LG AMNC093APM0, A3UH363FA0, AMNC123APM0, AMNH093APM0, AMNH123DEA0 User Manual 2

...
LG
Multi Type Air Conditioner
SERVICE MANUAL
LG
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
MODEL
• Indoor Unit:
• Outdoor Unit: A3UH363FA0(LMU360HE) A3UC363FA0(LMU360CE)
Room Type
AMNH093D4A0(LMN090HE) AMNC093D4A0(LMN090CE) AMNH123DEA0(LMN120HE) AMNC123DEA0(LMN120CE)
AMNH093APM0(LMAN090HNS) AMNC093APM0(LMAN090CNS) AMNH123APM0(LMAN120HNS) AMNC123APM0(LMAN120CNS)
Art Cool Type
2 Multi type Air Conditioner
Multi type Air Conditioner Service Manual
TABLE OF CONTENTS
Model Number Nomenclature....................................................................................................................3
Symbols Used in this Manual...................................................................................................................4
Safety Precautions......................................................................................................................................5
Dimensions................................................................................................................................................11
Indoor Unit.............................................................................................................................................11
Outdoor Unit...........................................................................................................................................12
Product Specifications.............................................................................................................................13
Installation.................................................................................................................................................15
Installation Parts.....................................................................................................................................15
Installation Tools.....................................................................................................................................15
Select the best location .........................................................................................................................16
Piping length and elevation....................................................................................................................17
Fixing Installation Plate(Standart Type)..................................................................................................18
Preparing work for Installation (Artcool Type Only) ................................................................................19
Flaring Work and Connection of Piping..................................................................................................21
Flaring work............................................................................................................................................21
Connecting the Piping............................................................................................................................22
Connecting the Cable between Indoor Unit and Outdoor Unit.............................................................30
Connect the cable to the Indoor unit. .....................................................................................................30
Connect the cable to the Outdoor unit....................................................................................................31
Connection method of the connecting cable(Example)..........................................................................32
Connect the cable to the indoor unit.......................................................................................................33
Checking the Drainage, Forming the Pipings and Long Pipe Setting .................................................34
Checking the drainage............................................................................................................................34
Forming the piping..................................................................................................................................35
Air Purging and Evacuation.....................................................................................................................36
Checking method ...................................................................................................................................36
Evacuation..............................................................................................................................................37
Charging ....................................................................................................................................................38
Test Running.............................................................................................................................................39
Operation...................................................................................................................................................40
Function of control..................................................................................................................................40
Function of Indoor Unit...........................................................................................................................45
Function of Outdoor Unit........................................................................................................................47
Remote Control Operation .....................................................................................................................48
Disassembly..............................................................................................................................................49
Indoor Unit..............................................................................................................................................49
Schematic Diagram...................................................................................................................................54
Electronic Control Device.......................................................................................................................54
Wiring Diagram.......................................................................................................................................58
Components Locations...........................................................................................................................59
Troubleshooting Guide.............................................................................................................................64
Refrigeration Cycle Diagram..................................................................................................................64
Self-diagnosis Function..........................................................................................................................65
Cycle Troubleshooting Guide..................................................................................................................66
Electronic Parts Troubleshooting Guide.................................................................................................67
General Information................................................................................................................................72
2-way, 3-way Valve....................................................................................................................................78
Exploded View & Replacement Parts List ..............................................................................................82
Indoor Unit .............................................................................................................................................82
Outdoor Unit ..........................................................................................................................................86
Service Manual 3
Model Number Nomenclature
Model Number Nomenclature
Indoor Unit
Outdoor Unit
AMN H 3
09
4DA0
Serial Number
A3U H 336 F A 0
Electrical Ratings
MPS Variable Multi System Indoor Unit
Model Type
H: Heat Pump C: Cooling Only
Ex) 9,000 Btu/h '09', 12,000 Btu/h '12'
Nominal Cooling Capacity in Btu/h
Electrical Rating
3: 1Ø, 208~230V, 60Hz
Chassis Name Indoor Unit Type
Wall mounted split
D : D- look type L : L- look type G : G- look type M : M- look type N : N- look type
Artcool type
A : standard/wide type D : Deluxe type
B : Ceiling Concealed Duct V : Ceiling & Floor(Convertible)
Function
A : Basic, L : Nano Plasma + Auto Clean(Wall Mounted) C: Plasma(Ceiling Cassette), G: Low Static Motor
ART COOL(DELUXE) Type Front Panel Color
B : Blue, D : Wood, M : Metal, R : Mirror, W : White
R-410A MPS Variable Multi System Outdoor Unit And No. of Connectable Indoor Units
Ex) A3U : Connectable max. 2 Indoor Units
Model Type
H: Heat Pump C: Cooling Only
Ex) 24,000 Btu/h '24', 36,000 Btu/h '36'
Nominal Cooling Capacity in Btu/h
3: 1Ø, 208~230V, 60Hz
Multi Type
Function
A : Basic
F : Free Joint Multi Type
Serial Number
4 Multi type Air Conditioner
Model Number Nomenclature
Combination table
A B C Total Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Total (Btu/h.w) (w/w) 9 9 9000 9000 1320 5.9 6.8 9000 9000 1550 7.0 5.8 1.7
12 12 12000 12000 1320 5.9 9.1 12000 12000 1410 6.3 8.5 2.5
9 9 18 9000 9000 18000 2180 9.8 8.3 9000 9000 18000 2160 9.8 8.3 2.4 9 12 21 9000 12000 21000 2200 9.9 9.5 9000 12000 21000 2160 9.8 9.7 2.8
12 12 24 12000 12000 24000 2200 9.9 10.9 12000 12000 24000 2160 9.8 11.1 3.3
9 9 9 27 9000 9000 9000 27000 3650 16.5 7.4
9000 9000 9000 27000 3300 14.9 8.2 2.4
9 9 12 30 9000 9000 12000 30000 3650 16.5 8.2
9000 9000 12000 30000 3340 15.0 9.0 2.6
9 12 12 33 9000 12000 12000 33000 3650 16.5 9.0
9000 12000 12000 33000 3340 15.0 9.9 2.9
12 12 12 36 12000 12000 12000 36000 3680 16.6 9.8
12000 12000 12000 36000 3340 15.0 10.8 3.2
1 UNIT
COP
Operation
Combination(k Btu)
Cooling
2 UNIT
3 UNIT
Heating
Capacity (Btu/h)
Input
(W)
Current
(A)
EER
(Btu/h.w)
Capacity (Btu/h)
Input
(W)
Current
(A)
Notes :
1.Cooling Capacity is based on : indoor temp. 26.7°C(80.1°F)DB, 19.4°C(66.9°F)WB; outdoor temp. 35°C(95°F)DB, 23.9°C(75°F)WB
2.Heating Capacity is based on : indoor temp. 21.1°C(70°F)DB, 15.6°C(60.1°F)WB; outdoor temp. 8.3°C(46.9°F)DB, 6.1°C(43°F)WB
3.The total ability of connected a indoor unit is up to 24k Btu/h
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Service Manual 5
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the follo wing instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
WARNING
Installation
Be sure not to do.
Be sure to follow the instruction.
Do not use a defective or under­rated circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center
.
Do not disassemble or repair the product. There is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire or electric shock.
Always install a dedicated cir­cuit and breaker.
Improper wiring or installation may cause fire or electric shock
Use the correctly rated break­er or fuse.
There is risk of fire or electric shock.
WARNING
CAUTION
6 Multi type Air Conditioner
Safety Precautions
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
Sharp edges could cause injury. Be especially careful of the case edges and the fins on the con­denser and evaporator.
For installation, always con­tact the dealer or an Authorized Service Center.
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air condi­tioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power cable.
There is risk of fire or electric shock.
Service Manual 7
Safety Precautions
Do not allow water to run into electric parts.
It may cause There is risk of fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustibles near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off. There is risk of explosion or fire
If strange sounds, or small or smoke comes from product. Turn the breaker off or discon­nect the power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or hurricane. If possible, remove the prod­uct from the window before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
Do not touch(operate) the product with wet hands.
There is risk of fire or electrical shock.
Do not place a heater or other appliances near the power cable.
There is risk of fire and electric shock.
Gasolin
8 Multi type Air Conditioner
Safety Precautions
Do not open the inlet grill of the product during operation. (Do not touch the elec­trostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
There is risk of fire or electric shock.
Be cautious that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
When the product is not be used for a long time, dis­connect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintend­ed operation.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product dam­age.
Always check for gas (refrigerant) leak­age after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration or water leak­age.
CAUTION
Installation
90°
Service Manual 9
Safety Precautions
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, sol­vents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of personal injury.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.)
This could harm to your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
There is risk of damage or loss of property.
Operational
Wax
Thinner
10 Multi type Air Conditioner
Safety Precautions
Do not step on or put anyting on the product. (outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter secure­ly. Clean the filter every two weeks or more often if neces­sary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or dam­age.
Do not insert hands or other objects through the air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the product.
It is not sanitary and could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or dif­ferent types of batteries.
There is risk of fire or explosion
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn or explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
The chemicals in batteries could cause burns or other health hazards.
Service Manual 11
Dimensions
Dimensions
Indoor Unit
1. Split Type Indoor 2. Art Cool Type Indoor Unit
Pipe Hole
Fix Hole
Hanger Hole
H
W
D
Installation plate
D
H
W
W mm 840 895 570
H mm 270 282 568 D mm 153 165 129
Model
Dimension
Split Type ARTCOOL Type
S4 SE
9 kBtu/h 12 kBtu/h 9 kBtu/h 12 kBtu/h
SP3
12 Multi type Air Conditioner
Outdoor Unit
L6L7 L8
L9
L4
H
L5
W
D
L1
L3
L2
L10 L11L11 L11L11L11
Gas side 3-way valve
Liquid side 2-way valve
Dimensions
UE2 36k
MODEL
DIM
W mm 870
H mm 1038
D mm 320 L1 mm 360 L2 mm 340 L3 mm 25 L4 mm 1035 L5 mm 25 L6 mm 546 L7 mm 160 L8 mm 160 L9 mm 44
L10 mm 64.5 L11 mm 50
Service Manual 13
Product Specifications
Product Specifications
Indoor Unit
Nominal Cooling Capacity kcal/h(W)
Btu/h
Nominal Heating Capacity kcal/h(W)
Btu/h Air Circulation H/M/L CMM(CFM) Setting temperature range(cool/heat) °C Fan motor Output W
Model Input V Running Current A
Fan Type
No. Used / Diameter EA/inch(mm)
Noise Level (Sound Press,1m)
H/M/L dBA Temperature controller Coil Tube Size (OD) inch(mm)
Fins per inch
No. of Rows & Column Dehumidification Rate l/h Dimensions (W*H*D) inch(mm) Net Weight kg(lbs) Piping Connection Liquid inch(mm)
Gas inch(mm)
Drain hose (ID Ø)mm Packing Dimension (W*H*D) inch(mm) Stuffing Quantity With(Without) S/Parts 20/40ft(hi-c)
Wall Mounted
AMNC093D4A0(LMN090CE)
AMNH093D4A0(LMN090HE) AMNC123DEA0(LMN120CE) AMNH123DEA0(LMN120HE)
Indoor Unit Type
Model
Note : 1.★See the page "Combination Table"
2. Due to our policy of innovation some specifications may be changed without notification.
2,267(2,637) 2,267(2,637) 3,023(3,516) 3,023(3,516)
9,000 9,000 12,000 12,000
- 2,267(2,637) - 3,023(3,516)
- 9,000 - 12,000
8.2(289) 8.2(289) 9.4(332) 9.4(332) 18~30 16~30 18~30 16~30
15 15 15 15
DL-88430LGIF DL-88430LGIF DL-88430LGIF DL-88430LGIF
DC36 DC36 DC36 DC36
0.15 0.15 0.15 0.15
Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan
1/3.74(95) 1/3.74(95) 1/3.74(95) 1/3.74(95) 31 / 29 / 22 31 / 29 / 22 36 / 32 / 29 36 / 32 / 29 Thermistor Thermistor Thermistor Thermistor
0.197(5.0) 0.197(5.0) 0.197(5.0) 0.197(5.0) 20 20 18 18
2R,15C 2R,15C 2R,15C 2R,15C
- 1.1 - 1.2
33.0*10.6*6.0(840*270*153) 33.0*10.6*6.0(840*270*153) 35.2*11.1*6.5(895*282*165) 35.2*11.1*6.5(895*282*165) 7(15.4) 7(15.4) 9.5(20.9) 9.5(20.9)
1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
20 20 20 20
35.7*13.1*8.8(906*332*223) 35.7*13.1*8.8(906*332*223) 38.3*9.1*14.6(973*231*372) 38.3*9.1*14.6(973*231*372)
440/910 (1091) 440/910 (1091) 353/719 (792) 353/719 (792)
2,267(2,637) 2,267(2,637) 3,023(3,516) 3,023(3,516)
9,000 9,000 12,000 12,000
- 2,267(2,637) - 3,023(3,516)
- 9,000 - 12,000
7.5(264) 7.5(264) 8.5(300) 8.5(300) 18~30 16~30 18~30 16~30
24 24 24 24
DL-89812LGIB DL-89812LGIB DL-89812LGIB DL-89812LGIB
DC36 DC36 DC36 DC36
1.5 1.5 1.5 1.5
Turbo Fan Turbo Fan Turbo Fan Turbo Fan
1/24.32(617.7) 1/24.32(617.7) 1/24.32(617.7) 1/24.32(617.7)
37 / 31 / 27 37 / 31 / 27 43 / 39 / 31 43 / 39 / 31 Thermistor Thermistor Thermistor Thermistor
0.197(5.0) 0.197(5.0) 0.197(5.0) 0.197(5.0) 20 20 20 20
2R,20C 2R,20C 2R,20C 2R,20C
- 1.1 - 1.4
22.4*22.4*5.1(570*568*129) 22.4*22.4*5.1(570*568*129) 22.4*22.4*5.1(570*568*129) 22.4*22.4*5.1(570*568*129) 9(19.84) 9(19.84) 9(19.84) 9(19.84)
1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
20 20 20 20
26.2*25.7*9.1(665*653*231) 26.2*25.7*9.1(665*653*231) 26.2*25.7*9.1(665*653*231) 26.2*25.7*9.1(665*653*231)
237/534(239/539) 237/534(239/539) 237/534(239/539) 237/534(239/539)
Nominal Cooling Capacity kcal/h(W)
Btu/h
Nominal Heating Capacity kcal/h(W)
Btu/h Air Circulation H/M/L CMM(CFM) Setting temperature range(cool/heat) °C Fan motor Output W
Model No. of Poles Input V Running Current A
Fan Type
No. Used / Diameter EA/inch(mm)
Noise Level (Sound Press,1m)
H/M/L dBA Temperature controller Coil Tube Size (OD) inch(mm)
Fins per inch
No. of Rows & Column Dehumidification Rate l/h Dimensions (W*H*D) inch(mm) Net Weight kg(lbs) Piping Connection Liquid inch(mm)
Gas inch(mm)
Drain hose (ID Ø)mm Packing Dimension (W*H*D) inch(mm) Stuffing Quantity With(Without) S/Parts 20/40ft(hi-c)
Artcool
AMNC093APM0(LMAN090CNS) AMNH093APM0(LMAN090HNS) AMNC123APM0(LMAN120CNS) AMNH123APM0(LMAN120HNS)
Indoor Unit Type
Model
14 Multi type Air Conditioner
Outdoor Unit - Multiple piping models
Product Specifications
Notes: 1. Capacities are based on the following conditions:
Cooling: -Indoor Temperature 26.7°C(80.1°F)DB/19.4°C66.9°F)WB
-Outdoor Temperature 35°C(95°F)DB/23.9°C(75°F)WB
-Interconnecting Piping Length 7.5m
-Level Difference of Zero.
Heating: -Indoor Temperature 21.1°C(70°F)DB/15.6°C(60.1°F)WB
-Outdoor Temperature 8.3°C(46.94°F)DB/6.1°C(42.98°F)WB
-Interconnecting Piping Length 7.5m
-Level Difference of Zero.
2. Capacities are Net Capacities.
3.
: See the page "Combination Table"
4. Due to our policy of innovation some specifications may be changed without notification.
Model
Cooling Capacity Btu/hr
W
kcal/hr
Heating Capacity Btu/hr
W
kcal/hr
Input Cooling W
Heating W
Running Current(208/230V)
Cooling A
Heating A
Power Supply Ø,V,Hz Max. Number of Connectable Indoor Units Compressor Type (Constant) Model
Motor Type
Quantity Ea
Motor Input W
Oil Charge cc
Oil Type
Capacitor µF/Vac
O.L.P Type(model name)
Compressor Type (Constant) Model
Motor Type
Quantity Ea
Motor Input W
Oil Charge cc
Oil Type
Capacitor µF/Vac
O.L.P Type(model name)
Refrigerant charge Charge g(oz)
Type
Control
Coil Tube Size (OD) inch(mm)
Fins per inch
No. of Rows & Column/No.
Fan motor Model
Output W
Capacitor µF/Vac
Fan Type
No. Used / Diameter EA/inch(mm)
Discharge Side / Top
Air Circulation Outdoor CMM(CFM) Noise Level(H/L) at 230V
Sound Press,1m dB(A) 1
SVC Valve Liquid inch(mm)
Gas
Dimensions W*H*D inch(mm) Net Weight Outdoor kg(lbs) Max. Interunit Piping Length
Total of Each Room m
For One Room m
Max. Installation Indoor Unit~Outdoor Unit m Height Difference Indoor Unit~Indoor Unit m Packing Dimension W*H*D inch(mm) Stuffing Quantity 20/40ft
9,000~36,000 9,000~36,000
2637~10,550 2637~10,550
2267~9071 2267~9071
- 9,000~36,000
- 2637~10,550
- 2267~9071
1320~3680 1320~3680
- 1410~3340
5.9~16.6 5.9~16.6
- 6.3~15.0
1,208/230,60 1,208/230,60
33
Rotary Rotary
GK141K GK141K
2 Pole Induction(PSC) 2 Pole Induction(PSC)
11
1430 1430 350Å}10 350Å}10 FVC68D FVC68D
35 / 370 35 / 370
External Type External Type
Rotary Rotary
GJ230K GJ230K
2 Pole Induction(PSC) 2 Pole Induction(PSC)
11
2370 2370
700±10 7000±10
FVC68D FVC68D
50 / 400 50 / 400
Internal Type Internal Type
2400 2400
R410A R410A
L.E.V L.E.V
0.276(7.0) 0.276(7.0) 18 18
2R,48C 2R,48C
ARC286B01 * 2 ARC286B01 * 2
102 102
2/370 2/370
Propeller Propeller
2 / 15.7(400) 2 / 15.7(400)
Side Side
63(2225) 63(2225)
51 51
1/4 (6..35) * 3EA 1/4 (6..35) * 3EA
3/8 (9.52) * 3EA 3/8 (9.52) * 3EA
34.3*41.7*12.6 (870*1060*320) 34.3*41.7*12.6 (870*1060*320) 80(176) 80(176)
45 45 15 15
7.5 7.5
7.5 7.5
41.1*44.9*17.3 (1045*1140*440) 41.1*44.9*17.3 (1045*1140*440) 51/111 51/111
A3UC363FA0(LMU360CE) A3UH363FA0(LMU360HE)
Service Manual 15
Installation
Installation
Type "A" screw and plastic anchor
Type "B" screw
Remote Control Holder
Installation plate
Figure FigureName
Screw driver
Electric Drill
Measuring Tape, Knife
Hole Core Drill
Spanner
Torque wrench
Ohmmeter
Hexagonal wrench
Ammeter
Gas Leak Detector
Thermometer,
Level
Flaring Tool Set
Name
Installation Parts
Installation Tools
Read carefully, and then follow step by step.
Installation
16 Multi type Air Conditioner
Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front of the unit.
3. Make sure that condensation drainage can be conve­niently routed away.
4. Do not install near a doorway.
5. Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
6. Use a stud finder to locate studs to prevent unneces­sary damage to the wall.
Outdoor unit
1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radia­tion from the condenser is not restricted.
2. Ensure that the spaces indicated by arrows around front, back and side of the unit.
3. Do not place animals and plants in the path of the warm air.
4. Take the air conditioner weight into account and select a place where noise and vibration are mini­mum.
5.
Select a place so that the warm air and sound from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
Select the best location
More than 5cm
(2.0 inch)
More than 5cm
(2.0 inch)
More than 2.3m
(90.6 inch)
More than 5cm
(2.0 inch)
CAUTION: Install the indoor unit
on the wall where the height from the floors more than 2.3m(7.5ft).
More than 10cm
More than 50cm
More than 50cm
More than 2m
more than 30cm
(11.8 inch)
more than 30cm
(11.8 inch)
more than 70cm
(27.6 inch)
Service Manual 17
Installation
Piping length and elevation
h2
h2
h1
A
B
C
h1
h1
CAUTION: Capacity is based on standard length and maximum allowance length is on the
basis of reliability. Oil trap should be installed every 5~7 meters (16.4~23.0ft).
Multi Piping Type
36k 45m(150ft) 15m(50ft) 3m(10ft) 7.5m(25ft) 7.5m(25ft)
Capacity(Btu/h)
Max total length of
all pipes
(A+B/A+B+C)
Max length of each
pipe (A/B/C)
Min length of each
pipe (A/B/C)
Max Elevation between each
indoor unit and out-
door unit (h1)
Max elevation
between indoor
units (h2)
9K 3/8" 1/4" 7.5m(25ft) 20g/m(0.32oz/ft)
12K 3/8" 1/4" 7.5m(25ft) 20g/m(0.32oz/ft)
Gas Liquid Standard Length Additional Refrigerant
Indoor Capacity
(Btu/h)
Pipe Size
18 Multi type Air Conditioner
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the
centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
Fixing Installation Plate(Standard Type)
Installation Plate
Type "A" screw
Chassis
Hook
ABCD S4 50 105 59 105 SE 65 110 85 110
CHASSIS
(Grade)
Distance (mm)
D
C
Ø70mm
Left rear piping Right rear piping
Installation plate
B
A
Ø70mm
Service Manual 19
Installation
Preparing work for Installation (Artcool Type Only)
Open panel front
1. First, push the front panel backward and lift it up to remove the two screws.
2. The moment of lifting the both lower parts of panel front, you can hear sound this panel came out, In this time panel front is separated
3. After pull down this panel a bit, and separate connecting wire with product.
Remove cover pipe and cover side
1. Remove two screws(for fixing cover pipe)
2. Pull up the cover side of desired connecting direction, then cover side is separated.
3. In case of connecting direction is left or right, path through the hole of cover side.
CAUTION: After removing the pipe hole, cut the burr for safety.
When connecting pipe path through rear wall, dont remove the hole.
NOTICE
Drain hose junction
1. Remove the rubber stopple of desired direction of drainage.
2. As the following picture, Insert drain hose in the handle of drain pan, and join drain hose and con­necting hose.
Panel Front
Connector
Pipe hole
Adhesive
Only one
desiring direction
Connecting
Drain
hose
part
rubber cap
20 Multi type Air Conditioner
Installation
Sticking the installation guide map and
fixing Indoor unit
Drill a hole in the wall
Drill the piping hole with a ø50mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Plastic anchors
INSTALLATION GUIDE MAP
10m
m
INSTALLATION GU
INSTAIIATION G
UIDE MAP
INSTALLATION GUIDE MAP
1. Put an Installation Guide Map on the desired surface.
2. Make a hole with diameter of 6mm and depth of 30-35mm when piercing a screw point.
3. Drive the fore plastic anchors into drilled points.
4. Hang the hole of product at the upper screws. (In this time, Remove the map)
(Falling attention)
5. Check the fixed product with light power.
6. Look at suited horizon by horizontal meter on the horizontal setting line, and Fix lightly the map by adhesive tape.
7. Drill the piercing part for connecting pipe as diameter 50mm. (In case of piercing rear surface)
Refer to No. 5 on this page when making a hole in the wall.
8. First, Drive the two points of the upper parts by screws. (Leave 10mm for hanging product)
9. Drive the lower parts after facing the hole of product with plastic anchors, and fix completely the upper screws.
In case of nothing wrong in the matter, connect the pipe and the wire. (Installation manual reference)
Horizontality
IN
S
T
A
L
L
A
T
IO
N
G
U
ID
E
M
A
P
Plastic anchors
IN
S
T
A
L
L
A
T
IO
N
G
U
ID
E
M
A
P
Hanger hole
(Rear side of
product)
5-7mm
(0.2~0.3")
Indoor
WALL
Outdoor
Service Manual 21
Flaring Work and Connection of Piping
Flaring work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable.
1. Use the piping kit accessory or the pipes purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5m (5.0ft) longer than the pipe length.
Burrs removal
1. Completely remove all burrs from the cut cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then
put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Carry out flaring work using flaring tool as shown below.
Firmly hold copper pipe in a die in the dimension shown in the
table above.
Copper
pipe
90°
Slanted Uneven Rough
mm inch mm
Ø6.35 1/4 0~0.5 Ø9.52 3/8 0~0.5
Outside diameter A
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Flaring Work and Connection of Piping
Pipe
Reamer
Point down
Flare nut
Copper tube
22 Multi type Air Conditioner
Flaring Work and Connection of Piping
Check
1. Compare the flared work with the figure by.
2. If a flared section is defective, cut it off and do flaring work again.
Indoor
1. Prepare the indoor unit's piping and drain hose for installation through the wall.
2. Remove the plastic tubing retainer(see the illustration by) and pull the tubing and drain hose away from chassis.
3. Replace only the plastic tubing holder 1, not the holder 2 in the original position.
1. Route the indoor tubing and the drain hose in the direction of rear right.
2.
Insert the connecting cable into the indoor unit from the out­door unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
3. Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the uper side can cause drain pan to overflow inside the unit.
If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweat­ing"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Connecting the Piping
For right rear piping
Drain hose
Tape
Connecting pipe
Drain hose
Connecting cable
Drain hose
Connecting cable
Drain hose
Loop
Gas side piping
Liquid side piping
Service Manual 23
Flaring Work and Connection of Piping
4. Indoor unit installation Hook the indoor unit onto the upper portion of the installa­tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Connecting the piping to the indoor unit and drain hose to drain pipe.
1. Align the center of the pipes and sufficiently tighten the flare nut by hand.
2. Tighten the flare nut with a wrench.
3. When extending the drain hose at the indoor unit, install the drain pipe.
Wrap the insulation material around the connecting por­tion.
1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Drain hose
Connecting
cable
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Outside diameter Torque
Indoor unit tubing Flare nut Pipes
Open-end wrench (fixed)
Flare nut
Wrench
Indoor unit tubing
Connection pipe
Drain pipe
Connection pipe
Vinyl tape (wide)
Connecting cable
Pipe
Indoor unit drain hose
Adhesive
Vinyl tape(narrow)
Plastic bands
Insulation material
Wrap with vinyl tape
Vinyl tape(narrow)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Drain hose
Vinyl tape(wide)
24 Multi type Air Conditioner
Flaring Work and Connection of Piping
1. Route the indoor tubing and the drain hose to the required piping hole position.
2. Insert the piping, drain hose, and the connecting cable into the piping hole.
3.
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection
later.
4. Tape the drain hose and the connecting cables.
5. Indoor unit installation
Hang the indoor unit from the hooks at the top of the
installation plate.
Insert the spacer etc. between the indoor unit and the
installation plate and separate the bottom of the indoor unit from the wall.
Connecting the piping to the indoor unit and the drain hose to drain pipe.
1. Align the center of the pipes and sufficiently tighten the flare nut by hand.
2. Tighten the flare nut with a wrench.
3. When extending the drain hose at the indoor unit, install the drain pipe.
For left rear piping
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Outside diameter Torque
1 2
Connecting
cable
Drain pipe
Indoor unit
Spacer
Installation plate
8cm
Indoor unit tubing Flare nut Pipes
Open-end wrench (fixed)
Flare nut
Wrench Indoor unit tubing
Drain hose
Indoor unit drain hose
Adhesive
Vinyl tape
Connection pipe
(narrow)
Service Manual 25
Flaring Work and Connection of Piping
Wrap the insulation material around the connecting por­tion.
1. Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Reroute the pipings and the drain hose across the back of the chassis.
Indoor unit installation
1. Remove the spacer.
2. Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
3. Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Plastic bands
Insulation material
Connection pipe
Vinyl tape (wide)
Connecting cable
Drain hose
Wrap with vinyl tape
Pipe
Vinyl tape(narrow)
Pipe
Vinyl tape(narrow)
Wrap with vinyl tape(wide)
Indoor unit piping
Piping for passage through piping hole
Connecting
cable
Drain hose
26 Multi type Air Conditioner
Flaring Work and Connection of Piping
Panel Assembly(Art Cool Type only)
1. First, Check the side cover assembly exactly, Fix power cord in the bottom groove of cover side left.
2. Assemble connecting lead wire with controller and first fix the upper part of panel front, then match the lower part of panel front
3. Drive two screws.
Panel F ront
Connector
Service Manual 27
Installation Information. For left piping. Follow the instruction below.
Good case
Press on the upper side of clamp and unfold the tubing to downward slowly.
Bad case
Following bending type from right to left may cause damage to the tubing.
Flaring Work and Connection of Piping
28 Multi type Air Conditioner
Flaring Work and Connection of Piping
Remove the battery cover from the remote con­troller.
Slide the cover according to the arrow direction.
Insert the two batteries.
Be sure that the (+) and (-) directions are correct.
Be sure that both batteries are new.
Re-attach the cover.
Slide it back into position.
REMOTE CONTROL PREPARATION(OPTIONAL)
HOW TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
Do not use rechargeable batteries, such batteries differ from standard dry cells in shape, dimensions, and per­formance.
Romove the batteries from the remote controller if the air conditioner is not going to be used for some long time.
HOW TO INSERT BATTERIES
Service Manual 29
Flaring Work and Connection of Piping
Outdoor
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Outdoor unit
Outside diameter Torque
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
A-UNIT
Gas side piping
B-UNIT
Liquid side piping
C-UNIT
Torque wrench
30 Multi type Air Conditioner
Connecting the Cable between Indoor Unit and Outdoor Unit
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are
the same as those of the indoor unit.)
The earth wire should be longer than the common wires. The circuit diagram is not subject to change without notice. When installing, refer to the electrical diagram behind the front panel of Indoor Unit. The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.
Connect the cable to the Indoor unit.
RECOMMAND:
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring to the wiring diagram.
RECOMMAND: Provide a circuit breaker
between power source and the outdoor unit as shown below.
RECOMMAND:
The power cord connected to the outdoor unit should be complied with the following
specifications (ETL recognized and CSA certified).
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications
(ETL recognized and CSA certified).
Air
Conditioner
Main power source
Circuit Breaker Use a circuit breaker or time delay fuse.
RECOMMAND:
When using the separate wire as the power cord, please fix the separate wire into the
control box panel by using tie wrap as the fixture.
Connecting the Cable between Indoor Unit and Outdoor Unit
AWG14
Line voltage (208~230V)
GN/YL
20mm
AWG18
Low voltage (below 40V)
GN/YL
20mm
Service Manual 31
Connect the cable to the Outdoor unit.
1. Remove the cover control from the unit by loosening the
screw. Connect the wires to the terminals on the control board individually as the following.
2. Secure the cable onto the control board with the holder
(clamper).
3. Refix the cover control to the original position with the
screw.
:
1. Separately wire the high and low voltage line.
2. Use heat-proof electrical wiring capable of withstanding temperature up to 75°C(167°F).
3. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit.
(For example, Type SJO-WA)
WARNING:
Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.
NOTICE
Outdoor unit
Over 5mm
Holder for
power supply
cord
Connecting
cable
Cover control
Terminal block
Power supply
cable
Connecting cable(Low voltage)
Connecting cable(Low voltage)
Connecting the Cable between Indoor Unit and Outdoor Unit
36k Outdoor side
A-UNIT
4321
B-UNIT
4321
Connecting cable(Low voltage)
Connecting cable(Low voltage)
C-UNIT
4321
Terminal BLOCK
Indoor A-UNIT
LN
4321
Power Source
208/230V AC
(High voltage)
Terminal BLOCK
Indoor B-UNIT
4321
Terminal BLOCK
Indoor C-UNIT
4321
32 Multi type Air Conditioner
(1) Remove two-caps on the conduit panel. (2) Make a hole appropriate for the passage of connection cable
through on cap by tool.
(for low voltage line) (3) Pass the connecting cable through the hole. (4) Properly connect the cable on the terminal block. (5) Fix the connection cable with cord clamp provided on the unit
not to have strain at the terminal when the connection cable is
pulled outside up to a 35 pound weight. (6) Wind the vinyl tape round the connecting cable for sealing
between the surface of the connection cable and cap. (7)Finally, Fix the cap to the conduit panel.
WARNING: Loose wiring may cause the termi­nal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
For strand wiring (1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to expose the strand wiring about 10mm(3/8").
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using a round terminal fastener or pliers, securely clamp
each stripped wire end with a round terminal.
(4) Position the round terminal wire, and replace and tighten
the terminal screw using a screwdriver.
Connection method of the connecting cable(Example)
G
Terminal block
Lock nut
Power supply line
(1ø, 230/208V)
Conduit panel
Cap(Reuse)
Cord clamp
Hole (for low voltage line)
Cap(Remove) Taping
(for sealing)
Low voltage line (connecting cable)
High voltage
Low voltage
Strip 10mm(3/8")
Round terminal
Connecting cable
Loosening the terminal block screw
Fastening the wire tightly
Strand wire
Connecting the Cable between Indoor Unit and Outdoor Unit
Service Manual 33
Connect the cable to the indoor unit
CAUTION: Provide a circuit breaker between power source and the unit as shown
below.
Air
Conditioner
Circuit Breaker
Use a circuit breaker or time delay fuse.
Main power source
Model
36k 1Ø, 230/208V 40A
Power source
Fuse or breaker
Capacity
1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the
terminal No. are the same as those of indoor unit respec­tively.
2. Attach the Grille onto the cabinet.
Grasp the lower left and right side of the Grille and
engage four tabs on the top inside edge of the chassis.
Press the Grille toward the chassis until it will be back into
place.
Connecting cable
Connecting the Cable between Indoor Unit and Outdoor Unit
34 Multi type Air Conditioner
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Checking the drainage
To check the drainage.
1. Pour a glass of water on the evaporator.
2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
Drain piping
1. The drain hose should point downward for easy drain flow.
2. Do not make drain piping.
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Accumulated drain water
Air
Waving
Water leakage
Water leakage
Do not raise
Water leakage
Tip of drain hose dipped in water
Ditch
Downward slope
Less than 50mm gap
Service Manual 35
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Forming the piping
Form the piping by wrapping the con­necting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
1. Tape the piping, drain hose and connecting cable from
down to up.
2. Secure the tapped piping along the exterior wall using
saddle or equivalent.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
1. Tape the piping and connecting cable from down to up.
2. Secure the taped piping along the exterior wall. Form a
trap to prevent water entering the room.
3. Fix the piping onto the wall by saddle or equivalent.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Trap is required to prevent water from entering into electrical parts.
Plastic band
Taping
Drain hose
Pipings Connecting
cable
Power supply cord
Seal a small opening around the pipings with gum type sealer.
36 Multi type Air Conditioner
Air Purging and Evacuation
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system. Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensi­ble gas and moisture in the system.
Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the ser­vice valve caps from both the gas and the liquid side on the out­door unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leakage test
Connect the manifold valve(with pressure gauges) and dry nitro­gen gas cylinder to this service port with charge hoses.
CAUTION: Be sure to use a manifold
valve for leak testing. The high side manifold valve must always be kept closed.
Pressurize the system to no more than 150 P.S.I.G. with dry
nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
CAUTION:
To avoid nitrogen entering the
refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
:
Leakage test shoud be done for each indoor
unit connection set, separately.
1. Do a leakage test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
2. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
NOTICE
Checking method
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Pressure gauge
Air Purging and Evacuation
Service Manual 37
Checking the Drainage, Forming the Pipings and Long Pipe Setting
1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
2. When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
2. Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side ser­vice port and fasten the flare nut securely with an adjustable wrench. This process is very important to pre­vent leakage from the system.
5. Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready for test running.
: Repeat evacuation procedure for each indoor
unit.
NOTICE
Required time for evacuation when 30 gal/h vacuum
pump is used
10 min. or more 15 min. or more
If tubing length is less
than 10m (33 ft)
If tubing length is longer
than 10m (33 ft)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Evacuation
38 Multi type Air Conditioner
Charging
Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor line.
Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant charge has to be adjusted.
Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g(0.22oz) of R-410A per meter(foot).
Example: A 80ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit.
Charging
36k 45m(150ft) 15m(50ft) 3m(10ft) 7.5m(25ft) 7.5m(25ft) 20g/m(0.22oz/ft)
Capacity (Btu/h)
Max total length
of all pipes
(A+B+C)
Max length of
each pipe
(A/B/C)
Min length of
each pipe
(A/B/C)
Max Elevation between each indoor unit and outdoor unit
(h1)
Max elevation
between indoor
units (h2)
Additional
Refrigerant
Service Manual 39
1. Check that all tubing and wiring have been properly con­nected.
2. Check that the gas and liquid side service valves are fully open.
1) Prepare remote controller
Remove the battery cover by pulling it according to the arrow direction.
Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
Reattach the cover by pushing it back into position.
NOTE:
Use 2 AAA(1.5volt) batteries. Do not use rechargeable
batteries.
Remove the batteries from the remote controller if the sys-
tem is not going to be used for a long time.
2) Precautions in test run
The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated.
For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compres­sor. Then attention must be paid.
Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later auto­matically)
The test run is started by pressing timer cancel button five times continuously. (Room type)
To cancel the test run, press any button.
3) Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration rubber.
4) Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake temperature and the discharge is more than 8°C(46°F) (Cooling) or reversely (Heating).
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
Test Running
Split, Art Cool Type
Discharge temperature
Discharge air
Intake temperature
R-410A 35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
Test Running
40 Multi type Air Conditioner
Operation
1. MAIN UNIT FUNCTION
DISPLAY
Operation Indicator
On while in appliance operation, off while in appliance pause
Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
Off except when hot start during heating mode operation or while in defrost control
Cooling Mode Operation
When the intake air temperature reaches 0.5°C(32.9
°F)
below the setting temp, the compressor and the outdoor
fan stop.
When it reaches 0.5°C(32.9
°F)
above the setting temp, they start to operate again.
Compressor ON Temp Setting Temp+0.5°C(32.9
°F)
Compressor OFF Temp ➲ Setting Temp-0.5°C(31.1
°F)
While in compressor running, operating with the airflow speed set by the remote control. While compressor is
off fan operates at low speed regardless of the setting.
Soft Dry Operation Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C(78.8
°F)
Intake Air Temp 25°C(77
°F)
24°C(75.2
°F)
Intake Intake Air Temp<26°C(78.8
°F)
Intake Air Temp-1°C(30.2
°F)
18°C(64.4
°F)
Intake Intake Air Temp<24°C(75.2
°F)
Intake Air Temp-0.5°C(31.1
°F)
Intake Air Temp<18°C(64.4
°F)
18°C(64.4
°F)
While compressor off, the indoor fan repeats low airflow speed and stop.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp. Setting Temp+0.5°C(32.9
°F)
Compressor OFF Temp. ➲ Setting Temp-0.5°C(31.1
°F)
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation
When the intake air temp reaches +3°(37.4
°F)
above the setting temp, the compressor is turned off. When
below the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. ➲ Setting Temp.+3°C(37.4
°F)
While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C(68
°F)
, when above
27°C(80.6
°F)
, it operates with the low or setting speed. When the indoor pipe temp is between 20°C(68
°F)
and
Function of control
Operation
Service Manual 41
Operation
27°C(80.6
°F)
, it operates with Super-Low(while in sleep mode, with the medium airflow speed).
While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(91.4
°F)
, when above
35°C(95
°F)
, it operates with the low airflow speed.
While in defrost control, the indoor is outdoor fans are turned off.
Defrost Control(Heating)
Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2
°F)
after 35 minutes
passed from starting of heating operation and more than 4 minutes operation of compressor.
Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature rises over 15°C(59
°F)
even before 12 minutes.
The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2
°F)
after 35 minutes
passed from ending of the first defrost and more than 4 minutes operation of compressor.
Fuzzy Operation
When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.
When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.
24°C(75.2
°F)
Inatake Air Temp ➲ Fuzzy Operation for Cooling
21°C(69.8
°F)
Inatake Air Temp<24°C(75.2
°F)
Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C(69.8
°F)
Fuzzy Operation for Heating
If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(32.9
°F)
or more
below the setting temp, the compressor is turned off. When 0.5°C(32.9
°F)
or more above the setting temp, the
compressor is turned on.
Compressor ON Temp ➲ Setting Temp +0.5°C(32.9
°F)
Compressor OFF Temp ➲ Setting Temp + 0.5°C(32.9
°F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78.8
°F)
Intake Air Temp 25°C(77
°F)
24°C(75.2
°F)
Intake Air Temp<26°C(78.8
°F)
Intake Air Temp + 1°C(33.8
°F)
22°C(71.6
°F)
Intake Air Temp<24°C(75.2
°F)
Intake Air Temp + 0.5°C(32.9
°F)
18°C(64.4
°F)
Intake Air Temp<22°C(71.6
°F)
Intake Air Temp
Intake Air Temp<18°C(64.4
°F)
18°C(64.4
°F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper­ature.
42 Multi type Air Conditioner
Operation
2) Fuzzy Operation for Dehumidification
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(32.9
°F)
or more
below the setting temp, the compressor is turned off. When 0.5°C(32.9
°F)
or more above the setting temp, the
compressor is turned on.
Compressor ON Temp Setting Temp + 0.5°C(32.9
°F)
Compressor OFF Temp ➲ Setting Temp+0.5°C(32.9
°F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78.8
°F)
Intake Air Temp 25°C(77
°F)
24°C(75.2
°F)
Intake Air Temp<26°C(78.8
°F)
Intake Air Temp+1°C(33.8
°F)
22°C(71.6
°F)
Intake Air Temp<24°C(75.2
°F)
Intake Air Temp+0.5°C(32.9
°F)
18°C(64.4
°F)
Intake Air Temp<22°C(71.6
°F)
Intake Air Temp
Intake Air Temp<18°C(64.4
°F)
18°C(64.4
°F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation.
3) Fuzzy Operation for Heating
According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37.4
°F)
or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.
Compressor ON Temp Setting Temp Compressor OFF Temp ➲ Setting Temp + 3°C(37.4
°F)
At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C(68
°F)
Intake Air Temp Intake Air Temp + 0.5°C(32.9
°F)
Intake Air Temp<20°C(68
°F)
20°C(68
°F)
When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.
While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature.
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or power (auto) by the input of the airflow speed selection key on the remote control.
On-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance starts to operate.
The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
Off-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance stops operating.
The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
Service Manual 43
Operation
If the appliance is on pause at the time set by the timer, the pause continues.
Off-Timer <=> On-Timer Operation
When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is carried out according to the set time.
Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C(33.8
°F)
. After another 30 min elapse, it increases by 1°C(33.8
°F)
again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Swing Mode
By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are fixed to the desired direction.
While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64.4
°F)
.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Auto Restarting Operation
When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
44 Multi type Air Conditioner
Operation
Forced Operation
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
When the power is supplied while the slide switch is on the forced operation position, or when the slide switch position is switched to the Auto Restarting (or test operation) position or switched from the remote control position to the forced operation position while the power is on, the forced operation is carried out.
When the slide switch position is switched from the forced operation position to the Auto Restarting position or the remote control position, the forced operation is canceled and the appliance stops operating.
In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the opera­tion condition is set according to the intake air temperature as follows.
24°C(75.2
°F)
Intake Air Temp Cooling Mode Operation, 22°C(71.6
°F)
, High Speed
21°C(69.8
°F)
Intake Air Temp<24°C(75.2
°F)
Dehumidification Operation, 23°C(73.4
°F)
, High Speed
Intake Air Temp<21°C(69.8
°F)
Heating Mode Operation, 24°C(75.2
°F)
, High Speed
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
Service Manual 45
"Wall Mounted Type is standard" * Functions is dependent on model type.
Operation
Function of Indoor Unit
On/Off : Lights up during the system operation. Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation. Defrost Mode
Outdoor unit operation
: Lights up during Defrost Mode or Hot Start operation (Heat pump model only) : Lights up during outdoor unit operation.(Cooling model only)
Desire temperature For cooling,dehumidification,heating modes it display Destired temperature indicator Cooling : 18°C~30°C(64°F~86°F) AI : Auto Operation
Dehumidification : 18°C~30°C(64°F~86°F) • Po : Jet Cool
Heating : 16~30°C(60°F~86°F) Lo : Test Mode
Plasma
: The function illustrates its dynamic mode by using a multiple lighting system. (Optional)
Room temperature sensor. (THERMISTOR)
Maintains the room temperature in accordance with the Setting Temp.
Indoor fan is delayed for 5 seconds at the starting.
Restarting is delayed for approx. 3 minutes.
High, Med, Low, Chaos, Jet Cool
Intermittent operation of fan at low speed.
The fan is switched to low(Cooling), med(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
The louver can be set at the desired position or swing up and down automatically.(Model base)
Split Type
Indoor Unit
Operation ON/OFF by Remote controlle
r
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
Both the indoor and outdoor fan stops during deicing.
Hot start after deice ends.
The indoor fan stops until the
evaporator piping temperature will be reached at 27°C(80.6°F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
* Airflow Direction Control
Deice (defrost) control (Heating)
Hot-start Control (Heating)
46 Multi type Air Conditioner
Operation
Room temperature sensor. (THERMISTOR)
Maintains the room temperature in accordance with the Setting Temp.
Indoor fan is delayed for 5 sec at the starting.
Restarting is inhibited for approx. 3 minutes.
High, Med, Low, CHAOS, JET COOL
Intermittent operation of fan at low speed.
The fan is switched to low(Cooling), med(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
The fan is switched to intermittent or irregular operatio
n
The fan speed is automatically switched from high to low speed.
The louver can be set at the desired position or swing up and down automatically.
Art Cool Type Indoor Unit
Operation ON/OFF by Remote controller Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Soft Dry Operation Mode
The function will be operated while in any operation mode with selecting the function.
The function is to be stopped while it is operating with selecting the function.
Both the indoor and outdoor fan stops dur­ing defrosting.
The indoor fan stops until the evaporator pipe temperature will be reached at 28°C(82.4°F).
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Defrost(Deice) control (Heating)
Hot-start Control (Heating)
PLASMA
: Lights up during the system operation.
Sleep Mode : Lights up during Sleep Mode Auto operation. Timer : Lights up during Timer operation. Defrost Mode : Lights up during Defrost Mode or
Hot Start operation.(Heat pump model only)
PLASMA : Indicate PLASMA purifier operation.
On/Off
Desire temperature For cooling,dehumidification,heating modes it display Destired temperature indicator Cooling : 18°C~30°C(64°F~86°F) AI : Auto Operation
Dehumidification : 18°C~30°C(64°F~86°F) Po : Jet Cool
Heating : 16~30°C(60°F~86°F) Lo : Test Mode
Outdoor unit operation
: Lights up during outdoor unit operation.(Cooling model only)
Service Manual 47
Operation
Function of Outdoor Unit
Outdoor Unit
Two Comp algorithm
Operating Step
LEV Control
Out door Fan Control
Compressor step varies considering condition such as room temp,outdoor temp, operating room number,Temp gap between room temp and set temp and so on.
LEV pulse is modulated to keep constant superheat or subcooling.
Outdoor fan operates at High or Off to respond to the load condition.
R/Valve Control(Heating Model Only)
Convert R/Valve to change cooling to heating, heating to cooling.
Defrost Function
After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -
5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min cooing mode.
To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to
Oil Return System
In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.
Comp Overload Protection
To protect comp from being overload, protector will turn off the comp.
High Pressure Protction
If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A
Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion.
48 Multi type Air Conditioner
Operation
Remote Control Operation
ON
OFF
CANCEL
AUTO CLEAN
°C/°F
SET
Cooling Operation
Auto Operation
Healthy Dehumidification Operation
Flip-up door (opened)
Heating Operation
Signal transmitter
Cooling Model( ), Heat Pump Model( )
5
1
3
10
9
16
17
12
18 15
6
4 2
7
11
8
13
14
Operation Mode
The Remote Controller transmits the signals to the system.
START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high and CHAOS.
JET COOL
Used to start or stop the speed cooling/heating. (Speed cooling/heating operates super high fan speed.)
CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
TIME SETTING BUTTONS
Used to adjust the time.
TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating.
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
PLASMA(OPTIONAL)
Used to start or stop the plasma-purification function.
RESET BUTTON
Initialize remote controller.
2nd F Button
Used prior to using modes printed in blue at the bottom of buttons.
AUTO CLEAN
Used to set Auto Clean mode.
˚C TO ˚F SWITCHING BUTTON
Used to switch temperature reading from Centigrade to Fahrenheit.
HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (NOT ON ALL MODELS)
Used to set the desired horizontal airflow direction.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
16
17
18
15
(Heat Pump)
(Cooling Only)
Service Manual 49
Disassembly
Disassembly
Indoor Unit
Split Type Indoor Unit
Disconnect the unit from power supply before mak­ing any checks. Be sure the power switch is set to “OFF”.
To remove the Grille from the Chassis.
• Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
• Remove the securing screws.
• To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Earth Conductor
50 Multi type Air Conditioner
Disassembly
2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis
carefully.
3. To remove the Discharge Grille.
Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).
Screw
When repair, do not damage the Caution label.
Service Manual 51
Disassembly
Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5.To remove the Motor Cover
Remove 2 securing screw.
Pull the motor cover out from the chassis
carefully.
6.To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from the self-aligning bearing.
Motor cover
Bearing
Cross-flow fan
52 Multi type Air Conditioner
Disassembly
Art Cool Type Indoor Unit
CAUTION: Disconnect the unit from power supply before making any checks. Be sure the power switch is set to “OFF”.
1. To remove the Grille from the Chassis.
- Pull the grille bottom, the remove 2 securing screws.
- Lift the both lower parts of panel front.
- After pull down this panel a bit, separate connecting wire with product.
2. To remove the Control Box.
- Before removing the control box, be sure to disconnect the wires from PWB.
- Pull the cover control out from the control box and disconnect other wires.
- Remove securing screws.
- Pull the control box out from the chassis carefully.
Step Motor Connectors
Sensor Connector
Comp Connector
4Way/Fan Connector
Motor Connector
Power Connector
Power Connector
Comp Connector
Panel Front
Connector
Service Manual 53
Disassembly
3) To remove the Evaporator.
- Remove 4 screws securing the evaporator.
- Pull the evaporator out from the chassis carefully.
4) Before removing the Turbo Fan.
- Remove the securing screws from the chassis.
- Pull the pipe cover, top cover and the air guide.
5) To remove the Motor.
- Remove the securing bolt from the motor shaft.
- Pull the fan out from the motor shaft.
- Remove 4 screws securing motor mount from the chassis and lift up the motor mount and the brack­et.
Top Cover
Pipe Cover
Air Guide
Turbo Fan
Bracket
Bolt Motor Mount
54 Multi type Air Conditioner
Schematic Diagram
Schematic Diagram
Electronic Control Device
1. Indoor Unit
1) Split Type
Service Manual 55
Schematic Diagram
2) Art Cool Type
OUTDOOR
64
17
Digit2
10
LED2
LED4
LED3
LED1
DEFROST
ON/OFF
TIMER
SLEEP
6(d)
Digit1
c
5
d
e
8(c)
7(e)
b
gfa
9(b)
1(g)
3(a)
4(f)
4
12
16
15
14
13
8
10
11
9
6
7
5
2
3
1
45
27
22
20
19
18
21
25
24
23
26
37
32
30
29
28
31.
33
34
35
36
41
39
38
40
43
42
44
54
59
61
62
63
60
56
57
58
55
49
52 51
53
50
47
46
48
HVB ASSY
231
231
CN-HVB(BL)
2
1
1
2
Vdd0
VssO
R28H 20K
R27H 20K
DISPLAY
44
STEPPING MOTOR
STEPPING MOTOR
KEY
TEST
Vcc
RECEIVER
Vout
GND
DC 5V
25V
0.01
C04L
CN-MAIN
14
88
10
13
9
10
9
765 765
14
88
1010
99
13
66
77
55
CN-D5
11
4
3
2
4
3
2
1 1
CN-D6
11
33
22
44
CN-D3
5 5
RD
YL
BLPK
OR
4
4
3 3
2
2
BLPK
YL
33
22
11
OR
RD
55
receiver
10
4965321
CN-D2
CN-D2(WH)
8
9
7
564
3
C02L
10V
220
5V
R12H
10K
50V
C13H
103
R11H
1K
Q
45
5V
123
876
DCS
Q02C
Q03C
R05G 220
R06G 220
R07G 220
5V
Q01C
LED scan
15
16
14
2
1
3
digit 1
digit 2
ecd
CN-D1
CN-D1(WH)
2
1
5V
R02G 220
R03G 220
R04G 220
R01G 220
IC01M
KID65004AF
12
11
13
10
5
6
4
7
9
8
agb
f
KID65004AF
IC02M
12V
680pF
50V
R01L
C01L
5.1K
F2
OJ02H
5V
OR2H
OR3HOR6H OR5H OR4H
MedS-Hi Hi Low
AVss
AVdd1
AVret
AVdd
RESET
X1X2INTO
Vss1
INT1
R23H
OR1H
F1
R25H
R24H
R26H
R21H~R26H
12.1K 1%
R22H
R21H
5V
5V
CST-8.00MTW
OSC01B
uPD780023AGC
0IMCRNE002M
CN-UD(BL)
1
2
3
4
5
R01E
1K
12V
R02E 20
PKM13EPP-4002
BZ01E
PIPE-TH
ROOM-TH
STEP MOTOR
6.2K
12.1K
R05H
10K
1%
1%
22
11
R02H
R04H
5V
5V
receiver
CN-TH1(WH)
3
4
3
4
CN-LR2(WH)
L / R 2
STEP MOTOR
RD
12V
RD
YL
OR
PK1BL
CN-LR1(WH)
BL
344
5
OR
PK
YL
L / R 1
STEPPING MOTOR
RD
PKBL YL OR
SUB PCB ASM
5V
HVB
7
8
12
11 1111
12
5V
10987654
321
8910
123
456
77
654
3
2
1098
1
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
11
2
3
4
5
6
7
8
9
HVB PIN1
10
11
12
13 13
12
11
10
5
421
3
5
421
33
124
5
5
1
2
4 3
14
13
12
14
13
12
11
E3 1K
E2 1K
C02M
103
C01M
103
C03M
103
CN-D1(WH)
CN-CON(WH)
CN-12V(WH)
10
11
12
13
10
11
13
12
3
3
2
2112 2
3 3
11
2222
3
3
3 3
11
11
OJ01H
0.01
25V
C01A
R02A 20K
5V
1
KSC7536
KIA7036P
3
3.6V
2
IC01A
R02L
1K
R01B
1M
HVB PIN2
HVB PIN1
HVB
HVB PIN2
12V
5V
DC5V
103
C06D
C01D
35V
2200uF
DC12V
+
IC02D
7805
C05D
25V
470uF
+
O
C04D
104
50V
I
I
C03D
25V
470uF
O
7812
IC01D
104
C02D
50V
+
+
-
R97
10K
R96
10K
DC 5V
3
2
4
IC9-1
KA393
DC12V
8
1
R95
10K
63V
100uF
C07D
CN-MOTOR1(WH)
MOTOR1
INDOOR
FAN
34
34
1
1
2
2
+
104,50V
CN-DC/DC(BL)
POLY SW1
RXE250
~
3
2
4
3
2
4
1/4W
C92
11
DC 5V
R90 1K
C91
103
5
IC9-2
KA393
-
R92 10K
4.7K
R91
7
+
6
R93 10K
2
3
1
4
DC12V
2
3
1
R99
750
4
C03L
L3
10V
220
RXD
TXD
TXD
RXD
FG
C81
103
R81 1K
FG1
FG1
EEPROM
2
15
16
1
7
10
13
11
12
14
4
6
5
3
9
8
13
14
3
15
16
2
1
KID65004AF
IC03M
10
11
6
12
5
4
9
8
7
12V
4 23
FAN
INDOOR
MOTOR2
1
4
23 1
RXE250~POLY SW2
FG2
DC12V
CN-MOTOR2(WH)
R81A 1K
FG2
C81A
103
56 Multi type Air Conditioner
Schematic Diagram
2. Outdoor Unit
Service Manual 57
Schematic Diagram
58 Multi type Air Conditioner
1. Room Type Indoor Unit -S4/SE chassis
2. Art Cool Type Indoor Unit
Wiring Diagram
Schematic Diagram
3. Outdoor Unit
1. A3UH363FA0(LMU360HE) 2. A3UC363FA0(LMU360CE)
Service Manual 59
Schematic Diagram
1. Indoor Unit
MAIN P.C.B ASM
1) Split Type
Components Locations
• TOP VIEW
• BOTTOM VIEW
PCB :6870A90409B ASSY:6871A20771
6871A20782
60 Multi type Air Conditioner
Schematic Diagram
2) Art Cool Type
• TOP VIEW
• BOTTOM VIEW
Service Manual 61
Schematic Diagram
2. Display ASSEMBLY
1) Split Type (6871A20680)
2) Art Cool Type (6871A20462)
BOTTOM VIEW
TOP VIEW
62 Multi type Air Conditioner
Schematic Diagram
3. Outdoor Unit
1) Component side
Service Manual 63
Schematic Diagram
2) Solder side
64 Multi type Air Conditioner
Field Piping Gas
Field Piping Liquid
Refrigerant Flow
Th1: Discharge thermistor Th2: Discharge thermistor Th3: Outdoor temperature thermistor
Room A
Cooling
LEV-B
LEV-A
Heat Exchanger
Header
OUTDOOR UNIT
Room B
Ø9.52
Room A
Room B
Ø6.35
Ø6.35
Ø6.35
Ø9.52
Room C
Ø9.52
Th2
High pressure S/W
Th3
Th1
LEV-C
Room C
Constant
Compressor
Constant
Compressor
Accumulator
1. A3UH363FA0(LMU360HE)
2. A3UC363FA0(LMU360CE)
Troubleshooting Guide
Troubleshooting Guide
Refrigeration Cycle Diagram
Ø9.52
Room C
Room B
Room A
Room C
Room B
Room A
Ø9.52
Ø9.52
Ø6.35
Ø6.35
Ø6.35
Field Piping Gas
Field Piping Liquid
Refrigerant Flow
Cooling Heating
Th1: Discharge thermistor Th2: Discharge thermistor Th3: Outdoor temperature thermistor Th4: Defrost thermistor
Header
LEV-C
LEV-B
LEV-A
Accumulator
Constant
Th1
Compressor
High pressure S/W
Th2
Constant
Compressor
OUTDOOR UNIT
Th3
Heat Exchanger
Th4
Service Manual 65
Troubleshooting Guide
Error Indicator
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
Having or not of error code is different from Model.
Self-diagnosis Function
00 No Error ON 01 Indoor Room Thermistor Error 1 time OFF 02 Indoor In-Piping Error 2 times OFF 05 Communication Error between In and Out 5 times OFF 06 Indoor Out-Piping Error 6 times OFF 07 Differnt mode operation 7 times OFF 10 Indoor fan motor locked error 1 times OFF
Error code Description MPS Variable LED1 LED2 Indoor Status
33 D-Pipe High(Normal) 3 times 3 times OFF 44 Outdoor Air Thermistor Error(Open/Short) 4 times 4 times OFF 45 Cond Pipe Thermistor Error(Open/Short) 4 times 5 times OFF 47
Const. D-Pipe Thermistor Error(Open/Short)
4 times 7 times OFF
51 Capcity Error(High/Low)
5 times 1 times OFF
Error code Description MPS Variable LED1(Red) LED2(Green) Indoor Status
Indoor Error
Outdoor Error
LED1
LED2
66 Multi type Air Conditioner
Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current.
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakage Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Temp. difference : approx. 0°C(32°F) Current : less than 80% of
rated current
Temp. difference : approx. 8°C
(46.4°F)
Current : less than 80% of
rated current
Temp. difference : less than 8°C
(46.4°F)
Current : near the rated cur-
rent
Temp. difference : over 8°C
(46.4°F)
Temp. Difference
Operating Current
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal value)
High Defective compressor Current is low.
Normal Excessive amount of High pressure does not quickly
refrigerant rise at the beginning of operation. Insufficient amount of Current is low.
Lower Higher refrigerant(Leakage)
Clogging
Higher
Cycle Troubleshooting Guide
Service Manual 67
Troubleshooting Guide
Electronic Parts Troubleshooting Guide
Refer to electronic contorol device drawing & schematic diagram.
The Product doesn’t operate at all.
Turn off the main power and wait until LED on outdoor PCB is off.
Turn on the main power again.
Does "Beeping" sound is made from the indoor unit?
Primarily, the operating condi­tion of Micom is O.K.
Check CN-DISP1
Check the voltage of power(AC208V/AC230V, 60Hz).
The voltage of main power.
The voltage applied to the unit.
The connecting method of Indoor/Outdoor connecting cable (each color)
The P.W.B. Ass'y
(Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.)
Trouble 1
NO
YES
The operation check of the P.C.B. Ass'y
Procedure
1) The input voltage of power trans­former.
2) The output voltage of power transformer.
3) IC01D(7812)
4) IC02D(7805)
5) IC01A(KIA7036)
Specification
1) AC230V ± 30V : Check the rated voltage
2) 15V ± 1.5V
3) DC12V
4) DC5V
5) The voltage of micom pin 29 : DC4.5V
Remedy
1) Replace power transfomer.
2) Replace power transfomer.
3) Replace IC01D.
4) Replace IC02D.
5) Replace IC01A.
68 Multi type Air Conditioner
Troubleshooting Guide
Turn on main power.
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)
Caused by the remote controller.
Caused by other parts except
the remote controller
When the mark ( ) is displayed in LCD
screen, replace battery.
Check the contact of CN-DISP 1 connector
When the detect switch (double key) inside the
remote controller door is fault, it is impossible to
operate temperature regulating(▲ / ▼) and wind
speed selecting.
Check DISP PWB Ass'y
-Voltage between CN1 ➀ - ➆ : DC +5V
Check the Display PWB Ass'y Check receiver ass'y
Product doesn't operate with the remote controller.
Trouble 2
Service Manual 69
Troubleshooting Guide
Turn on the main power.
When in air circulation mode, compressor/outdoor fan is stopped.
Turn off main power.
Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor.
Check the sensor for Indoor temperature is attatched as close as to be effected by the themperature of Heat Exchange (EVA.)
When the sensor circuit for Indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor fan is stopped.
Check the related circuit of R01H(1K), R02H(1K), R03H(1K), R04H(1K), Micom(pin No. 74 ,
75 , 76 , 77 ).
Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).
Check the Relay(RY-PWR, RY-START) for driving Compressor.
Check the voltage between brown and blue cable of terminal to connect the Outdoor (About AC208V / 230V).
Check the related circuit of relay in Outdoor PCB Ass'y.
Operate Cooling Mode by setting the disired temperature of the remote controller is less than one of the Indoor temperature by 1°C at least.
The Compressor/Outdoor Fan are don't operate
Trouble 3
Check Point
Between Micom(No. 50,51) and GND
DC 5V DC 0V
DC 12VDC 1V
Between IC01M(No. 10) and GND
Comp. ON Comp. OFF
70 Multi type Air Conditioner
Troubleshooting Guide
When indoor Fan does not operate.
Check connecting condition of the CN-MOTOR CON­NECTOR
Does the voltage of terminal of CN-DC/DC CONNECTOR in Indoor unit corresponds to the values in the table of page 56
Do the voltage of terminal of CN-DC/DC CONNECTOR in Outdoor unit corresponds to the values in the table of page 56
Check the patterns and the conditions of outdoor unit PWB Assy's.
Check the connecting condi­tion and disconnection of connecting wires between Indoor and Outdoor unit.
Check the pattern and the condition of Indoor unit PWB Ass'y.
Check the interference of Indoor Fan.
Does the voltage of each terminals of CN-MOTOR CONNECTOR in Indoor unit corresponds to values in the Table of page 69
Check the motor of Indoor Fan
Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode). Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F. (At that times, Defrost indicator is turned on)
NO
YES
When indoor Fan does not operate.
Trouble 4
Service Manual 71
Troubleshooting Guide
When the louver does not operate.
Trouble 5
When Vertical Louver does not operate.
Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.
If the regular torque is detected when rotating the Vertical Louver with hands Normal
Check the connecting condition of CN-UP/DOWN Connector
Check the soldering condition(on PWB) of CN-UP/DOWN Connector
Check the operating circuit of the Vertical Louver
Confirm that there is DC +12V between pin (RED) of CN-UP/DOWN and GND.
Confirm that there is a soldering short at following terminals.
- Between 60 , 61 , 62 and 63 of MICOM
- Between
2 , 3 , 4 and 5 of IC01M
- Between 12 , 13 ,
14 , 15
of IC01M
- Between
1 , 2 , 3 , 4 and 5 of CN-UP/DOWN
If there are no problems after above checks
Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
72 Multi type Air Conditioner
Troubleshooting Guide
Error Code
Trouble Shooting
Error
Title Cause of error Check point & Normal condition
code
01 Indoor air sensor
02 Indoor inlet pipe sensor
06 Indoor outlet pipe sensor
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Normal resistor : 10K/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged)
Normal resistor : 5K/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged)
Normal resistor : 5K/ at 25°C (Unplugged) Normal voltage : 2.5Vdc / at 25°C (plugged)
Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor
3. If the resistance of the sensor is 10KΩ/5KΩ at 25°C, then sensor is normal
4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc / at 25°C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB
10K
2.5Vdc
V
Check the resistance / voltage
Service Manual 73
Troubleshooting Guide
Error
Title Cause of error Check point & Normal condition
code
05 / 53
Communication (Indoor Outdoor)
Communication poorly
Power input AC 230V.(Outdoor, Indoor)
The connector for transmission is disconnected.
The connecting wires are misconnected.
The GND 1,2 is not connected at main GND.
The communication line is shorted at GND.
Transmission circuit of outdoor PCB is abnormal.
Transmission circuit of indoor PCB is abnormal.
Check Point
1. Check the input power AC 230V.(Outdoor, Indoor)
2. Check the communication wires are correctly connected.
Adjust the connection of wireConfirm the wire of "Live", "Neutral".
3. Check the resistance between communication line and GND.(Normal : Over 2MΩ)
4. Check the connector for communication is correctly connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no problem. Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.
74 Multi type Air Conditioner
Troubleshooting Guide
Error
Title Cause of error Check point & Normal condition
code
33 D-Pipe Temp. High
Discharge sensor temp. high
Check the discharge pipe sensor.
Check the install condition for over load.
Check the leakage of refrigerent.
Check the SVC V/V open.
Error
Title Cause of error Check point & Normal condition
code
51 Capacitor error
Over Capacitor com­bination
Check the indoor unit capacity.
Check the combination table
Check Point
1. Check the indoor unit capacity.
2. Check the combination table.
In the tropical model case single cycle has no error for over capacity.
Check Point
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerent.
4. Check the constant compressor.
115°C(239°F) 100°C(212°F)
95°C(203°F)
A3UH363FA0(LMU360HE)/A3UC363FA0(LMU360CE)
COMP OFF
LEV OPEN(16PULSE/MIN) LEV OPEN(10PULSE/MIN)
NORMAL
Service Manual 75
Troubleshooting Guide
Error
Title Cause of error Check point & Normal condition
code
44 Outdoor air sensor
45 Condensor pipe sensor
47 D-Pipe sensor
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Open / Short
Soldered poorly
Internal circuit error
Normal resistor : 10KΩ / at 25°C(77°F) (Unplugged) Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 5K/ at 25°C
(77°F)
(Unplugged)
Normal voltage : 2.5Vdc / at 25°C
(77°F)
(plugged)
Normal resistor : 200K/ at 25°C
(77°F)
(Unplugged)
Normal voltage : 4.5Vdc / at 25°C
(77°F)
(plugged)
Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance is 0V or 5Vdc, then sensor is abnormal
Check the resistance
76 Multi type Air Conditioner
2-way, 3-way Valve
2-way, 3-way Valve
2-way Valve (Liguid Side) 3-way Valve (Gas Side)
Works Shaft position Shaft position Service port
Shipping Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Air purging Open Closed Open
(Installation) (counter-clockwise) (clockwise) (push-pin or with
vacuum pump)
Operation Open Open Closed
(with valve cap) (with valve cap) (with cap)
Pumping down Closed Open Open
(Transfering) (clockwise) (counter-clockwise) (connected
manifold gauge)
Evacuation Open Open Open
(Servicing) (with charging
cylinder)
Gas charging Open Open Open
(Servicing) (with charging
cylinder)
Pressure check Open Open Open
(Servicing) (with charging
cylinder)
Gas releasing Open Open Open
(Servicing) (with charging
cylinder)
3.
2.
1.
4.
5.
6.
Flare nut
To piping connection
Open position Closed position
Flare nut
Valve cap
To piping connection
Open position Closed position
Hexagonal wrench (4mm)
To outdoor unit
Pin
Service port
Service port cap
To outdoor unit
Service Manual 77
2-way, 3-way Valve
(1) Pumping down
Procedure
1. Confirm that both the gas side and liquid side valves are set to the open position.
- Remove the valve stem caps and confirm that the valve stems are in the raised position.
- Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then con­nect the manifold gauge to the service port of the gas side valve.
- Connect the hose of the gauge with the push pin to the service port.
4. Air purging of the charge hose.
- Open the Low-handle valve on the gauge slightly to air purge from the hose.
5. Set the liquid side valve to the closed position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm2g.
7. Immediately set the gas side valve to the closed position.
- Do this quickly so that the gauge ends up indicat­ing 1kg/ g.
8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut.
- Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m)
- Be sure to check for gas leakage.
Indoor unit
Outdoor unit
Liquid side
Close
Gas side
2-Way
valve
Open
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Close
Gas side
2-Way
valve
Open
3-Way
valve
Hi- handle (CLOSE)
Low­handle (CLOSE)
Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor.
78 Multi type Air Conditioner
2-way, 3-way Valve
(2) Evacuation
(All amount of refrigerant leaked)
Procedure
1. Confirm that both the liguid side valve and gas side valve are set to the opened position.
2. Connect the vaccum pump to the center hose of the manifold gauge.
3. Connect the service port of the gas side valve to the low side of the gauge.
4. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less).
5. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge needle does not move(approximately 5 minutes after turning off the vacuum pump).
6. Disconnect the charge hose from the vacuum pump.
- Vacuum pump oil. If the vacuum pump oil becomes dirty or deplet­ed,replenish as needed.
7. Mount the valve caps and the service port caps.
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
manifold gauge
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Vacuum pump
Hi- handle (OPEN)
Low­handle (OPEN)
Service Manual 79
2-way, 3-way Valve
(3) Gas Charging
(After Evacuation)
Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect­ed from the vacuum pump to the valve at the bottom of the cylinder.
- If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid.
2. Purge the air from the charge hose.
-
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.
3. Open the low handle on the gauge and charge the system with liquid refrigerant.
- If the system can not be charged with the speci­fied amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure(pumping down-pin).
4. Immediately disconnect the charge hose from the gas side valve's service port.
- Stopping partway will allow the gas to be dis-
charged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
5. Mount the valve stem nuts and the service port nut.
- Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
manifold gauge
Charging
cylinder
Hi- handle (OPEN)
Low-handle
(OPEN)
Check valve
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
80 Multi type Air Conditioner
135301
152302-2
152313
152302-1
342800
263230-2 263230-1
359011
131410 733010
135311
135312
159901
268712
146811
147582
346810
135516
35211B
354210
249951
352150
268714
668713
267110
135500
Exploded View & Replacement Parts List
Exploded View & Replacement Parts List
Indoor Unit
S4, SE chassis
Service Manual 81
Exploded View & Replacement Parts List
Parts List (S4, SE chassis)
PART No.
S4 chassis SE chassis
AMNH093D4A0
(LMN090HE)
AMNC093D4A0
(LMN090CE)
AMNH123DEA0
(LMN120HE)
AMNC123DEA0
(LMN120CE)
131410 CHASSIS ASSEMBLY 3141A20019C 3141A20019C 3141A20034A 3141A20034A R 135311 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A14003K 3531A14003K 3531A18015A 3531A18015A R
135301 GRILLE,FRONT 3530A10253A 3530A10253A 3530A10287A 3530A10287A R 152302-1 FILTER,AIR 5230A20051B 5230A20051B 5230A20064A 5230A20064A R 152302-2 FILTER,AIR 5230A20051D 5230A20051D 5230A20064A 5230A20064A R
135312
GRILLE ASSEMBLY,DISCHARGE(INDOOR)
3531A11307A 3531A10307V 3531A11362A 3531A11362B R 159901 LOUVER,HORIZONTAL 5990A20069A 5990A20069A 5990A20068A 5990A20068A R 147582 LOUVER,VERTICAL 4758A30052A 4758A30052A 4758A30057A 4758A30057A R 146811 MOTOR,DC 4681A20055A 4681A20055A 4681A20055A 4681A20055A R 268712 PCB ASSEMBLY,DISPLAY 6871A20680D 6871A20680F 6871A20680D 6871A20680F R 135516 COVER ASSEMBLY,MOTOR 3551A20156B 3551A20156B 3551A20156B 3551A20156B R 346810 MOTOR,DC 4681AR2295L 4681AR2295L 4681AR2295L 4681AR2295L R 152313 FILTER ASSEMBLY,DEODORIZER 5231A20040A 5231A20040A 5231A20040K 5231A20040K R 249951 CASE ASSEMBLY,CONTROL(INDOOR) 4995A20831A 4995A20831A 4995A20831A 4995A20831A R 268714 PCB ASSEMBLY,MAIN 6871A20782A 6871A20782A 6871A20782A 6871A20782A R 668713 PCB ASSEMBLY(OPTION PCB) 6871A20989A 6871A20989D 6871A20989B 6871A20989C R
263230-1 THERMISTOR,NTC 6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T R 263230-2 THERMISTOR,NTC 6323A20004A 6323A20004A 6323A20004A 6323A20004A R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20128C 6711A20128A 6711A20128C 6711A20128A R 342800 BEARING 4280A20004B 4280A20004B 4280A20004B 4280A20004B R 354210 EVAPORATOR ASSEMBLY,FINAL 5421A20222C 5421A20222C 5421A20282A 5421A20282A R 35211B TUBE ASSEMBLY,TUBING 5211A21363E 5211A21363E 5211A15008A 5211A15008A R 352150 HOSE ASSEMBLY,DRAIN 5251A20011B 5251A20011B 5251A20011G 5251A20011G R 359011 FAN ASSEMBLY,CROSS FLOW 5901A20017F 5901A20017F 5901A20017H 5901A20017H R 733010 PLATE ASSEMBLY,INSTALLATION 3301A20020C 3301A20020C 3301A20020A 3301A20020A R 135500 COVER 3550A30262A 3550A30262A 3550A30315A 3550A30315A R
DESCRIPTION
SVC
CODE
LOCATION
No.
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
82 Multi type Air Conditioner
Exploded View & Replacement Parts List
135515
267110
135500-3
268714
352150
35211B
263230-2
147581
359012
349600
352380
146811
146811
147581
346810
147581
268712
135500-1
131410
354210
263230-1
135500-2
146811
268717-1
268717-2
330870
135312
146811
135314
159830
249951
SP3 Chassis Art Cool Type
Service Manual 83
Exploded View & Replacement Parts List
Parts List (SP3 chassis)
PART No.
AMNH093APM0
(LMAN090HNS)
AMNC093APM0 (LMAN090CNS)
AMNH123APM0 (LMAN120HNS)
AMNC123APM0 (LMAN120CNS)
131410 CHASSIS ASSEMBLY 3141A20030C 3141A20030C 3141A20030C 3141A20030C R 135312
GRILLE ASSEMBLY,FRONT(INDOOR)
3531A21035N 3531A21035T 3531A21035N 3531A21035T R 135314 GRILLE ASSEMBLY,INLET 3531A20212K 3531A20212K 3531A20212K 3531A20212K R 152302 FILTER, AIR 5230A20032A 5230A20032A 5230A20032A 5230A20032A R 268712 PCB ASSEMBLY,DISPLAY 6871A20462A 6871A20462B 6871A20462A 6871A20462B R
268717-1 PCB ASSEMBLY,SUB 6871A20259B 6871A20259B 6871A20259B 6871A20259B R 268717-2 PCB ASSEMBLY,SUB 6871A20363D 6871A20363D 6871A20363D 6871A20363D R 135500-1 COVER 3550A20123C 3550A20123C 3550A20123C 3550A20123C R 135500-2 COVER 3550A20124B 3550A20124B 3550A20124B 3550A20124B R 135500-3 COVER 3550A20060A 3550A20060A 3550A20060A 3550A20060A R
135515 COVER ASSEMBLY,TOP(INDOOR) 3551A20031H 3551A20031H 3551A20031H 3551A20031H R 147581 LOUVER,HORIZONTAL 4758A20014B 4758A20014B 4758A20014B 4758A20014B R 146811 MOTOR,DC 4681A20055A 4681A20055A 4681A20055A 4681A20055A R 159830 FILTER ASSEMBLY,AIR CLEANER 5983A20007F 5983A20007F 5983A20007F 5983A20007F R 249951
CASE ASSEMBLY,CONTROL(INDOOR)
4995A20832B 4995A20832A 4995A20832D 4995A20832C R 268714 PCB ASSEMBLY 6871A20387K 6871A20387M 6871A20387M 6871A20387N R
263230-2 THERMISTOR,NTC(ROOM+IN PIPE) 6323A20004N 6323A20004N 6323A20004N 6323A20004N R 263230-1 THERMISTOR,NTC(OUT PIPE) 6323AQ3226T 6323AQ3226T 6323AQ3226T 6323AQ3226T R
267110 REMOTE CONTROLLER ASSEMBLY 6711A20128F 6711A20083R 6711A20128F 6711A20083R R 330870 PAN ASSEMBLY,DRAIN 3087A30004A 3087A30004A 3087A30004A 3087A30004A R 346810 MOTOR,UNCLASSIFIED 4681A20047B 4681A20047B 4681A20047B 4681A20047B R 349600 BRACKET,MOTOR 4960A20016A 4960A20016A 4960A20016A 4960A20016A R
35211B TUBE ASSEMBLY,TUBING 5211AR7066F 5211AR7066F 5211AR7066F 5211AR7066F R
352150 HOSE ASSEMBLY,DRAIN 5251AR1222R 5251AR1222R 5251AR1222R 5251AR1222R R 354210 EVAPORATOR ASSEMBLY,FIRST 5421A20072A 5421A20072A 5421A20072A 5421A20072A R 359012 FAN,TURBO 5900A00003A 5900A00003A 5900A00003A 5900A00003A R
DESCRIPTION
SVC
CODE
LOCATION
No.
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
84 Multi type Air Conditioner
Exploded View & Replacement Parts List
546810
559010
552116
552203-1
552203-2
554160-2
554160-1
567502
554031
447910
430410
435512
135301
437211
137213-2137213-1
135314
548490
552112
552113
552117
561411-1
561411-2
561411-3
263230-1
263230-2
649950
668711-2
668711-1
W0CZZ-1
W0CZZ-2
435511
561410
A3UH363FA0(LMU360HE), A3UC363FA0(LMU360CE)
Outdoor Unit
Service Manual 85
Exploded View & Replacement Parts List
Parts List (A3UH363FA0(LMU360HE), A3UC363FA0(LMU360CE))
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Solenoid(Coil Assembly, Reverse) is only for heat pump model.
PART No.
A3UH363FA0(LMU360HE) A3UC363FA0(LMU360CE)
135301 GRILLE,DISCHARGE 3530A20006G 3530A20006G R
135314 GRILLE,REAR 3530A10176B 3530A10176B R 263230-1 THERMISTOR, NTC 6323A20028A 6323A20028A R 263230-2 THERMISTOR, NTC 6323A20026A 6323A20026A R
430410 BASE ASSEMBLY, OUTDOOR 3041AP2741H 3041AP2741H R
435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 3551A10044G 3551A10044H R
435512 COVER ASSEMBLY,TOP(OUTDOOR) 3H03266H 3H03266H R
437211 PANEL ASSEMBLY,FRONT(OUTDOOR) 3721A10109C 3721A10109C R
447910 BARRIER ASSEMBLY,OUTDOOR 4791A10019B 4791A10019B R
546810 MOTOR ASSEMBLY,OUTDOOR 4681AR1392X 4681AR1392X R
548490 ACCUMULATOR ASSEMBLY(MECH) 4848A20006L 4848A20006L R
552112 TUBE ASSEMBLY,CONDENSER IN 5211A11010A 5211A11010A R
552113 TUBE ASSEMBLY, CONDENSER OUT 5211A12001A 5211A12001A R
552116 TUBE ASSEMBLY, REVERSING AJR30111101 AJR30111101 R
552117 TUBE ASSEMBLY, SUCTION(OUTDOOR) AJR30125001 AJR30125001 R
554031 CONDENSER ASSEMBLY, BENDING 5403A20168A 5403A20168C R
559010 FAN ASSEMBLY, PROPELLER 5901A10033A 5901A10033A R
561410 COIL ASSEMBLY, REVERSING VALVE 3A02028Z - R
649950 CASE ASSEMBLY,CONTROL(OUTDOOR) 4995A00002H 4995A00002H R 668711-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20500B 6871A20500B R 668711-2 PWB(PCB) ASSEMBLY,MAIN(OUTDOOR) 6871A20479E 6871A20479E R 137213-1 PANEL ASSEMBLY, SIDE 3721A10110A 3721A10110A R 137213-2 PANEL ASSEMBLY, SIDE 3721A10111C 3721A10111C R 552203-1 VALVE,SERVICE 5220A20001K 5220A20001K R 552203-2 VALVE,SERVICE 2H02479J 2H02479J R 554160-1 COMPRESSOR 2520UHGK2AA 2520UHGK2AA R 554160-2 COMPRESSOR TBZ30111701 TBZ30111701 R 561411-1 DRAWING,ASSEMBLY(EEV COIL) 6877A20050A 6877A20050A R 561411-2 DRAWING,ASSEMBLY(EEV COIL) 6877A20050B 6877A20050B R 561411-3 DRAWING,ASSEMBLY(EEV COIL) 6877A20050C 6877A20050C R W0CZZ-1 CAPACITOR,FILM,BOX 0CZZA20007Q 0CZZA20007Q R W0CZZ-2 CAPACITOR,FILM,BOX 2H01451S 2H01451S R
567502 O.L.P 6750U-L048A 6750U-L048A R
DESCRIPTION
SVC
CODE
LOCATION
No.
P/No.: 3828A20474C
May, 2006
Printed in Korea
Loading...