LG ARUN260LLS5 INSTALLATION MANUAL

Page 1
INSTALLATION MANUAL
AIR CONDITIONER
www.lg.com
Copyright © 2018 - 2019 LG Electronics Inc. All Rights Reserved.
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Heat Pump Or
iginal instruction
MFL71320401
Rev.00_020819
ENGLISH
ESPAÑOL
PORTUGUÊS
BAHASA INDONESIA
Page 2
2
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock or fire may result.
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage,
electric shock, or fire.
• Always ground the product.
- There is risk of fire or electric shock.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Do not store or use flammable gas or combustibles near the air conditioner.
- There is risk of fire or failure of product.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Prepare for strong wind or earthquake and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in
injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• When installing and moving the air conditioner to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant,
the refrigerant cycle may malfunction and the unit may be damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
• Ventilate before operating air conditioner when gas leaked out.
- It may cause explosion, fire, and burn.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed securely, dust or water may
enter the outdoor unit and fire or electric shock may result.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
- Consult the dealer regarding the appropriate measures to prevent
the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
Operation
• Do not damage or use an unspecified power cord.
- There is risk of fire, electric shock, explosion, or injury.
• Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Do not touch the power switch with wet hands.
- There is risk of fire, electric shock, explosion, or injury.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious not to touch the sharp edges when installing.
- It may cause injury.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
!
!
!
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Page 3
3
• Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion
may result.
• Use power cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a
fire.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Keep the unit away from children. The heat exchanger is very sharp.
- It can cause the injury, such as cutting the finger. Also the
damaged fin may result in degradation of capacity.
• When installting the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency
medical equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the product where it is exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on
the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operation
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the
performance of the air conditioner or damage its parts.
• Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
• Make the connections securely so that the outside force of the cable may not be applied to the terminals.
- Inadequate connection and fastening may generate heat and
cause a fire.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing
property damage, product failure, or personal injury.
• Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
- A bad connection may cause water leakage.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your
fingers.
- When transporting the outdoor unit, suspending it at the specified positions on the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
• Turn on the power at least 6 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
• Do not touch any of the refrigerant piping during and after operation.
- It can cause a burn or frostbite.
• Do not operate the air conditioner with the panels or guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not directly turn off the main power switch after stopping operation.
- Wait at least 5 minutes before turning off the main power switch.
Otherwise it may result in water leakage or other problems.
• Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the indoor unit PCB.
• Use a firm stool or ladder when cleaning or maintaining the air conditioner.
- Be careful and avoid personal injury.
• Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
- There are sharp and moving parts that could cause personal injury.
• Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
!
ENGLISH
Page 4
4
ENGLISH
31 Auto Dust Removal Mode
31 Compressor Max. Frequency Limit
31 ODU Fan Max. RPM Limit
32 SLC (Smart Load Control)
32 Humidity Reference
32 Central Control Connection at Indoor Unit side
32 Compressor Input Current Limit
33 Power Consumption Display on wired remote controller
33 Overall Defrost Operating in Low temperature (Heating)
33 Base pan Heater operation
33 Comfort Cooling operation
34 Self-Diagnosis Function
37 CAUTION FOR REFRIGERANT LEAK
37 Introduction
37 Checking procedure of limiting concentration
38 INSTALLATION GUIDE AT THE SEASIDE
38 Model Designation
38 Airborne Noise Emission
2 TIPS FOR SAVING ENERGY 2 IMPORTANT SAFETY INSTRUCTIONS 5 INSTALLATION PROCESS 5 OUTDOOR UNITS INFORMATION 5 ALTERNATIVE REFRIGERANT R410A 6 SELECT THE BEST LOCATION 6 INSTALLATION SPACE
6 Individual Installation
7 LIFTING METHOD 8 INSTALLATION
8 The location of the Anchor bolts
8 Foundation for Installation
8 Preparation of Piping
10 Plumbing materials and storage methods
11 REFRIGERANT PIPING INSTALLATION
11 Precautions on Pipe connection / Valve operation
11 Connection of Outdoor units
11 Caution
12 PIPE CONNECTIONS BETWEEN INDOOR
AND OUTDOOR UNIT
12 Preparation Work
13 Pipe Drawing Out during Single / Series connection
13 Refrigerant piping system
14 Pipe Connection Method between outdoor unit/indoor unit
16 Branch pipe Fitting
18 Distribution Method
18 Vacuum Mode
18 Leak Test and Vacuum drying
19 Refrigerant charging
20 Thermal insulation of refrigerant piping
21 ELECTRICAL WIRING
21 Caution
23 Control box and connecting position of wiring
23 Communication and Power Cables
24 Wiring of main power supply and equipment capacity
24 Field Wiring
26 Checking the setting of outdoor units
27 Automatic Addressing
27 The Procedure of Automatic Addressing
28 Cool & Heat selector
29 High Static Pressure Compensation mode
29 Night Low Noise Function
29 Overall defrost mode
29 Setting the ODU address
30 Snow removal & rapid defrost
30 Setting Capacity Up Airflow Adjusting for IDU (Heating)
30 Target pressure adjusting
30 Low Ambient Kit
31 High Efficiency Mode (Cooling Operation)
TABLE OF CONTENTS
Page 5
5
ENGLISH
ALTERNATIVE REFRIGERANT R410A
The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should also be considered during the installation. R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0.
CAUTION
!
• The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrants such change.
• The thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8 MPa (551.1 psi).
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)
CAUTION
!
Notes : * We can guarantee the operation only within 130 %
combination. If you want to connect more than 130 % combination, please contact us and discuss the requirement like below.
• If the operation of indoor unit is more than 130 %, the airflow will be operated as low in the all indoor units.
Combination Ratio(50~200%)
Outdoor Number Connection Ratio
Single outdoor units 200 %
Double outdoor units 160 %
Triple outdoor units 130 %
Over the triple unit 130 %
CAUTION
!
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8 MPa [551.1psi]
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
OUTDOOR UNITS INFORMATION
The foundation must be level even
Outdoor unit foundation work
Avoid short circuits and ensure sufficient space is allowed for service
Installation of outdoor unit
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24hours at 3.8MPa (38.7 kgf/cm
2
)[551.1psi]
there must be no drop in pressure.
Airtight test
Multiple core cable must not be used. (suitable cable should be selected)
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness, cleanness and tightness
Refrigerant piping work
Check model name to make sure the fitting is made correctly
Installation of indoor unit
Take account of gradient of drain piping
Sleeve and insert work
Make connection clearly between outdoor, indoor, remote controller and option.
Preparation of contract drawings
Indicate clearly who will be responsible for switch setting.
Determination of division work
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Vacuum drying
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order
Transfer to customer with explanation
Preheat the crank case with the electrical heater for more than 6 hours.
INSTALLATION PROCESS
Page 6
6
ENGLISH
During the installation of the unit, consider service, inlet, and outlet acquire the minimum space as shown in the figures below. Side space should be more than 49 mm for operating of Auto Dust Removal mode.
Limitati
ons on
the
height
of the
wall
(Refer
to 4 side
walls)
h2
h1
1 500 (59)
Inlet side
A
B
50500
(19-11/16’’)(19-11/16’’)
500
(19-11/16’’)
Fron t
side
500
(19-11/16’’)
240 (9-1/2’’) or more
50 (2) or more
45° or
more
• The height of the wall on the front side must be 1 500 mm (59 inch) or less.
• The height of the wall on the inlet side must be 500 mm (19-11/16’’) or less.
• There is no limit to the wall on Inlet side.
• If the height of the walls on the front and Inlet side are higher than the limit, there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1 500 (59 inch)
- h2 = B(Actual height) - 500 (19-11/16’’)
Individual Installation
INSTALLATION SPACE
Category
Installation Space
Case 1
(10mm(13/32inch)Side
Space49mm(13/14inch))
Case 2
(Side Space
49mm(13/14inch))
4 sides
are
walls
A10 (13/32) B300 (11-13/16) C10 (13/32) D500 (19-11/16)
A50 (1-31/32) B100 (3-15/16) C50 (1-31/32) D500(19-11/16)
A10 (13/32) B300 (11-13/16) C10 (13/32) D500 (19-11/16) E20 (25/32)
A50 (1-31/32) B100 (3-15/16) C50 (1-31/32) D500 (19-11/16) E100 (3-15/16)
A10 (13/32) B300 (11-13/16) C10 (13/32) D500 (19-11/16) E20 (25/32) F600 (23-5/8)
A50 (1-31/32) B100 (3-15/16) C50 (1-31/32) D500 (19-11/16) E100 (3-15/16) F500 (19-11/16)
A10 (13/32) B300 (11-13/16) C10 (13/32) D300 (11-13/16) E20 (25/32) F500 (19-11/16)
A50 (1-31/32) B100 (3-15/16) C50 (1-31/32) D100 (3-15/16) E100 (3-15/16) F500 (19-11/16)
Rear
to
Rear
A10 (13/32) B500 (19-11/16) C10 (13/32) D500 (19-11/16) F900 (35-7/16)
A50 (1-31/32) B500 (19-11/16) C50 (1-31/32) D500 (19-11/16) F600 (23-5/8)
A10 (13/32) B500 (19-11/16) C10 (13/32) D500 (19-11/16) E20 (25/32) F1200 (47-1/4)
A50 (1-31/32) B500 (19-11/16) C50 (1-31/32) D500 (19-11/16) E100 (3-15/16) F900 (35-7/16)
A10 (13/32) B500 (19-11/16) C10 (13/32) D500 (19-11/16) E20 (25/32) F1 800 (70-7/8)
A50 (1-31/32) B500 (19-11/16) C50 (1-31/32) D500 (19-11/16) E100 (3-15/16) F1 200 (47-1/4)
Only 2
sides
are
walls
A10 (13/32) B300 (11-13/16)
A10 (13/32) B300 (11-13/16) E20 (25/32)
ac
b
d
aee c
b
d
aec
b
f
d
aec
b
f
d
ac
b
f
d
aec
b
f
d
aeec
b
f
d
a
b
aee
b
Front
Front
Front Front
Front Front
Front
Front
Front
Front Front
Front Front
Front Front Front
Front
Front
Front
Front Front
No limit for the height of wall
No limit for the height of wall
Front
SELECT THE BEST LOCATION
Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors due to noise of unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the outdoor unit.
• If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of
sunshine in case of installing the product at a place With a high humidity in winter (near beach, coast, lake, etc.) (Ex : Rooftop where there is always sunshine.)
Page 7
7
ENGLISH
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow areas or severe cold areas in winter so that product can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit In such a way that it should not come in contact with snow directly. If snow piles up and freezes on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Install the outdoor unit at the higher installation console by 50 cm (19.7 inch) than the average snowfall (annual average snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10 cm (3.9 inch), always remove snow for operation.
- The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the product. (If width of the frame is wider than that of the product, snow may accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
• When carrying the suspended, unit pass the ropes under the unit and use the two suspension points each at the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
LIFTING METHOD
CAUTION
!
Be very careful while carrying the product.
• Do not have only one person carry product if it is more than 20 kg (44 lbs).
• PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
• When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall.
• Use 2 belts of at least 8 m (26.2 ft) long.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
Hoist the unit making sure it is being lifted at its center of gravity.
Remove the Rear Grille
• Remove the rear grille in snowy area.
• Make sure that heat exchanger should not be damaged.
Locking points for
transportation ropes
Forklift Carrying Hole
UXA UXB
Rear Grille
Forklift Carrying Guide
Page 8
8
ENGLISH
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit support blocks at the bottom shall have width of at least 100 mm (3-15/16 inch) under the Unit’s legs before being fixed.
• The outdoor unit support blocks should have minimum height of 200 mm (7-7/8 inch).
• Anchor bolts must be inserted at least 75 mm (2-15/16 inch).
Chassis A [mm (inch)] B [mm (inch)]
UXA 930 (36-5/8) 730 (28-3/4) UXB 1 240 (47-1/4) 1 040 (40-15/16)
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200 mm (7-7/8 inch)).
At least 200 (7.87)
Unit : mm (inch)
200(7.87)
75(2.95)
75(2.95)
200(7.87)
100(3.94)
The corner part must be fixed firmly. Otherwise, the support for the
installation may be bent.
Get and use M10 Anchor bolt.Put Cushion Pad between the outdoor unit and ground support for
the vibration protection in wide area.
Space for pipes and wiring (Pipes and wirings for bottom side)H-beam supportConcrete support
CAUTION
!
• Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit Base panel before fixing the bolt. It may cause the unstable state of the outdoor settlement, and may cause freezing of the heat exchanger resulting in abnormal operations.
• Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit before welding. Not removing Pallet(Wood Support) causes hazard of fire during welding.
WARNING
!
• Install where it can sufficiently support the weight of the
outdoor unit. If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or
earthquake. If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the
ground, water outlet treatment(treatment of the water flowing out of the outdoor unit in operation), and the passages of the pipe and wiring, when making the ground support.
• Do not use tube or pipe for water outlet in the Base panel. Use
drainage instead for water outlet. The tube or pipe may freeze and the water may not be drained.
Pallet(Wood Support)
- Remove before Installation
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
- Use the accessory piping kit or the pipes purchased locally.
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5 m (4.92 ft) longer than the pipe length.
Preparation of Piping
Pipe
Reamer
Point down
Copper
tube
90°
Slanted Uneven Rough
Foundation for Installation
The location of the Anchor bolts
INSTALLATION
Outdoor units should not be supported only by the corner supports.
65
(2-9/16)
65
(2-9/16)
At least 100 mm
(3-15/16 inch)
At least 100 mm
(3-15/16 inch)
At least 100 mm
(3-15/16 inch)
At least 100 mm
(3-15/16 inch)
At least
65 (2-9/16)
At least
65 (2-9/16)
Unit : mm (inch)
731 (28-25/32)
At least 100 mm
(3-15/16 inch)
Center of the Unit
At least 100 mm
(3-15/16 inch)
Center of the Unit
760 (29-29/32)
Page 9
9
ENGLISH
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Flare shape and flare nut tightening torque
Opening shutoff valve
Precautions when connecting pipes
- See the following table for flare part machining dimensions.
- When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first. (Use ester oil or ether oil.)
-
See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
- After all the piping has been connected, use nitrogen to perform a gas leak check.
1 Remove the cap and turn the valve counter clockwise with the
hexagon wrench.
2 Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3 Make sure to tighten the cap securely.
Pipe size
[mm (inch)]
Tightening Torque
N.m (lbs.ft)
A [mm (inch)] Flare shape
Ø 9.52 (3/8) 38±4 (28±3.0) 12.8 (0.5)~13.2 (0.52)
Ø 12.7 (1/2) 55±6 (41±4.4) 16.2 (0.64)~16.6 (0.65)
Ø 15.88 (5/8) 75±7 (55±5.2) 19.3 (0.76)~19.7(0.78)
CAUTION
!
• Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks are present
.
• When loosening a flare nut, always use two wrenches in combination, When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare(inner and outer faces) with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as the initial tightening.
Union
Insulation of shutoff valve
1
Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120 °C [248 °F]).
2 Precautions in high humidity circumstance:
This air conditioner has been tested according to the "ISO Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere (dew point temperature: More than 23 °C [73.4 °F]), water drops are liable to fall. In this case, add heat insulation material according to the following procedure:
- Heat insulation material to be prepared: EPDM (Ethylene Propylene Diene Methylene)-over 120 °C [248 °F] the heat-resistance temperature.
- Add the insulation over 10 mm [0.39 inch] thickness at high
humidity environment.
Closing shutoff valve
1 Remove the cap and turn the valve clockwise with the hexagon
wrench.
2 Securely tighten the valve until the shaft contacts the main body seal.
3 Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
Shut
off
valve
size
(mm
(inch))
Tightening torque N.m (lbs.ft) (Turn clockwise to close)
Shaft
(valve body)
Cap
(Valve lid)
Service
port
Flare nut
Gas line
piping
attached
to unit
Closed Opened
Hexagonal
wrench
Ø 6.35
(1/4)
6.0±0.6
(4.4±0.4)
5.0±0.0
(3.7±0.4)
4 mm
(0.16 inch)
17.6±2.0
(13.0±1.5)
12.7±2
(9.4±1.5)
16±2
(12±1.5)
-
Ø 9.52
(3/8)
38±4
(28±3.0)
Ø 12.7
(1/2)
10.0±1.0 (7.4±0.7)
20.0±2.0
(14.8±1.5)
55±6
(41±4.4)
Ø 15.88
(5/8)
12.0±1.2 (8.9±0.9)
5 mm
(0.24 inch)
25.0±2.5
(18.4±1.8)
75±7
(55±5.1)
Ø 19.05
(3/4)
14.0±1.4
(10.3±1.0)
110±10
(81.1±7.4)
Ø 22.2
(7/8)
30.0±3.0
(22.1±2.2)
8 mm
(0.31 inch)
-
Ø 25.4
(1)
25±3
(18.5±2.2)
Flaring work
- Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the flared section and do flaring work again.
Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
Pipe diameter
Inch (mm)
A inch (mm)
Wing nut type Clutch type
Ø 1/4 (Ø 6.35)
0.04~0.07 (1.1~1.8) 0~0.02 (0~0.5)
Ø 3/8 (Ø 9.52) Ø 1/2 (Ø 12.7)
Ø 5/8 (Ø 15.88)
<Wing nut type> <Clutch type>
Bar
"A"
Copper pipe
±2
90°
45°
±2
A
R=0.4~0.8
Fastening band (accessory)
Refrigerant piping
Indoor unit
Thermal insulator (accessory)
Page 10
10
ENGLISH
Refrigerant piping on three principles
Drying Cleanliness Airtight
Should be no moisture
inside
No dust inside.
There is no refrigerant
leakage
Items
Moisture
Dust
Leakage
Cause failure
- Significant hydrolysis of refrigerant oil
- Degradation of refrigerant oil
- Poor insula’tion of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Degradation of refrigerant oil
- Poor insulation of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Gas shortages
- Degradation of refrigerant oil
- Poor insulation of the compressor
- Do not cold and warm
Counter
measure
-
No moisture in the pipe
- Until the connection is completed, the plumbing pipe entrance should be strictly controlled.
- Stop plumbing at rainy day.
- Pipe entrance should be taken side or bottom.
-
When removal burr after cutting pipe, pipe entrance should be taken down.
- Pipe entrance should be fitted cap when pass through the walls.
- No dust in the pipe.
- Until the connection is completed, the plumbing pipe entrance should be strictly controlled.
- Pipe entrance should be taken side or bottom.
- When removal burr after cutting pipe, pipe entrance should be taken down.
- Pipe entrance should be fitted cap when pass through the walls.
- Airtightness test should be.
- Brazing operations to comply with standards.
- Flare to comply with standards.
- Flange connections to comply with standards.
Nitrogen substitution method
Welding, as when heating without nitrogen substitution a large amount of the oxide film is formed on the internal piping.
The oxide film is a caused by clogging EEV, Capillary, oil hole of accumulator and suction hole of oil pump in compressor.
It prevents normal operation of the compressor. In order to avoid this problem, Welding should be done after replacing
air by nitrogen gas. When welding plumbing pipe, the work is required.
• Always use the nitrogen.(not use oxygen, carbon dioxide, and a Chevron gas): Please use the following nitrogen pressure 0.02 MPa (2.9 psi) Oxygen - Promotes oxidative degradation of refrigerant oil. Because it is flammable, it is strictly prohibited to use Carbon dioxide - Degrade the drying characteristics of gas Chevron Gas ­Toxic gas occurs when exposed to direct flame.
Always use a pressure reducing valve.
Please do not use commercially available antioxidant. The residual material seems to be the oxide scale is observed. In fact, due to the organic acids generated by oxidation of the alcohol contained in the anti-oxidants, ants nest corrosion occurs. (causes of organic acid alcohol + copper + water + temperature)
CAUTION
!
Regulator
Nitrogen gas Pressure 0.02 MPa (2.9 psi) less
Auxiliary valve
Taping (Should not contain air)
Welding Point
Note) should not block the outlet side. When the internal pressure in pipe is abo ve the atmospheric pressure, pinhole is occurred and it is a leakage cause.
Oxide scale
Nitrogen
Plumbing materials and storage methods
Pipe must be able to obtain the specified thickness and should be used with low impurities. Also when handling storage, pipe must be careful to prevent a fracture, deformity and wound. Should not be mixed with contaminations such as dust, moisture.
Page 11
11
ENGLISH
CAUTION
!
Please block the pipe knock outs of the front and side panels after installing the pipes. (Animals or foreign objects may be brought in to damage wires.)
WARNING
!
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas leakage after the work.
ABCD
IDU side connection pipeODU to ODU connection pipe (1st branch)ODU to ODU connection pipe (2st branch)ODU to ODU connection pipe (3rd brach)
2 Unit
3 Unit
4 Unit
ARCNN21
ARCNN31
ARCNN41
C
C
A
Outdoor units Model
Liquid Pipe Gas Pipe
I.D.15.88 I.D.15.88
I.D.15.88
I.D.19.05
I.D.12.7
I.D.12.7
I.D.9.52
331
83
70
314
I.D.22.2
O.D.19.05
O.D.12.7
I.D.9.52
334 281
I.D.15.88
I.D.19.05
I.D.19.05
I.D.12.7
83
I.D.22.2
334 281
I.D.15.88
I.D.19.05
I.D.19.05
I.D.12.7
83
I.D.22.2
C
C
I.D.28.58I.D.22.2O.D.19.05
O.D.22.2I.D.28.58I.D.31.8
I.D. 19.05O.D.15.88
I.D. 19.05O.D.15.88
I.D.22.2O.D.19.05
I.D.19.05O.D.15.88
I.D.19.05O.D.15.88
I.D.12.7
I.D.15.88
O.D.19.05
C
C
C
I.D.28.58
O.D.22.2
125
I.D.41.3
O.D.34.9
111
130
416 408
I.D.28.58 I.D.28.58
I.D.34.9
I.D.41.3 I.D.38.1
O.D.34.9
I.D.31.8
I.D.22.2
I.D.28.58
341
111
298
I.D.34.9
I.D.41.3
I.D.28.58
134
415 375
I.D.44.48 I.D.53.98
I.D.41.3
I.D.28.58
I.D.34.9O.D. 28.58I.D.22.2
I.D.34.9O.D.28.58I.D.22.2
I.D.34.9O.D.28.58I.D.22.2
I.D.53.98I.D.44.5O.D.41.3
I.D.34.9O.D.28.58I.D.22.2
O.D.41.3I.D. 44.5I.D.53.98
O.D.34.9
I.D.28.58
2, 3, 4 Outdoor Units
For more information, refer accessory installation manual.
Y branch
A
B
To outdoor unit To branch piping or indoor unit
A B
Viewed from point A in direction of arrow
Within +/- 10
2 Commercially available piping often contains dust and other
materials. Always blow it clean with a dry inert gas.
3 Use care to prevent dust, water or other contaminants from entering
the piping during installation.
4 Reduce the number of bending portions as much as possible, and
make bending radius as big as possible.
5 Always use the branch piping set shown below, which are sold
separately.
Caution
1 Use the following materials for refrigerant piping.
- Material: Seamless phosphorous deoxidized copper pipe
- Wall thickness : Comply with the relevant local and national regulations for the designed pressure 3.8 MPa (551 psi). We recommend the following table as the minimum wall thickness.
Outer diameter
[mm(inch)]
6.35 (1/4)
9.52 (3/8)
12.7 (1/2)
15.88 (5/8)
19.05 (3/4)
22.2 (7/8)
25.4 (1)
28.58
(1-1/8)
31.8
(1-1/4)
34.9
(1-3/8)
38.1
(1-1/2)
41.3
(1-5/8)
44.45
(1-3/4)
53.98
(2-1/8)
Minimum thickness
[mm(inch)]
0.8
(0.03)
0.8
(0.03)
0.8
(0.03)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
1.1
(0.04)
1.21
(0.05)
1.35
(0.05)
1.43
(0.06)
1.55
(0.06)
2.1
(0.08)
Y branch
Header
4 branches 7 branches 10 branches
ARBLB01621, ARBLB03321, ARBLB07121, ARBLB14521,
ARBLB23220
ARBL054 ARBL057 ARBL1010
ARBL104 ARBL107 ARBL2010
Connection of Outdoor units
When installing ODU series, refer below picture.
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the branching pipes, and the refrigerant pipe coming out of the outdoor unit is divided at the end to connect to each indoor unit. Flare connection for the indoor unit, and welding connection for the outdoor pipe and the branching parts.
- Use hexagonal wrench to open/close the valve.
REFRIGERANT PIPING INSTALLATION
Service Port
Liquid pipe
Gas pipe
AB
(Master)
(Slave1)
C
(Slave2)
(Slave3)
D
Page 12
12
ENGLISH
6 If the diameters of the branch piping of the designated refrigerant
piping differs, use a pipe cutter to cut the connecting section and then use an adapter for connecting different diameters to connect the piping.
7 Always observe the restrictions on the refrigerant piping (such as
rated length, difference in height, and piping diameter). Failure to do so can result in equipment failure or a decline in heating/cooling performance.
8 A second branch cannot be made after a header.
(These are shown by .)
To Outdoor Unit
Sealed Piping
A
A B
9 The Multi V will stop due to an abnormality like excessive or
insufficient refrigerant. At such a time, always properly charge the unit. When servicing, always check the notes concerning both the piping length and the amount of additional refrigerant.
10 Never perform a pump down. This will not only damage the
compressor but also deteriorate the performance.
11 Never use refrigerant to perform an air purge. Always evacuate air
by using a vacuum pump.
12 Always insulate the piping properly. Insufficient insulation will
result in a decline in heating/cooling performance, drip of condensate and other such problems.
13 When connecting the refrigerant piping, make sure the service
valves of the Outdoor Unit is completely closed (the factory setting) and do not operate it until the refrigerant piping for the Outdoor and Indoor Units has been connected, a refrigerant leakage test has been performed and the evacuation process has been completed.
14 Always use a non-oxidizing brazing material for brazing the parts
and do not use flux. If not, oxidized film can cause clogging or damage to the compressor unit and flux can harm the copper piping or refrigerant oil.
A
B
WARNING
!
When installing and moving the air conditioner to another site, be sure to make recharge refrigerant after perfect evacuation.
• If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
• After selecting diameter of the refrigerant pipe to suit total capacity of the indoor unit connected after branching, use an appropriate branch pipe set according to the pipe diameter of the indoor unit and the installation pipe drawing.
- Pipe connections can be done on the front side or on the side according to the installation environments.
- Be sure to let 0.2 kgf/cm
2
(2.8 psi) Nitrogen flow in the pipe when
welding.
- If Nitrogen was not flown during welding, many oxidized membranes may form inside the pipe and disturb the normal operations of valves and condensers.
Nitrogen Direction
Removal area for pipes
bottom side connections.
Knock Out for
communication cable
Knock Out for power supply cable
Knock Out for gas pipe
Knock Out for
Liquid pipe
CAUTION
!
• Do not give damage to the pipe/base during the Knock Out work.
• Proceed to pipe work after removing burr after Knock Out work.
• Perform sleeve work to prevent damage to the wire when connecting wires using Knock Outs.
Preparation Work
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or Bottom pipe drawing outs.
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Regulator
Valve
Nitrogen
Left Side
Pipe Draw
Out
Right Side Pipe Draw Out
Front Pipe Draw Out
Refrigerant Pipe
Nitrogen
Nitrogen Direction
Direction
Taping
Page 13
13
ENGLISH
Remove leakage prevention cap
• Remove the leakage prevention cap attached to the outdoor unit service valve before pipe work.
• Proceed the leakage prevention cap removal as follows:
- Verify whether all the pipes are locked.
- Extract remaining refrigerant or air inside using the service port.
- Remove the leakage prevention cap
Method of drawing out pipes on the bottom side
- Drawing out common pipe through side panel
Combination of Y branch/header Method
: Outdoor Unit: 1st branch (Y branch) : Y branch: Indoor Unit: Header: Sealed piping
h * : See Table 4
Header Method
: Outdoor Unit: Indoor Units: Sealed piping: Header
: Outdoor Unit: 1st branch (Y branch) : Indoor Units: Downward Indoor Unit: Connection branch
pipe between Outdoor units: ARCNN41
: Connection branch
pipe between Outdoor units : ARCNN31
: Connection branch
pipe between Outdoor units : ARCNN21
Y branch method
h * : See Table 4
Series Outdoor Units (2 Units ~ 4 Units)
Combination of Y branch/ header Method
: Outdoor Unit: 1st branch(Y branch): Y branch: Indoor Unit: Connection branch pipe
between Outdoor units : ARCNN41
: Connection branch pipe
between Outdoor units : ARCNN31
: Connection branch pipe
between Outdoor units : ARCNN21
: Header: Sealed piping
h * : See Table 4
Y branch method
: Outdoor Unit: 1st branch (Y branch) : Indoor Units
h * : See Table 4
Refrigerant piping system 1 Outdoor Units
Pipe Drawing Out during Single / Series connection
Method of drawing out pipes on the front side
- Proceed with the pipe work as shown in the below figure for front
side pipe drawing out.
Service Port
Liquid pipe
Gas pipe
Leakage Prevention Cap
H 110 m [361 ft]
H 110 m [361 ft]
L 150 m [492 ft] (200 m [656 ft])
l 40 m [131 ft] (90m [295 ft])
h 40 m [131 ft]
L 150 m [492 ft] (200 m [656 ft])
l 40 m [131 ft] (90m [295 ft])
Indoor Unit
h 40m(131ft)
Liquid pipe
Liquid pipe
Gas pipe
Gas pipe
H 110 m [361 ft]
h 40 m [131 ft]
L 200 m [656 ft]
l 40 m [131 ft]
D
Slave3
Slave2
10m or
less
G
F
E
H 110 m [361 ft]
Slave1
Master
C
h 40 m (131 ft)
ODU Capacity Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
L 150 m [492 ft] (200 m [656 ft])
l 40 m [131 ft] (90m [295 ft])
C
C
C
Indoor
Unit
C
Liquid pipe
Remove Knock Out for the pipes
Gas pipe
Slave3
Slave2
10m or
less
G
F
E
H 110 m [361 ft]
Slave1
Master
ODU Capacity Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
L 150 m [492 ft] (200 m [656 ft])
40 m [131 ft] (90m [295 ft]
l
H
I
h 40 m (131 ft)
Page 14
14
ENGLISH
Header Method
: Outdoor Unit: Header branch: Indoor Units: Sealed piping: Connection branch pipe
between Outdoor units : ARCNN41
: Connection branch pipe
between Outdoor units : ARCNN31
: Connection branch pipe
between Outdoor units : ARCNN21
Pipe Connection Method between outdoor unit/indoor unit
h See Table 2 A : Refrigerant pipe diameter from outdoor unit to first branch E : Refrigerant pipe diameter for outdoor unit capacity
(Slave 1+ Slave 2+ Slave 3)
F : Refrigerant pipe diameter for outdoor unit capacity
(Slave 2+ Slave 3)
G : Refrigerant pipe diameter for outdoor unit capacity(Slave 3)
Level Difference
(Outdoor unit Outdoor unit)
5 m [16.4 ft]
Max length from first branch to
each outdoor unit (L1, L2, L3)
Less than 10 m [32.8 ft]
(equivalent length of piping 13 m
[42.7 ft])
h * : See Table 4
WARNING
!
Increased Pipe Diameter(table 2)
- When pipe length is 90m [295 ft] or more from ODU to 1st branch
- When level difference is 50 m [164 ft] or more
WARNING
!
• Branch pipe can not be used after header.
• It is recommended that difference in length of the pipes connected to the indoor units (a~f) is minimized. Performance difference between indoor units may occur.
Y branch
Method
Combination of Y
branch/header
Method
Header
Method
Max pipe
length
Outdoor Unit
Indoor Unit
Longest
pipe
length(L)
A+B+C+D+e 150 m
[492 ft]
(200 m [656 ft] :
Conditional application)*
A+B+b 150 m [492 ft] A+C+e 150 m [492 ft]
(200 m [656 ft] :
Conditional application)*
A+f 200 m
[656 ft]
Equivalent
pipe length
175 m [574 ft]
(225 m [738 ft] :
Conditional application)*
175 m [574 ft]
(225 m [738 ft] :
Conditional application)*
225 m
[738 ft]
Total pipe
length
1000 m [3281 ft] 1000 m [3281 ft]
1000 m
[3281 ft]
Max
difference
in height
Outdoor Unit
Indoor Unit
Difference in
height(H)
110 m [361 ft] 110 m [361 ft] 110 m [361 ft]
Indoor Unit
Indoor Unit
Difference in
height(h)
40 m [131 ft] 40 m [131 ft] 40 m [131 ft]
Longest pipe
length after
1st branch
Pipe
length()
40 m [131 ft]
(90 m [295 ft] :
Conditional application)*
40 m [131 ft]
(90 m [295 ft] :
Conditional application)*
40 m [131 ft]
(Table 1) Limit Pipe length
(Table 2) Refrigerant pipe diameter from outdoor unit to first branch. (A)
ODU
capacity
(hp)
Pipe diameter when pipe
length is < 90 m (295 ft)
(Standard)
Pipe diameter when pipe length is 90 m (295 ft)
Pipe diameter when height
differential (ODUIDU) is
> 50 m (164 ft)
Liquid Pipe
mm (inch)
Gas Pipe
mm (inch)
Liquid Pipe
mm (inch)
Gas Pipe
mm (inch)
Liquid Pipe
mm (inch)
Gas Pipe
mm (inch)
8
Ø 9.52 (3/8) Ø 19.05 (3/4) Ø 12.7 (1/2) Ø 22.2 (7/8) Ø 12.7 (1/2) Not increased
10
Ø 9.52 (3/8) Ø 22.2 (7/8) Ø 12.7 (1/2)
Ø 28.58 (1-1/8)
Ø 12.7 (1/2) Not increased
12~16
Ø 12.7 (1/2)
Ø 28.58 (1-1/8)
Ø 15.88 (5/8)
Ø 34.9 (1-3/8)
Ø 15.88 (5/8) Not increased
18~22
Ø 15.88 (5/8)
Ø 28.58 (1-1/8)
Ø 19.05 (3/4)
Ø 34.9 (1-3/8)
Ø 19.05 (3/4) Not increased
24
Ø 15.88 (5/8)
Ø 34.9 (1-3/8)
Ø 19.05 (3/4)
Ø 41.3 (1-5/8)
Ø 19.05 (3/4) Not increased
26~34
Ø 19.05 (3/4)
Ø 34.9 (1-3/8)
Ø 22.2 (7/8)
Ø 41.3 (1-5/8)
Ø 22.2 (7/8) Not increased
36~60
Ø 19.05 (3/4)
Ø 41.3 (1-5/8)
Ø 22.2 (7/8)
Ø 44.5 (1-3/4)
Ø 22.2 (7/8) Not increased
62~64
Ø 22.2 (7/8)
Ø 44.5 (1-3/4)
Ø 25.4 (1)
Ø 53.98 (2-1/8)
Ø 25.4 (1) Not increased
66~104
Ø 22.2 (7/8)
Ø 53.98 (2-1/8)
Ø 25.4 (1)
Ø 53.98 (2-1/8)
Ø 25.4 (1) Not increased
(Table 3) Refrigerant pipe diameter from first branch to last branch (B,C,D)
Downward indoor unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
5.6(19 100)
Ø 6.35(1/4) Ø 12.7(1/2)
< 16.0 (54 600) Ø 9.52(3/8) Ø 15.88(5/8)
22.4 (76 400)
Ø 9.52(3/8) Ø 19.05(3/4) < 33.6 (114 700) Ø 9.52(3/8) Ø 22.2(7/8) < 50.4 (172 000) Ø 12.7(1/2) Ø 28.58(1-1/8) < 67.2 (229 400) Ø 15.88(5/8) Ø 28.58(1-1/8)
< 72.8(248 500) Ø 15.88(5/8) Ø 34.9(1-3/8) < 100.8(344 000) Ø 19.05(3/4) Ø 34.9(1-3/8) < 173.6(592 500) Ø 19.05(3/4) Ø 41.3(1-5/8) < 184.8(630 700) Ø 22.2(7/8) Ø 44.5(1-3/4)
224.0(764 400)
Ø 22.2(7/8) Ø 53.98(2-1/8)
(Table 4) Conditional Application
Condition Example
1
Diameter of pipes between first branch and the last branch should be increased by one step, except pipe diameter B,C,D is same as Diameter A
40 m [131 ft] <
B+C+D+e
90 m [295 ft] ’B, C, D
Change a diameter
2
While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice.
A+Bx2+Cx2+Dx2
+a+b+c+d+e
1 000 m [3 281 ft]
3
Length of pipe from each indoor unit to the closest branch
a,b,c,d,e≤40 m
[131 ft]
4
Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)] - [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] ≤40 m [131 ft]
(A+B+C+D+e)-
(A+a) 40 m
[131 ft]
• To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
Ø 6.35(1/4) Ø 9.52(3/8), Ø 9.52(3/8) Ø 12.7(1/2), Ø 12.7(1/2) Ø 15.88(5/8), Ø 15.88(5/8) Ø 19.05(3/4), Ø 19.05(3/4) Ø 22.2(7/8), Ø 22.2(7/8) Ø 25.4(1), Ø 25.4(1) Ø 28.58(1-1/8), Ø 28.58(1-1/8) Ø 31.8(1-1/4), Ø 31.8(1-1/4) Ø 34.9(1-3/8), Ø 34.9(1-3/8) Ø 38.1(1-1/2)
Master
L2
L3
Indoor
Unit
E GF
1st branch
l 40m (131ft)
Slave3
Slave2
Slave1
10m or
less
G
Slave1
H1
L1
Refrigerant pipe diameter from outdoor unit to first branch
Master
F
E
B
H 110 m [361 ft]
C
h 40 m (131 ft)
Slave2
C
ODU Capacity Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
L 200 m [656 ft]
l
40 m [131 ft]
D
CCC
C
Slave3
h 40 m (131 ft)
L
l
H 110 m [361 ft]
h 40 m [131 ft]
Indoor Unit
Page 15
15
ENGLISH
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe [mm(inch)]
5.6(19 100)
Ø 6.35(1/4) Ø 12.7(1/2) < 16.0(54 600) Ø 9.52(3/8) Ø 15.88(5/8) < 22.4(76 400) Ø 9.52(3/8) Ø 19.05(3/4) < 28.0(95 900) Ø 9.52(3/8) Ø 22.2(7/8)
WARNING
!
• In case of pipe diameter B connected after first branch is bigger than the main pipe diameter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio 120 % is connected to
24 HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø 34.9(1-3/8)(Gas pipe), Ø15.88(5/8)(liquid pipe)
2) Pipe diameter B after first branch according to 120 % indoor unit combination(80.6 kW) : Ø 34.9(1-3/8)(gas pipe), Ø 19.05(3/4)(liquid pipe)
Therefore, pipe diameter B connected after first branch would be Ø 34.9(1-3/8)(gas pipe) / Ø 15.88(5/8)(liquid pipe) which is same with main pipe diameter.
Pipe Connection Method/Precautions for Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between outdoor units.
- Please refer to the below connection examples to install pipe connections between outdoor units.
Pipe connection between outdoor units (General Case)
The maximum pipe length after the first branching between the outdoor units is 10 m [32.8 ft] or less
Pipes between outdoor units are 2 m [6.6 ft] or less
2 m [6.6 ft] or less
- If the distance between the outdoor units becomes more than 2 m [6.6 ft], apply Oil Traps between the gas pipes.
- If the outdoor unit is located lower than the main pipe, apply Oil Trap.
Pipes between outdoor units are 2 m [6.6 ft] or longer
Oil Trap
Oil Trap Oil Trap
2 m [6.6 ft] or less
2 m [6.6 ft] or less 2 m [6.6 ft] or less
0.2 m [0.66 ft]
2 m [6.6 ft] or longer
2 m [6.6 ft] or longer
2 m [6.6 ft] or longer
CAUTION
!
• Bending radius should be at least twice the diameter of the pipe.
• Bend pipe after 500 mm [19.7 inch] or more from branch(or header). Do not bend U type. It may affect performance or result in noise. If U type bending is required, the R should be more than 200 mm [7.9 inch]
Toward indoor unit
Toward indoor unit
Pipe inclination (2° or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
- Apply Oil Trap as shown below when the length of the pipe between the outdoor units is more than 2 m [6.6 ft]. Otherwise, the unit may not operate properly.
(Example 1)
Toward indoor unit
≤ 2m
Examples of Wrong Pipe Connections
If the main pipe is higher than the outdoor units, oil is accumulated in the outdoor unit.
Oil Trap
500 mm [19.7 inch]
or more
500 mm [19.7 inch]
or more
R
If there are differences in the height between the outdoor units, oil is accumulated in the lower outdoor unit.
Page 16
16
ENGLISH
Toward indoor unit
≤ 2 m [6.6 ft]
≥ 2 m [6.6 ft]
≥ 0.2 m [0.66 ft]
Oil Trap
(Example 2)
- When connecting the pipes between the outdoor units, the accumulation of oil in the slave outdoor unit should be avoided. Otherwise, the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
h
h
≥ 0.2 m [0.66 ft]
Toward indoor unit
Toward indoor unit
Oil Trap
(Example 3)
h
Toward indoor unit
(Example 2)
Y branch
A
B
Viewed from point A in direction of arrow
Horizontal plane
Within +/- 10°
A
To Outdoor UnitTo Branch Piping or Indoor Unit
• Ensure that the branch pipes are attached horizontally (see the diagram below.)
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
Branch pipe Fitting
• When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connection then cap pipes should be fitted to the surplus branches.
Header
A
B
To Outdoor UnitTo Indoor Unit
• The indoor unit having larger capacity must be installed closer to than smaller one.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter.
Pipe cutter
• When the number of pipes to be connected is smaller than the number of header branches, install a cap to the unconnected branches.
• Fit branch pipe lie in a horizontal plane.
Horizontal plane
View from point B in the direction of the arrow
Tape (field supply)
Insulator
(included with kit)
Liquid and gas pipe joints
Insulator for field piping
C
B
Pinched pipe
Page 17
17
ENGLISH
• Header should be insulated with the insulator in each kit.
• Joints between branch and pipe should be sealed with the tape included in each kit.
• Any cap pipe should be insulated using the insulator provided with each kit and then taped as described above.
Y branch pipe
Models Gas pipe Liquid pipe
ARBLN01621
I.D.19.05(3/4)
O.D.15.88(5/8)
I.D.12.7(1/2)
I.D.15.88(5/8)
I.D.15.88(5/8)
I.D.15.88(5/8)
I.D.12.7(1/2)
I.D.12.7(1/2)
292(11-1/2)
281(11-1/16)
74
(2-29/32)
70(2-3/4)
1
1
I.D.12.7(1/2)
292(11-1/2)
281(11-1/16)
74
(2-29/32)
70(2-3/4)
I.D.6.35(1/4)
I.D.6.35(1/4)
I.D.6.35(1/4)
1
1
I.D.9.52(3/8)
I.D.9.52(3/8)
I.D.9.52(3/8)
O.D.9.52(3/8)
ARBLN03321
413(16-1/4)
390(15-11/32)
I.D.19.05(3/4)
I.D.19.05(3/4)
I.D.19.05(3/4)
I.D.12.7(1/2)
I.D.12.7
(1/2)
70(2-3/4)
I.D.15.88(5/8)
I.D.15.88(5/8)
I.D.25.4(1)
I.D.25.4(1)
O.D.25.4(1)
80(3-5/32)
110(4-11/32)
83
(3-9/32)
1
2
3
3
O.D.19.05(3/4)
O.D.19.05(3/4)
1 2
I.D.22.2(7/8)
I.D.22.2(7/8)
I.D.22.2(7/8)
I.D.28.58(1-1/8)
I.D.6.35(1/4)
I.D.12.7(1/2)
I.D.12.7(1/2)
I.D.12.7(1/2)
74
(2-29/32)
332(13-1/16)
321(12-5/8)
I.D.6.35(1/4)
I.D.9.52(3/8)
I.D.9.52(3/8)
I.D.9.52(3/8)
I.D.6.35(1/4)I.D.6.35(1/4)
ARBLN07121
I.D.12.7
(1/2)
376(14-13/16)
404(15-29/32)
120(4-23/32) 120(4-23/32)
90(3-17/32)
I.D.15.88(5/8)
I.D.15.88(5/8)
2
3
1
2
1 3
I.D.19.05(3/4)
I.D.19.05(3/4)
O.D.19.05(3/4)
96
(3-25/32)
I.D.22.2(7/8)
I.D.22.2(7/8)
O.D.22.2(7/8)
I.D.34.9(1-3/8)
I.D.28.58(1-1/8)
I.D.28.58(1-1/8)
I.D.28.58(1-1/8)
O.D.31.8(1-1/4)
I.D.31.8(1-1/4)
I.D.31.8(1-1/4)
I.D.6.35(1/4)
I.D.15.88(5/8)
I.D.15.88(5/8)
I.D.15.88(5/8)
I.D.12.7(1/2)
I.D.12.7(1/2)
I.D.12.7(1/2)
O.D.12.7(1/2)
O.D.12.7(1/2)
70(2-3/4)
110(4-11/32)
371(14-19/32)
394(15-1/2)
83
(3-9/32)
2
3
3
I.D.19.05(3/4)
I.D.19.05(3/4)
I.D.19.05(3/4)
2
I.D.6.35(1/4)
I.D.9.52(3/8)
I.D.9.52(3/8)
I.D.6.35(1/4)
ARBLN14521
I.D.12.7(1/2)
70(2-3/4)
471(18-17/32)
517(20-11/32)
125
(4-29/32)
130(5-1/8)
I.D.15.88(5/8)
I.D.41.3(1-5/8)
I.D.41.3 (1-5/8)
I.D.41.3(1-5/8)
I.D.38.1(1-1/2)
I.D.38.1(1-1/2)
I.D.38.1(1-1/2)
O.D.38.1(1-1/2)
O.D.15.88(5/8)
2
3
3
2
2
3
3
120(4-23/32)
120(4-23/32)
90(3-17/32)
I.D.19.05(3/4)
I.D.19.05(3/4)
I.D.22.2(7/8)
I.D.22.2(7/8)
O.D.22.2(7/8)
I.D.34.9(1-3/8)
I.D.34.9(1-3/8)
I.D.34.9(1-3/8)
O.D.34.9(1-3/8)
I.D.28.58(1-1/8)
O.D.28.58(1-1/8)
I.D.28.58(1-1/8)
I.D.6.35(1/4)
I.D.12.7(1/2)
O.D.12.7(1/2)
I.D.12.7
(1/2)
110(4-11/32)110(4-11/32)
416(16-3/8)
444(17-15/32)
O.D.15.88(5/8)
I.D.15.88(5/8)
I.D.19.05(3/4)
I.D.15.88(5/8)
I.D.15.88(5/8)
I.D.19.05(3/4)
I.D.19.05(3/4)
O.D.19.05(3/4)
80(3-5/32)
2
3
1
2 3 3
96
(3-25/32)
I.D.22.2(7/8)
I.D.22.2(7/8)
I.D.22.2(7/8)
I.D.6.35(1/4)
I.D.9.52(3/8)
I.D.9.52(3/8)
I.D.6.35(1/4)
ARBLN23220
O.D.28.58(1-1/8)
I.D.22.2(7/8)
115(4-17/32)
X2
100(4-11/32)
O.D.15.88(5/8)
I.D.12.7(1/2)
70(2-3/4)
O.D.22.2(7/8)
I.D.15.88(5/8)
I.D.19.05(3/4)
120(4-23/32)
O.D.38.1(1-1/2)
I.D.34.9(1-3/8)
I.D.28.58(1-1/8)
O.D.44.48(1-3/4)
X2
175(6-7/8)
I.D.31.8(1-1/4)
I.D.53.98(2-1/4)
I.D.25.4(1)
I.D.44.48(1-3/4)
I.D.44.48(1-3/4)
I.D.38.1(1-1/2)I.D.41.3(1-5/8)
I.D.44.48(1-3/4)
I.D.38.1(1-1/2)
I.D.41.3(1-5/8)
I.D.53.98(2-1/4)
420(16-17/32)
490(19-9/32)
134
1
2
3
32
3 3
3
3
2
I.D.6.35(1/4)
O.D.19.05(3/4)
O.D.12.7(1/2)
I.D.15.88(5/8)
O.D.12.7(1/2) I.D.6.35(1/4)
I.D.9.52(3/8)
X2
110(4-11/32) 110(4-11/32)
I.D.25.4(1)
I.D.22.2(7/8)
I.D.19.05(3/4)
I.D.19.05(3/4)I.D.22.2(7/8)
I.D.25.4(1)
I.D.25.4(1)
I.D.22.2(7/8)
346(13-5/8)
379(14-29/32)
96(3-25/32)
2
3 32
3
I.D.6.35(1/4)
[Unit:mm(inch)]
[Unit:mm(inch)]
Header
Models Gas pipe Liquid pipe
4 branch
ARBL054
120
150
360
120
ID15.88
ID12.7
ID12.7
ID15.88
ID15.88
ID19.05
120(4-23/32)
360(14-5/32)
ID9.52(3/8)ID9.52(3/8)ID9.52(3/8)
ID9.52(3/8)
ID6.35(1/4)
ID6.35(1/4)
ID9.52(3/8)
ID12.7(1/2)
150 (5-29/32)
120 (4-23/32)
7 branch
ARBL057
540
120
150
120
ID15.88
ID12.7
ID15.88
ID12.7
ID15.88
ID19.05
540(21-1/4)
ID9.52(3/8)
150 (5-29/32)
120 (4-23/32)
120(4-23/32)
ID6.35(1/4)
ID9.52(3/8)
ID9.52(3/8)
ID12.7(1/2)
4 branch
ARBL104
120
150
400
160
ID15.88
ID12.7
ID19.05
ID15.88
ID22.2
ID28.58ID25.4
ID9.52(3/8)
150 (5-29/32)
120(4-23/32)
120 (4-23/32)
360(14-5/32)
ID9.52(3/8)ID9.52(3/8)ID9.52(3/8)
ID9.52(3/8)
ID6.35(1/4)
ID6.35(1/4)
ID9.52(3/8)
ID12.7(1/2)
7 branch
ARBL107
120
150
160
580
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
ID9.52(3/8)
120 (4-23/32)
700(27-9/16)
120(4-23/32)
ID6.35(1/4)
ID9.52(3/8)
ID9.52(3/8)ID9.52(3/8)
ID6.35(1/4)ID6.35(1/4)
ID9.52(3/8)
ID6.35(1/4)
ID9.52(3/8)ID12.7(1/2)
150 (5-29/32)
ID9.52(3/8)
10 branch
ARBL1010
120
150
160
760
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
ID9.52(3/8)
120 (4-23/32)
120(4-23/32)
720(28-11/32)
ID6.35(1/4)
ID9.52(3/8)
ID9.52ID9.52 (3/8)(3/8)
ID9.52 (3/8)
ID6.35(1/4)
ID12.7(1/2)
ID9.52(3/8)
150 (5-29/32)
ID9.52(3/8)
10 branch
ARBL2010
120
150
182
775
ID19.05
ID15.88
ID15.88
ID12.7
ID28.58
ID31.8 ID34.9
ID9.52(3/8)
120 (4-23/32)
ID9.52(3/8)
ID6.35(1/4)
ID9.52 (3/8)
107(4-7/32)
60*9=540(21-1/2)
700(27-9/16)
ID6.35(1/4)
ID9.52(3/8)
ID19.05(3/4)
ID15.88(5/8)
ID9.52 (3/8)
ID6.35 (1/4)
ID9.52 (3/8)
ID6.35 (1/4)
150 (5-29/32)
ID9.52(3/8)
Insulate the header using the insulation material attached to the branch pipe kit as shown in the figure.
Tape
Insulator
Insulator of field pipe
Insulator for cap pipe
Cap pipe
Tape
Page 18
18
ENGLISH
- Ensure that the branch pipes are attached vertically.
Slave
Master
Header
Slave
Master
Slave
Master
Slave
Master
Vertical Distribution
The others
Leak test Leak test should be made by pressurizing nitrogen gas to 3.8 MPa(38.7
kgf/cm
2
). If the pressure does not drop for 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method, refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid pipe, gas pipe and high pressure gas pipe)
The test result can be judged good if the pressure has not be reduced after leaving for about one day after completion of nitrogen gas pressurization.
Leak Test and Vacuum drying
Indoor unit
Nitrogen gas cylinder
Slave 1 outdoor unit Master outdoor unit
Liquide pipe
Gas pipe
Liquide pipe
Gas pipe
Liquid side
Gas side
Close
Close
Close
Close
When inserting nitrogen gas of high pressure, it must be used with regulator.
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement or IDU addition/replacement.
Vacuum mode setting method
SW01C (Ɨ: Confirm / Automatic Addressing)
SW02C (ȭ: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW01D (reset)
SW03C (ȯ: forward)
Vacuum mode off method
CAUTION
!
ODU operation stops during vacuum mode. Compressor can't operate.
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“SVC” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Se3” Push the ‘’ button
Start the vacuum mode : “VACC”
ODU Valve open
ODU EEV open
IDU EEV open
HR unit valve open, SC EEV open
DIP switch off and push the reset button on Master unit PCB
Vacuum Mode
Slave
Master
Slave
Master
1st
1st
1st
Main pipe
Distribution
2nd
2nd
3rd
3rd
Main pipe
Distribution
Slave
Master
1st
3rd
3rd main pipe distribution
2nd
Horizontal Distribution
Distribution Method
Page 19
19
ENGLISH
WARNING
!
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
CAUTION
!
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must be at higher position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
Vacuum Drying Vacuum drying should be made from the service port provided on the outdoor
unit’s service valve to the vacuum pump commonly used for liquid pipe, gas pipe and high/low pressure common pipe. (Make Vacuum from liquid pipe, gas pipe and high/low pressure common pipe with the service valve closed.) * Never perform air purging using refrigerant.
• Vacuum drying: Use a vacuum pump that can evacuate to -100.7 kPa (-14.6 psi, 5 Torr, -755 mmHg).
- Evacuate the system from the liquid and gas pipes with a vacuum
pump for over 2 hrs and bring the system to -100.7 kPa(-14.6 psi). After maintaining system under that condition for over 1 hr, confirm the vacuum gauge rises. The system may contain moisture or leak.
- Following should be executed if there is a possibility of moisture
remaining inside the pipe. (Rainwater may enter the pipe during work in the rainy season or over a long period of time) After evacuating the system for 2 hrs, give pressure to the system to 0.05 MPa(7.3 psi) (vacuum break) with nitrogen gas and then evacuate it again with the vacuum pump for 1hr to -100.7 kPa(-14.6 psi)(vacuum drying). If the system cannot be evacuated to -100.7 kPa(-14.6 psi) within 2 hrs, repeat the steps of vacuum break and its drying. Finally, check if the vacuum gauge does not rise or not, after maintaining the system in vacuum for 1 hr.
NOTE
!
Always add an appropriate amount of refrigerant. (For the refrigerant additional charge) Too much or too little refrigerant will cause trouble. To use the Vacuum Mode (If the Vacuum mode is set, all valves of Indoor units and Outdoor units will be opened.)
WARNING
!
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
WARNING
!
When installing and moving the air conditioner to another site, recharge after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
Scale Use a graviometer. (One that can measure down to 0.1 kg). If you are unable to prepare such a high-precision gravimeter you may use a charge cylinder.
Indoor unit
Slave 1 outdoor unit Master outdoor unit
Liquide pipe
Gas pipe
Liquide pipe
Gas pipe
Liquid side
Gas side
Close
Close
Close
Close
Vacuum pump
NOTE
!
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is checked, apply the following correction factor
There is a pressure change of approximately 0.01 Mpa(1.5 psi) for each
33.8 °F (1°C) of temperature difference. Correction= (Temp. at the time of pressurization – Temp. at the time of
check) X 0.1 For example: Temperature at the time of pressurization
3.8 MPa(551 psi) is 80.6°F (27 °C) 24 hour later: 3.73 MPa(541 psi), 68 °F (20 °C) In this case the pressure drop of 0.07 MPa (10 psi) is because of temperature drop And hence there is no leakage in pipe occurred.
Heat Pump System Installation
Manifold GaugeLow Pressure Side HandleHigh Pressure Side Handle
WARNING
!
• Pipe to be vacuumed : gas pipe, liquid pipe
• If the refrigerant amount is not exact, it may not operate
properly.
• If additionally bottled refrigerant amount is over 10 %, condenser
burst or insufficient indoor unit performance may be caused.
Refrigerant charging
Liquid pipe
Gas pipe
Page 20
20
ENGLISH
The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correction Factor) value of indoor unit.
Total liquid pipe : Ø 25.4 mm (1.0 inch)
Additional charge(kg)
Total liquid pipe : Ø 22.2 mm (7/8 inch)
Total liquid pipe : Ø 19.05 mm (3/4 inch)
Total liquid pipe : Ø 15.88 mm (5/8 inch)
Total liquid pipe : Ø 12.7 mm (1/2 inch)
Total liquid pipe : Ø 9.52 mm (3/8 inch)
Total liquid pipe : Ø 6.35 mm (1/4 inch)
CF value of indoor unit
=
+
+
+
+
+
+
× 0.480 kg/m (0.323 lbs/ft)
× 0.354 kg/m (0.238 lbs/ft)
× 0.266 kg/m (0.179 lbs/ft)
× 0.173 kg/m (0.116 lbs/ft)
× 0.118 kg/m (0.079 lbs/ft)
× 0.061 kg/m (0.041 lbs/ft)
× 0.022 kg/m (0.015 lbs/ft)
Amount refrigerant of Indoor units Example) 4Way Ceiling Cassette 14.5 kW -1 ea, Ceiling concealed
Duct 7.3 kW-2 ea, Wall Mounted 2.3 kW-4 ea CF = [0.64 kg (1.411 lbs)×1EA] + [0.26 kg (0.573
lbs)×2EA] + [0.26 kg (0.529 lbs)×4 EA] = 2.12 kg (4.67 lbs)
WARNING
!
• Regulation for refrigerant leakage : the amount of refrigerant leakage should satisfy the following equation for human safety.
If the above equation can not be satisfied, then follow the following steps.
• Selection of air conditioning system: select one of the next
- Installation of effective opening part
- Reconfirmation of Outdoor Unit capacity and piping length
- Reduction of the amount of refrigerant
- Installation of 2 or more security device (alarm for gas leakage)
• Change Indoor Unit type : I
nstallation position should be over 2 m (6.6 ft) from the floor (Wall
mounted type Cassette type)
• Adoption of ventilation system : Choose ordinary ventilation system or building ventilation
system
• Limitation in piping work : Prepare for earthquake and thermal stress
Volume of the room at which Indoor Unit of
the least capacity is installed
Total amount of refrigerant in the system
0.44 kg/m
3
(0.028 lbs/ft3)
Attach the additional refrigerant table of IDU.
Bad example
• Do not insulate gas or low pressure pipe and liquid or highpressure pipe together.
• Be sure to fully insulate connecting portion.
These parts are not insulated.
Liquid pipeGas pipePower lines
Finishing tape
Insulating material
Communication lines
A
C
D
E
B
F
A
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a possibility of condensation drip, etc. Pay special attention to insulation work to ceiling plenum.
Heat insulation materialPipe Outer covering(Wind the connection part and cutting part of heat
insulation material with a finishing tape.)
Heat insulation
material
Adhesive + Heat - resistant
polyethylene foam + Adhesive tape
Outer
covering
Indoor Vinyl tape
Floor
exposed
Water-proof hemp cloth +
Bronze asphalt
Outdoor
Water-proof hemp cloth +
Zinc plate + Oily paint
NOTE
!
When using polyethylene cover as covering material, asphalt roofing shall not be required.
Thermal insulation of refrigerant piping
Good example
Liquid pipeGas pipePower lines
Insulating material
Communication lines
Communication lines
Separation
Power lines
E
D
D
B
A
C
Page 21
21
ENGLISH
A
B
E
B
I
A
B
D
C
1 m
(3.28 ft)
1 m
(3.28 ft)
D
F
F
G
B
G
D
B
H
I
J
A
Penetrations
SleeveHeat insulating materialLaggingCaulking materialBandWaterproofing layerSleeve with edgeLagging materialMortar or other incombustible caulkingIncombustible heat insulation material
When filling a gap with mortar, cover the penetration part with steel plate so that the insulation material will not be caved in. For this part, use incombustible materials for both insulation and covering. (Vinyl covering should not be used.)
Inner wall (concealed) Outer wall Outer wall (exposed)
Floor (fireproofing)
Penetrating portion on fire
limit and boundary wall
Roof pipe shaft
Caution
- Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.
-
Install the Outdoor Unit communication cable away from the power
source wiring so that it is not affected by electric noise from the power source. (Do not run it through the same conduit.)
- Be sure to provide designated grounding work to Outdoor Unit.
- Give some allowance to wiring for electrical part box of Indoor and
Outdoor Units, because the box is sometimes removed at the time of service work.
- Never connect the main power source to terminal block of
communication cable. If connected, electrical parts will be burnt out.
- Use the 2-core shielded wires for communication cable.( mark in
the figure below) If communication cable of different systems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations. ( mark in the figure below)
- Only the communication cable specified should be connected to the
terminal block for Outdoor Unit communication.
CAUTION
!
Be sure to correct the outdoor unit to earth. Do not connect ground wire to any gas pipe, liquid pipe, lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
WARNING
!
Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with regulations and this installation manual. If power supply circuit has a lack of capacity or electric work deficiency, it may cause an electric shock or fire.
ELECTRICAL WIRING
2-core shielded cables
Remote control
Remote control
Remote control
Remote control
Indoor
Unit
Indoor
Unit
1Unit
Master
2Unit
Slave1
3Unit
Slave2
4Unit
Slave3
Master Slave1 Slave2 Slave3
Indoor
Unit
Indoor
Unit
Page 22
Master Slave
Master Slave
Master Slave1 Slave2
Master Slave1 Slave2
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Multi-Core Cable
Master Slave
Master Slave
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Remote control
Master Slave1 Slave2 Slave3
Master Slave1 Slave2 Slave3
Indoor
Unit
Indoor
Unit
Remote control
Remote control
Indoor
Unit
Indoor
Unit
22
ENGLISH
Master Slave1 Slave2
Master Slave1 Slave2
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
Remote control
Indoor
Unit
CAUTION
!
When the 400 volt power supply is applied to “N” phase by mistake, check damaged parts in control box and replace them.
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Round pressure terminal
Power cable
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
- When connecting cable which is the same thickness, do as shown in the figure below.
- For wiring, use the designated power cable and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may break them.
CAUTION
!
• Use the 2-core shielded wires for communication cables. Never use them together with power cables.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never install a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2 %. If it is greater the units lifespan will be reduced.
Page 23
23
ENGLISH
UXA
UXB
WARNING
!
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
NOTE
!
• The figures are based on assumed length of parallel cabling up to 100 m [328 ft]. For length in excess of 100 m [328 ft] the figures will have to be recalculated in direct proportion to the additional length of cable involved.
• If the power supply waveform continues to exhibit some distortion the recommended spacing in the table should be increased.
- If the cable are laid inside conduits then the following point must also be taken into account when grouping various cable together for introduction into the conduits
- Power cable(including power supply to air conditioner) and communication cables must not be laid inside the same
- In the same way, when grouping the power wires and communication cables should not be bunched together.
CAUTION
!
If apparatus is not properly earthed then there is always a risk of electric shock, the grounding of the apparatus must be carried out by a qualified person.
CAUTION
!
In case of using the shielded wires, it should be grounded.
Separation of communication and power cables
- If communication and power cables are installed alongside each other then there is a strong likelihood of operational faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic coupling. The tables below indicates our recommendation as to appropriate spacing of communication and power cables where these are to be run side by side
Communication and Power Cables
Communication cable
- Types : shielded wires or unshielded wires
- Cross section : 1.0 ~ 1.5 mm
2
(1.55 × 10-3~ 2.32 × 10-3in2)
- Maximum allowable temperature: 60 °C (140 °F)
- Maximum allowable cable length: under 1 000 m (3 281 ft)
Remote control cable
- Types : 3-core cables
Central control cable
Product type Cable type Diameter
ACP&AC Manager
2-core wires (shielded)
1.0 ~ 1.5 mm
2
(1.55 × 10-3~
2.32 × 10-3in2)
AC Smart
2-core wires (shielded)
1.0 ~ 1.5 mm
2
(1.55 × 10-3~
2.32 × 10-3in2)
Simple central controller
4-core wires (shielded)
1.0 ~ 1.5 mm
2
(1.55 × 10-3~
2.32 × 10-3in2)
AC Ez
4-core wires (shielded)
1.0 ~ 1.5 mm
2
(1.55 × 10-3~
2.32 × 10-3in2)
Current capacity of power cable Spacing
100 V or more
10 A 300 mm (11-13/16 inch) 50 A 500 mm (19-11/16 inch)
100 A 1 000 mm (39-3/8 inch)
Exceed 100 A 1 500 mm (59-1/16 inch)
Control box and connecting position of wiring
- Remove all of the screws at front panel and remove the panel by pulling it forward.
- Connect communication cable between main and sub outdoor unit through the terminal block.
- Connect communication cables between outdoor unit and indoor units through the terminal block.
- When the central control system is connected to the outdoor unit, a dedicated PCB must be connected between them.
- When connecting communication cable between outdoor unit and indoor units with shielded cable, connect the shield ground to the earth screw.
Front Panel
Main Board
External Board
Main power line
terminal block
(Take care of the phase
sequence of 3-phases
4-wires power system)
Page 24
24
ENGLISH
CAUTION
!
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.
WARNING
!
• Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.
• Make sure to use specified cables for connections so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Ground wire
1 The power wire Between the master outdoor unit and slave1
outdoor unit - minimum : 6 mm2[9.3 × 10-3inch2]
2 The power wire Between the slave1 outdoor unit and slave2
outdoor unit - minimum : 4 mm2[6.2 × 10-3inch2]
3 The power wire Between the slave2 outdoor unit and slave3
outdoor unit - minimum : 2.5 mm2[3.875 × 10-3inch2]
h The above standard is CV wire standard. h Please use the 3-phases 4-wires quadrupole Leakage circuit breaker
of circuit breaker.
The thickness of Minimum wire (mm2[ inch2])
Leakage
circuit breaker
(4P ELCB)
Main power
wire
Branch wire Ground wire
1 Unit
2.5~16
[3.875 × 10
-3
~2.48 × 10-2]
-
2.5~4
[3.875 × 10
-3
~6.2 × 10-3]
Below 20~60 A
100 mA 0.1 s
2 Unit
16~50
[2.48 × 10
-2
~7.75 × 10-2]
-
4~10
[6.2 × 10
-3
~1.55 × 10-2]
Below 75~150 A
100 mA 0.1 s
3 Unit
50~95
[7.75 × 10
-2
~1.4725 × 10-1]
-
10
[1.55 × 10-2]
Below 150~200 A
100 mA 0.1 s
4 Unit
95~120
[1.4725 × 10
-1
~1.86 × 10-1]
-
10~16
[1.55 × 10
-2
~2.48 × 10-2]
Below 200~250 A
100 mA 0.1 s
Field Wiring
Single outdoor unit
R S T N
Switch
Fuse
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(3 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Outdoor Unit]
[Indoor Units]
Outdoor
Power supply
(3Ø 4 wires)
Indoor
Power supply
(1Ø 2 wires)
(Main Switch)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Frequency
Voltage range(V)
Outdoor Indoor 60 Hz 380 V 220 V 50 Hz 380-415 V 220-240 V
Wiring of main power supply and equipment capacity
- Use a separate power supply for the Outdoor Unit and Indoor Unit.
- Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
- The cable size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10 %.
- Specific wiring requirements should adhere to the wiring regulations of the region.
- Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.
- Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
34 34 34
Master Outdoor Unit
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’ terminal for dry contact, it is not the point to make ground connection.
WARNING
!
• Indoor Unit ground wires are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor and other parts.
Series outdoor units
When the power source is connected
In series between the units.
R S T N
Switch
Fuse
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(3 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Master]
[Indoor Units]
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
[Slave1] [Slave2]
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Frequency
Voltage range(V)
Outdoor Indoor 60 Hz 380 V 220 V 50 Hz 380~415 V 220~240 V
Page 25
25
ENGLISH
Example) Connection of communication cable
[BUS type] [STAR type]
When the power source is supplied to Each outdoor unit individually.
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(3 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Master]
[Indoor Units]
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
[Slave1] [Slave2]
R S T N
Switch
Fuse
R S T N
Switch
Fuse
R S T N
Switch
Fuse
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Between Indoor and Master Outdoor unit The communication cables between indoor unit and master outdoor unit are possible to connect with BUS type or STAR type.
The GND terminal at the main PCB is a ‘-’ terminal for dry contact. It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units are matched.(A-A, B-B)
WARNING
!
• Indoor Unit ground wires are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor and other parts.
WARNING
!
When the total capacity is over than 68 HP, Do not use single power source for connecting series units.
The First terminal block could be burnt out.
- Connection of communication cable must be installed like below figure between indoor unit to outdoor unit.
- Abnormal operation can be caused by communication defect, when connection of communication cable is installed like below figure(STAR type).
Frequency
Voltage range(V)
Outdoor Indoor 60 Hz 380 V 220 V 50 Hz 380~415 V 220~240 V
CAUTION
!
It should be wiring power cables or communication cables to avoid interference with the oil level sensor. Otherwise, That oil level sensor would be operated abnormally.
Example) Connection of power and communication cable (UXA)
Gap : Over
50mm(1.97’’)
When connecting
Main power lines
/ Ground wire from left side
When connecting
Communication wires
/ Ground wire from left side
Main power terminal block
Ground wire
Main power
terminal block
Insulation sleeves
attachments
Ground wire
Ground wire ODU-IDU
Communication cable
ODU-ODU Communication cable
Bottom Side
Main power terminal block
Ground wire
When connecting Communication wires / Ground wire from front guide panel
When connecting Main power lines / Ground wire from front guide panel
Gap : Over 50mm(1.97’’)
Front Side
Fix firmly with cable tie or
clamp cord not to be displaced
Main power line
connection
Communication/Ground
wire connection
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
34 34 34
Master
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Master Outdoor unit
Slave1 Outdoor Unit
Slave2 Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Slave3 Outdoor Unit
Page 26
26
ENGLISH
CAUTION
!
It should be wiring power cables or communication cables to avoid interference with the oil level sensor. Otherwise, That oil level sensor would be operated abnormally.
Checking the setting of outdoor units
Checking according to DIP switch setting
- You can check the setting values of the Master outdoor unit from the 7 segment LED. The DIP switch setting should be changed when the power is OFF.
Checking the initial display The number is sequentially appeared at the 7 segment in 5 seconds
after applying the power. This number represents the setting condition.
[Main Board]
DIP switch
7 segment
SW01C (Automatic Addressing Setting)
Main power
terminal block
Insulation sleeves
attachments
Ground wire
Ground wire
ODU-IDU Communication cable
ODU-ODU Communication cable
Main power
terminal block
Ground wire
When connecting Communication wires / Ground wire from front guide panel
When connecting Main power lines / Ground wire from front guide panel
Gap : Over 50mm(1.97’’)
Front Side
Fix firmly with cable tie or clamp cord not to be displaced
Main power line
connection
Communication/Ground
wire connection
Quick control Setting In the factory setting, main PCB DIP switch setting is all “OFF”.
- Check and make sure that all the indoor unit model name are ARNU******4.
- Change the main PCB DIP switch No. 3 “OFF ON” like below picture.
- Push the reset button.
7 segmentDIP Switch
Reset button
• Initial display order
• Example) ARUN620LLS5 62 HP 380 V Heat Pump System (Master unit: 18 HP, Slave 1: 16 HP, Slave 2: 14 HP, Slave 3: 14 HP)
Order No Mean
8~26 Master unit capacity
10~24 Slave 1 unit capacity
10~24 Slave 2 unit capacity
10~24 Slave 3 unit capacity
8~96 Total capacity
2 Heat Pump
38 380 V model 46 460 V model 22 220 V model
50 Product type
18 16 14 14 62 2 38 50
Example) Connection of power and communication cable (UXB)
Main power
terminal block
Ground wire
Gap : Over
50mm(1.97’’)
When connecting
Main power lines
/ Ground wire from left side
When connecting
Communication wires
/ Ground wire from left side
Bottom Side
Page 27
27
ENGLISH
Master/Slave DIP switch setting
• Master Unit
• Slave Unit
DIP switch
setting
ODU Setting
Slave 1
Slave 2
Slave 3
DIP switch
setting
ODU Setting
Factory Setting
Main Board
The Procedure of Automatic Addressing
CAUTION
!
• In replacement of the indoor unit PCB, always perform Automatic addressing setting again (At that time, please check about using Independent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error occur.
• Automatic Addressing has to be performed after more than 3 minutes to improve indoor unit communition when initial power is supplied.
• Please be sure that all the DIP switch (1~7) of master outdoor unit is OFF before Automatic Addressing setting
Setting the optional function Select the mode/function/option/value using ‘’, ‘’ Button and
confirm that using the ‘’ button after DIP switch No.5 is turned on.
SW01C (Ɨ: Confirm / Automatic Addressing)
SW02C (ȭ: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW01D (reset)
SW03C (ȯ: forward)
Automatic Addressing
The address of indoor units would be set by Automatic Addressing
- Wait for 3 minutes after supplying power. (Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A “88” is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on numbers of connected indoor units
-
Numbers of connected indoor units whose addressing is completed are indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated on the wired remote control display window. (CH01, CH02, CH03, ……, CH06 : Indicated as numbers of connected indoor units)
DIP switch
Power On
Waiting 3 minutes
Press RED Button for 5 s
(SW01C)
7-segment LED = 88
Don’t press RED Button
(SW01C)
Waiting about 2~7 minutes
7-segment LED
= 88
YES
OK
Automatic Addressing process start
• Automatic addressing process end Numbers of indoor unit connected are indicated for 30seconds on 7-segment LED after completing process
NO Check the connections
Indoor address number is displayed on wired remote controller or indoor unit display window. It is not an error message, will disappeared when on/off button is pressed on remote controller ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
and Automatic addressing is completed normally.
of communication cable
7 segment
SW01C (Automatic Addressing Setting)
Page 28
28
ENGLISH
Optional Mode Selection Function Selection Option Selection
Remarks
Content
Display ()
Content
Display
(, )
Default
Optional
(, )
FDD Fdd
Automatic Refrigerant
Charging (Cooling)
Fd 1 - -
* Refer FDD
guidance
Automatic Refrigerant
Charging (Heating)
Fd 2 - -
Refrigerant Amount
Check (Cooling)
Fd 3 - -
Refrigerant Amount
Check (Heating)
Fd 4 - -
Automatic system
check mode(cooling
or heating)
Fd 7 - -
All IDU operation
(Cooling)
Fd 8 - -
Compulsory
Operation for
1 hour
All IDU operation
(Heating)
Fd 9 - -
Installation Func
Cool & Heat
Selector
Fn 1 oFF
oFF,
oP1~oP2
Saving in
EEPROM
High Static Pressure
Compensation
mode
Fn 2 oFF
oFF,
oP1~oP7
Night Low Noise
mode
Fn 3 oFF
oFF,
oP1~oP12
Overall Defrost
mode
Fn 4
North
America: oFF
Europe: oFF Tropical: oN
on, oFF
ODU address
setting
Fn 5 0 255
Snow Removal &
Rapid Defrost
Fn 6 oFF
oFF,
oP1~oP3
Airflow Adjusting
for IDU (Heating
capacity up)
Fn 7 oFF on, oFF
Target Pressure
Adjusting
Fn 8 oFF
oFF,
oP1~oP4
Low Ambient Kit Fn 9 oFF on, oFF
High Efficiency
Mode (Cooling
Operation)
Fn 10 oFF on, oFF
Auto Dust Removal
Mode
Fn 11 oFF
oFF,
oP1~oP5
Compressor Max.
Frequency Limit
Fn 12 oFF
oFF,
oP1~oP9
ODU Fan Max.
RPM Limit Mode
settting
Fn 13 oFF
oFF,
oP1~oP7
Smart Load Control
Mode setting
Fn 14 oFF
oFF,
oP1~oP3
Central Control
Connection at
Indoor Unit side
Fn 19 oFF oFF, on
Compressor Input
Current Limit mode
Fn 20 oFF
oFF,
oP1~oP10
Power
Consumption
Display on wired
remote controller
Fn 21
SPL0
SPL0, SPL1
[Pd10~Pd11]
Overall Defrost
Operating in Low
temperature (Heating)
Fn 22 oFF on, oFF
Optional Base panel
Heater
Fn 23 oFF on, oFF
User Idu
Comfort Cooling
Mode setting
Id 10 EAch
* Refer Comfort
Cooling guidance
Saving in
EEPROM
Service SvC Vaccum Mode SE 3 vACC -
1time / 1
Selection
* Functions save in EEPROM will be maintained continuously, though
the system power was reset.
CAUTION
!
• To perform the otional funtion should be sure that All the IDU is off mode, unless the function will not be performed.
Function setting
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn1” Push the ‘’ button
Select the Option using ‘’, ‘’ Button : “oFF”,“op1”,“op2” Push the ‘’ button
Cool & Heat Selection mode is set
Cool & Heat selector
Mode setting method
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, first install a Cool & Heat selector.
Switch Control Function
Switch
(Up)
Switch
(Down)
oFF op1(mode) op2(mode)
Right side
(On)
Left side
(On)
Not operate Cooling Cooling
Right side
(On)
Right side
(On)
Not operate Heating Heating
Left side
(Off)
- Not operate Fan mode Off
Switch (Up)
Switch (Down)
Left side
Right side
Page 29
29
ENGLISH
FAN Maximum RPM of each step
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn2” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op7” Push the ‘’ button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Chassis UXA UXB
Max. RPM
Standard 880 1 000
Overload / Low
Temperature
1 000 1 150
op1 860 950 op2 840 900 op3 820 850 op4 800 800 op5 780 750 op6 760 700 op7 740 650
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn3” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op12” Push the ‘’ button
Start the Night low noise function :
Save the selected option value in EEPROM
Time Settings
Step Judgment Time(Hr) Operation Time(Hr)
op1 8 9 op2 6.5 10.5 op3 5 12 op4 8 9 op5 6.5 10.5 op6 5 12 op7 8 9 op8 6.5 10
op9 5 12 op10 Continuous operation op11 Continuous operation op12 Continuous operation
Noise
Chassis UXA UXB Capacity 8~14 HP 16~22 HP 24~26 HP
Step Noise(dBA)
op1~op3,op10 55 59 60 op4~op6,op11 52 56 57 op7~op9,op12 49 53 55
CAUTION
!
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn4” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on” ~ “oFF” Push the ‘’ button
Overall defrost mode is set
Mode setting
- on: Operate overall defrost
- off: Operate partial defrost
CAUTION
!
• Ask an authorized technician to setting a function.
Setting the ODU address
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn5” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“0” ~ “255” Push the ‘’ button
ODU address is set
Overall defrost mode
Mode setting method
Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
High Static Pressure Compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan discharge of ODU.
Static pressure compensation mode setting method
Page 30
30
ENGLISH
CAUTION
!
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
Mode setting
setting Mode
oFF Not setting
op1 Snow removal mode
op2 Rapid defrost mode
op3 Snow removal mode. + Rapid defrost mode.
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn6” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1” ~ “op3” Push the ‘’ button
Mode is set
CAUTION
!
• Ask an authorized technician to setting a function.
Step Mode OFF Not setting
ON Low capacity mode
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn7” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on” ~ “oFF” Push the ‘’ button
IDU capacity adjusting is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn9” Push the ‘’ button
Low Ambient Kit Mode is set
Select the Option using ‘’, ‘’ Button :
“on”,“oFF” Push the ‘’ button
Low Ambient Kit
Mode setting method
h Reference for functional logic of I/O Module
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Setting
Mode
Purpose
Condensing
temperature
variation
Evaporating temperature
variation
Heat Cool
op1 Increase capacity Increase capacity
+2 °C
(35.6 °F)
-3 °C
(37.4 °F)
op2
Decrease power
consumption
Increase capacity
+2 °C
(35.6 °F)
-1.5 °C
(-34.7 °F)
op3
Decrease power
consumption
Decrease power
consumption
-4 °C
(-39.2 °F)
+2.5 °C
(36.5 °F)
op4
Decrease power
consumption
Decrease power
consumption
-6 °C
(-42.8 °F)
-4.5 °C
(-40.1 °F)
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1” ~ “op4” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Target pressure is set
Select the Option using ‘’, ‘’ Button :
“HEAT” , “COOL” Push the ‘’ button
Target pressure adjusting
Mode setting method
Setting Capacity Up Airflow Adjusting for IDU (Heating)
If the operation of indoor unit is more than 130 %, the air flow is operated as low in the all indoor units.
Mode setting method
Snow removal & rapid defrost
Mode setting method
Page 31
31
ENGLISH
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn10” Push the ‘’ button
High Efficiency Mode is set
Select the Option using ‘’, ‘’ Button :
“on”,“oFF” Push the ‘’ button
Mode Setting
Setting
Operation
time
Operating
time
Repeat
cycle
Detail of function
op1
Stop
+2hour
5minutes 2hour
After product stopped 2 hour, fan operating 5 minutes(Repeated every 2 hours)
op2
stop
+5minutes
3minutes
Twice in
2 hour
after product stopped 5 minutes, fan operating 3 minutes (Limited to two times within 2 hours)
op3
stop
+5minutes
3minutes 1 time
after product stopped 2 hour, fan operating 5 minutes(Repeated every 2 hours)
op4
Stop
+1minutes
1minutes 1 time
after product stopped 5 minutes, fan operating 3 minutes(when io module connection/one-time operation)
op5
Stop
+1minutes
1minutes
Low
speed
after product stopped 1minutes, fan operating 1 minutes(every time the product stops)
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn11” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~“op5” Push the ‘’ button
Auto Dust Removal Mode is set
Function setting
Setting Inverter (Hz)
oFF ­op1 143 Hz op2 135 Hz op3 128 Hz op4 120 Hz op5 113 Hz op6 105 Hz op7 98 Hz op8 90 Hz op9 83 Hz
CAUTION
!
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn13” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~“op7” Push the ‘’ button
ODU Fan Max. RPM Limit Mode is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn 12” Push the ‘’ button
Select the Option using ‘’, ‘’ Button : “oFF”,“op1”,“op9” Push the ‘’ button
Cool & Heat Selection mode is set
ODU Fan Max. RPM Limit
Mode setting method
Compressor Max. Frequency Limit
Mode setting method
Auto Dust Removal Mode
The ability to set reverse run outdoor fan to remove dust, heat exchanger.
Mode setting method
High Efficiency Mode (Cooling Operation)
Target low pressure will change according to ODU temperature during the cooling operation.
Mode setting method
MAX. RPM Limit Setting
Chassis UXA UXB
Fan MAX. RPM
Limit (RPM)
oFF 880 1000 oP1 -20 -50 oP2 -40 -100 oP3 -60 -150 oP4 -80 -200 oP5 -100 -250 oP6 -120 -300 oP7 -140 -350
Page 32
32
ENGLISH
SLC(Smare Lode Control) Mode
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn14” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~“op3” Push the ‘’ button
SLC(Smare Lode Control) Mode is set
Setting Mode Detail of function
oFF Not Setting ­oP1 Smooth Mode Slowly control, a target pressure value oP2 Normal Mode Normal control, a target pressure value oP3 Peak Mode Fast control, a target pressure value
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn16” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“Fn19” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on”,“oFF” Push the ‘’ button
Central Control Connection at Indoor
Unit side Mode is set
Compressor Input Current Limit
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn20” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~”op10” Push the ‘’ button
Compressor Input Current Limit mode is set
Mode Compressor Input Current Limit
op1 95 % op2 90 % op3 85 % op4 80 % op5 75 % op6 70 % op7 65 % op8 60 % op9 55 %
op10 50 %
Compressor Input Current Limit
System Input Current Control Mode setting method
Central Control Connection at Indoor Unit side
Mode setting method
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
SLC (Smart Load Control)
Function for set the variable target pressure which for the high efficiency and comport operation depend on ODU load.
Mode setting method
Page 33
33
ENGLISH
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn21” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“SPL0”,“SPL1”,”Pd10”,”Pd11”Push the ‘
button
Power Consumption Display on wired remote
controller Mode is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn22” Push the ‘’ button
Overall Defrost Operating in Low Mode is set
Setting Detail of function
Defualt OFF
Setting ON/OFF Control
Setting Detail of function
SPL0 Not used Smart plug logic
SPL1 Using smart plug logic
Pd10 Not installation
Pd11 PDI was installed
Setting of continous cooling operation
Mode setting Effect
0 No setting 1 Cooling capacity low,Power consumption low 2 Cooling capacity mid,Power consumption mid 3 Cooling capacity high,Power consumption high
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Idu” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Id10” Push the ‘’ button
EEV pulse appearing
(seg1, seg2:Idu No./seg3, seg4:Mode)
Select the Function using ‘’, ‘’ Button :
Idu No. setting and Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
Mode setting and Push the ‘’ button
*Mode can be set 0~3 (”0” is no setting)
Setting of continous cooling operation
Comfort Cooling operation
It is function to reduce the ODU energy consumption by the continuou s operation without thermo off.
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn23” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“on” Push the ‘’ button
Base pan Heater operation mode is set
CAUTION
!
• Function to prevent freezing of ODU base pan in a cold area.
• Heater is accesory.(Sold separately)
Base pan Heater operation
Overall Defrost Operating in Low temperature (Heating)
Mode setting method
Power Consumption Display on wired remote controller
Mode setting method
Page 34
34
ENGLISH
Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display 1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number.(* = 1: Master, 2: Slave 1, 3: Slave 2, 4: Slave 3)
Ex) 1051 : Error occurrence with error number 105 at No. 1 outdoor unit (=Master unit)
In case of indoor unit error occurrence, the error number is only shown at remote controller without 7 segment LED of outdoor unit.
Ex) CH 01 : Error occurrence with error number 01 (at remote controller)
In case of compressor error occurrence, 7 segment LED of outdoor unit control board will display its error number alternately with compressor number.
Ex) 213 C23 : It means that compressor error occurred with Error No. 21 at No. 3 Outdoor unit (=Slave2)
* Refer to the DX-Venitilation manual for DX-Venitilation error code.
• 1 : Master outdoor unit error, 2 : salve 1 outdoor unit error
• 3 : slave2 outdoor unit error, 4 : slave3 outdoor unit error
Display Title Cause of Error
0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
0 3 -
Communication error : wired remote controller indoor unit
Failing to receive wired remote controller signal in indoor unit PCB
0 4 - Drain pump Malfunction of drain pump
0 5 -
Communication error : outdoor unit indoor unit
Failing to receive outdoor unit signal in indoor unit PCB
0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short
08 -
Hydro Kit Hot water storage tank Temperature sensor
Pipe temperature sensor is open or short
0 9 - Indoor EEPROM Error
In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFF
1 0 - Poor fan motor operation
Disconnecting the fan motor connector / Failure of indoor fan motor lock
1 1 -
Communication error : Hydro Kit Indoor unit Inv.PCB
Failing to receive Inv. PCB signal in indoor unit
1 2 - Hydro Kit Inv.PCB error Hydro Kit Inv.PCB error
13 -
Hydro Kit Solar heat piping temperature sensor error
Pipe temperature sensor is open or short
1 4 - Hydro Kit Indoor unit Flow switch error Flow switch flow detection error
1 5 - Hydro Kit Liquid pipe Strange overheat Error Temperature sensor defective or hot water inflow
16 -
Hydro KitIndoor unit Inlet and Outlet pipe Temperature sensor Error
Pipe temperature sensor is open or short
17 -
Hydro Kit Indoor unit Inlet pipe Temperature sensor Error Outside air Introduction duct Inlet pipe Temperature sensor Error
Pipe temperature sensor is open or short
18 -
Hydro Kit Indoor unit Outlet pipe Temperature sensor Error
Pipe temperature sensor is open or short
2 1 *
Outdoor Unit Inverter Compressor IPM Fault
Outdoor Unit Inverter Compressor Drive IPM Fault
2 2 *
Inverter PCB Input Over Current(RMS) of Master Outdoor Unit
Outdoor Unit Inverter PCB Input Current excess (RMS)
2 3 *
Outdoor Unit Inverter Compressor DC Link Low or High Voltage
System is turned off by Master Outdoor Unit DC Link Low/High Voltage.
2 4 * Outdoor Unit High Pressure Switch
System is turned off by Master Outdoor Unit high pressure switch.
2 5 *
Outdoor Unit Input Voltage High/ Low Voltage
Over 537V or below 247V (ARUM***LTE5) Over 310V or below 143V (ARUM***BTE5) Over 598V or below 320V (ARUM***DTE5)
Indoor unit related errorOutdoor unit related error
Error No.
Repeat
Error No. of Unit
Error No. of Compressor
Page 35
35
ENGLISH
Display Title Cause of Error
2 6 * Outdoor Unit Inverter Compressor Start Failure
The first start failure by Outdoor Unit Inverter Compressor abnormality or Compressor locked
2 9 * Outdoor Unit Inverter Compressor Over Current Outdoor Unit Inverter Compressor Fault OR Drive Fault
3 2 *
Outdoor Unit Inverter Compressor1 High Discharge Temperature
Outdoor Unit Inverter Compressor1 High Discharge Temperature
3 3 *
Outdoor Unit Inverter Compressor2 High Discharge Temperature
Outdoor Unit Inverter Compressor2 High Discharge Temperature
3 4 * High Pressure of Outdoor Unit High Pressure of Outdoor Unit
3 5 * Low Pressure of Outdoor Unit Low Pressure of Outdoor Unit
4 0 * Outdoor Unit Inverter Compressor CT Sensor Fault Outdoor Unit Inverter Compressor CT Sensor open or short
4 1 *
Outdoor Unit Inverter Compressor1 Discharge Temperature Sensor Fault
Outdoor Unit Inverter Compressor Discharge Temperature Sensor open or short
4 2 * Outdoor Unit Low Pressure Sensor Fault Outdoor Unit Low Pressure Sensor open or short
4 3 * Outdoor Unit High Pressure Sensor Fault Outdoor Unit High Pressure Sensor open or short
4 4 * Outdoor Unit Air Temperature Sensor Fault Outdoor Unit Air Temperature Sensor open or short
4 5 *
Outdoor Unit Heat Exchanger Temperature Sensor (Front side) Fault
Outdoor Unit Heat Exchanger Temperature Sensor(Front side) open or short
4 6 * Outdoor Unit Suction Temperature Sensor Fault Outdoor Unit Suction Temperature Sensor open or short
4 7 *
Outdoor Unit Inverter Compressor2 Discharge Temperature Sensor Fault
Outdoor Unit Inverter Compressor2 Discharge Temperature Sensor open or short
4 9 * Outdoor Unit Faulty IPM Temperature Sensor Outdoor Unit IPM Temperature Sensor short/open
50*
Omitting connection of R, S, T power of Outdoor Unit
Omitting connection of outdoor unit
5 1 * Excessive capacity of indoor units
Excessive connection of indoor units compared to capacity of Outdoor Unit
52*
Communication error : inverter PCB Main PCB
Failing to receive inverter signal at main PCB of Outdoor Unit
53*
Communication error : indoor unit Main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of Outdoor Unit.
57*
Communication error : Main PCB inverter PCB
Failing to receive signal main PCB at inverter PCB of Outdoor Unit
6 0 * Inverter PCB EEPROM Error of Master Outdoor Unit Access Error of Inverter PCB of Outdoor Unit
6 2 * Outdoor Unit Inverter Heatsink High Temperature
System is turned off by Outdoor Unit Inverter Heatsink High Temperature
65*
Outdoor Unit Inverter Heatsink Temperature Sensor Fault
Outdoor Unit Inverter Heatsink Temperature Sensor open or short
6 7 * Outdoor Unit Fan Lock Restriction of Outdoor Unit
7 1 * Inverter CT Sensor Error of Master Outdoor Unit Inverter CT Sensor open or short of Outdoor Unit
7 5 * Outdoor Unit Fan CT Sensor Error Outdoor Unit Fan CT Sensor open or short
7 7 * Outdoor Unit Fan Over Current Error Outdoor Unit Fan Current is over 6A
7 9 * Outdoor Unit Fan Start Failure Error
The first start failure by Outdoor Unit Fan abnormality or Fan locked
8 6 * Outdoor Unit Main PCB EEPROM Error
Communication Fail Between Outdoor Unit Main MICOM and EEPROM or omitting EEPROM
8 7 * Outdoor Unit Fan PCB EEPROM Error
Communication Fail Between Outdoor Unit Fan MICOM and EEPROM or omitting EEPROM
1 0 4*
Communication Error Between Outdoor Unit and Other Outdoor Unit
Failing to receive Slave Unit signal at main PCB of Outdoor Unit
1 0 5* Outdoor Unit Fan PCB Communication Error Failing to receive fan signal at main PCB of Outdoor unit
1 0 6* Outdoor Unit Fan IPM Fault Error Instant Over Current at Outdoor Unit Fan IPM
Outdoor unit related error
Page 36
36
ENGLISH
Display Title Cause of Error
1 0 7* Outdoor Unit Fan DC Link Low Voltage Error Outdoor Unit Fan DC Link Input Voltage is under 380V
1 1 3* Outdoor Unit Liquid pipe Temperature Sensor Error Liquid pipe temperature sensor of Outdoor Unit is open or short
1 1 4*
Outdoor Unit Subcooling Inlet Temperature Sensor Error
Outdoor Unit Subcooling Inlet Temperature Sensor Error
115 *
Outdoor Unit Subcooling Outlet Temperature Sensor Error
Outdoor Unit Subcooling Outlet Temperature Sensor Error
1 1 6 * Outdoor Unit Oil Level Sensor Error Oil Level Sensor of Outdoor Unit is open or short
145 *
Outdoor unit Main Board - External Board communication Error
Outdoor unit Main Board - External Board communication Error
1 5 0 * Outdoor Unit Discharge Superheat not satisfied
Outdoor Unit Compressor Discharge Superheat not satisfied during 5 minutes
151 *
Failure of operation mode conversion at Outdoor Unit
Failure of operation mode conversion at Outdoor Unit
153 *
Outdoor Unit Heat Exchanger Temperature Sensor (upper part) Fault
Outdoor Unit Heat Exchanger Temperature Sensor (upper part) Fault
154 *
Outdoor Unit Heat Exchanger Temperature Sensor (lower part) Fault
Outdoor Unit Heat Exchanger Temperature Sensor(lower part) open or short
182 *
Outdoor unit External Board Main-Sub Micom communication Error
Outdoor Unit Main Board Main-Sub Micom communication failed
1 8 7 * Hydro - Kit P,HEX bursting error
Inlet water temperature is below 5 degree or water temperature error during defrosting operation.
1 9 3 * Outdoor Unit Fan Heatsink High Temperature
System is turned off by Outdoor Unit Fan Heatsink High Temperature
194 *
Outdoor Unit Fan Heatsink Temperature Sensor Fault
Outdoor Unit Fan Heatsink Temperature Sensor open or short
Network error
2 4 2 * Network error of cntral controller Communication wiring defect
Outdoor unit related error
Page 37
37
ENGLISH
Checking procedure of limiting concentration
Check Concentration limit along following steps and take appropriate measure depending on the situation.
Calculate amount of all the replenished refrigerant [kg (lbs)] per each refrigerant system.
Calculate refrigerant concentration level Calculate the volume of the room where indoor unit is installed as
single room or the smallest room.
- With partition but opened which serve passage of air to adjoining room
- Without partition
Concentration limit is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The Concentration limit shall be described in the unit of [kg/m
3
(lbs/ft3)] (Freon gas weight per unit
air volume) for facilitating calculation.
Concentration limit: 0.44 kg/m3(0.028 lbs/ft3) (R410A)
Amount of additional replenished refrigerant
Total amount of refrigerant in the system [kg (lbs)]
+
=
Note : In case one refrigerant facility is
divided into 2 or more refrigerant systems and each system is independent, amount of replenished refrigerant of each system shall be adopted.
Amount of pre charged refrigerant per single unit system
Amount of replenished refrigerant at factory shipment
Amount of additionally replenished refrigerant depending on piping length or piping diameter by customer
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Opening
Partition
In the case of opening without door , or 0.15 % or more openings (to floor space) both above and below door)
Outdoor unit
(No.1 system)
Flow of refrigerant
Indoor unit
Room where refrigerant leaks (Refrigerant of the whole No.1 system flows out.)
CAUTION FOR REFRIGERANT LEAK
The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.
Introduction
Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should be large to such an extent that the refrigerant gas will not exceed the Concentration limit even if the refrigerant gas leaks in the room.
Concentration limit
- With partition and without opening which serve as passage of air to adjoining room
Calculate refrigerant concentration
Total amount of refrigerant
system [kg(lbs)]
Volume of smallest room
whereindoor unit is installed
[m
3
(ft3)]
- In case the result of calculation exceeds the Concentration limit, perform the same calculations by shifting to the second smallest, and the third smallest rooms until at last the result is below the Concentration limit.
= Maximum concentration limit
[kg/m
3
(lbs/ft3)]
(R410A)
In case the concentration exceeds the limit When the concentration exceeds the limit, change original plan or take
one of the countermeasures shown below:
• Countermeasure 1
Provide opening for ventilation. Provide 0.15% or More size of opening to floor space both above and below door, or provide opening without door.
• Countermeasure 2
Provide gas leak alarm linked with mechanical ventilator.
• Countermeasure 3
Reducing the system`s refrigerant quantity by deviding into smaller separate system.
Outdoor unit
Indoor unit
Smallest room
Countermeasure 2
Gas leak alarm Mechanical ventilator
Countermeasure 1
Opening effective to ventilation
Indoor unit
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air.
Page 38
38
ENGLISH
• Product Name : Air conditioner
• Model Name :
• Additional information : Serial number is refer to the bar code on the
product.
Product Sales Name Model Factory Name
ARUx***LTy5 series
x =
N (Heat Pump), V (Cooling Only), M (Heat Recovery / Heat Pump) y = E (Basic function), S(Standard) *** = Numeric; (Cooling capacity)
Product information
Airborne Noise Emission
The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels.
Whilst there is a correlation between the emission and exposure levels, this cannot be used reliably to determine whether or not further precautions are required.
Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the number of equipment and other adjacent processes and the length of time for which an operator exposed to the noise. Also, the permissible exposure level can vary from country to country.
This information, however, will enable the user of the equipment to make a better evaluation of the hazard and risk.
Model Designation
CAUTION
!
• Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
• Avoid installing the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
• If outdoor unit is installed close to the seaside, should avoid direct exposure to the sea wind.
INSTALLATION GUIDE AT THE SEASIDE
• Periodic ( 1times per 6 month) cleaning of the dust or salt particles stuck on the heat exchanger is necessary by using clean water
In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
- It should be strong enough like concrete to prevent the sea wind from the sea.
- The height and width should be more than 150 % of the outdoor unit.
- It should be kept more than 70 cm (2.3 ft) of distance between outdoor unit and the windbreak for smooth air flow.
Select a well-drained place.
If there is improper installation or maintenance not complying with the installation guide, product’s performance and reliability is not guauranteed.
Sea wind
Windbreak
Selecting the location(Outdoor Unit)
If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
Sea wind
Loading...