LG ARNU09GSJC4 INSTALLATION INSTRUCTIONS

Page 1
INSTALLATION MANUAL
AIR CONDITIONER
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
[
Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[
Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si,
Gyeongsangnam-do, KOREA
WALL MOUNTED Original instruction
MFL69485413
Rev.28_061319
www.lg.com
Copyright © 2017 - 2019 LG Electronics Inc. All Rights Reserved.
ENGLISH
ITALIANO ESPAÑOL
FRANÇAIS DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
РУССКИЙ ЯЗЫК
УКРАÏНСЬКА
ҚАЗАҚ ТІЛІ
БЕЛАРУСКАЯ МОВА
OZBEK TILI
Page 2
2
TIPS FOR SAVING ENERGY
ENGLISH
• Do not cool excessively indoors. This may be harmful for your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
TIPS FOR SAVING ENERGY
Page 3
IMPORTANT SAFETY INSTRUCTIONS
3
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
The following symbols are displayed on indoor and outdoor units.
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
Installation
• Compliance with national gas regulations shall be observed.
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire
or electric shock.
!
!
!
Read the precautions in this manual carefully before operating the unit.
This appliance is filled with flammable refrigerant (R32)
This symbol indicates that the Operation Manual should be read carefully.
This symbol indicates that a service personnel should be handling this equipment with reference to the Installation Manual.
Page 4
4
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the
case edges and the fins on the condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it,
causing property damage, product failure, and personal injury.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or
death.
Page 5
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock or fire may result.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric
shock.
• The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. (for R32)
• The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.)
• Keep any required ventilation openings clear of obstruction.
• Mechanical connections shall be accessible for maintenance purposes.
• To prevent the mixing of different types of refrigerants, be sure to check the type of refrigerant used in the outdoor unit.
Operation
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
Page 6
6
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Take care to ensure that power cable could not be pulled out or damaged during operation.
- There is risk of fire or electric shock.
• Do not place anything on the power cable.
- There is risk of fire or electric shock.
• Do not plug or unplug the power supply plug during operation.
- There is risk of fire or electric shock.
• Do not touch(operate) the product with wet hands.
- There is risk of fire or electrical shock.
• Do not place a heater or other appliances near the power cable.
- There is risk of fire and electric shock.
• Do not allow water to run into electric parts.
- There is risk of fire, failure of the product, or electric shock.
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
• Do not use the product in a tightly closed space for a long time.
- Oxygen deficiency could occur.
• When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
- Do not use the telephone or turn switches on or off. There is
risk of explosion or fire.
• If strange sounds, smell or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
- There is risk of electric shock or fire.
• Stop operation and close the window in storm or hurricane. If possible, remove the product from the window before the hurricane arrives.
- There is risk of property damage, failure of product, or electric
shock.
Page 7
IMPORTANT SAFETY INSTRUCTIONS
7
ENGLISH
• Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product
failure.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Ventilate the product from time to time when operating it together with a stove, etc.
- There is risk of fire or electric shock.
• Turn the main power off when cleaning or maintaining the product.
- There is risk of electric shock.
• When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
- There is risk of product damage or failure, or unintended
operation.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
• When mechanical connectors are reused indoors, sealing parts shall be renewed. (for R32)
• When flared joints are reused indoors, the flare part shall be re­fabricated. (for R32)
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.
• Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
• Do not pierce or burn refrigerant cycle part.
Page 8
8
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Be aware that refrigerants may not contain an odour.
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly
on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
• Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification. (for R32)
• The appliance shall be stored so as to prevent mechanical damage from occurring.
• Refrigerant tubing shall be protected or enclosed to avoid damage.
!
Page 9
IMPORTANT SAFETY INSTRUCTIONS
9
ENGLISH
• Flexible refrigerant connectors (such as connecting lines between the indoor and outdoor unit) that may be displaced during normal operations shall be protected against mechanical damage.
• The installation of pipe-work shall be kept to a minimum.
• Pipe-work shall be protected from physical damage.
• A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts.
• Dismantling the unit, treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards.
Operation
• Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.)
- This could harm to your health.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow.
- It may cause product failure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
- There is risk of fire, electric shock, or damage to the plastic
parts of the product.
• Do not touch the metal parts of the product when removing the air filter. They are very sharp!
- There is risk of personal injury.
Page 10
10
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Do not step on or put anything on the product. (outdoor units)
- There is risk of personal injury and failure of product.
• Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
- A dirty filter reduces the efficiency of the air conditioner and
could cause product malfunction or damage.
• Do not insert hands or other objects through the air inlet or outlet while the product is operated.
- There are sharp and moving parts that could cause personal
injury.
• Do not drink the water drained from the product.
- It is not sanitary and could cause serious health issues.
• Use a firm stool or ladder when cleaning or maintaining the product.
- Be careful and avoid personal injury.
• Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
- There is risk of fire or explosion.
• Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
- They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
- The chemicals in batteries could cause burns or other health
hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked.
- The chemicals in batteries could cause burns or other health
hazards.
Page 11
IMPORTANT SAFETY INSTRUCTIONS
11
ENGLISH
• Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. (for R32)
• Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Page 12
12
TABLE OF CONTENTS
ENGLISH
2 TIPS FOR SAVING ENERGY 3 IMPORTANT SAFETY INSTRUCTIONS 13 INSTALLATION PARTS 13 INSTALLATION TOOLS 14 INSTALLATION MAP 15 INSTALLATION
15 Select the best Location 17 Drill a Hole in the Wall 17 Fixing Installation Plate 18 Flaring Work 19 Connecting the Piping 23 Checking the Drainage 25 Manual the decor, air filter Assembly & Disassembly 26 Wiring Connection 28 DIP Switch Setting 29 Group Control Setting 34 Model Designation 34 Airborne Noise Emission 34 Limiting concentration
TABLE OF CONTENTS
Page 13
INSTALLATION PARTS
13
ENGLISH
INSTALLATION TOOLS
Cloth tape is not attached to the product.
INSTALLATION PARTS
Name
Installation plate
Quantity Shape
1 EA
SJ SK
Drain hose
Type "A" screw
Type "C" screw
Cloth tape
1 EA
5 EA
2 EA
1 EA
Figure FigureName
Screw driver
Name
Multi-meter
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
Hexagonal wrench
Ammeter
Gas-leak detector
Thermometer,
Level
Flaring tool set
Page 14
14
INSTALLATION MAP
ENGLISH
INSTALLATION MAP
Remote Controller
(Accessory)
Vinyl tape (Wide)
• Apply after carrying out a drainage test.
• To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Saddle
Installation plate Sleeve Bushing-Sleeve
Putty(Gum Type Sealant)
Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.
NOTE
!
• You should purchase the installation parts.
* The feature can be changed according to type of model.
Page 15
INSTALLATION
15
ENGLISH
Select the best Location
- There should not be any heat or steam near the unit.
- Select a place where there are no obstacles around of the unit.
- Make sure that condensation drainage can be conveniently routed away.
- Do not install near a doorway.
- Ensure that the interval between a wall and the left (or right) of the unit is more than 100 mm. The unit should be installed as high as possible on the wall, allowing a minimum of 200 mm from ceiling.
- Use a metal detector to locate studs to prevent unnecessary damage to the wall.
* The feature can be changed according to
type of model.
CAUTION
!
Install the indoor unit on the wall where the height from the floor is more than 2 300 mm.
INSTALLATION
More than
100
More than 2 300
More than 200
More than
100
(Unit : mm)
Page 16
16
INSTALLATION
ENGLISH
- The appliance shall be installed, operated and stored in a room with a floor area larger than the minimum area.
- Use the graph of table to determine the minimum area.
- m : Total refrigerant amount in the system
- Total refrigerant amount : factory refrigerant charge + additional refrigerant amount
- Amin : minimum area for installation
Minimum floor area (for R32)
Floor location
m (kg) Amin (m
2
)
< 1.224
-
1.224 12.9
1.4 16.82
1.6 21.97
1.8 27.80 2 34.32
2.2 41.53
2.4 49.42
2.6 58.00
2.8 67.27 3 77.22
3.2 87.86
3.4 99.19
3.6 111.20
3.8 123.90 4 137.29
4.2 151.36
4.4 166.12
Floor location
m (kg) Amin (m
2
)
4.6 181.56
4.8 197.70 5 214.51
5.2 232.02
5.4 250.21
5.6 269.09
5.8 288.65 6 308.90
6.2 329.84
6.4 351.46
6.6 373.77
6.8 396.76 7 420.45
7.2 444.81
7.4 469.87
7.6 495.61
7.8 522.04
Wall mounted
m (kg) Amin (m
2
)
< 1.224
-
1.224 1.43
1.4 1.87
1.6 2.44
1.8 3.09 2 3.81
2.2 4.61
2.4 5.49
2.6 6.44
2.8 7.47 3 8.58
3.2 9.76
3.4 11.02
3.6 12.36
3.8 13.77 4 15.25
4.2 16.82
4.4 18.46
Wall mounted
m (kg) Amin (m
2
)
4.6 20.17
4.8 21.97 5 23.83
5.2 25.78
5.4 27.80
5.6 29.90
5.8 32.07 6 34.32
6.2 36.65
6.4 39.05
6.6 41.53
6.8 44.08 7 46.72
7.2 49.42
7.4 52.21
7.6 55.07
7.8 58.00
Ceiling Mounted
m (kg) Amin (m
2
)
< 1.224
-
1.224 0.956
1.4 1.25
1.6 1.63
1.8 2.07 2 2.55
2.2 3.09
2.4 3.68
2.6 4.31
2.8 5.00 3 5.74
3.2 6.54
3.4 7.38
3.6 8.27
3.8 9.22 4 10.21
4.2 11.26
4.4 12.36
Ceiling Mounted
m (kg) Amin (m
2
)
4.6 13.50
4.8 14.70 5 15.96
5.2 17.26
5.4 18.61
5.6 20.01
5.8 21.47 6 22.98
6.2 24.53
6.4 26.14
6.6 27.80
6.8 29.51 7 31.27
7.2 33.09
7.4 34.95
7.6 36.86
7.8 38.83
Amin (m2)
600
500
400
300
200
100
0
0 1.224 2 3 4 5 6 7 8
Floor standing
Wall mounted Ceiling mounted
m (kg)
Page 17
INSTALLATION
17
ENGLISH
Fixing Installation Plate
The wall you select should be strong and solid enough to prevent vibration
1 Mount the installation plate on the wall
with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
- Mount the installation plate horizontally by aligning the centerline using Horizontal meter.
2 Measure the wall and mark the centerline.
It is also important to use caution concerning the location of the installation plate. Routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
Tubatura posteriore sinistra
Ø 65
Ø 65
83
Measuring
Tape
Measuring Tape
Hanger
83
Right rear piping
Place a level on raised tab
Unit Outline
(Unit : mm)
494 504
134
150
Ø 65
152
98 134
194
Ø 65
Right rear piping
Left rear piping
Place a level on raised tab
Unit Outline
(Unit : mm)
418 418
Installation Plate
Drill a Hole in the Wall
- Drill the piping hole with a ø 65 mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
WALL
Indoor
Outdoor
5-7 mm
(3/16"~5/16")
Page 18
18
INSTALLATION
ENGLISH
Flaring Work
Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure.
1 Use the piping kit accessory or the pipes
purchased locally.
2 Measure the distance between the indoor
and the outdoor unit.
3 Cut the pipes a little longer than measured
distance.
4 Cut the cable 1.5 m longer than the pipe
length.
1 Completely remove all burrs from the cut
cross section of pipe/tube.
2 While removing burrs put the end of the
copper tube/pipe in a downward direction while removing burrs location is also changed in order to avoid dropping burrs into the tubing.
- Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after finishing flare work)
1 Firmly hold copper pipe in a bar with the
dimension shown in below table table below.
2 Carry out flaring work with the flaring tool.
Cut the pipes and the cable
Burrs removal
Putting nut on
Flaring work
Pipe
Reamer
Point down
Pipe diameter
inch (mm)
A inch (mm)
Wing nut type Clutch type
Ø 1/4 (Ø 6.35) 0.04~0.05 (1.1~1.3)
0~0.02 (0~0.5)
Ø 3/8 (Ø 9.52) 0.06~0.07 (1.5~1.7) Ø 1/2 (Ø 12.7) 0.06~0.07 (1.6~1.8)
Ø 5/8 (Ø 15.88) 0.06~0.07 (1.6~1.8)
Ø 3/4 (Ø19.05) 0.07~0.08 (1.9~2.1)
CAUTION
!
(for R32)
• When mechanical connectors are reused indoors, sealing parts shall be renewed.
• When flared joints are reused indoors, the flare part shall be re-fabricated.
Copper
pipe
90°
Slanted Uneven Rough
Flare nut
Copper tube
Page 19
INSTALLATION
19
ENGLISH
1 Compare the flared work with the figure
by.
2 If a flared section is defective, cut it off
and do flaring work again.
Connecting the Piping
1 Pull the cover at the bottom of the indoor
unit. Pull the cover ① → ②.
2 Remove the cover from the indoor unit.
3 Pull back the tubing holder. 4 Remove pipe port cover and positioning
the tubing
* The feature can be changed according to
type of model.
1 Insert 3 hooks of the chassis cover into
gap of the chassis certainly.
2 Push the hooks to assemble chassis
cover. Push the chassis cover ① → ②.
Check
Assembly of chassis cover
Bar
Copper pipe
<Wing nut type>
"A"
<Clutch type>
Smooth all round
Even length
all round
Inside is shiny without scratches
= Improper flaring =
Surface
damaged
Cracked Uneven
Inclined
thickness
Indoor unit back side view
Right
Downwards
Tubing holder
Left
Backwards
ڹ
ڸ
ڸ
ڸ
ڹ
ڹ
ڸ
ڸ
ڸ
ڸ
ڹ
Page 20
20
INSTALLATION
ENGLISH
- Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly.
* The feature can be changed according to
type of model.
- Following bending case from right to left directly may cause damage to the tubing.
* The feature can be changed according to
type of model.
Good case
Bad case
CAUTION
!
Installation Information. For right piping. Follow the instruction above.
Page 21
INSTALLATION
21
ENGLISH
Installation of Indoor Unit
1 Hook the indoor unit onto the upper
portion of the installation plate. (engage the three hooks at the top of the indoor unit with the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left and right
2 Unlock the tubing holder from the chassis
and mount between the chassis and installation plate in order to separate the bottom side of the indoor unit from the wall.
* The feature can be changed according to
type of model.
Piping
1 Insert the connecting cable through the
bottom side of indoor unit and connect the cable (You can see detail contents in 'Connecting the cables' section)
<Left side piping>
<Right side piping>
2 Secure the cable onto the control board
with the cable retainer.
3 Tape the tubing pipe, drain hose and the
connection cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause overflow from the drain pan through the inside of the unit.
<Left side piping>
<Right side piping>
* The feature can be changed according to
type of model.
Installation plate
Tubing Holder
View
Terminal block of indoor unit
1(L) 2(N) 3(A) 4(B)
Indoor power input
Slide up the metal plate cover
Outdoor unit
View
Terminal block of indoor unit
1(L) 2(N) 3(A) 4(B)
Indoor power input
Slide up the metal plate cover
Outdoor unit
Tape
Connecting cable
Drain hose
Drain hose
Connecting pipe
Tape
Connecting cable
Drain hose
Connecting pipe
Page 22
22
INSTALLATION
ENGLISH
1 Align the center of the pipes and
sufficiently tighten the flare nut by hand
2 Tighten the flare nut with a wrench
3 When needed to extend the drain hose of
indoor unit, assembly the drain pipe as shown on the drawing
Wrap the insulation material around the connecting portion.
1 Overlap the connection pipe insulation
material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.
2 Set the tubing cutting line upward.
Wrap the area which accommodates the rear piping housing section with vinyl tape.
3 For left rear piping, bundle the piping and
drain hose together by wrapping them cloth tape over the range within which they fit into the rear piping housing section.
* Wrap the piping of the indoor unit that are
visible from the outside with vinyl tape.
CAUTION
!
If the drain hose is routed inside the room insulate the hose with an insulation material* so that dripping from sweating condensation) will not damage furniture or floors.
* Foamed polyethylene or equivalent is
recommended.
Outside diameter
Torque
Connecting the installation pipe and drain hose to the indoor unit.
mm inch kgf.m Ø 6.35 1/4 1.8~2.5 Ø 9.52 3/8 3.4~4.2 Ø 12.7 1/2 5.5~6.5
Ø 15.88 5/8 6.3~8.2 Ø 19.05 3/4 9.9~12.1
Gas Pipe
Liquid Pipe
Cutting Line
Cutting Line
Good Case Bad Case
* Tubing cutting line have to be upward.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Indoor unit tubing Flare nut Pipes
Insulation material
Torque wrench
Indoor unit tubing
Drain pipe
Adhesive
Open-end wrench (fixed)
Flare nut
Connection pipe
Indoor unit drain hose
Vinyl tape(narrow)
Wrap with cloth tape
Pipe
Cloth tape
Drain hose
Page 23
INSTALLATION
23
ENGLISH
Finishing the indoor unit installation
1 Mount the tubing holder in the original
position.
2 Ensure that the hooks are properly seated
on the installation plate by moving it left and right.
3 Press the lower left and right sides of the
unit against the installation plate until the hooks engage into their slots (clicking sound).
4 Finish the assembly by screwing the unit
to the installation plate by using two pieces of type "C" screws. And assemble a chassis cover.
Checking the Drainage
To check the drainage
1 Pour a glass of water on the evaporator. 2 Ensure the water flows through the drain
hose of the indoor unit without any leakage and goes out the drain exit.
Drain piping
1 The drain hose should point downward for
easy drain flow.
Downward slope
Connecting area
drain hose
Leakage
checking
Drain pan
Drain
hose Leakage checking
Type 'C' screw
Page 24
24
INSTALLATION
ENGLISH
2 Do not make drain piping like the
following.
* The feature can be changed according to
type of model.
Do not raise
Water leakage
Accumulated drain water
Air
Waving
Water leakage
Tip of drain hose dipped in water
Water leakage
Ditch
Less than 50 mm gap
Page 25
INSTALLATION
25
ENGLISH
Manual the decor, air filter Assembly & Disassembly
Page 26
26
INSTALLATION
ENGLISH
Wiring Connection
- Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
- Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Resistance measurement position for incorrect wiring.
CAUTION
!
The Power cord connected to the unit should be selected according to the following specifications.
CAUTION
!
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (This equipment shall be provided with a cable set complying with the national regulation).
If the supply cable is damaged, it must be replaced by a special cable or assembly available from the manufacturer of its service agent.
WARNING
!
Make sure that the screws of the terminal are free from looseness.
SJ/SK
Terminal block of indoor unit
1(L) 2(N) 3(A) 4(B)
Indoor power input
Outdoor unit
SODU SODU
Terminal block of outdoor unit
Indoor unit
IDU IDU
Central controller
INTERNET
DRY1
10±3 mm
NORMAL CROSS-SECTIONAL AREA 0.75 mm
DRY2
GN/YL
GND
35±5 mm
2
12 V
20 mm
Page 27
INSTALLATION
27
ENGLISH
CAUTION
!
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
- Vibration of a magnetic switch, damage on the contact point there of, fuse breaking,
disturbance to the normal function of a overload protection device.
- Proper starting power is not given to the compressor.
10) Before applying power to the indoor unit, be sure to check for incorrect wiring of the power
and communication lines.
CAUTION
!
Be sure to test the power line and communication line for incorrect wiring before power is applied.
1) If the power line and communication line are swapped over, the product will be damaged.
2) Incorrect wiring confirmation test method : Measure the resistance across the power terminals (L,N) using a multi meter.
- Resistance value of a normal connection: 1 or more
- Incorrect wiring resistance value: 500 or less
Page 28
DIP Switch Setting
Indoor Unit
Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function can start automatically with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.
* Specific conditions:
- All names of the indoor units are ARNU****4
- The serial number of Multi V super IV (outdoor units) is after October 2013,
28
ENGLISH
INSTALLATION
CAUTION
!
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Function Description Setting Off Setting On Default
SW1 Communication N/A (Default) - - Off
SW2 Cycle N/A (Default) - - Off
SW3 Group Control
Selection of Master or Slave
Master Slave Off
SW4
Dry Contact Mode
Selection of Dry Contact Mode
Wired/Wireless remote
controller
Selection of Manual or
Auto operation Mode
Auto
Off
SW5 Installation
Fan continuous operation
Continuous operation
Removall
- Off
SW6 Heater linkage N/A - - Off
SW7
Ventilator linkage
Selection of Ventilator linkage
Linkage Removal
Working
Off
Vane selection (Console)
Selection of up/down side Vane
Up side + Down side
Vane
Up side Vane
Only
Region selection
Selection tropical region
General model Tropical model
SW8 Etc. Spare - - Off
Outdoor Unit PCB Outdoor Unit DIP Switch
DIP switch 7 segment
Page 29
29
ENGLISH
INSTALLATION
Group Control Setting
Group Control 1
n Wired remote controller 1 + Standard Indoor Units
Some products have no DIP switch on PCB. It is possible to set indoor units to Master or Slave by using the wireless remote controller instead of DIP switch.
For the details of the setting, please refer to the manual of the wireless remote controller.
1. It is possible to 16 indoor units(Max.) by one wired remote controller. Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired remote controller. It is possible to control the other indoor units except the error units.
n DIP Switch in PCB
GND Signal 12 V
Master Slave Slave Slave
Display Error Message
Only connect serial signal and
GND lines between indoor units.
or
LGAP Network System
Master
°C / °F (5 s)°C / °F (5 s)
TIME (3 s)TIME (3 s)
Master Setting
- No. 3 Off
Slave Setting
- No. 3 On
Indoor Unit DIP Switch
Page 30
30
ENGLISH
INSTALLATION
GND Signal 12 V
Slave
Slave
Master
or
Donʼt connect serial 12 V line
LGAP Network System
Master
MasterMaster
Display Error Message
°C / °F (5 s)°C / °F (5 s)
TIME (3 s)TIME (3 s)
Group Control 2
n Wired remote controllers + Standard Indoor Units
* It is possible to connect indoor units since Feb. 2009. * It can be the cause of malfuctions when there is no setting of master and slave. * In case of Group Control, it is possible to use following functions.
- Selection of operation, stop or mode
- Temperature setting and room temperature check
- Current time change
- Control of flow rate (High/Middle/Low)
- Reservation settings
- It is not possible at some functions.
* It is possible to control 16 indoor units(Max.) with the master wired remote control.
* Other than those, it is same with the Group Control 1.
Page 31
31
ENGLISH
INSTALLATION
°C / °F (5 s)
TIME (3 s)
Group Control 3
n Mixture connection with indoor units and Fresh Air Intake Unit
* In case of connecting with standard indoor unit and Fresh Air Intake Unit, separate Fresh Air
Intake Unit with standard units. (N, M 16) (Because setting temperature are different.)
* Other than those, it is same with Group Control 1.
or
FAU
Master
Display Error Message
°C / °F (5 s)
TIME (3 s)
Master
FAU
Slave
Master
N
Master
LGAP Network System
Slave
Display Error Message
M
FAU
FAU FAU
Standard Standard
Standard
FAU
Standard
GND Signal 12 V
* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit
Page 32
32
ENGLISH
2 Remote Control
n Wired remote controller 2 + Indoor unit 1
INSTALLATION
°C / °F (5 s)
TIME (3 s)
1. It is possible to connect two wired remote controllers (Max.) with one indoor unit. Set only one indoor unit to Master, set the others to Slave. Set only one wired remote controller to Master, set the others to Slave.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired remote controller.
6. There isn't limits of indoor unit function.
or
Master
°C / °F (5 s)
TIME (3 s)
Display Error Message
Master
Slave
Slave
Slave
LGAP Network System
Slave
GND Signal 12 V
Page 33
33
ENGLISH
INSTALLATION
Accessories for group control setting
It is possible to set group control by using below accessories.
Indoor unit 2 EA +Wired remote controller Indoor unit 1 EA +Wired remote controller 2 EA
* PZCWRCG3 cable used for connection * PZCWRC2 cable used for connection
CAUTION
!
Apply totally enclosed noncombustible conduit in case of local building code Requiring plenum cable usage.
PZCWRCG3
Master
Slave
PZCWRC2
Master Slave
Master
Page 34
The A-weighted sound pressure emitted by this product is below 70 dB. ** The noise level can vary depending on the site. The figures quoted are emission level and are not necessarily safe working levels. Whilst there is
a correlation between the emission and exposure levels, this cannot be used reliably to determine whether or not further precautions are required. Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the number of equipment and other adjacent processes and the length of time for which an operator exposed to the noise. Also, the permissible exposure level can vary from country to country. This information, however, will enable the user of the equipment to make a better evaluation of the hazard and risk.
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the unit of kg/m3(Freon gas weight per unit air volume) for facilitating calculation
n Calculate refrigerant concentration
Refrigerant concentration =
Total amount of replenished refrigerant in refrigerant facility (kg)
Capacity of smallest room where indoor unit is installed (m
3
)
Limiting concentration: 0.44 kg/m3(R410A)
Limiting concentration
34
INSTALLATION
ENGLISH
Airborne Noise Emission
Model Designation
ARN U G15 ASJ 4
Serial Number Combinations of functions
A:Basic function L: Neo Plasma(Wall Mounted) N/C : Ionizer
Chassis Name Electrical Ratings
1 : 1Ø, 115 V, 60 Hz 6 : 1Ø, 220 - 240 V, 50 Hz 3 : 1Ø, 208/230 V, 60 Hz
Total Cooling Capacity in Btu/h EX) 5 000 Btu/h '05' 18 000 Btu/h '18'
Combination of Inverter Type and Cooling Only or Heat Pump N: AC Inverter and H/P V: AC Inverter and C/O U: DC Inverter and H/P and C/O
System with Indoor Unit using R32/R410A
LGETA:U Ex) URN
2 : 1Ø, 220 V, 60 Hz 7 : 1Ø, 100 V, 50/60 Hz
1Ø, 220 - 240 V, 50 Hz/1Ø, 220 V, 60 Hz
G :
Page 35
Loading...