1. Specification
Nominal Capacity Cooling kW (Min~Rated~Max) Btu/h
Heating kW
Btu/h Nominal Input Cooling kW (Min~Rated~Max) Heating kW Energy label Testing Combination Running Current Cooling A
Heating A Starting Current (Cooling/Heating) A Power Supply Ø / V / Hz Power Supply Cable (outdoor) No.x mm
2
Power and transmission cable (outdoor to BD) No.x mm
2
Power and transmission cable (BD to indoor) No.x mm
2
Dimensions W*H*D mm(inch) Net Weight kg(lbs) Max. Number of Connectable Indoor Units Compressor (Inverter) Type
Qty x Model
Motor Type
Oil Charge volume cc
Oil Type Refrigerant Charge (at 5m) g(oz)
Type
Control Heat Exchanger Rows x Column x FPI
Defrosting Method Fan Capacitor µF/Vac
Drive
Discharge direction Side / Top
Air Flow Rate CMM(CFM) Noise Level(H/L) Sound Pressure at 1m dB(A)±3 Piping connections Liquid(Ø) mm(inch)
Gas(Ø) mm(inch) Max. Interunit Piping Length Total Piping(Main+Total Branch) m
Main Piping m
Total Branch Piping m
Each Branch Piping m Max. Elevation Difference Indoor Unit~Outdoor Unit m
Indoor Unit~Indoor Unit m
Outdoor Unit
A9UW566FA3[FM56AH U33]
4.0~16.7~18.52
13,800~57,000~63,200
4.5~17.87~18.75
15,456~61,000~64,000
1.0~4.96~5.65
1.25~4.62~5.70 A/A
MS09AH N40*8EA
4.6~21.7~24
7.4~22.4~26
-
1/220~240/50
3*4.0 4*1.25(Including Earth) 4*0.75(Including Earth)
950*1380*330 (37.4*54.3*12.3)
108(238.1)
9
Twin-Rotary
5JD420Z
BLDC
1300
FV50S
4800(169.3)
R410A
EEV
2R x 64C x 17
Reversing cycle
-
DC
Side
60(2,119) x 2
59
9.52(3/8)
19.05(3/4) 145
55 90 15 30 15
Note:
1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Conversion Formula kW = Btu/h x 0.0002931 cfm = CMM x 35.3
- 3 -
Copyright ©2007 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
2. List of Functions
Defrost / Deicing High Pressure Switch Low Pressure Switch Phase protection Restart Delay (3-minutes) Self Diagnosis Soft Start Test Function Auto Operation(Artificial intelligence) Auto Restart Operation Central control(LGAP) PDI(Power Distribution Indicator) PI485 Low Ambient Kit Thermistor
FunctionCategory
A9UW566FA3[FM56AH U33]
Reliability
Convenience
Special Function Kit Others
CAC Network Function
O
X
O
X O O O
X O O O
PQNUD1S00 PMNFP14A0
O(Logic)
-
Note :
O : Applied, X : Not applied, – : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.