LG ARUN120LTH4 INSTALLATION MANUAL

P/NO : MFL68069301
www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
ENGLISH
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condi­tioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
TIPS FOR SAVING ENERGY
2
ENGLISH
TIPS FOR SAVING ENERGY
3
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal­function, property damage, personal injury and/or death.
Installation
• Have all electric work done by a licensed electrician according to "Electric Facility Engineering Stan­dard" and "Interior Wire Regulations" and the instructions given in this manual and always use a spe­cial circuit.
- If the power source capacity is inadequate or electric work is performed improperly, electric shock
or fire may result.
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock, or fire.
• Always ground the product.
- There is risk of fire or electric shock.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Do not store or use flammable gas or combustibles near the air conditioner.
- There is risk of fire or failure of product.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Prepare for strong wind or earthquake and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
!
!
!
• When installing and moving the air conditioner to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may mal-
function and the unit may be damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly,
or parts other than those specified by LGE are used, fire or explosion may result.
• Ventilate before operating air conditioner when gas leaked out.
- It may cause explosion, fire, and burn.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed securely, dust or water may enter the outdoor unit and fire
or electric shock may result.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
- Consult the dealer regarding the appropriate measures to prevent the safety limit from being ex-
ceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
Operation
• Do not damage or use an unspecified power cord.
- There is risk of fire, electric shock, explosion, or injury.
• Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Do not touch the power switch with wet hands.
- There is risk of fire, electric shock, explosion, or injury.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious not to touch the sharp edges when installing.
- It may cause injury.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
• Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
IMPORTANT SAFETY INSTRUCTIONS
4
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neigh­borhoods.
- It may cause a problem for your neighbors.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Use power cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a con­sumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Keep the unit away from children. The heat exchanger is very sharp.
- It can cause the injury, such as cutting the finger. Also the damaged fin may result in degradation
of capacity.
• When installting the unit in a hospital, communication station, or similar place, provide sufficient pro­tection against noise.
- The inverter equipment, private power generator, high-frequency medical equipment, or radio com-
munication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs med­ical treatment or image broadcasting.
• Do not install the product where it is exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator
fins, could cause product malfunction or inefficient operation.
Operation
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or dam-
age its parts.
• Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
• Make the connections securely so that the outside force of the cable may not be applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure, or
personal injury.
• Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
- A bad connection may cause water leakage.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspending it at the specified positions on the unit base. Also sup-
port the outdoor unit at four points so that it cannot slip sideways.
!
6
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause stabs or other in­juries.
- Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
• Turn on the power at least 6 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
• Do not touch any of the refrigerant piping during and after operation.
- It can cause a burn or frostbite.
• Do not operate the air conditioner with the panels or guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not directly turn off the main power switch after stopping operation.
- Wait at least 5 minutes before turning off the main power switch. Otherwise it may result in water leakage or other problems.
• Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the indoor unit PCB.
• Use a firm stool or ladder when cleaning or maintaining the air conditioner.
- Be careful and avoid personal injury.
• Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
- There are sharp and moving parts that could cause personal injury.
7
2 TIPS FOR SAVING EN-
ERGY
3 IMPORTANT SAFETY IN-
STRUCTIONS
8 INSTALLATION
PROCESS
9 OUTDOOR UNITS IN-
FORMATION
11 ENVIRONMENT-
FRIENDLY ALTERNATIVE REFRIGERANT R410A
12 SELECT THE BEST LO-
CATION
13 INSTALLATION SPACE
13 Individual Installation
15 LIFTING METHOD 16 INSTALLATION
16 The location of the Anchor bolts 17 Foundation for Installation 18 Preparation of Piping 21 Plumbing materials and storage meth-
ods
23 REFRIGERANT PIPING
INSTALLATION
23 Precautions on Pipe connection / Valve
operation
24 PIPE CONNECTIONS BE-
TWEEN INDOOR AND OUTDOOR UNIT
24 Preparation Work 25 Pipe Drawing Out during Single / Series
connection
27 Refrigerant piping system
40 Refrigerant charging 41 Distribution Method 42 Branch pipe Fitting 46 Leak Test and Vacuum drying 48 Vacuum Mode 49 Thermal insulation of refrigerant piping
50 ELECTRICAL WIRING
50 Caution 52 Control box and connecting position of
wiring
53 Communication and Power Cables 54 Wiring of main power supply and
equipment capacity
55 Field Wiring 61 Checking the setting of outdoor units 62 Automatic Addressing 65 Group Number setting 66 Cool & Heat selector 67 Static pressure compensation mode 68 Night Low Noise Function 69 Overall defrost mode 70 Setting the ODU address 71 Snow removal & rapid defrost 72 IDU capacity adjusting 73 Target pressure adjusting 74 Comfort Operation 75 Auto Dust Removal 76 Self-Diagnosis Function
79 CAUTION FOR REFRIG-
ERANT LEAK
79 Introduction 79 Checking procedure of limiting concen-
tration
81 INSTALLATION GUIDE
AT THE SEASIDE
TABLE OF CONTENTS
TABLE OF CONTENTS
ENGLISH
8
INSTALLATION PROCESS
ENGLISH
CAUTION
• The above list indicates the order in which the individual work operations are normally car­ried out but this order may be varied where local conditions warrants such change.
• The thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8 MPa.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)
!
INSTALLATION PROCESS
Determination of division work
Preparation of contract drawings
Sleeve and insert work
Installation of indoor unit
Refrigerant piping work
Drain pipe work
Duct work
Heat insulation work
Electrical work
(connection circuits and drive circuits)
Airtight test
Vacuum drying
Additional charge of refrigerant
Fit facing panels
Indicate clearly who will be responsible for switch setting.
Make connection clearly between outdoor, indoor, remote controller and option.
Take account of gradient of drain piping
Check model name to make sure the fitting is made correctly
Special attention to dryness, cleanness and tightness
Adjust to downward gradient
Make sure airflow is sufficient
Make sure no gaps are left where the insulating materials are joined
Multiple core cable must not be used. (suitable cable should be selected)
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Outdoor unit foundation work
Installation of outdoor unit
2
) there must be no drop in pressure.
The foundation must be level even
Avoid short circuits and ensure sufficient space is allowed for service
Automatic addressing of indoor unit
Test run adjustment
Transfer to customer with explanation
Refer to automatic addressing flowchart Preheat the crank case with the electrical heater for more than 6 hours.
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order
OUTDOOR UNITS INFORMATION
9
ENGLISH
Power Supply : 3Ø, 400V, 60Hz / 3Ø, 380 - 415V, 50Hz
Model Name : ARUN***LTH4
CAUTION
Notes : * We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and dis­cuss the requirement like below.
• If the operation of indoor unit is more than 130%, the airflow is operated as low in the all indoor units.
• The number of ( ) means the number of Max. connectable indoor units, when the con­nected capacity of indoor units is in the table above.
Combination Ratio(50~200%)
Outdoor Number Connection Ratio
Single outdoor units 200%
Double outdoor units 160%
Triple outdoor units 130%
!
OUTDOOR UNITS INFORMATION
Unit
1 Outdoor Unit 2 Outdoor Unit
System(HP)
16 18 20 22
Model
Combination Unit
ARUN160LTH4 ARUN180LTH4 ARUN200LTH4 ARUN220LTH4
Independent Unit
ARUN160LTH4 ARUN100LTH4 ARUN100LTH4 ARUN120LTH4
ARUN080LTH4 ARUN100LTH4 ARUN100LTH4 Refrigerant Precharged Amount
kg
10 6.5 x 2 6.5 x 2 8.5 + 6.5
lbs
22 14.3 x 2 14.3 x 2 18.7 + 14.3
Number of maxmum connectable indoor units 26(40) 29(45) 32(50) 35(44)
Net Weight
kg
280 × 1 195 × 1 + 201 × 1 201 × 1 + 201 × 1 235 × 1 + 201 × 1
lbs
617 × 1 430 × 1 + 433 × 1 433 × 1 + 433 × 1 518 × 1 + 433 × 1
Dimensions (WxHxD)
mm
(1,240 x 1,680 x 760)
x 1
(920×1,680×760) × 1
+ (920×1,680×760) × 1
(920×1,680×760) × 1 +
(920×1,680×760) × 1
(1,240 x 1,680 x 760) x 1
+ (920×1,680×760) × 1
inch
(48-13/16 × 66-5/32 ×
29-29/32) x 1
(36-7/32 × 66-5/32 × 29 -29/32) x 1+
(36-7/32 × 66-5/32 × 29-29/32) x 1
(36-7/32 × 66-5/32 × 29-29/32) x 1+
(36-7/32 × 66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-29/32) x 1
+ (36-7/32 × 66-5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 12.7(1/2) Ø 15.88(5/8) Ø 15.88(5/8) Ø 15.88(5/8)
mm(inch)
Ø 28.58(1 1/8) Ø 28.58(1 1/8) Ø 28.58(1 1/8) Ø 28.58(1 1/8)
Unit
1 Outdoor Unit
System(HP) 8
10 12 14
Model
Combination Unit ARUN080LTH4
ARUN100LTH4 ARUN120LTH4 ARUN140LTH4
Independent Unit ARUN080LTH4
ARUN100LTH4 ARUN120LTH4 ARUN140LTH4 Refrigerant Precharged Amount
kg 6.5
6.5 8.5 8.5
lbs 16.5
16.5 18.7 18.7
Number of maxmum connectable indoor units
13(20)
16(25) 20(30) 23(35)
Net Weight
kg 195 × 1
201 × 1 235 × 1 270 × 1
lbs 430 × 1
433 × 1 518 × 1 595 × 1
Dimensions (WxHxD)
mm
(920×1,680×760) × 1
(920×1,680×760) × 1
(1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1
inch
(36-7/32 × 66-5/32 × 29-29/32) x 1
(36-7/32 × 66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-29/32) x 1
Piping Conections
mm(inch) Ø 9.52(3/8)
Ø 9.52(3/8) Ø 12.7(1/2) Ø 12.7(1/2)
mm(inch) Ø 19.05(3/4)
Ø 22.2(7/8) Ø 28.58(1 1/8) Ø 28.58(1 1/8)
10
OUTDOOR UNITS INFORMATION
ENGLISH
Unit
2 Outdoor Unit
System(HP)
24 26 28 30
Model
Combination Unit
ARUN240LTH4 ARUN260LTH4 ARUN280LTH4 ARUN300LTH4
Independent Unit
ARUN140LTH4 ARUN160LTH4 ARUN160LTH4 ARUN160LTH4 ARUN100LTH4 ARUN100LTH4 ARUN120LTH4 ARUN140LTH4
Refrigerant Precharged Amount
kg
8.5 + 6.5 10 + 6.5 10 + 8.5 10 + 8.5
lbs
18.7 + 14.3 22 + 14.3 22 + 18.7 22 + 18.7
Number of maxmum connectable indoor units 39(48) 42(52) 45(56) 49(60)
Net Weight
kg
270 × 1 + 201 × 1 280 × 1 + 201 × 1 280 × 1 + 235 × 1 280 × 1 + 270 × 1
lbs
595 × 1 + 433 × 1 617 × 1 + 433 × 1 518 × 1 + 617 × 1 617 × 1 + 595 × 1
Dimensions (WxHxD)
mm
(1,240 x 1,680 x 760) x 1
+ (920×1,680×760) × 1
(1,240 x 1,680 x 760) x 1
+ (920×1,680×760) × 1
(1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
(1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
inch
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (36-7/32 ×
66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (36-7/32 ×
66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 15.88(5/8) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 34.9(1 3/8) Ø 34.9(1 3/8) Ø 34.9(1 3/8) Ø 34.9(1 3/8)
Unit
3 Outdoor Unit
System(HP)
32 34 36 38
Model
Combination Unit
ARUN320LTH4 ARUN340LTH4 ARUN360LTH4 ARUN380LTH4
Independent Unit
ARUN160LTH4 ARUN140LTH4 ARUN140LTH4 ARUN160LTH4 ARUN160LTH4 ARUN100LTH4 ARUN120LTH4 ARUN120LTH4
ARUN100LTH4 ARUN100LTH4 ARUN100LTH4 Refrigerant Precharged Amount
kg
10 + 10 8.5 +(6.5 x 2) (8.5 x 2) + 6.5 10 + 8.5 + 6.5
lbs
22 + 22 18.7 + (14.3 x 2) (18.7 x 2) + 14.3 22 + 18.7 + 14.3
Number of maxmum connectable indoor units 52(64) 55(64) 58(64) 61(64)
Net Weight
kg
280 × 1 + 280 × 1
270 × 1 + 201 × 1 + 201 × 1 270 × 1 + 235 × 1 + 201 × 1 280 × 1 + 235 × 1 + 201 × 1
lbs
617 × 1 + 617 × 1
595 × 1 + 433 × 1 + 433 × 1 595 × 1 + 518 × 1 + 433 × 1 617 × 1 + 518 × 1 + 433 × 1
Dimensions (WxHxD)
mm
(1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
(1,240 x 1,680 x 760) x 1 +
(920×1,680×760) × 1 +
(920×1,680×760) × 1
(1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
(920×1,680×760) × 1
(1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
(920×1,680×760) × 1
inch
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (36-7/32 ×
66-5/32 × 29-29/32) x 1 +
(36-7/32 × 66-5/32 ×
29-29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1 +
(36-7/32 × 66-5/32 × 29-
29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1 +
(36-7/32 × 66-5/32 ×
29-29/32) x 1
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 34.9(1 3/8) Ø 34.9(1 3/8) Ø 41.3(1 5/8) Ø 41.3(1 5/8)
Unit
3 Outdoor Unit
System(HP)
40 42 44 46
48
Model
Combination Unit
ARUN400LTH4 ARUN440LTH4 ARUN440LTH4 ARUN460LTH4
ARUN480LTH4
Independent Unit
ARUN160LTH4 ARUN160LTH4 ARUN160LTH4 ARUN160LTH4
ARUN160LTH4
ARUN120LTH4 ARUN140LTH4 ARUN160LTH4 ARUN160LTH4
ARUN160LTH4
ARUN120LTH4 ARUN120LTH4 ARUN120LTH4 ARUN140LTH4
ARUN160LTH4 Refrigerant Precharged Amount
kg
10 + (8.5 x 2) (8.5 x 2) + 10 (10 x 2) + 8.5 (10 x 2) + 8.5
10 x 3
lbs
22 + (18.7 x 2) (18.7 x 2) + 22 (22 x 2) + 18.7 (22 x 2) + 18.7
22 x 3
Number of maxmum connectable indoor units 64 64 64 64
64
Net Weight
kg
280 × 1 + 235 × 1 + 235 × 1 280 x 1 + 270 x 1 + 235 x 1 280 × 1 + 280 × 1 + 235 × 1 280 × 1 + 280 × 1 + 270 × 1 280 × 1 + 280 × 1 + 280 × 1
lbs
617 × 1 + 518 × 1 + 518 × 1 617 x 1 + 596 x 1 + 518 x 1
617 × 1 + 617 × 1 + 518 × 1
617 × 1 + 617 × 1 + 595 × 1 617 × 1 + 617 × 1 + 617 × 1
Dimensions (WxHxD)
mm
(1,240 x 1,680 x 760) x 1 + (1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
(1,240 x 1,680 x 760) x 1 + (1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
(1,240 x 1,680 x 760) x 1 + (1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
(1,240 x 1,680 x 760) x 1 + (1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
(1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1 +
(1,240 x 1,680 x 760) x 1
inch
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1 +
(48-13/16 × 66-5/32 ×
29-29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1 + (48-13/16 × 66-5/32 × 29-
29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1 +
(48-13/16 × 66-5/32 ×
29-29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1 +
(48-13/16 × 66-5/32 ×
29-29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 1 + (48-13/16 ×
66-5/32 × 29-29/32) x 1 +
(48-13/16 × 66-5/32 ×
29-29/32) x 1
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
Ø 19.05(3/4)
mm(inch)
Ø 41.3(1 5/8) Ø 41.3(1 5/8) Ø 41.3(1 5/8) Ø 41.3(1 5/8)
Ø 41.3(1 5/8)
ENVIRONMENT-FRIENDLY ALTERNATIVE REFRIGERANT R410A
11
ENGLISH
CAUTION
• The wall thickness of the piping should comply with the relevant local and national regula­tions for the designed pressure 3.8 MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also considered during the installation. R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0. These days the developed countries have approved it as the environment-friendly refrigerant and encouraged to use it widely to prevent environment pollution.
!
ENVIRONMENT-FRIENDLY ALTERNATIVE RE­FRIGERANT R410A
12
SELECT THE BEST LOCATION
ENGLISH
Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors by noise from unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stag­nation, and leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the outdoor unit.
• If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid bad condition when addi­tionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of in-
stalling the product at a place With a high humidity in winter (near beach, coast, lake, etc.) (Ex : Rooftop where there is always sunshine.)
SELECT THE BEST LOCATION
INSTALLATION SPACE
13
ENGLISH
Individual Installation
During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space as shown in the figures below.
INSTALLATION SPACE
Category Installation Space
Distance
(Side Space49 mm)
4 sides
are walls
A50 B100 C50 D500
A50 B100 C50 D500 E100
A50 B100 C50 D500 E100 F500
A50 B100 C50 D100 E100 F500
Rear to
Rear
A50 B500 C50 D500 E100 F600
A50 B500 C50 D500 E100 F900
A50 B500 C50 D500 E100 F1200
A
C
B
D
A E
B
D
A
C
B
D
E
C
AE
B
D
A
C
B
D
E
C
A E
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A E
B
F
C
D
A E
B
F
C
D
A E
B
F
D
E
C
A
B
F
C
D
14
INSTALLATION SPACE
ENGLISH
*Distance is more than 49 cm because of Auto Dust Removal mode.
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product
can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes
on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Install the outdoor unit at the higher installation console by 50 cm than the average snowfall
(annual average snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always
remove snow for operation.
- The height of H frame must be more than 2 times the snowfall and its width shall not ex­ceed the width of the product. (If width of the frame is wider than that of the product, snow may accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
Category Installation Space Distance
Only 2
sides are
walls
Limita-
tions on the height of the wall
(Refer to 4 side walls)
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
B
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A
E
B
A
B
E
h2
h1
1500
A
B
500
• The height of the wall on the front side must be 1500 mm or less.
• The height of the wall on the inlet side must be 500 mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than the limit, there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1.
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1500
- h2 = B(Actual height) - 500
A50 B300
A200 B300 E400
15
ENGLISH
LIFTING METHOD
CAUTION
Be very careful while carrying the product.
• Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
• When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall.
• Use 2 belts of at least 8 m long.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
• When carrying the suspended, unit pass the ropes under the unit and use the two suspension points each at the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
Locking points for
transportation ropes
!
LIFTING METHOD
Forklift Carrying Hole
Forklift Carrying Guide
16
ENGLISH
INSTALLATION
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100 mm under the Unit’s legs before being fixed.
• The outdoor unit supports should have minimum height of 200 mm.
• Anchor bolts must be inserted at least 75 mm.
Chassis Outdoor Unit Capacity A(mm) B(mm)
UX2 8~10 HP 920 792 UX3 12~16 HP 1240 1102
INSTALLATION
For outdoor units should not be supported only by the corner supports.
6565
At least 100 mm
At least 100 mm
At least 100 mm
At least 100
At least 65At least 65
At least 100 mm
Center of the Unit
At least 100 mm
mm
Center of the Unit
Unit : mm
730
760
17
ENGLISH
INSTALLATION
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200 mm).
At least 200 mm
Unit : mm
200
75
75
200
100
The corner part must be fixed firmly. Otherwise,
the support for the installation may be bent.
Get and use M10 Anchor bolt.Put Cushion Pad between the outdoor unit and
ground support for the vibration protection in wide area.
Space for pipes and wiring (Pipes and wirings for
bottom side)
H-beam supportConcrete support
CAUTION
• Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit Base Pan before fix­ing the bolt. It may cause the unstable state of the outdoor settlement, and may cause freezing of the heat exchanger resulting in abnormal operations.
• Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit before welding. Not removing Pallet(Wood Support) causes hazard of fire during welding.
WARNING
• Install where it can sufficiently support the weight of the outdoor unit. If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake. If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treat­ment(treatment of the water flowing out of the outdoor unit in operation), and the pas­sages of the pipe and wiring, when making the ground support.
• Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet. The tube or pipe may freeze and the water may not be drained.
Pallet(Wood Support)
- Remove before Installation
!
!
18
ENGLISH
INSTALLATION
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
- Use the accessory piping kit or the pipes pur­chased locally.
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5 m longer than the pipe length.
Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe to down­ward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
Flaring work
- Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as in­dicated dimension in the table above.
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the flared section and do flaring work again.
Indoor unit [kW(Btu/h]
Pipe " A "
Gas Liquid Gas Liquid
<5.6(19,100) 1/2" 1/4" 0.5~0.8 0~0.5 <16.0(54,600) 5/8" 3/8" 0.8~1.0 0.5~0.8 <22.4(76,400) 3/4" 3/8" 1.0~1.3 0.5~0.8
Copper
tube
90
Slanted Uneven Rough
Pipe
Reamer
Point down
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Preparation of Piping
19
ENGLISH
INSTALLATION
Flare shape and flare nut tightening torque
Opening shutoff valve
Precautions when connecting pipes
- See the following table for flare part machining dimensions.
- When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first. (Use ester oil or ether oil.)
-
See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
- After all the piping has been connected, use nitrogen to perform a gas leak check.
1 Remove the cap and turn the valve counter clockwise with the hexagon wrench.
2 Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3 Make sure to tighten the cap securely.
pipe size tightening torque(N·cm) A(mm) flare shape
Ø9.52 38±4 12.8-13.2
Ø12.7 55±6 16.2-16.6
Ø15.88 75±7 19.3-19.7
CAUTION
• Always use a charge hose for service port connection.
• After tightening the cap, check that no refrigerant leaks are present.
• When loosening a flare nut, always use two wrenches in combination, When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare(inner and outer faces) with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as the initial tightening.
Union
!
2
90
A
45
2
R=0.4~0.8
20
ENGLISH
INSTALLATION
Insulation of shutoff valve
1
Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120 °C).
2 Precautions in high humidity circumstance:
This air conditioner has been tested according to the "ISO Conditions with Mist" and confirmed that there is not any default. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23 °C), water drops are liable to fall. In this case, add heat insulation material according to the fol­lowing procedure:
- Heat insulation material to be prepared... EPDM (Ethylene Propylene Diene Meth­ylene)-over 120 °C the heat-resistance temperature.
- Add the insulation over 10 mm thickness at high humidity environment.
Closing shutoff valve
1 Remove the cap and turn the valve clockwise with the hexagon wrench.
2 Securely tighten the valve until the shaft contacts the main body seal.
3 Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
Shut off
Valvesize
Tightening torque N·m (Turn clockwise to close)
Shaft (valve body)
Cap
(valve lid)
Service
port
Flare nut
Gas line piping At­tached to
unit
Closed Opened
Hexagonal
wrench
Ø 6.35
6.0±0.6
25±3
4 mm
17.6±2.0
12.7±2
16±2
-
Ø 9.52 38±4
Ø 12.7 10.0±1.0 20.0±2.0 55±6
Ø 15.88 12.0±1.2
5 mm
25.0±2.5
75±7
Ø 19.05 14.0±1.4 110±10
Ø 22.2
30.0±3.0 8 mm -
Ø 25.4 25±3
Fastening band (accessory)
Refrigerant piping
Indoor unit
Thermal insulator (accessory)
21
ENGLISH
INSTALLATION
Plumbing materials and storage methods
Pipe must be able to obtain the specified thickness and should be used with low impurities. Also when handling storage, pipe must be careful to prevent a fracture, deformity and wound. Should not be mixed with contaminations such as dust, moisture.
Refrigerant piping on three principles
Drying Cleanliness Airtight
Should be no moisture inside No dust inside.
There is no refrigerant leak-
age
Items
Moisture
Dust
Leakage
Cause failure
- Significant hydrolysis of re­frigerant oil
- Degradation of refrigerant oil
- Poor insulation of the com­pressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Degradation of refrigerant oil
- Poor insulation of the com­pressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Gas shortages
- Degradation of refrigerant oil
- Poor insulation of the com­pressor
- Do not cold and warm
Counter­measure
- No moisture in the pipe
- Until the connection is completed, the plumbing pipe entrance should be strictly controlled.
- Stop plumbing at rainy day.
- Pipe entrance should be taken side or bottom.
- When removal burr after cutting pipe, pipe entrance should be taken down.
- Pipe entrance should be fitted cap when pass through the walls.
- No dust in the pipe.
- Until the connection is completed, the plumbing pipe entrance should be strictly controlled.
- Pipe entrance should be taken side or bottom.
- When removal burr after cutting pipe, pipe entrance should be taken down.
- Pipe entrance should be fitted cap when pass through the walls.
- Airtightness test should be.
- Brazing operations to com­ply with standards.
- Flare to comply with stan­dards.
- Flange connections to comply with standards.
22
ENGLISH
INSTALLATION
Nitrogen substitution method
Welding, as when heating without nitrogen substitution a large amount of the oxide film is formed on the internal piping.
The oxide film is a caused by clogging EEV, Capillary, oil hole of accumulator and suction hole of oil pump in compressor.
It prevents normal operation of the compressor. In order to avoid this problem, Welding should be done after replacing air by nitrogen gas. When welding plumbing pipe, the work is required.
1 Always use the nitrogen.(not use oxygen, carbon dioxide, and a Chevron gas):
Please use the following nitrogen pressure 0.02 MPa Oxygen – Promotes oxidative degradation of refrigerant oil. Because it is flammable, it is strictly prohibited to use Carbon dioxide – Degrade the drying characteristics of gas Chevron Gas – Toxic gas occurs when exposed to direct flame.
2 Always use a pressure reducing valve.
3. Please do not use commercially available antioxidant. The residual material seems to be the oxide scale is observed. In fact, due to the organic acids generated by oxidation of the alcohol contained in the anti­oxidants, ants nest corrosion occurs. (causes of organic acid  alcohol + copper + water + temperature)
CAUTION
!
Regulator
Welding Point
Nitrogen gas Pressure 0.02MPa less
Oxide scale
Note) should not block the outlet side. When the internal pressure in pipe is abo ve the atmospheric pressure, pinhole is o ccurred and it is a leakage cause.
Taping (Should not contain air)
Auxiliary valve
Nitrogen
23
ENGLISH
REFRIGERANT PIPING INSTALLATION
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the branching pipes, and the refrigerant pipe coming out of the outdoor unit is divided at the end to connect to each indoor unit. Flare connection for the indoor unit, and welding connection for the outdoor pipe and the branching parts.
- Use hexagonal wrench to open/close the valve.
CAUTION
Please block the pipe knock outs of the front and side panels after installing the pipes. (Animals or foreign objects may be brought in to damage wires.)
!
WARNING
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas leakage after the work.
!
REFRIGERANT PIPING INSTALLATION
Service Port
Liquid pipe
Gas pipe
Refrigerant
Charging Port
24
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
- Pipe connections can be done on the front side or on the side according to the installation envi­ronments.
- Be sure to let 0.2 kgf/cm² Nitrogen flow in the pipe when welding.
- If Nitrogen was not flown during welding, many oxidized membranes may from inside the pipe and disturb the normal operations of valves and condensers.
Nitrogen Direction
Preparation Work
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or Bottom pipe drawing outs.
CAUTION
• Do not give damage to the pipe/base during the Knock Out work.
• Proceed to pipe work after removing burr after Knock Out work.
• Perform sleeve work to prevent damage to the wire when connecting wires using knock Outs.
!
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Regulator
Valve
Nitrogen
Left Side Pipe
Draw Out
Right Side Pipe Draw Out
Front Pipe Draw Out
Refrigerant Pipe
Nitrogen
Nitrogen Direction
Direction
Taping
Removal Area for Liquid/Gas pipe bottom side connections.
25
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Remove leakage prevention cap
• Remove the leakage prevention cap attached to the outdoor unit service valve before pipe work.
• Proceed the leakage prevention cap removal as follows:
- Verify whether the liquid/gas pipes are locked.
- Extract remaining refrigerant or air inside using the service port.
- Remove the leakage prevention cap
Pipe Drawing Out during Single / Series connection
Method of drawing out pipes on the front side
- Proceed with the pipe work as shown in the below figure for front side pipe drawing out.
Service Port
Liquid pipe
Gas pipe
Leakage Prevention Cap
Refrigerant Charging Port
Pipe Knock Out for Liquid/Gas pipes
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Method of drawing out pipes on the bottom side
- Drawing out common pipe through side panel
ENGLISH
26
Liquid pipe Gas pipe
Remove only liquid/gas pipe Knock out
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Y branch method
1 Outdoor Units Example : 5 Indoor Units connected
: Outdoor Unit: 1st branch (Y branch) : Indoor Units
2 Outdoor Units Example : 5 Indoor Units connected
: Outdoor Unit: 1st branch (Y branch) : Indoor Units: Downward Indoor Unit: Connection branch pipe between Outdoor
units: ARCNN21
Piping length from outdoor branch to outdoor unit 10 m, equivalent length:max 13 m (for 18HP or more)
Conditional Application To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
• Diameter of pipes between first branch and the last branch should be increased by one step, except pipe diameter B,C,D is same as Diameter A Ø6.35
Ø 9.52 →Ø 12.7 →Ø 15.88 →Ø 19.05 →Ø 22.2 →Ø 25.4*, Ø 28.58 →Ø 31.8*, Ø 34.9 →Ø 38.1* * : It is not necessary to size up.
• While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice. A+Bx2+Cx2+Dx2+a+b+c+d+e 1,000 m
• Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) 40 m
• [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] 40 m
Refrigerant piping system
ENGLISH
27
L150 m (200 m : Conditional application)
l 40 m (90 m : Conditional application)
H 110 m
h 40 m
10 m or
less
Slave
Slave
Master
h1
Master
Slave
Master
H 110 m
L150 m (200 m : Conditional application)
l 40 m (90 m : Conditional application)
h 40 m
ODU Capacity Master ≥ Slave
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
3 Outdoor Units Example : 5 Indoor Units connected
: Outdoor Unit: 1st branch (Y branch) : Indoor Units: Downward Indoor Unit: Connection branch pipe between Outdoor
units: ARCNN31
: Connection branch pipe between Outdoor
units: ARCNN21
Piping length form outdoor branch to outdoor unit 10 m, equivalent length : max. 13 m (for 18 HP or more)
Conditional Application To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
• Diameter of pipes between first branch and the last branch should be increased by one step, except pipe diameter B,C,D is same as Diameter A Ø6.35
Ø 9.52 →Ø 12.7 →Ø 15.88 →Ø 19.05 →Ø 22.2 →Ø 25.4*, Ø 28.58 →Ø 31.8*, Ø 34.9 →Ø 38.1* * : It is not necessary to size up.
• While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice. A+Bx2+Cx2+Dx2+a+b+c+d+e 1,000 m
• Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) 40 m
• [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] 40 m
ENGLISH
28
10 m or
less
Slave2
Slave1
Master
h1
ODU Capacity
Master ≥ Slave1 ≥ Slave 2
H 110 m
L150 m (200 m : Conditional application)
l 40 m (90 m : Conditional application)
h 40 m
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Refrigerant pipe diameter from branch to branch (B,C,D)
• * : Assume equivalent piping length of Y branch to be 0.5 m, that of header to be 1 m, calculation purpose.
• ** : To apply Conditional Application
Downward Indoor Unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
22.4(76,400)
Ø9.52(3/8) Ø19.05(3/4) < 33.6(114,700) Ø9.52(3/8) Ø22.2(7/8) < 50.4(172,000) Ø12.7(1/2) Ø28.58(1-1/8 ) < 67.2(229,400) Ø15.88(5/8) Ø28.58(1-1/8 ) < 72.8(248.500) Ø15.88(5/8) Ø34.9(1-3/8)
< 100.8(344,000) Ø19.05(3/4) Ø34.9(1-3/8) < 173.6(592,500) Ø19.05(3/4) Ø41.3(1-5/8)
Total pipe length = A+B+C+D+a+b+c+d+e 1,000 m
L
Longest pipe length Equivalent pipe length A+B+C+D+e 150 m(200 m**) *A+B+C+D+e 175 m(225 m**)
l
Longest pipe length after 1st branch B+C+D+e 40 m(90 m**)
H
Difference in height (Outdoor Unit Indoor Unit) H 110 m
h
Difference in height (Indoor Unit Indoor Unit) h 40 m
h1
Difference in height (Outdoor Unit Outdoor Unit) h1 5 m
WARNING
When the any one (or both ) of below conditions are satisfied, the diameter of main pipe (A) must be increased according to below table.
- The equivalent length between outdoor unit and the farthest indoor unit is 90 m or more (Liquid and Gas pipes are increased)
- The level difference (Outdoor unit Indoor unit) is 50 m or more (Only liquid pipe is in­creased)
!
ENGLISH
29
30
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Refrigerant pipe diameter from outdoor unit to first branch. (A)
* If the step up size is not available, you can not select the next higher size available.
Upward Out-
door unit
total capacity
Standard Pipe Diameter
Increased Pipe Diameter
When pipe length is 90 m or
more from ODU to 1st branch
When level difference is 50 m
or more
HP
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
8 Ø 9.52(3/8) Ø 19.05(3/4) Ø 12.7(1/2) Ø 22.2(7/8) Ø 12.7(1/2) not increased
10 Ø 9.52(3/8) Ø 22.2(7/8) Ø 12.7(1/2) Ø 25.4(1) Ø 12.7(1/2) not increased
12 ~ 14 Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) not increased Ø 15.88(5/8) not increased
16 Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) Ø 31.8(1-1/4) Ø 15.88(5/8) not increased
18 ~ 22 Ø 15.88(5/8) Ø 28.58(1-1/8) Ø 19.05(3/4) Ø 31.8(1-1/4) Ø 19.05(3/4) not increased
24 Ø 15.88(5/8) Ø 34.9(1-3/8) Ø 19.05(3/4) not increased Ø 19.05(3/4) not increased 26 ~ 34 Ø 19.05(3/4) Ø 34.9(1-3/8) Ø 22.2(7/8) Ø 38.1(1-1/2) Ø 22.2(7/8) not increased 36 ~ 48 Ø 19.05(3/4) Ø 41.3(1-5/8) Ø 22.2(7/8) not increased Ø 22.2(7/8) not increased
Header Method
1 Outdoor Unit Example : 6 Indoor Units connected
: Outdoor Unit: 1st branch: Indoor Units: Sealed piping
2 Outdoor Units Example : 6 Indoor Units connected
: Outdoor Unit: Header branch: Indoor Units: Sealing: Connection branch pipe between Outdoor
units: ARCNN21
H 110 m
L 200 m
40 m
10 m or less
L 110 m
40 m
Slave
h1
Master
40 m
Slave
Master
L 200 m
Slave
Master
ODU Capacity Master ≥ Slave
40 m
31
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
3 Outdoor Units Example : 6 Indoor Units connected
: Outdoor Unit: Header branch: Indoor Units: Sealing: Connection branch pipe between Outdoor
units: ARCNN31
: Connection branch pipe between Outdoor
units: ARCNN21
Branch pipe can not be used after header
Total pipe length = A+a+b+c+d+e+f 1,000 m
L
Longest pipe length *Equivalent pipe length A+f 200 m A+f 225 m
l
Longest pipe length after 1st branch f 40 m
H
Difference in height (Outdoor Unit Indoor Unit) H 110 m
h
Difference in height (Indoor Unit Indoor Unit) h 40 m
h1
Difference in height (Outdoor Unit Outdoor Unit) h1 5 m
Slave2
Slave1
Master
h1
10 m or less
H 110 m
40 m
ODU Capacity
Master ≥ Slave1 ≥ Slave2
L 200 m
40 m
32
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
• * : Assume equivalent piping length of Y branch to be 0.5 m, that of header to be 1 m, cal­culation purpose
• Indoor Unit should be installed at lower position than the header.
• Piping length from outdoor branch to outdoor unit 10 m, equivalent length : max 13 m
(for 22HP or more)
1 Outdoor Units Example : 5 Indoor Units connected
: Outdoor Unit: 1st branch (Y branch) : Y branch: Indoor Unit: Header: Sealed piping
2 Outdoor Units Example : 5 Indoor Units connected
: Outdoor Unit: 1st branch: Y branch: Indoor Unit: Connection branch pipe between Outdoor
units: ARCNN21
: Header: Sealed piping
Branch pipe can not be used after header
Branch pipe can not be used after header
Combination of Y branch/header method
WARNING
Pipe length after header branching (a~f) It is recommended that difference in length of the pipes connected to the Indoor Units is
minimized. Performance difference between Indoor Units may occur.
!
L 110 m
L 150 m(200 m : Conditional application)
40 m(90 m : Conditional application)
h 40 m
10 m or less
H 110 m
Slave
h1
Slave
Master
L 150 m(200 m : Conditional application)
40 m(90 m : Conditional application)
Slave
Master
Master
ODU Capacity
Master ≥ Slave
h 40 m
33
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
3 Outdoor Units Example : 5 Indoor Units connected
: Outdoor Unit: 1st branch(Y branch): Y branch: Indoor Unit: Connection branch pipe between Outdoor
units: ARCNN31
: Connection branch pipe between Outdoor
units: ARCNN21
: Header: Sealing
F
E
Branch pipe can not be used after header
Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
22.4(76,400)
Ø9.52(3/8) Ø19.05(3/4) < 33.6(114,700) Ø9.52(3/8) Ø22.2(7/8) < 50.4(172,000) Ø12.7(1/2) Ø28.58(1-1/8 ) < 67.2(229,400) Ø15.88(5/8) Ø28.58(1-1/8 ) < 72.8(248.500) Ø15.88(5/8) Ø34.9(1-3/8)
< 100.8(344,000) Ø19.05(3/4) Ø34.9(1-3/8) < 173.6(592,500) Ø19.05(3/4) Ø41.3(1-5/8)
10 m or less
Slave2
Slave1
Master
h1
F
E
Master ≥ Slave1 ≥ Slave2
H 110 m
ODU Capacity
L 150 m(200 m : Conditional application)
40 m(90 m : Conditional application)
h 40 m
34
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
• * : Assume equivalent pipe length of Y branch to be 0.5 m, that of header to be 1 m, cal­culation purpose
• ** : To apply Conditional Application
• Indoor Unit should be installed at lower position than the header.
Total pipe length = A+B+C+a+b+c+d+e 1,000 m
L
Longest pipe length *Equivalent pipe length A+B+b 150 m(200 m**) A+B+b 175 m(225 m**)
l
Longest pipe length after 1st branch B+b 40 m(90 m**)
H
Difference in height (Outdoor Unit Indoor Unit) H 110 m
h
Difference in height (Indoor Unit Indoor Unit) h 40 m
h1
Difference in height (Outdoor Unit Outdoor Unit) h1 5 m
Refrigerant pipe diameter from outdoor unit to first branch. (A)
* If the step up size is not available, you can not select the next higher size available.
Upward Out-
door unit
total capacity
Standard Pipe Diameter
Increased Pipe Diameter
When pipe length is 90 m or
more from ODU to 1st branch
When level difference is 50 m
or more
HP
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
Liquid pipe [mm(inch)]
Gas pipe
[mm(inch)]
8 Ø 9.52(3/8) Ø 19.05(3/4) Ø 12.7(1/2) Ø 22.2(7/8) Ø 12.7(1/2) not increased
10 Ø 9.52(3/8) Ø 22.2(7/8) Ø 12.7(1/2) Ø 25.4(1) Ø 12.7(1/2) not increased
12 ~ 14 Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) not increased Ø 15.88(5/8) not increased
16 Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) Ø 31.8(1-1/4) Ø 15.88(5/8) not increased
18 ~ 22 Ø 15.88(5/8) Ø 28.58(1-1/8) Ø 19.05(3/4) Ø 31.8(1-1/4) Ø 19.05(3/4) not increased
24 Ø 15.88(5/8) Ø 34.9(1-3/8) Ø 19.05(3/4) not increased Ø 19.05(3/4) not increased 26 ~ 34 Ø 19.05(3/4) Ø 34.9(1-3/8) Ø 22.2(7/8) Ø 38.1(1-1/2) Ø 22.2(7/8) not increased 36 ~ 48 Ø 19.05(3/4) Ø 41.3(1-5/8) Ø 22.2(7/8) not increased Ø 22.2(7/8) not increased
WARNING
• It is recommended that difference of piping length for pipes connected to the Indoor Unit is minimized. Performance difference between Indoor Units may occur.
• When the any one (or both ) of below conditions are satisfied, the diameter of main pipe (A) must be increased according to below table.
- The equivalent length between outdoor unit and the farthest indoor unit is 90 m or more (Liquid and Gas pipes are increased)
- The level difference (Outdoor unit Indoor unit) is 50 m or more (Only liquid pipe is in­creased)
!
35
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Outdoor unit Connection
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2) < 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8) < 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
<28.0(95,900 Ø 9.52(3/8) Ø 22.2(7/8)
WARNING
• In case of pipe diameter B connected after first branch is bigger than the main pipe diame­ter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio 120% is connected to 24 HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(Gas pipe), Ø15.88(liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor unit ombination(80.6 kW) : Ø34.9(gas pipe), Ø19.05(liquid pipe)
Therefore, pipe diameter B connected after first branch would be Ø34.9(gas pipe) / Ø15.88(liquid pipe) which is same with main pipe diameter.
[Example] Do not choose the main pipe diameter by downward indoor unit total capacity but its outdoor unit model name. Do not let the connection pipe from branch to branch exceed the main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 22 HP (61.6 kW) outdoor unit to 130% of its
system capacity (80.1 kW) and branching 7 k (2.2 kW) indoor unit at the 1st branch.
1) Main pipe diameter(22 HP outdoor unit): Ø28.58(gas pipe), Ø15.88(Liquid pipe)
2) Pipe diameter between 1st and 2nd branch (77.9 kW indoor units) : Ø34.9(Gas pipe), Ø19.05(Liquid pipe) in conformity with downward indoor units.
Since the main pipe diameter of 22 HP outdoor unit is Ø28.58(gas pipe), Ø15.88(Liquid pipe) is used as the main pipe and the connection pipe between 1st and 2nd branch.
!
CAUTION
• Bending radius should be at least twice the diameter of the pipe.
• Bend pipe after 500 mm or more from branch (or header). Do not bend U type. It may cause Performance unsatisfactory or noise.
• If want U type, bending R is more than 200 mm
!
500 mm or more
500 mm or more
36
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Pipe Connection Method/Precautions for Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between outdoor units.
- Please refer to the below connection examples to install pipe connections between outdoor units.
- If the distance between the outdoor units becomes more than 2 m, apply Oil Traps between the gas pipes.
- If the outdoor unit is located lower than the main pipe, apply Oil Trap.
Pipe connection between outdoor units (General Case)
The maximum pipe length after the first branching between the outdoor units is 10 m or less
Pipes between outdoor units are 2 m or less
Examples of Wrong Pipe Connections
2 m or less
Pipes between outdoor units are 2 m or longer
Oil Trap
Oil Trap Oil Trap
2 m or less
2 m or less
2 m or less
0.2 m or more
2 m or longer
2 m or longer2 m or longer
If the main pipe is higher than the outdoor units, oil is accumulated in the outdoor unit.
If there are differences in the height between the outdoor units, oil is accumulated in the lower outdoor unit.
Oil Trap
37
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
- The pipes between the outdoor units must maintain horizontal levelness or give an inclination to prevent a back flow toward the slave outdoor unit. Otherwise, the unit may not operate prop­erly.
- Apply Oil Trap as shown below when the length of the pipe between the outdoor units is more than 2 m. Otherwise, the unit may not operate properly.
Toward indoor unit
Toward indoor unit
Pipe inclination (2 or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
(Example 1)
(Example 2)
Toward indoor unit
Toward indoor unit
2 m
2 m
2 m
0.2 m Oil Trap
38
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
- When connecting the pipes between the outdoor units, the accumulation of oil in the slave out­door unit should be avoided. Otherwise, the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
h
h
0.2 m
Toward indoor unit Toward indoor unit
Oil Trap
h
Toward indoor unit
(Example 3)
(Example 2)
39
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correc­tion Factor) value of indoor unit.
Additional charge(kg) = Total liquid pipe : Ø25.4 mm x 0.480(kg/m)
+ Total liquid pipe : Ø22.2 mm x 0.354(kg/m)
+ Total liquid pipe : Ø19.05 mm x 0.266(kg/m)
+ Total liquid pipe : Ø15.88 mm x 0.173(kg/m)
+ Total liquid pipe : Ø12.7 mm x 0.118(kg/m)
+ Total liquid pipe : Ø9.52 mm x 0.061(kg/m)
+ Total liquid pipe : Ø6.35 mm x 0.022(kg/m)
+ CF value of indoor unit
Amount refrigerant of Indoor units Example) 4 Way Ceiling Cassette 14.5 kW -1ea, Ceiling concealed Duct 7.3 kW-2 ea,
Wall Mounted 2.3 kW-4ea CF = 0.64 × 1 + 0.26 × 2 + 0.24 × 4 = 2.12 kg
Attach the additional refrigerant table of IDU.
CAUTION
• Use only 2-series of indoor unit. Ex) EX) ARNU ***2
• Do not connect Hydro kit with Multi V IV Models.
!
40
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
WARNING
• Regulation for refrigerant leakage : the amount of refrigerant leakage should satisfy the following equation for human safety.
If the above equation can not be satisfied, then follow the following steps.
• Selection of air conditioning system: select one of the next
- Installation of effective opening part
- Reconfirmation of Outdoor Unit capacity and piping length
- Reduction of the amount of refrigerant
- Installation of 2 or more security device (alarm for gas leakage)
• Change Indoor Unit type :
installation position should be over 2 m from the floor (Wall mounted type Cassette type)
• Adoption of ventilation system : choose ordinary ventilation system or building ventilation system
• Limitation in piping work : Prepare for earthquake and thermal stress
Liquid pipe
Gas pipe
Manifold GaugeLow pressure side HandleHigh pressure side Handle
Total amount of refrigerant in the system
0.44 ( kg / m3)
Volume of the room at which Indoor Unit of the least capacity is installed
!
WARNING
• Pipe to be vacuumed : gas pipe, liquid pipe
• If the refrigerant amount is not exact, it may not operate properly.
• If additionally bottled refrigerant amount is over 10%, condenser burst or insufficient in­door unit performance may be caused.
!
Refrigerant charging
41
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
- Ensure that the branch pipes are attached vertically.
Header
Slave
Master
Slave
Master
Slave
Master
Slave
Master
Slave
Master
Slave
Master
1st
1st
1st
Main pipe
Distribution
2nd
2nd
3rd
3rd
Main pipe
Distribution
Slave
Master
1st
3rd
3rd main pipe distribution
2nd
Horizontal Distribution
Vertical Distribution
The others
Distribution Method
42
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Y branch
Header
A
B
A
B
To Branch Piping or Indoor UnitTo Outdoor Unit
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
To Outdoor Unit To Indoor Unit
• The indoor unit having larger capacity must be in­stalled closer to than smaller one.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint, the connecting section should be cut with a pipe cutter.
Pipe cutter
• When the number of pipes to be connected is smaller than the number of header branches, install a cap to the unconnected branches.
Branch pipe Fitting
Horizontal plane
Within +/- 10
A
Viewed from point A in direction of arrow
Facing
downwards
Within 3 Within 3
Facing
upwards
Tape
(field supply)
Insulator
(included with kit)
Liquid and gas pipe joints
Insulator for field piping
C
43
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
• When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connection then cap pipes should be fitted to the surplus branches.
• Fit branch pipe lie in a horizontal plane.
• Header should be insulated with the insulator in each kit.
• Joints between branch and pipe should be sealed with the tape included in each kit.
• Any cap pipe should be insulated using the insulator provided with each kit and then taped as described above.
Horizontal plane
View from point B in the direction of the arrow
B
Pinched pipe
Insulate the header using the insulation material attached to the branch pipe kit as shown in the figure.
Insulator
Cap pipe
Tape
Insulator of field pipe
Insulator for cap pipe
Tape
44
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Y branch pipe
Models Gas pipe Liquid pipe
ARBLN01621
I.D19.05
O.D15.88
I.D12.7
I.D15.88
I.D12.7
I.D15.88
I.D15.88
I.D12.7
292
281
74
70
I.D12.7
O.D9.52
I.D6.35
I.D9.52
I.D.9.52
I.D.6.35
I.D9.52
I.D.6.35
292
281
74
70
1
1
ARBLN03321
I.D25.4
413
390
83
I.D15.88
I.D19.05
I.D12.7
I.D12.7I.D19.05I.D15.88I.D19.05I.D22.2
I.D28.58
O.D25.4
I.D22.2
O.D19.05
O.D19.05
I.D22.2
I.D25.4
70 80 11 0
1
2
3
3 1 2
I.D9.52
I.D12.7
53.6D.I25.9D.I
I.D9.52
I.D12.7
I.D6.35
I.D12.7
332
321
74
ARBLN07121
376 404
96
I.D34.9
O.D31.8
I.D22.2
O.D22.2
I.D28.58
I.D31.8
O.D19.05
I.D28.58
120 90 120
I.D31.8
2.22D.I85.82D.I
I.D19.05
I.D15.88
I.D12.7
I.D19.05
I.D15.88
2
3
1
2
1 3
25.9D.I25.9D.I7.21D.O
I.D15.88 I.D19.05
I.D12.7
I.D12.7
I.D19.05
I.D15.88I.D12.7
I.D19.05
O.D12. 7I.D6.35
I.D15.88
371 394
83
11 0 70
2
3
3 2
ARBLN14521
471 517
125
120 130
I.D19.05
I.D15.88
I.D12.7
I.D19.05
I.D22.2
I.D41.3 I.D38.1
I.D41.3
O.D34.9
I.D34.9
I.D34.9
I.D22.2
I.D28.58
I.D28.58I.D38.1
I.D41.3
I.D34.9
I.D38.1
O.D22.2
O.D38.1
O.D15.88
O.D28.58
90
2
3
3
3
2
2
3
416 444
96
O.D15.88 I.D9.52
I.D12.7
O.D12. 7 I.D6.35
I.D9.52
I.D15.88 I.D19.05
I.D22.2
I.D22.2
I.D19.05
I.D15.88
I.D12.7
I.D15.88
I.D19.05
I.D22.2
O.D19.0 5
80
11 0 11 0
2
3
1
2 3 3
ARBLN23220
O.D.28.58
I.D.22.2
115
X2
100
O.D15.88
I.D12.7
70
O.D.22.2
I.D.15.88I.D.19.05
120
O.D.38.1
I.D.34.9
I.D.28.58 O.D.44.48
X2
175
I.D31.8 I.D.53.98 I.D.25.4
I.D.44.48
I.D.44.48
I.D38.1I.D41.3
I.D.44.48
I.D38.1I.D41.3
I.D.53.98
420 490
134
1
2
3
32
3 3
3
3
2
O.D.19.05 I.D.12.7
I.D.15.88
O.D12.7 I.D6.35
I.D9.52
X2
110 110
I.D25.4 I.D22.2
I.D.19.05
I.D.19.05I.D.22.2
I.D.25.4
I.D.25.4
I.D.22.2
346 379
96
2
3 32
3
[unit:mm]
45
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Header
Models Gas pipe Liquid pipe
4 branch
ARBL054
120
150
360
120
ID15.88
ID12.7
ID12.7
ID15.88
ID15.88
ID19.05
120
120
150
360
ID9.52
ID9.52
ID6.35
ID6.35
ID9.52
ID12.7
7 branch
ARBL057
540
120
150
120
ID15.88
ID12.7
ID15.88
ID12.7
ID15.88
ID19.05
540
120
150
120
ID6.35
ID9.52
ID9.52
ID12.7
4 branch
ARBL104
120
150
400
160
ID15.88
ID12.7
ID19.05
ID15.88
ID22.2
ID28.58ID25.4
120
120
150
360
ID9.52
ID9.52
ID6.35
ID6.35
ID9.52
ID12.7
7 branch
ARBL107
120
150
160
580
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
120
150
700
120
ID6.35
ID9.52
ID9.52
ID6.35
ID9.52ID12.7
10 branch
ARBL1010
120
150
160
760
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
120
150
160
760
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
10 branch
ARBL2010
120
150
182
775
ID19.05
ID15.88
ID15.88
ID12.7
ID28.58
ID31.8 ID34.9
120
150
107
60*9=540
700
ID6.35
ID9.52
ID19.05ID15.88
ID9.52
ID6.35
[unit:mm]
46
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Leak test Leak test should be made by pressurizing nitrogen gas to 3.8 MPa(38.7 kgf/cm
2
). If the pressure does not drop for 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method, refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid pipe, gas pipe and high/low pressure common pipe)
The test result can be judged good if the pressure has not be reduced after leaving for about one day after completion of nitrogen gas pressurization.
NOTE
!
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is checked, apply the following correction factor
There is a pressure change of approximately 0.1 kg/cm2 (0.01 MPa) for each 1°C of temperature difference. Correction= (Temp. at the time of pressurization – Temp. at the time of check) x 0.1
For example: Temperature at the time of pressurization (3.8 MPa) is 27 °C
24 hour later: 3.73 MPa, 20 °C In this case the pressure drop of 0.07 is because of temperature drop And hence there is no leakage in pipe occurred.
CAUTION
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must be at higher position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
!
WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not com­press air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explo­sion.
- There is the risk of death, injury, fire or explosion.
!
Leak Test and Vacuum drying
Slave 1 outdoor unit Master outdoor unit
Close
Nitrogen gas cylinder
Close
Close
Liquide pipe
Gas pipe
Close
Liquide pipe
Gas pipe
Liquid side
Gas side
Indoor unit
47
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Vacuum Vacuum drying should be made from the service port provided on the outdoor unit’s service valve to the
vacuum pump commonly used for liquid pipe, gas pipe and high/low pressure common pipe. (Make Vacuum from liquid pipe, gas pipe and high/low pressure common pipe with the service valve closed.) * Never perform air purging using refrigerant.
• Vacuum drying: Use a vacuum pump that can evacuate to -100.7 kPa (5 Torr, -755 mmHg).
- Evacuate the system from the liquid and gas pipes with a vacuum pump for over 2 hrs and bring the system to -100.7 kPa. After maintaining system under that condition for over 1 hr, confirm the vacuum gauge rises. The system may contain moisture or leak.
- Following should be executed if there is a possibility of moisture remaining inside the pipe. (Rainwater may enter the pipe during work in the rainy season or over a long period of time) After evacuating the system for 2 hrs, give pressure to the system to 0.05 MPa(vacuum break) with nitrogen gas and then evacuate it again with the vacuum pump for 1 hr to -100.7 kPa(vac­uum drying). If the system cannot be evacuated to -100.7 kPa within 2 hrs, repeat the steps of vacuum break and its drying. Finally, check if the vacuum gauge does not rise or not, after main­taining the system in vacuum for 1 hr.
NOTE
!
Always add an appropriate amount of refrigerant. (For the refrigerant additional charge) Too much or too little refrigerant will cause trouble. To use the Vacuum Mode (If the Vacuum mode is set, all valves of Indoor units and Outdoor units will be opened.)
WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
!
WARNING
When installing and moving the air conditioner to another site, recharge after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
!
Slave 1 outdoor unit Master outdoor unit
Vacuum pump
Close
Close
Close
Close
Scale Use a graviometer. (One that can measure down to 0.1 kg). If you are unable to prepare such a high-precision gravimeter you may use a charge cylinder.
Liquide pipe
Gas pipe
Liquide pipe
Gas pipe
Liquid side
Gas side
Indoor unit
48
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement or IDU addition/replacement.
Vacuum mode setting method
Vacuum mode off method
CAUTION
ODU operation stops during vacuum mode. Compressor can't operate.
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“SVC” Push the ‘’ button
Select the Function using ‘’, ‘’ Button : :
“Se3” Push the ‘’ button
Start the vacuum mode : “VACC”
ODU V/V open
ODU EEV open
IDU EEV open
Dip switch off and push the reset button on Master unit PCB
!
Vacuum Mode
DIP SWITCH 7-Segment
SW04C
( X : cancel)
SW03C (
SW02C ( : backward)
SW01C ( : confirm)
SW01D (reset)
: forward)
ȯ
ȭ
Ɨ
49
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe sepa­rately with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit and insulating material, and insulating materials themselves. When insula­tion work is insufficient, there is a possibility of condensation drip, etc. Pay special attention to in­sulation work to ceiling plenum.
Heat insulation materialPipe Outer covering(Wind the connection part
and cutting part of heat insulation material with a finishing tape.)
Penetrations
Heat insulation
material
Adhesive + Heat - resistant poly-
ethylene foam + Adhesive tape
Outer
covering
Indoor Vinyl tape
Floor ex-
posed
Water-proof hemp cloth +
Bronze asphalt
Outdoor
Water-proof hemp cloth +
Zinc plate + Oily paint
NOTE
!
When using polyethylene cover as cover­ing material, asphalt roofing shall not be required.
Bad
example
• Do not insulate gas or low pressure pipe and liquid or high pressurepipe together.
Liquid pipe Gas pipe Power cables Finishing tape Insulating material Communication cables
• Be sure to fully insulate connecting portion.
These parts are not insulated.
Good
example
Liquid pipe
Communication cables
Communication cables
Separ
-ation Gas pipe Power cables
Insulating material
Power cables
SleeveHeat insulating materialLaggingCaulking materialBandWaterproofing layerSleeve with edgeLagging materialMortar or other incombustible caulkingIncombustible heat insulation material
When filling a gap with mortar, cover the penetration part with steel plate so that the insulation material will not be caved in. For this part, use incombustible mate­rials for both insulation and covering. (Vinyl covering should not be used.)
Thermal insulation of refrigerant piping
Inner wall (concealed)
A
B
Floor (fireproofing)
D
F
G
B
Outer wall Outer wall (exposed)
D
C
A
Roof pipe shaft
G
D
B
H
E
B
B
I
Penetrating portion on fire
limit and boundary wall
I
A
1m1m
J
50
ENGLISH
ELECTRICAL WIRING
Caution
- Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.
-
Install the Outdoor Unit communication cable away from the power source wiring so that it is not af­fected by electric noise from the power source. (Do not run it through the same conduit.)
- Be sure to provide designated grounding work to Outdoor Unit.
- Give some allowance to wiring for electrical part box of Indoor and Outdoor Units, because the box is sometimes removed at the time of service work.
- Never connect the main power source to terminal block of communication cable. If connected, electrical parts will be burnt out.
- Use 2-core shield cable for communication cable.(O mark in the figure below) If communication cable of different systems are wired with the same multiplecore cable, the resultant poor trans­mitting and receiving will cause erroneous operations. ( mark in the figure below)
- Only the communication cable specified should be connected to the terminal block for Outdoor Unit communication.
CAUTION
Be sure to correct the outdoor unit to earth. Do not connect ground wire to any gas pipe, liquid pipe, lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
2-Core Shield Cable Multi-Core Cable
Remote control
Remote control
Remote control
Remote control
Indoor
Unit
Outdoor Unit
Outdoor Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Outdoor Unit
Outdoor Unit
Remote control
Remote control
Indoor
Unit
Indoor
Unit
Remote control
Remote control
Indoor
Unit
Indoor
Unit
!
WARNING
Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with regulations and this installation manual. If power supply circuit has a lack of capacity or electric work deficiency, it may cause an electric shock or fire.
!
ELECTRICAL WIRING
51
ENGLISH
ELECTRICAL WIRING
2-Core Shield Cable Multi-Core Cable
Master Slave1 Slave2
Remote controller
Remote controller
Indoor
Unit
Indoor
Unit
Remote controller
Outdoor Unit
Outdoor Unit
Remote controller
Indoor
Unit
Indoor
Unit
Master Slave1 Slave2
Master Slave1 Slave2
Outdoor Unit
Remote controller
Remote controller
Indoor
Unit
Indoor
Unit
Remote controller
Remote controller
Indoor
Unit
Indoor
Unit
Master Slave1 Slave2
Outdoor Unit
CAUTION
• Use the 2-core shield cables for communication cables. Never use them together with power
cables.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteri-
orate power factor improvement effect, but also may cause capacitor abnormal heating. There­fore, never install a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2%. If it is greater the units lifes-
pan will be reduced.
CAUTION
When the 400 volt power supply is applied to “N” phase by mistake, check damaged parts in control box and replace them.
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Round pressure terminal
Power cable
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
- When connecting cable which is the same thickness, do as shown in the figure below.
- For wiring, use the designated power cable and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may break them.
!
!
52
ENGLISH
ELECTRICAL WIRING
Control box and connecting position of wiring
- Remove all of the screws at front panel and remove the panel by pulling it forward.
- Connect communication cable between main and sub outdoor unit through the terminal block.
- Connect communication cables between outdoor unit and indoor units through the terminal block.
- When the central control system is connected to the outdoor unit, a dedicated PCB must be connected between them.
- When connecting communication cable between outdoor unit and indoor units with shielded cable, connect the shield ground to the earth screw.
[Heat pump]
UX3
UX2
WARNING
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
!
Main PCB
Noise Filter
External PCB
Take care of the phase
sequence of 3-phase 4-wire
power system
Front Panel
53
ENGLISH
ELECTRICAL WIRING
Communication and Power Cables
Communication cable
- Types : shielding cable
- Cross section : 1.0~1.5 mm
2
- Maximum allowable temperature: 60 °C
- Maximum allowable cable length: under 1000 m
Remote control cable
- Types : 3-core cable
Central control cable
Separation of communication and power cables
- If communication and power cables are run alongside each other then there is a strong likeli­hood of operational faults developing due to interference in the signal wiring caused by electro­static and electromagnetic coupling. The tables below indicates our recommendation as to appropriate spacing of communication and power cables where these are to be run side by side
NOTE
!
• The figures are based on assumed length of parallel cabling up to 100 m. For length in ex­cess of 100 m the figures will have to be recalculated in direct proportion to the additional length of cable involved.
• If the power supply waveform continues to exhibit some distortion the recommended spacing in the table should be increased.
- If the cable are laid inside conduits then the following point must also be taken into ac­count when grouping various cable together for introduction into the conduits
- Power cable(including power supply to air conditioner) and communication cables must not be laid inside the same
- In the same way, when grouping the power wires and communication cables should not be bunched together.
Product type Cable type Diameter
ACP&AC Manager 2-core cable (Shielding cable) 1.0~1.5 mm
2
AC Smart 2-core cable (Shielding cable) 1.0~1.5 mm
2
Simple central controller 4-core cable (Shielding cable) 1.0~1.5 mm
2
Current capacity of power cable Spacing
100V or more
10 A 300 mm 50 A 500 mm
100 A 1000 mm
Exceed 100 A 1500 mm
CAUTION
If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the apparatus must be carried out by a qualified person.
!
54
ENGLISH
ELECTRICAL WIRING
Wiring of main power supply and equipment capacity
- Use a separate power supply for the Outdoor Unit and Indoor Unit.
- Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
- The cable size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
- Specific wiring requirements should adhere to the wiring regulations of the region.
- Power supply cords of parts of appliances for outdoor use should not be lighter than polychloro­prene sheathed flexible cord.
- Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
CAUTION
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.
!
WARNING
• Follow ordinance of your governmental organization for technical standard related to elec­trical equipment, wiring regulations and guidance of each electric power company.
• Make sure to use specified cables for connections so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that gener­ated overcurrent may include some amount of direct current.
!
55
ENGLISH
ELECTRICAL WIRING
Field Wiring
Single outdoor unit
R S T N
Switch
Fuse
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(3 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Outdoor Unit]
[Indoor Units]
Outdoor
Power supply
(3Ø 4 wires)
Indoor
Power supply
(1Ø 2 wires)
(Main Switch)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
34 34 34
Master Outdoor Unit
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
[Heat Pump] Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’ terminal for day contact, it is not the point to make ground connection.
WARNING
• Indoor Unit ground wires are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connec­tion to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor and other parts.
!
Frequency
Voltage range(V)
Outdoor Indoor 60 Hz 400 V 220 V 50 Hz 380~415 V 220~240 V
56
ENGLISH
ELECTRICAL WIRING
Series outdoor units
When the power source is connected In series between the units.
When the power source is supplied to Each outdoor unit individually.
R S T N
Switch
Fuse
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(3 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Master]
[Indoor Units]
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
[Slave1] [Slave2]
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(3 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Master]
[Indoor Units]
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
[Slave1] [Slave2]
R S T N
Switch
Fuse
R S T N
Switch
Fuse
R S T N
Switch
Fuse
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
Pull Box (Installer option)
WARNING
When the total capacity is over than as follow, the power source do not use in series be­tween the units.
The First terminal block could be burnt out. (Heat Pump : 68 Hp)
!
Frequency
Voltage range(V)
Outdoor Indoor 60 Hz 400 V 220 V 50 Hz 380~415 V 220~240 V
Frequency
Voltage range(V)
Outdoor Indoor 60 Hz 400 V 220 V 50 Hz 380~415 V 220~240 V
57
ENGLISH
ELECTRICAL WIRING
Slave1 Outdoor Unit
Master Outdoor unit
Slave2 Outdoor Unit
34 34 34
Master Outdoor Unit
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
[Heat Pump] Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’ terminal for dry contact. It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
WARNING
• Indoor Unit ground wires are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connec­tion to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor and other parts.
!
58
ENGLISH
ELECTRICAL WIRING
Example) Connection of transmission wire
[BUS type] [STAR type]
- Abnormal operation can be caused by com­munication defect, when connection of communication cable is installed like below figure(STAR type).
- Connection of communication cable must be installed like below figure between indoor unit to outdoor unit.
59
ENGLISH
ELECTRICAL WIRING
CAUTION
It should be wiring power cables or communication cables to avoid interference with the oil level sensor. Otherwise, That oil level sensor would be operated abnormally.
!
Example) Connection of power and communication cable (UX2)
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication
cable
Main power terminal block
Ground wire
Power/ Ground cable
Over 50mm gap
Communication cable
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication cable
Main power
terminal block
Insulation sleeves
attachments
Fix firmly not
to be displaced
ODU-IDU Communication cable
ODU-ODU Communication cable
Main power terminal block
Ground wire
Power/Ground cable
Over
50mm gap
Communication
cable
Left Side Right Side
Front Side 1 Front Side 2
Main Power Connection Communication Connection
60
ENGLISH
ELECTRICAL WIRING
CAUTION
It should be wiring power cables or communication cables to avoid interference with the oil level sensor. Otherwise, That oil level sensor would be operated abnormally.
!
Example) Connection of power and communication cable (UX3)
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication
cable
Main power terminal block
Ground wire
Power/ Ground cable
Over 50mm gap
Communication cable
e
wer
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication cable
Main power
terminal block
Insulation sleeves
attachments
Fix firmly not
to be displaced
ODU-IDU Communication cable
ODU-ODU Communication cable
Main power terminal block
Ground wire
Power/Ground cable
Over
50mm gap
Communication cable
Left Side Right Side
Front Side 1 Front Side 2
Main Power Connection Communication Connection
61
ENGLISH
ELECTRICAL WIRING
Checking the setting of outdoor units
Checking according to dip switch setting
- You can check the setting values of the Master outdoor unit from the 7 segment LED. The dip switch setting should be changed when the power is OFF.
Checking the initial display The number is sequentially appeared at the 7 segment in 5 seconds after applying the power.
This number represents the setting condition. (For example, represents R410A 36 HP)
• Initial display order • Example) ARUN360LTH4
• Master Unit • Slave Unit
Dip switch setting Dip switch setting ODU Setting
Slave 1
Slave 2
Order No Mean
8~16 Master model capacity
10~16 Slave 1 model capacity
10~16 Slave 2 model capacity
8~48 Total capacity
1 Cooling Only 2 Heat Pump 3 Heat Recovery
40 400 V model 46 460 V model 22 220 V model
1 LTE 2 LTS / LTN 6 LTH
10 12 14 36 2 40 6
62
ENGLISH
ELECTRICAL WIRING
Automatic Addressing
The address of indoor units would be set by Automatic Addressing
- Wait for 3 minutes after supplying power. (Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A “88” is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on numbers of connected in­door units
- Numbers of connected indoor units whose addressing is completed are indicated for 30 sec­onds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated on the wired remote con­trol display window. (CH01, CH02, CH03, ……, CH06 : Indicated as numbers of connected in­door units)
[Heat Pump (MAIN PCB)]
DIP-SWITCH 7 - Segment
SW01C ( : confirm)
SW02C (ඔ : backward)
SW03C (ඖ : forward)
SW04C (
: cancel)
SW01D (reset)
CAUTION
• In replacement of the indoor unit PCB, always perform Automatic addressing setting again (At that time, please check about using Independent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error occur.
• Automatic Addressing is only possible on the master Unit.
• Automatic Addressing has to be performed after 3 minutes to improve communication.
!
63
ENGLISH
ELECTRICAL WIRING
The Procedure of Automatic Addressing
Power On
Waiting 3 minutes
Press RED Button for 5 sec.
(SW01C)
7-segment LED = 88
Don’t press RED Button
(SW01C)
Waiting about 2~7 minutes
7-segment LED
= 88
YES
OK
Automatic addressing start
• Automatic addressing setting end Numbers of indoor unit connection set whose addressing is completed are indicated for 30 seconds on 7-segment LED after completing setting
NO Check the connections
of communication cable
Indoor address number is displayed on wired remote control or indoor unit display window. It is not an error message, will disappeared when on/off button is pressed on remote control ex) Display of 01, 02, ..., 15 means connection of 15 indoor units and Automatic addressing is completed normally.
64
ENGLISH
ELECTRICAL WIRING
MODE FUNCTION OPTION VALUE ACTION
remarks
con­tent
Display1
content
Display2
content Display3
con-
tent
Display4
implement Display5
In-
stalla-
tion
Cool & Heat
Selector
oFF
op1~op2
selected the
option
- -
change the
set value
blank
save in
EEPROM
Static pressure
compensation
oFF
op1~op3
selected the
option
- -
change the
set value
blank
save in
EEPROM
Night low noise
oFF
op1~op12
selected the
option
- -
change the
set value
blank
save in
EEPROM
Overall defrost
on
oFF
selected the
option
- -
change the
set value
blank
save in
EEPROM
ODU address
-
-
0~255
set the
value
change the
set value
blank
save in
EEPROM
Snow removal &
rapid defrost
oFF
op1~op3
selected the
option
- -
change the
set value
blank
save in
EEPROM
IDU capacity
adjusting
on
oFF
selected the
option
--
change the
set value
blank
save in
EEPROM
Target pressure
adjusting
op1~op4
selected the
option
- -
change the
set value
blank
save in
EEPROM
Comfort
Operation
on
oFF
selected the
option
--
change the
set value
blank
save in
EEPROM
Auto
Dust Removal
on
oFF
selected the
option
--
change the
set value
blank
save in
EEPROM
* Functions save in EEPROM will be kept continuously, though the system power was reset.
Setting the function Select the mode/function/option/value using ‘’, ‘’ Button and confirm that using the ‘’ but-
ton after dip switch No.5 is turned on.
DIP-SW01 7 - Segment
SW01C ( : confirm)
SW02C (ඔ : backward)
SW03C (ඖ : forward)
SW04C (
: cancel)
SW01D (reset)
65
ENGLISH
ELECTRICAL WIRING
Group Number setting
Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal should be connected to central control of Outdoor Unit with care for their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID from 0 to F for this pur­pose.
Outdoor Units (External PCB)
Example) Group number setting
1
st
number indicate the group number
2nd number point out indoor unit number
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
B(D) A(C)
1 F
Group Indoor unit
Group recognizing the central controller
No.0 group (00~0F) No.1 group (10~1F) No.2 group (20~2F) No.3 group (30~3F) No.4 group (40~4F) No.5 group (50~5F) No.6 group (60~6F) No.7 group (70~7F) No.8 group (80~8F) No.9 group (90~9F) No. A group (A0~AF) No. B group (B0~BF) No. C group (C0~CF) No. D group (D0~DF) No. E group (E0~EF) No. F group (F0~FF)
66
ENGLISH
ELECTRICAL WIRING
Cool & Heat selector
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn1” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”,“op2” Push the ‘’ button
Cool & Heat Selection mode is set
Function setting
Switch control Function
Switch(Phase) Switch(Bottom) oFF op1(mode) op2(mode)
Right Left Not operate Cooling Cooling Right Right Not operate Heating Heating
Left - Not operate Fan mode Off
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, first install a Cool & Heat selector.
!
Switch (Phase)
Switch (Bottom)
Left side
Right side
67
ENGLISH
ELECTRICAL WIRING
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan discharge of ODU.
Static pressure compensation mode setting method
FAN Maximum RPM of each step
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn2” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op3” Push the ‘’ button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Capacity 8~10 HP 12~16 HP
Max. RPM
Standard 730 950
op1 760 1020 op2 780 1050 op3 800 1130
68
ENGLISH
ELECTRICAL WIRING
Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
Time Settings Noise
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn3” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op12” Push the ‘’ button
Start the Night low noise function :
Save the selected option value in EEPROM
Step
Judgment
Time(Hr)
Operation
Time(Hr) op1 8 9 op2 6.5 10.5 op3 5 12 op4 8 9 op5 6.5 10.5 op6 5 12 op7 8 9 op8 6.5 10 op9 5 12
op10 Continuous operation op11 Continuous operation op12 Continuous operation
Capacity
Heat Pump 8~10 HP 12~16 HP
Step Noise(dB) op1~op3, op10 55 59 op4~op6, op11 52 56 op7~op9, op12 49 53
CAUTION
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.
!
69
ENGLISH
ELECTRICAL WIRING
Overall defrost mode
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn4” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on” ~ “oFF” Push the ‘’ button
Overall defrost mode is set
mode setting
CAUTION
• Ask an authorized technician to setting a function. * ARUN***LTH4 models operate only overall defrost function.
!
- on: Operate overall defrost
- off: Operate partial defrost
70
ENGLISH
ELECTRICAL WIRING
Setting the ODU address
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn5” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“0” ~ “255” Push the ‘’ button
ODU address is set
CAUTION
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
!
71
ENGLISH
ELECTRICAL WIRING
Snow removal & rapid defrost
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn6” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1” ~ “op3” Push the ‘’ button
Mode is set
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
!
mode setting
setting Mode
oFF Not setting
op1 Snow removal mode
op2 Rapid defrost mode
op3 Snow removal mode. + Rapid defrost mode.
72
ENGLISH
IDU capacity adjusting
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn7” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on” ~ “oFF” Push the ‘’ button
IDU capacity adjusting is set
CAUTION
• Ask an authorized technician to setting a function. * ARUN***LTH4 models operate only overall defrost function.
!
ELECTRICAL WIRING
73
ENGLISH
Target pressure adjusting
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1” ~ “op4” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Target pressure is set
Select the Option using ‘’, ‘’ Button :
“HEAT” , “COOL” Push the ‘’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
mode
Purpose
Condensing
temperature
variation
Evaporating
temperature
variation
“Heat” “Cool”
op1 Increase capacity Increase capacity -3 °C +2 °C
op2
Decrease power consumption
Increase capacity -1.5 °C -2 °C
op3
Decrease power consumption Decrease power consumption
+2.5 °C -4 °C
op4
Decrease power consumption Decrease power consumption
-4.5 °C -6 °C
74
ELECTRICAL WIRING
ENGLISH
Comfort Operation
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn9” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on” ~ “oFF” Push the ‘’ button
Mode is set
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
!
ELECTRICAL WIRING
75
ENGLISH
Auto Dust Removal
This function make a clean heat exchanger from dust.
mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn10” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on” ~ “oFF” Push the ‘’ button
Auto Dust Removal
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
!
76
ELECTRICAL WIRING
ENGLISH
Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condi­tion.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7­segment LED of outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display 1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number. Ex)
* If error code displayed is apart from above list, refer related indoor unit’s manual.
Display Title Cause of Error
Indoor unit related error
0 1 -
Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 -
Inlet pipe temperature sensor of indoor unit
Inlet pipe temperature sensor of indoor unit is open or short
0 3 -
Communication error : wired remote con­troller indoor unit
Failing to receive wired remote controller signal in in­door unit PCB
0 4 -
Drain pump Malfunction of drain pump
0 5 -
Communication error : outdoor unit in­door unit
Failing to receive outdoor unit signal in indoor unit PCB
0 6 -
Outlet pipe temperature sensor of indoor unit
Outlet pipe temperature sensor of indoor unit is open or short
0 9 -
Indoor EEPROM Error
In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFF
1 0 -
Poor fan motor operation
Disconnecting the fan motor connector / Failure of in­door fan motor lock
Outdoor unit related error
2 1 *
Master Outdoor Unit Inverter Compressor IPM Fault
Master Outdoor Unit Inverter Compressor Drive IPM Fault
2 2 *
Inverter Board Input Over Current(RMS) of Master Outdoor Unit
Master Outdoor Unit Inverter Board Input Current ex­cess (RMS)
2 3 *
Master Outdoor Unit Inverter Compressor DC link Low Voltage
DC charging is not performed at Master Outdoor Unit after starting relay turn on.
2 4 *
Master Outdoor Unit High Pressure Switch
System is turned off by Master Outdoor Unit high pressure switch.
2 5 *
Master Outdoor Unit Input Voltage High/ Low Voltage
Master Outdoor Unit input voltage is over 506V or below 414V
26*
Master Outdoor Unit Inverter Compressor Start Failure
The First Start Failure by Master Outdoor Unit Inverter Compressor Abnormality
29*
Master Outdoor Unit Inverter Compressor Over Current
Master Outdoor Unit Inverter Compressor Fault OR Drive Fault
Repeat
Error No. of Unit
Error No.
Error No. of Compressor
ELECTRICAL WIRING
77
ENGLISH
Display Title Cause of Error
Outdoor unit related error
3 2 *
Master Outdoor Unit Inverter Compres­sor1 High Discharge Temperature
Master Outdoor Unit Inverter Compressor1 High Dis­charge Temperature
3 3 *
Master Outdoor Unit Inverter Compres­sor2 High Discharge Temperature
Master Outdoor Unit Inverter Compressor2 High Dis­charge Temperature
3 4 *
High Pressure of Master Outdoor Unit High Pressure of Master Outdoor Unit
3 5 *
Low Pressure of Master Outdoor Unit Low Pressure of Master Outdoor Unit
3 6 *
Master Outdoor Unit Low Compression Ratio Limited
Master Outdoor Unit Low Compression Ratio Limited
4 0 *
Master Outdoor Unit Inverter Compressor CT Sensor Fault
Master Outdoor Unit Inverter Compressor CT Sensor open or short
4 1 *
Master Outdoor Unit Inverter Compres­sor1 Discharge Temperature Sensor Fault
Master Outdoor Unit Inverter Compressor Discharge Temperature Sensor open or short
4 2 *
Master Outdoor Unit Low Pressure Sen­sor Fault
Master Outdoor Unit Low Pressure Sensor open or short
4 3 *
Master Outdoor Unit High Pressure Sen­sor Fault
Master Outdoor Unit High Pressure Sensor open or short
4 4 *
Master Outdoor Unit Air Temperature Sensor Fault
Master Outdoor Unit Air Temperature Sensor open or short
4 5 *
Master Outdoor Unit Heat Exchanger Temperature Sensor (Front side) Fault
Master Outdoor Unit Heat Exchanger Temperature Sensor(Front side) open or short
4 6 *
Master Outdoor Unit Suction Temperature Sensor Fault
Master Outdoor Unit Suction Temperature Sensor open or short
4 7 *
Master Outdoor Unit Inverter Compres­sor2 Discharge Temperature Sensor Fault
Master Outdoor Unit Inverter Compressor2 Discharge Temperature Sensor open or short
4 9 *
Master Outdoor Unit Faulty IPM Tempera­ture Sensor
Master Outdoor Unit IPM Temperature Sensor short/open
5 0 *
Omitting connection of R, S, T power of Master Outdoor Unit
Omitting connection of Master outdoor unit
5 1 *
Excessive capacity of indoor units
Excessive connection of indoor units compared to ca­pacity of Outdoor Unit
5 2 *
Communication error : inverter PCB Main PCB
Failing to receive inverter signal at main PCB of Mas­ter Outdoor Unit
5 3 *
Communication error : indoor unit Main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of Outdoor Unit .
5 7 *
Communication error : Main PCB in­verter PCB
Failing to receive signal main PCB at inverter PCB of Master Outdoor Unit
5 9 *
Wrong combination of Outdoor Units
Installation might be mixed with old series models(Multi V lll,ll …)
6 0 *
Inverter PCB EEPROM Error of Master Outdoor Unit
Access Error of Inverter PCB of Master Outdoor Unit
6 2 *
Master Outdoor Unit Inverter Heatsink High Temperature
System is turned off by Master Outdoor Unit Inverter Heatsink High Temperature
6 5 *
Master Outdoor Unit Inverter Heatsink Temperature Sensor Fault
Master Outdoor Unit Inverter Heatsink Temperature Sensor open or short
67*
Master Outdoor Unit Fan Lock Restriction of Master Outdoor Unit
78
ELECTRICAL WIRING
ENGLISH
Display Title Cause of Error
Outdoor unit related error
7 1 *
Converter CT Sensor Error of Master Out­door Unit
Converter CT Sensor open or short of Master Outdoor Unit
7 5 *
Master Outdoor Unit Fan CT Sensor Error Master Outdoor Unit Fan CT Sensor open or short
7 6 *
Master Outdoor Unit Fan DC Link High Voltage Error
Master Outdoor Unit Fan DC Link High Voltage Error
7 7 *
Master Outdoor Unit Fan Over Current Error
Master Outdoor Unit Fan Current is over 5A
7 9 *
Master Outdoor Unit Fan Start Failure Error
Master Outdoor Unit Fan First Position Sensing Fail­ure
8 6 *
Master Outdoor Unit Main PCB EEPROM Error
Communication Fail Between Master Outdoor Unit Main MICOM and EEPROM or omitting EEPROM
8 7 *
Master Outdoor Unit Fan PCB EEPROM Error
Communication Fail Between Master Outdoor Unit Fan MICOM and EEPROM or omitting EEPROM
Outdoor unit related error
1 0 4*
Communication Error Between Master Outdoor Unit and Other Outdoor Unit
Failing to receive Slave Unit signal at main PCB of Master Outdoor Unit
1 0 5*
Master Outdoor Unit Fan PCB Communi­cation Error
Failing to receive fan signal at main PCB of Master unit.
1 0 6*
Master Outdoor Unit FAN IPM Fault Error Instant Over Current at Master Outdoor Unit Fan IPM
107*
Master Outdoor Unit Fan DC Link Low Voltage Error
Master Outdoor Unit Fan DC Link Input Voltage is under 380V
113*
Master Outdoor Unit Liquid pipe Temper­ature Sensor Error
Liquid pipe temperature sensor of Master Outdoor Unit is open or short
114*
Master Outdoor Unit Subcooling Inlet Temperature Sensor Error
Master Outdoor Unit Subcooling Inlet Temperature Sensor Error
115*
Master Outdoor Unit Subcooling Outlet Temperature Sensor Error
Master Outdoor Unit Subcooling Outlet Temperature Sensor Error
116*
Master Outdoor Unit Oil Level Sensor Error
Oil Level Sensor of Master Outdoor Unit is open or short
145*
Master outdoor unit Main Board - External Board communication Error
Master outdoor unit Main Board - External Board communication Error
151*
Failure of operation mode conversion at Master Outdoor Unit
Failure of operation mode conversion at Master Out­door Unit
153*
Master Outdoor Unit Heat Exchanger Temperature Sensor (upper part) Fault
Master Outdoor Unit Heat Exchanger Temperature Sensor (upper part) Fault
154*
Master Outdoor Unit Heat Exchanger Temperature Sensor (lower part) Fault
Master Outdoor Unit Heat Exchanger Temperature Sensor(lower part) open or short
182*
Master outdoor unit External Board Main­Sub Micom communication Error
Master Outdoor Unit Main Board Main-Sub Micom communication failed
193*
Master Outdoor Unit Fan Heatsink High Temperature
System is turned off by Master Outdoor Unit Fan Heatsink High Temperature
194*
Master Outdoor Unit Fan Heatsink Tem­perature Sensor Fault
Master Outdoor Unit Fan Heatsink Temperature Sen­sor open or short
CAUTION FOR REFRIGERANT LEAK
79
ENGLISH
Checking procedure of limiting concentration
Check limiting concentration along following steps and take appropriate measure depending on the situation.
Calculate amount of all the replenished refrigerant (kg) per each refrigerant system.
Calculate minimum room capacity Calculate room capacity by regarding a portion as one room or the smaller room.
- Without partition - With partition and with opening which serve as passage of air to adjoining room
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The limiting concen­tration shall be described in the unit of kg/m3(Freon gas weight per unit air volume) for facili­tating calculation.
Limiting concentration: 0.44 kg/m
3
(R410A)
Amount of additional replenished refrigerant
Total amount of replenished refrigerant in refrigerant facility (kg)
+
=
Note : In case one refrigerant facility is
divided into 2 or more refrigerant systems and each system is independent, amount of replenished refrigerant of each system shall be adopted.
Amount of replenished refrigerant per one outdoor unit system
Amount of replenished refrigerant at factory shipment
Amount of additionally replenished refrigerant depending on piping length or piping diameter at customer
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Opening
Partition
In the case of opening without door , or 0.15 % or more openings (to floor space) both above and below door)
Outdoor unit
(No.1 system)
Flow of refrigerant
Indoor unit
Room where refrigerant leaks (Refrigerant of the whole No.1 system flows out.)
The installer and system specialist shall secure safety against leakage according to local regula­tions or standards. The following standards may be applicable if local regulations are not available.
Introduction
Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should be large to such an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room.
Limiting concentration
CAUTION FOR REFRIGERANT LEAK
80
CAUTION FOR REFRIGERANT LEAK
ENGLISH
- With partition and without opening which serve as passage of air to adjoining room
Calculate refrigerant concentration
In case the concentration exceeds the limit When the concentration exceeds the limit, change original plan or take one of the countermea-
sures shown below:
• Countermeasure 1 Provide opening for ventilation. Provide 0.15% or more opening to floor space both above and below door, or provide opening without door.
• Countermeasure 2 Provide gas leak alarm linked with mechanical ventilator. Reducing the outdoor refrigerant qty.
(R410A)
=
Refrigerant concentration
(kg/m
3
)
Total amount of replenished refrigerant in refrigerant facility (kg)
Capacity of smallest room where indoor unit is installed (m
3
)
In case the result of calculation exceeds the limiting concentration, perform the same calculations by shifting to the second smallest, and the third smallest rooms until at last the result is below the limiting concentration.
Outdoor unit
Indoor unit
Smallest room
Countermeasure 2
Gas leak alarm
Mechanical ventilator
Countermeasure 1
Opening effective to ventilation
Indoor unit
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air.
INSTALLATION GUIDE AT THE SEASIDE
81
ENGLISH
Selecting the location(Outdoor Unit)
If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
In case, to install the outdoor unit on the sea­side, set up a windbreak not to be exposed to the sea wind.
- It should be strong enough like concrete to prevent the sea wind from the sea.
- The height and width should be more than 150% of the outdoor unit.
- It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
Select a well-drained place.
CAUTION
• Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
• Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
• If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Sea wind
Sea wind
Sea wind
Windbreak
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
INSTALLATION GUIDE AT THE SEASIDE
!
Loading...