LG ARUN50LL2 INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.your set and retain it for future reference.
www.lg.com
MODELS: ARUV Series ARUN Series
ENGLISH
ITALIANO ESPAÑOL
FRANÇAIS DEUTSCH
PORTUGUESE
2 Outdoor Unit
ARUV/ARUN Series Outdoor unit Installation Manual
TABLE OF CONTENTS
Safety Precautions.................................................................................................3
Installation Process ...............................................................................................7
Outdoor units Information.....................................................................................8
Environment-friendly Alternative Refrigerant R410A ........................................9
Select the Best Location........................................................................................9
Installation Space.................................................................................................10
Lifting method ......................................................................................................12
Installation ............................................................................................................13
Refrigerant piping installation ............................................................................17
Electrical Wiring ...................................................................................................35
Test Run ................................................................................................................48
Caution For Refrigerant Leak..............................................................................56
Installation guide at the seaside.........................................................................58
Safety Precautions
ENGLISH
Installation Manual 3
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
n Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
n Installation
Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
• If the power source capacity is inadequate or electric work is performed improperly, electric shock and fire may result.
Ask the dealer or an authorized technician to install the air conditioner.
• Improper installation by the user may result in water leakage, electric shock, or fire.
Always ground the product.
• There is risk of fire or electric shock.
Always intstall a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock.
For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install, remove, or re-install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Do not store or use flammable gas or combustibles near the air conditioner.
• There is risk of fire or failure of product.
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Prepare for typhoons and other strong winds and earthquakes and install the unit at the specified place.
• Improper installation may cause the unit to top­ple and result in injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Safety Precautions
4 Outdoor Unit
When installing and moving the air condition­er to another site, do not charge it with a differnet refrigerant from the refrigerant specified on the unit.
• If a differnet refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be gamaged.
Do not reconstruct to change the settings of the protection devices.
• If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
Ventilate before operating air conditioner when gas goes out.
• It may cause explosion, fire, and burn.
Securely install the cover of control box and the panel.
• If the cover and panel are installed securely, dust or water may enter the outdoor unit and fire or electric shock may result.
If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
• Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceed­ed. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxy­gen in the room could result.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion.
There is the risk of death, injury, fire or explosion.
Operation Do not damage or use an unspecified power
cord.
• There is risk of fire, electric shock, explosion, or injury.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Do not touch the power switch with wet hands.
• There is risk of fire, electric shock, explosion, or injury.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or electric shock.
Be cautious not to touch the sharp edges when installing.
• It may cause injury.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
• This could result in personal injury and product damage.
Do not open the inlet grill of the product dur­ing operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.
Installation Manual 5
ENGLISH
Safety Precautions
n Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the unit where combustible gas may leak.
• If the gas leaks and accumulates around the unit, an explosion may result.
Use power cables of sufficient current carrying capacity and rating.
• Cables that are too small may leak, generate heat, and cause a fire.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
• There is risk of damage or loss of property.
Keep the unit away from children. The heat exchanger is very sharp.
• It can cause the injury, such as cutting the finger. Also the damaged fin may result in degradation of capacity.
When installting the unit in a hospital, com­munication station, or similar place, provide surfficient protection against noise.
The inverter equipment, private power generator, high-frequency medical equipment, or radio com­munication equipment may cause the air condition­er to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
n Operation
Do not use the air conditioner in special environments.
• Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
Do not block the inlet or outlet.
• It may cause failure of appliance or accident.
Make the connections securely so that the outside force of the cable is not applied to the terminals.
• Inadequate connection and fastening may gen­erate heat and cause a fire.
Be sure the installation area does not deteri­orate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Safety Precautions
6 Outdoor Unit
Be very careful about product transportation.
• Only one person should not carry the product if it weighs more than 20 kg.
• Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
• Do not touch the heat exchanger fins. Doing so may cut your fingers.
• When transporting the Outdoor Unit, suspending it at the specified positions on the unit base. Also support the Outdoor Unit at four points so that it cannot slip sideways.
Safely dispose of the packing materials.
Packing materials, such as mails and other metal or wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
Turn on the power at least 6 hours before starting operation.
• Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
Do not touch any of the refrigerant piping during and after operation.
• It can cause a burn or frostbite.
Do not operate the air conditioner with the panels and guards removed.
• Rotating, hot, or high-voltage parts can cause injuries.
Do not directly turn off the main power switch after stopping operation.
• Wait at least more than 5 minutes before turning off the main power switch. Otherwise it may result in water leakage or other problems.
Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the Indoor Unit board(PCB).
Use a firm stool or ladder when cleaning or maintaining the air conditioner.
• Be careful and avoid personal injury.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
• There are sharp and moving parts that could cause personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
• A bad connection may cause water leakage.
Do not operate with "System louver" closed.
• It may cause failure of appliance or accident.
Installation
Installation Process
The foundation must be level even
Outdoor unit foundation work
Avoid short circuits and ensure sufficient space is allowed for service
Installation of outdoor unit
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
2
) there must be no drop in pressure.
Airtight test
Multiple core cable must not be used. (suitable cable should be selected)
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness, cleanness and tightness
Refrigerant piping work
Check model name to make sure the fitting is made correctly
Installation of indoor unit
Take account of gradient of drain piping
Sleeve and insert work
Make relationship between outdoor, indoor, remote controller, and option connections clear. (Prepare control circuit diagram)
Preparation of contract drawings
Indicate clearly who is to be responsible for switch settings
Determination of division work
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Vacuum drying
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order
Transfer to customer with explanation
Preheat the crank case with the electrical heater for more than 6 hours.
• The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrants such change.
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pres­sure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refriger­ant is charged in its gaseous state, its composition changes and the system will not work properly.)
ENGLISH
Installation Manual 7
8 Outdoor Unit
Outdoor units Information
Outdoor units Information
CAUTION: Ratio of the connectable Indoor Units to the Outdoor: Within 50 ~ 130%
Ratio of the running Indoor Units to the Outdoor: Within 10 ~ 100% A combination operation over 100% cause to reduce the total capacity.
Power Supply: Outdoor Unit (3Ø, 380~415V, 50Hz / 3Ø, 380V, 60Hz)
Connectable Indoor Unit
Model
HP(Equivalent horsepower)
Chassis
Refrigerant
Product charge kg
CF(Correction Factor)
kg
Max. Connectable No. of Indoor Units
Net Weight kg
Dimensions (WxHxD)
mm
inch
Connecting Pipes
Liquid Pipes
[mm(inch)]
Gas Pipes
[mm(inch)]
ARUN50LR2 ARUN50LL2
5
UV
5.2
0
8
200
750x1,790x650
29.5x70.5x25.6
9.52(3/8)
15.88(5/8)
ARUN60LR2
ARUN60LL2
6
UV
5.2
0
9
200
750x1,790x650
29.5x70.5x25.6
9.52(3/8)
19.05(3/4)
ARUN80LR2 ARUN80LL2
8
UV
6.4
0
13
200
750x1,790x650
29.5x70.5x25.6
9.52(3/8)
19.05(3/4)
should be connected with "2 series" indoor unit only.
Ex) ARNU07GSEA2
n Heat Pump
Model
HP(Equivalent horsepower)
Chassis
Refrigerant
Product charge kg
CF(Correction Factor)
kg
Max. Connectable No. of Indoor Units
Net Weight kg
Dimensions (WxHxD)
mm
inch
Connecting Pipes
Liquid Pipes
[mm(inch)]
Gas Pipes
[mm(inch)]
ARUV80LR2 ARUV100LR2 ARUV80LL2 ARUV100LL2
810
UV1 UV
4.5 5.1
00
13 16
175 190
750 x 1,790 x 495 750x1,790x650
29.5 x 70.5 x 19.5 29.5x70.5x25.6
9.52(3/8) 9.52(3/8)
19.05(3/4) 22.2(7/8)
n Cooling Only
ENGLISH
Installation Manual 9
Environment-friendly Alternative Refrigerant R410A
Select the Best Location
Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying the neighbors by noise from unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leak of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the outdoor unit.
• If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation.
1. Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the prod-
uct at a place with a high humidity in winter (neare beach, coast, lake, etc). (Ex) Rooftop where sunshine always shines.
2. Performance of heating will be reduced and preheat time of the indoor unit may be lengthened in case of
installing the outdoor unit in winter at following location: (1) Shade position with a narrow space (2) Location with much moisture in neighboring floor. (3) Location with much humidity around. (4) Location where water gathers since the floor is not even.
• The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this character­istic should be also considered during the installation. R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is
0. These days the developed countries have approved it as the environmental-friendly refrigerant and encour­aged to use it widely to prevent environmental pollution.
Environment-friendly Alternative Refrigerant R410A
CAUTION:
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat up pipes more than its necessity to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
10 Outdoor Unit
Installation Space
Installation Space
• Space for the "*" display part of by type of system louver When installing automatic louver: 150 When installing manual louver: 150 When installing fixed louver: 100 (Basic space)
• Please install the product so that the door of the outdoor unit room is completely opened for smooth installation and service.
• A water drain outlet is required to discharge rain water on the bottom of the outdoor unit room or
condensation water to possibly generate when operating.
The recommended Specification of louver
• Multi V Space should be installed in the special outdoor room with soundproofing walls.
CAUTION:
Do not use bended louver like the above Fig. It disturbs the air circulation.
(Unit : mm)
65 596 40
954
137
650
(Min) 884 (+5)
UV : 1150 UV1 : 995
Door Width
UV : 900
UV1 : 745
660
500
(600)
676
100 (Min) * 100 (Min)
(Min) 1605 (+5)
1024
90
723(Anchor Bolt)
750
Drain hole
Drain pipe
660mm
550mm970mm
85mm
Installation Space
ENGLISH
Installation Manual 11
Cautions in winter especially for seasonal wind
• Sufficient measures are required at a snow area or severe cold area in winter so that product can be operated well.
• Get ready for seasonal wind or snow in winter even in other area.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction hole, the system may malfunction.
• Don't install the suction hole and discharge hole of the outdoor unit facing to the seasonal wind.
W
H
N
Air Flow Rate Q = Discharge Area(Ad) * Discharge air velocity Air Flow Rate Q = Suction Area(As) * Suction air velocity
Ad + As
Af
X 100
ho
h
θ
θ
E.O.R > 120%
Recommended Effective Opening Ratio(E.O.R) of Louver
• ho = h * COSθ
• Total Area(A) = H * W
• Effective Area(Af) = ho * W * N
• Opening Ratio(n) = Af/A Af = A * n
E.O.R(%) =
Af
Ad + As
12 Outdoor Unit
Lifting Method
• When carrying the unit suspended, pass the ropes under the unit and use the two suspension points each at the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
Lifting method
CAUTION
Be very careful to carry product.
• Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
• When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall of it.
• Use 2 belts of at least 8 m long.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
40° or less
A
Rope suspension point
B
WARNING
ENGLISH
Installation Manual 13
Installation
Installation
Location of anchor bolt
n Installation foot (Location of anchor bolt)
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation status. Thus, use anti-vibration materials (Anti-vibration pad) fully (The base pad shall be more than 200mm).
A
B
D
E
F
G
C
Ensure that the corner part can be securely mounted. Otherwise, the support for installation may be bent.
Obtain and use the M10 anchor bolt. The corner was not properly mounted. Outdoor unit (Insert the cushion pad between outdoor unit and base support to ensure that
anti-vibration may be done in a wide area) Pipe and wiring space (in case of piping and wiring on the floor surface) H-Beam support Concrete base support
Foundation bolt executing method
200
Nut
75
75
200
Spring washer
Frame
Anti-vibration
materials
Four bolt are required 3 thread ridges
H-Beam
Concrete
base
100
WARNING
• Be sure to install unit in a place strong enough to withstand its weight. Any lack of strength may cause unit to fall down, resulting in a personal injury.
• Have installation work in order to protect against a strong wind and earthquake. Any installation deficiency may cause unit to fall down, resulting in a personal injury.
• Especially take care for support strength of the floor surface, water drain processing (processing of water flown out from the outdoor unit during operation) and paths of the pipe and wiring when mak­ing a base support.
• Don't use a tube or pipe for water drain in the base pan and perform water drain processing by using the drain path. Water drain may not be done due to freezing of a tube or pipe.
(Unit : mm)
723
UV : 516
UV1 : 362
G
14 Outdoor Unit
Installation
Preparation of Piping
1) Cut the pipes and the cable.
n Use the accessory piping kit or the pipes purchased
locally.
n Measure the distance between the indoor and the out-
door unit.
n Cut the pipes a little longer than measured distance. n Cut the cable 1.5m longer than the pipe length.
2) Burrs removal
n Completely remove all burrs from the cut cross section
of pipe/tube.
n Put the end of the copper tube/pipe to downward direc-
tion as you remove burrs in order to avoid to let burrs drop in the tubing.
3) Flaring work
n Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
4) Check
n Compare the flared work with figure below. n If flare is noted to be defective, cut off the flared section
and do flaring work again.
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Pipe " A " (mm)
Gas Liquid Gas
Liquid
<5.6(19,100) 1/2" 1/4" 0.5~0.8 0~0.5 <16.0(54,600) 5/8" 3/8" 0.8~1.0 0.5~0.8 <22.4(76,400) 3/4" 3/8" 1.0~1.3 0.5~0.8
Indoor unit [kW(Btu/h]
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
ENGLISH
Installation Manual 15
Installation
1. Remove the cap and turn the valve counter clockwise with the hexagon wrench.
2. Turn it until the shaft stops. Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3. Make sure to tighten the cap securely.
1. Remove the cap and turn the valve clockwise with the hexagon wrench.
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely. * For the tightening torque, refer to the table on the below.
Precautions when connecting pipes
• See the following table for flare part machining dimensions.
• When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three
or four times at first. (Use ester oil or ether oil.)
• See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
• After all the piping has been connected, use nitrogen to perform a gas leak check.
Tightening torque
Union
CAUTION
• Always use a charge hose for service port connection.
• After tightening the cap, check that no refrigerant leaks are present.
• When loosening a flare nut, always use two wrenches in combination, When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare(inner and outer faces) with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as the initial tightening.
Opening shutoff valve
Closing shutoff valve
FLARE SHAPE and FLARE NUT TIGHTENING TORQUE
Shutoff
valve size
Ø6.4 Ø9.5
Ø12.7
Ø15.9
Ø22.2 Ø25.4
13.5~16.5
18~22
14~17 33~39 50~60
62~75
23~27
13.5~16.5
5.4~6.6
Hexagonal
wrench 4mm
Hexagonal
wrench 6mm
Hexagonal
wrench 10mm
8.1~9.9
27-33 36~44
-
11.5-13.9
22~28-
Tightening torque (N.m)(Turn clockwise to close)
Shaft(valve body)
Gas line piping attached to unit
Cap(Valve lid) Service port Flare nut
90°
±2
45
°
±
2
A
R=0.4~0.8
pipe size tightening torque(N.m) A(mm) flare shape
Ø9.5 3.27~3.99 12.8~13.2
Ø12.7 4.95~6.30 16.2~16.6
Ø15.9 6.18~7.54 19.3~19.7
16 Outdoor Unit
Installation
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
2. Precautions in high humidity circumstance: This air conditioner has been tested according to the "ISO Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere (dew point tempera­ture: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according to the following procedure:
• Heat insulation material to be prepared... EPDM (Ethylene Propylene Diene Methylene)-over 120°C the heat-resistance temperature.
• Add the insulation over 10mm thickness at high humidity environment.
Indoor unit
Thermal insulator (accessory)
Fastening band (accessory)
Refrigerant piping
HEAT INSULATION
ENGLISH
Installation Manual 17
Refrigerant piping installation
WARNING
After completing work, securely tighten both service ports and caps so that gas does not leak.
Refrigerant piping installation
WARNING
Always use extreme care to prevent the refrigerant gas (R410A) from leakage while using fire or flame. If the refrigerant gas comes in contact with the flame from any source, such as a gas stove, it breaks down and generates a poisonous gas which can cause gas poisoning. Never perform brazing in an unventilated room. Always conduct an inspection for gas leakage after installation of the refrig­erant piping has been completed.
Cautions in pipe connection/valve operation
Open status when both the pipe and the valve are in a straight line.
Cut both the pipe and the valve with a cutter to suit the length (Don't cut the length of less than 70mm)
CLOSE OPEN
Pipe joint (auxiliary parts): Securely perform brazing with
a nitrogen blow into the service valve port.(Releasing pressure : 0.02 MPa or less)
Flare nut: Loose or tighten flare nut by using the wrench
with both ends. Coat the flare connection part with oil for the compressor.
Cap: Remove caps and operate valve, etc. After opera-
tion, always reattach caps (tightening torque of valve cap: 25N.m (250kgf.cm) or more). (Don't remove the internal part of the port)
Service port: Make the refrigerant pipe vacuum and
charge it using the service port. Always reattach caps after completing work (tightening torque of service cap: 14N.m (140kgf.cm) or more).
Liquid pipe
Gas pipe
Ball Valve(Gas Pipe)
22.2 : brazing type
19.05 : flare type
Ball Valve(Liquid Pipe)
18 Outdoor Unit
Refrigerant piping installation
To Outdoor Unit
Sealed Piping
A
A
B
A B
1. Use the following materials for refrigerant piping.
• Material: Seamless phosphorous deoxidized copper pipe
• Wall thickness : Comply with the relevant local and national regulations for the designed pressure
3.8MPa. We recommend the following table as the minimum wall thickness.
2. Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.
3. Use care to prevent dust, water or other contaminants from entering the piping during installation.
4. Reduce the number of bending portions as much as possible, and make bending radius as big as possible.
5. Always use the branch piping set shown below, which are sold separately.
6. If the diameters of the branch piping of the designated refrigerant piping differs, use a pipe cutter to cut the connecting section and then use an adapter for connecting different diameters to connect the piping.
7. Always observe the restrictions on the refrigerant piping (such as rated length, difference in height, and piping diameter). Failure to do so can result in equipment failure or a decline in heating/cooling performance.
8. A second branch cannot be made after a header. (These are shown by .)
9. The Multi V will stop due to an abnormality like excessive or insufficient refrigerant. At such a time, always properly charge the unit. When servicing, always check the notes concerning both the piping length and the amount of additional refrigerant.
10. Never perform a pump down. This will not only damage the compressor but also deteriorate the
performance.
11. Never use refrigerant to perform an air purge. Always evacuate using a vacuum pump.
Caution
ARBLN01621 ARBLN03321 ARBL054 ARBL057 ARBL1010
Y branch
Header
4 branch 7 branch 10 branch
0.99
22.2
1.1
31.8
1.21
34.9
1.35
38.1
1.43
41.3
0.99
28.58
0.99
25.4
0.99
19.05
0.99
15.88
0.8
12.7
0.8
9.52
0.8
6.35
Minimum
thickness [mm]
Outer diameter
[mm]
ENGLISH
Installation Manual 19
Refrigerant piping installation
WARNING
When installing and moving the air conditioner to another site, be sure to make recharge refrigerant after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
- After selecting diameter of the refrigerant pipe to suit total capacity of the indoor unit connected after branching, use an appropriate branch pipe set according to the pipe diameter of the indoor unit and the installation pipe drawing.
Do not use anti-oxidants when brazing the pipe joints. Residue can clog pipes and break equipment.
12. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling perfor­mance, drip of condensate and other such problems.
13. When connecting the refrigerant piping, make sure the service valves of the Outdoor Unit is completely closed (the factory setting) and do not operate it until the refrigerant piping for the Outdoor and Indoor Units has been connected, a refrigerant leakage test has been performed and the evacuation process has been completed.
14. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film can cause clogging or damage to the compressor unit and flux can harm the copper piping or refrigerant oil.
1 Refrigerant piping 4 Taping 2 Pipe to be brazed 5 Valve 3 Nitrogen 6 Pressure-reducing valve
6
1
2
45
3
20 Outdoor Unit
Refrigerant piping installation
Selection of Refrigerant Piping
Selection of pipe sizeName
Size of main pipe
Pipe size of between branching sections
Connecting pipe size of indoor unit
Piping partsNo.
Outdoor unit
1st branching section
Branching section
Branching section
Branching section
Indoor unit
Main pipe
Branching pipe
Indoor unit
connecting pipe
Outdoor unit capacity type
Liquid pipe Gas pipe [mm(inch)] [mm(inch)]
5HP Ø9.52(3/8) Ø15.88(5/8)
6, 8HP Ø9.52(3/8) Ø19.05(3/4)
10HP Ø9.52(3/8) Ø22.2(7/8)
Indoor unit capacity[kW(Btu/h)]
Liquid pipe Gas pipe
[mm(inch)] [mm(inch)]
≤ 5.6(19,100) Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,000) Ø9.52(3/8) Ø15.88(5/8)
Indoor unit capacity[kW(Btu/h)]
Liquid pipe Gas pipe
[mm(inch)] [mm(inch)]
≤ 5.6(19,100) Ø6.35(1/4) Ø12.7(1/2) < 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8) < 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
Outdoor unit
Gas pipe
Main pipe
Liquid pipe
Branching
Branching
pipe
pipe
Indoor unit
ENGLISH
Installation Manual 21
• * :
Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• ** : Indoor Unit should be installed at lower position than the header
Refrigerant piping installation
u Y branch method
Refrigerant piping system
Example : 5 Indoor Units connected
: Outdoor Unit: 1st branch (Y branch) : Indoor Units
L150m
l 40m
H 50m
h 15m
Ú Total pipe length = A+B+C+D+a+b+c+d+e ≤ 300m
Longest pipe length * Equivalent pipe length A+B+C+D+e ≤ 150m A+B+C+D+e ≤ 175m Longest pipe length after 1st branch B+C+D+e ≤ 40m Difference in height(Outdoor Unit ÷ Indoor Unit) H ≤ 50m(40m:Outdoor unit is lower than Indoor Units)** Difference in height (Indoor Unit ÷ Indoor Unit) h ≤ 15m
L
l
H
h
22 Outdoor Unit
Refrigerant piping installation
u Header Method
Example : 6 Indoor Units connected
: Outdoor Unit
: 1st branch
: Indoor Units
: Sealed piping
L 150m
40m
H 50m
h 15m
Branch pipe can not be used after header
Ú Total pipe length = A+a+b+c+d+e+f ≤ 300m
Longest pipe length * Equivalent pipe length A+f ≤ 150m A+f ≤ 175m Longest pipe length after 1st branch f ≤ 40m Difference in height(Outdoor Unit ÷ Indoor Unit) H ≤ 50m(40m:Outdoor unit is lower than Indoor Units)** Difference in height (Indoor Unit ÷ Indoor Unit) h ≤ 15m
L
l
H
h
• * :
Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• ** : Indoor Unit should be installed at lower position than the header
WARNING
Pipe length after header branching (a~f) It is recommended that difference in length of the pipes connected to the Indoor Units is minimized. Performance difference between Indoor Units may occur.
ENGLISH
Installation Manual 23
Refrigerant piping installation
u Combination of Y branch/header method
Example : 5 Indoor Units connected
: Outdoor Unit
: 1st branch (Y branch)
: Y branch
: Indoor Unit
: Header
: Sealed piping
L150m
40m
H 50m
h 15m
Branch pipe can not be used after header
Ú Total pipe length = A+B+C+a+b+c+d+e ≤ 300m
• * :
Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• ** : Indoor Unit should be installed at lower position than the header
Longest pipe length * Equivalent pipe length A+B+b ≤ 150m A+B+b ≤ 175m Longest pipe length after 1st branch B+b ≤ 40m Difference in height(Outdoor Unit ÷ Indoor Unit) H ≤ 50m(40m:Outdoor unit is lower than Indoor Units)** Difference in height (Indoor Unit ÷ Indoor Unit) h ≤ 15m
L
l
H
h
Ú Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor Unit total capacity
[kW(Btu/h)]
≤5.6(19,100) Ø6.35(1/4) Ø12.7(1/2)
<16(54,600) Ø9.52(3/8) Ø15.88(5/8)
<22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
< 33(112,600) Ø9.52(3/8) Ø22.2(7/8)
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
24 Outdoor Unit
Refrigerant piping installation
u The Amount of Refrigerant
The calculation of the additional charge should take account of the length of pipe.
Additional charge (kg)
Product Charge ARUN50LL2(R2) = 5.2kg ARUN60LL2(R2) = 5.2kg ARUN80LL2(R2) = 6.4 kg ARUV80LL2(R2) = 4.5kg ARUV100LL2(R2) = 5.1kg
= + +
+ +
+
+=
+
Total liquid pipe (m): Ø22.2mm
x 0.354(kg/m)
x 0.266(kg/m)
x 0.173(kg/m)
x 0.118(kg/m)
x 0.061(kg/m)
x 0.022(kg/m)
Total liquid pipe (m): Ø19.05mm
Total liquid pipe (m): Ø15.88mm
Total liquid pipe (m): Ø12.7mm
Total liquid pipe (m): Ø9.52mm
Total liquid pipe (m): Ø6.35mm
CF(kg)
(Correction Factor)
Total amount(kg)
If a negative result is obtained from the calculation, no refrigerant needs to be added.
A
A B
B
CAUTION
B B B
BB
A
B
C
X
b
a
c d
34 5
21
e
Outdoor Unit Indoor Unit A : ø9.52, 40m B : ø9.52, 20m C : ø9.52, 20m
Ex
Additional Charge = A x 0.061 + B x 0.061 + C x 0.061 + (a+b+c+d+e) x 0.022 + CF
= 40 x 0.061 + 20 x 0.061 + 20 x 0.061
+ (10 x 5) x 0.022 - 0 (CF)
= 5.98(kg)
a : ø6.35, 10m b : ø6.35, 10m c : ø6.35, 10m d : ø6.35, 10m e : ø6.35, 10m
u Special condition
In case of the No. of CST TQ/TR/RAC SE/ARTCOOL SF models are over than 50% of the connected indoor units when the total No. of connected indoor units are over than 50% of the max. connectable indoor units.
n Additional refrigerant charging amount (kg) :
= (A x
α+ B x ß) - (AVG x ß)
• A = Total No. of TQ,TR,SE and SF Indoor units,
α= 0.5
• B = Total No. of except TE,SE and SF Indoor units, ß = 0.3
• AVG = 50% of Max. No. of connectable Indoor units.
Example)
1) Installation Information
- Outdoor unit : 6HP
- Total indoor units : 6 units (TQ 3 units, SE 2 units, BH 1 unit)
2) Information from PDB
- Max. No. of connectable indoor units : 9 units
- Calculated additional refrigerant amount = 2 kg :
3) Indoor refrigerant charging amount
= (5 units x 0.5+1 unit x 0.3) - (5 units x 0.3) = 1.3 kg :
Revised the total additional charging amount = Ⓑ + Ⓒ = 2 kg +1.3 kg
= 3.3 kg
Total amount(kg)
+=
AB+C
ENGLISH
Installation Manual 25
Refrigerant piping installation
WARNING
Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
p If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
1. Installation of effective opening part
2. Reconfirmation of Outdoor Unit capacity and piping length
3. Reduction of the amount of refrigerant
4. Installation of 2 or more security device (alarm for gas leakage)
- Change Indoor Unit type : installation position should be over 2m from the floor (Wall mounted type Cassette type)
- Adoption of ventilation system : choose ordinary ventilation system or building ventilation system
- Limitation in piping work : Prepare for earthquake and thermal stress
Total amount of refrigerant in the system
0.44 ( kg / m
3
)
Volume of the room at which Indoor Unit of the least capacity is installed
26 Outdoor Unit
Refrigerant piping installation
1. Line Distribution
2. Vertical Distribution
Ensure that the branch pipes are attached vertically.
3. The others
Header
1st
1st
1st
Main pipe
Distribution
2nd
2nd
3rd
2nd
Main pipe
Distribution
1st
3rd
3rd main pipe distribution
2nd
Distribution Method
ENGLISH
Installation Manual 27
Refrigerant piping installation
Branch pipe Fitting
Y branch
A
B
To Outdoor Unit To Branch Piping or Indoor Unit
A
B
Facing
upwards
Facing
downwards
Viewed from point A in direction of arrow
Horizontal plane
Within +/- 10°
A
A
B
Header
To outdoor unit To indoor unit
A
B
C
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
• When the number of pipes to be connected is smaller than the number of header branches, install a cap to the unconnected branches.
• The indoor unit having larger capacity must be installed closer to than smaller one.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint,
the connecting section
should be cut with a pipe cutter.
Pipe cutter
28 Outdoor Unit
Refrigerant piping installation
• When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connection then cap pipes should be fitted to the surplus branches.
• Fit branch pipe lie in a horizontal plane.
• Header should be insulated with the insulator in each kit.
• Joints between branch and pipe should be sealed with the tape included in each kit.
• Any cap pipe should be insulated using the insulator provided with each kit and then taped as described above.
B
Pinched pipe
Horizontal plane
View from point B in the direction of the arrow
Insulate the header using the insulation material attached to the branch pipe kit as shown in the figure.
Insulator
Insulator of field pipe
Tape
Tape
Cap pipe
Insulator for cap pipe
ENGLISH
Installation Manual 29
Refrigerant piping installation
1. Y Branch
Selection of Y Branch and Header
Models Gas pipe Liquid pipe
ARBLN01621
ARBLN03321
ARBLN07121
I.D12.7
I.D15.88
I.D19.05
1
I.D25.4
O.D19 .05
3
1
I.D31.8
I.D28.58
2
O.D22.2
O.D15 .88
I.D28.58
I.D22.2
70 80 110
I.D34.9
I.D31.8
120 90
390 413
376 404
O.D31.8
281 292
O.D25.4
I.D12.7
I.D15.88
I.D15.88
74
I.D12.7I.D19.05I.D15.88I.D19.05I.D22.2 2
83
I.D12.7
3
I.D22.2
I.D25.4
I.D15.88
2
8
96
I.D12.7
3
I.D22.2
I.D28.58
120 110 70
I.D15.88
O.D19 .05
1 2
I.D19.05
O.D19 .05
1 3
I.D12.7
I.D19.05
2.22D.I85.82D.I
I.D19.05
I.D15.8
I.D12.7
3
I.D.6.35
1
1
I.D12.7
I.D19.05
I.D9.52
7070
I.D15.88
O.D9. 52
281 292
321 332
371 394
I.D9.52
I.D.9.52
I.D12.7
I.D9.52
I.D12.7
I.D6.35
I.D9.52
I.D19.05
I.D15.88I.D12.7
I.D12.7
I.D15.88 I.D19.05
O.D12 .7I.D6.35
2
[unit:mm]
I.D6.35
I.D.6.35
I.D12.7
2
25.9D.I25.9D.I7.21D.O
74
53.6D.I25.9D.I
7
4
83
3
I.D34.9
I.D34.9
O.D34 .9
3
I.D28.58
I.D22.2
I.D28.58I.D38.1
2
I.D22.2
3
I.D41.3
I.D19.05
I.D15.88 I.D19.05
1
125
I.D22.2
O.D15.88 I.D9.52
2 3 3
ARBLN14521
I.D41.3
I.D34.9
I.D38.1
I.D15.88
I.D19.05
3
O.D22.2
120 130
I.D12.7
3
O.D15 .88
471 517
I.D41.3 I.D38.1
O.D38 .1
2
90 O.D28 .58
2
For example. Indicated Ø9.52 is the outer diameter(O.D..) of field jointed piping
I.D19.05
I.D22.2
I.D15.88
I.D19.05
416 444
I.D12.7
110 110
O.D19 .05
80
I.D22.2
I.D9.52
O.D12.7 I.D6.35
I.D15.88
2
I.D12.7
96
3
30 Outdoor Unit
Refrigerant piping installation
2. Header
[unit:mm]
Models Gas pipe Liquid pipe
80
OD12.7ID9.52
75
120
150
320
60*3=180
ID9.52
ID9.52
ID6.35
ID6.35
ID12.7
60*3=180
120
150
320
75
120
OD28.58
ID25.4
ID22.2
ID15.88
ID12.7
ID28.58
ID19.05
ID15.88
4 branch
ARBL054
7 branch
ARBL057
4 branch
ARBL104
7 branch
ARBL107
10 branch
ARBL1010
10 branch
ARBL2010
120
150
320
7560*3=180
ID15.88
ID12.7
ID12.7
ID15.88
ID19.05
120
80
OD19.05
ID15.88
ID12.7
OD12.7
75
120
150
320
60*3=180
ID9.52
ID9.52
ID9.52
ID6.35
ID6.35
ID12.7
120
150
75
60*6=360
500
ID19.05
ID15.88
ID12.7
ID15.88
ID12.7
120
OD19.05
ID15.88
ID12.7
120
150
60*6=360
500
75
ID6.35
ID9.52
ID12.7
120
150
75
60*6=360
500
ID28.58
ID19.05
ID15.88
ID15.88
ID12.7
120
OD28.58
ID25.4
ID22.2
120
150
60*6=360
500
75
ID6.35
ID9.52
ID12.7
ID9.52
ID6.35
80
OD12.7ID9.52
120
150
75
60*9=540
680
ID28.58
ID19.05
ID15.88
ID15.88
ID12.7
120
150
75
60*9=540
680
ID6.35
ID9.52
ID12.7
120
OD28.58
ID25.4
ID22.2
ID9.52
ID6.35
80
OD12.7ID9.52
80
OD19.05
ID15.88
120
150
127
60*9=540
700
ID38.1
ID3.18
ID19.05
ID15.88
ID15.88
ID12.7
120
OD38.1
ID34.9
ID28.58
120
150
127
60*9=540
700
ID6.35
ID9.52
ID19.05
ID15.88
ID9.52
ID6.35
80
OD12.7
ID9.52
ENGLISH
Installation Manual 31
Refrigerant piping installation
Leak Test and Vacuum
(1) Leak test
Leak test should be m
ade by pressurizing nitrogen gas to 3.8 MPa(38.7kgf/cm2). If the pressure does not drop for 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method, refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid pipe, gas pipe and high/low pressure common pipe) The test result can be judged good if the pressure has not be reduced after leaving for about one day after com­pletion of nitrogen gas pressurization. During this test, set DIP switch as Vacuum Mode.
Note:
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is checked, apply the following correction factor
There is a pressure change of approximately 0.1 kgf/cm
2
(0.01 MPa) for each 1°C of temperature difference.
Correction= (Temp. at the time of pressurization – Temp. at the time of check) X 0.1
For example: Temperature at the time of pressurization (3.8 MPa) is 27 °C
24 hour later: 3.73 MPa, 20°C In this case the pressure drop of 0.07 is because of temperature drop And hence there is no leakage in pipe occurred.
CAUTION
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must be at higher position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
Gas pipe
Nitrogen gas
Liquide pipe
cylinder
32 Outdoor Unit
Refrigerant piping installation
(2) Vacuum
Vacuum drying should be made from the service port provided on the outdoor unitʼs service valve to the vac­uum pump commonly used for liquid pipe, gas pipe. Vaccum of the pipe and the indoor units should be made from the port of the outdoor unit's service valve with the service valve closed. * Never perform air purging using refrigerant.
• Vacuum drying: Use a vacuum pump that can evacuate to -100.7kPa (5 Torr, -755mmHg).
1) Evacuate the system from the liquid and gas pipes with a vacuum pump for over 2 hrs and bring the sys­tem to -100.7kPa. After maintaining system under that condition for over 1 hr, confirm the vacuum gauge rises. The system may contain moisture or leak.
2) Following should be executed if there is a possibility of moisture remaining inside the pipe. (Rainwater may enter the pipe during work in the rainy season or over a long period of time) After evacuating the system for 2 hrs, give pressure to the system to 0.05MPa(vacuum break) with nitro­gen gas and then evacuate it again with the vacuum pump for 1hr to -100.7kPa(vacuum drying). If the system cannot be evacuated to -100.7kPa within 2 hrs, repeat the steps of vacuum break and its drying. Finally, check if the vacuum gauge does not rise or not, after maintaining the system in vacuum for 1 hr.
WARNING
• If the primary charging is not performed after vacuum, wet air may go into the outdoor unit. If air is mixed with the refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
• Charging of refrigerant while the compressor is working is prohibited. Otherwise, liquid may go into the compres­sor. It may cause faults of the compressor.
• Use a gravimeter accurate to 0.1kg.
• If other refrigerants are mixed in the original refrigerant, a refrigerant cycle may cause malfunction or damage.
• Add accurate refrigerant quantity via calculation. Too much or too little refrigerant may cause problems
• Repeated on and off of the indoor units without charging refrigerant may cause faults of EEV.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
Vacuum pump
Gas pipe
Liquide pipe
ENGLISH
Installation Manual 33
Refrigerant piping installation
Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replace­ment or IDU addition/replacement.
Master main PCB DIP switch ON ( No.11,14)
Vacuum mode setting
ODU V/V OPEN
Main EEV, SC EEV OPEN
IDU EEV OPEN
ODU power reset
Press the black button Main PCB (5 sec.)
Main PCB SW01S
Main PCB SW02B
Main PCB SW01V
ODU operation stops during vacuum mode. Compressor can't operate.
Vacuum mode setting method Vacuum mode cancellation method
Master main PCB DIP switch OFF( No.11,14)
Power reset
Vacuum mode cancellation
Caution
34 Outdoor Unit
Refrigerant piping installation
Thermal Insulation of refrigerant piping
Heat
insulation
material
Outer
covering
Adhesive + Heat - resistant polyethylene foam + Adhesive tape
Indoor Vinyl tape Floor exposed
Water-proof hemp cloth + Bronze asphalt
Outdoor
Water-proof hemp cloth + Zinc plate + Oily paint
Note: When using polyethylene cover as covering material, asphalt roof­ing shall not be required.
• Do not insulate gas or low pressure pipe and liquid or high pressure pipe together.
• Be sure to fully insulate connecting portion.
Liquid pipe Gas pipe Power lines Finishing tape Insulating material
Bad example
Good example
These parts are not insulated.
B A C
A B C
A
C
D
E
A B C D E
Communication lines
F
Liquid pipe
Communication lines
Communication lines
Separation
Gas pipe Power lines Insulating material
A B C D E
A
A
B
F
Heat insulation material Pipe Outer covering
(Wind the connection part and cutting part of heat insulation material with a finishing tape.)
Power lines
E
D
D
B
A
C
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a possi­bility of condensation drip, etc. Pay special attention to insulation work to ceiling plenum.
1m1m
A
B
D
F
G
B
G
D
B
H
I
J
A
E
B
I
A
B
D
C
Inner wall (concealed)
Floor (fireproofing)
Penetrating portion on fire
limit and boundary wall
Roof pipe shaft
Outer wall Outer wall (exposed)
Penetrations
Sleeve Heat insulating material Lagging Caulking material Band Waterproofing layer Sleeve with edge Lagging material Mortar or other incombustible caulking Incombustible heat insulation material
When filling a gap with mortar, cover the penetration part with steel plate so that the insulation material will not be caved in. For this part, use incombustible materials for both insulation and covering.(Vinyl covering should not be used.)
ENGLISH
Installation Manual 35
Electrical Wiring
CAUTION
• Use the 2-core shield cables for communication lines. Never use them together with power cables.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never install a phase leading capacitor.
• Keep power imbalance within 2% of the supply rating. Large imbalance will shorten the life of the smoothing capacitor.
Remote control
Remote control
Remote control
Remote control
Indoor
Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Indoor
Unit
Remote control
Remote control
Indoor
Unit
Indoor
Unit
Remote control
Remote control
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
2-Core Shield Cable Multi-Core Cable
Electrical Wiring
Areas of Caution
CAUTION
Be sure to put Outdoor Unit to earth. Do not connect earth line to any gas pipe, water pipe, lighten­ing rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
WARNING
Be sure to have authorized electric engineers do electric work using special circuits in accordance with regulations and this installation manual. If power supply circuit has a lack of capacity or elec­tric work deficiency, it may cause an electric shock or fire.
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.
2. Install the Outdoor Unit communication line away from the power source wiring so that it is not affected by electric noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to Outdoor Unit.
4. Give some allowance to wiring for electrical part box of Indoor and Outdoor Units, because the box is some­times removed at the time of service work.
5. Never connect the main power source to terminal block of communication line. If connected, electrical parts will be burnt out.
6. Use 2-core shield cable for communication line.(O mark in the figure below) If communication lines of differ­ent systems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations. ( mark in the figure below)
7. Only the communication line specified should be connected to the terminal block for Outdoor Unit communi­cation .
36 Outdoor Unit
CAUTION
The Power cord connected to the unit should be selected according to the following specifications.
Electrical Wiring
Control box and connecting position of wiring
- Remove all of the screws at front panel and remove the panel by pulling it forward.
- Connect communication line between main and sub outdoor unit through the terminal block.
- Connect communication lines between outdoor unit and indoor units through the terminal block.
- When the central control system is connected to the outdoor unit, a dedicated PCB must be connected between them.
- When connecting communication line between outdoor unit and indoor units with shielded wire, connect the shield ground to the earth screw.
WARNING
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
Front Panel
DIRECTION OF PIPING/WIRING
Diode
Inverter PCB
Noise Filter
FAN PCB
Reactor
Main PCB
Terminal Block (3-Phase 4-wire power system)
ENGLISH
Installation Manual 37
Electrical Wiring
Communication and Power Lines
1) Communication cable
• Types : shielding wire
• Use wires of size : over 1.25mm
2
• Maximum allowable temperature: 60°C
• Maximum allowable line length: under 300m
2) Remote control cable
• Types : 3-core cable
3) Simple central control cable
• Types : 4-core cable (Shielding wire)
• Use wires of size : over 0.75mm
2
4) Separation of communication and power lines
• If communication and power lines are run alongside each other then there is a strong likelihood of opera­tional faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic coupling. The tables below indicates our recommendation as to appropriate spacing of communication and power lines where these are to be run side by side
Note:
1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m
the figures will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the
table should be increased.
• If the lines are laid inside conduits then the following point must also be taken into account when grouping various lines together for introduction into the conduits
• Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
• In the same way, when grouping the lines power and signal lines should not be bunched together.
Current capacity of power line Spacing
10A 300mm
50A 500mm
100A 1000mm
Exceed 100A 1500mm
100V or more
CAUTION
n If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the
apparatus must be carried out by a qualified person.
38 Outdoor Unit
Electrical Wiring
1. Use a separate power supply for the Outdoor Unit and Indoor Unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceed­ing with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.
6. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from
the power supply.
WARNING
• Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring reg­ulations and guidance of each electric power company.
• Make sure to use specified wires for connections so that no external force is imparted to terminal connections. If con­nections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
CAUTION
Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.
u Wiring of Main Power Supply and Equipment Capacity
CAUTION
When the 400 volt power supply is applied to "N" phase by mistake, replace inverter PCB and transformer in control box.
ENGLISH
Installation Manual 39
Electrical Wiring
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
• For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head will strip the head and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.
u Precautions when laying power wiring
Round pressure terminal
Power wire
Use round pressure terminals for connections to the power terminal block.
40 Outdoor Unit
Electrical Wiring
3 Phase 4 Wires
Power supply
50Hz 380-415V
3 Phase 4 Wires Power line(R, S, T, N) Communication line (3 line): Wired remote control Single Phase of power supply line(L, N) Communication line (2 shield line): Between Indoor Unit and Outdoor Unit
The GND terminal is a '–' terminal for the central controller, not Ground Line
Power supply switch (Switch fuse : ELCB)
34 34 34
(Main Switch)
IDUSODU DRY1 DRY2 GND 12V
INTERNET
BABA
Power supply
1 Phase 50Hz
220-240V
Power supply switch
(Switch)
Pull Box(Installer Option)
u Example Connection of Communication Cable
1. 50Hz
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident in current leakage, communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
ENGLISH
Installation Manual 41
Electrical Wiring
3 Phase 4 Wires
Power supply
60Hz 380V
3 Phase 4 Wires Power line(R, S, T, N) Communication line (3 line): Wired remote control Single Phase of power supply line(L, N) Communication line (2 shield line): Between Indoor Unit and Outdoor Unit
Power supply switch (Switch fuse : ELCB)
The GND terminal is a '–' terminal for the central controller, not Ground Line
34 34 34
IDUSODU DRY1 DRY2 GND 12V
INTERNET
BABA
Power supply
1 Phase 50Hz
220-240V
Power supply switch
(Switch)
Pull Box(Installer Option)
2. 60Hz
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident in current leakage, communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
42 Outdoor Unit
Electrical Wiring
Location of setting Switch
n Location of setting Switch
Main PCB
SW01B
(DIP S/W)
SW02B
(DIP S/W)
7 - Segment
SW02V Auto addressing
SW01V Data confirm
n Checking according to dip switch setting
1. You can check the setting values of the outdoor unit from the 7 segment LED. The dip switch setting should be changed when the power is OFF.
2. It checks whether the input is properly performed without the bad contact of the dip switch or not
n Checking the setting of the unit
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power. This number represents the setting condition. & model code total capacity ‘ 2 ‘ 25 ‘ model type
1 ~255 : model code6~10HP : HP numbersNo display : cooling only 2 : heat pump 25 : normal ARUV series : 70, ARUN series : 170
Example) ARUN60LL2(R2)
85 6 2 25 170
 
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
Model code Capacity [kW] Remarks
82 8
Cooling only
83 10 84 5 85 6 Heat pump 86 8
ENGLISH
Installation Manual 43
Electrical Wiring
n Setting the DIP switch (SW01B/SW02B)
• If you set the Dip switch when power is on, the changed setting will not be applied immediately. The changed setting will be enabled only when Power is reset or by pressing Reset button.
1. Settings of Master outdoor unit
SW01B Setting RemarksSW02B SettingFunction SW01B Setting Remarks
1234567ON1234567
ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1234567ON1234567
ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1234567ON1234567
ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Cool/Heat
selector
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1234567 891011121314
1234567ON1234567
ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1234567ON1234567
ON
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Standard
Power reset is
Necessary
40 ESP<60Pa
Power reset is
necessary
Factory Setting
Power reset is
Necessary
- Cooling Target Pressure : Standard-39
- Heating Target Pressure : Standard+131
Power reset is
Necessary
60 ESP<80Pa
Power reset is
Necessary
100 ESP 120Pa
Power reset is
Necessary
ARUN
series only
Optional device
Power reset is
Necessary
80 ESP<100Pa
Long Pipe Length
Outdoor unit
ESP
Compensation
(step 1)
Outdoor unit
ESP
Compensation
(step 2)
Outdoor unit
ESP
Compensation
(step 3)
Outdoor unit
ESP
Compensation
(step 4)
Low blowing
Noise
* In long piping mode, power consumption will be increased.
44 Outdoor Unit
Electrical Wiring
SW01B Setting RemarksSW02B SettingFunction SW01B Setting RemarksSW02B SettingFunction
ON
ON
Night Silent
Operation
Pump Down
Forced Oil Return
Vacuum Mode
Pump Out
Snow
Forced
Defrosting
Note: Oil collecting operation is default function which operates after every six hours.
- To enable forced operation of this function change the dip switch setting. And after using, make sure to restore the dip switch setting.
1234567ON1234567
1234567ON1234567
1234567 891011121314
1234567 891011121314
ON
ON
1234567ON1234567
1234567ON1234567
1234567 891011121314
1234567 891011121314
ON
ON
1234567ON1234567
1234567ON1234567
1234567 891011121314
1234567 891011121314
ON
ON
1234567ON1234567
1234567ON1234567
1234567 891011121314
1234567 891011121314
ON
ON
1234567ON1234567
1234567ON1234567
1234567 891011121314
1234567 891011121314
ON
ON
1234567ON1234567
1234567ON1234567
1234567 891011121314
1234567 891011121314
ON
ON
1234567ON1234567
1234567ON1234567
1234567 891011121314
1234567 891011121314
Power reset is
Necessary Fan RPM down at on night time
Power reset is
Necessary
All the refrigerant flows
back into the ODU
Dip switch +
Black button(SW01V)
During Vacuuming,
Valves &
EEV should be opened
ARUN
series only
ARUN
series only
Used when snow piles up
On the ODU Fan.
Fan operates periodically.
ARUN
series only
Accelerates defrost
operation
ENGLISH
Installation Manual 45
Electrical Wiring
Automatic Addressing
• The address of indoor units would be set by auto addressing
1) Wait for 3 minutes after applying power supply (main and sub outdoor unit, indoor unit).
2) Press the switch of the outdoor unit (SW02V) for 5 seconds.
3) A "88" is indicated on 7-segment LED of the out­door unit PCB.
4) For completing addressing, 2~7 minutes are required depending on numbers of indoor unit con­nection set.
5) Numbers of indoor unit connection set whose addressing is completed are indicated for 30sec­onds on 7-segment LED of the outdoor unit PCB.
6) After completing addressing, address of each indoor unit is indicated on the wired remote control
display window. (CH01, CH02, CH03, .............
CH06: Indicated as numbers of indoor unit connec­tion set.)
Main PCB
SW01B
(DIP S/W)
SW02B
(DIP S/W)
7 - Segment
SW02V Auto addressing
SW01V Data confirm
CAUTION
- In replacement of the indoor unit PCB, always perform auto address setting again. If power supply is not applied to the indoor unit, operation error occurs. Auto addressing is only possible on the main PCB Auto addressing has to be performed after 3 minutes to improve communication.
u The Procedure of Automatic Addressing
• Auto addressing setting end Numbers of indoor unit connection set whose addressing is completed are indicated for 30seconds on 7-segment LED after completing setting
Indoor address number is displayed on wired remote control or indoor unit display window. It is not an error message, will disappeared when on/off button is pressed on remote control ex) Display of 01, 02, ..., 15 means connection of 15 indoor units and auto addressing is completed normally.
Auto addressing start
Waiting 3 minutes
Power On
Press SW02V for 5 sec.
7-segment LED = 88
Don't Press SW02V
Waiting about 2~7 minutes
7-segment LED
OK
YES
NO Check the connections
of communication line
= No. of IDUs
46 Outdoor Unit
Electrical Wiring
Group Number setting
Group Number setting for Indoor Units
Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off.The communication lines connected to INTERNET terminal should be connected to central control of Outdoor
unti with care for their polarity( A ’ A, B ’ B )
Turn the whole system on. Set the group and Indoor Unit number with a wired remote control. To control several sets of Indoor Units into a group, set the group ID from 0 to F for this purpose.
Terminal block on the main PCB
SODU IDU INTERNET DRY1 DRY2
B
A
B(D) A(C)
GND 12V
B
A
BA
Group recognizing the simple central controller
No.0 group (00~0F) No.1 group (10~1F) No.2 group (20~2F) No.3 group (30~3F) No.4 group (40~4F) No.5 group (50~5F) No.6 group (60~6F) No.7 group (70~7F) No.8 group (80~8F) No.9 group (90~9F) No. A group (A0~AF) No. B group (B0~BF) No. C group (C0~CF) No. D group (D0~DF) No. E group (E0~EF) No. F group (F0~FF)
Outdoor Units
ENGLISH
Installation Manual 47
Electrical Wiring
n Using Cool/Heat Selector Installation and Connection
• Connect wires as below figure at the hole of backside of Outdoor Unit Dry Contact.
• Insert the wire in the connection hole pushing the "Push" button.
• Maximum communication line length for Cool/Heat Selector : 200m.
• Setting Main PCB Dip S/W of Master Outdoor Unit.
Cool/Heat Selector Installation and Connection
n Without Cool/Heat Selector Installation and Connection
In case, try to set mode without Cool/Heat Selector and try to use other switch except from LG Outdoor Cool/Heat Selector in field.
Connect signal terminal block as below figure and description.
- How to set mode without Cool/Heat Selector
• Cooling Mode Setting
¿‘GND Connection ¡‘Off (Open)
• Heating Mode Setting
¿‘ GND Connection ¡‘GND Connection
• Fan Mode Setting
¿‘ Off (Open) ¡‘GND Connection
Mode Change
Outdoor Unit
Heating
Back
Fan
Cooling
GND
GND
GND
48 Outdoor Unit
Test Run
Test Run
1
2
3
4
Check to see whether there is any refrigerant leakage, and slack of power or communication cable.
Confirm that 500 V megger shows 2 MΩ or more between power supply terminal block and ground. Do not operate in the case of 2 MΩ or less.
NOTE: Never carry out megaohm check over terminal control board. Otherwise the control board
would be broken. Immediately after mounting the unit or after leaving it turned off for an extended length of time, the resistance of the insulation between the power supply terminal board and the ground may decrease to approx. 2 MΩ as a result of refrigerant accumulating in the internal compressor. If the insulation resistance is less than 2 MΩ, turning on the main power supply and energizing the crankcase heater for more than 6 hours will cause the refrigerant to evaporate, increasing the insulation resistance.
Check if high/low pressure common pipe, liquid pipe and gas pipe valves are fully opened.
NOTE: Be sure to tighten caps.
Check if there are any problems in automatic addressing or not: Check and confirm that there are no error messages in the display of indoor units or remote controls and LED in outdoor units.
Checks Before Test Run
CAUTION
Preheat of compressor
- Start preheat operation for 3 hours after supplying main power.
- In case that the outdoor temperature is low, be sure to supply power 6 hours before operation so that the heater is heated(insufficient heating may cause damage of the compressor.)
CAUTION
When cutting main power of the Multi V
- Always apply main power of the outdoor unit during use of product (cooling season/heating season).
- Always apply power 6 hours in advance to heat the crank case heater where performing test run after installation of product. It may result in burning out of the compressor if not preheating the crank case with the electrical heater for more than 6 hours.(In case of the outdoor temperatue below 10°C)
ENGLISH
Installation Manual 49
Test Run
How to Cope with Test Run Abnormality
The phenomena from main component failure
When system fault occurs, the error code is displayed at indoor unit display or remote control display, the trouble shooting guide is in the service manual
Compressor
Outdoor
fan
Outdoor
EEV
Not operating
Stop during running
Abnormal noise during running
High pressure error at cooling
Heating failure, fre­quent defrosting
No operating sound at applying power
Heating failure, frozen outdoor heat exchanger part
Low pressure error or discharge temper­ature error
Motor insulation broken
Strainer clogged
Oil leakage
Motor insulation failure
R-S-T misconnection
Motor failure, bad ventilation around outdoor heat exchanger
Bad connector contact
Coil failure
EEV clogged
EEV clogged
Check resistance between terminals and chassis
Change strainer
Check oil amount after opening oil port
Check resistance between terminals and chassis
Check compressor R-S-T connection
Check the outdoor fan operation after being turned the outdoor units off for some time. Remove obstacles around the outdoor units
Check connector
Check resistance between terminals
Service necessary
Service necessary
Component Phenomenon Cause Check method and Trouble shooting
50 Outdoor Unit
Test Run
n ARUV series
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load.
Night Silent Operation
Max. RPM setting method
Dip S/W No.12+14 ON
Master ODU SW01B
Main PCB Power Reset
Note 1)
Setting the Fan Max. RPM
Master ODU SW01S
SW01V SW02V
Setting Complete
CAUTION
1. Request installer to set the function during installation.
2. In case the function is not used, set the dip S/W OFF and reset the power.
3. If ODU RPM changes, cooling capacity may go down.
[Note]
1. Select appropriate RPM referencing noise table.
Step
Setting
Red buttonBlack button
1 time1 2 times2 3 times3
1 time 1 time 1 time
Fan Max
RPM 450+ESP 400+ESP
350+ESP
Judgment
(hr)
8
Operation
(hr)
9 98 98
ENGLISH
Installation Manual 51
Test Run
n ARUN series
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load.
Max. RPM setting method
Judgment
(hr)
8
6.5 5 8
6.5 5 8
6.5 5
Judgment
(hr)
8
6.5 5 8
6.5 5 8
6.5 5
Master ODU SW01B
Master ODU SW01S
SW01V SW02V
Operation
(hr)
9
10.5 12
9
10.5 12
9
10.5 12
Operation
(hr)
9
10.5 12
9
10.5 12
9
10.5 12
Dip S/W No.12+14 ON
Main PCB Power Reset
Note 1)
Setting the Fan Max. RPM
Setting Complete
CAUTION
1. Request installer to set the function during installation.
2. In case the function is not used, set the dip S/W OFF and reset the power.
3. If ODU RPM changes, cooling capacity may go down.
[Note]
1. Select appropriate RPM referencing noise table.
• ARUN50/60LL2(R2)
Step
1 2 3 4 5 6 7 8 9
1time 2times 3times
4time 5times 6times 7times 8times 9times
Setting
Red buttonBlack button
1time 1time 1time 1time 1time 1time 1time 1time 1time
Fan Max
RPM 380+ESP 380+ESP 380+ESP 340+ESP 340+ESP 340+ESP 300+ESP 300+ESP 300+ESP
• ARUN80LL2(R2)
Step
1 2 3 4 5 6 7 8 9
1time 2times 3times
4time 5times 6times 7times 8times 9times
Setting
Red buttonBlack button
1time 1time 1time 1time 1time 1time 1time 1time 1time
Fan Max
RPM 480+ESP 480+ESP 480+ESP 440+ESP 440+ESP 440+ESP 400+ESP 400+ESP 400+ESP
52 Outdoor Unit
Test Run
This function is used for creating vacuum in the system after compressor replacement, ODU parts replace­ment or IDU addition/replacement.
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan
discharge of ODU.
n Static pressure compensation dip S/W setting method
n Each step's ESP setting condition
Vacuum Mode
External static pressure compensation mode
Step Range [Pa] Max. RPM
Step0 0 ≤ ESP < 40 -
Step1 40 ≤ ESP < 60 + 30 RPM
Step2 60 ≤ ESP < 80 + 60 RPM
Step3 80 ≤ ESP < 100 + 100 RPM
Step4 100 ≤ ESP ≤ 120 + 150 RPM
Vacuum mode setting method Vacuum mode cancellation method
Main PCB SW01S
Main PCB SW02B
Main PCB SW01V
Master main PCB DIP switch ON ( No.11,14)
Press the black button Main PCB (5 sec.)
Caution
ODU operation stops during vacuum mode. Compressor can't operate.
ODU power reset
Vacuum mode setting
ODU V/V OPEN
Main EEV, SC EEV OPEN
IDU EEV OPEN
Master main PCB DIP switch OFF( No.11,14)
Power reset
Vacuum mode cancellation
Static pressure compensation mode setting
method
DIP switch setting
Static pressure compensation mode cancellation
method
DIP switch OFF
Power Reset
Static pressure compensation mode is set
Power Reset
Static pressure compensation mode is cancelled
ENGLISH
Installation Manual 53
Test Run
Self-Diagnosis Function
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table.
•  If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st, 2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
Ex) 211 : No.21 error of unit
011 051 : No.105 error of unit
Display Title Cause of Error
01-
02-
03-
04-
05-
06-
07-
09-
10-
11-
211
221
231
241
251
261
Air temperature sensor of indoor unit
Inlet pipe temperature sensor of indoor unit
Communication error : wired remote controller ÷ indoor unit
Drain pump
Communication error : outdoor unit ÷ indoor unit
Outlet pipe temperature sensor of indoor unit
Different operation mode
Indoor EEPROM error.
Poor fan motor operation
Communication error: indoor unit main PCB of outdoor.
Outdoor Unit Inverter Compressor IPM Fault
Inverter Board Input Over Current(RMS) of Outdoor Unit
Outdoor Unit Inverter Compressor DC link Low Voltage
Outdoor Unit High Pressure Switch
Outdoor Unit Input Voltage High/ Low Voltage
Outdoor Unit Inverter Compressor Start Failure
Air temperature sensor of indoor unit is open or short
Inlet pipe temperature sensor of indoor unit is open or short
Failing to receive wired remote controller signal in indoor unit PCB
Malfunction of drain pump
Failing to receive outdoor unit signal in indoor unit PCB
Outlet pipe temperature sensor of indoor unit is open or short
Operation mode between indoor unit and outdoor unit is different
In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFF
Disconnecting the fan motor connector/Failure of indoor fan motor lock
When the addressing signal doesn't respond for 3mins. suddenly, while the indoor unit gets the calling signal from the outdoor unit,
Outdoor Unit Inverter Compressor Drive IPM Fault
Outdoor Unit Inverter Board Input Current excess (RMS)
DC charging is not performed at outdoor unit after starting relay turn on.
System is turned off by outdoor unit high pressure switch.
Outdoor Unit input voltage is over 487V or below 270V.
The First Start Failure by Outdoor Unit Inverter Compressor Abnormality
Indoor unit related error
Outdoor unit related error
54 Outdoor Unit
Test Run
System is turned off by outdoor unit Inverter Compressor High Discharge Temperature
System is turned off by Outdoor Uunit Constant Speed High Discharge Temperature
System is turned off by excessive increase of high pressure of outdoor unit
System is turned off by excessive decrease of low pressure of outdoor unit
Outdoor Unit Inverter Compressor CT Sensor open or short
Outdoor Unit Inverter Compressor Discharge Temperature Sensor open or short
Outdoor Unit Low Pressure Sensor open or short
Outdoor Unit High Pressure Sensor open or short
Outdoor Unit Air Temperature Sensor open or short
Outdoor Unit Heat Exchanger Temperature Sensor open or short
Outdoor Unit Suction Temperature Sensor open or short
Omitting connection of outdoor unit
Excessive connection of indoor units compared to capacity of outdoor unit
Failing to receive inverter signal at main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of out­door Unit.
Reverse connection or omitting connection of R, S, T power of outdoor unit
Access Error of Inverter PCB of Outdoor Unit
Restriction of Outdoor Unit (Inverter PCB)
Restriction of Outdoor Unit
System is turned off by outdoor unit DC Voltage Over Charging
Outdoor Unit Inverter Compressor Fault OR Drive Fault
Outdoor Unit Inverter Compressor High Discharge Temperature
Outdoor Unit Constant Speed Compressor High Discharge Temperature
High Pressure of Outdoor Unit
Low Pressure of Outdoor Unit
Outdoor Unit Inverter Compressor CT Sensor Fault
Outdoor Unit Inverter Compressor Discharge Temperature Sensor Fault
Outdoor Unit Low Pressure Sensor Fault
Outdoor Unit High Pressure Sensor Fault
Outdoor Unit Air Temperature Sensor Fault
Outdoor Unit Heat Exchanger Temperature Sensor Fault
Outdoor Unit Suction Temperature Sensor Fault
Omitting connection of R, S, T power of Outdoor unit
Excessive capacity of indoor units
Communication error : inverter PCB Main PCB
Communication error : indoor unit main PCB of outdoor unit
Reverse connection of R, S, T power of Outdoor unit
Inverter PCB EEPROM Error of Outdoor Unit
Communication error : inverter PCB Main PCB
Outdoor Unit Fan Lock
Outdoor Unit Inverter DC link High Voltage
Outdoor Unit Inverter Compressor Over Current
Display Title Cause of Error
321
331
341
351
401
411
421
431
441
451
461
501
511
521
531
541
561
571
671
Outdoor unit related error
281
291
ENGLISH
Installation Manual 55
Test Run
Outdoor Unit R-T Phase Difference is over 5A
Outdoor Unit Fan CT Sensor open or short
Outdoor Unit Fan DC Link High Voltage Error
Outdoor Unit Fan Current is over 5A
Outdoor Unit Fan First Position Sensing Failure
Communication Fail Between Outdoor Unit Main MICOM and EEPROM or omitting EEPROM
Communication Fail Between Outdoor Unit Fan MICOM and EEPROM or omitting EEPROM
Failing to receive fan signal at main PCB of unit.
Instant Over Current at Outdoor Unit Fan IPM
Outdoor Unit Fan DC Link Input Voltage is under 380V
Liquid pipe temperature sensor of outdoor unit is open or short
Outdoor Unit Subcooling Inlet Temperature Sensor open or short
Outdoor Unit Subcooling Outlet Temperature Sensor open or short
Pressure unbalance in Outdoor Units
Outdoor Unit Fan Inverter PCB Temperature is Over 95°C
Outdoor Unit Fan PCB Heat Sink Temperature Sensor open or short
Outdoor Unit 3 Phase Power unbalance
Outdoor Unit Fan CT Sensor Error
Outdoor Unit Fan DC Link High Voltage Error
Outdoor Unit Fan Over Current Error
Outdoor Unit Fan Start Failure Error
Outdoor Unit Main PCB EEPROM Error
Outdoor Unit Fan PCB EEPROM Error
Outdoor Unit Fan PCB Communication Error
Outdoor Unit FAN IPM Fault Error
Outdoor Unit Fan DC Link Low Voltage Error
Outdoor Unit Liquid pipe Temperature Sensor Error
Outdoor Unit Subcooling Inlet Temperature Sensor Error
Outdoor Unit Subcooling Outlet Temperature Sensor Error
Failure of operation mode conver­sion at Outdoor Unit
Excessive increase of Outdoor Unit Fan PCB Heat Sink Temperature
Outdoor Unit Fan PCB Heat Sink Temperature Sensor Error
Display Title Cause of Error
871
861
105
106
107
113
114
151
115
193
194
Outdoor unit related error
741
751
761
771
791
56 Outdoor Unit
Caution For Refrigerant Leak
The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.
Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should be large to such an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room.
n Limiting concentration
Check limiting concentration along following steps and take appropriate measure depending on the situation.
n Calculate amount of all the replenished refrigerant (kg) per each refrigerant
system.
n Calculate minimum room capacity
Calculate room capacity by regarding a portion as one room or the smaller room.
(1) Without partition
(2) With partition and with opening which serve as
passage of air to adjoining room
Caution For Refrigerant Leak
Introduction
Checking procedure of limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken with­out hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the unit of kg/m
3
(Freon gas weight per unit air volume) for facilitating calculation.
Limiting concentration: 0.44kg/m
3
(R410A)
Outdoor unit
(No.1 system)
Flow of refrigerant
Indoor unit
Room where refrigerant leaks (Refrigerant of the whole No.1 system flows out.)
Amount of additional replenished refrigerant
Total amount of replenished refrigerant in refrigerant facility (kg)
+
=
Note : In case one refrigerant facility is
divided into 2 or more refrigerant systems and each system is independent, amount of replenished refrigerant of each system shall be adopted.
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Opening
Partition
In the case of opening without door , or 0.15 % or more openings (to floor space) both above and below door)
Amount of replenished refrigerant per one outdoor unit system
Amount of replenished refrigerant at factory shipment
Amount of additionally replenished refrigerant depending on piping length or piping diameter at customer
ENGLISH
Installation Manual 57
Caution For Refrigerant Leak
(3) With partition and without opening which serve as passage of air to adjoining room
n Calculate refrigerant concentration
n In case the concentration exceeds the limit
When the concentration exceeds the limit, change original plan or take one of the countermeasures shown below:
• Countermeasure 1
Provide opening for ventilation. Provide 0.15% or more opening to floor space both above and below door, or provide opening without door.
• Countermeasure 2
Provide gas leak alarm linked with mechanical ventilator. Reducing the outdoor refrigerant qty.
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air.
Outdoor unit
Indoor unit
Smallest room
(R410A)
=
Refrigerant concentration
(kg/m
3
)
Total amount of replenished refrigerant in refrigerant facility (kg)
Capacity of smallest room where indoor unit is installed (m
3
)
In case the result of calculation exceeds the limiting concentration, perform the same calculations by shifting to the second smallest, and the third smallest rooms until at last the result is below the limiting concentration.
Countermeasure 2
Gas leak alarm
Mechanical ventilator
Countermeasure 1
Opening effective to ventilation
Indoor unit
58 Outdoor Unit
Installation guide at the seaside
Installation guide at the seaside
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are pro­duced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc­tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
CAUTION
2.1 Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
2) Select a well-drained place.
Sea wind Sea wind
h 1. If you canʼt meet above guide line in the seaside installation, please contact LG Electronics for the addi-
tional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by
using water.
CAUTION:
Multi V Space should be installed in the special outdoor room with soundproofing walls.
Loading...