LG 395CAV User Manual

Page 1
installation instructions
395CAV
and operating instructions
UPFLOW GAS-FIRED INDUCED-COMBUSTION FURNACES
NOTE: Read the entire instruction manual before starting the installation.
This symbol indicates a change since the last issue. Index Page
SAFETY CONSIDERATIONS.....................................................1
Clearances From Combustible Materials.................................1
Dimensional Drawing...............................................................2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE........................................................................2-3
INTRODUCTION..........................................................................3
LOCATION....................................................................................3
General......................................................................................3
Location Relative to Cooling Equipment ................................3
Hazardous Locations.................................................................3
Unconfined Space.....................................................................4
Confined Space......................................................................4-5
FILTER ARRANGEMENT .......................................................5-6
GAS PIPING...............................................................................6-7
ELECTRICAL CONNECTIONS..................................................7
115-v Wiring.............................................................................7
24-v Wiring...............................................................................7
Accessories................................................................................7
VENTING ......................................................................................7
General...................................................................................7-8
Sequence Of Operation .......................................................8-11
Heating Mode............................................................................9
Cooling Mode......................................................................9-11
Continuous Blower Mode.......................................................11
Heat Pump Mode....................................................................11
Start-Up Procedures................................................................11
Adjustments .......................................................................11-14
Set Gas Input Rate ............................................................11-13
Set Temperature Rise..............................................................13
Set Thermostat Heat Anticipator............................................14
Check Safety Controls .................................................................14
Checklist.......................................................................................14
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified person­nel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA No. 54-1992/ANSI Z223.1-1992. In Canada, refer to the current edition of the National Standard of Canada CAN/CGA-B149.1-
Series G
Cancels: II 395C-40-9 II 395C-40-10
1-96
®
and .2-M95 Natural Gas and Propane Installation Codes (NSC­NGPIC). Wear safety glasses and work gloves. Have fire extin­guisher available during start-up and adjustment procedures and service calls.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residen­tial construction practices. We require these instructions as a minimum for a safe installation.
TABLE 1—MINIMUM CLEARANCES FROM
COMBUSTIBLE MATERIALS (IN.)
UNIT SIZE 045 AND 070 091-155
Sides Single-Wall Vent 1 0
Type B-1 Double-Wall Vent 0 0
Back 00
Plenum Top 11
Vent Single-Wall Vent 6 6
Type B-1 Double-Wall Vent 1 1
Front Single-Wall Vent 6 6
Type B-1 Double-Wall Vent 3 3 Service 30 30
NOTES:
1. Provide 30-in. front clearance for servicing. An open door in front of the unit can meet this requirement.
2. A minimum clearance of 3 in. must be provided in front of the unit for combustion air and proper operation.
ama
CANADIAN GAS ASSOCIATION
APPROVED
R
.
—1—
Page 2
39 7⁄8
28 1⁄2
FLUE COLLAR
7
8-IN. DIA HOLE
POWER ENTRY
7
8-IN. DIA
ACCESSORY
1 3⁄4-IN. DIA HOLE
GAS ENTRY
1
2-IN. DIA HOLE
THERMOSTAT
WIRE ENTRY
2 1⁄16 1
5 3⁄8
5 13⁄16
2 3⁄8
12 5⁄16
AIRFLOW
A D
13
16
5 3⁄8
5 13⁄16
2 3⁄8
2 11⁄16
2 1⁄16
1
7
8-IN. DIA
POWER ENTRY
1 1⁄2-IN. DIA R.H. GAS ENTRY
7
8-IN. DIA ACCESSORY
1
2-IN. DIA THERMOSTAT
WIRE ENTRY
19
OUTLET
13
16
SIDE INLET
TYP 1
11
11
16
24 5⁄16
AIR INLET
3
NOTES:
11
16
E
1. Two additional 7⁄8-in. dia knockouts are located in the top plate.
16
5
TYP
8″
SIDE INLET
231⁄4″
SIDE RETURN
DUCT LOCATION
2. Minimum return-air opening at furnace: a. For 800 CFM–16-in. round or 141⁄2 x 12-in. rectangle. b. For 1200 CFM–20-in. round or 141⁄2 x 191⁄2-in. rectangle. c. For 1600 CFM–22-in. round or 141⁄2 x 231⁄4-in. rectangle. d. For airflow requirements above 1800 CFM, use both side inlets, a combination of 1 side inlet and the bottom, or the bottom only.
Fig. 1—Dimensional Drawing
TABLE 2—DIMENSIONS (IN.)
UNIT SIZE A D E VENT CONN SHIP. WT (LB)
024045 14-3/16 12-9/16 12-11/16 4 122 036045 14-3/16 12-9/16 12-11/16 4 124 024070 14-3/16 12-9/16 12-11/16 4 132 036070 14-3/16 12-9/16 12-11/16 4 134 042091 17-1/2 15-7/8 16 4 150 048091 21 19-3/8 19-1/2 4 154 036110 17-1/2 15-7/8 16 4 160 048111 21 19-3/8 19-1/2 4 166 060111 24-1/2 22-7/8 23 4 184 048135 21 19-3/8 19-1/2 5 178 060135 24-1/2 22-7/8 23 5 194 060155 24-1/2 22-7/8 23 5 204
141⁄2
3
4
1
1
A88367
PROCEDURE
CAUTION: Electrostatic discharge can affect electronic
components. Take precautions during furnace installation
and servicing to protect the furnace electronic control.
Precautions will prevent electrostatic discharges from
personnel and hand tools which are held during the
procedure. These precautions will help to avoid exposing
the control to electrostatic discharge by putting the
furnace, the control, and the person at the same electro-
static potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch un­grounded objects, etc.).
—2—
Page 3
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touch­ing control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
INTRODUCTION
The Model 395CAV, Series G Furnace is available in sizes 45,000 through 155,000 Btuh input capacities.
Installation must conform to the regulations of the serving gas supplier and the local building, heating, and plumbing codes in effect in the area in which the installation is made, or in the absence of local codes with the requirements of the NFGC.
CAUTION: Application of this furnace should be in­doors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause prema­ture component failure.
This furnace is designed for a minimum continuous return-air temperature of 60°F db or an intermittent operation down to 55°F db such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F db.
WARNING: Improper installation, adjustment, alter­ation, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product. Failure to follow this warning can cause electrical shock, fire, personal injury, or death.
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
I. LOCATION A. General
CAUTION: Do not install furnace in a corrosive or
contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
CAUTION: Do not use this furnace during construction when adhesives, sealers, and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which cause corrosion of the heat exchangers and metal vent system. Some of these compounds are found in paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction pro­cess. Excessive exposure to contaminated combustion air will result in safety and performance related problems.
This furnace must be installed so the electrical components are protected from water. This furnace shall not be installed directly on carpeting, tile, or any combustible material other than wood flooring.
Locate furnace as close to the chimney/vent and as near the center of the air distribution system as possible. The furnace should be installed as level as possible.
When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Provide ample space for servicing and cleaning. Always comply with the minimum fire protection clearances shown on the unit rating plate.
B. Location Relative to Cooling Equipment
The cooling coil must be installed parallel with or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
C. Hazardous Locations
When the furnace is installed in a residential garage, it must be installed so that the burners and ignition source are located at least 18 in. above the floor. The furnace should be protected from physical damage by vehicles. When a furnace is installed in public garages, airplane hangars, or other buildings having hazardous atmospheres, the unit must be installed in accordance with the recommended good practice requirements of the National Fire Protection Association, Inc.
II. AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3 of the NFGC, Air for Combustion and Ventilation, or applicable provisions of the local building codes.
Canadian installations must be installed in accordance with NSC­NGPIC and all authorities having jurisdiction.
—3—
Page 4
CAUTION: Air for combustion must not be contami­nated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
SUPPLY
AIR
VENT THROUGH ROOF
All fuel-burning equipment must be supplied with air for combus­tion of the fuel. Sufficient air MUST be provided to ensure there will not be a negative pressure in the equipment room or space. In addition, a positive seal MUST be made between the furnace cabinet and the return-air duct to prevent pulling air from the burner area and draft safeguard opening.
CAUTION: The operation of exhaust fans, kitchen ven­tilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST BE PROVIDED for the ventilation devices, in addition to that required by the furnace.
The requirements for combustion and ventilation air depend upon whether the furnace is located in an unconfined or confined space.
A. Unconfined Space
An unconfined space must have at least 50 cubic ft for each 1000 Btuh of input for all the appliances (such as furnaces, clothes dryer, water heaters, etc.) in the space.
For Example:
395CAV FURNACE
INPUT BTUH
44,000 293 66,000 440
88,000 587 110,000 733 132,000 880 154,000 1026
MINIMUM SQ FT WITH
7-1/2 FT CEILING
If the unconfined space is constructed unusually tight, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined space. A minimum opening with a total of at least 1 sq in. per 5000 Btuh of total input rating for all equipment must be provided. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room.
B. Confined Space
A confined space has volume less than 50 cu ft per 1000 Btuh of the total input rating for all appliances installed in that space. A confined space MUST have 2 permanent openings, 1 within 12 in. of the ceiling and the other within 12 in. of the floor. (See Fig. 2.)
NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens must be considered. If the free area of a louver or grille design is unknown, it may be assumed that wood louvers have a 20 percent free area, and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.
The size of the openings depends upon whether the air comes from inside or outside of the structure.
1. All air from inside the structure: a. Each opening MUST have at least 1 sq in. of free area
per 1000 Btuh of the total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 2.)
12 MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
INTERIOR
HEATED
SPACE
RETURN AIR
* Minimum opening size is 100 square in. with minimum dimensions of 3-In.
Minimum of 3-In. when type-B1 vent is used.
UNCONFINED SPACE
CONFINED
SPACE
6 MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
12 MAX
A89012
Fig. 2—Air For Combustion and Ventilation (Inside Air)
For Example:
395CAV FURNACE
INPUT BTUH
44,000 100 66,000 100
88,000 100 110,000 110 132,000 132 154,000 154
FREE AREA PER OPENING
(SQ IN.)
b. If the building is constructed unusually tight, a perma-
nent opening directly communicating with the outdoors should be provided. This opening shall have a minimum free area of 1 sq in. per 5000 Btuh of total input rating for all equipment in the enclosure.
c. If the furnace is installed on a raised platform to provide
a return-air plenum, and return air is taken directly from the hallway or space adjacent to the furnace, all air for combustion must come from outdoors.
2. All air from outside the structure: a. If combustion air is taken from outdoors through vertical
ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of the total input for all equipment within the confined space. (See Fig. 3.)
b. If combustion air is taken from the outdoors through
horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of the total input for all equipment within the confined space.
—4—
Page 5
For Example:
395CAV FURNACE
INPUT BTUH
44,000 11.0 4 66,000 16.5 5
88,000 22.0 6 110,000 27.5 6 132,000 33.0 7 154,000 38.5 7
FREE AREA PER OPENING
(SQ IN.)
For Example:
395CAV FURNACE
INPUT BTUH
44,000 22.0 6
66,000 33.0 7
88,000 44.0 8 110,000 55.0 9 132,000 66.0 10 154,000 77.0 10
FREE AREA PER OPENING
(SQ IN.)
c. When ducts are used, they must be of the same cross-
sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular ducts must not be less than 3 in. (See Fig. 3.)
ROUND PIPE
(IN. DIA)
ROUND PIPE
(IN. DIA)
WARNING: Do not install the furnace on its back;
safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace. A failure to follow this warning can cause a fire, personal injury, or death.
III. FILTER ARRANGEMENT
The factory-supplied filter(s) is shipped in the blower compart­ment. Determine location for the filter and relocate filter retaining wire if necessary. See Fig. 4 for side return application and Fig. 5 for bottom return application. See Table 3 to determine correct filter size for desired filter location. Table 3 indicates filter size, location, and quantity shipped with the furnace.
WASHABLE
FILTER
FILTER RETAINER
DUCTS
A
B
TO
SUPPLY
AIR
D
VENT THROUGH ROOF
CONFINED
C
DUCT
TO
OUTDOORS
OUTDOORS
12 MAX
1 SQ IN. PER 2000 BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
12
MAX
RETURN AIR
*Minimum dimensions of 3-In.
Use any of the following
NOTE:
combinations of openings: A & B C & D D & E F & G
Fig. 3—Air For Combustion and Ventilation
(Outside Air)
SPACE
E
12 MAX
1 SQ IN. PER 4000 BTUH*
F
1 SQ IN.
BTUH*
1 SQ IN.
BTUH*
G
1 SQ IN. PER 4000 BTUH*
12 MAX
PER
4000
OUTDOORS
PER 4000
12 MAX
A89013
A93045
Fig. 4—Side Filter Arrangement
(Control Removed for Clarity)
For bottom air-return applications, filter may need to be cut to fit some furnace casing widths. A bottom closure panel is factory installed in the bottom of the furnace. When bottom return inlet is desired, remove and discard the bottom closure panel. Remove side clip(s) and install in hole. Two sets of hardware are needed for furnaces in 24-1/2-in. wide casings using 2 filters for bottom return. All hardware is provided for filter installation.
NOTE: Furnaces with a 17-1/2-in. wide casing require an addi­tional procedure when locating the filter for bottom return-air application. Field fabricate a sheet metal filler strip1X3X24-1/2 in. and install it along side of the filter as shown in Fig. 5. Drive 2 screws through the casing side and into the filler strip to secure it in place. Filter should rest on the top of the filler strip when installed.
WARNING: Never operate unit without a filter or with filter access door removed. Failure to follow this warning can cause fire, personal injury, or death.
IV. LEVELING LEGS (IF REQUIRED)
When the furnace is used with side inlet(s) and leveling legs are required, refer to Fig. 6, and install field-supplied, corrosion­resistant 5/16-in. machine bolts and nuts.
NOTE: The maximum length of the bolt should not exceed 1-1/2 in.
1. Lay furnace on its back. Locate and drill 5/16-in. diameter hole in each bottom corner of furnace as shown in Fig. 6.
2. Install nut on bolt and install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
—5—
Page 6
171⁄2-IN. WIDE  CASINGS ONLY:
INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER.
3
1
24
/2″
1
FILTER SUPPORT
241⁄2-IN. WIDE  CASINGS ONLY:
CUT AND FOLD FACTORY-PROVIDED FILTERS AS SHOWN TO DESIRED SIZE.
WASHABLE FILTER
FILTER RETAINER
A96030
Fig. 5—Bottom Filter Arrangement
(Control Removed for Clarity)
TABLE 3—FILTER INFORMATION (IN.)
FURNACE
CASING WIDTH
14-3/16 (1) 16 X 25 X 1† (1) 14 X 25 X 1 Cleanable
17-1/2 (1) 16 X 25 X 1† (1) 16 X 25 X 1 Cleanable
21 (1) 16 X 25 X 1 (1) 20 X 25 X 1† Cleanable
24-1/2 (2) 16 X 25 X 1† (1) 24 X 25 X 1 Cleanable
* Filters can be field modified by cutting the frame as marked and folding to the desired size. Alternate sizes can be ordered from your distributor or dealer. † Factory-provided with the furnace.
FILTER SIZE*
Side Return Bottom Return
FILTER TYPE
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
V. GAS PIPING
Refer to Table 4 for the recommended gas pipe size. Risers must be used to connect to the furnace and the meter.
5
16
5
16
1 3⁄4
3
4
1
5
16
5
16
1 3⁄4
1 3⁄4
Fig. 6—Leveling Leg Installation
TABLE 4—MAXIMUM CAPACITY OF PIPE*
NOMINAL IRON
PIPE SIZE
(IN.)
1/2 0.622 175 120 97 82 73 3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285 1-1/4 1.380 1400 950 770 660 580 1-1/2 1.610 2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 10-2 NFPA 54-1992.
INTERNAL DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
CAUTION: If a flexible connector is required or al­lowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and extend a minimum of 2 in. outside the furnace casing.
Piping should be pressure tested in accordance with local and
national plumbing and gas codes before the furnace has been attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe must be disconnected from the furnace and capped before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), turn off electric shutoff switch located on the gas valve before the test. It is recommended that the ground joint union be loosened before pressure testing. After all connections have been made, purge the lines and check for leakage with regulated gas supply pressure. Install a sediment trap in the riser leading to the furnace. The trap can be installed by connecting a tee to the riser leading from the furnace. Connect a capped nipple into the lower end of the tee. The capped nipple should extend below the level of the gas controls. (See Fig. 7.) Apply joint compound (pipe dope) sparingly and only to the male threads of each joint. The compound must be resistant to the action of propane gas.
An accessible manual shutoff valve MUST be installed upstream of the furnace gas controls and within 72 in. of the furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of the gas supply connection to the furnace and downstream of the manual shutoff valve. Place ground joint union between the gas control manifold and the manual shutoff valve.
A89014
—6—
Page 7
GAS
SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
WARNING: The cabinet MUST have an uninterrupted or unbroken ground according to NEC, ANSI/NFPA 70-1996 and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death.
SEDIMENT TRAP
UNION
VI. ELECTRICAL CONNECTIONS A. 115-v Wiring
Refer to the unit rating plate or Table 5 for equipment electrical requirements. The control system requires an earth ground for proper operation.
Make all electrical connections in accordance with the National
Electrical Code (NEC) ANSI/NFPA 70-1996 and local codes or ordinances that might apply. For Canadian installations, all elec­trical connections must be made in accordance with CSA C22.1 Canadian Electrical Code, or authorities having jurisdiction.
Fig. 7—Typical Gas Pipe Arrangement
WARNING: Use the proper length of pipes to avoid
stress on the gas control manifold. Failure to follow this warning can result in a gas leak, causing fire, explosion, personal injury, or death.
CAUTION: Connect the gas pipe to the furnace using a backup wrench to avoid damaging gas controls.
WARNING: Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning can cause a fire, explosion, personal injury, or death.
CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
A89417
The auxiliary junction box (J-box) can be moved to the left-hand side of the furnace when a left-side power supply is desired. Remove the 2 screws holding the auxiliary J-box. Mount the J-box on the left-hand side of the furnace (holes have been pre-drilled in casing). When moved, tuck the wiring harness behind the clip provided to keep extra wire lengths out of the way.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control board fault code indicator light will flash rapidly and the furnace will not operate.
B. 24-v Wiring
Make field 24-v connections at the 24-v terminal strip. (See Fig.
9.) Connect terminal Y as shown in Fig. 8 for proper cooling operation. Use only AWG No. 18, color-coded, copper thermostat wire.
The 24-v circuit contains an automotive-type, 3-amp fuse located on the main control board. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse of identical size.
C. Accessories
1. Electronic Air Cleaner (EAC)
Two spring clamp terminals (for 12 gage maximum, solid or stranded wire), marked EAC-1 and EAC-2 are provided for EAC connection. (See Fig. 9.) These terminals are energized with 115-v, (1-amp maximum) during blower motor operation. To connect EAC power leads to furnace control center, strip approximately 1/8 in. of insulation from wire. Open terminal by depressing switch arm with a screwdriver or finger, and insert wire as shown in Fig. 10.
2. Humidifier (HUM)
Screw terminals (HUM and Com) are provided for 24-v humidifier connection. The terminals are energized with 24-v 0.5-amp maximum after inducer motor prepurge period.
NOTE: A field-supplied, 115-v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation.
VII. VENTING
Refer to the National or Local Installation Code such as; National Fuel Gas Code Z223.1-1992, or the Canadian Installation Code, CAN B149.1- and .2-M95, for proper vent sizing and installation requirements. Use the enclosed Venting Tables for Category I Fan-Assisted Furnaces for a quick, easy reference. The horizontal portion of the venting system shall maintain a minimum of 1/4-in. upward slope per linear ft and it shall be rigidly supported every 5 ft or less with hangers or straps to ensure that there will be no movement after installation.
VIII. START-UP, ADJUSTMENT, AND SAFETY CHECK A. General
NOTE: Proper polarity must be maintained for 115-v wiring. If
—7—
Page 8
BLK
WHT
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
THREE-WIRE
BLK
AUXILIARY J-BOX
FIVE
WIRE
NOTE 2
WCR GY
THERMOSTAT TERMINALS
HEATING-
ONLY
W
R
GND
CONTROL
BOX
FURNACE
G
C Y
24-VOLT
TERMINAL
BLOCK
NOTE 1
CONDENSING UNIT
TWO WIRE
NOTES: Connect Y-terminal as shown for proper operation.
1.
2.
Some thermostats require a "C" terminal connection as shown.
3.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
Fig. 8—Heating and Cooling Application Wiring Diagram
FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING
FIELD-SUPPLIED FUSED DISCONNECT
208/230- OR 460-VOLT THREE PHASE
208/230- VOLT SINGLE
GND
PHASE
A95241
TABLE 5—ELECTRICAL DATA
UNIT SIZE
024045 115—60—1 127 104 6.0 14 47 15 036045 115—60—1 127 104 8.3 14 34 15 024070 115—60—1 127 104 5.9 14 47 15 036070 115—60—1 127 104 8.7 14 32 15 042091 115—60—1 127 104 9.0 14 31 15 048091 115—60—1 127 104 10.4 14 27 15 036110 115—60—1 127 104 8.0 14 35 15 048111 115—60—1 127 104 10.1 14 28 15 060111 115—60—1 127 104 14.4 12 31 20 048135 115—60—1 127 104 10.1 14 28 15 060135 115—60—1 127 104 13.3 12 33 20 060155 115—60—1 127 104 14.0 12 31 20
* Permissible limits of the voltage range at which the unit operates satisfactorily. † Time-delay fuse is recommended. ‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
VOLTS— HERTZ—
PHASE
The furnace must have a 115-v power supply properly connected and grounded. Proper polarity must be maintained for correct operation. Thermostat wire connections at R, W, C, and Y must be made at the 24-v terminal block on the control board. The gas service pressure must not exceed 0.5 psig (14-in. wc), but must be no less than 0.16 psig (4.5-in. wc).
CAUTION: This furnace is equipped with a manual reset limit switch or fuse link in the gas control area. The
OPERATING
VOLTAGE RANGE
Maximum* Minimum*
MAXIMUM
UNIT AMPS
MINIMUM
WIRE GAGE
MAXIMUM
WIRE LENGTH (FT)‡
The blower compartment door must be in place to complete the 115-v circuit to the furnace.
B. Sequence of Operation
CAUTION: Furnace control must be grounded for
proper operation, or control will lockout. Control is grounded through green wire routed to gas valve and burner bracket screw.
switch or fuse link opens and shuts off power to the gas valve if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switch. Correct inadequate combustion air supply problem and reset the switch or replace the fuse link.
Using the schematic diagram shown in Fig. 11, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.
Before operating the furnace, check each manual reset switch for
another cycle.
continuity. If necessary, press the button to reset the switch.
MAXIMUM
FUSE OR
HACR-TYPE CKT
BKR AMPS†
—8—
Page 9
BLOWER OFF DELAY ADJUSTMENT SWITCH
115-VAC (L1)
POWER
SUPPLY
HOT SURFACE
CONNECTOR
TEST/TWIN
SEC-1
3-AMP FUSE
COOL
HEAT
IGNITOR
G R Y W
Com
24V 
HUM
115-VAC (L2) NEUTRAL CONNECTION
INDUCER MOTOR CONNECTOR
Fig. 9—Control Board
24V THERMOSTAT TERMINALS
HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX)
LED OPERATION & DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24V TRANSFORMER SEC-2 SPARE 1 BLOWER SPEED
SELECTION TERMINALS SPARE 2
EAC 1 (BLACK) EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX) EAC 2 (WHITE)
A93052
Fig. 10—EAC Terminals on Control Board
1. Heating mode When the wall thermostat "calls for heat," the R-W circuit closes. The furnace control performs a self-check, verifies the pressure switch contacts are open, and starts inducer motor. a. Prepurge period—As the inducer motor comes up to
speed, the pressure switch contacts close to begin a 15-sec prepurge period.
b. Ignitor warm-up—At the end of the prepurge period, the
ignitor is energized for a 17-sec ignitor warm-up period.
c. Ignition sequence—When the ignitor warm-up period is
completed, the gas valve opens, permitting gas flow to the burners where it is ignited. After 5 sec, the ignitor is de-energized and a 2-sec flame-sensing period begins.
A93053
d. HUM terminal is energized with the gas valve. See
accessories in the Electrical Connections section.
e. Flame-sensing—When burner flame is sensed, the con-
trol begins the blower on delay period and continues holding the gas valve open. If burner flame is not sensed, the control closes the gas valve and repeats ignition cycle.
NOTE: Ignition sequence will repeat 3 additional time before a lockout occurs. Lockout automatically resets after 3 hrs, or can be manually reset by turning 115v off (not at thermostat) for 3 sec minimum, then on again.
f. Blower on delay—Forty sec after burner flame is proven,
the blower motor is energized on heating speed. Simul­taneously, the humidifier and electronic air cleaner terminals (HUM and Com for humidifier, EAC-1 and EAC-2 for electronic air cleaner) are energized. If jumper is on pin 6 and pin 9, blower on delay is 60 sec.
g. Blower off delay—When the thermostat is satisfied, the
circuit between R-W is broken, de-energizing the gas valve stopping gas flow to the burners. The blower motor and EAC remain energized 90, 135, 180, or 225 sec (depending on the blower off-time selection). The furnace is factory set for a 135-sec blower off delay.
h. Post-purge—The inducer motor remains energized 5 sec
after the burners are extinguished. If jumper is on pin 6 and pin 9, the post-purge period is 15 sec.
2. Cooling mode When the thermostat "calls for cooling," R-G and R-Y
circuits close. The R-Y circuit starts the outdoor condensing
—9—
Page 10
L2
CAP
BLWM
START
SCHEMATIC DIAGRAM
(NATURAL GAS & PROPANE)
NOTE #4
EQUIPMENT GROUND
OL
LO
HI
MED LO
MED HI
COM
NOTE #8
HEAT
SPARE-2
COM
COOL
SPARE-1
HI/LO
EAC-1
TO 115VAC FIELD DISCONNECT
NEUTRAL
L1
ILK
PRS
ALS
NOTE #12
(WHEN USED)
DSS
ORN
OM
GRY
W
C
SW1
SW2
OFF
DELAY
BLOWER
NOTE #9
(NOT ON ALL MODELS)
PCB
YEL
HUM
TEST/TWIN
SELECTION CHART
BLOWER OFF DELAY
BLU
LED
90 SEC
L1
BLWR
FRS1 FRS2
RED
135 SEC
3-P
1-M
1 2 3
PL1
180 SEC
GV
LS
WHT
4
HSIR
FL
(WHEN USED)
FSE
5 6
225 SEC
EAC-2
87 9
IDM
HSI
1
2
1
PR2
PL52
1
PL2
115VAC
PR1
IDR
NOTE #5
2-C
GRN
WHT
BLK
TRAN
RED
BLU
RED
SEC-2
SEC-1
HI/LO
RELAY
NOT USED
PL3
2
3
24VAC
TRAN
NOTE #6
FU1
TEST/TWIN
GRN
WHT (COM)
24 VAC-3A
CAP
BRN
START
OL
NOTE #8
BLK (HI)
YEL (MED HI)
SPARE-1
FUSE
COOL
FU1
SPEED
SELECT
BLOWER
GVR
HSIR IDR BLW R
FL
PRS
NOTE #11
ALS
LS
FRS1 FRS2
(WHEN USED
1
7
SEC-2
SEC-1
GVR-2
HUM
NOTE #12
BRN
BLWM
RED (LO)
BLU (MED LO)
1.5 AMP
SPARE-2
EAC-1
EAC-2
HEAT
OM
L2
C
PR2 123
PL3
2
1
PL2
PR1
VAC
L1
120
PL1
4
GVR
HI/LO
BLWR
IDR
HSIR
R
W
NOTE #4
FUSED DISCONNECT
SWITCH (WHEN REQ’D)
JB
BLK
ILK
WHT
WHT (COM)
WHT
BLK BLK
BLK
WHT
PL5
12
WHT
2-C
(WHEN USED)
GV
DSS
3-P
1-M
2
3
GVR-1
CPU
L1
NEUTRAL
FU2
GRN
WHT
BLK
GRN
IDM
BLK
HSI
8
Y
NOTE #5
FSE
6
5
G
PCB PRINTED CIRCUIT BOARD
PL1 9-CIRCUIT CONNECTOR
PL2 2-CIRCUIT PCB CONNECTOR
ALS AUXILIARY LIMIT SWITCH, OVERTEMP. -MANUAL RESET, SPST-(N.C.)
BLWR BLOWER MOTOR RELAY, SPST-(N.O.)
LEGEND
NOT USED
PL3 3-CIRCUIT IDM CONNECTOR
BLWM BLOWER MOTOR
A95335
322869-101 REV. C
NOT USED
9
OM
C
PL5 2-CIRCUIT HSI/PCB CONNECTOR
PRS PRESSURE SWITCH, SPST-(N.O.)
CAP CAPACITOR
CPU MICROPROCESSOR AND CIRCUITRY
DSS DRAFT SAFEG UARD SWITCH
NOTES:
TEST/TWIN COMPONENT TEST & TWIN TERMINAL
EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.5 AMP MAX.)
optimum speed selection.
1. If any of the original equipment wire is replaced use wire rated for 105°C.
2. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL).
3. Blower motor speed selections are for average conditions, see installation instructions for details on
4. Use only copper wire between the disconnect switch and the furnace junction box (JB).
5. This wire must be connected to furnace sheetmetal for control to detect flame.
JUNCTION
UNMARKED TERMINAL
PCB TERMINAL
FACTORY WIRING (115VAC)
TRAN TRANSFORMER-115VAC/24VAC
(FIELD INSTALLED & SUPPLIED)
EAC-2 ELECTRONIC AIR CLEANER CO NNECTION (COMMON)
FL FUSIBLE LINK
FRS FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.)
FSE FLAME PROVING ELECTRODE
FU1 F USE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED
FU2 FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DE VI CE
GV GAS VALVE- REDUNDANT OPERATORS
GVR GAS VALVE RELAY, DPST-(N.O.)
(135 seconds only on some models)
after three hours.
6. Replace only with a 3 amp fuse.
7. Yellow lead not on all motors.
8. Blower-on delay, gas heating 45 seconds, cooling or heat pump 2 seconds.
9. Blower-off delay, gas heating 90, 135, 180 or 225 seconds, cooling or heat pump 90 seconds.
FACTORY WIRING (24VAC)
FIELD WIRING (115VAC)
FIELD WIRING (24VAC)
CONDUCTOR ON PCB
HI/LO BLOWER MOTOR SPEED CHANGE RELAY, SPDT
HSI HOT SURFACE IGNITOR (115 VAC)
HSIR HOT SURFACE IGNITOR RELAY, SPST-(N.O.)
HUM 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.)
IDM INDUCED DRAFT MOTOR
models only.
10. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset
11. When used auxiliary limit switch (ALS) is on downflow models only. When used FL is on upflow
12. Some models may have spade quick connect terminals.
FIELD WIRING TERMINAL
FIELD GROUND
EQUIPMENT GROUND
FIELD SPLICE
PLUG RECEPTACLE
IDR INDUCED DRAFT RELAY, SPST-(N.O.)
ILK BLOWER ACCESS PANEL IN TE R LOCK SWITCH, SPST-(N.O.)
JB JUNCTION BOX
LED LIGHT-EMITTING DIODE FOR STATUS CODES
LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.)
LS LIMIT SWITCH, AUTO RESET, SPST(N.C.)
OL AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW.
Fig. 11—Unit Wiring Diagram
—10—
Page 11
unit and the combined R-Y and R-G circuits start the furnace blower motor on cooling speed. The EAC-1 termi­nal is energized with 115v when the blower is operating on cooling speed.
When the thermostat is satisfied, R-G and R-Y circuits are broken. The furnace blower and EAC continue operating on cooling speed for an additional 90 sec.
3. Continuous blower mode
NOTE: EAC-1 terminal is energized with 115v whenever blower operates.
When the R-G circuit is made, the blower motor operates on heating speed. During a call for heat, the blower stops, allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the 40-sec blower on delay period. If jumper is on pin 6 and pin 9, the blower on delay is 60 sec.
The blower reverts to continuous operation after the heating cycle is completed.
When the thermostat "calls for cooling," the blower oper­ates on cooling speed. When the thermostat is satisfied, the blower operates an additional 90 sec before reverting back to continuous operation on heating speed.
4. Heat pump mode When installed with a heat pump, the furnace control
automatically changes the timing sequence to avoid long blower off time during demand defrost cycles. When the W-Y or W-Y-G thermostat inputs are received at the same time, the control changes the blower to heating speed or starts the blower if it was off, and begins a heating cycle. The blower remains on until the end of the prepurge period, then shuts off until the end of the ignition warm-up and trial for ignition periods (a total of 24 sec). The blower then comes back on at heating speed.
When the W input signal disappears, the control begins the normal inducer post-purge period and the blower changes to cooling speed after a 1-sec delay. If the W-Y-G signals disappear at the same time, the blower remains on for the selected heating blower off delay period and the inducer goes through its normal post-purge period. If the W-Y inputs should disappear, leaving the G signal input, the control goes into continuous blower and the inducer re­mains on for the normal post-purge period.
Anytime the control senses false flame, the control locks out of the heating mode. This occurs because the control cannot sense the W input due to the false flame signal, and as a result, sees only the Y input and goes into cooling mode, blower off delay. All other control functions remain in standard format.
NOTE: EAC-1 terminal is energized whenever blower operates. HUM terminal is only energized when gas valve is energized
C. Start-up Procedures
1. Purge gas lines—After all connections have been made, purge the lines and check for leaks.
WARNING: Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning can cause fire, explosion, personal injury, or death.
2. Component test—The furnace control board allows all components, except gas valve, to be run for a short period of time.
This feature helps diagnose a system problem in case of a component failure. To initiate component test procedure, short (jumper) the TEST 1/4-in. quick connect terminal on control board (adjacent to diagnostic light) and the Com terminal on thermostat connection block for approximately 2 sec. (See Fig. 9.)
NOTE: Component test feature will not operate if any thermostat signal is present at control board.
Component test sequence is as follows. a. Momentarily jumper TEST and Com terminals until
LED goes off. b. LED will display previous fault 4 times. c. Inducer motor operates for 10 sec, then stops. d. Hot surface ignitor is energized for 15 sec, then de-
energized. e. Blower motor operates on cooling speed for 10 sec, then
stops. f. Blower motor operates on heating speed for 10 sec, then
stops.
3. To operate furnace, follow procedures on operating instruc­tions label attached to furnace.
4. With furnace operating, set thermostat below room tem­perature and observe that furnace goes off. Set thermostat above room temperature and observe that furnace restarts.
D. Adjustments
1. Set gas input rate. There are 2 methods of adjusting the gas input rate. The
preferred method is by using Table 6 and following the instructions in item a. The second method is by clocking the gas meter and using the instructions in item b.
The gas valve regulator has been nominally set at 3.5-in. wc for natural gas. When adjusting input rate, do not set manifold pressure above 3.8-in. wc or below 3.2-in. wc.
a. Check gas input rate using Table 6.
(1.) Obtain average yearly heat value for local gas
supply.
(2.) Obtain average yearly specific gravity for local gas
supply.
(3.) Verify furnace model. Table 6 can only be used for
model 395CAV Furnaces.
(4.) Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
(5.) Find natural gas heat value and specific gravity in
Table 6.
(6.) Follow heat value and specific gravity lines to point
of intersection. Find orifice size and manifold pres­sure settings for proper operation at given natural gas conditions.
EXAMPLE: Heat value 1070 Btu/cu ft specific gravity 0.58 Therefore; Orifice No. 44* Manifold pressure 3.3-in. wc *The furnace is shipped with No. 43 orifices. Therefore, in this example all main burner orifices must be changed and manifold pressure must be adjusted.
(7.) Proceed to item c to adjust manifold pressure.
—11—
Page 12
GAS
HEAT
VALUE
(BTU/CU FT)
860
875
890
905
920
935
950
965
980
995
1010
1025
1040
1055
1070
1085
1100
TABLE 6—MODEL 395CAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT RATE
(Tabulated Data Based on Altitude Up to 2000 Ft and 22,000 Btuh Per Burner)
SPECIFIC GRAVITY OF NATURAL GAS
0.56 0.58 0.60 0.62 0.64 0.66 0.68 0.70 0.72
Orf
Mnfld
No.
Press.
41 42
42
— —
42
— —
42
— —
43—3.8—42—3.2—42—3.3—42—3.4—41423.2
43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—41423.2
43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—41423.2
43—3.4—43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—41423.2
44433.8
44433.7
44—3.6—44433.7
44—3.5—44433.6
44—3.4—44—3.5—44433.6
44—3.3—44—3.4—44—3.5—44433.6
44—3.2—44—3.3—44—3.4—44—3.5—44433.7
45—3.8—44—3.2—44—3.3—44—3.4—44—3.6—44433.7
45—3.7—45—3.8
Orf
No.
3.2
41
3.6
42
3.4
41
42
3.3
42
3.2
42
3.342—
3.24443
Mnfld
Orf
Press.
3.3
3.7 —
3.2
3.6 —
3.4 — —
3.3 — —
3.5—43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—42—3.4—41423.2
3.8
3.443—
3.34443
3.24443
3.444—
No.
41 42 40
41 42 —
41 42 —
42 — —
Mnfld
Press.
Orf
Mnfld
No.
Press.
3.4
41
3.8
40
3.2
3.3
41
3.7
42
40
3.2
41
3.6
42
3.4
41
42
3.5—43—3.6—43—3.7—43—3.8—42—3.2—42—3.3—42—3.4
3.8
3.443—
3.7
3.343—
3.24443
3.2—44—3.4—44—3.5—44—3.6—44433.7
Orf
Mnfld
Orf
No.
Press.
3.5
41
3.3 —
3.4
3.8
3.2
3.3
3.7 —
3.2
3.6 —
3.5—43—3.6—43—3.7—43—3.8—42—3.2—42—3.3
3.4—43—3.5—43—3.6—43—3.7—43—3.8—43—3.2
3.7
3.343—
3.24443
3.7
39
3.2
40
3.4
41
3.5
40
3.3
41
3.4
42
3.8
41
3.3
42
3.7
3.54142
3.4—43—3.5—43—3.6—43—3.7—43—3.8
3.8
3.343—
3.24443
No.
41 39 40
41 39 40
41 40 —
41 42 —
Mnfld
Press.
Orf
Mnfld
Orf
No.
Press.
3.8
39
3.3
3.5
3.6
3.2
3.4
3.5
3.2 —
3.4
3.8 —
3.3
3.74142
3.54142
3.4—43—3.5—43—3.6—43—3.7
3.8
3.343—
2.34443
3.4
40
3.6
41
3.8
39
3.3
40
3.5
41
3.6
40
3.3
41
3.5
40
3.2
3.4
3.84140
3.3
3.74142
3.54142
3.4—43—3.5—43—3.6
3.8
3.343—
3.24443
No.
38 39 40
39 40 —
41 39 40
41 40 —
Mnfld
Press.
3.2
3.5
3.7
3.3
3.6
3.7
3.2
3.4
3.6
3.3
3.5
3.24140
3.4
3.84140
3.3
3.64142
3.54142
3.4—43—3.5
3.8
3.343—
Orf
No.
38 39 40
38 39 40
41 39 40
41 39 40
Mnfld
Press.
3.3
3.6
3.8
3.2
3.4
3.7
3.8
3.3
3.5
3.7
3.2
3.4
3.6
3.3
3.5
3.2
3.4
3.7
3.3
3.6
3.5
3.4 —
b. Check gas input rate by clocking gas meter.
(1.) Obtain average yearly heat value for local gas
supply.
(2.) Check and verify orifice size in furnace. NEVER
ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
CAUTION: DO NOT redrill burner orifices. Improper drilling (burrs, out of round, etc.) can cause excessive burner operating noise and misdirection of burner flames. This could result in flame impingement on burners and heat exchanger surfaces, leading to potential failures.
(3.) Turn off all other gas appliances and pilots. (4.) Start furnace and let run for 3 minutes. (5.) Measure time (in sec) for gas meter to complete 1
revolution. (6.) Refer to Table 7 for cu ft of gas per hr. (7.) Multiply gas rate (cu ft/hr) by heating value (Btu/cu
ft).
EXAMPLE: Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 1070 Btu/cu ft Time for 1 revolution of 2 cu ft dial = 72 sec Gas rate = 100 X 1070 = 107,000 Btuh
(8.) Measured gas input should not exceed gas input on
unit rating plate.
(9.) Proceed to item c to adjust manifold pressure.
c. Adjust gas input.
(1.) Remove regulator adjustment seal cap. (See Fig.
12.)
(2.) Turn adjusting screw counterclockwise to decrease
input. Turn screw clockwise to increase input. DO NOT set manifold pressure less than 3.2-in. wc or more than 3.8-in. wc for natural gas. Make any major adjustments by changing main burner ori­fices.
—12—
Page 13
TABLE 7—GAS RATE CU FT/HR
SECONDS
FOR 1
REVOLUTION
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49
SIZE OF
TEST DIAL
1 cu ft2cu ft5cu ft 360
720 655 600 555 514 480 450 424 400 379 360 343 327 313 300 288 277 267 257 248 240 232 225 218 212 206 200 195 189 185 180 176 172 167 164 160 157 153 150 147
1800 1636 1500 1385 1286 1200 1125 1059
100 947 900 857 818 783 750 720 692 667 643 621 600 581 563 545 529 514 500 486 474 462 450 439 429 419 409 400 391 383 375 367
327 300 277 257 240 225 212 200 189 180 171 164 157 150 144 138 133 129 124 120 116 113 109 106 103 100
97 95 92 90 88 86 84 82 80 78 76 75 73
SECONDS
FOR 1
REVOLUTION
50 51 52 53 54 55 56 57 58 59 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96
98 100 102 104 106 108
110 112 116 120
(3.) When correct input is obtained, replace regulator
seal cap. Main burner flame should be clear blue, almost transparent. (See Fig. 13.)
ON AND OFF SWITCH
SIZE OF
TEST DIAL
1
cu ft2cu ft5cu ft
72
144 141 138 136 133 131 129 126 124 122 120 116 112 109 106 103 100
97 95 92 90 88 86 84 82 80 78 76 75 74 72 71 69 68 67
65 64 62 60
360 355 346 340 333 327 321 316 310 305 300 290 281 273 265 257 250 243 237 231 225 220 214 209 205 200 196 192 188 184 180 178 173 170 167
164 161 155 150
71 69 68 67 65 64 63 62 61 60 58 56 54 53 51 50 48 47 46 45 44 43 42 41 40 39 38 38 37 36 35 35 34 33
33 32 31 30
GAS PRESSURE REGULATOR ADJUSTMENT
BURNER FLAME
BURNER
MANIFOLD
Fig. 13—Burner Flame
e. Canadian installations only—The Canadian ratings are
approved for altitudes up to 2000 ft for natural and propane gases. High-altitude ratings are from 2000 ft to 4500 ft above sea level. See Table 8 for nominal burner orifice size. High-altitude rating includes a 10 percent derate as required by Canadian standards.
TABLE 8—CANADIAN ORIFICE SIZE
GAS
SEA LEVEL
0—2000 FT
Natural 43 44
Propane 54 55
HIGH ALTITUDE
2000—4500 FT
2. Set temperature rise. Furnace must operate within range of temperature rise
specified on the unit rating plate. Determine the air tem­perature rise as follows.
a. Place duct thermometers in return and supply ducts as
near furnace as possible. Be sure thermometers do not "see" heat exchangers so that radiant heat will not affect thermometer readings. This is particularly important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine temperature rise.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. De­crease blower speed to increase temperature rise.
A89020
INLET PRESSURE TAP
MANIFOLD PRESSURE TAP
Fig. 12—Redundant Automatic Gas Control Valve
d. High altitude—In the United States gas input on rating
plate is for altitudes up to 2000 ft. Ratings for altitudes over 2000 ft must be 4 percent less for each 1000 ft above sea level. To obtain the adjusted altitude rating, adjust the manifold pressure (see item c) and replace the main burner orifices as needed. Refer to National Fuel Gas Code Appendix F, Table F-4 for proper orifice sizing at high altitudes.
A95618
WARNING: Disconnect the electrical power before changing the speed tap. A failure to follow this warning can cause personal injury.
d. To change blower motor speed selections for heating
mode, remove blower motor lead from control board HEAT terminal. (See Fig. 11.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to HEAT terminal. See Table 9 for lead color identification. Reconnect original lead on SPARE termi­nal.
CAUTION: Recheck temperature rise. It must be within limits specified on unit rating plate. Recommended op­eration is at midpoint of rise or above.
—13—
Page 14
TABLE 9—SPEED SELECTOR
COLOR SPEED
Black High Cool
Yellow (When
present)
Blue Medium-Low Heat
Red Low Spare
White Common COM
Medium-High Spare
FACTORY-
ATTACHED TO
3. Set thermostat heat anticipator. The thermostat heat anticipator must be set to match the
amp draw of the electrical components in the R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 14 illustrates an easy method of obtaining the actual amp draw. The amp reading should be taken after the blower motor has started. See the thermostat manufacturer’s instructions for adjusting the heat anticipator and for varying the heating cycle length.
NOTE: When using an electronic thermostat, set the cycle rate for 3 cycles per hr.
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED
HOOK-AROUND
VOLT/AMMETER
R Y W G
10 TURNS
FROM UNIT 24-VOLT TERMINAL BLOCK
The preferred method of checking the limit control is to gradually block off the return air after the furnace has been operating for a period of at least 5 minutes. As soon as the limit has shut off the burners, the return-air opening should be unblocked. By using this method to check the limit control, it can be established that the limit is functioning properly and operates if there is a motor failure.
2. Check draft safeguard switch. The purpose of this control is to permit the safe shutdown
of the furnace during certain blocked vent conditions. a. Disconnect power to furnace and remove vent connector
from furnace outlet collar. Be sure to allow time for vent pipe to cool down before removing.
b. Restore power to furnace and set room thermostat above
room temperature.
c. After normal start-up, allow furnace to operate for 2
minutes, then block flue outlet 100 percent. Furnace should cycle off within 2 minutes.
d. Remove blockage and reconnect vent pipe to furnace
outlet collar.
e. Wait 5 minutes and then reset draft safeguard switch.
3. Check pressure switch. This control proves operation of draft inducer blower.
a. Turn off 115-v power to furnace. b. Remove control door and disconnect inducer motor lead
wires from wire harness. c. Turn on 115-v power to furnace. d. Set thermostat to "call for heat" and wait 1 minute. When
pressure switch is functioning properly, hot surface
ignitor should NOT glow and control center diagnostic
light flashes a 31 fault. If hot surface ignitor glows when
inducer motor is disconnected, shut down furnace im-
mediately. Determine reason pressure switch did not
function properly and correct condition. e. Turn off 115-v power to furnace. f. Reconnect inducer motor wires, replace control door, and
turn on 115-v power.
EXAMPLE:
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
= 0.5 AMPS FOR THERMOSTAT SETTING
A80201
Fig. 14—Amp Draw Check With Ammeter
E. Check Safety Controls
1. Check primary limit control. This control shuts off the combustion control system and
energizes the circulating-air blower motor if the furnace overheats.
F. Checklist
1. Put away tools, instruments, and clean up debris.
2. Verify manual reset switches have continuity.
3. Ensure blower and control access doors are properly in­stalled.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instruc­tions.
6. Review User’s Manual with owner.
7. Leave literature packet near furnace.,
—14—
Page 15
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:  • Unit Familiarization • Maintenance  • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.  Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. 
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
—15—
Page 16
© 1996 BDP Co. • P.O. Box 70 • Indianapolis, IN 46206 Printed in U.S.A.
—16—
395c4010 Catalog No. BDP-3339-518
Loading...