LG ARUN050LMC0, ARUN050GME0 Installation Manual

P/NO : MFL70344401
INSTALLATION MANUAL
VRF FOR INDOOR INSTALLAION
Original instruction
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
Gyeongsangnam-do, KOREA
For more information, Refer to the CD or LG Web site (www.lg.com).
AIR CONDITIONER
www.lg.com
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Copyright © 2018 LG Electronics Inc. All Rights Reserved.
ENGLISH
ITALIANO
ESPAÑOL
FRANÇAIS
DEUTSCH
ČEŠTINA
ΕΛΛΗΝΙΚΆ
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
www.lgcomfortcooling.co.uk
2
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate
or electric work is performed improperly, electric shock or fire may result.
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result
in water leakage, electric shock, or fire.
• Always ground the product.
- There is risk of fire or electric shock.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause
fire or electric shock.
• For re-installation of the installed product, always contact a dealer or an Authorized Service Center.
- There is risk of fire, electric shock,
explosion, or injury.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock,
explosion, or injury.
• Do not store or use flammable gas or combustibles near the air conditioner.
- There is risk of fire or failure of product.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Prepare for strong wind or earthquake and install the unit at the specified place.
- Improper installation may cause the unit to
topple and result in injury.
!
!
!
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
www.lgcomfortcooling.co.uk
3
ENGLISH
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to
the product.
• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or
explosion.
• When installing and moving the air conditioner to another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with
the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or
other protection device is shorted and operated forcibly, or parts other than those specified by LGE are used, fire or explosion may result.
• Ventilate before operating air conditioner when gas leaked out.
- It may cause explosion, fire, and burn.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed
securely, dust or water may enter the outside unit and fire or electric shock may result.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
- Consult the dealer regarding the
appropriate measures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
• Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazrd.
• This equipment shall be provided with a supply conductor complying with the national regulation.
Operation
• Do not damage or use an unspecified power
cord.
- There is risk of fire, electric shock, explosion, or injury.
• Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product
damage.
• Do not touch the power switch with wet hands.
- There is risk of fire, electric shock, explosion, or
injury.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious not to touch the sharp edges when installing.
- It may cause injury.
• Take care to ensure that nobody could step on or fall onto the outside unit.
- This could result in personal injury and product
damage.
• Do not open the inlet grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or
product failure.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
www.lgcomfortcooling.co.uk
4
ENGLISH
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of
product.
• Do not install the product where the noise or hot air from the outside unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the
unit, an explosion may result.
• Use power cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate
heat, and cause a fire.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Keep the unit away from children. The heat exchanger is very sharp.
- It can cause the injury, such as cutting the
finger. Also the damaged fin may result in degradation of capacity.
• When installting the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
-
The inverter equipment, private power generator, high-frequency medical equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the product where it is exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product.
Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operation
• Do not use the air conditioner in special environments.
-
Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of the air conditioner or damage its parts.
• Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
• Make the connections securely so that the outside force of the cable may not be applied to the terminals.
- Inadequate connection and fastening may
generate heat and cause a fire.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could
fall with it, causing property damage, product failure, or personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the installation manual.
- A bad connection may cause water leakage.
• Be very careful about product transportation.
- Only one person should not carry the product if
it weighs more than 20 kg.
-
Some products use PP bands for packaging. Do not use any PP bands for a means
of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so
may cut your fingers.
- When transporting the outside unit, suspending
it at the specified positions on the unit base. Also support the outside unit at four points so that it cannot slip sideways.
• Safely dispose of the packing materials.
-
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
-
Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
• Turn on the power at least 6 hours before starting operation.
- Starting operation immediately after turning on
the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
!
www.lgcomfortcooling.co.uk
5
ENGLISH
• Do not touch any of the refrigerant piping during and after operation.
- It can cause a burn or frostbite.
• Do not operate the air conditioner with the panels or guards removed.
- Rotating, hot, or high-voltage parts can cause
injuries.
• Do not directly turn off the main power switch after stopping operation.
- Wait at least 5 minutes before turning off the
main power switch. Otherwise it may result in water leakage or other problems.
Auto-addressing should be done in condition of connecting the power of all indoor and outdoour units. Auto-addressing should also be done in case of changing the indoor unit PCB.
• Use a firm stool or ladder when cleaning or maintaining the air conditioner.
- Be careful and avoid personal injury.
• Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
- There are sharp and moving parts that could
cause personal injury.
• This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
TABLE OF CONTENTS
2 TIPS FOR SAVING ENERGY 2 IMPORTANT SAFETY INSTRUCTIONS 6 INSTALLATION PROCESS 6 OUTSIDE UNIT INFORMATION 6 ALTERNATIVE REFRIGERANT R410A 7 SELECT THE BEST LOCATION :
COMPRESSOR MODULE
7 INSTALLATION SPACE : COMPRESSOR
MODULE
7 SELECT THE BEST LOCATION : HEAT
EXCHANGER MODULE
7 INSTALLATION SPACE : HEAT
EXCHANGER MODULE
8 CARRYING METHOD 8 INSTALLATION : COMPRESSOR
MODULE
8
The location of the Anchor bolts
8
Foundation for Installation
9 INSTALLATION : HEAT EXCHANGER
MODULE
10
Heat Exchanger Module Installation
10
Method when insatalling the ducting
10
Method connect the refrigerant piping to the Heat Exchanger Module.
11
Checking the Drainage
11
Indoor Unit Drain Piping
11
Preparation of Piping
12
Plumbing materials and storage methods
12 REFRIGERANT PIPING INSTALLATION
12
Precautions on Pipe connection / Valve operation
13 TO CONNECT THE REFRIGERANT
PIPING TO THE COMPRESSOR MODULE
13
Preparation Work
13
Pipe Drawing Out
14
Refrigerant piping system
14
Selection of Refrigerant Piping
16
Refrigerant charging
16
Distribution Method
17
Branch pipe Fitting
18
Leak Test and Vacuum drying
19
Vacuum Mode
19
Thermal insulation of refrigerant piping
20 ELECTRICAL WIRING
20
Caution
21
Wiring of main power supply and equipment capacity
21
Control box and connecting position of wiring
21
Communication and Power Cables
22
Field Wiring
23
Checking the setting of outside units
23
Automatic Addressing
24
Group Number setting
24
Cool & Heat selector
24
Static pressure compensation mode
25
Night Low Noise Function
25
Setting the ODU address
25
Snow removal & rapid defrost
25
Target pressure adjusting
26
Self-Diagnosis Function
28 CAUTION FOR REFRIGERANT LEAK
28
Introduction
28
Checking procedure of limiting concentration
29 INSTALLATION GUIDE AT THE SEASIDE
29
Model Designation
29
Airborne Noise Emission
www.lgcomfortcooling.co.uk
6
ENGLISH
The foundation must be level even
Avoid short circuits and ensure sufficient space is allowed for service
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
2
) there
must be no drop in pressure.
Airtight test
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness, cleanness and tightness
Refrigerant piping work
Check model name to make sure the fitting is made correctly
Installation of indoor unit
Take account of gradient of drain piping
Sleeve and insert work
Make connection clearly between outdoor, indoor, remote controller and option.
Preparation of contract drawings
Indicate clearly who will be responsible for switch setting.
Determination of division work
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Vacuum drying
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and make sure all relevant documentation is in order
Transfer to customer with explanation
Preheat the crank case with the electrical heater for more than 6 hours.
Installation of Compressor module &
Heat exchanger module
Foundation work for Compressor Module
& Heat exchanger Module installation
Multiple core cable must not be used. (suitable cable should be selected) (Including Connecting communicate wiring to between Cycle module and Condenser module)
CAUTION
• The above list indicates the order in which the individual work
operations are normally carried out but this order may be varied where local conditions warrants such change.
• The thickness of the piping should comply with the relevant
local and national regulations for the designed pressure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)
!
Compressor Module Power Supply : 380-415 V 3N~ 50 Hz
CAUTION
• Ratio of the connectable Indoor Units to the Outdoor: Within
50 ~ 130%
• Ratio of running Indoor Units to the Outdoor: Within 10 ~ 100%
• A combination operation over 100% cause to reduce each
indoor unit capacity.
!
System(HP) 5 Model ARUN050LMC0
Refrigerant Precharged Amount
kg 2
lbs 4.4
Number of maximum connectable indoor units
10
Net weight
kg 70
lbs 169
Dimensions (WxHxD)
mm 580 × 700 × 500 inch 22.3 x 27.5 x 19.6
Piping Connections
Liquid Pipes mm(inch) Ø 9.52(3/8) to IDU Gas Pipes mm(inch) Ø 15.88(5/8) to IDU
Heat Exchanger Module Power Supply : 220-240 V~ 50 Hz
System(HP) 5 Model ARUN050GME0
Refrigerant Precharged Amount
kg -
lbs -
Number of maximum connectable indoor units
-
Net weight
kg 89
lbs 198
Dimensions (WxHxD)
mm 1,562 × 460 × 688 inch 61.5 × 18.1 × 27
Piping Connections
Liquid Pipes mm(inch) Ø 12.7(1/2) to Compressor Module Gas Pipes mm(inch) Ø 19.05(3/4) to Compressor Module
CAUTION
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
!
ALTERNATIVE REFRIGERANT R410A
The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also considered during the installation. R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0.
OUTSIDE UNIT INFORMATION
INSTALLATION PROCESS
www.lgcomfortcooling.co.uk
7
ENGLISH
WARNING
Fix the outside unit firmly with anchor bolt or it may fall and hurt people. (refer to ‘Foundation for installation’)
!
INSTALLATION SPACE : HEAT EXCHANGER MODULE
• The following values are the least space for installation. If any service area is needed for service according to field circumstance, obtain enough service space.
• The unit of values is mm.
Installation Space for Heat Exchanger Module
ab
cd
e
Service Space
(Front Side)
Front side
Top View Front View
[Unit: mm]
[Unit: mm]
600 or more
70 or more
H = 100 or more
Top View
Front View
10 or more
Air discharge
Air Suction
Inspection hole (600 x 600)
Control box
SELECT THE BEST LOCATION : HEAT EXCHANGER MODULE
It must be installed indoors. Ambient design temprature of compressor module and Heat exchange module is 5~35°C (26°C WB)
The heat exchanger module has the same installation site requirements as the compressor module, and few additional ones.
Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the Heat Exchanger Module weight.
• The place shall be able to inspect the Heat Exchanger Module as the figure.
• The place where the Heat Exchanger Module shall be leveled.
• The place shall allow easy water drainage. (Suitable dimension “H” is necessary to get a slope to drain as figure.)
• The place shall easily connect with the Compressor Module.
• The place where the Heat Exchanger Module is not affected by an electrical noise.
• There should not be any heat source or steam near the unit.
INSTALLATION SPACE : COMPRESSOR MODULE
• The following values are the least space for installation. If any service area is needed for service according to field circumstance, obtain enough service space.
• The unit of values is mm.
Installation Space for Compressor Module
SELECT THE BEST LOCATION : COMPRESSOR MODULE
It must be installed indoors. Ambient design temprature of compressor module and Heat exchange module is 5~35°C (26°C WB)
Select space for installing compressor module, which will meet the following conditions:
• No direct thermal radiation from other heat sources.
• Do not installation where sensitive place the noise
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the compressor module in order to prevent any person or animal from accessing the compressor module.
Select installation location considering following conditions to avoid bad condition when additionally performing defrost operation.
• Install the outside unit at a place well ventilated and having a lot of sunshine in case of installing the product at a place with a high humidity in winter (near beach, coast, lake, etc). (Ex) Rooftop where sunshine always shines.
• Performance of heating will be reduced and preheat time of the indoor unit may be lengthened in case of installing the outside unit in winter at following location:
- Shade position with a narrow space
- Location with much moisture in neighboring floor.
- Location with much humidity around.
- Location where ventilation is good. It is recommended to install the outside unit at a place with a lot of sunshine as possible as.
- Location where water gathers since the floor is not even.
WARNING
Fix the outside unit firmly with anchor bolt or it may fall and hurt people. (refer to ‘Foundation for installation’)
!
Category Mark Description Installation Space [ mm ]
Compressor
Module
a Right 10 or more b Left 10 or more c Rear 10 or more d Front 500 or more e Top 200 or more
www.lgcomfortcooling.co.uk
8
CARRYING METHOD
ENGLISH
CAUTION
Be very careful while carrying the product.
Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent damage.
!
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be more than 200mm).
At least 200mm
Unit : mm
200
75
75
200
100
The corner part must be fixed firmly. Otherwise, the support for the
installation may be bent.
Get and use M10 Anchor bolt.Put Cushion Pad between the outside unit and ground support for
the vibration protection in wide area.
Space for pipes and wiring (Pipes and wirings for bottom side)H-beam supportConcrete support
WARNING
• Install where it can sufficiently support the weight of the compressor module. If the support strength is not enough, the compressor module may drop and hurt people.
• Install where the compressor module may not fall in strong wind or earthquake. If there is a fault in the supporting conditions, the outside unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground and the passages of the pipe and wiring, when making the ground support.
!
Foundation for Installation
Front panel
a
cd
b
ARUN050LMC0 a 580 b 530 c 500 d 462 e25
[Unit : mm]
At least 100mm
At least 100mm
At least 100mm
For outdoor units should not be supported only by the corner supports.
Center of the Unit
At least 100mm
At least 100mm
At least 100mm
Center of the Unit
The location of the Anchor bolts
INSTALLATION : COMPRESSOR MODULE
• You can install the compressor module directly on the floor or on a structure. If you want to install on floor, you do not use ancor bolt.
• Install at places where it can endure the weight and vibration/noise of the compressor module.
• The compressor module supports at the bottom shall have width of at least 100mm under the Unit’s legs before being fixed.
• The compressor module supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
CARRYING METHOD
• Please transport the product referring to the figure.
• Use only accessories and parts which are of the designated specification when installing.
Compressor Module.
Heat Exchanger Module.
www.lgcomfortcooling.co.uk
9
ENGLISH
CAUTION
• In case of on the floor you should not have to fix the compressor module with anchor bolts.
• In case of on the structure you can fix the Compressor module securely use anchor bolts, nuts and washers to the structure. The foundation must be larger than the image
• If noise / vibration occurs, install rubber pad under the product
• Be sure to remove the Pallet(Wood Support) of the bottom side of the compressor module before welding. Not removing Pallet(Wood Support) causes hazard of fire during welding.
• When vibration is transmitted to the building, use a vibration proof rubber (field supply).
Pallet(Wood Support)
- Remove before Installation
!
INSTALLATION : HEAT EXCHANGER MODULE
- Install the unit above the ceiling correctly.
CASE 1
Position of suspension Bolt
- Apply a joint-canvas between the module and duct to absorb unnecessary vibration.
CASE 2
- Install the module leaning to a drainage hole side as a figure for easy water drainage.
Position of console Bolt
- A place where the module will be leveled and that can support the weight of the unit.
- A place where the module can withstand its vibration.
- A place where service can be easily performed.
Dimension
Chassis
ABCDEFGH I JKL
B8
1680 1565 1160 330 460 580 700 1400 1635 390 445 15
(Unit:mm)
B8 Chassis
M10 Nut
M10 washer
X 4
X 4
M10 Nut
M10 washer
X 4 X 8
NOTE
!
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a
cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air
conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
www.lgcomfortcooling.co.uk
10
ENGLISH
Insulation, others : Insulate the joint and tubes completely.
Thermal insulation : All thermal insulation must comply with local requirement.
Heat Exchanger Module
Method connect the refrigerant piping to the Heat Exchanger Module.
1. Cut the liquid pipe and gas pipe.
2. Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.
3. Wrap the pipe with a wet cloth.
4. Braze the liquid pipe and gas pipe.
5. Remove the wet cloth.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Make sure that there is no clearance here.
Overlap with thermal insulator for piping.
Thermal insulator for refrigerant pipe (Local supply)
Thermal insulator for piping(Local supply)
Hose crip for thermal insulator(Local supply)
Union for liquid pipe
Refrigerant pipe and thermal insulator(Local supply)
Union for gas pipe
Thermal insulator for refrigerant pipe (Local supply)
Hose crip for thermal insulator (Local supply)
CAUTION
• Tighten the nut and bolt to prevent unit falling
!
Heat Exchanger Module Installation
- Select and mark the position for fixing bolts.
- Drill the hole for set anchor on the face of ceiling.
- Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the set anchor firmly.
- Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
Method when insatalling the ducting
- Ducting is to be field supplied
- For prevent water from flowing into the Heat exchanger module, Make sure the ductiong has slopes down
- You Protect the ducting against reverse airflow from wind.
- If the suction ducting or discharge ducting is connected with the inside air, it might be impossible to reach the desired room temperature.
- Connect suction ducting and discharge ducting with the outside air.
1 Set anchor
Old building New building
2 Plate washer 3 Spring washer
4 Nut
5 Suspension bolts



www.lgcomfortcooling.co.uk