LG ARUN100LT2.EWGBLEU, PQRCUSA0 Installation Manual

ENGLISH
LG
Wide Wired Remote Controller
LG
IMPORTANT
• Please read this owner's & installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this owner's & installation manual for future reference after reading it thoroughly.
Owner's & Installation Manual
Models: PQRCUSA0
ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
2 Wide Wired Remote Controller
Wide Wired Remote Controller Owner’s & Installation Manual
TABLE OF CONTENTS
Safety Precaution .............................................................................................3~4
Part Description....................................................................................................5
Installation instruction .........................................................................................6
Group control ........................................................................................................8
Installer Setting-How to enter installer setting mode.............................................9
Installer Setting-Test Run mode .........................................................................11
Installer Setting-Setting Address of Central Control............................................12
Installer Setting-E.S.P.........................................................................................13
Installer Setting-Thermistor.................................................................................15
Installer Setting-Ceiling Height Selection............................................................16
Installer Setting-Static Pressure Setting..............................................................17
Installer Setting-Group Setting............................................................................18
Installer Setting-Mode Override Setting..............................................................19
Installer Setting-Dry Contact Mode Setting.........................................................20
Installer Setting-Airflow Rate Setting...................................................................21
Installer Setting-Celsius/Fahrenheit Switching....................................................22
Installer Setting-Option Function Setting.............................................................23
Cooling mode(Standard operation).....................................................................23
Owner's instruction ............................................................................................24
Cooling Mode-Standard Operation .....................................................................24
Cooling Mode-Powr Cooling ...............................................................................25
Dehumidification Mode........................................................................................26
Auto Changeover Mode......................................................................................26
Auto Operation Mode..........................................................................................27
Fan Mode............................................................................................................28
Temperature Setting/Room Temperature Check................................................29
Airflow Setting.....................................................................................................30
Sub function: Plasma Purification .......................................................................31
Sub function: Humidifier......................................................................................31
Sub function: Electric Heater...............................................................................32
Sub function : Fan Auto.......................................................................................33
Function setting: Filter Sign Clear.......................................................................33
Function setting: Child Lock................................................................................34
Function setting: Elevation Grill...........................................................................35
Function setting: Vane Angle Control..................................................................36
Function setting: ACO Converting Temp ............................................................37
Changing Current Time.......................................................................................38
Programming: Setting Simple Reservation.........................................................40
Programming: Setting Sleep Reservation...........................................................41
Programming: Setting ON Reservation...............................................................42
Programming: Setting OFF Reservation.............................................................43
Programming: Weekly Reservation.....................................................................44
Programming: Holiday Reservation ....................................................................45
Ventilation Kit Control..........................................................................................46
Safety Precaution
Owner’s & Installation Manual 3
ENGLISH
Be sure to request to the service center or installation specialty store when installing products.
• It will cause fire or electric shock or explosion or injury.
Request to the service center or installation specialty store when reinstalling the installed product.
• It will cause fire or electric shock or explosion or injury.
Do not disassemble, fix, and modify products randomly.
• It will cause fire or electric shock.
Do not place flammable stuffs close to the product.
• It will cause fire.
Do not allow water to run into the product.
• It will cause electric shock or breakdown.
Do not give the shock to the product.
• It will cause breakdown when giving the shock to the product.
Installation
Safety Precaution
• The installation requires expert skills, and it should be installed by the service center or other shops specialized in the installation and recognized by our company.
• For all the problems arising after installation by someone who has no relevant qualifications, our company will not provide free service.
• The following safety cautions are provided to prevent unexpected dangers or losses.
: If the user does not follow the mandatory items, it may result in serious injury or death. : If the user does not follow the mandatory items, it may cause personal injury or property
damage.
: Warning and Caution are to call the user’s attention to the possible danger. Read and follow
them carefully in order to prevent a safety accident.
: Warning and Caution are indicated in this guide and the product itself to help protect the users
from danger.
WARNING
CAUTION
WARNING
In-use
T E
M
P
T E
M
P
T E
M
P
T E
M
P
T E
M
P
Safety Precaution
4 Wide Wired Remote Controller
In-use
CAUTION
Request to the service center or installation specialty store when the product becomes wet.
• It will cause fire or electric shock.
Do not give the shock using sharp and pointed objects.
• It will cause breakdown by damaging parts.
Do not clean using the powerful detergent like solvent but use soft cloths.
• It will cause fire or product deformation.
Do not press the screen using powerful pressure or select two buttons.
• It will cause product breakdown or malfunction.
Do not touch or pull the lead wire with wet hands.
• It will cause product breakdown or electric shock.
T E
M
P
T E
M
P
Wax
Thinner
T E
M
P
T E
M
P
Part Description
Owner’s & Installation Manual 5
ENGLISH
Part Description
Name and Function of Remote Controller
OPERATION INDICATION SCREEN
SET TEMPERATURE Button WIRELESS REMOTE
CONTROLLER RECEIVER
• Some products don't receive the wireless signals.
VENTILATION Button OPERATION MODE SELECTION
Button SUBFUNCTION Button FUNCTION SETTING Button EXIT Button ON/ OFF Button ROOM TEMPERATURE Button FAN SPEED Button AIR FLOW Button RESERVATION/ TIME SETTING
Button SETTING/ CANCEL Button UP, DOWN, LEFT, RIGHT Button
12V SIG GND
1
9
11 12
3
5 6
2
4 10
13 14
7 8
15
Please attach the inform label inside of the door. Please choose proper language defend on your country.
1
2 3
4 5
6 7 8
9 10 11
12 13
14 15
Connection Cable
(1EA, 10m)
Remote controller
screw
(4 EA)
Owner's /
Installation manual
Wired remote
controller
installation board
Inform label
(5EA-5Language)
Accessory
Some functions may not be operated and displayed depending on the product type.
Installation instruction
6 Wide Wired Remote Controller
12V SIG GND
Red Yellow Black
Remote Controller Cable
Guide slot
Fixate the remote controller cable to the guide slot.
Use the screws for fixate the unit firmly on the wall.
Installation board
<Front side of
installation board>
<Rear side of
installation board>
Top
Bottom
Wall
Side
1. Connect the remote controller cable to the wired remote controller installation board as shown in the right picture.
2. After fixing the cable to the guide slot, attach the wired remote controller installation board at the desired location.
Before fixing the remote controller cable to the
guide slot, remove any clogged part of the case in the direction to install before the installation.
3. After locating the wired remote controller installation board at the desired location, screw the unit firmly. (When there is a buried box, install the wired remote controller board to fit the buried box.)
Use the screws provided.
Installation instruction
12V Red wire SIG Yellow wire
GND Black wire
The remote controller cable is connected as factory default.
Installation instruction
Owner’s & Installation Manual 7
ENGLISH
Wall
Side
Wall
Side
Wall
Side
Wall
Side
Check whether the connector is connected correctly.
Connecting cable
Indoor unit side
4. After fixing the top part of the remote controller to the installation board as shown in beside picture, press the bottom part to assemble the controller to its board.
When disassembling the remote controller from the installation board, use the driver as shown in the right picture and insert it into the hole with the arrow. And when you pull the driver in the front direction, the remote controller will be separated.
5. Use the connecting cable to connect the indoor unit and the remote controller.
6. When the distance between the wired remote controller and the indoor unit is 10m and above, use the extension cable.
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in the temperature sensor.) Do not install the cable to be 50m or above. (It can cause communication error.)
When installing the extension cable, check the connecting direction of the connector of the remote controller side and the product side for correct installation.
If you install the extension cable in the opposite direction, the connector will not be connected.
Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
CAUTION
Installation instruction
8 Wide Wired Remote Controller
GND
GND
12V
Signal wire
Signal wire
GND
12V
B Y R B Y R
MASTER SLAVE
Signal wire
GND
12V
Signal wire
Group control
1. When installing more than 2 units of air conditioner to one wired remote controller, please connect as the right figure.
If it is not event communication
indoor unit, set the unit as slave.
Check for event communication
through the product manual.
Refer to regarding page on how to
set the slave.
2. When installing more than 2 wired remote controllers to one air conditioner, please connect as the right picture.
When installing more than 2 units of wired
remote controller to one air conditioner, set one wired remote controller as master and the others all as slaves, as shown in the right picture.
Refer to Installer setting section on how to
set master/slave.
You cannot control the group as shown in
the right for some products.
<When simultaneously connecting
2 sets of wired remote controller>
Some products do not use 'Group control'. It depends on the product type. For more detail, refer to the product manual.
Owner’s & Installation Manual 9
ENGLISH
Installation instruction
Installer setting mode is to set the detail function of the remote controller. If the installer setting mode is not set correctly, it can cause problems to the product, user injury or property damage. This must be set by an certificated installer, and any installation or change that is carried out by a non-certificated person should be responsible for the results. In this case, free service cannot be provided.
CAUTION
Installer Setting -How to enter installer setting mode
Function Code Value
1
Press button for 4 secsonds to enter the installer setting mode. (When you enter the setting mode initially, Function code is displayed on the bottom of the LCD screen.)
1
Repeat pressing button, the menu will change with the corresponding function code.
Test Run Address Setting E.S.P. Value → Thermistor → Ceiling Height → Static Pressure → Group Setting → Override Setting Dry Contact Release 3Min. Delay Zone State Convert Temp . → Plasma → Electric heater Humidifier Elevation Grill Ventilation Kit
2
Some contents may not be displayed depending on the product function.
Installation instruction
10 Wide Wired Remote Controller
<Installer Setting Code Table>
Some contents may not be displayed depending on the product function
Function Code ESP valueESP step
No. Function Code Value
1 Test Run 01 01:Set 2 Address Setting 02 00~FF : Address
<ESP Step> <ESP Value> 01:VeryLow 0 ~ 255 02:Low
3 E.S.P. Value 03
03:Med 04:High 05:Very High
01:Remo
4 Thermistor 04 02:Indoor
03:2TH 01:Med
02:Low
5 Ceiling Height 05
03:High 04:Very High
01:V-H 02:F-H
6 Static Pressure 06
03:V-L 04:F-L
7 Group Setting 07
00:Slave 01:Master
8 Override Setting 08
00:Slave 01:Master
9 Dry Contact 09
00:OFF 01:ON
10
Release 3 Min.
10 01:Set
Delay
11 Zone State 11
01:Variable 02:Fixed
12
Celsius
12
01:Celsius
(Optimized only for U.S.A)
Fahrenheit Switching 02: Fahrenheit 13 Plasma 20 14 Electric heater 21 15 Humidifier 22
00: Not Installed
16 Elevation Grill 23
01: Installed
17 Ventilation Kit 24
Installation instruction
Owner’s & Installation Manual 11
ENGLISH
Function Code Set
1
2
Keep pressing button setting for 4 secs to enter installer setting mode until code displayed in timer segment.
1
Press button to start.
2
Installer Setting -Test Run Mode
After installing the product, you must run a Test Run mode. For details related to this operation, refer to the product manual.
18˚C cooling, High Fan Speed, Airflow direction mode will be operated during 18 minutes with
ignoring room temperature.
After running 18 minutes under test run mode, system will automatically turn OFF.In case of duct type, the Airflow UP/DOWN function is not displayed.During test run mode, receiving signal from wireless remote controller will release this operation.
If you press any kind of button, Test Run mode will be released.
Function Code Group No
Indoor No.
Press the button for 4 seconds to enter the installer setting mode until timer segment display "01:01".
1
Set Group No. by pressing button.
3
Move to Indoor No. setting option by pressing button.
4
Set Indoor No. by pressing button.
5
Press button to save or release.
6
Press button to exit or system will automatically exit after 25 seconds without any input.
7
Repeat pressing button to select Function code 02.
Ex) Setting Address as 'F5'
2
Installation instruction
12 Wide Wired Remote Controller
Installer Setting - Setting Address of Central Control
Owner’s & Installation Manual 13
ENGLISH
Installation instruction
Function Code ESP valueESP step
Press button for 4 seconds to enter the installer setting mode until timer segment display “01:01”.
1
Repeat pressing button to select Function code 03.
2
Set ESP step by pressing button. (01: very low, 02: low, 03: medium, 04: high. 05: power)
3
Move to ESP setting by pressing button.
4
Press button to select ESP value(0~255).
5
Installer Setting -E.S.P.
If you set ESP incorrectly, the air conditioner may malfunction. This setting must be carried out by a certificated-technician. This function is used for only Duct product.
CAUTION
What is an E.S.P function?
This is the function that decides the strength of the wind for each wind level and because this function is to make the installation easier, please do not use this function when using the remote controller.
Installation instruction
14 Wide Wired Remote Controller
Press button to save or release.
6
Press button to exit or the system will automatically exit after 25 seconds without any input.
7
Weak and Power setting is not available for some products. Because the ESP value is already appropriately set when manufactured from the factory, it is
recommended that you do not change the ESP value.
Owner’s & Installation Manual 15
ENGLISH
Installation instruction
Function Code Thermistor setting
Press button for 4 seconds to enter the installer setting mode until timer segment display “01:01”.
1
Set Thermistor mode by pressing button. (01: Remote Controller, 02: Indoor, 03: 2TH)
3
Press button to save or release.
4
Press button to exit or system will automatically exit after 25 seconds without any input.
5
Repeat pressing button to select Function code 04.
Ex) Setting Thermistor as '2TH'.
2
Installer Setting -Thermistor
Therefore system will use value that sensed from indoor unit or remote controller
Temperature sensor location Function
01 Indoor unit Operation in indoor unit temperature sensor 02 Remote controller Operation in remote controller Temperature sensor
03 2-Thermistor(2TH)
Operation in lower temperature after comparing the temperature between the indoor unit and remote controller
<Thermistor Table>