LG Art Cool LA090HSV4, Art Cool LA120HSV4, Art Cool LA180HSV4 Engineering Manual

SINGLE ZONE ART COOL™ MIRROR
WALL MOUNTED ENGINEERING MANUAL
3/4, 1, and 1-1/2 Tons
Models:
LA090HSV4 LA120HSV4 LA180HSV4
PROPRIETARY DATA NOTICE
This document, as well as all reports, illustrations, data, information,
and other materials are the property of LG Electronics U.S.A., Inc., and are
disclosed by LG Electronics U.S.A., Inc. only in confidence.
This document is for design purposes only.
A summary list of safety precautions is on page 4.
For more technical materials such as submittals, catalogs, installation,
owner’s, and service manuals, visit www.lghvac.com.
© LG Electronics U.S.A., Inc.
About LG Electronics, Inc.
LG Electronics, Inc. is a global leader and technology innovator in consumer electronics, mobile communications, and home appliances. LG Electronics, Inc. comprises five business units— Home Entertainment, Mobile Communications, Air Conditioning, Business Solutions, and Home Appliance. LG is one of the world’s leading producers of flat panel televisions, audio and video products, mobile handsets, air conditioners, and washing machines. LG’s commercial air conditioning business unit was established in 1968 and has built its lineup of residential and commercial products to include VRF, Multi F, duct-free split systems, packaged terminal air conditioners (PTACs), and room air conditioners. In 2011, the air conditioning and energy solutions business unit grew to include LED lighting and solar products. For more information, visit www.lg.com.
Duct-Free Split Systems
LG HVAC systems offer a range of solutions that are cost efficient, quiet and attractive. Duct-Free Split systems are “split” into indoor and outdoor units, and provide a smart alternative to both central HVAC and window-mounted air conditioners. These inverter heat pump systems are available in a variety of configurations to suit dif­ferent cooling and heating situations. Installation by a qualified HVAC contractor is safe and easy – little to no duct work or sheet metal is required.
Inverter Systems
LG Single Zone Art Cool™ Mirror Wall Mounted air-source systems offer the opportunity to minimize ductwork in the same configuration. The system offers zoning without the need for zone damper systems. The LG Single Zone Inverter Wall Mount system’s advanced controls provide exceptional building dehumidification and temperature control, and can rapidly adapt system operating parameters to the ever changing building load. The LG Single-Zone Art Cool Mirror Wall-Mounted system is easy to design, install, and maintain. The modular design allows occupants to control their environmental condition, providing individualized control of the setpoint temperature and allowing occupants to condition only the occupied zones.
Quality Commitment
LG is committed to the success of Duct-Free Split projects. We provide industry leading technical support during installation and commissioning. LG offers a variety of classes designed for installers and servicers to ensure that every system installation is completed successfully.
Classes are conducted at LG’s training centers and in field locations at various times throughout the year and upon special request.
Introduction
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
3
TABLE OF CONTENTS
DANGER
CAUTION
INTRODUCTION ..................................................................................... 5
ARCHITECTURAL APPEAL .................................................................. 6
PRODUCT FEATURES AND BENEFITS ............................................... 8
UNIT NOMENCLATURE .........................................................................9
General Data ................................................................................... 10-11
Electrical Data ...................................................................................... 12
Functions, Controls, and Options ...................................................... 13
Outdoor Unit Dimensions ................................................................... 14
LSU090HSV4, LSU120HSV4 ............................................................ 14
LSU180HSV4 .................................................................................... 15
Indoor Unit Dimensions ...................................................................... 16
LAN090HSV4, LAN120HSV4 ............................................................ 16
LAN180HSV4 .................................................................................... 17
ACOUSTIC DATA .................................................................................18
Refrigerant Flow Diagrams ................................................................. 20
LAN090HSV4, LSU090HSV4
LAN120HSV4, LSU120HSV4 ............................................................20
LAN180HSV4, LSU180HSV4 ............................................................ 21
Wiring Diagram .................................................................................... 22
LAN090HSV4, LAN120HSV4 ............................................................ 22
LAN180HSV4 .................................................................................... 23
LSU090HSV4, LSU120HSV4 ............................................................ 24
LSU180HSV4 .................................................................................... 25
Accessories ......................................................................................... 26
PERFORMANCE DATA ........................................................................ 31
Cooling Capacity ............................................................................... 32
Heating Capacity ............................................................................... 34
Equipment Selection Procedure ........................................................ 38
LAN090HSV4, LSU090HSV4
LAN120HSV4, LSU120HSV4 ............................................................38
LAN180HSV4, LSU180HSV4 ........................................................... 39
Building Ventilation Design Guide ..................................................... 41
Placement Considerations ............................................................ 42-44
REFRIGERANT PIPING DESIGN & LAYOUT
BEST PRACTICES ...............................................................................45
Refrigerant Piping Design .................................................................. 46
Design Guideline Summary ............................................................... 46
Selecting Field-Supplied Copper Tubing ........................................... 47
Installation & Layout Best Practices ................................................. 48
Refrigerant Piping System Layout ..................................................... 48
Piping Connection ............................................................................. 50
ELECTRICAL CONNECTIONS ............................................................52
Mechanical Specications .................................................................. 54
Acronyms ............................................................................................. 55
TABLE OF SYMBOLS
This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
This symbol indicates situations that may result in equipment or property damage accidents only.
This symbol indicates an action should not be completed.
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
INTRODUCTION
“Architectural Appeal” on page 6
ARCHITECTURAL APPEAL
Convergence of Technological Innovation with Flexibility and Style
Single Zone Art Cool
Benefits of Single Zone
Art Cool Mirror Wall-Mounted System
•Available in 9,000 - 18,000 Btu/h
•Inverter technology
•All-season use - heat pump models for both
cooling and heating capabilities
•Operating range for outdoor units of 14°F to
118°F (DB) in cooling and -4°F to 65°F (WB) in heating
•Operating range for indoor units of 53°F to
75°F (WB) in cooling and 60°F to 86°F (DB) in heating
Mirror Wall-Mounted Systems
Choosing an LG Single-Zone Art Cool Mirror Wall-Mounted product provides a system designer an edge to engineer a system with individual control, and design flexibility with advanced controls.
These single-zone systems are avail­able in a nominal capacity range of 3/4 to 1-1/2 tons. These are best suited for applications with zones that require heat­ing or cooling, such as residential, and small business office buildings. Single­Zone Art Cool Mirror Wall-Mounted outdoor and indoor units are available in 208–230V/60Hz/1Ph.
•Quiet operation inside and outside
•Duct-free split system
Mirror Wall Mounted Engineering Manual
Art Cool
Adaptable and Flexible
Single-zone wall-mounted duct-free split systems allow cooling or heating for the entire residence or just a single room without the need for invasive ductwork. There is minimal renovation needed.
Long refrigerant piping lengths allow for extra design flexibility in indoor unit installation.
These units may be used for a number of residential or commercial environments such as:
•Older homes
•New home construction
•Office buildings
•Restaurants
•Hospitals / Medical facilities
•Schools
•Nursing homes
•Retail establishments
•House of worship
Inverter Technology
Inverter variable-speed duct-free split systems are measurably quieter and consume less energy than conventional air conditioners. The inverter compressor ramps up or down to match the required room capacity and maintain the comfort level. When the selected temperature is reached, the inverter compressor operates at low speed to maintain that comfort level, thereby using less energy.
6 | INTRODUCTION
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA
“Product Features and Benefits” on page 8
“Unit Nomenclature” on page 9
“General Data” on page 10
“Electrical Data” on page 11
“Outdoor Unit Dimensions” on page 14
“Indoor Unit Dimensions” on page 16
“Acoustic Data” on page 18
“Refrigerant Flow Diagram” on page 20
“Indoor Unit Wiring Diagram” on page 22
“Outdoor Unit Wiring Diagram” on page 24
“Accessories” on page 26
PRODUCT FEATURES AND BENEFITS
Single Zone Art Cool™ Mirror Wall Mount
Single zone systems are equipped with inverter components that offer superior load matching and long piping installation. The product works for optimizing power consumption in residential and small office buildings. Utilizing multiple indoor wall mount units each with custom temperature controls allow for precise temperature settings in each zone of the building. Single zone sys­tems allow flexibility in interior design and complement any decor.
Low Sound Levels
When outdoor units run at full load, they have a quiet operating sound level. To pro­mote a quiet, comfortable environment, the LG single zone system indoor units operate at sound levels as low as 23 dB(A) (19dB(A) in sleep mode) (Art Cool Mirror Wall-Mount­ed) and the outdoor units as low as 45 dB(A) at full load (Art Cool Mirror Wall-Mounted). All rotating components are soft-started by the controller using digitally controlled invert­ers, which reduce undesirable noise caused by fans and compressors cycling on and off.
Comfort Control at Its Best
Unlike traditional air conditioning control systems, which use thermostatic controls to
Mirror Wall Mounted Engineering Manual
maintain room temperatures, LG single zone
inverter controls continuously vary the indoor unit fan speed and refrigerant flow.
LG single zone one-to-one systems continu­ously measure the room temperatures and adjust system operations accordingly to
Art Cool
maintain set temperature. The outdoor unit responds by varying the
compressor speed and outdoor fan mo­tors as needed to maintain system operat­ing pressure. As a result, the single zone systems deliver targeted space temperature control.
Inverter Driven
The rotary (9k/12k Btu/h systems) and twin-rotary (18k Btu/h systems) compres­sors are optimized to maximize compressor efficiency, which reduces power consump­tion and monthly utility bills. This latest inverter technology allows single zone system outdoor units to vary the compressor motor shaft speed to deliver an appropriate
amount of cooling to the indoor unit. Precise refrigerant volume delivery translates into long periods with coil surface temperatures below dew point and minimizes compressor and fan component run time which may lead to lower utility usage.
Simplified Installation
Cooling and heating applications that use single zone systems simplify and reduce the mechanical and control system design time. The designer no longer has to be concerned with interconnecting chilled and condenser water piping, air-distribution duct systems, matching and selecting chillers, towers, pumps, coils, fans, air handlers, or Variable Air Volume (VAV) boxes.
Operating Range
Single zone systems have a nominal capac­ity range of 3/4 to 1-1/2 tons (depending on outdoor/indoor units).
Outdoor unit operating ranges for single zone systems:
Cooling: 14°F DB to 118°F DB Heating: -4°F WB to 65°F WB Installing an optional Low Ambient Wind
Baffle Kit will allow operation down to 0°F in cooling mode for these single zone systems.
Compact Size
Single zone outdoor units have the following footprints.
LSU090HSV4, LSU120HSV4
(WxHxD (in)) 30 5/16 x 21-1/2 x 11-5/16.
LSU180HSV4
(WxHxD (in)) 34-1/4 x 31-1/2 x 12-5/8.
Fin Design with Gold­Fin™ Coating
All single zone outdoor units are provided with large surface coils made of copper tubes with louvered aluminum fins designed to maximize unit operating efficiency over a wide range of ambient conditions.
Standard from the factory, every single zone outdoor unit coil fin surface is coated with LG’s exclusive GoldFin™ anti-corrosive coating designed to prevent natural surface corrosion of the alumi­num fins. This maintains heat transfer properties of the coil for an extended time.
A hydrophilic coating is applied to the outdoor unit coil fin surface over the GoldFin
coating. This coating enhances the develop­ment of heavier water droplets gathering on the fin surface. As a result, the droplets roll off the fin surfaces, delaying the point when frost forms on the coil surface during heat­ing operation. This coating also makes it possible to easily clean the outdoor unit coil using a mild soap.
Other Features
•Inverter variable speed compressor
•Jet Cool / Jet Heat
•Dehumidifying mode
•3M™ Micro Protection Filter
•Chaos Wind
•Auto restart
•Auto operation
•Self-cleaning indoor coil
•Condensate sensor connection
•Precision load matching
•Meets AHRI 210/240
8 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
UNIT NOMENCLATURE
Single Zone Wall Mount Indoor and Outdoor Units
Family LA= Art Cool Premier / Gallery / Mirror LS= High Efficiency Wall Mount / Standard / Mega
Type N = Indoor Wall Mount Unit U = Outdoor Heat Pump Unit
Nominal Capacity (Nominal cooling capacity in Btu/h)
090/091 = 9,000 120/121 = 12,000 180/181 = 18,000 240 = 24,000 300/307 = 30,000 360 = 36,000
Indoor/Outdoor Product HEV = Mega HXV = Mega 115V HYV = Art Cool Premier HVP = Art Cool Gallery HSV = Art Cool Mirror, High Efficiency HV = Standard HLV = Extended Pipe
LA
N 090 HSV 4
Product Data
Generation or Revision 1 = First 2 = Second 3 = Third 4 = Fourth
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 9
GENERAL DATA
Art Cool Mirror Pairing Table
The following table shows the available outdoor and indoor units, along with the factory provided controller.
Table 1: Single Zone Art Cool Mirror Pairing Table
Outdoor Unit Model Indoor Unit Model Controller
LSU090HSV4 LSU120HSV4
LSU180HSV4 LAN180HSV4 AKB73835317
LAN090HSV4 LAN120HSV4
AKB73835317
Mirror Wall Mounted Engineering Manual
Art Cool
10 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
Table 2: SingleZoneArtCoolMirrorSystemSpecications.
System Model Number (IDU/ODU)
Cooling Capacity (Min/Rated/Max) (Btu/h) Cooling Power Input1 (kW) Heating Capacity (Min/Rated/Max) (Btu/h) Heating Power Input1 (kW) COP
(LAN090HSV4/LSU090HSV4)
LA090HSV4
1,023 ~ 9,000 ~ 12,625 1,023 ~ 11,200 ~ 13,785 3,070 ~ 18,200 ~ 29,515
0.68 0.90 1.45
1,023 ~ 10,800 ~ 17,061 1,023 ~ 13,300 ~ 22,178 3,070 ~ 22,000 ~ 38,898
0.70 1.0 1.76
4.51 3.90 3.66
Maximum Heating Capacity (Btu/h)
Outdoor 17°F (WB)/Indoor 70°F (DB) Outdoor 5°F (WB)/Indoor 70°F (DB) Outdoor -4 °F (WB)/Indoor 70°F (DB)
EER SEER HSPF
8,856 (82%) 10,906 (82%) 18,040 (82%) 7,452 (69%) 9,177 (69%) 15,180 (69%) 7,236 (67%) 8,911 (67%) 14,740 (67%)
13.29 12.5 12.58
21.5 21.5 20.5
10.8 11.0 9.7
Power Supply (V/Hz/Ø)
Outdoor Unit Operating Range
2
Cooling (°F DB) Heating (°F WB)
Indoor Unit Operating Range
Cooling (°F WB) Heating (°F DB)
Indoor Temperature Setting Range
Cooling (°F) Heating (°F)
Unit Data
Refrigerant Type
3
Refrigerant Control IDU Sound Pressure4 dB(A) (H/M/L/Sleep) ODU Sound Pressure4 dB(A)
38/33/23/19 39/33/23/19 45/40/35/29
45 45 53
Unit Weight (lbs)
IDU (Net/Shipping) ODU (Net/Shipping) Power/Communication Cable
5
(No. x AWG)
24/29 24/29 32/39 75/79 75/79 121/131
Compressor
Compressor Type (Qty)
Single Rotary (1) Single Rotary (1) Twin Rotary (1)
Fan
IDU Type (Qty) ODU Type (Qty) Motor/Drive
Airflow Rate
IDU Max/H/M/L (CFM) ODU Max (CFM)
423/353/272/191 423/353/272/191 735/622/509/339
1,165 1,165 2,119
Piping
Liquid Line (in, OD) Vapor Line (in, OD) Condensation Line (OD, ID) Additional Refrigerant Charge (oz/ft) Pipe Length6 (Minimum/Maximum)(ft) Piping Length6 (no add’l refrigerant, ft) Max Elevation Difference (ft)
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
1
Power Input is rated at high speed.
2
Optional Low Ambient Wind Baffle Kit allows operation down to 0°F in cooling mode.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
4
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
All power wiring/communication cables are field supplied and are to be minimum 18 AWG, 4-conductor,
stranded, shielded and must comply with applicable local and national codes.
1/4 1/4 3/8 3/8 3/8 5/8
27/32, 5/8 27/32, 5/8 27/32, 5/8
0.22 0.22 0.38
6.6/65.6 6.6/65.6 9.84/98.4
41.0 41.0 24.6
32.8 32.8 49.2
GENERAL DATA
(LAN120HSV4/LSU120HSV4)
(LAN180HSV4/LSU180HSV4)
208-230/60/1
14 to 118
-4 to 65
53 to 75 60 to 86
64 to 86 60 to 86
R410A
EEV
4 x 18
Cross Flow (1)
Propeller (1)
Brushless Digitally Controlled/Direct
6
Piping lengths are equivalent. This unit comes with a dry helium charge. This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units. Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB). Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
LA120HSV4
LA180HSV4
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 11
ELECTRICAL DATA
Table 3: Single-Zone Art Cool Mirror System Electrical Data Table.
Model Number Nominal Tons
Compressor
Qty.
Compressor (A)
Cool/Heat
Fan Qty. ODU Fan (A) IDU Fan (A) MCA(A) MOP(A)
LA090HSV4 3/4 1 8.3/8.3 1 0.40 0.40 10 15
LA120HSV4 1 1 8.3/8.3 1 0.40 0.40 10 15
LA180HSV4 1-1/2 1 14.6/14.6 1 0.25 0.40 19 25
Voltage tolerance is ±10%. Maximum allowable voltage unbalance is 2%. MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down to the nearest standard fuse size.
Mirror Wall Mounted Engineering Manual
Art Cool
12 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
Table 4: Indoor Units—Functions, Controls and Options.
Indoor Unit Type LA090HSV4 LA120HSV4 LA180HSV4 Air supply outlet Airflow direction (left/right) Airflow direction (up/down) Auto swing (left/right) Auto swing (up/down) Airflow steps (fan/cool/heat)
Airow
Auto swing Chaos wind (Auto wind) Jet-cool/heat Swirl wind One touch soft air Washable anti-fungal
1
Deodorizing filter
2
Plasma Allergy free filter
Air Purifying
3M Micro Protection filter
2
Drain pump E.S.P. control Electric heater High ceiling Defrost Low ambient Hot start Self diagnostics Soft dry (dehumidification) Auto changeover
Functions
Auto clean (coil dry) Auto restart Child lock Forced operation Sleep mode Timer (24hr on/off) Weekly timer Two thermistor control Wireless Remote Controller Simple Controller with Mode Selection Simple Controller without Mode Selection LG Programmable Thermostat Dry contact
Controllers
Central control (LGAP) PI 485 Zone control CTIE Electro thermostat Wi-Fi Module (Option)
Water level sensor connection (for optional AG-9300-LG) Wind baffle kit
Special Function Kit
FUNCTIONS, CONTROLS, OPTIONS
1 1 1 Auto Auto Auto Auto Auto Auto
6 / 6 / 6 6 / 6 / 6 6 / 6 / 6
√ √/√ √/√ √/√
X X X
X X X
X X X
X X X
X X X
X X X
X X X
X X X
√ √ √
√ √ √
X X X
X X X
X X X
o o o
o o o
o o o
o o o
o o o
o o o
X X X
X X X
X X X
X X X
o o o
o o o
Product Data
Thermistor
Other
1
Primary washable filters.
2
Secondary filters.
√=Standardfeature
o = Optional accessory (must be purchased separately) X = Not available
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
X X X
•WhenDryContactModeactive,Wi-FiFunctioncannotbeused.
•WhenchangingfromWi-Fimodetodrycontactmode,normaloperationresumesinapproximately3minutes.
PRODUCT DATA | 13
OUTDOOR UNIT DIMENSIONS
30-5/16
22
4-3/16
13-15/16
6-3/32
2-3/32
10-15/16
1
20-7/8
21-1/2
10-1/2
9-3/8
19-15/16
2-7/8
8-3/32
4
3
2
5
11-5/16
5-3/4
Ø18-5/16
Center of gravity
[Unit : inch ]
Discharge Air Grille
LSU090HSV4, LSU120HSV4
Mirror Wall Mounted Engineering Manual
Art Cool
14 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
OUTDOOR UNIT DIMENSIONS
34-1/4
21-1/2
12-19/32
14-3/16
6-5/16
2-3/16
13-1/8
31-1/2
30-7/8
15-7/16
13-3/4
21-1/8
3-1/8
2
Ø 20-7/8
Item No. Part Name
1 Discharge air grille 2 3 4 5 6
12-5/8
5-7/8
Center of gravity
[Unit : inch]
LSU180HSV4
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 15
INDOOR UNIT DIMENSIONS
Ø2-9/16
5-1/8
3-11/16
Right rear piping
Left rear piping
Place a level on raised tab
Unit Outline
8-1/2
6-15/16
17-3/8 17-3/8
5
Ø2-9/16
34-13/16
8-1/16
1-3/4
6-5/16
2-5/16
15/16
11-1/4
2
1-3/4 2-3/16
2-3/8
3
2
1
4
[Unit : Inch]
Return Air Grille
for piping and cables
LAN090HSV4, LAN120HSV4
Mirror Wall Mounted Engineering Manual
Art Cool
16 | PRODUCT DATA
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
INDOOR UNIT DIMENSIONS
3
2
1
40-9/16
9-11/16
1-13/16
12-3/4
2-1/16
1-3/4
2-9/16
2-1/16
Ø2-9/16
Right rear piping
Left rear piping
Measuring Tape
Measuring Tape Hanger
Place a level on raised tab
Unit Outline
18-1/8 22-7/16
8-1/8
4-1/8
2-11/16
2-1/8
Ø2-9/16
4
[Unit : Inch]
Return Air Grille
LAN180HSV4
Product Data
Due to our policy of continuous product innovation, some specications may change without notication.
LG Electr onics U.S.A., Inc., Englewood Cl iffs, NJ. All r ights reserved. “LG ” is a re gistered trademark of LG C orp.
©
PRODUCT DATA | 17