LG ARUN100LTE4 INSTALLATION MANUAL

INSTALLATION MANUAL
ENGLISH
ESPAÑOL
PORTUGUÊS
AIR CONDITIONER
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Original instruction
P/NO : MFL67221421
www.lg.com
2
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
IMPORTANT SAFETY INSTRUC­TIONS
READ ALL INSTRUCTIONS BEFORE USING THE AP­PLIANCE.
Always comply with the following precautions to avoid dangerous situ­ations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in haz­ards to you and others.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Have all electric work done by a licensed electrician according to "Elec­tric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is per-
formed improperly, electric shock or fire may result.
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric
shock, or fire.
• Always ground the product.
- There is risk of fire or electric shock.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Do not store or use flammable gas or combustibles near the air condi­tioner.
- There is risk of fire or failure of product.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Prepare for strong wind or earthquake and install the unit at the speci­fied place.
- Improper installation may cause the unit to topple and result in injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• When installing and moving the air conditioner to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the
refrigerant cycle may malfunction and the unit may be damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is
shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
• Ventilate before operating air conditioner when gas leaked out.
- It may cause explosion, fire, and burn.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed securely, dust or water may
enter the outdoor unit and fire or electric shock may result.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
- Consult the dealer regarding the appropriate measures to prevent the
safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
Operation
• Do not damage or use an unspecified power cord.
- There is risk of fire, electric shock, explosion, or injury.
• Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Do not touch the power switch with wet hands.
- There is risk of fire, electric shock, explosion, or injury.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious not to touch the sharp edges when installing.
- It may cause injury.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
• Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
!
!
!
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehu­midifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
3
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Use power cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Keep the unit away from children. The heat exchanger is very sharp.
- It can cause the injury, such as cutting the finger. Also the damaged fin may re-
sult in degradation of capacity.
• When installting the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
-
The inverter equipment, private power generator, high-frequency medical equipment, or radio communication equipment may cause the air condi­tioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs med­ical treatment or image broadcasting.
• Do not install the product where it is exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser
and evaporator fins, could cause product malfunction or inefficient operation.
Operation
• Do not use the air conditioner in special environments.
-
Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
• Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
• Make the connections securely so that the outside force of the cable may not be applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property
damage, product failure, or personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
- A bad connection may cause water leakage.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
-
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspending it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
• Safely dispose of the packing materials.
-
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
-
Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
• Turn on the power at least 6 hours before starting operation.
- Starting operation immediately after turning on the main power switch can re-
sult in severe damage to internal parts. Keep the power switch turned on dur­ing the operational season.
• Do not touch any of the refrigerant piping during and after operation.
- It can cause a burn or frostbite.
• Do not operate the air conditioner with the panels or guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not directly turn off the main power switch after stopping operation.
- Wait at least 5 minutes before turning off the main power switch. Otherwise it
may result in water leakage or other problems.
Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the indoor unit PCB.
• Use a firm stool or ladder when cleaning or maintaining the air conditioner.
- Be careful and avoid personal injury.
• Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
- There are sharp and moving parts that could cause personal injury.
TABLE OF CONTENTS
2 TIPS FOR SAVING ENERGY 2 IMPORTANT SAFETY INSTRUCTIONS
4 INSTALLATION PROCESS 4 OUTDOOR UNITS INFORMATION 6 ALTERNATIVE REFRIGERANT R410A 6 SELECT THE BEST LOCATION 7 INSTALLATION SPACE
7 Individual Installation
7 LIFTING METHOD 8 INSTALLATION
8 The location of the Anchor bolts 8 Foundation for Installation 8 Preparation of Piping 10
Plumbing materials and storage methods
10 REFRIGERANT PIPING INSTALLATION
10 Precautions on Pipe connection / Valve operation
11
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
11 Preparation Work 11 Pipe Drawing Out during Single / Series connection 12 Refrigerant piping system 12 Pipe Connection Method between outdoor unit/indoor unit 15 Refrigerant charging 16 Distribution Method 16 Branch pipe Fitting 17 Leak Test and Vacuum drying 18 Vacuum Mode 19 Thermal insulation of refrigerant piping
19 ELECTRICAL WIRING
19 Caution 20 Control box and connecting position of wiring 21 Communication and Power Cables 21 Wiring of main power supply and equipment capacity 22
Point for attention regarding quality of the public electric power supply
22 Field Wiring 24 Checking the setting of outdoor units 24 Automatic Addressing 25 Group Number setting 25 Cool & Heat selector 25 Static pressure compensation mode 26 Night Low Noise Function 26 Overall defrost mode 26 Setting the ODU address 26 Snow removal & rapid defrost 27 IDU capacity adjusting 27 Target pressure adjusting 27 Comfort Operation 28 Self-Diagnosis Function
30 CAUTION FOR REFRIGERANT LEAK
30 Introduction 30 Checking procedure of limiting concentration
31 INSTALLATION GUIDE AT THE SEASIDE
!
ENGLISH
4
ENGLISH
INSTALLATION PROCESS
The foundation must be level even
Outdoor unit foundation work
Avoid short circuits and ensure sufficient space is allowed for service
Installation of outdoor unit
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
2
) there
must be no drop in pressure.
Airtight test
Multiple core cable must not be used. (suitable cable should be selected)
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness, cleanness and tightness
Refrigerant piping work
Check model name to make sure the fitting is made correctly
Installation of indoor unit
Take account of gradient of drain piping
Sleeve and insert work
Make connection clearly between outdoor, indoor, remote controller and option.
Preparation of contract drawings
Indicate clearly who will be responsible for switch setting.
Determination of division work
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Vacuum drying
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order
Transfer to customer with explanation
Preheat the crank case with the electrical heater for more than 6 hours.
CAUTION
• The above list indicates the order in which the individual work operations are normally carried out but this order may be varied where local conditions warrants such change.
• The thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)
!
CAUTION
Notes : * We can guarantee the operation only within 130%
Combination. If you want to connect more than 130% combination, please contact us and discuss the requirement like below.
• If the operation of indoor unit is more than 130%, the airflow is operated as low in the all indoor units.
• The number of ( ) means the number of Max. connectable indoor units, when the connected capacity of indoor units is in the table above.
Combination Ratio(50~200%)
Outdoor Number Connection Ratio
Single outdoor units 200%
Double outdoor units 160%
Triple outdoor units 130%
!
OUTDOOR UNITS INFORMATION
Unit
1 Outdoor Unit
System(HP)
14 16 18 20
Model
Combination Unit
ARUN140LTE4 ARUN160LTE4 ARUN180LTE4 ARUN200LTE4
Independent Unit
ARUN140LTE4 ARUN160LTE4 ARUN180LTE4 ARUN200LTE4
Refrigerant Precharged Amount
kg
10.5 10.5 10.5 10.5
lbs
23.1 23.1 23.1 23.1
Number of maxmum connectable indoor units
23(35) 26(40) 29(45) 32(50)
Net Weight
kg
245 × 1 245 × 1 280 × 1 280 × 1
lbs
540 × 1 540 × 1 617 × 1 617 × 1
Dimensions (WxHxD)
mm
(1,240x1,680x760) x 1 (1,240×1,680×760) × 1 (1,240×1,680×760) × 1 (1,240×1,680×760) × 1
inch
(48-13/16 × 66-5/32
× 29-29/32) x 1
(48-13/16 × 66-5/32
× 29-29/32) x 1
(48-13/16 × 66-5/32
× 29-29/32) x 1
(48-13/16 × 66-5/32
× 29-29/32) x 1
Piping Conections
mm(inch)
Ø 12.7(1/2) Ø 12.7(1/2) Ø 15.88(5/8) Ø 15.88(5/8)
mm(inch)
Ø 28.58(1-1/8) Ø 28.58(1-1/8) Ø 28.58(1-1/8) Ø 28.58(1-1/8)
Unit
2 Outdoor Unit
System(HP)
22 24 26 28
Model
Combination Unit
ARUN220LTE4 ARUN240LTE4 ARUN260LTE4 ARUN280LTE4
Independent Unit
ARUN120LTE4 ARUN120LTE4 ARUN140LTE4 ARUN160LTE4 ARUN100LTE4 ARUN120LTE4 ARUN120LTE4 ARUN120LTE4
Refrigerant Precharged Amount
kg
7.5 x 2 7.5 x 2 10.5 + 7.5 10.5 + 7.5
lbs
16.5 x 2 16.5 x 2 23.1 + 16.5 23.1 + 16.5
Number of maxmum connectable indoor units
35(44) 39(48) 42(52) 45(56)
Net Weight
kg
208 x 2 208 x 2
(245 × 1) + (208 × 1) (245 × 1) + (208 × 1)
lbs
458 x 2 458 x 2
(540 × 1) + (458 × 1) 540 × 1) + (458 × 1)
Dimensions (WxHxD)
mm
(920×1,680×760) x 2 (920×1,680×760) x 2
(1,240x1,680x760) x 1 + (920x1,680x760) x 1
(1,240×1,680×760) × 1 + (920×1,680×760) × 1
inch
(36-7/32 × 66-5/32 ×
29-29/32) x 2
(36-7/32 × 66-5/32 ×
29-29/32) x 2
(48-13/16 × 66 -5/32 × 29 ­29/32) x 1 + (36-7/32 × 66 -
5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 1 + (36-7/32 × 66-
5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 15.88(5/8) Ø 15.88(5/8) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 28.58(1-1/8) Ø 34.9(1-3/8) Ø 34.9(1-3/8) Ø 34.9(1-3/8)
Unit
2 Outdoor Unit
System(HP)
30 32 34 36
Model
Combination Unit
ARUN300LTE4 ARUN320LTE4 ARUN340LTE4 ARUN360LTE4
Independent Unit
ARUN180LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN120LTE4 ARUN120LTE4 ARUN140LTE4 ARUN160LTE4
Refrigerant Precharged Amount
kg
10.5 + 7.5 10.5 + 7.5 10.5 × 2 10.5 × 2
lbs
23.1 + 16.5 23.1 + 16.5 23.1 × 2 23.1 × 2
Number of maxmum connectable indoor units
49(60) 52(64) 55(64) 58(64)
Net Weight
kg
(280 × 1) + (208 × 1) (280 × 1) + (208 × 1) (280 × 1) + (245 × 1) (280 × 1) + (245 × 1)
lbs
(617 × 1) + (458 × 1) (617 × 1) + (458 × 1) (617 × 1) + (540 × 1) (617 × 1) + (540 × 1)
Dimensions (WxHxD)
mm
(1,240×1,680×760) × 1 + (920×1,680×760) × 1
(1,240×1,680×760) × 1 + (920×1,680×760) × 1
(1,240×1,680×760) x 2 (1,240×1,680×760) x 2
inch
(48-13/16 × 66-5/32 × 29-
29/32) x 1 + (36-7/32 × 66-
5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 1 + (36-7/32 × 66-
5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32
× 29-29/32) x 2
(48-13/16 × 66-5/32 ×
29-29/32) x 2
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 34.9(1-3/8) Ø 34.9(1-3/8) Ø 34.9(1-3/8) Ø 41.3(1-5/8)
Unit
2 Outdoor Unit 3 Outdoor Unit
System(HP)
38 40 42 44
Model
Combination Unit
ARUN380LTE4 ARUN400LTE4 ARUN420LTE4 ARUN440LTE4
Independent Unit
ARUN200LTE4 ARUN200LTE4 ARUN180LTE4 ARUN200LTE4 ARUN180LTE4 ARUN200LTE4 ARUN140LTE4 ARUN140LTE4
ARUN100LTE4 ARUN100LTE4
Refrigerant Precharged Amount
kg
10.5 x 2 10.5 x 2 (10.5 × 2) + 7.5 (10.5 × 2) + 7.5
lbs
23.1 x 2 23.1 x 2 (23.1 × 2) + 16.5 (23.1 × 2) + 16.5
Number of maxmum connectable indoor units
61(64) 64 64 64
Net Weight
kg
280 x 2 280 x 2
(280 × 1) + (245 x 1) + (208 × 1) (280 × 1) + (245 x 1) + (208 × 1)
lbs
617 x 2 617 x 2
(617 × 1) + (540 x 1) + (458 × 1) (617 × 1) + (540 x 1) + (458 × 1)
Dimensions (WxHxD)
mm
(1,240×1,680×760) x 2 (1,240×1,680×760) x 2
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
inch
(48-13/16 × 66-
5/32 × 29-29/32)
x 2
(48-13/16 × 66-
5/32 × 29-29/32)
x 2
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 × 66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 × 66-
5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8)
Unit
1 Outdoor Unit
System(HP)
8 10 12
Model
Combination Unit
ARUN080LTE4 ARUN100LTE4 ARUN120LTE4
Independent Unit
ARUN080LTE4 ARUN100LTE4 ARUN120LTE4
Refrigerant Precharged Amount
kg
7.5 7.5 7.5
lbs
16.5 16.5 16.5
Number of maxmum connectable indoor units
13(20) 16(25) 20(30)
Net Weight
kg
202 x 1 208 x 1 208 x 1
lbs
445 x 1 458 x 1 458 x 1
Dimensions (WxHxD)
mm (920×1,680×760) × 1 (920×1,680×760) × 1 (920×1,680×760) × 1 inch
(36-7/32 × 66-5/32 × 29-29/32) x 1 (36-7/32 × 66-5/32 × 29-29/32) x 1 (36-7/32 × 66-5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 9.52(3/8) Ø 9.52(3/8) Ø 12.7(1/2)
mm(inch)
Ø 19.05(3/4) Ø 22.2(7/8) Ø 28.58(1-1/8)
Power Supply : 3Ø, 380V, 60Hz or 3Ø, 380 - 415V, 50Hz Model Name : ARUN***LTE4
5
ENGLISH
Unit
3 Outdoor Unit
System(HP)
46 48 50 52
Model
Combination Unit
ARUN460LTE4 ARUN480LTE4 ARUN500LTE4 ARUN520LTE4
Independent Unit
ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN160LTE4 ARUN180LTE4 ARUN200LTE4 ARUN200LTE4 ARUN100LTE4 ARUN100LTE4 ARUN100LTE4 ARUN120LTE4
Refrigerant Precharged Amount
kg
(10.5 × 2) + 7.5 (10.5 × 2) + 7.5 (10.5 × 2) + 7.5 (10.5 × 2) + 7.5
lbs
(23.1 × 2) + 16.5 (23.1 × 2) + 16.5 (23.1 × 2) + 16.5 (23.1 × 2) + 16.5
Number of maxmum connectable indoor units
64 64 64 64
Net Weight
kg
(280 × 1) + (245 x 1) + (208 × 1)
(280 x 2) +(208 × 1) (280 x 2) +(208 × 1) (280 x 2) +(208 × 1)
lbs
(617× 1) + (540 x 1) + (458 × 1)
(617 x 2) +(458 × 1) (617 x 2) +(458 × 1) (617 x 2) +(458 × 1)
Dimensions (WxHxD)
mm
(1,240×1,680×760) × 2
+ (920×1,680×760) × 1
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
inch
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 × 66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 × 66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 × 66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 × 66-5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8)
Unit
3 Outdoor Unit
System(HP)
54 56 58 60
Model
Combination Unit
ARUN540LTE4 ARUN560LTE4 ARUN580LTE4 ARUN600LTE4
Independent Unit
ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN140LTE4 ARUN160LTE4 ARUN180LTE4 ARUN200LTE4
Refrigerant Precharged Amount
kg
10.5 × 3 10.5 × 3 10.5 x 3 10.5 x 3
lbs
23.1 x 3 23.1 x 3 23.1 x 3 23.1 x 3
Number of maxmum connectable indoor units
64 64 64 64
Net Weight
kg
(280 × 2) + (245 x 1) (280 × 2) + (245 x 1)
280 × 3 280 × 3
lbs
(617 × 2) + (540 × 1) (617 × 2) + (540 × 1)
617 × 3 617 × 3
Dimensions (WxHxD)
mm
(1,240x1,680x760) x 3 (1,240×1,680×760) × 3 (1,240×1,680×760) × 3 (1,240×1,680×760) × 3
inch
(48-13/16 × 66-5/32
× 29-29/32) x 3
(48-13/16 × 66-
5/32 × 29-29/32) x 3
(48-13/16 × 66-
5/32 × 29-29/32) x 3
(48-13/16 × 66-
5/32 × 29-29/32) x 3
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8)
Unit
4 Outdoor Unit
System(HP)
62 64 66 68
Model
Combination Unit
ARUN620LTE4 ARUN640LTE4 ARUN660LTE4 ARUN680LTE4
Independent Unit
ARUN180LTE4 ARUN180LTE4 ARUN180LTE4 ARUN200LTE4 ARUN160LTE4 ARUN180LTE4 ARUN180LTE4 ARUN200LTE4 ARUN140LTE4 ARUN140LTE4 ARUN160LTE4 ARUN140LTE4 ARUN140LTE4 ARUN140LTE4 ARUN140LTE4 ARUN140LTE4
Refrigerant Precharged Amount
kg
10.5 x 4 10.5 x 4 10.5 x 4 10.5 x 4
lbs
23.1 x 4 23.1 x 4 23.1 x 4 23.1 x 4
Number of maxmum connectable indoor units
64 64 64 64
Net Weight
kg
(280 × 1) + (245 x 3) (280 × 2) + (245 x 2) (280 × 2) + (245 x 2) (280 × 2) + (245 x 2)
lbs
(617 × 1) + (540 × 3) (617 × 2) + (540 × 2) (617 × 2) + (540 × 2) (617 × 2) + (540 × 2)
Dimensions (WxHxD)
mm
(1,240x1.680x760) x 4 (1,240×1,680×760) × 4 (1,240×1,680×760) × 4 (1,240×1,680×760) × 4
inch
(48-13/16 × 66-5/32
× 29-29/32) x 4
(48-13/16 × 66-5/32 ×
29-29/32) x 4
(48-13/16 × 66-5/32 ×
29-29/32) x 4
(48-13/16 × 66-5/32 ×
29-29/32) x 4
Piping Conections
mm(inch)
Ø 22.2(7/8) Ø 22.2(7/8) Ø 22.2(7/8) Ø 22.2(7/8)
mm(inch)
Ø 44.5(1-3/4) Ø 44.5(1-3/4) Ø 53.98(2-1/8) Ø 53.98(2-1/8)
Unit
4 Outdoor Unit
System(HP)
70 72 74 76
Model
Combination Unit
ARUN700LTE4 ARUN720LTE4 ARUN740LTE4 ARUN760LTE4
Independent Unit
ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN160LTE4 ARUN180LTE4 ARUN180LTE4 ARUN180LTE4 ARUN140LTE4 ARUN140LTE4 ARUN160LTE4 ARUN180LTE4
Refrigerant Precharged Amount
kg
10.5 x 4 10.5 x 4 10.5 x 4 10.5 x 4
lbs
23.1 x 4 23.1 x 4 23.1 x 4 23.1 x 4
Number of maxmum connectable indoor units
64 64 64 64
Net Weight
kg
(280 × 2) + (245 x 2) (280 × 3) + (245 x 1) (280 × 3) + (245 x 1)
280 × 4
lbs
(617 × 2) + (540 × 2) (617 × 3) + (540 × 1) (617 × 3) + (540 × 1)
617 × 4
Dimensions (WxHxD)
mm
(1,240×1,680×760) × 4 (1,240×1,680×760) × 4 (1,240×1,680×760) × 4 (1,240×1,680×760) × 4
inch
(48-13/16 × 66-5/32
× 29-29/32) x 4
(48-13/16 × 66-5/32
× 29-29/32) x 4
(48-13/16 × 66-5/32
× 29-29/32) x 4
(48-13/16 × 66-5/32
× 29-29/32) x 4
Piping Conections
mm(inch)
Ø 22.2(7/8) Ø 22.2(7/8) Ø 22.2(7/8) Ø 22.2(7/8)
mm(inch)
Ø 53.98(2-1/8) Ø 53.98(2-1/8) Ø 53.98(2-1/8) Ø 53.98(2-1/8)
Unit
4 Outdoor Unit
System(HP)
78 80
Model
Combination Unit
ARUN780LTE4 ARUN800LTE4
Independent Unit
ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN200LTE4 ARUN180LTE4 ARUN200LTE4
Refrigerant Precharged Amount
kg
10.5 x 4 10.5 x 4
lbs
23.1 x 4 23.1 x 4
Number of maxmum connectable indoor units
64 64
Net Weight
kg
280 × 4 280 × 4
lbs
617 x 4 617 x 4
Dimensions (WxHxD)
mm
(1,240×1,680×760) × 4 (1,240×1,680×760) × 4
inch
(48-13/16 × 66-5/32 × 29-29/32) x 4 (48-13/16 × 66-5/32 × 29-29/32) x 4
Piping Conections
mm(inch)
Ø 22.2(7/8) Ø 22.2(7/8)
mm(inch)
Ø 53.98(2-1/8) Ø 53.98(2-1/8)
Unit
1 Outdoor Unit
System(HP)
14 16 18 20
Model
Combination Unit
ARUN140LTS4 ARUN160LTS4 ARUN180LTS4 ARUN200LTS4
Independent Unit
ARUN140LTS4 ARUN160LTS4 ARUN180LTS4 ARUN200LTS4
Refrigerant Precharged Amount
kg
8.5 8.5 8.5 10
lbs
18.7 18.7 18.7 22
Number of maxmum connectable indoor units
23(35) 26(40) 29(45) 32(50)
Net Weight
kg
235 × 1 235 × 1 270 × 1 280 × 1
lbs
518 × 1 518 × 1 595 × 1 617 × 1
Dimensions (WxHxD)
mm
(1,240x1,680x760) x 1 (1,240×1,680×760) × 1 (1,240×1,680×760) × 1 (1,240×1,680×760) × 1
inch
(48-13/16 × 66-5/32
× 29-29/32) x 1
(48-13/16 × 66-5/32
× 29-29/32) x 1
(48-13/16 × 66-5/32
× 29-29/32) x 1
(48-13/16 × 66-5/32
× 29-29/32) x 1
Piping Conections
mm(inch)
Ø 12.7(1/2) Ø 12.7(1/2) Ø 15.88(5/8) Ø 15.88(5/8)
mm(inch)
Ø 28.58(1-1/8) Ø 28.58(1-1/8) Ø 28.58(1-1/8) Ø 28.58(1-1/8)
Unit
2 Outdoor Unit
System(HP)
22 24 26 28
Model
Combination Unit
ARUN220LTS4 ARUN240LTS4 ARUN260LTS4 ARUN280LTS4
Independent Unit
ARUN120LTS4 ARUN120LTS4 ARUN140LTS4 ARUN160LTS4 ARUN100LTS4 ARUN120LTS4 ARUN120LTS4 ARUN120LTS4
Refrigerant Precharged Amount
kg
6.5 × 2 6.5 × 2 8.5 + 6.5 8.5 + 6.5
lbs
14.3 × 2 14.3 × 2 18.7 + 14.3 18.7 + 14.3
Number of maxmum connectable indoor units
35(44) 39(48) 42(52) 45(56)
Net Weight
kg
201 × 2 201 × 2
(235 × 1) + (201 × 1) (235 × 1) + (201 × 1)
lbs
443 × 2 443 × 2
(518 × 1) + (443 × 1) (518 × 1) + (443 × 1)
Dimensions (WxHxD)
mm
(920×1,680×760) x 2 (920×1,680×760) x 2
(1,240x1,680x760) x 1 +
(920x1,680x760) x 1
(1,240×1,680×760) × 1 +
(920×1,680×760) × 1
inch
(36-7/32 × 66-5/32 ×
29-29/32) x 2
(36-7/32 × 66-5/32 ×
29-29/32) x 2
(48-13/16 × 66 -5/32 × 29 ­29/32) x 1 + (36-7/32 × 66 -
5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 1 + (36-7/32 × 66-
5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 15.88(5/8) Ø 15.88(5/8) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 28.58(1-1/8) Ø 34.9(1-3/8) Ø 34.9(1-3/8) Ø 34.9(1-3/8)
Unit
2 Outdoor Unit
System(HP)
30 32 34 36
Model
Combination Unit
ARUN300LTS4 ARUN320LTS4 ARUN340LTS4 ARUN360LTS4
Independent Unit
ARUN180LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN120LTS4 ARUN120LTS4 ARUN140LTS4 ARUN160LTS4
Refrigerant Precharged Amount
kg
8.5 + 6.5 10 + 6.5 10 + 8.5 10 + 8.5
lbs
18.7 + 14.3 22 + 14.3 22 + 18.7 22 + 18.7
Number of maxmum connectable indoor units
49(60) 52(64) 55(64) 58(64)
Net Weight
kg
(270 × 1) + (201 × 1) (280 × 1) + (201 × 1) (280 × 1) + (235 × 1) (280 × 1) + (235 × 1)
lbs
(595× 1) + (443 × 1) (617 × 1) + (443 × 1) (617 × 1) + (518 × 1) (617 × 1) + (518 × 1)
Dimensions (WxHxD)
mm
(1,240x1,680x760) x 2 (1,240×1,680×760) x 2 (1,240×1,680×760) x 2 (1,240×1,680×760) x 2
inch
(48-13/16 × 66-5/32
× 29-29/32) x 2
(48-13/16 × 66-5/32
× 29-29/32) x 2
(48-13/16 × 66-5/32
× 29-29/32) x 2
(48-13/16 × 66-5/32 ×
29-29/32) x 2
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 34.9(1-3/8) Ø 34.9(1-3/8) Ø 34.9(1-3/8) Ø 41.3(1-5/8)
Unit
2 Outdoor Unit 3 Outdoor Unit
System(HP)
38 40 42 44
Model
Combination Unit
ARUN380LTS4 ARUN400LTS4 ARUN420LTS4 ARUN440LTS4
Independent Unit
ARUN200LTS4 ARUN200LTS4 ARUN180LTS4 ARUN200LTS4 ARUN180LTS4 ARUN200LTS4 ARUN140LTS4 ARUN140LTS4
ARUN100LTS4 ARUN100LTS4
Refrigerant Precharged Amount
kg
10 + 8.5 10 × 2 (8.5 × 2) + 6.5 10 + 8.5 + 6.5
lbs
22 + 18.7 22 × 2 (18.7 × 2) + 14.3 22 + 18.7 + 14.3
Number of maxmum connectable indoor units
61(64) 64 64 64
Net Weight
kg
(280 × 1) + (270 x 1)
280 × 2
(270 × 1) + (235 × 1)
+ (201 × 1)
(280 × 1) + (235 × 1)
+ (201 × 1)
lbs
(617 × 1) + (595 × 1)
617 × 2
(595 × 1) + (518 × 1) +
(443 × 1)
(617 × 1) + (518 × 1) +
(443 × 1)
Dimensions (WxHxD)
mm
(1,240×1,680×760) x 2 (1,240×1,680×760) x 2
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
inch
(48-13/16 × 66-5/32 ×
29-29/32) x 2
(48-13/16 × 66-5/32 ×
29-29/32) x 2
(48-13/16 × 66-5/32 ×
29-29/32) x 2 + (36-
7/32 × 66-5/32 × 29-
29/32) x 1
(48-13/16 × 66-5/32 ×
29-29/32) x 2 + (36-
7/32 × 66-5/32 × 29-
29/32) x 1
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8)
Unit
1 Outdoor Unit
System(HP)
8 10 12
Model
Combination Unit
ARUN080LTS4 ARUN100LTS4 ARUN120LTS4
Independent Unit
ARUN080LTS4 ARUN100LTS4 ARUN120LTS4 Refrigerant Precharged Amount
kg
6.5 6.5 6.5
lbs
14.3 14.3 14.3
Number of maxmum connectable indoor units
13(20) 16(25) 20(30)
Net Weight
kg
195 × 1 201 × 1 201 × 1
lbs
430 × 1 443 × 1 443 × 1
Dimensions (WxHxD)
mm (920×1,680×760) × 1 (920×1,680×760) × 1 (920×1,680×760) × 1 inch
(36-7/32 × 66-5/32 × 29-29/32) x 1 (36-7/32 × 66-5/32 × 29-29/32) x 1 (36-7/32 × 66-5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 9.52(3/8) Ø 9.52(3/8) Ø 12.7(1/2)
mm(inch)
Ø 19.05(3/4) Ø 22.2(7/8) Ø 28.58(1-1/8)
Model Name : ARUN***LTS4
6
ENGLISH
ALTERNATIVE REFRIGERANT R410A
The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also consid­ered during the installation. R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0.
SELECT THE BEST LOCATION
Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors by noise from unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sul­fur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to pre­vent any person or animal from accessing the outdoor unit.
• If installation site is area of heavy snowfall, then the following direc­tions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of
sunshine in case of installing the product at a place With a high hu­midity in winter (near beach, coast, lake, etc.) (Ex : Rooftop where there is always sunshine.)
CAUTION
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
!
Unit
3 Outdoor Unit
System(HP)
46 48 50 52
Model
Combination Unit
ARUN460LTS4 ARUN480LTS4 ARUN500LTS4 ARUN520LTS4
Independent Unit
ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN160LTS4 ARUN180LTS4 ARUN200LTS4 ARUN200LTS4 ARUN100LTS4 ARUN100LTS4 ARUN100LTS4 ARUN120LTS4
Refrigerant Precharged Amount
kg
10 + 8.5 + 6.5 10 + 8.5 + 6.5 (10 × 2) + 6.5 (10 × 2) + 6.5
lbs
22 + 18.7 + 14.3 22 + 18.7 + 14.3 (22 × 2) + 14.3 (22 × 2) + 14.3
Number of maxmum connectable indoor units
64 64 64 64
Net Weight
kg
(280 × 1) + (235 × 1) + (201 × 1) (280 × 1) + (270 × 1) + (201 × 1)
(280 × 2) + (201 × 1) (280 × 2) + (201 × 1)
lbs
(617 × 1) + (518 × 1) + (443 × 1) (617 × 1) + (595 × 1) + (443 × 1)
(617 × 2) + (443 × 1) (617 × 2) + (443 × 1)
Dimensions (WxHxD)
mm
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
(1,240×1,680×760) × 2 + (920×1,680×760) × 1
inch
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 ×
66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 ×
66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 ×
66-5/32 × 29-29/32) x 1
(48-13/16 × 66-5/32 × 29-
29/32) x 2 + (36-7/32 ×
66-5/32 × 29-29/32) x 1
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8)
Unit
3 Outdoor Unit
System(HP)
54 56 58 60
Model
Combination Unit
ARUN540LTS4 ARUN560LTS4 ARUN580LTS4 ARUN600LTS4
Independent Unit
ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN140LTS4 ARUN160LTS4 ARUN180LTS4 ARUN200LTS4
Refrigerant Precharged Amount
kg
(10 × 2) + 8.5 (10 × 2) + 8.5 (10 × 2) + 8.5 10 x 3
lbs
(22 × 2) + 18.7 (22 × 2) + 18.7 (22 × 2) + 18.7 22 x 3
Number of maxmum connectable indoor units
64 64 64 64
Net Weight
kg
(280 × 2) + (235 × 1) (280 × 2) + (235 × 1) (280 × 2) + (270 × 1)
280 × 3
lbs
(617 × 2) + (518 × 1) (617 × 2) + (518 × 1) (617 × 2) + (595 × 1)
617 × 3
Dimensions (WxHxD)
mm
(1,240x1,680x760) x 3 (1,240×1,680×760) × 3 (1,240×1,680×760) × 3 (1,240×1,680×760) × 3
inch
(48-13/16 × 66-5/32
× 29-29/32) x 3
(48-13/16 × 66-5/32 ×
29-29/32) x 3
(48-13/16 × 66-5/32 ×
29-29/32) x 3
(48-13/16 × 66-5/32 ×
29-29/32) x 3
Piping Conections
mm(inch)
Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4) Ø 19.05(3/4)
mm(inch)
Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8) Ø 41.3(1-5/8)
Unit
4 Outdoor Unit
System(HP)
62 64 66 68
Model
Combination Unit
ARUN620LTS4 ARUN640LTS4 ARUN660LTS4 ARUN680LTS4
Independent Unit
ARUN180LTS4 ARUN180LTS4 ARUN180LTS4 ARUN200LTS4 ARUN160LTS4 ARUN180LTS4 ARUN180LTS4 ARUN200LTS4 ARUN140LTS4 ARUN140LTS4 ARUN160LTS4 ARUN140LTS4 ARUN140LTS4 ARUN140LTS4 ARUN140LTS4 ARUN140LTS4
Refrigerant Precharged Amount
kg
8.5 x 4 8.5 x 4 8.5 x 4
(10 × 2) + (8.5 × 2)
lbs
18.7 x 4 18.7 x 4 18.7 x 4
(22 × 2) + (18.7 × 2)
Number of maxmum connectable indoor units
64 64 64 64
Net Weight
kg
(270 × 1) + (235 × 3) (270 × 2) + (235 × 2) (270 × 2) + (235 × 2) (280 × 2) + (235 × 2)
lbs
(595 × 1) + (518 × 1) (595 × 2) + (518 × 2) (595 × 2) + (518 × 2) (617 × 2) + (518 × 2)
Dimensions (WxHxD)
mm
(1,240x1,680x760) x 4 (1,240×1,680×760) × 4 (1,240×1,680×760) × 4 (1,240×1,680×760) × 4
inch
(48-13/16 × 66-5/32
× 29-29/32) x 4
(48-13/16 × 66-5/32 ×
29-29/32) x 4
(48-13/16 × 66-5/32 ×
29-29/32) x 4
(48-13/16 × 66-5/32 ×
29-29/32) x 4
Piping Conections
mm(inch)
Ø 22.2(7/8) Ø 22.2(7/8) Ø 22.2(7/8) Ø 22.2(7/8)
mm(inch)
Ø 44.5(1-3/4) Ø 44.5(1-3/4) Ø 53.98(2-1/8) Ø 53.98(2-1/8)
Unit
4 Outdoor Unit
System(HP)
70 72 74 76
Model
Combination Unit
ARUN700LTS4 ARUN720LTS4 ARUN740LTS4 ARUN760LTS4
Independent Unit
ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN160LTS4 ARUN180LTS4 ARUN180LTS4 ARUN180LTS4 ARUN140LTS4 ARUN140LTS4 ARUN160LTS4 ARUN180LTS4
Refrigerant Precharged Amount
kg
(10 × 2) + (8.5 × 2) (10 × 2) + (8.5 × 2) (10 × 2) + (8.5 × 2) (10 × 2) + (8.5 × 2)
lbs
(22 × 2) + (18.7 × 2) (22 × 2) + (18.7 × 2) (22 × 2) + (18.7 × 2) (22 × 2) + (18.7 × 2)
Number of maxmum connectable indoor units
64 64 64 64
Net Weight
kg
(280 × 2) + (235 × 2)
(280 × 2) + (270 × 1) + (235 × 1) (280 × 2) + (270 × 1) + (235 × 1)
(280 × 2) + (270 × 2)
lbs
(617 × 2) + (518 × 2)
(617 × 2) + (595 × 1) + (518 × 1) (617 × 2) + (595 × 1) + (518 × 1)
(617 × 2) + (595 × 2)
Dimensions (WxHxD)
mm
(1,240×1,680×760) × 4 (1,240×1,680×760) × 4 (1,240×1,680×760) × 4 (1,240×1,680×760) × 4
inch
(48-13/16 × 66-5/32
× 29-29/32) x 4
(48-13/16 × 66-5/32
× 29-29/32) x 4
(48-13/16 × 66-5/32
× 29-29/32) x 4
(48-13/16 × 66-5/32
× 29-29/32) x 4
Piping Conections
mm(inch)
Ø 22.2(7/8) Ø 22.2(7/8) Ø 22.2(7/8) Ø 22.2(7/8)
mm(inch)
Ø 53.98(2-1/8) Ø 53.98(2-1/8) Ø 53.98(2-1/8) Ø 53.98(2-1/8)
Unit
4 Outdoor Unit
System(HP)
78 80
Model
Combination Unit
ARUN780LTS4 ARUN800LTS4
Independent Unit
ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN200LTS4 ARUN180LTS4 ARUN200LTS4
Refrigerant Precharged Amount
kg
(10 × 3) + (8.5 × 1) 10 x 4
lbs
(22 × 3) + (18.7 × 1) 22 x 4
Number of maxmum connectable indoor units
64 64
Net Weight
kg
(280 × 3) + (270 × 1) 280 × 4
lbs
(617 × 3) + (595 × 1) 617 × 4
Dimensions (WxHxD)
mm
(1,240×1,680×760) × 4 (1,240×1,680×760) × 4
inch
(48-13/16 × 66-5/32 × 29-29/32) x 4 (48-13/16 × 66-5/32 × 29-29/32) x 4
Piping Conections
mm(inch)
Ø 22.2(7/8) Ø 22.2(7/8)
mm(inch)
Ø 53.98(2-1/8) Ø 53.98(2-1/8)
7
ENGLISH
INSTALLATION SPACE
Individual Installation
During the installation of the unit, consider service, inlet, and outlet acquire the minimum space as shown in the figures below.
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction hole, the system may mal­function. If it is installed at snowy area, attach the hood to the system.
• Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always remove snow for operation.
- The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the product. (If width of the frame is wider than that of the product, snow may accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
CAUTION
Be very careful while carrying the product.
Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
• Do not touch heat exchanger fins with your bare hands. Other­wise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate chil­dren to death.
• When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make Outdoor Unit unstable, resulting in a fall.
• Use 2 belts of at least 8 m long.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
Hoist the unit making sure it is being lifted at its center of gravity.
• When carrying the suspended, unit pass the ropes under the unit and use the two suspension points each at the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
!
LIFTING METHOD
Category
Installation Space
Case 1
(10mmSide Space49mm)
Case 2
(Side Space49mm)
4 sides
are
walls
A10 B300 C10 D500
A50 B100 C50 D500
A10 B300 C10 D500 E20
A50 B100 C50 D500 E100
A10 B300 C10 D500 E20 F600
A50 B100 C50 D500 E100 F500
A10 B300 C10 D300 E20 F500
A50 B100 C50 D100 E100 F500
Rear
to
Rear
A10 B500 C10 D500 E20 F900
A50 B500 C50 D500 E100 F600
A10 B500 C10 D500 E20 F1200
A50 B500 C50 D500 E100 F900
A10 B500 C10 D500 E20 F1800
A50 B500 C50 D500 E100 F1200
Only 2 sides
are
walls
A10 B300
A200 B300 E400
Limita-
tions on
the
height
of the
wall
(Refer
to 4 side
walls)
A
C
B
D
A E
B
D
A
C
B
D
E
C
AE
B
D
A
C
B
D
E
C
A E
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A E
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A
B
F
C
D
AE
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A E
B
F
C
D
A
B
F
C
D
AE
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
AE
B
F
C
D
A E
B
F
D
E
C
A
B
F
C
D
AE
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A
B
AE
B
F
C
D
AE
B
F
D
E
C
A
B
F
C
D
AE
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
AE
B
F
D
E
C
A
B
F
C
D
AE
B
F
C
D
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
AE
B
F
D
E
C
A
B
F
C
D
AE
B
F
C
D
h2
h1
1500
A
B
500
AE
B
D
A
C
B
D
E
C
AE
B
F
C
D
A
E
B
A
B
E
AE
B
F
C
D
AE
B
F
D
E
C
A
B
F
C
D
AE
B
F
C
D
240 or more
50 or more
45° or
more
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet side must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than the limit, there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1500
- h2 = B(Actual height) - 500
Locking points for
transportation ropes
Forklift Carrying Hole
Forklift Carrying Guide
8
ENGLISH
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm under the Unit’s legs before being fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
At least 100mm
At least 100m
m
At least 100mm
At least 100mm
At least 100mm
At least 100mm
Center of the Unit
For outdoor units should not be supported only by the corner supports.
Center of the Unit
730
760
6565
Unit : mm
At least 65At least 65
Chassis Outdoor Unit Capacity A(mm) B(mm)
UX2 8~12 HP 920 792 UX3 14~20 HP 1240 1102
INSTALLATION
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation sta­tus. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200mm).
At least 200mm
Unit : mm
200
75
75
200
100
The corner part must be fixed firmly. Otherwise, the support for the
installation may be bent.
Get and use M10 Anchor bolt.Put Cushion Pad between the outdoor unit and ground support for
the vibration protection in wide area.
Space for pipes and wiring (Pipes and wirings for bottom side)H-beam supportConcrete support
CAUTION
• Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit Base Pan before fixing the bolt. It may cause the unstable state of the outdoor settlement, and may cause freezing of the heat exchanger resulting in abnormal operations.
• Be sure to remove the Pallet(Wood Support) of the bottom side of the outdoor unit before welding. Not removing Pal­let(Wood Support) causes hazard of fire during welding.
WARNING
• Install where it can sufficiently support the weight of the out­door unit. If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake. If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment of the water flowing out of the outdoor unit in operation), and the passages of the pipe and wiring, when making the ground support.
• Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet. The tube or pipe may freeze and the water may not be drained.
Pallet(Wood Support)
- Remove before Installation
!
!
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable
- Use the accessory piping kit or the pipes purchased locally.
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5m longer than the pipe length.
Pipe
Reamer
Point down
Copper
tube
90
Slanted Uneven Rough
Preparation of Piping
9
Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you re­move burrs in order to avoid to let burrs drop in the tubing.
Flaring work
- Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the flared section and do flar­ing work again.
ENGLISH
Indoor unit [kW(Btu/h]
Pipe " A "
Gas Liquid Gas Liquid
<5.6(19,100) 1/2" 1/4" 0.5~0.8 0~0.5 <16.0(54,600) 5/8" 3/8" 0.8~1.0 0.5~0.8 <22.4(76,400) 3/4" 3/8" 1.0~1.3 0.5~0.8
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Flare shape and flare nut tightening torque
Opening shutoff valve
Precautions when connecting pipes
- See the following table for flare part machining dimensions.
- When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three or four times at first. (Use ester oil or ether oil.)
-
See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
- After all the piping has been connected, use nitrogen to perform a gas leak check.
1 Remove the cap and turn the valve counter clockwise with the
hexagon wrench.
2 Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3 Make sure to tighten the cap securely.
Pipe size
Tightening
torque(N·m)
A(mm) Flare shape
Ø9.52 38±4 12.8-13.2
Ø12.7 55±6 16.2-16.6
Ø15.88 75±7 19.3-19.7
CAUTION
• Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks are present
.
• When loosening a flare nut, always use two wrenches in combination, When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare(inner and outer faces) with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as the initial tightening.
Union
!
Insulation of shutoff valve
1 Use the heat insulation material for the refrigerant piping which has
an excellent heat-resistance (over 120°C).
2 Precautions in high humidity circumstance:
This air conditioner has been tested according to the "ISO Condi­tions with Mist" and confirmed that there is not any default. How­ever, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according to the fol­lowing procedure:
- Heat insulation material to be prepared... EPDM (Ethylene Propy­lene Diene Methylene)-over 120°C the heat-resistance tempera­ture.
- Add the insulation over 10mm thickness at high humidity environ­ment.
Closing shutoff valve
1 Remove the cap and turn the valve clockwise with the hexagon
wrench.
2 Securely tighten the valve until the shaft contacts the main body seal.
3 Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
Shutoff
valve
size
Tightening torque N·m(Turn clockwise to close)
Shaft
(valve body)
Cap
(Valve lid)
Service
port
Flare
nut
Gas line piping
attached to unit
Closed Opened
Hexagonal
wrench
Ø6.35
6.0±0.6
5.0±0.0
4mm
17.6±2.0
12.7±2
16±2
-
Ø9.52 38±4
Ø12.7 10.0±1.0 20.0±2.0 55±6
Ø15.88 12.0±1.2
5mm
25.0±2.5
75±7
Ø19.05 14.0±1.4 110±10
Ø22.2
30.0±3.0 8mm -
Ø25.4 25±3
±2
90°
4
±
A
R=0.4~0.8
2
Indoor unit
Fastening band (accessory)
Refrigerant piping
Thermal insulator (accessory)
10
ENGLISH
Plumbing materials and storage methods
Pipe must be able to obtain the specified thickness and should be used with low impurities. Also when handling storage, pipe must be careful to prevent a frac­ture, deformity and wound. Should not be mixed with contaminations such as dust, moisture.
Refrigerant piping on three principles
Drying Cleanliness Airtight
Should be no moisture
inside
No dust inside.
There is no refrigerant
leakage
Items
Moisture
Dust
Leakage
Cause failure
- Significant hydroly­sis of refrigerant oil
- Degradation of re­frigerant oil
- Poor insula’tion of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Degradation of re­frigerant oil
- Poor insulation of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Gas shortages
- Degradation of re­frigerant oil
- Poor insulation of the compressor
- Do not cold and warm
Coun-
termea-
sure
-
No moisture in the pipe
- Until the connec­tion is completed, the plumbing pipe entrance should be strictly controlled.
- Stop plumbing at rainy day.
- Pipe entrance should be taken side or bottom.
-
When removal burr after cutting pipe, pipe entrance should be taken down.
- Pipe entrance should be fitted cap when pass through the walls.
- No dust in the pipe.
- Until the connec­tion is completed, the plumbing pipe entrance should be strictly controlled.
- Pipe entrance should be taken side or bottom.
- When removal burr after cutting pipe, pipe entrance should be taken down.
- Pipe entrance should be fitted cap when pass through the walls.
- Airtightness test should be.
- Brazing operations to comply with standards.
- Flare to comply with standards.
- Flange connections to comply with standards.
Nitrogen substitution method
Welding, as when heating without nitrogen substitution a large amount of the oxide film is formed on the internal piping.
The oxide film is a caused by clogging EEV, Capillary, oil hole of accu­mulator and suction hole of oil pump in compressor.
It prevents normal operation of the compressor. In order to avoid this problem, Welding should be done after replacing
air by nitrogen gas. When welding plumbing pipe, the work is required.
1 Always use the nitrogen.(not use oxygen, carbon dioxide, and
a Chevron gas): Please use the following nitrogen pressure
0.02MPa Oxygen – Promotes oxidative degradation of refrig­erant oil. Because it is flammable, it is strictly prohibited to use Carbon dioxide – Degrade the drying characteristics of gas Chevron Gas – Toxic gas occurs when exposed to direct
flame. 2 Always use a pressure reducing valve. 3 Please do not use commercially available antioxidant.
The residual material seems to be the oxide scale is ob-
served. In fact, due to the organic acids generated by oxida-
tion of the alcohol contained in the anti-oxidants, ants nest
corrosion occurs. (causes of organic acid
alcohol + copper
+ water + temperature)
CAUTION
!
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the branching pipes, and the refrigerant pipe coming out of the outdoor unit is divided at the end to connect to each indoor unit. Flare connec­tion for the indoor unit, and welding connection for the outdoor pipe and the branching parts.
- Use hexagonal wrench to open/close the valve.
CAUTION
Please block the pipe knock outs of the front and side panels after installing the pipes. (Animals or foreign objects may be brought in to damage wires.)
!
WARNING
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body
if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas leak-
age after the work.
!
REFRIGERANT PIPING INSTALLATION
Welding Point
Regulator
Nitrogen gas Pressure 0.02MPa less
Service Port
Liquid pipe
Gas pipe
Refrigerant
Charging Port
Oxide scale
Note) should not block the outlet side. When the internal pressure in pipe is abo ve the atmospheric pressure, pinhole is o ccurred and it is a leakage cause.
Taping
(Should not
contain air)
Auxiliary valve
Nitrogen
Loading...