Installation
Read completely, then follow step by step.
1. Installation of Indoor, Outdoor unit
1) Select the best location
1. Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in
Make sure that condensation drainage can be conveniently routed away.
Do not install near a doorway.
Ensure that the space around the left and right of
the unit is more than 5cm. The unit should be installed as high on the wall as possible, allowing a minimum of 5cm from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
2. Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where noise and vibration are mini­mum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations: If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
2) Piping length and elevation
More than 5cm
More than 5cm
More than 2.3m
More than 5cm
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
In case more than 5m
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7 meters.
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
CAUTION
18K(60Hz) 5/8" 1/4" 5 10 20 20 18K(50Hz) 1/2" 1/4" 5 15 30 30 24K(50Hz) 5/8" 3/8" 5 15 30 30 26K(50Hz) 5/8" 3/8" 5 15 30 30
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
- 24 -
3) How to fix installation plate
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
§ Mount the installation plate horizontally by align-
ing the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping con­nections must be done safely.
5-7mm
(0.2~0.3")
Indoor
WALL
Outdoor
Installation Plate
Marking-off line
Thread
Weight
Type "A" screw
"D" "C"
Right rear pipingLeft rear piping
Hole center
ø70mm
4) Drill a hole in the wall
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
- 25 -
1) Flaring work
Main cause for gas leakage is due to defect in flar­ing work. Carry out correct flaring work in the follow­ing procedure.
1. Cut the pipes and the cable.
Use the piping kit accessory or the pipes pur­chased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than measured dis­tance.
Cut the cable 1.5m longer than the pipe length.
2. Burrs removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a down­ward direction as you remove burrs in order to avoid dropping burrs into the tubing.
3. Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having complet­ed burr removal. (not possible to put them on after flaring work)
Copper
pipe
90°
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Pipe
Reamer
Point down
4. Flaring work
Carry out flaring work using flaring tool as shown below.
Firmly hold copper pipe in a die in the dimension shown in the table above.
5. Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared
section and do flaring work again.
Outside diameter A
mm inch mm ø6.35 1/4 0 ~ 0.5 ø9.52 3/8 0 ~ 0.5 ø12.7 1/2 0 ~ 0.5
ø15.88 5/8 0 ~ 1.0
Flare nut
Copper tube
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
2. Flaring Work and Connection of Piping
- 26 -
2) Connection of piping-Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
Remove the plastic tubing retainer(see illustra­tion below) and pull the tubing and drain hose
away from chassis.
Replace the plastic tubing holder in the original position.
1. Route the indoor tubing and the drain hose in the direction of rear left.
2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy con-
nection later.
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the
rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by mov­ing it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
5. Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipings and sufficiently tighten the flare nut by hand.
NOTE:
If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
To remove the holder, press the bottom of chassis near the holder upward and pull the tab out of its hole.
Tubing holder
Pull
Press
2
1
Connecting cable
Loop
Gas side piping
Liquid side piping
Drain hose
Drain hose
Connecting
cable
Drain hose
Indoor unit tubing Flare nut Pipings
For left rear piping
CAUTION
When install, make sure that the remaining parts must be removed clearly so as not to damage the piping and drain hose, especially power cord and connecting cable.