Service Manual 3
Outdoor
Nominal Capacity Cooling kW
Btu/h
Heating kW
Btu/h
Nominal Input Cooling kW
Heating kW
Testing Combination
Running Current(Rating) Cooling A
Heating A
Starting Current Cooling/Heating A
Power Supply Ø / V / Hz
Power Supply Cable(Outdoor) No. x mm
2
Power and Transmission Cable
No. x mm
2
(Outdoor to Indoor or Outdoor to BD)
Power and Transmission Cable(BD to Indoor) No. x mm
2
Dimensions W x H x D mm(inch)
Net Weight kg(lbs)
Max. Number of Connectable Indoor Units
Compressor (#1) Type
Qty x Model
Motor type
Oil charge volume cc
Oil Type
Compressor (#2) Type
Qty x Model
Motor type
Oil charge volume cc
Oil type
Compressor (#3) Type
Qty x Model
Motor type
Oil charge volume cc
Oil type
Refrigerant Cycle A Charge (at 7.5m) g(oz)
Cycle B Charge (at 7.5m) g(oz)
Type
Control
Heat Exchanger (Rows x Column x FPI) x No.
Defrosting Method
Fan Capacitor µF/Vac
Drive
Discharge Direction(Side/Top)
Air Flow Rate x No. of Fan CMM(cfm)
Sound Level(H/L) Sound Pressure dB(A)+3
Piping Connections Liquid(Cycle A) mm(inch)
Gas(Cycle A) mm(inch)
Liquid(Cycle B) mm(inch)
Gas(Cycle B) mm(inch)
High Pressure Gas mm(inch)
Max. Interunit Total Piping m
Piping Length Main Piping m
Total Branch Piping m
Each Branch Piping m
Max. Elevation Outdoor Unit~Indoor Unit m
Difference Indoor Unit~Indoor Unit m
Outdoor Unit
ABUH366KSA0
10.00
34,120
10.25
34,973
3.9
3.4
18
15
40/-
1/220_240/50
3 x 5.5
5x1.0 (Including Earth)
-
870 x 1060 x 320(34.3 x 41.7 x 22.0)
80(176)
1
Rotary
1 x NN40VAAMT
Permenant Split Capacitor
1,300
MEL 56
-
-
-
-
-
-
-
-
-
-
3,250(145)
-
R410A
Capillary
(2R x 52C x 18) x 1
Reversing Cycle
-
Direct Drive
Side
53(1,872) x 2
58
9.52(3/8)
15.88(5/8)
-
-
30
7.5
-
15
-
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without notic for purpose of improvement.