HR Unit PCB.........................................................................................................................77
Test Run ...............................................................................................................................92
New Function ....................................................................................................................118
Caution For Refrigerant Leak...........................................................................................126
Installation guide at the seaside ......................................................................................128
Installation Guide for Harmonics.....................................................................................129
2Outdoor Unit
Page 3
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
n Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
n Installation
Have all electric work done by a licensed
electrician according to "Electric Facility
Engineering Standard" and "Interior Wire
Regulations" and the instructions given in
this manual and always use a special circuit.
• If the power source capacity is inadequate or
electric work is performed improperly, electric
shock or fire may result.
Ask the dealer or an authorized technician to
install the air conditioner.
• Improper installation by the user may result in
water leakage, electric shock, or fire.
Always ground the product.
• There is risk of fire or electric shock.
Always intstall a dedicated circuit and breaker.
• Improper wiring or installation may cause fire or
electric shock.
For re-installation of the installed product,
always contact a dealer or an Authorized
Service Center.
• There is risk of fire, electric shock, explosion, or
injury.
Do not install, remove, or re-install the unit
by yourself (customer).
• There is risk of fire, electric shock, explosion, or
injury.
Do not store or use flammable gas or
combustibles near the air conditioner.
• There is risk of fire or failure of product.
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
Prepare for strong wind or earthquake and
install the unit at the specified place.
• Improper installation may cause the unit to topple and result in injury.
Do not install the product on a defective
installation stand.
• It may cause injury, accident, or damage to the
product.
Installation Manual 3
Safety Precautions
ENGLISH
Page 4
Safety Precautions
Ventilate before operating air conditioner
when gas leaked out.
• It may cause explosion, fire, and burn.
Securely install the cover of control box and
the panel.
•
If the cover and panel are not installed securely, dust or water may
enter the outdoor unit and fire or electric shock may result.
If the air conditioner is installed in a small room, measures must be taken to prevent the
refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
•
Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded. Should the
refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxygen in the room could result.
n Operation
Do not damage or use an unspecified power cord.
•
There is risk of fire, electric shock, explosion, or injury.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock.
Be cautious that water could not enter the
product.
•
There is risk of fire, electric shock, or product damage.
Do not touch the power switch with wet
hands.
•
There is risk of fire, electric shock, explosion, or injury.
When installing and moving the air conditioner to
another site, do not charge it with a different refrigerant from the refrigerant specified on the unit.
• If a different refrigerant or air is mixed with the
original refrigerant, the refrigerant cycle may
malfunction and the unit may be damaged.
Do not reconstruct to change the settings of
the protection devices.
•
If the pressure switch, thermal switch, or other protection
device is shorted and operated forcibly, or parts other than
those specified by LGE are used, fire or explosion may result.
When the product is soaked (flooded or
submerged), contact an Authorized Service
Center.
• There is risk of fire or electric shock.
Be cautious not to touch the sharp edges
when installing.
• It may cause injury.
Take care to ensure that nobody could step
on or fall onto the outdoor unit.
• This could result in personal injury and product
damage.
Do not open the inlet grille of the product
during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or
product failure.
n Installation
Always check for gas (refrigerant) leakage
after installation or repair of product.
• Low refrigerant levels may cause failure of
product.
Do not install the product where the noise or
hot air from the outdoor unit could damage
the neighborhoods.
• It may cause a problem for your neighbors.
4Outdoor Unit
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or
Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.
Page 5
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the unit where combustible gas
may leak.
• If the gas leaks and accumulates around the
unit, an explosion may result.
Use power cables of sufficient current
carrying capacity and rating.
• Cables that are too small may leak, generate
heat, and cause a fire.
Do not use the product for special purposes,
such as preserving foods, works of art, etc. It
is a consumer air conditioner, not a precision
refrigeration system.
• There is risk of damage or loss of property.
Keep the unit away from children. The heat
exchanger is very sharp.
• It can cause the injury, such as cutting the finger.
Also the damaged fin may result in degradation
of capacity.
When installting the unit in a hospital, communication station, or similar place, provide
sufficient protection against noise.
•
The inverter equipment, private power generator,
high-frequency medical equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the
other hand, the air conditioner may affect such
equipment by creating noise that disturbs medical
treatment or image broadcasting.
Do not install the product where it is exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient operation.
n Operation
Do not use the air conditioner in special
environments.
• Oil, steam, sulfuric smoke, etc. can significantly
reduce the performance of the air conditioner or
damage its parts.
Do not block the inlet or outlet.
• It may cause failure of appliance or accident.
Make the connections securely so that the
outside force of the cable may not be applied
to the terminals.
• Inadequate connection and fastening may generate heat and cause a fire.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could
fall with it, causing property damage, product
failure, or personal injury.
Install and insulate the drain hose to ensure that water is drained away properly based on the
installation manual.
• A bad connection may cause water leakage.
Installation Manual 5
Safety Precautions
ENGLISH
Page 6
Safety Precautions
Safely dispose of the packing materials.
•
Packing materials, such as nails and other metal or
wooden parts, may cause stabs or other injuries.
•
Tear apart and throw away plastic packaging bags
so that children may not play with them. If children
play with a plastic bag which was not torn apart,
they face the risk of suffocation.
Turn on the power at least 6 hours before
starting operation.
• Starting operation immediately after turning on
the main power switch can result in severe
damage to internal parts. Keep the power switch
turned on during the operational season.
Be very careful about product transportation.
• Only one person should not carry the product if it weighs more than 20 kg.
• Some products use PP bands for packaging. Do not use any PP bands for a means of transportation.
It is dangerous.
• Do not touch the heat exchanger fins. Doing so may cut your fingers.
• When transporting the outdoor unit, suspending it at the specified positions on the unit base. Also
support the outdoor unit at four points so that it cannot slip sideways.
Do not touch any of the refrigerant piping
during and after operation.
• It can cause a burn or frostbite.
Do not operate the air conditioner with the
panels or guards removed.
• Rotating, hot, or high-voltage parts can cause
injuries.
Do not directly turn off the main power
switch after stopping operation.
• Wait at least 5 minutes before turning off the
main power switch. Otherwise it may result in
water leakage or other problems.
Auto-addressing should be done in condition of
connecting the power of all indoor and outdoour
units. Auto-addressing should also be done in
case of changing the indoor unit PCB.
Use a firm stool or ladder when cleaning or
maintaining the air conditioner.
• Be careful and avoid personal injury.
Do not insert hands or other objects through
the air inlet or outlet while the air conditioner
is plugged in.
• There are sharp and moving parts that could
cause personal injury.
6Outdoor Unit
Page 7
Installation Process
• The above list indicates the order in which the individual work operations are normally carried out but this order may be
varied where local conditions warrants such change.
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.)
Installation Manual 7
Installation Process
ENGLISH
Determination of division work
Preparation of contract drawings
Sleeve and insert work
Installation of indoor unit
Refrigerant piping work
Drain pipe work
Duct work
Heat insulation work
Electrical work
(connection circuits and drive circuits)
Airtight test
Vacuum drying
Additional charge of refrigerant
Indicate clearly who will be responsible for switch setting.
Make connection clearly between outdoor, indoor, remote controller and option.
Take account of gradient
of drain piping
Check model name to make
sure the fitting is made correctly
Special attention to dryness,
cleanness and tightness
Adjust to downward gradient
Make sure airflow is sufficient
Make sure no gaps are left where
the insulating materials are joined
Multiple core cable must not be used.
(suitable cable should be selected)
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Outdoor unit foundation work
Installation of outdoor unit
2
) there must be no drop in pressure.
The foundation must be level even
Avoid short circuits and ensure
sufficient space is allowed for service
Fit facing panels
Automatic addressing of indoor unit
Test run adjustment
Transfer to customer with explanation
Make sure there are no gaps left between the facing materials used on the ceiling
Refer to automatic addressing flowchart
Preheat the crank case with the electrical heater for more than 6 hours.
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Explain the use of the system as clearly as possible to your customer and make sure all relevant
documentation is in order
Page 8
Outdoor units Information
Outdoor units Information
n Heat Recovery
n Combination Ration(50~200%)
Notes: * We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and discuss the
requirement like below.
1) If the operation of indoor unit is more than 130%, the airflow is operated as low in the all indoor
units.
2) The number of () means the number of Max. connectable indoor units, when the connected
capacity of indoor units is in the table above.
Outdoor Number Connection Capacity
Single outdoor units 200%
Double outdoor units 160%
Triple outdoor units 130%
Power Supply: Outdoor Unit (3Ø, 380 - 415V, 50Hz/3Ø, 380V, 60Hz)
Unit
System(HP)
Model
Product Charge kg
Max. Connectable No. of Indoor Units
Net Weight kg
lbs
Dimensions (WxHxD) mm
inch
Connecting Pipes
Liquid[mm(inch)]
Low Pressure Gas [mm(inch)]
High Pressure Gas [mm(inch)]
418 x 1 529 x 1 529 x 1
(920 x 1,680 x 760) x 1 (920 x 1,680 x 760) x 1 (920 x 1,680 x 760) x 1
(36.2 x 66.1 x 29.9) x 1 (36.2 x 66.1 x 29.9) x 1 (36.2 x 66.1 x 29.9) x 1
9.52(3/8) 9.52(3/8) 12.7(1/2)
19.05(3/4) 22.2(7/8) 28.58(1 1/8)
15.88(5/8) 19.05(3/4) 19.05(3/4)
Unit
System(HP)
Model
Product Charge kg
Max. Connectable No. of Indoor Units
Net Weight kg
lbs
Dimensions (WxHxD) mm
inch
Connecting Pipes
Liquid[mm(inch)]
Low Pressure Gas [mm(inch)]
High Pressure Gas [mm(inch)]
595 x 1 595 x 1 705 x 1 727 x 1
(1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1
(48.8 x 66.1 x 29.9) x 1 (48.8 x 66.1 x 29.9) x 1 (48.8 x 66.1 x 29.9) x 1 (36.2 x 66.1 x 29.9) x 1
14.0 14.0 14.5 16.0
49(60) 52(64) 55(64) 58(64)
270 × 2 270 × 2 270 × 1 + 320 × 1 270 × 1 + 330 × 1
595 × 2 595 × 2 595 × 1 + 705 × 1 595 × 1 + 727 × 1
(1,240 x 1,680 x 760) x 2 (1,240 x 1,680 x 760) x 2 (1,240 x 1,680 x 760) x 2 (1,240 x 1,680 x 760) x 2
(48.8 x 66.1 x 29.9) x 2 (48.8 x 66.1 x 29.9) x 2 (48.8 x 66.1 x 29.9) x 2 (48.8 x 66.1 x 29.9) x 2
270 × 1 + 330 × 2 270 × 1 + 330 × 2 320 × 1 + 330 × 2 330× 3
595 × 1 + 727 × 2 595 × 1 + 727 × 2 7705 × 1 + 727 × 2 727× 3
(1,240 x 1,680 x 760) x 3 (1,240 x 1,680 x 760) x 3 (1,240 x 1,680 x 760) x 3 (1,240 x 1,680 x 760) x 3
(48.8 x 66.1 x 29.9) x 3 (48.8 x 66.1 x 29.9) x 3 (48.8 x 66.1 x 29.9) x 3 (48.8 x 66.1 x 29.9) x 3
19.05(3/4) 19.05(3/4) 19.05(3/4) 19.05(3/4)
41.3(1 5/8) 41.3(1 5/8) 41.3(1 5/8) 41.3(1 5/8)
34.9(1 3/8) 34.9(1 3/8) 34.9(1 3/8) 34.9(1 3/8)
Unit
System(HP)
Model
Product Charge kg
Max. Connectable No. of Indoor Units
Net Weight kg
lbs
Dimensions (WxHxD) mm
inch
Connecting Pipes
Liquid[mm(inch)]
Low Pressure Gas [mm(inch)]
High Pressure Gas [mm(inch)]
(1,240 x 1,680 x 760) x 4 (1,240 x 1,680 x 760) x 4
(48.8 x 66.1 x 29.9) x 4 (48.8 x 66.1 x 29.9) x 4
22.2(7/8) 22.2(7/8)
53.98(2 1/8) 53.98(2 1/8)
44.5(1 3/4) 44.5(1 3/4)
10Outdoor Unit
Page 11
Select the Best Location
Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors by noise from unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and
leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the
outdoor unit.
• If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid bad condition when additionally performing
defrost operation.
1. Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the prod-
uct at a place With a high humidity in winter (near beach, coast, lake, etc. )
(Ex : Rooftop where there is always sunshine.)
• The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should be also considered during the installation.
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is
0. These days the developed countries have approved it as the environment-friendly refrigerant and encouraged to use it widely to prevent environment pollution.
Environment-friendly Alternative Refrigerant R410A
CAUTION:
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed
pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
Installation Manual 11
Environment-friendly Alternative Refrigerant R410A
ENGLISH
Page 12
Select the Best Location
n Select installation location of the HR unit suitable for following conditions
• Avoid a place where rain may enter since the HR unit is for indoor.
• Sufficient service space must be obtained.
• Refrigerant pipe must not exceed limited length.
• Avoid a place subject to a strong radiation heat from other heat source.
• Avoid a place where oil spattering, vapor spray or high frequency electric noise is expected.
• Install the unit at a place in which it is not affected by operation noise. (Installation within cell such as meeting
room etc. may disturb business due to noise.)
• Place where refrigerant piping, drain piping and electrical wiring works are easy.
100 more
(Serviceing space)
100 more
(Serviceing space)
:
1. Be sure to install the inspection door at the control box side.
2. If reducers are used, servicing space must be increased equal to reducer's dimension.
n During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space
as shown in the figures below.
Installation Manual 13
Installation Space
ENGLISH
)-
*
,
)
+
*
,
-
+
)-
*
.
+
,
)-
*
.
+
,
)
-
*
)
*
-
Category
Case 1
(10mm≤Side Space≤49mm)
Case 2
(Side Space
≥
49mm)
Installation Space
4 sides are
walls
Only 2 sides
are walls
Limitations on
the height of
the wall
(Refer to 4
side walls)
Front
Front
Front
Front
Front
Front
Front
Front
Front
No limit to the height of the wall
No limit to the
height of the wall
Front
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet(rear) side must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the inlet side are higher than the
limit, there must be additional space on the front and the inlet side.
- Additional Space on the inlet side by 1/2 of h1.
• Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated
well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction
hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average
snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always remove snow for
operation.
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the
product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
Installation Space
14Outdoor Unit
Page 15
Lifting method
Installation Manual 15
ENGLISH
• When carrying the suspended, unit pass the ropes under the unit and use the two suspension points each at
the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
Lifting method
CAUTION
Be very careful while carrying the product.
• Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they
are dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging
bag may suffocate children to death.
• When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point
support may make Outdoor Unit unstable, resulting in a fall.
• Use 2 belts of at least 8 m long.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent
damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
Weight per Capacity
Chassis
Capacity(HP) Weight(kg)
UX2
8190
10240
12240
UX3
14270
16270
18320
20330
Locking points for
transportation ropes
Forklift Carrying Hole
Forklift Carrying Guide
Page 16
Installation
Installation
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom should have width of at least 100mm under the unitʼs legs before being fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
ChassisCapacity (HP)A(mm)B(mm)
UX28 ~ 12920792
UX314 ~ 2012401102
16Outdoor Unit
For outdoor units of 23kW or
above should not be supported
only by the corner supports.
6565
At least 100mm
At least 100mm
At least 100mm
At least 100mm
At least 65At least 65
At least 100mm
Needed for outdoor units of 23kW or above
Center of the Unit
At least 100mm
Needed for outdoor units of 23kW or above
Center of the Unit
Unit : mm
730
760
Page 17
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation
part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad
shall be more than 200mm).
WARNING
• Install where it can sufficiently support the weight of the outdoor unit.
If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake.
If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment of the water flowing out of the outdoor unit in operation), and the passages of the pipe and
wiring, when making the ground support.
• Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet.
The tube or pipe may freeze and the water may not be drained.
WARNING
• Be sure to remove the Pallet(Wood Support) of the bottom
side of the outdoor unit Base Pan before fixing the bolt. It
may cause the unstable state of the outdoor settlement,
and may cause freezing of the heat exchanger resulting in
abnormal operations.
• Be sure to remove the Pallet(Wood Support) of the bottom
side of the outdoor unit before welding. Not removing
Pallet(Wood Support) causes hazard of fire during welding.
At least 200mm
Unit : mm
200
75
75
200
100
- The corner part must be fixed firmly. Otherwise, the
support for the installation may be bent.
- Get and use M10 Anchor bolt.
- Put Cushion Pad between the outdoor unit and ground
support for the vibration protection in wide area.
- Space for pipes and wiring (Pipes and wirings for bottom side)
- H-beam support
- Concrete support
Pallet(Wood Support)
- Remove before Installation
Installation Manual 17
Installation
ENGLISH
Page 18
Installation
Preparation of Piping
1) Cut the pipes and the cable.
n Use the accessory piping kit or the pipes purchased
locally.
n Measure the distance between the indoor and the out-
door unit.
n Cut the pipes a little longer than measured distance.
n Cut the cable 1.5m longer than the pipe length.
2) Burrs removal
n Completely remove all burrs from the cut cross section
of pipe/tube.
n Put the end of the copper tube/pipe to downward direc-
tion as you remove burrs in order to avoid to let burrs
drop in the tubing.
3) Flaring work
n Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.
4) Check
n Compare the flared work with figure below.
n If flare is noted to be defective, cut off the flared section
and do flaring work again.
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1. Remove the cap and turn the valve counter clockwise with the hexagon wrench.
2. Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a
backseat type. Always use the special tool.
3. Make sure to tighten the cap securely.
1. Remove the cap and turn the valve clockwise with the hexagon wrench.
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Precautions when connecting pipes
• See the following table for flare part machining dimensions.
• When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three
or four times at first. (Use ester oil or ether oil.)
• See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
• After all the piping has been connected, use nitrogen to perform a gas leak check.
Tightening torque
Union
CAUTION
• Always use a charge hose for service port connection.
•
After tightening the cap, check that no refrigerant leaks are present.
• When loosening a flare nut, always use two wrenches in
combination, When connecting the piping, always use a spanner
and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare(inner and outer faces)
with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as
the initial tightening.
Shaft(valve body)Cap(Valve lid) Service portFlare nut
Gas line piping attached to unit
Ø6.4
5.4-6.6
Hexagonal
wrench 4mm
13.5-16.5
11.5-13.9
14-17
-
Ø9.533-39
Ø12.78.1-9.918-2250-60
Ø15.913.5-16.5
Hexagonal
wrench 6mm
23-2762-75
Ø22.2
27-33
Hexagonal
wrench 10mm
36-44-22-28
Ø25.4
Installation Manual 19
Installation
ENGLISH
2
90
45
2
A
R=0.4~0.8
Page 20
Installation
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over
120°C).
2. Precautions in high humidity circumstance:
This air conditioner has been tested according to the
"ISO Conditions with Mist" and confirmed that there is
not any default. However, if it is operated for a long
time in high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall. In
this case, add heat insulation material according to
the following procedure:
• Heat insulation material to be prepared... EPDM
(Ethylene Propylene Diene Methylene)-over 120°C
the heat-resistance temperature.
• Add the insulation over 10mm thickness at high humidity environment.
HEAT INSULATION
20Outdoor Unit
Indoor unit
Fastening band
(accessory)
Refrigerant piping
Thermal insulator
(accessory)
Page 21
Precautions on Pipe connection / Valve operation
Refrigerant piping installation
Low Pressure
Gas pipe
Liquid pipe
High Pressure
Gas pipe
Pipe connection is done by connecting from the end of the pipe to the
branching pipes, and the refrigerant pipe coming out of the outdoor
unit is divided at the end to connect to each indoor unit. Flare connection for the indoor unit, and welding connection for the outdoor pipe
and the branching parts.
• Use hexagonal wrench to open/close the valve.
WARNING
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas leakage after the work.
CAUTION
Please block the pipe knock outs of the front and side panels after installing the pipes.
(Animals or foreign objects may be brought in to damage the cables.)
Installation Manual 21
Refrigerant piping installation
ENGLISH
Page 22
Refrigerant piping installation
2, 3, 4 Outdoor Units
Connection of Outdoor units
For more information, refer accessory installation manual.
[Unit : mm]
Y branch
A
B
To outdoor unit
To branch piping or indoor unit
A
B
Facing
upwards
Facing
downwards
Within ± 3°Within ± 3°
Viewed from point A
in direction of arrow
Within +/- 10
22Outdoor Unit
Outdoor unitsModel
Low Pressure Gas PipeLiquid PipeHigh Pressure Gas Pipe
416
408
I.D.28.58I.D.28.58
I.D.34.9
I.D.31.8
I.D.41.3 I.D.38.1
O.D.34.9
130
341
298
I.D.41.3
O.D.34.9
I.D.41.3
125
415
375
I.D.44.48 I.D.53.98
2 Unit
3 Unit
4 Unit
C
C
C
ARCNB21
ARCNB31
C
A
C
ARCNB41
I.D.22.2
I.D.34.9
I.D.41.3
I.D.28.58
I.D.28.58
I.D.28.58
I.D.15.88I.D.15.88
111
I.D.19.05
I.D.22.2
111
I.D.22.2
I.D.22.2
134
I.D.19.05
I.D.19.05
O.D.19.05
70
80
331
314
I.D.12.7
334
281
334
281
O.D.22.2I.D.25.4
I.D.12.7
I.D.15.88
I.D.15.88
I.D.9.52
I.D.19.05
I.D.19.05
83
I.D.15.88
83
I.D.12.7
83
I.D.12.7
334
281
I.D.22.2
I.D.19.05
416
408
I.D.28.58I.D.28.58
I.D.34.9
I.D.31.8
I.D.41.3 I.D.38.1
O.D.34.9
130
341
298
I.D.41.3
O.D.34.9
I.D.41.3
125
I.D.19.05
I.D.15.88
I.D.22.2
I.D.34.9
83
I.D.12.7
111
I.D.28.58
111
I.D.28.58
Page 23
Installation of Outdoor Unit, HR Unit, Indoor Unit Refrigerant Pipe
3 pipes are connected to the HR unit from the outdoor unit, classified into liquid pipe, low pressure gas pipe and
high pressure gas pipe depending on status of refrigerant passing through the pipe.
You must connect 3 pipes from outdoor unit to HR unit.
For connection between indoor unit and HR unit, you must connect both liquid pipe and gas pipe from the HR
unit to the indoor unit. In this case, connect them to the indoor unit starting from No.1 connection port of the HR
unit (the port number is displayed on ports of the HR unit). Use auxiliary flare as annexed parts in connection to
the indoor unit.
CAUTION:
Whenever connecting the indoor units with the HR unit, install the indoor units in numerical order from No.1.
Ex) In case of installing 3 indoor units : No. 1, 2, 3 (O), No. 1, 2, 4 (X), No.1, 3, 4 (X), No.2, 3, 4 (X).
Installation procedure for HR unit
Hanger metal
Flat washer
Hanging bolt
1. Using an insert-hole-in- anchor, hang the hanging bolt.
2. Install a hexagon nut and a flat washer (locally-procured)to the hanging bolt as shown
in the figure in the bottom, and fit the main unit to hang on the hanger metal.
3. After checking with a level that the unit is level, tighten the hexagon nut.
* The tilt of the unit should be within ±5° in front/back and left/right.
4. This unit should be installed suspended from ceiling and side A should always be
facing up.
5. Insulate not used pipes completely as shown in the figure.
Installation Manual 23
Refrigerant piping installation
ENGLISH
Six-sided Nut
(M10 or M8)
Hanger metal
Hanger metal
Flat washer
Flat washer
(M10)
Hanging bolt
Hanging bolt
(M10 or M8)
A
Insulation
Gas pipe
Liquid pipe
Low pressure
Gas pipe
High pressure
Gas pipe
HR Unit
2
1
4
3
Liquid pipe
Gas pipe
Liquid pipe
Page 24
Refrigerant piping installation
24Outdoor Unit
Type of HR Unit
Select an HR unit according to the number of the indoor units to be installed. HR units are classified into 3 types
by the number of connectable indoor units.
Ex) Installation of 6 indoor units
Consists of HR unit for 4 branches and HR unit for 2 branches.
Joint Method of HR Unit (Big Duct : URNU76GB8-, URNU96GB8-)
Joint Method is required when B5/B8 chassis is installed. In Joint Method, two neighboring outlets of
one HR unit are linked by Y branch pipe and connected to one indoor unit.
Some indoor unit can be connected to one port of HR unit.
WARNING
• A branch pipe of HR unit allows up to 14.1kW based on cooling capacity of the indoor unit.
(up to 14.1kW (48kBtu/h) for max installation)
• The maximum total capacity of indoor units connected to a PRHR041 HR unit is 56.4kW
(192 kBtu/h).
• The maximum number of indoor units connected to a PRHR041 HR unit are 32 indoor units.
(The Maximum indoor units per a branch pipe of HR unit are 8 indoor units)
• There is not operate “Auto-changeover” & “Mode override” function in the zoning group.
• When there are operating indoor units on cooling(heating) mode, another indoor units arenʼt
changed on heating(cooling) mode in the zoning group.
HR unitHR unit
Zoning control group 1Zoning control group 2
(MAX 8 Indoor Units)
Changeover under controlAuto changeoverChangeover under control
sealing
(MAX 8 Indoor Units)
Page 26
Refrigerant piping installation
[ Reducers for indoor unit and HR unit ]
Models
High pressure
Gas pipe
Low pressure
Liquid pipe
Indoor unit
reducer
HR unit
reducer
PRHR021
OD22.2 Ø19.05 Ø15.88
OD15.88Ø
12.7
Ø6.35OD9.52
Ø6.35OD9.52
OD19.05Ø15.88 Ø12.7
OD22.2 Ø19.05 Ø15.88
OD15.88 Ø12.7
PRHR031/
PRHR041
OD19.05 Ø15.88
OD28.58 Ø22.2Ø19.05
OD12.7Ø9.52
OD15.88Ø12.7
OD15.88 Ø12.7 Ø9.52
(Unit: mm)
26Outdoor Unit
Page 27
Installation Manual 27
Refrigerant piping installation
ENGLISH
1. Use the following materials for refrigerant piping.
• Wall thickness : Comply with the relevant local and national regulations for the designed pressure
3.8MPa. We recommend the following table as the minimum wall thickness.
2. Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert
gas.
3. Use care to prevent dust, water or other contaminants from entering the piping during installation.
4. Reduce the number of bending portions as much as possible, and make bending radius as big as possible.
5. Always use the branch piping set shown below, which are sold separately.
6. If the diameters of the branch piping of the designated refrigerant piping differs, use a pipe cutter to cut
the connecting section and then use an adapter for connecting different diameters to connect the piping.
7. Always observe the restrictions on the refrigerant piping (such as rated length, difference in height, and
piping diameter).
Failure to do so can result in equipment failure or a decline in heating/cooling performance.
8. A second branch cannot be made after a header. (These are shown by .)
9. The Multi V will stop due to an abnormality like excessive or insufficient refrigerant. At such a time, always
properly charge the unit. When servicing, always check the notes concerning both the piping length and
the amount of additional refrigerant.
10. Never perform a pump down. This will not only damage the compressor but also deteriorate the perfor-
mance.
11. Never use refrigerant to perform an air purge. Always evacuate air by using a vacuum pump.
When installing and moving the air conditioner to another site, be sure to make recharge refrigerant
after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction
and the unit may be damaged.
- After selecting diameter of the refrigerant pipe to suit total capacity of the indoor unit connected after
branching, use an appropriate branch pipe set according to the pipe diameter of the indoor unit and the
installation pipe drawing.
12. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling performance, drip of condensate and other such problems.
13. When connecting the refrigerant piping, make sure the service valves of the Outdoor Unit is completely
closed (the factory setting) and do not operate it until the refrigerant piping for the Outdoor and Indoor
Units has been connected, a refrigerant leakage test has been performed and the evacuation process
has been completed.
14. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film
can cause clogging or damage to the compressor unit and flux can harm the copper piping or refrigerant
oil.
28Outdoor Unit
Page 29
Installation Manual 29
Refrigerant piping installation
ENGLISH
• Pipe connections can be done on the front side or on the side according to the installation environments.
• Be sure to let 0.2kgf/cm
2
Nitrogen flow in the pipe when welding.
• If Nitrogen was not flown during welding, many oxidized membranes may form inside the pipe and disturb the normal
operations of valves and condensers.
• Use Knock Outs of Base Pan of the outdoor unit for Left/Right or Bottom pipe drawing outs.
Refrigerant Pipe
Regulator
Nitrogen
Nitrogen
Direction
Taping
Valve
1. Open the front panel.
2. Remove Brackets
3. Fix with only nut and washer as shown in the
figure.
Brackets for Transportation
Washer
Nut
Pipe connections between indoor and outdoor unit
Preparation Work
CAUTION
•
Do not give damage to the pipe/base during the Knock Out work.
•
Proceed to pipe work after removing burr after Knock Out work.
• Perform sleeve work to prevent damage to the wire when
connecting wires using knock Outs.
CAUTION
• Remove the brackets on the inverter condenser legs that were fixed to protect the unit during the transportation.
(If bracket is not removed, abnormal noise or vibration may occur.)
Right Side Pipe Draw Out
Left Side Pipe Draw Out
Front Side Pipe Draw Out
Removal Area for common
pipe bottom side connections.
Removal Area for Liquid/Gas pipe
bottom side connections.
Page 30
Pipe connections between indoor and outdoor unit
n Remove leakage prevention cap
• Remove the leakage prevention cap attached to the outdoor unit service valve before pipe work.
• Proceed the leakage prevention cap removal as follows:
1. Verify whether the Liquid/Low Pressure/High Pressure
Gas pipes are locked.
2. Extract remaining refrigerant or air inside using the ser-
vice port.
3. Remove the leakage prevention cap
n Method of drawing out pipes on the front side
• Proceed with the pipe work as shown in the below figure for front side pipe drawing out.
Pipe Drawing Out during Single / Series connection
Liquid pipe Low Pressure Gas pipe
High Pressure Gas pipe
Pipe Knock Out for Liquid
/Low Pressure Gas pipes
Pipe Knock Out for High
Pressure Gas pipe
30Outdoor Unit
Service Port
Liquid pipe
Low Pressure
Gas pipe
High Pressure
Gas pipe
Leakage Prevention Cap
Page 31
Installation Manual 31
Pipe connections between indoor and outdoor unit
ENGLISH
High Pressure Gas pipe Liquid pipe Low Pressure Gas pipes
Remove only liquid/gas pipe Knock Out
• Removal of Base pan
High Pressure Gas pipe
• Removal of Base pan
Liquid pipe Low Pressure Gas pipes
n Method of drawing out pipes on the bottom side
①
Drawing out common pipe through side panel
n Figure of Sides when drawing out through bottom pipe
②
Drawing out common pipe through bottom pipe
i) Single/Series outdoor units
(Draw out High Pressure
Gas pipe through bottom)
ii) Single/Series outdoor units
(Draw out High Pressure
Gas pipe through side panel)
Remove Pipe
Knock Out Hole
Page 32
Pipe connections between indoor and outdoor unit
Refrigerant piping system
32Outdoor Unit
3 Outdoor Units
Example : 12 Indoor Units connected
Ⓐ : Outdoor Unit
Ⓑ : Y branch
Ⓓ : Indoor Unit
Ⓔ : Connection branch pipe between Outdoor units : ARCNB31
Ⓕ : Connection branch pipe between Outdoor units : ARCNB21
Ⓖ : Header
Ⓗ: HR Unit
Slave 2
A3
Slave 1
A2
Master
A1
F3
F2
F1
E
E2
E1
1
D
D
2
H
D
3
h
a
b
H1
c
d
D
4
A
B1
B
C1
B2
"a"
C3
C2
H2
f
e
D
6
D
5
■ Case 1 ("a")
: Maximum height is 15m if you install with Y branch.
■ Case 2 ("b")
: Maximum height is 5m in serial connection of HR units.
ODU Capacity
Master ≥ Slave1 ≥ Slave 2
H3
g
i
D
7
D
8
9
*
"b"
H4
j
l
m
D
D
10
k
G
sealing
x
n
D
D
12
11
Page 33
Installation Manual 33
Pipe connections between indoor and outdoor unit
ENGLISH
Ú Refrigerant pipe diameter from branch to branch (B,C,D)
WARNING
* : Serial connection of HR units : Capacity sum of indoor units ≤ 192.4 kBtu/hr
• Refer to the HR unit PCB part for the valve group control setting.
• It is recommended that difference in pipe lengths between an HR unit and indoor units, for example
difference in length of a, b, c, and d, be minimized. The larger difference in pipe lengths, the more different
performance between indoor units.
• Piping length from outdoor branch to outdoor unit ≤ 10m, equivalent length : max 13m (for 22HP or more)
j If the large capacity indoor units (Over 5 HP; using over Ø15.88/Ø9.52) are installed, it should be used the
Valve Group setting
Ú Refrigerant pipe diameter from branch to branch (B,C)
Ú Total pipe length = A+B+C1+C2+C3+a+b+c+d+e+f+g+i+j+k+l+m+n ≤ 1,000m
Longest pipe length * Equivalent pipe length
A+B+C3+D+k ≤ 150m(200m**) A+B+C3+D+k ≤ 175m(225m**)
Longest pipe length after 1st branch
B+C3+D+k ≤ 40m(90m**)
Difference in height(Outdoor Unit ÷ Indoor Unit)
H ≤ 110m
Difference in height (Indoor Unit ÷ Indoor Unit)
h ≤ 15m
Difference in height (Outdoor Unit ÷ Outdoor Unit)
h1 ≤ 5m
Difference in height(HR Unit ↔ HR Unit)
a ≤ 15m , b ≤ 5m ,
L
l
H
h
h1
"a", "b"
• * :
Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• It is recommended that indoor unit is installed at lower position than the header.
When the equivalent length between a outdoor and the farthest indoor unit
is 90m or more, main pipe(A) must be increased one grade.
Ú Refrigerant pipe diameter from outdoor unit to first branch. (A)
h If available on site, it use this size. Otherwise it can't be increased.
Upward outdoor
unit total capacity
Pipe diameter Pipe diameter when pipe length is 90m over to 1st branch
HP
Liquid
mm(inch)
Low pressure gas pipe
mm(inch)
High pressure gas pipe
mm(inch)
Liquid
mm(inch)
Low pressure gas pipe
mm(inch)
High pressure gas pipe
mm(inch)
8
9.52(3/8)
19.05(3/4) 15.88(5/8)
12.7(1/2)
22.2(7/8) 19.05(3/4)
1022.2(7/8)
19.05(3/4)
25.4(1)
22.2(7/8)
12
12.7(1/2)
28.58(1-1/8)
15.88(5/8)
31.8(1-1/4)
14
22.2(7/8) 25.4(1)
16
18
15.88(5/8) 19.05(3/4)
20
22
34.9(1-3/8)
28.58(1-1/8)
38.1(1-1/2)
31.8(1-1/4)
24
26
19.05(3/4) 22.2(7/8)
28
30
32
34
36
41.3(1-5/8) 44.5(1-3/4)
38
40
42
34.9(1-3/8) 38.1(1-1/2)
44
46
48
50
52
54
56
58
60
62
22.2(7/8)
44.5(1-3/4) 41.3(1-5/8)
25.4(1) 53.98(2-1/8)
44.5(1-3/4)
64
66
53.98(2-1/8) 44.5(1-3/4) 53.98(2-1/8)
68
70
72
74
76
78
80
Page 35
Installation Manual 35
Pipe connections between indoor and outdoor unit
ENGLISH
Ú Y branch, Header and HR unit connection pattern
Pattern 1Pattern 2
Pattern 3
Pattern 5
HR1
HR1
48k48k
1
1
2
234567
HR2
48k48k
7k7k7k 7k7k24k 24k
34
B
HR1
48k 48k 48k 48k
1234
Pattern 4
12k 12k 12k 12k
1234
HR1
HR1
48k
24k24k24k
12k12k
48k
A
B
12
HR2
48k48k
34
Pattern 6
• The maximum total capacity of indoor
units is 56.4kW(192 kBtu/h).
• The maximum total capacity of a branch
pipe of HR unit is 14.1kW(48 kBtu/h).
• Impossible installation : Head branch pipe HR unit
• Impossible installation : HR unit Head branch
pipe Y and Head branch pipe.
HR1
B
B
A
A
A
A
12 345
Page 36
Pipe connections between indoor and outdoor unit
36Outdoor Unit
Pattern 7
Pattern 8
HR1
A
A
A
48k48k
12
• * : Serial connection of HR units : Capacity sum of indoor units ≤ 192 kBtu/h
• * : Maximum indoor units per a branch are 8 indoor units
HR2
48k48k
34
HR3
48k48k
56
*
HR1
48k48k
12
HR2
*
B
12k12k12k12k
3456
24k724k
8
1
Indoor UnitY Branch pipe
Outdoor
Unit
• Pipe installation from outdoor units to HR units
: 3 pipes(Low pressure Gas pipe, High pressure Gas pipe, Liquid pipe)
• Pipe installation from HR units to indoor units
: 2 pipes(Gas pipe, Liquid pipe)
Low pressure Gas pipe
High pressure Gas pipe
Liquid pipe
A
HR1
Gas pipe
Liquid pipe
Indoor
B
Unit
Head Branch pipe
Page 37
Pipe connections between indoor and outdoor unit
Installation Manual 37
ENGLISH
1) Keep the 40m distance from the first branch to the farthest indoor.
Y branch
1) under 40m
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Keep the sum of indoor capacity under 56.4kW(192 kBtu/h).
1) under 40m
Indoor
Indoor
Indoor
Unit
Unit
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Keep the sum of indoor capacity under 56.4kW(192 kBtu/h).
5m(16ft)
15m(49ft)
Page 38
Pipe connections between indoor and outdoor unit
u Outdoor unit Connection
WARNING
• In case of pipe diameter B connected after first branch is bigger than the main pipe diameter A, B should be of the
same size with A.
Ex) In case indoor unit combination ratio 120% is connected to 70kW outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(Low pressure gas pipe), Ø15.88(liquid pipe), Ø28.58(High Pressure
liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor unit combination(84kW) : Ø34.9(Low pressure gas
pipe), Ø19.05(liquid pipe), Ø28.58(High Pressure liquid pipe)
Therefore, pipe diameter B connected after first branch would be Ø34.9(Low pressure gas pipe), Ø15.88(liquid
pipe), Ø28.58(High Pressure liquid pipe) which is same with main pipe diameter.
[Example]
Do not choose the main pipe diameter by downward indoor unit total capacity but its outdoor unit model name.
Do not let the connection pipe from branch to branch exceed the main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 22 HP (61.5 kW) outdoor unit to 120% of its system capacity (73.8 kW) and
branching 7k (2.1kW) indoor unit at the 1st branch
Main pipe diameter(22 HP outdoor unit): Ø28.58(Low pressure gas pipe), Ø15.88(Liquid pipe), Ø22.2(High pressure gas pipe)
Pipe diameter between 1st and 2nd branch (71.7kW indoor units):
Ø34.9(Gas pipe) Ø19.05(Liquid pipe) in conformity with downward indoor units.
Since the main pipe diameter of 22HP outdoor unit is Ø28.58(Low pressure gas pipe), Ø15.88(Liquid pipe), Ø22.2(High pressure gas pipe) is used as the main pipe and the connection pipe between 1st and 2nd branch.
u Indoor Unit Connection
Ú Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity [kW(Btu/h)]Liquid pipe [mm(inch)]Gas pipe [mm(inch)]
The maximum pipe length
after the first branching
between the outdoor units is
10m or less
2m or less
• If the distance between the outdoor units becomes more than 2m, apply Oil Traps between the gas pipes.
• If the outdoor unit is located lower than the main pipe, apply Oil Trap.
u Pipe Connection Method/Precautions for Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between outdoor units.
- Please refer to the below connection examples to install pipe connections between outdoor units.
Installation Manual 39
Pipe connections between indoor and outdoor unit
ENGLISH
Oil Trap
2m or less
0.2m or more
2m or longer
Oil TrapOil Trap
2m or less2m or less
2m or longer2m or longer
If the main pipe is higher
than the outdoor units, oil
is accumulated in the
outdoor unit.
If there are differences in the height
between the outdoor units, oil is
accumulated in the lower outdoor unit.
Oil Trap
Page 40
Pipe connections between indoor and outdoor unit
• The pipes between the outdoor units must maintain horizontal levelness or give an inclination to prevent a back flow toward
the slave outdoor unit. Otherwise, the unit may not operate properly.
• Apply Oil Trap as shown below when the length of the pipe between the outdoor units is more than 2m.
Otherwise, the unit may not operate properly.
Toward indoor unit
Toward indoor unit
Pipe inclination (2 or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
(Example 1)
(Example 2)
Toward indoor unit
Toward indoor unit
2m
2m
2m
0.2m
Oil Trap
40Outdoor Unit
Page 41
• When connecting the pipes between the outdoor units, the accumulation of oil in the slave outdoor unit should be avoided.
Otherwise, the unit may not operate properly.
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
h
h
h
0.2m
Toward indoor unit
Toward indoor unitToward indoor unit
Oil Trap
Installation Manual 41
Pipe connections between indoor and outdoor unit
ENGLISH
Page 42
Pipe connections between indoor and outdoor unit
u
The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correction
Factor) value of indoor unit.
Additional Charge = A x 0.118 + (B+C+D) x 0.061 + E
x 0.022 + HR unit
= 50 x 0.118 + 30 x 0.061 + 10 x 0.022
+ 0.5(HR)
= 8.45(kg)
Page 43
WARNING
▶ Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
p If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
1. Installation of effective opening part
2. Reconfirmation of Outdoor Unit capacity and piping length
3. Reduction of the amount of refrigerant
4. Installation of 2 or more security device (alarm for gas leakage)
- Change Indoor Unit type
: installation position should be over 2m from the floor (Wall mounted type ’ Cassette type)
- Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
- Limitation in piping work
: Prepare for earthquake and thermal stress
Total amount of refrigerant in the system
≤ 0.44 ( kg / m3)
Volume of the room at which Indoor Unit of the least capacity is installed
- Add exact amount of refrigerant calculated by the installation pipe diameter length and the indoor combination.
- If the refrigerant amount is not exact, it may not operate properly.
-
If additionally bottled refrigerant amount is over ±10%, condenser burning or insufficient indoor unit performance may be caused.
Liquid pipe
Low Pressure Gas pipe
High Pressure Gas pipe
Ⓐ Manifold Gauge
Ⓑ Low pressure side Handle
Ⓒ High pressure side Handle
Refrigerant Bottling
WARNING
- Pipe to be vacuumed : High Pressure Gas pipe, Low Pressure Gas pipes, Liquid pipe.
- If the refrigerant amount is not exact, it may not operate properly.
- If additionally bottled refrigerant amount is over ±10%, condenser burning or insufficient indoor unit performance may be caused.
Installation Manual 43
Pipe connections between indoor and outdoor unit
ENGLISH
Page 44
Pipe connections between indoor and outdoor unit
Branch pipe Fitting
A
B
Header
To outdoor unit
To indoor unit
A
B
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size of the
joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
• When the number of pipes to be connected is
smaller than the number of header branches,
install a cap to the unconnected branches.
• The indoor unit having larger capacity must be
installed closer to Ⓐ than smaller one.
• If the diameter of the refrigerant piping selected
by the procedures described is different from
the size of the joint,
the connecting section
should be cut with a pipe cutter.
ⓒ Pipe cutter
44Outdoor Unit
Y branch
To Outdoor Unit
A
B
A
To Branch Piping or Indoor Unit
B
Horizontal
plane
Within +/- 10
A
Viewed from point A
in direction of arrow
Facing
downwards
Within 3Within 3
Facing
upwards
Insulator
(included with kit)
Liquid and gas
pipe joints
Tap e
(field supply)
Insulator for
field piping
C
Page 45
• When the number of indoor units to be connected to the branch pipes is less than the number of branch
pipes available for connection then cap pipes should be fitted to the surplus branches.
• Fit branch pipe lie in a horizontal plane.
• Header should be insulated with the insulator in each kit.
• Joints between branch and pipe should be sealed with the tape included in each kit.
• Any cap pipe should be insulated using the insulator provided with each kit and then taped as described
above.
Horizontal plane
View from point B in the direction of the arrow
Installation Manual 45
Pipe connections between indoor and outdoor unit
ENGLISH
B
Pinched pipe
Insulate the header using
the insulation
material attached to the
branch pipe kit
as shown in the figure.
Insulator
Cap pipe
Tape
Insulator of field pipe
Insulator for cap pipe
Tape
Page 46
Pipe connections between indoor and outdoor unit
u Y branch pipe
[unit:mm]
ModelsLow Pressure Gas PipeHigh Pressure Gas PipeLiquid pipe
ARBLB01621
ARBLB03321
ARBLB07121
ARBLB14521
ARBLB23220
I.D19.05
O.D15.88
I.D12.7
I.D15.88
I.D12.7
I.D15.88
I.D15.88
I.D12.7
292
281
74
70
I.D12.7
O.D9.52
I.D6.35
I.D9.52
I.D.9.52
I.D.6.35
I.D9.52
I.D.6.35
292
281
74
70
1
1
I.D15.88
I.D 9.52
I.D15.88
I.D12.7
I.D 9.52
I.D15.88
I.D 9.52
I.D12.7
I.D12.7
372
351
74
I.D25.4
413
390
83
I.D15.88
I.D19.05
I.D12.7
I.D12.7I.D19.05I.D15.88I.D19.05
I.D22.2
I.D28.58
O.D25.4
I.D22.2
O.D19.05
O.D19.05
I.D22.2
I.D25.4
7080110
1
2
3
31 2
I.D9.52
I.D12.7
53.6D.I25.9D.I
I.D9.52
I.D12.7
I.D6.35
I.D12.7
332
321
74
2
32
3
I.D25.4
I.D15.88I.D 19.05
O.D15.88 I.D12.7 I.D 9.52
110
444
421
96
I.D 22.2
I.D 19.05
I.D15.88
I.D 19.05
I.D 22.2I.D 22.2
O.D15.88
I.D12.7
70
376
404
96
I.D34.9
O.D31.8
I.D22.2
O.D22.2
I.D28.58
50.91D.O8.13D.I
I.D28.58
12090120
I.D31.8
2.22D.I85.82D.I
I.D19.05
I.D15.88
I.D12.7
I.D19.05
I.D15.88
2
3
1
2
13
25.9D.I25.9D.I7.21D.O
I.D15.88 I.D19.05
I.D12.7
I.D12.7
I.D19.05
I.D15.88I.D12.7
I.D19.05
O.D12.7I.D6.35
I.D15.88
371
394
83
11070
2
3
32
32
2
3
3
381
409
96
I.D28.58
2.22D.I4.52D.I
I.D25.4
I.D19.05
I.D19.05
I.D22.2
I.D25.4
O.D19.05
I.D15.88 I.D12.7
110
O.D12.7
I.D9.52
70
O.D19.05
I.D15.88
70
471
517
125
120130
I.D19.05
I.D15.88
O.D22.2
I.D12.7
I.D19.05
I.D22.2
I.D41.3I.D38.1
I.D41.3
O.D34.9
I.D34.9
I.D34.9
I.D22.2
I.D28.58
I.D28.58I.D38.1
I.D41.3
I.D34.9
I.D38.1
O.D38.1
O.D15.88
O.D28.58
90
70
120
2
3
3
2
2
3
3
471
517
125
120130
I.D19.05
I.D15.88
O.D22.2
I.D12.7
I.D19.05
I.D22.2
I.D41.3I.D38.1
I.D41.3
O.D34.9
I.D34.9
I.D34.9
I.D22.2
I.D28.58
I.D28.58I.D38.1
I.D41.3
I.D34.9
I.D38.1
O.D38.1
O.D15.88
O.D28.58
90
70
120
2
3
3
2
2
3
3
416
444
96
O.D15.88 I.D9.52
I.D12.7
O.D12.7I.D6.35
I.D9.52
I.D15.88 I.D19.05
I.D22.2
I.D22.2
I.D19.05
I.D15.88
I.D12.7
I.D15.88
I.D19.05
I.D22.2
O.D19.05
80
110 110
2
3
1
233
3
3
3
3
1
2
2
O.D25.4 I.D22.2 I.D19.05
120
O.D12.7
I.D9.52
70
O.D19.05 I.D15.88 I.D12.7
110
O.D25.4
I.D22.2
80
453
491
111
I.D28.58
I.D34.9
I.D28.58
I.D31.8
I.D25.4
I.D31.8
I.D25.4
I.D28.58
I.D31.8
O.D.19.05I.D.12.7
I.D.15.88
O.D12.7I.D6.35
I.D9.52
X2
110110
I.D25.4 I.D22.2
I.D.19.05
I.D.19.05I.D.22.2
I.D.25.4
I.D.25.4
I.D.22.2
346
379
96
2
332
3
O.D.28.58
I.D.22.2
115
X2
100
O.D15.88
I.D12.7
70
O.D.22.2
I.D.15.88I.D.19.05
120
O.D.38.1
I.D.34.9
I.D.28.58 O.D.44.48
X2
175
I.D31.8
I.D.53.98
I.D.25.4
I.D.44.48
I.D.44.48
I.D38.1I.D41.3
I.D.44.48
I.D38.1I.D41.3
I.D.53.98
420
490
134
1
2
3
3
2
3
2
3
3
3
46Outdoor Unit
Page 47
u Header branch pipe
[unit:mm]
4 branch
ARBL054
7 branch
ARBL057
4 branch
ARBL104
7 branch
ARBL107
10 branch
ARBL1010
10 branch
ARBL2010
ModelsGas pipeLiquid pipe
120
150
360
540
540
120
ID15.88
ID12.7
ID12.7
ID15.88
ID15.88
ID19.05
120
120
150
360
ID9.52
ID9.52
ID6.35
ID6.35
ID9.52
ID12.7
120
150
400
160
ID15.88
ID12.7
ID19.05
ID15.88
ID22.2
ID28.58 ID25.4
120
120
150
360
ID9.52
ID9.52
ID6.35
ID6.35
ID9.52
ID12.7
120
150
120
ID15.88
ID12.7
ID15.88
ID12.7
ID15.88
ID19.05
120
150
120
ID6.35
ID9.52
ID9.52
ID12.7
120
150
160
580
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
120
150
700
120
ID6.35
ID9.52
ID9.52
ID6.35
ID9.52ID12.7
120
150
160
760
ID19.05
ID15.88
ID15.88
ID12.7
ID22.2ID28.58 ID25.4
120
150
120
720
ID6.35
ID9.52
ID9.52
ID6.35
ID12.7
ID9.52
120
150
107
60*9=540
700
ID6.35
ID9.52
ID19.05ID15.88
ID9.52
ID6.35
120
150
182
775
ID19.05
ID15.88
ID15.88
ID12.7
ID28.58
ID31.8 ID34.9
Installation Manual 47
Pipe connections between indoor and outdoor unit
ENGLISH
Page 48
Pipe connections between indoor and outdoor unit
Leak Test and Vacuum drying
(1) Leak test
Leak test should be m
ade by pressurizing nitrogen gas to 3.8 MPa(38.7kgf/cm2). If the pressure does not drop for
24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method,
refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize Liquid pipe,
Low Pressure Gas pipes, High Pressure Gas pipe)
The test result can be judged good if the pressure has not be reduced after leaving for about one day after completion of nitrogen gas pressurization.
Note:
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is
checked, apply the following correction factor
There is a pressure change of approximately 0.1 kg/cm
2
(0.01 MPa) for each 1°C of temperature difference.
Correction= (Temp. at the time of pressurization – Temp. at the time of check) X 0.1
For example: Temperature at the time of pressurization (3.8 MPa) is 27 °C
24 hour later: 3.73 MPa, 20°C
In this case the pressure drop of 0.07 is because of temperature drop
And hence there is no leakage in pipe occurred.
Caution:
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must be
at higher position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
48Outdoor Unit
Nitrogen gas
cylinder
Slave 1 outdoor unitMaster outdoor unit
Close
Close
Close
Close
Close
Close
Nitrogen gas
cylinder
Gas pipe
High Pressure
Liquide pipe
Low Pressure
Gas pipe
Gas pipe
High Pressure
Liquide pipe
Gas pipe
Low Pressure
HR unit
Liquid side
Gas side
Indoor unit
Page 49
(2) Vacuum
Vacuum drying should be made from the service port provided on the outdoor unitʼs service valve to the vacuum pump commonly used for Liquid pipe, Low Pressure Gas pipes, High Pressure Gas pipe. (Make
Vacuum from Liquid pipe, Low Pressure Gas pipes, High Pressure Gas pipe with the service valve closed.)
* Never perform air purging using refrigerant.
• Vacuum drying: Use a vacuum pump that can evacuate to -100.7kPa (5 Torr, -755mmHg).
1. Evacuate the system from the liquid and gas pipes with a vacuum pump for over 2 hrs and bring the system to -100.7kPa.
After maintaining system under that condition for over 1 hr, confirm the vacuum gauge rises. The system
may contain moisture or leak.
2. Following should be executed if there is a possibility of moisture remaining inside the pipe.
(Rainwater may enter the pipe during work in the rainy season or over a long period of time)
After evacuating the system for 2 hrs, give pressure to the system to 0.05MPa(vacuum break) with nitrogen gas and then evacuate it again with the vacuum pump for 1hr to -100.7kPa(vacuum drying). If the
system cannot be evacuated to -100.7kPa within 2 hrs, repeat the steps of vacuum break and its drying.
Finally, check if the vacuum gauge does not rise or not, after maintaining the system in vacuum for 1 hr.
WARNING
When installing and moving the air conditioner to another site, recharge after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and
the unit may be damaged.
Note : Always add an appropriate amount of refrigerant. (For the refrigerant additional charge)
Too much or too little refrigerant will cause trouble.
To use the Vacuum Mode
(If the Vacuum mode is set, all valves of Indoor units and Outdoor units will be opened.)
Installation Manual 49
Pipe connections between indoor and outdoor unit
ENGLISH
Slave 1 outdoor unitMaster outdoor unit
Vacuum
pump
Vacuum
pump
Close
Close
Gas pipe
High Pressure
Close
Liquide pipe
Gas pipe
Low Pressure
Close
Gas pipe
High Pressure
Close
Close
Liquide pipe
Gas pipe
Low Pressure
HR unit
Liquid side
Indoor unit
Scale
Use a graviometer. (One that can measure
down to 0.1kg). If you are unable to prepare
such a high-precision gravimeter you may
use a charge cylinder.
Gas side
Page 50
Pipe connections between indoor and outdoor unit
Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement or IDU addition/replacement.
Master unit PCB DIP switch on
Switch on : 10, 12, 13
Note:
When using polyethylene cover as covering material, asphalt roofing shall not be required.
• Do not insulate gas or low pressure pipe and liquid or high
pressure pipe together.
• Be sure to fully insulate connecting portion.
Liquid pipe
Gas pipe
Power lines
Finishing tape
Insulating material
Bad example
Good example
These parts are not insulated.
BA C
A
B
C
A
C
D
E
A
B
C
D
E
Transmission lines
F
Liquid pipe
Transmission lines
Transmission lines
Separation
Gas pipe
Power lines
Insulating material
A
B
C
D
E
A
A
B
F
Heat insulation material
Pipe
Outer covering
(Wind the connection part and cutting part of
heat insulation material with a finishing tape.)
Power lines
E
D
D
B
A
C
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with
enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit
and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a
possibility of condensation drip, etc. Pay special attention to insulation work to ceiling plenum.
Installation Manual 51
Pipe connections between indoor and outdoor unit
ENGLISH
Penetrations
Inner wall (concealed)
A
Floor (fireproofing)
D
B
Outer wallOuter wall (exposed)
D
C
B
Roof pipe shaft
G
F
G
B
A
Penetrating portion on fire
limit and boundary wall
D
B
H
I
A
E
B
I
J
1m1m
Sleeve
Heat insulating material
Lagging
Caulking material
Band
Waterproofing layer
Sleeve with edge
Lagging material
Mortar or other incombustible caulking
Incombustible heat insulation material
When filling a gap with mortar, cover the
penetration part with steel plate so that
the insulation material will not be caved in.
For this part, use incombustible materials
for both insulation and covering.(Vinyl
covering should not be used.)
Page 52
Electrical Wiring
Electrical Wiring
Caution
CAUTION
Be sure to correct the outdoor unit to earth. Do not connect earth line to any gas Liquid pipe, Low
Pressure Gas pipes, High Pressure Gas pipe, lightening rod or telephone earth line. If earth is
incomplete, it may cause an electric shock.
WARNING
Be sure to have authorized electrical engineers do the electric work using special circuits in
accordance with regulations and this installation manual. If power supply circuit has a lack of
capacity or electric work deficiency, it may cause an electric shock or fire.
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations and guidance of each electric power company.
2. Install the Outdoor Unit transmission line away from the power source wiring so that it is not affected by electric noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to Outdoor Unit.
4. Give some allowance to wiring for electrical part box of Indoor and Outdoor Units, because the box is sometimes removed at the time of service work.
5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts will
be burnt out.
6. Use 2-core shield cable for transmission line.(O mark in the figure below) If transmission lines of different systems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations. ( mark in the figure below)
7. Only the transmission line specified should be connected to the terminal block for Outdoor Unit transmission.
2-Core Shield CableMulti-Core Cable
52Outdoor Unit
Outdoor Unit
Outdoor Unit
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Outdoor Unit
Outdoor Unit
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Page 53
CAUTION
• Use the 2-core shield cables for transmission lines. Never use them together with power cables.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deterio-
rate power factor improvement effect, but also may cause capacitor abnormal heating. Therefore,
never install a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2%. If it is greater the units lifespan
will be reduced.
Installation Manual 53
Electrical Wiring
ENGLISH
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring
may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
• For wiring, use the designated power wire and connect firmly, then secure to prevent outside
pressure being exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head
will strip the head and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.
u Precautions when laying power wiring
Round pressure terminal
Power wire
Use round pressure terminals for connections to the power
terminal block.
CAUTION
When the 400 volt power supply is applied to “N” phase by mistake, replace inverter PCB and transformer in
control box.
Outdoor Unit
Master Slave1 Slave2
Outdoor Unit
Master Slave1 Slave2
Indoor
Unit
Indoor
Unit
Remote
controller
Remote
controller
Indoor
Unit
Indoor
Unit
Remote
controller
Remote
controller
Outdoor Unit
Master Slave1 Slave2
Outdoor Unit
Master Slave1 Slave2
Indoor
Unit
Indoor
Unit
Remote
controller
Remote
controller
Indoor
Unit
Indoor
Unit
2-Core Shield CableMulti-Core Cable
Remote
controller
Remote
controller
Page 54
Electrical Wiring
Control box and connecting position of wiring
- Remove all of the screws at front panel and remove the panel by pulling it forward.
- Connect transmission line between master and slave outdoor unit through
the terminal block.
- Connect transmission lines between outdoor unit and indoor units through
the terminal block.
- When the central control system is connected to the outdoor unit, a dedicated PCB must be connected between them.
- When connecting transmission line between outdoor unit and indoor units
with shielded wire, connect the shield ground to the earth screw.
WARNING
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
n Heat Recovery
54Outdoor Unit
Front Panel
UX2UX3
Main PCB
SUB PCB
Reactor
Inverter fan PCB
Noise filter
Bridge diode
Magnet switch
Inverter PCB
Take care of the phase
sequence of 3-phase 4-wire
power system
SUB PCB
Main PCB
Reactor
Inverter fan PCB
Noise filter
Bridge diode
Magnet switch
Inverter PCB
Take care of the phase
sequence of 3-phase 4-wire
power system
Page 55
Transmission and Power Lines
1) Transmission cable
• Types : shielding wire
• Cross section : 1.0~1.5mm
2
• Maximum allowable temperature: 60°C
• Maximum allowable line length: under 1000m
2) Remote control cable
• Types : 3-core cable
3) Central control cable
4) Separation of transmission and power lines
• If transmission and power lines are run alongside each other then there is a strong likelihood of operational
faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic coupling.
The tables below indicates our recommendation as to appropriate spacing of transmission and power lines
where these are to be run side by side
Note:
1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m
the figures will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the
table should be increased.
• If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits
• Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
• In the same way, when grouping the lines power and signal lines should not be bunched together.
Current capacity of power line Spacing
10A 300mm
50A 500mm
100A 1000mm
Exceed 100A 1500mm
100V or more
CAUTION
n If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the
apparatus must be carried out by a qualified person.
Simple central controller (2-shielding wire,2-core wire) 1.0~1.5mm
2
Installation Manual 55
Electrical Wiring
ENGLISH
Page 56
Electrical Wiring
Wiring of main power supply and equipment capacity
1. Use a separate power supply for the Outdoor Unit and Indoor Unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank
thicker taking into account the line voltage drops. Make sure the power-supply voltage does not drop
more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene
sheathed flexible cord.
6. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from
the power supply.
WARNING
• Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company.
• Make sure to use specified wires for connections so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include
some amount of direct current.
CAUTION
•
Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may
cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large
capacity may cause a malfunction of unit or fire.
56Outdoor Unit
Page 57
Field Wiring
1. 50Hz
u Example Connection of Communication Cable
n 1 Outdoor Unit-3Ø, 380-415V
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Outdoor Unit]
[Indoor Units]
Power supply
3 Phase 4 Wires
50Hz 380-415V
Power supply
1 Phase 50Hz
220-240V
(Main Switch)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
The GND terminal at the main PCB is a ‘-’ terminal for Dry contact, it is not the point to make
ground connection.
Between Indoor and Master Outdoor unit
Master
Outdoor Unit
SODU B SODU A IDU B IDU A INT B INT A
HR unit
3434343434
Installation Manual 57
Electrical Wiring
ENGLISH
Page 58
Electrical Wiring
n 2 Outdoor Units-3Ø, 380-415V
58Outdoor Unit
■ When the power source is connected
In series between the units.
Power supply
3 Phase 4 Wires
50Hz 380-415V
(Main Switch)
Power supply
1 Phase 50Hz
220-240V
N
L
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
■ When the power source is supplied to
Each outdoor unit individually.
Power supply
3 Phase 4 Wires
50Hz 380-415V
(Main Switch)
Power supply
1 Phase 50Hz
220-240V
N
L
Switch
Fuse
(4 Wires Cable)
Power Line
(2 Wires Cable)
HR unit
Switch
Fuse
Power Line
(2 Wires Cable)
R S T N
Power Line
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
R S T N
(4 Wires Cable)
Pull Box
(Installer option)
Power Line
Switch
Fuse
R S T N
[Master]
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Pull Box
(Installer option)
[Slave]
Pull Box
(Installer option)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
[Master]
Pull Box
(Installer option)
Communication Line
Power Line
[Slave]
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
HR unit
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
Power Line
Page 59
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Installation Manual 59
Electrical Wiring
ENGLISH
Between Indoor and Master Outdoor unit
SODU B SODU A IDU B IDU A INT B INT A
Master
Outdoor Unit
HR unit
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
3434343434
Master
Outdoor Unit
Slave
Outdoor Unit
Page 60
Electrical Wiring
n 3 Outdoor Units-3Ø, 380-415V
60Outdoor Unit
■ When the power source is connected
In series between the units.
Power supply
3 Phase 4 Wires
50Hz 380-415V
(Main Switch)
Power supply
1 Phase 50Hz
220-240V
N
L
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
■ When the power source is supplied to
Each outdoor unit individually.
Power supply
3 Phase 4 Wires
50Hz 380-415V
(Main Switch)
Power supply
1 Phase 50Hz
220-240V
N
L
Switch
Fuse
(4 Wires Cable)
Power Line
(2 Wires Cable)
HR unit
Switch
Fuse
Power Line
(2 Wires Cable)
(4 Wires Cable)
R S T N
Power Line
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
R S T N
Power Line
Pull Box
(Installer option)
Switch
Fuse
R S T N
[Master]
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Switch
Pull Box
(Installer option)
[Slave1] [Slave2]
Communication Line
(3 Wires Cable)
[Indoor Units]
R S T N
Fuse
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
[Master]
Pull Box
(Installer option)
Communication Line
(2 Wires Cable)
[Slave1] [Slave2]
Pull Box
(Installer option)
Communication Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
HR unit
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
Page 61
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Installation Manual 61
Electrical Wiring
ENGLISH
Between Indoor and Master Outdoor unit
SODU B SODU A IDU B IDU A INT B INT A
Master
Outdoor Unit
HR unit
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
3434343434
Master
Outdoor Unit
Slave1
Outdoor Unit
Slave2
Outdoor Unit
Page 62
Electrical Wiring
n 4 Outdoor Units - 3Ø, 380-415V
n When the power source is connected In series between the units.
n When the power source is supplied to Each outdoor unit individually.
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
Power supply
3 Phase 4 Wires
50Hz 380-415V
Power supply
1 Phase 50Hz
220-240V
(Main Switch)
[Slave1] [Slave2] [Slave3]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
Power supply
3 Phase 4 Wires
50Hz 380-415V
Power supply
1 Phase 50Hz
220-240V
(Main Switch)
[Slave1] [Slave2] [Slave3]
R S T N
Switch
Fuse
R S T N
Switch
Fuse
R S T N
Switch
Fuse
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
WARNING
When the total capacity is over than as follow, the power source do not use in series between the units.
The First terminal block could be burnt out.
62Outdoor Unit
Page 63
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Installation Manual 63
Electrical Wiring
ENGLISH
Between Indoor and Master Outdoor unit
SODU B SODU A IDU B IDU A INT B INT A
Master
Outdoor Unit
HR unit
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
3434343434
Master
Outdoor Unit
Slave1
Outdoor Unit
Slave2
Outdoor Unit
Slave3
Outdoor Unit
Page 64
Electrical Wiring
2. 60Hz
u Example Connection of Communication Cable
n 1 Outdoor Unit - 3Ø, 380V
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Outdoor Unit]
[Indoor Units]
Power supply
3 Phase 4 Wires
60Hz 380V
Power supply
1 Phase 60Hz
220V
(Main Switch)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
The GND terminal at the main PCB is a ‘-’ terminal for Dry contact, it is not the point to make
Between Indoor and Master Outdoor unit
Master
Outdoor Unit
SODU B SODU A IDU B IDU A INT B INT A
HR unit
3434343434
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the prod-
uct is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
64Outdoor Unit
Page 65
n 2 Outdoor Units - 3Ø, 380V
n When the power source is connected In series between the units.
n When the power source is supplied to Each outdoor unit individually.
Installation Manual 65
Electrical Wiring
ENGLISH
Power supply
3 Phase 4 Wires
60Hz 380V
(Main Switch)
Power supply
1 Phase 60Hz
220V
N
L
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Power supply
3 Phase 4 Wires
60Hz 380V
(Main Switch)
Power supply
1 Phase 60Hz
220V
N
L
Switch
Fuse
Power Line
(2 Wires Cable)
HR unit
Switch
Fuse
Power Line
(2 Wires Cable)
R S T N
Power Line
(4 Wires Cable)
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
R S T N
Power Line
(4 Wires Cable)
Pull Box
(Installer option)
Switch
R S T N
Fuse
[Master]
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Pull Box
(Installer option)
[Slave]
Pull Box
(Installer option)
Communication Line
(3 Wires Cable)
[Indoor Units]
[Master]
Pull Box
(Installer option)
Communication Line
Power Line
(2 Wires Cable)
[Slave]
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
HR unit
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
Page 66
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
66Outdoor Unit
Between Indoor and Master Outdoor unit
SODU B SODU A IDU B IDU A INT B INT A
Master
Outdoor Unit
HR unit
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
3434343434
Master
Outdoor Unit
Slave
Outdoor Unit
Page 67
n 3 Outdoor Units - 3Ø, 380V
n When the power source is connected In series between the units.
n When the power source is supplied to Each outdoor unit individually.
Installation Manual 67
Electrical Wiring
ENGLISH
Power supply
3 Phase 4 Wires
60Hz 380V
(Main Switch)
Power supply
1 Phase 60Hz
220V
N
L
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Switch
Fuse
(4 Wires Cable)
Power Line
(2 Wires Cable)
HR unit
R S T N
Power Line
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Power supply
3 Phase 4 Wires
60Hz 380V
(Main Switch)
Power supply
1 Phase 60Hz
220V
N
L
Switch
Fuse
Power Line
(2 Wires Cable)
(4 Wires Cable)
R S T N
Power Line
Pull Box
(Installer option)
Switch
Fuse
R S T N
[Master]
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Switch
Pull Box
(Installer option)
Fuse
[Slave1] [Slave2]
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
R S T N
Pull Box
(Installer option)
[Master]
Communication Line
(2 Wires Cable)
[Slave1] [Slave2]
Pull Box
(Installer option)
Communication Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
HR unit
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
Page 68
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
68Outdoor Unit
Between Indoor and Master Outdoor unit
SODU B SODU A IDU B IDU A INT B INT A
Master
Outdoor Unit
HR unit
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
3434343434
Master
Outdoor Unit
Slave1
Outdoor Unit
Slave2
Outdoor Unit
Page 69
n 4 Outdoor Units - 3Ø, 380V
n When the power source is connected In series between the units.
n When the power source is supplied to Each outdoor unit individually.
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
Power supply
3 Phase 4 Wires
60Hz 380V
Power supply
1 Phase 60Hz
220V
(Main Switch)
[Slave1] [Slave2] [Slave3]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
Power supply
3 Phase 4 Wires
60Hz 380V
Power supply
1 Phase 60Hz
220V
(Main Switch)
[Slave1] [Slave2] [Slave3]
R S T N
Switch
Fuse
R S T N
Switch
Fuse
R S T N
Switch
Fuse
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
WARNING
When the total capacity is over than as follow, the power source do not use in series between the units.
The First terminal block could be burnt out.
Installation Manual 69
Electrical Wiring
ENGLISH
Page 70
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product
is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
70Outdoor Unit
Between Indoor and Master Outdoor unit
SODU B SODU A IDU B IDU A INT B INT A
Master
Outdoor Unit
HR unit
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
SODU B SODU A IDU B IDU A INT B INT A
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
3434343434
Master
Outdoor Unit
Slave1
Outdoor Unit
Slave2
Outdoor Unit
Slave3
Outdoor Unit
Page 71
u Example Connection of Communication Cable
[BUS type]
• Connection of communication cable must be installed like below figure between indoor unit to outdoor
unit.
[STAR type]
• Abnormal operation can be caused by communication defect, when connection of communication
cable is installed like below figure(STAR type).
HR unit
HR unit
Installation Manual 71
Electrical Wiring
ENGLISH
Page 72
Electrical Wiring
u UX2 Chassis Wire Connection
Main Power Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Ground Cable
Power/Ground lines
Over 50mm Gap
Communication line
Left Side
Ground Cable
Communication line
Power/Ground lines
Over 50mm Gap
MainPowerTerminalBlock
Main Power Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Right Side
Ground Cable
Communication line
Power/Ground lines
Over
50mm Gap
MainPowerTerminalBlock
MainPowerTerminalBlock
Main Power Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Front Side 1
Main Power Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Insulation sleeves attachments
Fix firmly not to be displaced
ODU-ODUCommunicationline
Ground CableGround CableGround Cable
ODU-IDU
Communication line
ODU-ODU
ODU-ODU
Communication lineCommunication line
ODU-ODU
Communication line
Communication line
Power/Ground lines
Over 50mm Gap
Main Power
Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Ground Cable
Front Side 2
Main PCB ConnectionMain Power Connection
72Outdoor Unit
Page 73
u UX3 Chassis Wire Connection
႖ဴఎၴఝ႖ဴఎၴఝ
Main Power Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Ground Cable
Power/Ground lines
Over 50mm Gap
Communication line
Left Side
႖ဴఎၴఝ
MainPowerTerminalBlock
Main Power Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Ground Cable
Power/Ground lines
Over 50mm Gap
Communication line
Right Side
Main Power Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Ground Cable
Power/Ground lines
Over
50mm Gap
Communication line
Front Side 1
:;<6
Insulation sleeves attachments
Ground Cable
Fix firmly not
to be displaced
Main Power Terminal Block
Main Power Terminal BlockMain Power Terminal Block
ODU-ODUCommunicationline
ODU-ODUODU-ODU
Communication lineCommunication line
ODU-ODU
Communication line
ODU-IDU
Communication
line
MainPowerTerminalBlock
Main Power Main Power
Terminal BlockTerminal Block
Main Power
Terminal Block
Ground Cable
Power/Ground lines
Over 50mm Gap
Communication line
Front Side 2
Main PCB ConnectionMain Power Connection
Installation Manual 73
Electrical Wiring
ENGLISH
Page 74
Electrical Wiring
Location of setting dip switch
n SUB PCB
74Outdoor Unit
DIP-SW01DIP-SW02
7 - Segment
SW03B
(DATA CONFIRM)
SW02B
(AUTO ADDRESS)
Page 75
DIP switch setting
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
Installation Manual 75
Electrical Wiring
ENGLISH
n Checking according to dip switch setting
1. You can check the setting values of the Master outdoor unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
2. It checks whether the input is properly performed without the bad contact of the dip switch or not
n Checking the setting of the Master unit
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power. This
number represents the setting condition. (For example, represents R410A 30HP)
Master model code ‘ Slave1 model code ‘ Slave2 model code ‘ total capacity ‘ 2 ‘ 25 ‘ 180
1 ~255 : Master model code
1 ~255 : Slave1 model code
1 ~255 : Slave2 model code
1 ~255 : Slave3 model code
8~80HP : HP number(sum of master capacity and slave capacity)
No display : cooling only 2 : heat pump / heat recovery
25 : normal
180 : Model Type (ARUB***LT3)
Example) 30Hp, R410A
194 ’ 193 ’ 30 ’ 2 ’ 25 ’ 180
}
Refer to table code
Model Code
Model Code Unit (HP) Unit Ref.
190 8
191 10
192 12
193 14
194 16
195 18
196 20
Master &
Slave
R410A
Page 76
Electrical Wiring
n Setting the DIP switch
• If you set the Dip switch when power is on, the changed setting will not be applied immediately.
The changed setting will be enabled only when Power is reset or by pressing Reset button.
CAUTION
1. ʻXʼ mark within the table means that the dip switch must be pulled down. If not, the function may not work properly.
2. If the applicable dip switch is not set properly, the product may not work properly.
3. When executing the test operation, check the operating condition of the indoor unit and only execute the operation
when all indoor units are stopped.
4. Auto test operation function does not work for the product where only one indoor unit is connected for use.
Inverter backup
Const. 1 backup
Const. 2 backup
Unità backup
Night low noise operation(cooling, heating)
Night low noise operation(cooling only)
Snow removal function
Forced defrost
Snow removal + Forced defrost
Non-operation indoor unità EEV adjustment
Indoor unità target subcooling/overheating adjustment
Operation indoor unità EEV adjustment
Real-time sensor monitoring
Only overall defrost
Static pressure mode
Pump out
Pump down
Vacuum mode
Forced oil return operation
4way valve manual operation-upper, low OFF
4way valve manual operation-upper ON, low OFF
4way valve manual operation-upper OFF, low ON
4way valve manual operation-upper, low ON
Auto pipe detection mode 1
Auto pipe detection mode 2
Indoor unità pipe display
No. Indoor unitààs connected a branch of HR Unità
Auto charging
Refrigerant Checking Function
Intergrated test operation function (Heating)
Intergrated test operation function (Cooling)
Heating Capacity up
IDU Fan RPM Control
ODU Address setting
Master unità
Slave1 unità
Slave2 unità
Slave3 unità
Page 77
HR Unit PCB
Switch for setup of HR Unit
1. Main function of SW02M
1) Selection of the method for addressing valves of an HR unit (Auto/Manual)
AutoManual
SW02M
(Dip switch for setup of
the function of HR unit)
SW03M SW04M
SW01M/SW03M/SW04M
(Switch for manual valve
addressing)
SW01M
SW05M
(Switch for
addressing
HR unit)
7-SEG
#1 valve housing
#1 cooling valve LED(green)
#1 heating valve LED(red)
#4 valve housing
Switch No.1 OnSwitch No.1 Off
ON S/W
Selection
No.1
Method for addressing valves of an HR unit (Auto/Manual)
No.2
Model of HR unit
No.3
Model of HR unit
No.4
Model of HR unit
No.5
Valve group setting
No.6
Valve group setting
No.7
Use only in factory production (preset to “OFF”)
Zoning setting (“ON”)
No.8
Use only in factory production (preset to “OFF”)
SW02M
Installation Manual 77
HR Unit PCB
ENGLISH
2) Setting the zoning control
DIP S/W setting
Normal
control
Zoning
control
SW01M
SW01M
Turn the dip switch of the zoning
branch on.
Ex) Branch 1,2 are zoning control.
Page 78
HR Unit PCB
78Outdoor Unit
3) Selection of the model of the HR unit
h Each model is shipped with the switches No.2 and No.3 pre-adjusted as above in the factory.
WARNING
• If you want to use a PRHR031 for 2 branches HR unit after closing the 3rd pipes, set the dip switch for 2 branches HR unit.
• If you want to use a PRHR041 for 3 branches HR unit after closing the 4th pipes, set the dip switch for 3 branches HR unit.
•
If you want to use a PRHR041 for 2 branches HR unit after closing the 3rd and 4th pipes, set the dip switch for 2 branches HR unit.
• The unused port must be closed with a copper cap, not with a plastic cap.
(For 2 branches)
PRHR021
(For 3 branches)
PRHR031
(For 4 branches)
PRHR041
Initial
Setting
1 branches
Connected
2 branches
Connected
3 branches
Connected
4 branches
Connected
1
4
2
3
2
1
3
2
1
Page 79
] Y branch pipe
4) Setting the Valve Group.
[Unit:mm]
Note:
If the large capacity indoor units are installed, below Y branch pipe should be used
Installation Manual 79
HR Unit PCB
ENGLISH
DIP S/W setting
Example
Not control
No.1, 2 Valve
Control
No.2, 3 Valve
Control
No.3, 4 Valve
Control
No.1, 2 Valve
/
No.3, 4 Valve
Control
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Large capacity indoor unit
Indoor Unit
Large capacity indoor unit
Indoor Unit
Large capacity indoor unit
Indoor Unit
Indoor Unit
Large capacity indoor unit
Large capacity indoor unit
ModelsGas PipeLiquid pipe
ARBLB03321
I.D22.2
I.D25.4
1
390
413
I.D28.58
I.D22.2
O.D19.05
31 2
7080110
O.D25.4
I.D15.88
O.D19.05
I.D19.05
I.D22.2
I.D12.7I.D19.05I.D15.88I.D19.05
2
I.D12.7
3
I.D25.4
83
I.D12.7
I.D9.52
I.D12.7
I.D9.52
321
332
I.D12.7
I.D6.35
53.6D.I25.9D.I
74
Page 80
HR Unit PCB
2. SW05M (Rotary S/W for addressing HR unit)
Must be set to '0' when installing only one HR unit.
When installing multiple HR units, address the HR units with sequentially increasing numbers starting from '0'.
Ex) Installation of 3 HR units
3. SW01M/SW03M/SW04M (Dip S/W and tact S/W for manual valve addressing)
1) Normal setting (Non-Zoning setting)
- Set the address of the valve of the HR unit to the central control address of the connected indoor unit.
- SW01M: selection of the valve to address
SW03M: increase in the digit of 10 of valve address
SW04M: increase in the last digit of valve address
- Prerequisite for manual valve addressing : central control address of each indoor unit must be preset differently at its wired remote control.
S/W No.Setup
No.1Manual addressing of valve #1
No.2Manual addressing of valve #2
No.3Manual addressing of valve #3
No.4Manual addressing of valve #4
SW03MIncrease in the digit of 10 of valve address
SW04MIncrease in the last digit of valve address
SW01M
SW03M
SW04M
80Outdoor Unit
ABABAB
4
3
2
1
4
3
2
1
3
2
1
4
Page 81
2) Zoning setting
- Set the address of the valve of the HR unit to the central control address of the connected indoor unit.
- SW01M : selection of the valve to address
SW03M : increase in the digit of 10 of valve address
SW04M : increase in the last digit of valve address
SW05M :Rotary S/W
- Prerequisite for manual valve addressing : central control address of each indoor unit must be preset
differently at its wired remote control.
S/W No.Setup
No.1Manual addressing of valve #1
No.2Manual addressing of valve #2
No.3Manual addressing of valve #3
No.4Manual addressing of valve #4
SW03MIncrease in the digit of 10 of valve address
SW04MIncrease in the last digit of valve address
SW05MManual addressing of zoning indoor units
SW01M
SW03M
SW04M
SW05M
0
Installation Manual 81
HR Unit PCB
ENGLISH
Page 82
HR Unit PCB
Auto addressing for indoor units and HR units
82Outdoor Unit
n SUB PCB
1) Auto addressing for indoor unit
• The address of indoor units would be set by
auto addressing
1) Wait for 3 minutes after applying power supply
(Master and Slave Outdoor unit, Indoor unit).
2) Press the switch of the outdoor unit for
5~10seconds until display 88.(SW02B).
3) A "88" is indicated on 7-segment LED of the
outdoor unit PCB.
4) For completing addressing, 2~7 minutes are
required depending on numbers of indoor unit
connection set.
5) Numbers of inddor unit connection set whose
addressing is completed are indicated for
30seconds on 7-segment LED of the oudoor
unit PCB.
6) After completing addressing, address of each
indoor unit is indicated on the wired remote
control display window. (CH01, CH02, CH03,
........ CH06: Indicated as numbers of indoor
unit connection set).
1) Auto addressing for indoor unit
2) Auto pipe detection
3) Manual pipe detection(Execute in case of Auto pipe detection failure)
• Turn off all the indoor units before auto addressing.
If indoor unit is operated, auto addressing would not be completed.
2) Auto pipe detection
1) Turn No.1 of SW02M of HR unit PCB off.
2) Confirm that the setting of No.2, 3 of SW02M corresponds with the number of indoor units.
3) Reset the power of HR unit PCB
4) Turn on the No. 17 DIP S/W of main unit PCB when outdoor temperature is below 15°C
Turn on the No. 14, 17 DIP S/W of main unit PCB when outdoor temperature is over 15°C
5) Reset the power of outdoor unit.
6) Wait for 3 minutes.
7) Press SW03B of the outdoor unit main PCB for 5 Seconds.
8) The number of connected HR unit is displayed.
Ex) In case of installing four HR units : 04
9) Operated after 88 is displayed on 7-SEG of the outdoor unit main PCB.
CAUTION
• In replacement of the indoor unit PCB, always perform Auto addressing setting
again
(At that time, please check about using Independent power module to any
indoor unit.)
• If power supply is not applied to the indoor unit, operation error occur.
• Auto addressing is only possible on the master Unit.
• Auto addressing has to be performed after 3 minutes to improve communication.
DIP-SW01DIP-SW02
7 - Segment
SW03B
(DATA CONFIRM)
SW02B
(AUTO ADDRESS)
Page 83
Installation Manual 83
HR Unit PCB
ENGLISH
3) Manual pipe detection
1) Enter the central control address into each indoor unit using its wired remote control.
2) Turn No.1 of SW02M of HR unit PCB on.
3) Reset the power of HR unit PCB.
4) On the HR unit PCB, manually set address of each valve of the HR unit to the central control address of the
indoor unit connected to the valve.
5) Reset the power of outdoor unit PCB.
6) The number of the indoor unit installed is displayed after about 5 minutes.
Ex) HR ‡ The number of the indoor
7) Reset the power of outdoor unit PCB, HR unit.
8) Manual pipe detection is completed
WARNING
1. In case that central controller is not installed, remain the address data after installer sets central
control address as he wants
2. In case that central controller is installed, there would be central control address in wired remote
control of indoor unit.
3.
In this case, set the HR unit manual pipe address according to central control address of indoor unit.
4. Pipe which is not connected with indoor unit should be set different address with pipe Connected
with indoor unit.
(If addresses are piled up, corresponding valve is not working.
5. If you want to change the setting of manual pipe, you should do it on HR unit PCB.
6. If an error occurred, it means that manual pipe setting is not completed.
7. During 5 minutes after pipe detection is completed, do not turn off the main unit PCB to save the
result of pipe detection automatically.
WARNING
1. Execute auto addressing and auto pipe detection again whenever the indoor PCB and HR unit PCB
is replaced.
• Operation error occurs unless power is applied to the indoor and HR units.
2.
Error No.200 occurs if the number of connected indoor units and that of scanned indoor units are different.
3. When auto pipe detection fails, complete it with manual pipe detection (see Manual pipe detection).
4.
When auto pipe detection addressing is completed normally, manual pipe detection is not required.
5. If you want to do auto pipe detection again after auto pipe detection fails, do after reset of outdoor
unit by all means.
6. During 5 minutes after pipe detection is completed, do not turn off the main unit PCB to save the
result of pipe detection automatically.
10) Pipe detection proceed.
11) 5~30 minutes are required depending on the number of the indoor units and outdoor temperature.
12) The number of the indoor units installed is displayed on 7-SEG of the outdoor unit main PCB for about 1
minute
• For a HR unit, the number of the indoor units connected to each HR unit is displayed.
•
'200' is displayed in case of auto pipe detection error, and auto detection is completed after '88' is disappeared.
h Auto pipe detection function : the function that sets connection relationship automatically between the
indoor unit and HR unit.
Page 84
HR Unit PCB
Flow chart of auto-addressing for indoor units
84Outdoor Unit
Power On
Waiting 3 minutes
Press RED Button for
10~15sec. (SW02B)
7-segment LED = 88
Don’t press RED Button
(H/P : SW0B, C/O : SW02V)
The number of the indoor
units connected is
displayed at 7-SEG of the
outdoor unit main PCB
after 2~7 minutes
The number of HR units
connected is displayed
at 7-SEG of the outdoor
unit main PCB
7-segment LED
= 88
YES
OK
NOCheck the connections
Auto addressing start
• Auto addressing setting end
Numbers of indoor unit connection set whose
addressing is completed are indicated for 30seconds
on 7-segment LED after completing setting
of transmission line
Indoor address number is displayed on wired remote control or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor
units and auto addressing is completed normally.
Page 85
Flow chart of auto addressing for pipe detection
Installation Manual 85
HR Unit PCB
ENGLISH
Confirmation of indoor unit address setting
Turn No.1 of SW02M of HR unit PCB off.
Confirm that the setting of No.2, 3 of
SW02M corresponds with the number of
indoor units.
Reset the power of HR unit PCB
Confirm the DIP S/W of DIP-SW01,02 of
outdoor PCB
Outdoor temperature is below 15°C : 17 ON
Outdoor temperature is over 15°C : 14, 17 ON
In case of changing DIP-SW01,02 S/W
of outdoor unit, reset the power of
outdoor unit main PCB
Wait for 3 minutes
Press SW03B of the outdoor unit main
PCB for 5 seconds
Outdoor unit is operated for 5~60 minues.
Is the pipe
setting condition
satisfied during the operation of
indoor unit?
YES
The number of indoor units detected is
displayed for 30 seconds on the outdoor
unit PCB after outdoor unit stopped
Are the number
of indoor units connected to the
outdoor unit wiring and displayed
one equal?
YES
Completion of auto pipe detection
NO
NO
Display error on outdoor unit PCB
Display error on HR unit PCB
Outdoor unit PCB : HR ‡ HR unit
number ‡ Valve number
HR unit : '200'
Check the HR unit and indoor unit
Pipe detection error occur after 30
seconds.
Check the installation of pipe of
outdoor, indoor, HR unit
88' is displayed on 7-SEG of the outdoor
unit main PCB
❇ It is possible to be generated mode changing noise of
heating and cooling which is normal.
There is no mode changing noise at normal operation.
Retry auto pipe detection after
checking trouble
Incompletion of auto pipe detection
Page 86
HR Unit PCB
Flow chart of manual addressing for pipe detection
86Outdoor Unit
Execute in case of Auto pipe detection
failure
Wait for about 5 minutes.
Turn No.1 of SW02M of HR unit PCB on.
The number of the indoor units installed is
Reset the power of HR unit PCB.
Enter the central control address into
each indoor unit using its wired remote
control.
On the HR unit PCB, manually set address
of each valve of the HR unit to the central
control address of the indoor unit
connected to the valve.
Reset the power of outdoor unit PCB.
displayed.
Ex)HR ‡ The number of the indoor
Are the number
of indoor units connected to the
outdoor unit and displayed one
equal?
YES
Completion of manual pipe detection
NO
Check the central control address of
indoor and HR unit.
Make sure that reset the outdoor unit
power when changing the central
control unit
Page 87
Example of manual valve addressing (Non-Zoning setting)
(In case that an indoor unit of central control address "11" is connected to a valve #1 of an
HR unit)
• Prerequisite for manual valve addressing: central control address of each indoor unit must be preset differently at its wired remote control.
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be addressed with any other number than used
address numbers of the valves connected with indoor units.
(The valves does not work if the address numbers are same.)
Installation Manual 87
HR Unit PCB
ENGLISH
• Operation: None
• Display: None
No.
1
2
3
4
5
Display and setupSetup and Contents
• Operation: Turn dip S/W No.1 on to address valve #1
• Display: Existing value saved in EEPROM is displayed in
7-SEG.
• Operation: Set the digit of 10 to the number in Group High data
of the wired remote control connected to the corresponding
indoor unit to the valve #1 by pressing left tack S/W.
• Display: Digit increasing with the times of pressing tack S/W is
displayed in left 7-SEG
• Operation: Set the digit of 1 to the number in Group Low data
of the wired remote control connected to the corresponding
indoor unit to the valve #1 by pressing right tack S/W.
• Display: Digit increasing with the times of pressing tack S/W is
displayed in right 7-SEG
• Operation: Turn dip S/W No.1 off to save the address of
valve #1
• Display: "11" displayed in 7-SEG disappears
7-SEGSW01MSW03M SW04M
7-SEGSW01MSW03M SW04M
7-SEGSW01MSW03M SW04M
7-SEGSW01MSW03M SW04M
7-SEGSW01MSW03M SW04M
Page 88
HR Unit PCB
Example of manual valve addressing (Zoning setting)
(In case that an indoor unit of central control address "11" is connected to a valve #1 of an HR unit)
Zoning control is connecting 2 or more indoor units at one pipe of HR unit. In case of Zoning control, in order to set controls with
multiple indoor units connection uses the rotary switch. Namely, only the rotary switch changes from same valve set condition and
set indoor units connection.
1) On dip switch of the corresponding valves and sets the rotary switch at 0.
2) Setting the number with tact switch.
3) In case of addition of indoor units to same port, increases 1 with the rotary switch and sets number with tact switch.
4) In case of checking the number which the corresponding valve is stored, turn on dip switch and set the number of rotary switch.
5) Indoor units set available 7 per a port(rotary switch 0~6), in case of setting above of 7 with rotary switch, it will display error.
6) Setting the rotary switch on original condition(HR unit number set conditions) after all finishing a piping setting.
7) The rotary switch set value of above number of indoor units which is connected with FF and prevents a malfunction.
(Example: The case where 3 indoor units is connected in piping 1, sets from rotary switch 0,1,2 and 3,4,5 with FF set)
• Prerequisite for manual valve addressing: central control address of each indoor unit must be preset differ-
ently at its wired remote control.
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be addressed with any other number than used
address numbers of the valves connected with indoor units.
(The valves does not work if the address numbers are same.)
• Operation: None
• Display: None
No.
1
2
3
4
5
6
7
Display and setupSetup and Contents
• Operation : Turn dip S/W No.1 on to address valve #1
• Display : Existing value saved in EEPROM is displayed in
7-SEG.
• Operation : Set the digit of 10(1) to the number in Group
High data of the wired remote control connected to the corresponding indoor unit to the
valve #1 by pressing left tack S/W.
• Display : Digit increasing with the times of pressing tack
S/W is displayed in left 7-SEG.
• Operation : SW05M : 1
• Display : Display former value.
•
Operation : Setting No. using SW03M and SW04M,
SW05M : 1
• Display : Display setting value.
• Operation : Turn dip S/W No.1 off to save the address of
valve #1
• Display : "11" displayed in 7-SEG disappears.
• Operation : Return valve of addressing HR unit.
• Display : None
7-SEGSW01MSW03M SW04M
0
SW05M
7-SEGSW01MSW03M SW04M
SW05M
0
7-SEGSW01MSW03M SW04M
SW05M
0
1
7-SEGSW01MSW03M SW04M
SW05M
7-SEGSW01MSW03M SW04M
SW05M
1
7-SEGSW01MSW03M SW04M
SW05M
1
7-SEGSW01MSW03M SW04M
SW05M
0
88Outdoor Unit
Page 89
Example of checking valve address
(In case that an indoor unit of central control address "11" is connected to a valve #1 of an
HR unit)
• Operation: Turn dip S/W No.1 on.
• Display: "11" is displayed in 7-SEG
No.
1
2
Display and SetupSetup and Contents
• Operation: Turn dip S/W No.1 on.
• 7-SEG disappeared
7-SEGSW01M
7-SEGSW01M
Identification of Manual Valve ID (Address)
Method of checking the pipe detection result at outdoor unit
• Operation: more than 2 dip switches turned on.
• Display: "Er" is displayed in 7-SEG
No.
1
Display and SetupSetup and Contents
7-SEGSW01M
Installation Manual 89
HR Unit PCB
ENGLISH
ROTARY 01 ROTARY 02
0
0
1) Wait for 5 minutes, after Pipe detection is completed.
2) Turn on the No.10,14,16 DIP S/W of SUB PCB at master unit
3) Check the data on 7- segment, switching rotary 01,02.
The connected port number of HR unit
The connected HR unit number
The auto addressing number of indoor unit (digit of 1)
The auto addressing number of indoor unit (digit of 10)
Page 90
HR Unit PCB
Group Number setting
Group Number setting for Indoor Units
① Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off.
② The transmission lines connected to INTERNET terminal should be connected to central control of Outdoor
Unti with care for their polarity( A ’ A, B ’ B )
③ Turn the whole system on.
④ Set the group and Indoor Unit number with a wired remote control.
⑤ To control several sets of Indoor Units into a group, set the group ID from 0 to F for this purpose.
Outdoor Units
90Outdoor Unit
Setting method of Master indoor unit in zoning
ROTARY 01 ROTARY 02 7 segment
0
0
1) Turn dip switch 5,6,10 on at system off.
2) Set the left Ratary switch for HR unit.(Rotary switch No. "0" ‘ HR unit No. "1")
3) Set the right Ratary switch for IDU unit.(Rotary switch No. "0" ‘ HR unit branch No. "1")
4) Display the Master IDU No. of the HR unit on 7segment.(Default display is "00" on 7segment)
5) Press the black button.(The IDU No. increase every 1 second in the zoning )
6) Set the Master IDU(Press the red button during 1.5seconds stop twinkling)
No. of Indoor unit.
No. of HR unit branch.
No. of HR unit.
CAUTION
• Waiting for 80seconds after power on.
• The zoning information and Master IDU information remove from EEPROM after Auto-addressing.
• If there is installed the central control, it is impossible setting of Master IDU in zoning.
SODU B SODU A IDU B IDU AINT B INT A
B(D)A(C) BA
Page 91
WARNING
• Valve address and central control address of its corresponding indoor unit should be set identical in manual
addressing.
Example) Group number setting
1
st
number indicate the group number
2
nd
number point out indoor unit number
Group recognizing the simple central controller
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
1 F
Indoor unitGroup
Installation Manual 91
HR Unit PCB
ENGLISH
EX)
HR unit
Valve (04)
Valve (03)
Valve (02)
Valve (01)
Indoor unit (04)
Indoor unit (03)
Indoor unit (02)
Indoor unit (01)
Central control address
Page 92
Test Run
Functions of each Test run steps
Test Run
1
2
3
4
Check to see whether there is any refrigerant leakage, and slack of power or transmission cable.
Confirm that 500 V megger shows 2 MΩ or more between power supply terminal block and ground. Do
not operate in the case of 2 MΩ or less.
NOTE: Never carry out megaohm check over terminal control board. Otherwise the control board
would be broken.
Immediately after mounting the unit or after leaving it turned off for an extended length of time,
the resistance of the insulation between the power supply terminal board and the ground may
decrease to approx. 2 MΩ as a result of refrigerant accumulating in the internal compressor.
If the insulation resistance is less than 2 MΩ, turning on the main power supply and energizing
the crankcase heater for more than 6 hours will cause the refrigerant to evaporate, increasing
the insulation resistance.
Check if Liquid pipe, High Pressure Gas pipe, Low Pressure Gas pipe valves are fully opened.
NOTE: Be sure to tighten caps.
Check if there are any problems in automatic addressing or not:
Check and confirm that there are no error messages in the display of indoor units or remote controls
and LED in outdoor units.
Checks Before Test Run
CAUTION
when cutting main power of the Multi V
• Always apply main power of the outdoor unit during use of product
(cooling season/heating season).
• Always apply power 6 hours in advance to heat the crank case heater where performing test run
after installation of product. It may result in burning out of the compressor if not preheating the
crank case with the electrical heater for more than 6 hours.(In case of the outdoor temperatue
below 10°C)
Step 0. Verify the command signals
Select function to be executed during the test run
Step 1. Examine Sensor
Examine the normal operations of the sensors attached to the outdoor/indoor units
Step 2. Examine Indoor unit EEV and wrong wirings
Examine the normal operation of EEV attached to the indoor unit, and examine the wirings of the indoor unit.
Step 3. Refrigerant Automatic Recharge
If additional bottling of the refrigerant is needed, operate to perform this automatically.
Step 4. Automatic Refrigerant Decisions
Inspect if the bottled refrigerant in the system has adequate quantity.
Step 5. Integrated Test Run
Process to verify the normal operations of the parts attached to the system, and verify normal operation of the system.
Step 6. Real-time sensor checking
Check the sensors while operating in real-time.
h Gas pipes and Liquid pipes connections inspection
: Inspect whether the gas pipes and Liquid pipes are connected to each other.
92Outdoor Unit
Page 93
How to Cope with Test Run Abnormality
The phenomena from main component failure
When system fault occurs, the error code is displayed at indoor unit display or remote control display,
the trouble shooting guide is in the service manual
Compressor
Outdoor
fan
Outdoor
EEV
Not operating
Stop during running
Abnormal noise
during running
High pressure error
at cooling
Heating failure, frequent defrosting
No operating sound
at applying power
Heating failure,
frozen outdoor heat
exchanger part
Low pressure error
or discharge temperature error
Motor insulation broken
Strainer clogged
Oil leakage
Motor insulation failure
R-S-T misconnection
Motor failure,
bad ventilation around
outdoor heat exchanger
Bad connector contact
Coil failure
EEV clogged
EEV clogged
Check resistance between terminals and
chassis
Change strainer
Check oil amount after opening oil port
Check resistance between terminals and
chassis
Check compressor R-S-T connection
Check the outdoor fan operation after being
turned the outdoor units off for some time.
Remove obstacles around the outdoor units
Check connector
Check resistance between terminals
Service necessary
Service necessary
Component Phenomenon Cause Check method and Trouble shooting
Installation Manual 93
Test Run
ENGLISH
Page 94
Test Run
Sensor Checking Function
Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors is right or
not. 3 indoor temperature sensors, 10 outdoor temperature sensor
Note 1)
, 2 outdoor pressure sensors.
This function is used along with Refrigerant Auto recharge and Quantity auto decide function.
It is used for judging sensor abnormality.
Note2)
DIP Switch Settings
Warning : Please reset SUB PCB before starting this function
- Setting1
(Refrigerant Auto Recharge)
- Setting2
(Refrigerant Quantity Auto Decide)
- Setting3
(Integrated Test Run - cooling)
- Setting4
(Integrated Test Run - heating)
94Outdoor Unit
Page 95
Note 1. Outdoor temperature number is different according to each chassis.
Note 2. Please check the sensor that is found abnormal.
Note 3. Each step is displayed on the Main PCB LED.
Note 4. Please refer to the sensor error descriptions on the next page.
WARNING
1. Please confirm if auto addressing function was executed. (Check the number of installed indoor units)
2. Error may occur when the sensor is normal according to the installed location and the temperature
conditions. When error occurs, please check each sensor and decide faultiness.
ChassisUX2(2 comp)UX3(2 comp)UX3(3 comp)
No. of sensor111113
Installation Manual 95
Test Run
ENGLISH
Start
3 minutes
past after power
reset
YES
DIP switch set
Setting 1Setting 2Setting 3Setting 4
Note 3)
Press black button
for 2 seconds
Heat Pump?
NO
Press black button
for 5 seconds
NO
Sensor Normal
NO
Display Error
Press black button for 2 seconds
NO
YES
YES
YES
Press black button for
5 seconds
Setting 1Setting 2Setting 3Setting 4
: Heat
Recovery
End
All DIP switches OFF and press black
button for 2 seconds
Data Reset and Wait
Refrigerant
Auto Recharge
Refrigerant
Auto decide
Start Inspection of each Function
Cooling
Heating
Page 96
Test Run
96Outdoor Unit
Display codifica errore controllo sensori
In case error occurs during sensor checking process, error display is as shown below.
Following contents are displayed one after the other on the main PCB of master Unità esterna.
ex) Indoor unit No. 2 Pipe inlet temperature sensor
error
ex) Outdoor Master Unit Liquid pipe temperature
sensor error
ex) IDU No.2 Pipe inlet temperature sensor error and Master
ODU suction temperature sensor, Slave 3 high pressure
sensor error
Caution
1. Up to 5 number of errors is displayed continuously and
repeatedly. In case 5 error occurs, again perform sensor
checking after solving errors.
2. IDU in which error occurred operates air circulation mode.
........
Indoor sensor error :
319
Outdoor sensor error :
309
Displaying error content
* 5 number of errors is displayed
continuously and repeatedly.
No.Classification
1Pipe In Temperature
2Pipe Out Temperature
3Indoor Air Temperature
Table 2. IDU Sensor Error Code
Table 1. ODU Sensor Error Code
No.Sensor type
1
2
3
4
5
6
7
8
9
10
11
12
14
15
16
17
Displaying error content
n Indoor unit error display
1.1st and 2nd number represents indoor unit number.
2. Last number represents sensor.
1: Pipe inlet temperature sensor
2: Pipe outlet temperature sensor
3: Air temperature sensor
n Displaying outdoor unit error
1. 1st and 2nd number represents error content(code).
2. Last number represents outdoor unit number.
1 : Master
2 : Slave 1
3 : Slave 2
4 : Slave 3
*
Indoor unit number follows auto addressing number.
(To check the LGMV Data)
Outdoor Air Temperature
Heat Exchanger Temperature
Partition Heat Exchanger Temperature(Upper)
Partition Heat Exchanger Temperature(Low)
Liquid Pipe Temperature
SC pipe out
Suction Temperature
Inverter Comp. Discharge Temperature
Constant Comp.1 Discharge Temperature
Constant Comp.2 Discharge Temperature
High Pressure
Low Pressure
IPM temperature
INV. Oil Balance Temperature
Constant Comp.1 Oil Balance Temperature 1
Constant Comp.1 Oil Balance Temperature 2
Page 97
This function charges appropriate amount of refrigerant automatically through cycle operation.
It can be used when refrigerant amount Isn't certain because of SVC and leakage.
Refrigerant Auto Charging (Setting 1)
DIP Switch Settings
Warning : Please reset SUB PCB before starting this function
Note
1. After installing the refrigerant charging device, as shown in figure, open the valve
2. In case air temperature is out of guaranteed temperature, it may end without performing Auto charging
3. Refrigerant charging Time may change according to the charging amount. (Abt. 3min/kg)
Installation Manual 97
Test Run
ENGLISH
Start
Wait for 3 min. after power reset
Set the Dip S/W.
(Refer to DIP S/W setting)
Press the black button.
(Press until ‘508’ is displayed)
Press the black button.
IDU runs with cooling mode In designated order.
Is it necessary to
charge refrigerant?
No
IDU and ODU are turned off when Auto Charging
is completed. Close the valve.
Yes
Press the black button
Refrigerant Auto
Charging Process
*1)
*2)
Main PCB
SW01V
Press the black button
Press the black button for 2 sec. after turning off
all of dip S/W.
Completed.
Page 98
Test Run
Low pressure
gas pipe
CAUTION
1. Guaranteed temperature range (Error will occur if temperature is out of range)
IDU : 20°C(68°F) ~ 32°C(90°F)
ODU : 0°C(32°F) ~ 43°C (77°F)
2. For refrigerant charging, use designated device only. (Capillary Assem Set)
3. Set the IDU wired remote controller temperature sensing mode as IDU
4. Be careful that IDU should not be thermo off.
n Error contents about auto refrigerant charging function
1. : Temperature Range Error (In case that IDU or ODU is out of range)
2. : Low Pressure Descent Error (In case the system runs at low pressure limit for over 10 minutes)
3. : Judging rapid refrigerant inflow ( In case the liquid refrigerant flows in because of not using
designated Capillary Assembly)
4. : Instability Error( In case the high/low pressure target doesn't get satisfied for some time after the
starting operation)
98Outdoor Unit
Low pressure
Low pressure
gas pipe
gas pipe
manifold
Capillary Assembly
Procedure
1. Arrange manifold,capillary assembly, refrigerant vessel and scale
2. Connect manifold to the gas pipe service valve of ODU as shown in the figure.
3. Connect manifold and Capillary tube.
Use designated capillary assembly only.
If designated capillary assembly isn't used, the system may get damaged.
4. Connect capillary and refrigerant vessel.
5. Purge hose and manifold.
6. After Is displayed, open the valve and charge the refrigerant
Page 99
Refrigerant Checking Function (Setting 2)
This function judges refrigerant leakage and overcharging
It can be used with refrigerant auto charging function.
DIP Switch Settings
Warning : Please reset SUB PCB before starting this function
Note
1. In case air temperature is out of guaranteed temperature, refrigerant checking function may end without performing refrigerant
checking. Use guaranteed temperature range only.
2. During the process of judging refrigerant amount, if the cycle isn't stable, refrigerant checking function may end without
performing refrigerant checking.
Installation Manual 99
Test Run
ENGLISH
Inspection Start
Press black button for 2 seconds
YES
NO
NO
Gas/Liquid
pipe direct
connection
Press black button for 2 seconds
Press black button for 2 seconds
Too much
Refrigerant
Proper Temperature
Thermo off indoor unit
Decide Refrigerant Quantity
Based on Refrigerant Quantity
Not enough
Refrigerant
Cannot tell
Quantity
YES
Refrigerant
Quantity
Normal
Display Error
Display Error
End
Data Reset and Wait
Indoor Unit OFF
Page 100
Test Run
100Outdoor Unit
[ Error contents about auto refrigerant charging function ]
1. : Temperature Range Error (In case that IDU or ODU is out of range)
2. : System Unstable Error (In case, After 45 min operating the system, it does not be stable)
How to Cope with Result of Refrigerant checking
1. If the temperature is not in guaranteed Temperature range, the system will not execute Refrigerant checking and the system will be OFF.
2. Excess of Refrigerant(619)
After remove the 20% of calculated total refrigerant, recharge the refrigerant by using Refrigerant Auto
Charging Function.
3. Scarcity of Refrigerant(629)
Charge the refrigerant by using Refrigerant Auto Charging Function.
4. Impossible to Judge(639)
IF the system is not in order, check the other problem except refrigerant.
CAUTION
1. Guaranteed Temperature range(Error occurs out of guaranteed temperature range)
IDU : 20 ~ 35 °C
ODU : 0 ~ 43 °C
2. Set IDU wired remote controller temperature sensor setting as 'IDU'.
3. Make certain that IDU doesn't run with thermo off mode during operation.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.