 220-240 V~ 50Hz / 220 V~ 60Hz
S
witch
Master
When the power source is supplied to Each outdoor unit individually.
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
(Main Switch)
[Slave]
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
R S T
Switch
R S T
Switch
L
N
ELCB ELCB
ELCB
Power supply
3 Phase 3 Wires
Power supply
1Phase 2Wires
WARNING
When the total capacity is over than as follow, the power source do not use in series between the units.
!
Slave1 Outdoor Unit
Master Outdoor unit
Slave2 Outdoor Unit
34 34 34
Master Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
[Heat Pump] Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’ terminal for dry contact. It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
WARNING
• Indoor Unit ground wires are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, mo­mentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor and other parts.
!
22
ENGLISH
CAUTION
It should be wiring power cables or communication cables to avoid interference with the oil level sensor. Otherwise, That oil level sensor would be operated abnormally.
!
Example) Connection of power and communication cable (UX2)
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm(1.97inch)
gap
Communication
cable
Main power terminal block
Ground wire
Power/ Ground cable
Over 50mm(1.97inch) gap
Communication cable
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm(1.97inch)
gap
Communication cable
Fix firmly not
to be displaced
Main power
terminal block
Insulation sleeves
attachments
ODU-IDU Communication cable ODU-ODU Communication cable
Main power terminal block
Ground wire
Power/Ground cable
Over
50mm(1.97inch) gap
Communication
cable
Left Side Right Side
Front Side 1 Front Side 2
Main Power Connection Communication Connection
Example) Connection of power and communication cable (UX3)
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm(1.97inch)
gap
Communication
cable
Main power terminal block
Ground wire
Power/ Ground cable
Over 50mm(1.97inch) gap
Communication cable
Left Side Right Side
Example) Connection of transmission wire
[BUS type] [STAR type]
- Connection of communication cable must be installed like below figure between indoor unit to outdoor unit.
- Abnormal operation can be caused by communication de­fect, when connection of com­munication cable is installed like below figure(STAR type).
23
ENGLISH
CAUTION
It should be wiring power cables or communication cables to avoid interference with the oil level sensor. Otherwise, That oil level sensor would be operated abnormally.
!
e
wer
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm(1.97inch)
gap Communication cable
Main power
terminal block
Insulation sleeves
attachments
Fix firmly not
to be displaced
ODU-IDU Communication cable ODU-ODU Communication cable
Main power terminal block
Ground wire
Power/Ground cable
Over
50mm(1.97inch) gap
Communication cable
Front Side 1 Front Side 2
Main Power Connection Communication Connection
Checking the setting of outdoor units
Checking according to dip switch setting
- You can check the setting values of the Master outdoor unit from the 7 segment LED. The dip switch setting should be changed when the power is OFF.
Checking the initial display The number is sequentially appeared at the 7 segment in 5 seconds
after applying the power. This number represents the setting condition.
• Initial display order
• Example) ARUN360BTE4
• Master Unit • Slave Unit
Order No Mean
8~20 Master model capacity (HP)
8~20 Slave 1 model capacity (HP)
8~20 Slave 2 model capacity (HP)
8~60 Total capacity (HP)
1 Cooling Only
2 Heat Pump
3 Heat Recovery
38 380V model
46 460V model
22 220V model
1 Full function
2 Core function
14 12 10 36 2 22 1
Dip switch setting
Dip switch setting ODU Setting
Slave 1
Slave 2
Automatic Addressing
The address of indoor units would be set by Automatic Addressing
- Wait for 3 minutes after supplying power. (Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A “88” is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on numbers of connected indoor units
-
Numbers of connected indoor units whose addressing is completed are indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated on the wired remote control display window. (CH01, CH02, CH03, … …, CH06 : Indicated as numbers of connected indoor units)
[MAIN PCB]
DIP-SWITCH 7 - Segment
SW01C ( : confirm)
SW02C (ඔ : backward)
SW03C (ඖ : forward)
SW04C (
: cancel)
SW01D (reset)
CAUTION
• In replacement of the indoor unit PCB, always perform Automatic addressing setting again (At that time, please check about using Independent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error occur.
• Automatic Addressing is only possible on the master Unit.
• Automatic Addressing has to be performed after 3 minutes to im­prove communication.
!
The Procedure of Automatic Addressing
Setting the function Select the mode/function/option/value using ‘’, ‘’ Button and con-
firm that using the ‘’ button after dip switch No.5 is turned on.
DIP-SW01 7 - Segment
SW01C ( : confirm)
SW02C (ඔ : backward)
SW03C (ඖ : forward)
SW04C (
: cancel)
SW01D (reset)
Power On
Waiting 3 minutes
Press RED Button for 5 sec.
(SW01C)
7-segment LED = 88
Don’t press RED Button
(SW01C)
Waiting about 2~7 minutes
7-segment LED
= 88
YES
OK
Automatic addressing start
• Automatic addressing setting end Numbers of indoor unit connection set whose addressing is completed are indicated for 30seconds on 7-segment LED after completing setting
NO Check the connections
Indoor address number is displayed on wired remote control or indoor unit display window. It is not an error message, will disappeared when on/off button is pressed on remote control ex) Display of 01, 02, ..., 15 means connection of 15 indoor units and Automatic addressing is completed normally.
of communication cable
Mode Function Option Value Action
Remarks
Content
Display1
Content
Display2
Content Display3
Content Display4
Implement Display5
Installation
Cool & Heat
Selector
oFF
op1~
op2
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Static pres-
sure com-
pensation
oFF
op1~
op3
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Night low
noise
oFF
op1~o
p12
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Overall de-
frost
on
oFF
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
ODU ad-
dress
-
-
0~255
set the
value
Change
the set
value
Blank
Save in
EEPROM
Snow re-
moval &
rapid defrost
oFF
op1~
op3
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
IDU capacity
adjusting
on
oFF
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
Target pressure adjusting
oFF
op1~
op3
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
High effi-
ciency
mode
on
oFF
Selected
the option
- -
Change
the set
value
Blank
Save in
EEPROM
* Functions save in EEPROM will be kept continuously, though the
system power was reset.
Group Number setting
Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal should be connected to central control of Outdoor Unit with care for their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID from 0 to F for this purpose.
Outdoor Units (External PCB)
Example) Group number setting
1
st
number indicate the group number
2nd number point out indoor unit number
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
B(D) A(C)
1 F
Group Indoor unit
Group recognizing the central controller
No.0 group (00~0F) No.1 group (10~1F) No.2 group (20~2F) No.3 group (30~3F) No.4 group (40~4F) No.5 group (50~5F) No.6 group (60~6F) No.7 group (70~7F) No.8 group (80~8F) No.9 group (90~9F) No. A group (A0~AF) No. B group (B0~BF) No. C group (C0~CF) No. D group (D0~DF) No. E group (E0~EF) No. F group (F0~FF)
24
ENGLISH
Cool & Heat selector
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn1” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”,“op2” Push the ‘’ button
Cool & Heat Selection mode is set
Function setting
Switch control Function
Switch(Phase) Switch(Bottom)
oFF op1(mode) op2(mode) Right Left Not operate Cooling Cooling Right Right Not operate Heating Heating
Left - Not operate Fan mode Off
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, first install a Cool & Heat selector.
!
Switch (Phase)
Switch (Bottom)
Left side
Right side
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan discharge of ODU.
Static pressure compensation mode setting method
FAN Maximum RPM of each step
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn2” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op3” Push the ‘’ button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Chassis UX2 UX3
Max. RPM
Standard 850 1050
op1 870 1080 op2 890 1110 op3 900 1120
25
ENGLISH
Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
Time Settings
Noise
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn3” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op12” Push the ‘’ button
Start the Night low noise function :
Save the selected option value in EEPROM
Step Judgment Time(Hr) Operation Time(Hr)
op1 8 9 op2 6.5 10.5 op3 5 12 op4 8 9 op5 6.5 10.5 op6 5 12 op7 8 9 op8 6.5 10
op9 5 12 op10 Continuous operation op11 Continuous operation op12 Continuous operation
Step
Chassis
UX2 UX3
Noise(dB) op1~op3, op10 55 59 op4~op6, op11 52 56 op7~op9, op12 49 53
CAUTION
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.
!
Overall defrost mode
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn4” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on” ~ “oFF” Push the ‘’ button
Overall defrost mode is set
Mode setting
- on: Operate overall defrost
- off: Operate partial defrost
CAUTION
• Ask an authorized technician to setting a function.
• ARUV***BTS4 models do not have Defrost function.
!
Setting the ODU address
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn5” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“0” ~ “255” Push the ‘’ button
ODU address is set
CAUTION
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
!
Target pressure adjusting
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1” ~ “op4” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Target pressure is set
Select the Option using ‘’, ‘’ Button :
“HEAT” , “COOL” Push the ‘’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
Step
Purpose
Evaporating
temperature
variation
Condensing
temperature
variation
Heat Cool
op1 Increase capacity Increase capacity -3 °C +2 °C
op2
Decrease power
consumption
Increase capacity -1.5 °C -2 °C
op3
Decrease power
consumption
Decrease power
consumption
+2.5 °C -4 °C
op4
Decrease power
consumption
Decrease power
consumption
-4.5 °C -6 °C
26
ENGLISH
Snow removal & rapid defrost
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn6” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1” ~ “op3” Push the ‘’ button
Mode is set
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
!
Mode setting
Step Mode
oFF Not setting
op1 Snow removal mode
op2 Rapid defrost mode
op3 Snow removal mode. + Rapid defrost mode.
27
ENGLISH
Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display 1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number.(* = 1: Master, 2: Slave 1, 3: Slave 2)
Ex)
Display Title Cause of Error
Indoor unit related error
0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
0 3 -
Communication error : wired remote controller indoor unit
Failing to receive wired remote controller signal in indoor unit PCB
0 4 - Drain pump Malfunction of drain pump
0 5 -
Communication error : outdoor unit indoor unit
Failing to receive outdoor unit signal in indoor unit PCB
0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short
0 9 - Indoor EEPROM Error
In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFF
1 0 - Poor fan motor operation
Disconnecting the fan motor connector / Failure of indoor fan motor lock
1 7 - Inlet Air temperature sensor of FAU Air temperature sensor of indoor unit is open or short
Outdoor unit related error
2 1 *
Master Outdoor Unit Inverter Compressor IPM Fault
Master Outdoor Unit Inverter Compressor Drive IPM Fault
2 2 *
Inverter Board Input Over Current(RMS) of Master Outdoor Unit
Master Outdoor Unit Inverter Board Input Current excess (RMS)
2 3 *
Master Outdoor Unit Inverter Compressor DC link Low Voltage
DC charging is not performed at Master Outdoor Unit after start­ing relay turn on.
2 4 * Master Outdoor Unit High Pressure Switch
System is turned off by Master Outdoor Unit high pressure switch.
2 5 *
Master Outdoor Unit Input Voltage High/ Low Voltage
Master Outdoor Unit input voltage is over 242V or below 198V
26*
Master Outdoor Unit Inverter Compressor Start Failure
The First Start Failure by Master Outdoor Unit Inverter Compres­sor Abnormality
29*
Master Outdoor Unit Inverter Compressor Over Current
Master Outdoor Unit Inverter Compressor Fault OR Drive Fault
32*
Master Outdoor Unit Inverter Compressor1 High Discharge Temperature
Master Outdoor Unit Inverter Compressor1 High Discharge Tem­perature
33*
Master Outdoor Unit Inverter Compressor2 High Discharge Temperature
Master Outdoor Unit Inverter Compressor2 High Discharge Tem­perature
3 4 * High Pressure of Master Outdoor Unit High Pressure of Master Outdoor Unit
Error No.
Repeat
Error No. of Unit
Error No. of Compressor
28
ENGLISH
Display Title Cause of Error
Outdoor unit related error
3 5 * Low Pressure of Master Outdoor Unit Low Pressure of Master Outdoor Unit
3 6 *
Master Outdoor Unit Low Compression Ratio Lim­ited
Master Outdoor Unit Low Compression Ratio Limited
4 0 *
Master Outdoor Unit Inverter Compressor CT Sen­sor Fault
Master Outdoor Unit Inverter Compressor CT Sensor open or short
4 1 *
Master Outdoor Unit Inverter Compressor1 Dis­charge Temperature Sensor Fault
Master Outdoor Unit Inverter Compressor Discharge Tempera­ture Sensor open or short
4 2 * Master Outdoor Unit Low Pressure Sensor Fault Master Outdoor Unit Low Pressure Sensor open or short
4 3 * Master Outdoor Unit High Pressure Sensor Fault Master Outdoor Unit High Pressure Sensor open or short
4 4 * Master Outdoor Unit Air Temperature Sensor Fault Master Outdoor Unit Air Temperature Sensor open or short
4 5 *
Master Outdoor Unit Heat Exchanger Temperature Sensor (Front side) Fault
Master Outdoor Unit Heat Exchanger Temperature Sensor(Front side) open or short
4 6 *
Master Outdoor Unit Suction Temperature Sensor Fault
Master Outdoor Unit Suction Temperature Sensor open or short
4 7 *
Master Outdoor Unit Inverter Compressor2 Dis­charge Temperature Sensor Fault
Master Outdoor Unit Inverter Compressor2 Discharge Tempera­ture Sensor open or short
4 9 *
Master Outdoor Unit Faulty IPM Temperature Sen­sor
Master Outdoor Unit IPM Temperature Sensor short/open
5 0 *
Omitting connection of R, S, T power of Master Outdoor Unit
Omitting connection of Master outdoor unit
5 1 * Excessive capacity of indoor units
Excessive connection of indoor units compared to capacity of Out­door Unit
5 2 *
Communication error : inverter PCB Main PCB
Failing to receive inverter signal at main PCB of Master Outdoor Unit
5 3 *
Communication error : indoor unit Main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of Outdoor Unit .
5 7 *
Communication error : Main PCB inverter PCB
Failing to receive signal main PCB at inverter PCB of Master Out­door Unit
5 9 * Wrong combination of Outdoor units
Installed combination mixed with old series model (Multi V , ..)
6 0 * Inverter PCB EEPROM Error of Master Outdoor Unit Access Error of Inverter PCB of Master Outdoor Unit
6 2 *
Master Outdoor Unit Inverter Heatsink High Tem­perature
System is turned off by Master Outdoor Unit Inverter Heatsink High Temperature
6 5 *
Master Outdoor Unit Inverter Heatsink Tempera­ture Sensor Fault
Master Outdoor Unit Inverter Heatsink Temperature Sensor open or short
6 7 * Master Outdoor Unit Fan Lock Restriction of Master Outdoor Unit
7 1 * Converter CT Sensor Error of Master Outdoor Unit Converter CT Sensor open or short of Master Outdoor Unit
7 5 * Master Outdoor Unit Fan CT Sensor Error Master Outdoor Unit Fan CT Sensor open or short
76*
Master Outdoor Unit Fan DC Link High Voltage Error
Master Outdoor Unit Fan DC Link High Voltage Error
7 7 * Master Outdoor Unit Fan Over Current Error Master Outdoor Unit Fan Current is over 5A
7 9 * Master Outdoor Unit Fan Start Failure Error Master Outdoor Unit Fan First Position Sensing Failure
8 6 * Master Outdoor Unit Main PCB EEPROM Error
Communication Fail Between Master Outdoor Unit Main MICOM and EEPROM or omitting EEPROM
8 7 * Master Outdoor Unit Fan PCB EEPROM Error
Communication Fail Between Master Outdoor Unit Fan MICOM and EEPROM or omitting EEPROM
Loading...
+ 63 hidden pages