LG ARUN1208T1, ARUV1008T1, ARUV1408T1 INSTALLATION INSTRUCTIONS

System
Outdoor Unit
INSTALLATION MANUAL
LG
MODELS: ARUV Series
ARUN Series
website http://www.lgservice.com
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
R410A
ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
PORTUGUESE
2 Outdoor Unit
ARUV(N) Series Outdoor unit Installation Manual
TABLE OF CONTENTS
Safety Precautions.........................3
Installation Process .....................10
Outdoor units Information ..........11
Environment-friendly Alternative
Refrigerant R410A .......................15
Select the Best Location .............15
Installation Space ........................16
Lifting method ..............................20
Installation ....................................21
Refrigerant piping installation ....26
Electrical Wiring...........................46
Test Run........................................68
Caution For Refrigerant Leak .....76
Installation guide at the seaside .....78
Installation Manual 3
ENGLISH
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Installation
Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
• If the power source capacity is inadequate or
electric work is performed improperly, electric shock or fire may result.
Ask the dealer or an authorized technician to install the air conditioner.
• Improper installation by the user may result in water leakage, electric shock, or fire.
Always ground the product.
• There is risk of fire or electric shock.
Always intstall a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or electric shock.
4 Outdoor Unit
Safety Precautions
For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install, remove, or re-install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Do not store or use flammable gas or combustibles near the air conditioner.
• There is risk of fire or failure of product.
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Prepare for strong wind or earthquake and install the unit at the specified place.
• Improper installation may cause the unit to top­ple and result in injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
When installing and moving the air condition­er to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
• If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
Do not reconstruct to change the settings of the protection devices.
• If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
Gasolin
R22
R410A
R407C
ENGLISH
Installation Manual 5
Safety Precautions
Ventilate before operating air conditioner when gas leaked out.
• It may cause explosion, fire, and burn.
Securely install the cover of control box and the panel.
• If the cover and panel are not installed securely, dust or water may enter the outdoor unit and fire or electric shock may result.
If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
• Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceed­ed. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxy­gen in the room could result.
Operation
Do not damage or use an unspecified power cord.
• There is risk of fire, electric shock, explosion, or injury.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock.
Be cautious that water could not enter the product.
• There is risk of fire, electric shock, or product damage.
Do not touch the power switch with wet hands.
• There is risk of fire, electric shock, explosion, or injury.
6 Outdoor Unit
Safety Precautions
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or electric shock.
Be cautious not to touch the sharp edges when installing.
• It may cause injury.
T ake care to ensure that nobody could step on or fall onto the outdoor unit.
• This could result in personal injury and product damage.
Do not open the inlet grille of the product during operation. (Do not touch the electro­static filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.
Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the unit where combustible gas may leak.
• If the gas leaks and accumulates around the unit, an explosion may result.
90˚
Gasolin
ENGLISH
Installation Manual 7
Safety Precautions
Use power cables of sufficient current carrying capacity and rating.
• Cables that are too small may leak, generate heat, and cause a fire.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
• There is risk of damage or loss of property.
Keep the unit away from children. The heat exchanger is very sharp.
• It can cause the injury, such as cutting the finger. Also the damaged fin may result in degradation of capacity.
When installting the unit in a hospital, com­munication station, or similar place, provide sufficient protection against noise.
The inverter equipment, private power generator, high-frequency medical equipment, or radio com­munication equipment may cause the air condition­er to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not install the product where it is exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
8 Outdoor Unit
Safety Precautions
Operation
Do not use the air conditioner in special environments.
Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
Do not block the inlet or outlet.
It may cause failure of appliance or accident.
Make the connections securely so that the outside force of the cable may not be applied to the terminals.
Inadequate connection and fastening may gen­erate heat and cause a fire.
Be sure the installation area does not deteri­orate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, or personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
A bad connection may cause water leakage.
Be very careful about product transportation.
Only one person should not carry the product if it weighs more than 20 kg.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
Do not touch the heat exchanger fins. Doing so may cut your fin­gers.
When transporting the outdoor unit, suspending it at the specified positions on the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
ENGLISH
Installation Manual 9
Safety Precautions
Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
Turn on the power at least 6 hours before starting operation.
Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
Do not touch any of the refrigerant piping during and after operation.
It can cause a burn or frostbite.
Do not operate the air conditioner with the panels or guards removed.
Rotating, hot, or high-voltage parts can cause injuries.
Do not directly turn off the main power switch after stopping operation.
Wait at least 5 minutes before turning off the main power switch. Otherwise it may result in water leakage or other problems.
Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the indoor unit PCB.
Use a firm stool or ladder when cleaning or maintaining the air conditioner.
Be careful and avoid personal injury.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There are sharp and moving parts that could cause personal injury.
10 Outdoor Unit
Installation
Installation Process
The foundation must be level even
Outdoor unit foundation work
Avoid short circuits and ensure sufficient space is allowed for service
Installation of outdoor unit
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
2
) there must be no drop in pressure.
All tight test
Multiple core cable must not be used. (suitable cable should be selected)
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness, cleanness and tightness
Refrigerant piping work
Check model name to make sure the fitting is made correctly
Installation of indoor unit
Take account of gradient of drain piping
Sleeve and insert work
Make relationship between outdoor, indoor, remote controller, and option connections clear. (Prepare control circuit diagram)
Preparation of contract drawings
Indicate clearly who is to be responsible for switch settings
Determination of division work
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Vacuum drying
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order
Transfer to customer with explanation
Preheat the crank case with the electrical heater for more than 6 hours.
The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrants such change.
The wall thickness of the piping should comply with the relevant local and national regulations for the designed pres­sure 3.8MPa.
Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refriger­ant is charged in its gaseous state, its composition changes and the system will not work properly.)
ENGLISH
Installation Manual 11
Outdoor units Information
Outdoor units Information
CAUTION: A ratio of the connectable Indoor Units with the Outdoor: Within 50 ~ 130%
A ratio of the running Indoor Units with the Outdoor: Within 10 ~ 100% 130% combination ratio is a reduction in capacity in defrost
Power Supply: Outdoor Unit (3Ø, 380 ~ 415V, 50Hz)
Cooling Only
Unit System(HP) Model Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
1 Outdoor Unit(Half size) 1 Outdoor Unit
568101214
ARUV508T1 ARUV608T1 ARUV808T1S ARUV1008T1 ARUV1208T1 ARUV1408T1
4 4.5 5 8 8 8 001012 6 8 13 16 20 20
150 150 150 300 300 300
330.7 330.7 330.7 661.4 661.4 661.4
806 * 1607 * 730 806 * 1607 * 730 806 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730
31.7 * 63.3 * 28.74 31.7 * 63.3 * 28.74 31.7 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74
Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø12.7(1/2)
Ø15.88(5/8) Ø19.05(3/4) Ø19.05(3/4) Ø22.2(7/8) Ø28.58(1 1/8) Ø28.58(1 1/8)
Unit System(HP) Model
Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) inch
mm
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
2 Outdoor Units
3 Outdoor Units
16 18 20 22 24 26
ARUV1608T1 ARUV1808T1 ARUV2008T1 ARUV2208T1 ARUV2408T1 ARUV2608T1
ARUV808T1 ARUV1008T1 ARUV1008T1 ARUV1208T1 ARUV1208T1 ARUV1008T1 ARUC808T1 ARUC808T1 ARUC1008T1 ARUC1008T1 ARUC1208T1 ARUC808T1
ARUC808T1
16 16 16 16 16 24
-2 -1 0 1 2 -2 20 20 20 22 24 32
300x2 300x2 300x2 300x2 300x2 300x3
661.4x2 661.4x2 661.4x2 661.4x2 661.4x2 661.4x3 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x3 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x3
Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø19.05(3/4)
Ø28.58(1 1/8) Ø28.58(1 1/8) Ø28.58(1 1/8) Ø28.58(1 1/8)
Ø34.9(1 3/8
) Ø34.9(1 3/8
)
Unit System(HP) Model
Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
3 Outdoor Units
28 30 32 34 36 38 40
ARUV2808T1 ARUV3008T1 ARUV3208T1 ARUV3408T1 ARUV3608T1 ARUV3808T1 ARUV4008T1 ARUV1008T1 ARUV1008T1 ARUV1208T1 ARUV1208T1 ARUV1208T1 ARUV1408T1 ARUV1408T1 ARUC1008T1 ARUC1008T1 ARUC1008T1 ARUC1208T1 ARUC1208T1 ARUC1208T1 ARUC1408T1
ARUC808T1 ARUC1008T1 ARUC1008T1 ARUC1008T1 ARUC1208T1 ARUC1208T1 ARUC1208T1
24 24 24 24 24 24 24
-1012345
32 32 32 34 36 38 40
300x3 300x3 300x3 300x3 300x3 300x3 300x3
661.4x3 661.4x3 661.4x3 661.4x3 661.4x3 661.4x3 661.4x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3
Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø34.9(1 3/8
) Ø34.9(1 3/8
) Ø34.9(1 3/8
) Ø34.9(1 3/8
) Ø41.3(1 5/8
) Ø41.3(1 5/8
) Ø41.3(1 5/8
)
12 Outdoor Unit
Outdoor Units Information
Heat Pump
Unit System(HP) Model Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
1 Outdoor Unit(Half size)
1 Outdoor Unit
568101214
ARUN508T1 ARUN608T1 ARUN808T1 ARUN1008T1 ARUN1208T1 ARUN1408T1
44.58 8 8 8 00-1012 6 8 13 16 20 20
150 150 300 300 300 300
330.7 330.7 661.4 661.4 661.4 661.4
806 * 1607 * 730 806 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730
31.7 * 63.3 * 28.74 31.7 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74
Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø12.7(1/2)
Ø15.88(5/8) Ø19.05(3/4) Ø19.05(3/4) Ø22.2(7/8)
Ø28.58(1 1/8) Ø28.58(1 1/8)
Unit System(HP) Model
Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
2 Outdoor Units
3 Outdoor Units
16 18 20 22 24 26
ARUN1608T1 ARUN1808T1 ARUN2008T1 ARUN2208T1 ARUN2408T1 ARUN2608T1
ARUN808T1 ARUN1008T1 ARUN1008T1 ARUN1208T1 ARUN1208T1 ARUN1008T1 ARUH808T1 ARUH808T1 ARUH1008T1 ARUH1008T1 ARUH1208T1 ARUH808T1
ARUH808T1
16 16 16 16 16 24
-2 -1 0 1 2 -2
20 20 20 22 24 32
300x2 300x2 300x2 300x2 300x2 300x3
661.4x2 661.4x2 661.4x2 661.4x2 661.4x2 661.4x3
(1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2
(1280 * 1607 * 730)x3
(50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2
(50.4 * 63.3 * 28.74)x3
)
Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø19.05(3/4)
Ø28.58(1 1/8) Ø28.58(1 1/8) Ø28.58(1 1/8) Ø28.58(1 1/8)
Ø34.9(1 3/8
) Ø34.9(1 3/8
)
Unit System(HP) Model
Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
3 Outdoor Units
28 30 32 34 36 38 40
ARUN2808T1 ARUN3008T1 ARUN3208T1 ARUN3408T1 ARUN3608T1 ARUN3808T1 ARUN4008T1 ARUN1008T1 ARUN1008T1 ARUN1208T1 ARUN1208T1 ARUN1208T1 ARUN1408T1 ARUN1408T1 ARUH1008T1 ARUH1008T1 ARUH1008T1 ARUH1208T1 ARUH1208T1 ARUH1208T1 ARUH1408T1
ARUH808T1 ARUH1008T1 ARUH1008T1 ARUH1008T1 ARUH1208T1 ARUH1208T1 ARUH1208T1
24 24 24 24 24 24 24
-1 0 1 2 3 4 5
32 32 32 34 36 38 40
300x3 300x3 300x3 300x3 300x3 300x3 300x3
661.4x3 661.4x3 661.4x3 661.4x3 661.4x3 661.4x3 661.4x3
(1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3
(50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3
Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø34.9(1 3/8
) Ø34.9(1 3/8
) Ø34.9(1 3/8
) Ø34.9(1 3/8
) Ø41.3(1 5/8
) Ø41.3(1 5/8
) Ø41.3(1 5/8
)
Installation Manual 13
Outdoor Units Information
ENGLISH
Power Supply: Outdoor unit (3Ø, 380V, 60Hz)
Cooling Only
Unit System(HP) Model Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
1 outdoor unit(half size) 1 outdoor unit
568101214
ARUV509T1 ARUV609T1 ARUV809T1 ARUV1009T1 ARUV1209T1 ARUV1409T1
4 4.5 5 8 8 8 001012 6 8 13 16 16 16
150 150 150 300 300 300
330.7 330.7 330.7 661.4 661.4 661.4
806 * 1607 * 730 806 * 1607 * 730 806 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730
31.7 * 63.3 * 28.74 31.7 * 63.3 * 28.74 31.7 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74
Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø12.7(1/2)
Ø15.88(5/8) Ø19.05(3/4) Ø19.05(3/4) Ø22.2(7/8) Ø28.58(
11/8
) Ø28.58(
11/8
)
Unit System(HP) Model
Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
2 outdoor units
16 18 20 22 24 26
ARUV1609T1 ARUV1809T1 ARUV2009T1 ARUV2209T1 ARUV2409T1 ARUV2609T1
ARUV809T1 ARUV1009T1 ARUV1009T1 ARUV1209T1 ARUV1209T1 ARUV1409T1
ARUC809T1 ARUC809T1 ARUC1009T1 ARUC1009T1 ARUC1209T1 ARUC1209T1
16 16 16 16 16 16
-2 -1 0 1 2 3 20 20 20 22 24 26
300x2 300x2 300x2 300x2 300x2 300x2
661.4x2 661.4x2 661.4x2 661.4x2 661.4x2 661.4x2
(1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2
(50.4 * 63.3 * 28.74) +(31.7 * 63.3 * 28.74) (50.4 * 63.3 * 28.74) +(31.7 * 63.3 * 28.74)
(50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2
Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø19.05(3/4)
Ø28.58(
11/8
) Ø28.58(
11/8
) Ø28.58(
11/8
) Ø28.58(
11/8
) Ø34.9(13/8) Ø34.9(13/8)
Unit System(HP) Model
Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
3 outdoor units
28 30 32 34 36 38 40
ARUV2809T1 ARUV3009T1 ARUV3209T1 ARUV3409T1 ARUV3609T1 ARUV3809T1 ARUV4009T1 ARUV1009T1 ARUV1009T1 ARUV1209T1 ARUV1209T1 ARUV1209T1 ARUV1409T1 ARUV1409T1
ARUC1009T1 ARUC1009T1 ARUC1009T1 ARUC1209T1 ARUC1209T1 ARUC1209T1 ARUC1409T1
ARUC809T1 ARUC1009T1 ARUC1009T1 ARUC1009T1 ARUC1209T1 ARUC1209T1 ARUC1209T1
24 24 24 24 24 24 24
-1 0 1 2 3 4 5
32 32 32 34 36 38 40
300x3 300x3 300x3 300x3 300x3 300x3 300x3
661.4x2 661.4x3 661.4x3 661.4x3 661.4x3 661.4x3 661.4x3
(1280 * 1607 * 730)x3
(1280 * 1607 * 730)x3
(1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3
(50.4 * 63.3 * 28.74)x3
(50.4 * 63.3 * 28.74)x3
(50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3
Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø34.9(
13/8
) Ø34.9(
13/8
) Ø34.9(
13/8
) Ø34.9(
13/8
) Ø41.3(
15/8
) Ø41.3(
15/8
) Ø41.3(
15/8
)
14 Outdoor Unit
Outdoor Units Information
Heat Pump
Unit System(HP) Model Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
1 outdoor unit(half size)
1 outdoor unit
568101214
ARUN509T1 ARUN609T1 ARUN809T1 ARUN1009T1 ARUN1209T1 ARUN1409T1
4 4.5 5 8 8 8 001012 6 8 13 16 16 16
150 150 300 300 300 300
330.7 330.7 330.7 661.4 661.4 661.4
806 * 1607 * 730 806 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730 1280 * 1607 * 730
31.7 * 63.3 * 28.74 31.7 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74 50.4 * 63.3 * 28.74
Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø12.7(1/2)
Ø15.88(5/8) Ø19.05(3/4) Ø19.05(3/4) Ø22.2(7/8) Ø28.58(
11/8
) Ø28.58(
11/8
)
Unit System(HP) Model
Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
2 outdoor units
16 18 20 22 24 26
ARUN1609T1 ARUN1809T1 ARUN2009T1 ARUN2209T1 ARUN2409T1 ARUN2609T1
ARUN809T1 ARUN1009T1 ARUN1009T1 ARUN1209T1 ARUN1209T1 ARUN1409T1 ARUH809T1 ARUH809T1 ARUH1009T1 ARUH1009T1 ARUH1209T1 ARUH1209T1
16 16 16 16 16 16
-2 -1 0 1 2 3
20 20 20 22 24 26
300x2 300x2 300 x2 300 x2 300 x2 300 x2+150
661.4 x2 661.4 x2 661.4 x2 661.4 x2 661.4 x2 661.4 x2
(1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2 (1280 * 1607 * 730)x2
661.4 x2 661.4 x2
(50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2 (50.4 * 63.3 * 28.74)x2
Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Ø19.05(3/4)
Ø28.58(
11/8
) Ø28.58(
11/8
) Ø28.58(
11/8
) Ø28.58(
11/8
) Ø34.9(13/8) Ø34.9(13/8)
Unit System(HP) Model
Product Charge kg CF(Correction Factor) kg Max. Connectable No. of Indoor Units Net Weight kg
lbs
Dimensions (W*H*D) mm
inch
Connecting Pipes Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
3 outdoor units
28 30 32 34 36 38 40
ARUN2809T1 ARUN3009T1 ARUN3209T1 ARUN3409T1 ARUN3609T1 ARUN3809T1 ARUN4009T1 ARUN1009T1 ARUN1009T1 ARUN1209T1 ARUN1209T1 ARUN1209T1 ARUN1409T1 ARUN1409T1 ARUH1009T1 ARUH1009T1 ARUH1009T1 ARUH1209T1 ARUH1209T1 ARUH1209T1 ARUH1409T1
ARUH809T1 ARUH1009T1 ARUH1009T1 ARUH1009T1 ARUH1209T1 ARUH1209T1 ARUH1209T1
24 24 24 24 24 24 24
-1 0 1 2 3 4 5
32 32 32 34 36 38 40
300x3 300x3 300x3 300x3 300x3 300x3 300x3
661.4x3 661.4x3 661.4x3 661.4x3 661.4x3 661.4x3 661.4x3
(1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3 (1280 * 1607 * 730)x3
(50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3 (50.4 * 63.3 * 28.74)x3
Ø19.05(3/4)
Ø19.05(3/4)
Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4) Ø19.05(3/4)
Ø34.9(
13/8)Ø34.9(
13/8)Ø34.9(
13/8
) Ø34.9(
13/8
) Ø41.3(15/8) Ø41.3(15/8) Ø41.3(15/8)
ENGLISH
Installation Manual 15
Environment-friendly Alternative Refrigerant R410A
Select the Best Location
Select space for installing outdoor unit, which will meet the following conditions:
No direct thermal radiation from other heat sources
No possibility of annoying the neighbors by noise from unit
No exposition to strong wind
With strength which bears weight of unit
Note that drain flows out of unit when heating
With space for air passage and service work shown next
Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leak
of combustible gas is expected.
Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
Do not use unit under any special environment where oil, steam and sulfuric gas exist.
It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the
outdoor unit.
If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation.
1. Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the prod-
uct at a place with a high humidity in winter (neare beach, coast, lake, etc). (Ex) Rooftop where sunshine always shines.
2. Performance of heating will be reduced and preheat time of the indoor unit may be lengthened in case of
installing the outdoor unit in winter at following location: (1) Shade position with a narrow space (2) Location with much moisture in neighboring floor. (3) Location with much humidity around. (4) Location where ventilation is good.
It is recommended to install the outdoor unit at a place with a lot of sunshine as possible as.
(5) Location where water gathers since the floor is not even.
The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this character­istic should be also considered during the installation. R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is
0. These days the developed countries have approved it as the environmental-friendly refrigerant and encour­aged to use it widely to prevent environmental pollution.
Environment-friendly Alternative Refrigerant R410A
CAUTION:
The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8MPa
Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
For high-pressure refrigerant, any unapproved pipe must not be used.
Do not heat up pipes more than its necessity to prevent them from softening.
Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
16 Outdoor Unit
Installation Space
Installation Space
Individual Installation
Basic space required
A space of at least 250 mm is necessary at the back for inlet air. Taking servicing, etc. from the rear into account, a space of about 900 mm should be provided, the same as at the front.
When inlet air enters from right and left sides of unit
250 mm or more 900 mm or more (Control box is of a open/close type) Top discharge (open in principle) Front inlet (open in principle) Rear inlet (open in principle)
A B C D E
A
B
Control Box
Front Side
Rear Side
A
B
Control Box
Front Side
Rear Side
A
B
Control Box
Front Side
Rear Side
A
B C
900 mm or more (Control box is of a open/close type) 250 mm or more 150 mm from the wall
C
A
B
C
A
B
h
H
Front Side
Rear Side
C
A
B
C
Front Side
Rear Side
C
A
B
C
Front Side
Rear Side
C
A
B
C
A
B
Control Box
Front Side
Rear Side
Front Side
Rear Side
< Side view > < Top view >
< Side view > < Top view >
C
ED
A
B
250 mm or more (350mm or more at the coastal area) 150 mm from the wall
B
A
B
A
h
H
Front Side
Rear Side
B
A
B
Front Side
Rear Side
B
A
B
Front Side
Rear Side
B
A
B
Front Side
Rear Side
< Side view > < Top view >
CAUTION
Wall height(H) must not exceed height of the product. If the wall height is higher than the whole height of product by (h), Add (h) to , .
CAUTION
Wall height(H) must not exceed height of the product. If the wall height is higher than the whole height of product by (h), Add (h) to
, .
Installation Manual 17
ENGLISH
Installation Space
E
D
F
A
B
C
A
B
C
A
B
C
45° or more 200 mm or more 250 mm or more
A B C
1000 mm or more Air outlet guide (Procured at the site) 250 mm or more
D E F
A
B
C
< Front view >
< Side view >
When there is an obstruction above the unit
When unit is surrounded by walls
900 mm or more (Control box is of a open/close type) 250 mm or more
A B
A
B
B
B
Front Side
Rear Side
A
B
B
B
Front Side
Rear Side
A
B
B
B
Front Side
Rear Side
Front Side
Rear Side
A
B
B
B
18 Outdoor Unit
Installation Space
Collective / Continuous installation
Space required for collective installation and continuous installation:When installing several units, leave the space between each block as shown below considering passage for air and people.
(Be opened) 900mm or more (control box is of a open/close type) 250 mm or more
A B
= 1250mm or more at the coastal area
B
C
Front Side
Rear Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Front Side
Rear Side
Installation Manual 19
ENGLISH
Cautions in winter especially for seasonal wind
Sufficient measures are required at a snow area or severe cold area in winter so that product can be operated
well.
Get ready for seasonal wind or snow in winter even in other area.
Install a suction and discharge duct not to let in snow or rain.
Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction
hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average
snowfall) if it is installed at the area with much snowfall.
Where snow accumulated on the upper part of the outdoor unit by more than 10cm, always remove snow for
operation.
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the outdoor unit facing to the seasonal wind.
Installation Space
CAUTION
Always apply main power of the outdoor unit during use of product (cooling season/heating season).
Always apply power before 6 hours to heat the crank case heater where performing test run after instal­lation of product or where operating the product after cutting the main power of the outdoor unit (for example, power failure). It may result in burning out of the compressor if not preheating the crank case with the electrical heater for more than 6 hours.(In case of the outdoor temperature below 10°C)
20 Outdoor Unit
Lifting Method
When carrying the unit suspended, pass the ropes under the unit and use the two suspension points each at the front and rear.
Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
Attach the ropes to the unit at an angle of 40° or less.
Lifting method
CAUTION
Be very careful while carrying the product.
Do not have only one person carry product if it is more than 20 kg.
PP bands are used to pack some products. Do not use them as a mean for transportation because they
are dangerous.
Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging
bag may suffocate children to death.
When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it.
Sub line
A
40° or less
WARNING
Installation Manual 21
ENGLISH
Installation
Location of anchor bolt
Installation
Individual installation
Example of collective installation
Installation foot (Location of anchor bolt)
700
10
900
383
900
700
900
700
900
700
900
10
383
900
10
383
900
900
10 383
900
383
900
10
383
900
10
383
900
10
383
900
10
Half size
22 Outdoor Unit
Installation
Foundation for Installation
Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
Use the H-beam support as a base support
Noise and vibration may occur from the floor or wall since vibration is transferred through the installation
part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200mm).
A
B
D
E F G
C
Ensure that the corner part can be securely mounted. Otherwise, the support for installation may be bent.
Obtain and use the M10 anchor bolt. The corner was not properly mounted. Outdoor unit (Insert the cushion pad between outdoor unit and base support to ensure that
anti-vibration may be done in a wide area) Pipe and wiring space (in case of piping and wiring on the floor surface) H-Beam support Concrete base support
G
WARNING
Be sure to install unit in a place strong enough to withstand its weight. Any lack of strength may cause unit to fall down, resulting in a personal injury.
Have installation work in order to protect against a strong wind and earthquake. Any installation deficiency may cause unit to fall down, resulting in a personal injury.
Especially take care for support strength of the floor surface, water drain processing (processing of water flown out from the outdoor unit during operation) and paths of the pipe and wiring when mak­ing a base support.
Don't use a tube or pipe for water drain in the base pan and perform water drain processing by using the drain path. Water drain may not be done due to freezing of a tube or pipe.
Rear view Side view
Water
Drain Path
Installation Manual 23
ENGLISH
Installation
Preparation of Piping
1) Cut the pipes and the cable.
Use the accessory piping kit or the pipes purchased locally.
Measure the distance between the indoor and the out­door unit.
Cut the pipes a little longer than measured distance.
Cut the cable 1.5m longer than the pipe length.
2) Burrs removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe to downward direc­tion as you remove burrs in order to avoid to let burrs drop in the tubing.
3) Flaring work
Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
4) Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared section
and do flaring work again.
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Pipe " A "
Gas Liquid Gas
Liquid
<5.6(19,100) 1/2" 1/4" 0.5~0.8 0~0.5 <16.0(54,600) 5/8" 3/8" 0.8~1.0 0.5~0.8 <22.4(76,400) 3/4" 3/8" 1.0~1.3 0.5~0.8
Indoor unit [kW(Btu/h]
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
24 Outdoor Unit
Installation
1. Remove the cap and turn the valve counter clockwise with the hexagon wrench.
2. Turn it until the shaft stops. Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3. Make sure to tighten the cap securely.
1. Remove the cap and turn the valve clockwise with the hexagon wrench.
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely. * For the tightening torque, refer to the table on the below.
Precautions when connecting pipes
See the following table for flare part machining dimensions.
When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three
or four times at first. (Use ester oil or ether oil.)
See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
After all the piping has been connected, use nitrogen to perform a gas leak check.
Tightening torque
Union
CAUTION
Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks are
present.
When loosening a flare nut, always use two wrenches in combination, When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.
When connecting a flare nut, coat the flare(inner and outer faces) with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as the initial tightening.
Opening shutoff valve
Closing shutoff valve
FLARE SHAPE and FLARE NUT TIGHTENING TORQUE
Shutoff
valve size
Ø6.4 Ø9.5
Ø12.7 Ø15.9 Ø22.2
Ø25.4
13.5-16.5 18-22
14-17 33-39 50-60
62-75
23-27
13.5-16.5
5.4-6.6
Hexagonal
wrench 4mm
Hexagonal
wrench 6mm
Hexagonal
wrench 10mm
8.1-9.9
27-33 36-44
-
11.5-13.9
22-28-
Tightening torque N-m(Turn clockwise to close)
Shaft(valve body)
Gas line piping attached to unit
Cap(Valve lid) Service port Flare nut
90°
±2
45
°
±
2
A
R=0.4~0.8
pipe size tightening torque(Ncm) A(mm) flare shape
Ø9.5 3270-3990 12.8-13.2
Ø12.7 4950-6030 16.2-16.6
Ø15.9 6180-7540 19.3-19.7