LEWCO EUROTHERM 3216, EUROTHERM 3216i Instruction Manual

INDUSTRIAL OVENS
GENERAL INSTRUCTION GUIDE
EUROTHERM 3216 & 3216i CONTROLLERS
This guide is provided by LEWCO, Inc. to assist its customers in becoming familiar with how LEWCO Inc. sets up and uses the Eurotherm Controllers to test equipment prior to shipping. This document does not replace respective Eurotherm user’s manuals and anyone using any of the Eurotherm products mentioned here is responsible for obtaining and understanding the user’s manual before using any of these controllers. The user is responsible for setting up and configuring these devices to meet their own application requirements, not limited to but including adjusting set points, and setting up alarms.
If you do not have a manual for your controller or just wish to view an online version of it, please use the following link: http://www.eurothermonline.com/search?searchwords=manuals&searchsmall_4920=
3216 AND 3216i INSTRUCTION
This set of instructions will work for both the 3216 Process Controller and 3216i FM approved High Limit controller.
BUTTON LEGEND:
INDUSTRIAL OVENS
GENERAL INSTRUCTION GUIDE
EUROTHERM 3216 & 3216i CONTROLLERS
TO CHANGE ENGINEERING UNITS (°F TO °C):
Press and hold the PAGE button until LEv1 shows in the upper display and GOTO shows in the lower
display. Select access level will scroll through the lower display.
Press the UP and DOWN arrows and change LEv1 to LEv2 The word CODE will be shown in the lower display and a “0” will be shown in the upper display
Press the UP and DOWN arrows and change the “0” to a “2” Press the SCROLL button until UNITS is shown in the lower display and the current units are shown in
the upper display
Press the UP and DOWN arrows and change to desired units °F
TO CHANGE THERMOCOUPLE TYPE:
Press and hold the PAGE button until LEv3 shows in the upper display and GOTO shows in the lower
display. Release the PAGE button.
The word CODE will be shown in the lower display and a “0” will be shown in the upper display Press the UP and DOWN arrows and change the “0” to a “3” Press the PAGE button until INPUT is shown in the lower display. Press the SCROLL button until IN.TYP is shown in the lower display and the current type is shown in
the upper display (J.TC)
Press the UP and DOWN arrows and change to desired units type Press the SCROLL button t o save Press and hold the PAGE button again and until CONF is in the upper display and GOTO is in the
lower display
Press the UP and DOWN arrows and change LEv3 to LEv1 Controller will cycle power and automatically restart.
3216 INSTRUCTION
The 3216 Process Controller is a 1/16-DIN highly precise temperature controller.
OPERATION:
Provides simple and precise temperature control
TO CHANGE SET POINT:
Press the UP and DOWN arrows until desired set point is reached