LG ARUN134DT2, ARUN076DT2, ARUN154DT2, ARUN173DT2, ARUN192DT2 Service Manual

...
System
Outdoor Unit
SERVICE MANUAL R410A
MODEL : ARUN Series
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
http://biz.lgservice.com
R410A
- 2 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions............................................................................................................................3
Part 1 General Information.............................................................................................................10
Model Names .............................................................................................................................11
External Appearance .................................................................................................................12
Combination of Outdoor Units .................................................................................................14
Nomenclature .............................................................................................................................15
Outdoor Units Information ........................................................................................................16
Part 2 Outdoor Units ................................................................................................................
19
Part 3 PCB Setting and Test Run
........................................................................................57
Part 4 Trouble shooting guide .............................................................................................
69
- 3 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Installation
Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
• If the power source capacity is inadequate or electric work is performed improperly, electric shock or fire may result.
Ask the dealer or an authorized technician to install the air conditioner.
• Improper installation by the user may result in water leakage, electric shock, or fire.
Always ground the product.
• There is risk of fire or electric shock.
Always intstall a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock.
- 4 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install, remove, or re-install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Do not store or use flammable gas or combustibles near the air conditioner.
• There is risk of fire or failure of product.
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Prepare for strong wind or earthquake and install the unit at the specified place.
• Improper installation may cause the unit to top­ple and result in injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
When installing and moving the air condition­er to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
• If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
Do not reconstruct to change the settings of the protection devices.
• If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
Gasolin
R22
R407C
R410A
- 5 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Safety Precautions
Ventilate before operating air conditioner when gas leaked out.
• It may cause explosion, fire, and burn.
Securely install the cover of control box and the panel.
• If the cover and panel are not installed securely,
dust or water may enter the outdoor unit and fire or electric shock may result.
If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
• Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceed­ed. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxy­gen in the room could result.
Do not damage or use an unspecified power cord.
• There is risk of fire, electric shock, explosion, or injury.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Do not touch the power switch with wet hands.
• There is risk of fire, electric shock, explosion, or injury.
- 6 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
CAUTION
Installation
Safety Precautions
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or electric shock.
Be cautious not to touch the sharp edges when installing.
• It may cause injury.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
• This could result in personal injury and product damage.
Do not open the inlet grille of the product during operation. (Do not touch the electro­static filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the unit where combustible gas may leak.
• If the gas leaks and accumulates around the unit, an explosion may result.
90˚
Gasolin
- 7 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Use power cables of sufficient current carrying capacity and rating.
Cables that are too small may leak, generate heat, and cause a fire.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
There is risk of damage or loss of property.
Keep the unit away from children. The heat exchanger is very sharp.
It can cause the injury, such as cutting the finger. Also the damaged fin may result in degradation of capacity.
When installting the unit in a hospital, com­munication station, or similar place, provide sufficient protection against noise.
The inverter equipment, private power generator, high-frequency medical equipment, or radio com­munication equipment may cause the air condition­er to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not install the product where it is exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
- 8 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Operation
Do not use the air conditioner in special environments.
Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
Do not block the inlet or outlet.
It may cause failure of appliance or accident.
Make the connections securely so that the outside force of the cable may not be applied to the terminals.
Inadequate connection and fastening may gen­erate heat and cause a fire.
Be sure the installation area does not deteri­orate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, or personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
A bad connection may cause water leakage.
Be very careful about product transportation.
Only one person should not carry the product if it weighs more than 20 kg.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
Do not touch the heat exchanger fins. Doing so may cut your fin­gers.
When transporting the outdoor unit, suspending it at the specified positions on the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
- 9 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
Turn on the power at least 6 hours before starting operation.
Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
Do not touch any of the refrigerant piping during and after operation.
It can cause a burn or frostbite.
Do not operate the air conditioner with the panels or guards removed.
Rotating, hot, or high-voltage parts can cause injuries.
Do not directly turn off the main power switch after stopping operation.
Wait at least 5 minutes before turning off the main power switch. Otherwise it may result in water leakage or other problems.
Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the indoor unit PCB.
Use a firm stool or ladder when cleaning or maintaining the air conditioner.
Be careful and avoid personal injury.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There are sharp and moving parts that could cause personal injury.
- 10 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Part 1
General Information
1. Model Names ................................................................11
1.1 Indoor Unit .............................................................11
1.2 Outdoor Unit ..........................................................11
2. External Appearance.....................................................12
2.1 Indoor Unit .............................................................12
2.2 Outdoor Unit ..........................................................13
3. Combination of Outdoor Units .....................................15
4. Nomenclature.................................................................17
4.1 Indoor Unit .............................................................17
4.2 Outdoor Unit ..........................................................17
- 11 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
1. Model Names
1.1 Indoor Unit
Model Names
SE
Wall Mounted (General)
S5
SE
Mirror
S3
SF
1 Way TJ
2 Way TL
TE
4 Way
TP
TN
TM
BH
BG
High
Static
BR
B8
B1
Low Static
B2
B3
B4
Ceiling & Floor VE
Ceiling Suspended VJ
CE
With Case
CF
CE
CF
Capacity(MBh (kW))
Category
Chassis
Name
7 9 12 15 18 24 28 36 42 48 76 96
(2.2) (2.8) (3.6) (4.5) (5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28)
Ceiling
Concealed
Duct
Built In
ART Cool
Gallery
Floor
Standing
Without
Case
Ceiling
Cassette
ART COOL
*
ART COOL- B: Blue, M:Metal, D:Wood, R:Mirror, W:White Wood, V:Silver, E:Red, G:Gold, 1: Kiss (Photo changeable)
*Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma
ARNU073
SE*2
ARNU093
SE*2
ARNU123
SE*2
ARNU153
SE*2
ARNU073
TJ*2
ARNU093
TJ*2
ARNU123
TJ*2
ARNU183
TL*2
ARNU243
TL*2
ARNU073
TE*2
ARNU093
TE*2
ARNU123
TE*2
ARNU153
TE*2
ARNU183
TE*2
ARNU243
TP*2
ARNU283
TP*2
ARNU073
BHA2
ARNU093
BHA2
ARNU123
BHA2
ARNU153
BHA2
ARNU183
BHA2
ARNU243
BHA2
ARNU073
B1G2
ARNU093
B1G2
ARNU123
B1G2
ARNU153
B1G2
ARNU073
B3G2
ARNU093
B3G2
ARNU123
B3G2
ARNU153
B3G2
ARNU073
CEA2
ARNU093
CEA2
ARNU123
CEA2
ARNU153
CEA2
ARNU073
CEU2
ARNU093
CEU2
ARNU123
CEU2
ARNU153
CEU2
ARNU093
VEA2
ARNU123
VEA2
ARNU183
VJA2
ARNU243
VJA2
ARNU183
CFA2
ARNU243
CFA2
ARNU183
CFU2
ARNU243
CFU2
ARNU283
BGA2
ARNU363
BGA2
ARNU423
BGA2
ARNU363
TN*2
ARNU483
BRA2
ARNU423
TM*2
ARNU483
TM*2
URNU76
3B8A2
URNU96
3B8A2
ARNU183
B2G2
ARNU243
B2G2
ARNU183
B4G2
ARNU243
B4G2
ARNU073
SE*2
ARNU093
SE*2
ARNU123
SE*2
ARNU153
SE*2
ARNU073
SF*2
ARNU093
SF*2
ARNU123
SF*2
ARNU183
S5*2
ARNU243
S5*2
ARNU183
S3*2
ARNU243
S3*2
- 12 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
1.2 Outdoor Unit
Heat Pump ARUN
Power Supply
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP
6.5ton 8.0ton 9.5ton 11.0ton 12.5ton 14.5ton 16.0ton 17.5ton 19.0ton
3Ø, 460V, 60Hz 076DT2 096DT2 115DT2 134DT2 154DT2 173DT2 192DT2 211DT2 230DT2
3Ø, 208/230V , 60Hz 076BT2 096BT2 115BT2 - 154BT2 173BT2 192BT2 211BT2 230BT2
Power Supply
26HP 28HP 30HP 32HP
20.5ton 22.5ton 24.0ton 25.5ton
3Ø, 460V, 60Hz 250DT2 270DT2 290DT2 310DT2
- 13 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
External Appearance
2. External Appearance
2.1 Indoor Units
Wall Mounted
ART COOL Mirror
Ceiling Cassette- 1Way
Ceiling Cassette- 4Way
Ceiling & Floor
Ceiling Suspended
ARNU073TJ*2 ARNU093TJ*2 ARNU123TJ*2
Ceiling Cassette -2Way
ARNU183TL*2 ARNU243TL*2
ARNU073TE*2 ARNU093TE*2 ARNU123TE*2 ARNU153TE*2 ARNU183TE*2
ARNU243TP*2 ARNU283TP*2 ARNU363TN*2 ARNU423TM*2 ARNU483TM*2
Ceiling Concealed Duct - Low Static
ARNU073B1G2 ARNU093B1G2 ARNU123B1G2
ARNU153B1G2 ARNU183B2G2 ARNU243B2G2
ARNU073SE*2 ARNU093SE*2 ARNU123SE*2
ARNU153SE*2 ARNU183S5*2 ARNU243S5*2
ARNU073SE*2 ARNU093SE*2 ARNU123SE*2 ARNU153SE*2 ARNU183S3*2 ARNU243S3*2
ARNU093VEA2 ARNU123VEA2
ARNU183VJA2 ARNU243VJA2
Floor Standing With case
ARNU073CEA2 ARNU093CEA2 ARNU123CEA2 ARNU153CEA2 ARNU183CFA2 ARNU243CFA2
Without case
ARNU073CEU2 ARNU093CEU2 ARNU123CEU2 ARNU153CEU2 ARNU183CFU2 ARNU243CFU2
Ceiling Concealed Duct - High Static
ARNU073BHA2 ARNU093BHA2 ARNU123BHA2 ARNU153BHA2 ARNU183BHA2 ARNU243BHA2 ARNU283BGA2
ARNU363BGA2 ARNU423BGA2 ARNU483BRA2 URNU763B8A2 URNU963B8A2
Ceiling Concealed Duct – Built-in
ARNU073B3G2 ARNU093B3G2 ARNU123B3G2
ARNU153B3G2 ARNU183B4G2 ARNU243B4G2
* A:Basic, L:Plasma
ART COOL Gallery
ARNU073SF*2 ARNU093SF*2 ARNU123SF*2
* E:Red V:Silver G:Gold 1: Kiss (Photo changeable)
* A:Basic, C:Plasma
* A:Basic, C:Plasma * A:Basic, C:Plasma
S3: * B : Blue
M : Metal D : Wood R : Mirror W:White Wood
SE: * R:Mirror
V:Silver B : Blue
These are model names of the basic function.
- 14 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
External Appearance
2.2 Outdoor Units(460V)
ARUN076DT2 ARUN096DT2 ARUN115DT2 ARUN134DT2 ARUN154DT2
ARUN173DT2 ARUN192DT2 ARUN211DT2 ARUN230DT2 ARUN250DT2 ARUN270DT2 ARUN290DT2 ARUN310DT2
- 15 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
External Appearance
2.2 Outdoor Units(208/230V)
ARUN076BT2 ARUN096BT2 ARUN115BT2
ARUN154BT2 ARUN173BT2 ARUN192BT2 ARUN211BT2 ARUN230BT2
- 16 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Combination of Outdoor Units
3. Combination of Outdoor Units
3.1 460V
A maximum of 32HP can be obtained by combining 8, 10, 12, 14 and 16HP
System
Number of Units
Capacity 60Hz
Module
810121416
8HP(6.5ton) 1 1 - - - -
10HP(8.0ton) 1 - 1 - - -
12HP(9.5ton) 1 - - 1 - -
14HP(11.0ton) 1 - - - 1 -
16HP(12.5ton) 1 - - - - 1
18HP(14.5ton) 2 1 1 - - -
20HP(16.0ton) 2 1 - 1 - -
22HP(17.5ton) 2 1 - - 1 -
24HP(19.0ton) 2 1 - - - 1
26HP(20.5ton) 2 - - 1 1 -
28HP(22.5ton) 2 - - - 2 -
30HP(24.0ton) 2 - - - 1 1
32HP(25.5ton) 2 - - - - 2
System
Number of Units
Capacity 60Hz
Module
81012
8HP(6.5ton) 1 1 - -
10HP(8.0ton) 1 - 1 -
12HP(9.5ton) 1 - - 1
16HP(12.5ton) 2 2 - -
18HP(14.5ton) 2 1 1 -
20HP(16.0ton) 2 - 2 -
22HP(17.5ton) 2 - 1 1
24HP(19.0ton) 2 - - 2
3.2 208/230V
- 17 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Nomenclature
4. Nomenclature
4.1 Indoor Unit
4.2 Outdoor Unit
ARN U 307 ATJ 2
Generation
Chassis Name
Electrical Ratings 1:1Ø, 115V, 60Hz 2: 1Ø, 220V, 60Hz
6:1Ø, 220 ~ 240V, 50Hz 7: 1Ø, 100V, 50/60Hz 3:1Ø, 220 ~ 240V, 50Hz, 208/230V 60Hz
Total Cooling Capacity in Btu/h EX) 5,000 Btu/h'05' 18,000 Btu/h'18'
Combination of Inverter Type and Cooling Only or Heat Pump
N: AC Inverter and H/P V: AC Inverter and C/O U: DC Inverter and H/P and C/O
System with Indoor Unit using R410A
LGETA:U Ex) URN
Combinations of functions A:Basic function L:Neo Plasma(Wall Mounted) C:Plasma(Ceiling Cassette) G: Low Static ART COOL Type Panel Color B:Blue D:Wood M:Metal R:Mirror W:White Wood V: Silver E:Red G:Gold 1: Kiss (Photo changeable)
ARU N D096 T2
Generation
Air Discharge Type S:Side Discharge T:Top Discharge
Electrical Ratings
8: 3Ø, 380 ~ 415V, 50Hz 9: 3Ø, 380V, 60Hz A: 3Ø, 220V, 50Hz B: 3Ø, 208/230V, 60Hz L: 3Ø, 380 ~ 415V, 50Hz / 3Ø, 380V, 60Hz D: 3Ø, 460V, 60Hz
Total Cooling Capacity in Btu/h EX) 76,000 Btu/h
'076' 96,000 Btu/h '096'
Combination of Inverter Type and Cooling Only or Heat Pump N: Inverter and H/P V: Inverter and C/O B: Inverter and Heat Recovery
System with Outdoor Unit using R410A
- 18 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
- 19 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Part 2
Outdoor Units
- 20 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
• Function ........................................................................................21
• Replacement procedure for Compressor ..................................57
ARUN Series
- 21 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Function
1. Basic control ...................................................................................................................22
1.1 Normal operation .......................................................................................................22
1.2 Compressor control....................................................................................................22
1.3 Master and slave unit's EEV control...........................................................................23
2. Special control ................................................................................................................24
2.1 Oil return control ........................................................................................................24
2.2 Defrost control............................................................................................................26
2.3 Oil equalizing control..................................................................................................27
3. Protection control ...........................................................................................................28
3.1 Pressure protection control ........................................................................................28
3.2 Discharge temperature control...................................................................................29
3.3 Inverter protection control ..........................................................................................29
3.4 Liquid back control .....................................................................................................30
3.5 Phase detection .........................................................................................................30
3.6 Pressure switch..........................................................................................................30
4. Other control ...................................................................................................................31
4.1 Initial setup.................................................................................................................31
4.2 Instant indoor unit checking mode .............................................................................33
4.3 Emergency operation.................................................................................................34
4.4 Refrigerant Auto Charging .........................................................................................36
4.5 Refrigerant Checking Function...................................................................................38
4.6 Pump Down................................................................................................................40
4.7 Pump Out...................................................................................................................41
4.8 Auto Back Up Function_Inverter compressor ............................................................43
4.9 Auto Back Up Function_constant speed compressor ................................................44
4.10 Night Low Noise Function ........................................................................................45
4.11 Vacuum Mode ..........................................................................................................47
4.13 Black Box Function ..................................................................................................48
Function
- 22 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Note : Heating operation is not functional at an outdoor air temperature of 27°C(80°F) or more.
Cooling operation is not functional at an outdoor air temperature of 2°C(36°F) or less with indoor unit combination of 10% or less
1.2 Compressor control
Fuzzy control : Maintain evaporating temperature(Te) to be constant on cooling mode and condensing tem­perature(Tc) on heating mode by Fuzzy control to ensure the stable system performance. [Tc:47~51°C(117~124°F), Te:2~5°C(36~41°F)] (1) Cooling mode Te can be set by initial dip switch setting. (Normal mode, capacity up mode, and energy save mode)
(2) Heating mode Tc can be set by initial dip switch setting. (Normal mode, capacity up mode, and energy save mode)
Note: By setting dip switch, Te and Tc are decided simultaneously.
1.1 Normal operation
1. Basic control
Compressor
Fan
Main EEV
4 way valve
Subcooling
Indoor Unit
EEV
EEV
Fuzzy control
Fuzzy control
Full open
Off
Fuzzy control
Superheat fuzzy
control
Normal : minimum pulse
Avoiding control of high
discharge temperature
Subcooling fuzzy control
Fuzzy control
Fuzzy control
Fuzzy control
On
Cooling operation Heating operationActuator
stop
stop
Before 15 min. : Max. pulse After 15 min. : Min. pulse
After 60 min. : Off
Before 15 min. : Max. pulse After 15 min. : Min. pulse
Before 10 min. : Min. pulse After 10 min. : Max. pulse
Stop state
Fuzzy Control
Stop(0Hz)
Min. frequency
Fuzzy control start
Target
Inverter linear control as cooling and heating load increasing
System Capacity
Cooling and heating load
Inverter
Comperssor
Inverter
Comperssor
Inverter
Comperssor
Inverter
Comperssor
Constant Speed
Compressor
B
Constant Speed
Compressor
B
Constant Speed
Compressor
B
Constant Speed
Compressor
A
Constant Speed
Compressor
C
Constant Speed
Compressor
A
(Linear Control)(Linear Control)(Linear Control)
Function
- 23 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
1.3 Master and slave Unit's EEV control
(1) Main EEV control
Main EEV operates with fuzzy control rules to keep the degree of super Heat(Superheat) (about 3°C)at the evaporator outlet stable during heating mode The degree of Superheat = Tsuction - Tevaporation Tsuction : temperature at suction pipe sensor(°C/°F) Tevaporation : evaporation temperature equivalent to low pressure(°C/°F)
(2) Subcooling EEV control(about 15°C/58°F)
Subcooling EEV works with fuzzy rules to keep the degree of Subcool at the outlet of subcooler during cooling mode The degree of Subcool = Tcondensation - Tliquid Tliquid : temperature at outlet of subcooler(°C/°F) Tcondensation : condensation temperature equivalent to high pressure(°C/°F)
(3) Avoiding excessive high discharge temperature : when main EEV opens some given opening (R410A :
800 pls) and discharge temperature is above 85°C(185°F) in heating operation, subcooling EEV may con­trol the "subcooling out temperature-evaporating temperature" to be some given difference.
Function
- 24 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
2.1 Oil return control
2.1.1 Oil return control on cooling mode
Oil return operation recovers oil amount in compressor by collecting oil accumulated in pipe. Each cycle component operates as following table during oil return operation.
Oil return operation time : 3 min for running step
Starting condition:every 6 hours operate
Oil return process ends if compressor protection control starts
Normal control
OFF
100 pulse
Max. pulse
Normal control
OFF
40Hz
Ending
Normal control
OFF
Main. pluse
Max. pulse
Normal control
ON
Setting Value
Running
Normal control
OFF
Normal control
Max. pulse
Normal control
OFF
25Hz
Starting
Hot gas bypass valve
4way valve
Subcooling EEV
Main EEV
FAN
Constant Speed Compressor
Inv Compressor
Component
OFF
Min. pulse
Normal control
Normal control
Ending
ON
1200 pulse
1200 pulse
OFF
Running
OFF
Min. pulse
Normal control
Normal control
Starting
Oil return signal
Thermo off unit EEV
Thermo on unit EEV
Fan
Component
Outdoor Unit
Indoor Unit
2. Special control
Function
- 25 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
2.1.2 Oil return control on heating mode
Oil return operation time : 3 min for running step
Starting condition:same as cooling mode
Oil return process ends if compressor protection control starts
Outdoor Unit
Indoor Unit
OFF
Min. pulse
Normal control
Normal control
Ending
ON
1200 pulse
1200 pulse
OFF
Running
OFF
Min. pulse
Normal control
Normal control
Starting
Hot gas bypass valve
4way valve
Subcooling EEV
Main EEV
FAN
Constant Speed Compressor
Inv Compressor
Component
Normal control
OFF
Normal control
Max. pulse
Normal control
OFF
25Hz
Starting
Normal control
ON
Min. pulse
Max. pulse
Normal control
ON
Setting Value
Running
Normal control
ON
100 pulse
Max. pulse
Normal control
OFF
25Hz
Ending
Oil return signal
Thermo off unit EEV
Thermo on unit EEV
Fan
Component
Function
- 26 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Outdoor Unit
Indoor Unit
Normal control
ON
Min. pulse
200 pulse
50Hz
OFF
25Hz
Ending
Normal control
OFF
Min. pulse
Max. pulse
High pressure control
ON
Setting Value
Running
Normal control
On OFF
Min. pulse
Normal control
Stop
OFF
25Hz
Starting
Hot gas bypass valve
4way valve
Subcooling EEV
Main EEV
FAN
Constant Speed Compressor
Inv Compressor
Component
Min. pulse
Normal control
OFF
Ending
1200 pulse
1200 pulse
OFF
Running
Min. pulse
Normal control
OFF
Starting
Thermo off unit EEV
Thermo on unit EEV
Fan
Component
Function
2.2 Defrost
Defrost operation eliminates ice attached on heat exchanger, recovering performance of heat exchanger. Each cycle component operates as following table during defrost operation.
Ending condition
1) All heat exchanger pipe temperature are above 15°C(58°F)(UY2) or 20°C(68°F)(UW1) for 30 sec.
2) The running time of defrost operation is over 30% of the total heating time
3) If compressor protection control starts by high discharge temperature of compressor etc.
- 27 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Function
2.3 Stopping operation
2.3.1 Stopping operation on cooling mode
2.3.2 Stopping operation on heating mode
After 15 min.
(Before 15 Min. : ON)
-
After 15 min.
(Before 15 min. : Min. pulse)
After 15 min.
(Before 15 min. : Min. pulse)
-
-
-
Note
OFF
OFF
Max. pulse
Max. pulse
Stop
OFF
0Hz
Operation
Hot gas bypass valve
4way valve
Subcooling EEV
Main EEV
FAN
Constant Speed Compressor
Inv Compressor
Component
After 15 min.
(Before 15 Min. : ON)
After 60 min.
After 15 min.
(Before 15 min. : Min. pulse)
After 15 min.
(Before 15 min. : Min. pulse)
-
-
-
Note
OFF
OFF
Max. pulse
Max. pulse
Stop
OFF
0Hz
Operation
Hot gas bypass valve
4way valve
Subcooling EEV
Main EEV
FAN
Constant Speed Compressor
Inv Compressor
Component
- 28 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
3.1.2 Pressure control on heating mode
High pressure control
Low pressure control
Frequency holding : frequency (or RPM) is not increasing ( can decrease )
Pressure Range Compressor Fan Hot_gas
Pd 4003 kPa (580.6 psi) Stop Stop On
Pd > 3676 kPa (533.2 psi)
-5Hz/4sec.1) -50RPM/4sec. On
P
d 3448 kPa (500.1 psi) Normal control Normal control
P
d Target press
Normal control
off
Pressure Range Compressor Fan Hot_gas
P
s 229 kPa (33.2 psi)
after 1min
Stop Stop
On
Ps 229 kPa (33.2 psi)
1min
-5Hz/4sec. +100RPM/4sec.
Ps 242 kPa (35.1 psi) Frequency holding Normal control
Ps 268 kPa (38.9 psi)
Normal control
Ps > 307 kPa (44.5 psi)
Off
2
1
3
Function
3.1 Pressure protection control
3.1.1 Pressure control on cooling mode
High pressure control
Low pressure control
Frequency holding : frequency (or RPM) is not increasing ( can decrease )
3. Protection control
Pressure Range Compressor Fan Hot_gas
Pd 4003 kPa (580.6 psi)
Stop Stop
-
P
d > 3676 kPa (533.2 psi)
-5Hz/4sec. +100RPM/4sec.
Pd 3448 kPa (500.1 psi) Frequency holding Normal control
P
d < 3284 kPa (476.3 psi)
Normal control
-
Pressure Range Compressor Fan Hot_gas
P
s 229 kPa (33.2 psi)
after 1min
Stop Stop
On
P
s 229 kPa (33.2 psi)
1min
-5Hz/4sec. -100RPM/4sec.
P
s 242 kPa (35.1 psi)
Normal control Normal control
Ps 399 kPa (57.9 psi)
Normal control
Off
- 29 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Function
3.2 Discharge temperature control
Outdoor unit control
Indoor unit control
3.3 Inverter protection control
AC input current is inverter input current except constant speed compressor current(Noise filter passed current)
Emergency
SH control
System stop
103°C(217°F) <
Tdis 112°C(234°F)
Tdis > 115°C(239°F)
Temperature range
EEV
Keep current control
98°C(208°F) < Tdis 103°C(217°F)
SH control
Tdis 98°C(208°F)
Frequency down +
const. Comp off
Liquid injection on
No frequency up
System stop
105°C(221°F) <
Tdis
112°C(234°F)
Tdis > 115°C(239°F)
Temperature range
Compressor
On
Liquid injection
Keep state
OFF
(below 20°C(212°F))
Pressure control
Tdis 98°C(208°F)
Off
Max. limit 490 pulse
Max. limit 490 pulse
Subcooling EEV
Max. limit 300 pulse
Pressure control
Tdis > 95°C(203°F)
Off
10 pulse open /10sec
30A or more28A or more28A or lessCompressor Current
20A or more18A or more18A or lessAC Input Current
System StopFrequency DownNormal Operation
98°C(208°F) <
Tdis
103°C(217°F)
- 30 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
3.5 Phase detection
Main unit
If a phase is missed, 7-segment displays 50* on main PCB. If phases are reversed, 7-segment displays 54* on main PCB.
3.6 Pressure switch
- Main has pressure sensing switch in series between compressor and power relay.
- The state of pressure sensing switch is normally on. It has small electric current from 220V AC. Never touch the connecting terminal with hand nor short two wires directly.
3.4 Liquid back control
Cooling mode
Heating mode
The logic starts after 9 min. on heating mode and 4 min. on cooling mode from the compressor running.
Tdis < Tc + 12°C(54°F)
Discharge temperature Indoor units EEV
Normal SH control
Tdis > Tc + 16°C(60°F)
SH increasing control
SH increasing control
Tdis < Tc + 17°C(62°F)
Discharge temperature Outdoor unit s EEV
Normal SH control
Tdis > Tc + 18°C(64°F)
Function