LG A2UW18GFAA INSTALLATION MANUAL

P/NO : MFL68883813
INSTALLATION MANUAL
AIR CONDITIONER
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Ɠ
This product contains Fluorinated Greenhouse Gases. (R410A)
Multi Standard
Original instruction
www.lg.com
Copyright © 2017 LG Electronics Inc. All Rights Reserved.
ENGLISH ESPAÑOL
PORTUGUÊS
IMPORTANT SAFETY INSTRUCTIONS
2
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situa­tions and ensure peak performance of your product
WARNING
!
It can result in serious injury or death when the directions are ignored
CAUTION
!
It can result in minor injury or product damage when the directions are ignored
WARNING
!
• Installation or repairs made by unqualified persons can result in haz­ards to you and others.
• Installation work must be performed in accordance with the National Electric Code by qualified and authorized personnel only.
• The information contained in the manual is intended for use by a quali­fied service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Do not use a defective or underrated circuit breaker. Use the correctly rated breaker and fuse. There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center. Do not disassemble or repair the prod­uct by yourself. There is risk of fire or electric shock.
• Always ground the product as per the wiring diagram. Do not connect the ground wire to gas or water pipes lightening rod or telephone ground wire. There is risk of fire or electric shock.
• Install the panel and the cover of control box securely. There is risk of fire or electric shock due to dust , water etc.
• Use the correctly rated breaker or fuse. There is risk of fire or electric shock.
IMPORTANT SAFETY INSTRUCTIONS
3
ENGLISH
• Do not modify or extend the power cable. If the power cable or cord has scrathes or skin peeled off or deteriorated then it must be replaced. There is risk of fire or electric shock.
• For installation, removal or reinstall , always contact the dealer or an Authorized Service Center. There is risk of fire, electric shock, explo­sion, or injury.
• Do not install the product on a defective installation stand. Be sure that the installation area does not deteriorate with age. It may cause product to fall.
• Never install the outdoor unit on a moving base or a place from where it can fall down. The falling outdoor unit can cause damage or injury or even death of a person.
• In outdoor unit the step-up capacitor supplies high voltage electricity to the electrical components. Be sure to discharge the capacitor com­pletely before conducting the repair work. An charged capacitor can cause electrical shock.
• When installing the unit, use the installation kit provided with the product. Otherwise the unit may fall and cause severe injury.
• Indoor/outdoor wiring connections must be secured tightly and the cable should be routed properly so that there is no force pulling the cable from the connection terminals. Improper or loose connections can cause heat generation or fire.
• Safely dispose off the packing materials. Like screws, nails, batteries, broken things etc after installation or svc and then tear away and throw away the plastic packaging bags. Children may play with them and cause injury.
• Be sure to check the refrigerant to be used. Please read the label on the product. Incorrect refrigerant used can prevent the normal opera­tion of the unit.
Operation
• When the product is soaked (flooded or submerged) in water , contact an Authorized Service Center for repair before using it again. There is risk of fire or eletric shock.
• Be sure to use only those parts which are listed in the svc parts list. Never attempt to modify the equipment. The use of inappropriate parts can cause an electrical shock, excessive heat generation or fire.
• Do not touch , operate, or repair the product with wet hands. Hold the plug by hand when taking out. There is risk of electric shock or fire.
IMPORTANT SAFETY INSTRUCTIONS
4
ENGLISH
• Do not place a heater or other heating appliances near the power cable. There is risk of fire and electric shock.
• Do not allow water to run into electric parts. Install the unit away from water sources. There is risk of fire, failure of the product, or electric shock.
• Do not store or use or even allow flammable gas or combustibles near the product. There is risk of fire.
• Do not use the product in a tightly closed space for a long time. Perform ventilation regularly. Oxygen deficiency could occur and hence harm your health.
• Do not open the front grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) There is risk of physical injury, electric shock, or product failure.
• If strange sound, smell or smoke comes from product.Immediately turn the breaker off or disconnect the power supply cable. There is risk of electric shock or fire.
• Ventilate the product room from time to time when operating it together with a stove, or heating element etc. Oxygen deficiency can occur and hence harm your health.
• When the product is not to be used for a long time, disconnect the power supply plug or turn off the breaker. There is risk of product damage or failure, or unintended operation.
• Take care to ensure that nobody especially kids could step on or fall onto the outdoor unit. This could result in personal injury and product damage.
• Take care to ensure that power cable could not be pulled out or dam­aged during operation. There is risk of fire or electric shock.
• Do not place ANYTHING on the power cable. There is risk of fire or electric shock.
• When flammable gas leaks, turn off the gas and open a window for ventilation befor turning on the product. Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
CAUTION
!
Installation
• Two or more people must lift and transport the product. Avoid person­al injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly. It may cause corrosion on the product.
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
• Install the drain hose to ensure that the condensed water is drained away properly. A bad connection may cause water leakage.
• Keep level even when installing the product. To avoid vibration or noise.
• Do not install the product where the noise or hot air from the outdoor unit could damage or disturb the neighborhoods. It may cause a prob­lem for your neighbors and hence dispute.
• Always check for gas (refrigerant) leakage after installation or repair of product. Low refrigerant levels may cause failure of product.
• Please install safely at a place that can sufficiently endure the weight of the product. If the strength is not sufficient, the product may fall and cause injury.
Operation
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a preci­sion refrigeration system. There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow. It may cause product fail­ure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents or splashing water etc. There is risk of fire, electric shock, or damage to the plastic parts of the product.
• Do not touch the metal parts of the product when removing the air fil­ter. There is risk of personal injury.
• Do not step on or put anyting on the product. (outdoor units) There is risk of personal injury and failure of product.
• Always insert the filter securely after cleaning. Clean the filter every two weeks or more often if necessary. A dirty filter reduces the effi­ciency.
• Do not insert hands or other objects through the air inlet or outlet while the product is operating. There are sharp and moving parts that could cause personal injury.
• Be cautious when unpacking and installing the product. Sharp edges could cause injury.
• If the refrigerant gas leaks during the repair, do not touch the leakaing refrigerant gas. The refrigernat gas can cause frostbite (cold burn).
• Do not tilt the unit when removing or uninstalling it. The condensed water inside can spill.
IMPORTANT SAFETY INSTRUCTIONS
6
ENGLISH
• Do not mix air or gas other than the specified refrigerant used in the system. If air enters the refrigerant system, an excessively high pres­sure results, causing equipment damage or injury.
• If the refrigerant gas leaks during the installation, ventilate the area immediately. Otherwise it can be harmfull for your health.
• Dismantling the unit, treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards.
• Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of bat­teries. There is risk of fire or product failure.
• Do not recharge or disassemble the batteries. Do not dispose off bat­teries in a fire. They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.
• If you eat the liquid from the batteries, brush your teeth and see doc­tor. Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open. Moisture may con­dense and wet or damage furniture.
• Do not expose your skin or kids or plants to the cool or hot air draft. This could harm to your health.
• Do not drink the water drained from the product. It is not sanitary and could cause serious health issues.
• Use a firm stool or ladder when cleaning, maintaining or repairing the product at an height. Be careful and avoid personal injury.
TABLE OF CONTENTS
TABLE OF CONTENTS
7
ENGLISH
2 IMPORTANT SAFETY
INSTRUCTIONS
8 INSTALLATION 9 INSTALLATION OF
INDOOR, OUTDOOR UNIT
9 Select the best location 10 Fixing Installation Plate 11 Piping length and elevation 11 Refrigerant charge 12 Drill a hole in the wall
12 INSTALLATION OF
WIRED REMOTE CON­TROLLER
14 Wired remote controller installation
15 FLARING WORK AND
CONNECTION OF PIPING
15 Flaring work 16 Connection of piping - Indoor 18 Connection of piping - Outdoor
19 CONNECTING THE CABLE
BETWEEN INDOOR UNIT AND OUTDOOR UNIT
19 Connect the cable to the Indoor unit 21 Connect the cable to the Outdoor unit
25 AIR PURGING AND EVAC-
UATION
25 Checking method 26 Evacuation
27 INSTALLATION PI485 28 TEST RUNNING 29 FUNCTION
29 Dip S/W Setting 30 Forced Cooling Operation 31 Wiring Error Check 31 Saving Power Consumption 32 Night Quiet Mode 33 Mode Lock 33 SLC (Smart Load Control) Mode 34 PCB Display(18/24 k Model Only)
35 MAX COMBINATION
CAPACITY
36 INSTALLATION GUIDE AT
THE SEASIDE
36 SEASONAL WIND AND
CAUTIONS IN WINTER
37 Airborne Noise Emission 37 Limiting concentration
23 CHECKING THE
DRAINAGE AND FORM­ING THE PIPINGS
23 Checking the Drainage 24 Forming the Piping
INSTALLATION
Installation plate
Type "B" screws
Type "A" screw (6 EA) Type "A" screw (8 EA) Type "A" screw (7 EA)
Holder Remote Control
Type "A" screw and plastic anchors
500(19-11
/16
) or
le
ss
8
ENGLISH
INSTALLATION
Installation Parts
Clearance of side discharge unit [Unit : mm(inch)]
Do not install the product where sufficient ventilation is not secured. The performance may be decreased or the product may not be operated.
s
les
300(11-13/16) or
more
500(19-11/16) or
600(23-19/ or
more
32)
600(23-19/32) or more
1000(39-3/8) or more
300(11-13/16)
or more
ss
ss
e
rom
or
more
ro )8/
3-9 3(0001
H
more
300(11-13/16)
or
500(19-11/16) or le
500(19-11/16) or le
D
L
1000(39-3/8)
h In case of series or another installation, please refer to related PDB.
39-3/8) or more
( 0 001
300(11-13/16)
or more
300(11-13/16) or more
2000(78-3/4) or more
INSTALLATION OF INDOOR, OUTDOOR UNIT
More than 20cm
More than
10cm
More than 2.3m
More than
10cm
More than 20cm
More than
10cm
More than 2.3m
More than
10cm
More than 20cm
More than
10cm
More than 2.3m
More than
10cm
more than
70cm
more than
30cm
more than 60cm
more than
30cm
more than
60cm
INSTALLATION OF INDOOR, OUTDOOR UNIT
9
ENGLISH
Read completely, then follow step by step. You need to select adequate installation location
considering the following conditions, and make sure to acquire the consent of the user.
Select the best location
1 Do not have any heat or steam near the unit. 2 Select a place where there are no obstacles
3 Make sure that condensation drainage can be
4 Do not install near a doorway. 5
6 Use a stud finder to locate studs to prevent
Indoor unit
in front of the unit.
conveniently routed away.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
unnecessary damage to the wall.
CAUTION
!
Install the indoor unit on the wall where the height from the floors more than 2.3 meters. (ART COOL Type Only 1.5m)
Outdoor unit
1 If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2 Ensure that the spaces indicated by arrows
around front, back and side of the unit.
3 Do not place animals and plants in the path of
the warm air.
4 Take the air conditioner weight into account
and select a place where noise and vibration are minimum.
5 Select a place so that the warm air and noise
from the air conditioner do not disturb neigh­bors.
6 Place that can sufficiently endure the weight
and vibration of the outdoor unit and where even installation is possible.
7 Place that has no direct influence of snow or
rain.
8 Place with no danger of snowfall or icicle
drop.
9 Place without weak floor or base such as
decrepit part of the building or with a lot of snow accumulation.
10 Sufficient ventilation is secured.
Rooftop Installations
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof struc­ture and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
10
Chassis
Hook
Installation Plate
Type “A”
Installation Plate
Type “A”
Installation Plate
Chassis
Hook
Type "A" Screws
Unit Outline
Left Rear Piping
Right Rear Piping
Place a level on raised tab
(Unit : mm)
Installation plate
Ø65
Ø65
184
220
156
307
460 567
Chassis
Hook
Installation Plate
Type “A”
Installation plate
Left rear piping Right rear piping
Ø65
Ø65
105mm
105mm
65mm
55mm
45mm
140mm
Ø65
65mm65mm
65mm
45mm
Ø65
Installation plate
Left rear piping Right rear piping
Installation plate
Left rear piping Right rear piping
Ø65
133mm
101mm
101mm
Ø65
100mm
ENGLISH
INSTALLATION OF INDOOR, OUTDOOR UNIT
Fixing Installation Plate
The wall you select should be strong and solid enough to prevent vibration
1 Mount the installation plate on the wall
with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
- Mount the installation plate horizontally by aligning the centerline using a level.
<Type 1>
2 Measure the wall and mark the centerline.
It is also important to use caution concern­ing the location of the installation plate­routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
<Type 2>
Indoor Type
Wall mounted
<Type 1>
<Type 2>
<Type 3>
Capacity
(kBtu/h)
9, 12 1, 3
18 2, 4
Type
<Type 3>
<Type 4>
<Type 4>
INSTALLATION OF INDOOR, OUTDOOR UNIT
Piping length and elevation
Multiple Piping Models (Unit: m)
Phase
Capacity
(kBtu/h)
18 30 20 15 7.5 24 50 25 15 7.5 36 75 25 15 7.5
Total Length
Max Length
(A/B)
Max Elevation
(h1)
In-In Elevation
(h2)
11
ENGLISH
A
h2
h1
B
Multiple Piping Type
CAUTION
!
Capacity is based on standard length and maximum allowance length is on the basis of reliability. If outdoor unit is at higher elevation than the indoor units, after 24m of vertical height, 1 oil trap is required.
Refrigerant charge
The calculation of the additional charge should be taken in account for the length of extra pipe.
Multiple Piping Models (Unit: m)
Phase
• Multiple Piping Models Additional charge (g) = ((A Room Installation Length – Standard Length ) x 20g/m
h CF = Max. number of connectable indoor unit – Total number of connected indoor unit
Capacity
(kBtu/h)
18 7.5 20 30 20 20 24 7.5 25 50 22.5 20 36 7.5 25 75 37.5 20
Standard
Length (m)
+ (B Room Installation Length – Standard Length ) x 20g/m +.. )
- CF(Correction Factor) x 150
Max Piping for
one room (m)
Max total
Piping Length
Chargeless
Length
Charge (g/m)
Additional
INSTALLATION OF WIRED REMOTE CONTROLLER
2
2
1
3
3
<Wire guide grooves>
12
ENGLISH
Drill a hole in the wall
Drill the piping hole with a Ø65mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
WALL
Indoor
Outdoor
5-7mm
(3/16"~5/16")
INSTALLATION OF WIRED REMOTE CON­TROLLER
1 Please fix tightly using provided screw after placing remote controller setup board on the
place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends. Please set up remote controller board fit to the reclamation box if there is a reclamation box.
2 Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing remote controller cable guide groove.
h Remove guide groove with long nose.
Reclamation to the surface of the wallUpper part guide grooveRight part guide groove