Leviton VerifEye 7000, VerifEye 7100 User Manual

Page 1
VerifEye® Series 7000/7100
Cat. No 70D48, 71D48, 70N48
User Guide
Cat. 71D48 Cat. 70D48
PK-A3259-10-00-0A ARN0439
Page 2
Page 3
TABLE OF CONTENTS
1 Introduction ........................................................................................1
1.1 Unpacking the Unit .........................................................................1
1.2 VerifEye Anatomy ...........................................................................2
2 Planning For Field Installation ..........................................................3
2.1 Project Manager Aspects ...............................................................3
2.1.1 Configuration & Data Viewing Options ..................................3
2.1.2 Information Access by Interface Type ....................................3
2.2 Meter Configuration Overview ........................................................4
2.3 Meter Installation Overview ............................................................4
2.4 Verification & Communication Overview ........................................4
2.5 RTU Programming and Scripting Overview ...................................4
3 Meter Configuration .............................................................................5
3.1 Install the S7 Configuration Utilities Software ................................5
3.1.1 Connection & Config. Using S7 Configuration Utilities ..........5
3.1.2 USB Connection (Power & Communications) .......................6
3.1.3 Ethernet Network Connections ..............................................6
3.2 S7 Configuration Utilities Software Overview .................................9
3.2.1 Configuring Electrical Components .....................................10
3.2.2 Configuring RS-485 Communications .................................11
3.2.3 Configuring Ethernet Communications ................................12
3.2.4 Configuring Alarms ..............................................................13
3.2.5 Setting the Real Time Clock ................................................14
3.2.6 Retrieving Interval Data .......................................................15
3.3 VerifEye Web App Overview ........................................................16
3.3.1 Connect to Web App Using USB .........................................16
3.3.2 Connect to Web App Using Ethernet ...................................16
3.3.3 Authentication ......................................................................16
4 Meter Installation ................................................................................17
4.1 Meter Mounting Configurations ....................................................17
4.2 Installation Sequence ...................................................................18
4.3 Wiring in a 3-wire, Split Phase Service Panel ..............................21
4.4 Wiring in a 3 Phase, 4 Wire Service Panel ..................................22
4.5 Current Transformers Basics .......................................................23
4.6 Wiring the CTs to the VerifEye Meter ...........................................24
5 Communication & Verification ........................................................25
5.1 Physical Connections on an RS-485 Multidrop Network ..............25
5.2 Communication Verification ..........................................................26
5.3 Physical Interface Verification ......................................................27
Page 4
TABLE OF CONTENTS
5.4 Protocol Verification .....................................................................27
5.5 Modbus Settings ..........................................................................28
5.6 BACnet Settings ...........................................................................28
5.7 Pulse Inputs .................................................................................29
5.8 Alarms (SPDT) .............................................................................29
5.9 12 Volt Auxillary Power .................................................................29
5.10 Access Restriction Limitations ....................................................30
5.11 Security PIN Protection ..............................................................30
5.12 Verification of Installation ...........................................................32
5.12.1 Installation Phase Verification ............................................32
5.12.2 Phase Checking by Phasor Plot ........................................33
5.12.3 CT Orientation Check ........................................................34
5.13 Power Factor Convention ...........................................................35
5.14 Total Harmonic Distortion ...........................................................35
5.15 Pre-Processing Aids ...................................................................36
6 RTU Programming & Scripting .........................................................37
6.1 Register Organization ..................................................................37
6.2 Element vs. System Scope ..........................................................37
6.3 Configuring Element and Channel Register for Service Types ....38
6.4 Configuring System Registers ......................................................40
6.5 Modbus Protocol Commands .......................................................40
6.6 BACnet .........................................................................................41
Appendix A: LCD Menu Navigation .....................................................43
Appendix B: Technical Specifications .................................................46
Page 5
WARNING:
RISK OF ELECTROCUTION, SHOCK, EXPLOSION, OR ARC FLASH. CAREFULLY READ AND FOLLOW INSTRUCTIONS:
HIGH VOLTAGE MAY BE PRESENT. RISK OF ELECTRIC SHOCK. LIFE THREATENING VOLTAGES MAY BE PRESENT. Qualified personnel only.
TO AVOID FIRE, SHOCK OR DEATH, turn off all power supplying equipment before working on or inside the equipment. Use a properly rated voltage sensing device to confirm power is off.
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment MUST be installed and serviced by qualified electrical personnel with the requisite knowledge, training and experience related to the installation and operation of this equipment.
Product may use multiple voltage/power sources. Be sure all sources of power have been disconnected before servicing.
Do not depend on this product for voltage indication.
Only install this product on insulated conductors.
If the meter appears damaged or defective, first disconnect all power to the meter. Then call or email technical support for assistance.
DO NOT EXCEED 346V Line to Neutral or 600 volts Line to Line. This meter is equipped to monitor loads up to 346V L-N. Exceeding this voltage will cause damage to the meter and danger to the user. Always use a Potential Transformer (PT) for voltages in excess of 346V L-N or 600 volts line to line. The VerifEye® is a 600 Volt Over Voltage Category III device.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with the environment. Installation category: CAT II or CAT III
Provide a disconnect device to disconnect the meter from the supply source. Place this device in close proximity to the equipment, and within easy reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconnecting device for supply conductors with approved current limiting devices suitable for protecting the wiring. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the device may be impaired.
Page 6
CAUTION:
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
If the collector is connected directly to a source of voltage, the pulse isolator will immediately burn out and become non-responsive.
Do no use any cleaning agents, including water, on the VerifEye device.
No accessories are approved for use with the VerifEye meter other than those specified in the Leviton Manufacturing product literature and price sheets.
A circuit breaker used as a disconnect must meet the requirements of IEC 60947-1 and IEC 60947-3 (Clause 6.11.4.2)
Current transformers may not be installed in equipment where they exceed 75 percent of the wiring space of any cross-sectional area within the equipment.
Current transformers may not be installed in an area where they block ventilation openings.
Current transformers may not be installed in an area of breaker arc venting.
Not suitable for Class 2 wiring method nor intended for connection to Class 2 equipment.
Secure current transformer and route conductors so that they do not directly contact live terminals or bus.
External secondary inputs and outputs should be connected to devices meeting the requirements of IEC 60950
The following additional requirements apply for Recognized board versions of the VerifEye meter
• For use only with Listed Energy-monitoring Current Transformers
Associated leads of the current transformers shall be maintained within the
Unless the current transformers and their leads have been evaluated for
The current transformers are intended for installation within the same
Use this device with copper or copper clad wire only.
For indoor use only.
same overall enclosure.
REINFORCED INSULATION, the leads must be segregated or insulated from different circuits.
enclosure as the equipment. These may not be installed within switchgears and panel boards or similar.
Page 7
1 INTRODUCTION
There are two meters in the VerifEye® series: the VerifEye 7000 and the VerifEye 7100. These meters monitor the voltage, current, power, energy, and many other electrical parameters on single and three-phase electrical systems. A VerifEye meter uses direct connections to each phase of the voltage and current transformers to monitor each phase of the current. Information on energy use, demand, power factor, line frequency, and more are derived from these voltage and current inputs.
The VerifEye meter is not meant to be a standalone energy recorder; rather it is connected as a slave device to a data logger, Remote Terminal Unit (RTU), or Building Management host network. The VerifEye meter communication interfaces include Ethernet (LAN), or RS-485 serial. BACnet MS/TP and Modbus RTU are the two communication protocols that operate over an RS-485 serial network and BACnet IP and Modbus TCP are supported over Ethernet. A USB port is also provided as the preferred connection for on-site configuration and can be run concurrently with an RTU.
1.1 Unpacking the Unit
The VerifEye meters can be ordered with optional product features which are
identifiable on the part number label.
VerifEye Part Numbering Scheme
70D48-000 Series 7000 Embedded Branch Circuit Monitor, Mounting Plate
48 Input, with LCD Display
70N48-000 Series 7000 Embedded Branch Circuit Monitor, Mounting Plate
48 Input, with no display
71D48-000 Series 7100 Branch Circuit Monitor, Plastic Enclosure
48 Input, with LCD Display
Each VerifEye meter shipment also includes the following items:
Meter with Options Installed – Serial Number, MAC ID, and FCC ID
Pluggable Connectors (2 voltage, 50 three-position terminals,
Thumb drive containing VerifEye S7 Configuration Utilities Software,
• Certificate of Calibration (COC) for each unit
indicated on side label
3 two-position terminals)
Register List, Manual, Tutorial Videos
1
Page 8
1 INTRODUCTION
1.2 Meter Anatomy
All user connections are made on the circuit board. Connectors are
identified by function and include polarity markers.
Expansion
Element ID Element ID
LCD Display
Navigation Buttons
Serial # Model # MAC ID(s)
Card (12V)
Voltage Input 1
Pulse Input
Pulse Input
ETHERNET
RS-485
USB
+12 VDC
Voltage Input 2
Alarm
Expansion
Card (12V)
Voltage
Cover
(transparent)
Plate Ground
2
Page 9
2 PLANNING FOR FIELD INSTALLATION
2.1 Project Manager Aspects
Meter installation often includes coordination between individuals or groups of
people with different responsibilities. Spend a few minutes considering who will be executing each portion of the installation and what tools are needed at each stage. Things to consider include determining how to communicate with the meter, setting address configuration, installing S7 Configuration Utilities, access to PIN numbers, etc. The more tasks completed before installation the fewer tasks will be needed in the field. The following section gives an overview of typical process activities followed by details in the next section.
2.1.1 Configuration & Data Viewing Options
The VerifEye meter has three methods for configuration and data viewing. The
most powerful interface is a Microsoft Windows application (S7 Configuration Utilities ) that runs on PCs or tablets. S7 Configuration Utilities is encouraged for complex installations and is required for configuring advanced functions like alarms. The second interface is the VerifEye Web App and is intended for smart phones or tablets that can connect over USB, or Ethernet. The third interface is an optional LCD display which is intended for intermittent end-user observation and is restricted in capability. The RTU can also be used for configuration if communication settings are already established. The feature set of each interface is summarized next.
2.1.2 Information Access by Interface Type
Interface Options
When Meter Setup
Real Time Values
Configuration Entire Meter
Security PINs Factory Support –
PC or Laptop Running S7 Configuration Utilities
Field Visit
All Meter Parameters Waveform Capture Harmonic Analysis All Element View Phasor Plot Alarms
Visual Guides Copy / Paste
Level 3
* If PINs are configured
Smart Device or Tablet via VerifEye Web App
Field Visit
All Meter Parameters Multi-Element View
Entire Meter Text Based
Read Only - Level 1* Read/Write - Level 2*
3
LCD on Meter (if equipped)
End User Building
Voltage Current VA VAR kWh Single Element View
Communications Only
Read Only – Level 1* Read / Write Level 2* (limited to communication)
RTU (Host System) Modbus /BACnet
System
All Meter Parameters
Entire Meter Register Based
Factory Support – Level 3
Page 10
2 PLANNING FOR FIELD INSTALLATION
2.2 Meter Configuration Overview
Work performed ahead of the installation saves time in the field and results in
fewer mistakes!
Tools Typical Work
• Desktop or Laptop PC
USB Type AB Cable (preferred) or Ethernet & USB wall charger (> 500 mA)
• Thumb Drive (S7 Configuration Utilities Installer) or access www.Leviton.com and go tosoftware downloads for this product
• Electrical Schematics of project
2.3 Meter Installation Overview
Performed by licensed electrician.
Tools Typical Work
• Mounting hardware (customer supplied)
• Wiring & supplies, labels, wire ties
• T
ablet, Smart Device, or Laptop PC
• Multi Meter, Current Clamp
• Camera
2.4 Verification & Communication Overview
Can be modified with power applied to the meter.
Tools Typical Work
• Tablet, Smart Device (Web Page Based), or Laptop PC (S7 Configuration Utilities Software)
• On site troubleshooting
• Multi Meter
• Camera
, Current Clamp
2.5 RTU Programming and Scripting Overview
Tools Typical Work
• Laptop PC (Remote Access to RTU)
• Remote troubleshooting
• Register List
• Installation of S7 Configuration Utilities Software
• Connect USB/Ethernet cable from PC to meter
• Establish communication with meter
• Firmware update (if desired)
• Configure software for anticipated meter setup
• Field wiring documentation
• Mechanical mounting
• Electrical installation
• Install voltage cover
• Apply power to meter
• Confirm basic operation of meter
• Locate the power meter
• Confirm RTU device
• Add wire terminations (if required)
• Confirm meter communication settings
• Meter health metrics (check for setup errors)
• Analytics (S7 Configuration Utilities )
• Correct instrumentation
• Set security PINs
• Checklist
• Confirm meter communication settings
• Confirm communication protocols
• Exer
cise remote connectivity
• Run configuration scripting
• Confirm data integrity
4
Page 11
3 METER CONFIGURATION
This section is written to support setting up the VerifEye in an office environment and configuring the power meter for a pre-determined configuration. In many cases, the setup is standardized for an organization or project. In other cases, the setup can be documented and emailed to an installer. The setup can also be performed on-site and reflect “as-built” configurations.
3.1 Install the S7 Configuration Utilities Software
Insert the S7 Configuration Utilities thumb drive into the computer or download
from the Leviton FTP site. (qualified Leviton personnel only). The installer should start automatically. If it does not, browse the thumb drive and locate the S7ConfigurationUtilities.exe program, double-click on it, and follow the installer instructions.
Custom Installation
For users who want to specify the location of the S7 Configuration Utilities
software and support files, double-click the folder [Install Files] and run setup. exe. This will prompt the user for additional details.
3.1.1 Connection & Configuration Options Using S7 Configuration Utilities
When the S7 Configuration Utilities application is launched, it will prompt the
user to select one of four connectivity options.
• Connect over USB cable
• Connect over Ethernet to a Predetermined IP address
• Scan Network
• Create Setup file only (no meter connected)
NOTE: The USB connection method is recommended for new users who have physical access to the meter using a USB A to B cable.
5
Page 12
3 METER CONFIGURATION
3.1.2 USB Connection (Power & Communications)
1. Connect the VerifEye meter to a USB port of your computer to provide both
power and communications.
a. If equipped, the LCD display is the most visible indication of a
b. For meters without a display, a green flashing LED on the circuit board
CAUTION: The VerifEye meter draws 450mA from the USB port. Be sure
The meter should now be communicating. The S7 Configuration Utilities
3.1.3 Ethernet Network Connections
Configuring the meter over Ethernet requires that the meter be powered used a
NOTE: In the rare case that a computer’s USB port cannot provide 500mA of
NOTE: Both the Network Scan and Connect Over Ethernet to IP options
running meter.
indicates that the VerifEye meter has booted and is running.
the USB host is industry standard otherwise overloading may occur. If the meter fails to power, or flickers when powering over USB, an alternate configuration for power must be used.
2. Launch the S7 Configuration Utilities application and select
[CONNECT OVER USB] on the pop up window.
application offers visual guides and context help to facilitate meter configuration. Please read the S7 Configuration Utilities overview section for additional information on configuring the meter. By default, VerifEye meters are configured for DNS Ethernet addressing. A very common configuration sequence is using USB to configure a meter for Ethernet communications at a static IP address and then switching from USB over to Ethernet to locate it. This is facilitated in S7 Configuration Utilities by selecting [Refresh Connectivity] located in the upper right hand corner.
second connection. The meter does not support Power Over Ethernet (POE). If the meter is already installed within the buildings electrical network, closing the AC breaker (or approved disconnect) will turn on the meter through the meter’s internal power supply.
current, an AC / USB charger or a USB battery can be used as a power source while using Ethernet for communications.
require that a valid network connection exists between the VerifEye meter and configuration PC.
Dynamic Host Configuration Protocol (DHCP):
VerifEye meters are shipped in DHCP mode to prevent IP conflicts with other
equipment. The meter is expecting to receive an IP address from a DHCP service provided by a router, Layer 3 switch, or a server providing DHCP service. Under this configuration, as long as the VerifEye meter and the host PC are requesting an IP address from the same DHCP service provider, they will be able to communicate. Upon powering up, the VerifEye meter will indicate the IP address on the LCD display (if equipped) or can be found using the Network Scan function.
6
Page 13
3 METER CONFIGURATION
Direct
When a PC is directly connected to a VerifEye meter via an ethernet cable,
no DHCP service exists. This configuration can be made to work, but requires changes to either the meter communication settings or the PC network configuration.
LCD Display
For units equipped with an LCD display, navigate to
Communications > Ethernet Settings > DHCP > OFF
Change the IP address in the meter to match the subnet of your PC’s IP
address, making the meter IP unique, or note the current address on the meter and prepare to configure your PC’s IP settings as shown below.
Control Panel
> Network and Sharing Center
> Change Adapter Settings
> Properties
> Internet Protocol Version 4 (TCP/IPv4)
> Properties
Change Computer IP Address and Subnet Mask to 192.168.1.100 and
255.255.255.000 respectively.
Once the PC and VerifEye meter are set to communicate on the same
IP subnet:
1. Launch the S7 Configuration Utilities application and enter the IP address of
the meter (shown as the factory default).
2. Select [Connect over Ethernet to:] on the pop up window.
3. The meter should now be communicating. S7 Configuration Utilities is an
intuitive application; read the S7 Configuration Utilities overview section for additional information on configuring the meter.
No LCD Display
A VerifEye meter without a display can only communicate directly with a PC over
ethernet if the IP address of the meter is set to static. Setting the IP address must be done ahead of time using another interface (such as USB or serial).
7
Page 14
3 METER CONFIGURATION
Network Scan
Network Scan is a feature for monitoring previously installed and configured
VerifEye meters over an Ethernet network. Network Scan will broadcast a UDP discovery packet on the same network as the PC running the S7 Configuration Utilities application. Normally this will be performed on a corporate network running DHCP. Any VerifEye meter that responds will be displayed in a table that includes the system description register, IP address, serial number, and communication configuration.
Highlight the desired meter and select OK, Test or Setup. Note that the
effectiveness of this technique is highly dependent on the configuration of the PC running S7 Configuration Utilities (which may have more than one network card) and the network configuration. Rescans can be used to make multiple attempts to locate a particular meter on busy networks (UDP has no built-in retry provisions).
Launch Configurator
The final option in the S7 Configuration Utilities Connect to Meter pop-up
window is Launch Configurator. This option allows for the creation of a meter setup or alarm table for future use without connecting to a meter. After prompting the user for a meter model, the S7 Configuration Utilities application launches under a mode with restricted functionality. This mode operates on files only.
8
Page 15
3 METER CONFIGURATION
3.2 S7 Configuration Utilities Software Overview
S7 Configuration Utilities is a Windows application and is the most versatile
software tool for configuring and verifying a VerifEye meter. All functions and menus are accessed under the central drop-down list which has a content filter for viewing Basic metering data or Extended meter data that can be helpful in troubleshooting. The information displayed in the drop-down list for each filter setting is summarized below.
ExtendedBasic
Display Data Basic Extended
Monitor Power
Energy
Demand
Power Factor
W
aveform Capture
Harmonics
Phasor Plots
Setup Meter Setup
Communication Setup
Alarms
Advanced
About the Meter
DD
DD
DD
D
D
D
D
DD
DD
D
DD
DD
9
Page 16
3 METER CONFIGURATION
3.2.1 Configuring Electrical Components Using S7 Configuration Utilities
1. Navigate to Meter Setup under Display Menu List Box.
2. Enter a System Description for the physical location of the meter.
3. Enter Element Description (defaults are A, B, etc.).
4. Select the Voltage Input (voltage connector 1 or 2) - for OS48 only.
5. Select the Voltage Multiplier (optional).
6. Select the Service Type (3-Phase 4-Wire, etc.).
7. Select CT Type (HSC-050, etc.).
8. Set CT Multiplier (optional).
9. Set CT Flipper (optional).
10. Repeat steps 3 - 7 for each Element.
11. Click SEND SETUP TO METER
10
Page 17
3 METER CONFIGURATION
3.2.2 Configuring RS-485 Communications Using S7 Configuration Utilities
If planning to setup communication via RS-485, follow the steps below:
1. Navigate to Communication Setup under Display Menu List Box.
2. Select RS-485.
3. Select either Modbus or BACnet.
4. If Modbus is selected, set the following:
• Serial Settings
If BACnet is selected, set the following:
• Serial Settings
• Device ID
• MS/TP Address
• Max Masters (optional)
• Max Info Frames (optional)
5. Click SEND SETUP TO METER
11
Page 18
3 METER CONFIGURATION
3.2.3 Configuring Ethernet Communications Using S7 Configuration Utilities
If planning to setup communication via Ethernet, follow the steps below:
1. Navigate to Communication Setup under Display Menu List Box.
2. Select Ethernet.
3. Select either Modbus or BACnet.
4. If Modbus is selected, set the following:
• Modbus Port (optional)
If BACnet is selected, set the following:
• Device ID
• BACnet Port & BBMD
5. Select either DHCP or Static IP.
6. If DHCP is selected, proceed to the next step.
If Static IP is selected, set the following:
• Static IP Address
• Subnet Mask
• Gateway Mask
• Default Gateway
7. Click SEND SETUP TO METER
12
Page 19
3 METER CONFIGURATION
3.2.4 Configuring Alarms in S7 Configuration Utilities
The VerifEye power meter has the ability to set alarms for over and under
conditions for voltage and current on any meter channel.
Configuration Input Methods
S7 Configuration Utilities uses dynamic entry for the specification of Alarm
settings. Whichever text entry field is selected becomes the forcing condition and the other related fields are updated by calculation to reflect a consistent set of conditions. The text entry fields in grey are Configuration and are NOT retained by the meter. Only the fields with a black background are stored in the meters memory or in configuration files
Nominal Values
Entering alarm thresholds based on “percent of nominal” values is helpful
Absolute Values
Entering alarms based on absolute value is a matter of entering the
when alarm conditions are desired to be centered around electrical components or industry standard conditions. For example, an over current alarm may be set to 80% of an installed circuit breaker to alert when that breaker exceeds NEC recommendations.
triggering values directly in the register fields (black background).
13
Page 20
3 METER CONFIGURATION
3.2.5 Setting the Real Time Clock
The VerifEye meter includes a Real Time Clock. The clock is used only to time
stamp Interval Data in the log, it is not used for calculation within the meter. For those customers using the IDR function of the meter, it is helpful (but not strictly necessary) to set the real time clock so that data records can be uniquely identified. The time can be set using S7 Configuration Utilities, under the Advanced Tab, by clicking on the small time icon in the bottom right corner of the clock.
The clock icon launches the Window Calendar and allows the user to choose
desired date and time. Set Time to Now populates the current time. Click OK to commit this time to the RTC chip onboard the meter.
Real Time Clock Power Source
The RTC integrated circuit is a stand alone low power circuit within the VerifEye
meter. Time is kept in the absence of a connected external power source (AC or USB power) by a super capacitor. The capacitor can keep the RTC running over normal power outages (days to weeks) but is not expected to keep time while the meter is being stored or shipped.
NOTE: It is recommended that users desiring to use the Interval Data
Recording capability of the VerifEye meter ensure the Real Time Clock is set as part of the commissioning process.
14
Page 21
3 METER CONFIGURATION
3.2.6 Retrieving Interval Data
The VerifEye meter maintains an internal log of the energy data (Net kWh) for
each channel in the meter. This log is updated every 15 minutes and is always active. The meter stores 63 days’ worth of 15 minute data in its memory. This data can be retrieved by users looking to restore gaps in data collection where RTUs may have been offline or communication has been interrupted. The Interval Data Recording (IDR) is assessed through S7 Configuration Utilities in the Advanced menu.
Click Download
By default, the name of the data file will include the Serial Number of the Meter
and the System Description followed by – Datalog.
After clicking OK the entire data path will be displayed
The data log is a Comma Separated Values (CSV) file that can be opened
in Excel or another program. The data will be listed in Chronological Order according to an internal 32 bit sequence counter. The sequence counter can be used to merge separate files together if necessary.
EXAMPLE:
Sequence Number
123456 5/15/2018 12:00 1.11E+5 2.22E+5 3.33E+5 6.66E+5 0
123457
Time Stamp A1 kWh A2 kWh A3 kWh A System B1 kWh …
5/15/2018 12:15 1.12E+5 2.23E+5 3.34E+5 6.69E+5 0
15
Page 22
3 METER CONFIGURATION
3.3 VerifEye Web App Overview
The VerifEye meter hosts a Web Application that can be accessed by any smart
device running a web browser. The VerifEye Web App can be accessed by using the USB or Ethernet port.
NOTE: Mac users can configure the meter using the VerfiEye Web App Interface
by installing a driver which is included in the Media Distribution materials.
3.3.1 Connect to Web App Using USB
1. Connect your smart device to the meter.
2. Open Web Browser.
3. Enter http://169.245.1.5 in the address bar
3.3.2 Connect to Web App Using Ethernet
Navigate to About Meter on the LCD menu.
(this is the static address of the USB port)
1. Discover the IP address of the meter by one of the following methods.
Use a network discovery tool to find the address by connecting
– Set the meter to a static address using the serial interface.
2. Connect your smart device to the same subnet as the VerifEye meter.
3. Open a Web Browser.
4. Enter the meter's Ethernet address into the web browser.
3.3.3 Authentication
Because the VerifEye Web App can be viewed and controlled by any smart
device, and communicates in parallel to the host system, the meter can be configured to require a PIN# to restrict access to it.
Enter the PIN#, if assigned, or leave blank, if unassigned, and click Login.
Organizationally, the VerifEye Web App works much the same as S7
Configuration Utilities , although it has no analytics and operates on a single element at a time.
and disconnecting the Ethernet cable.
16
Page 23
4 METER INSTALLATION
This section is intended to support the physical installation of the meter and provide guidance on connecting the current transformers (CTs) correctly within the electrical load center and to the VerifEye meter.
4.1 Meter Mounting Configurations
VerifEye meters are sold in several form factors. Enclosures are designed to be
wall mounted and connected to electrical conduit. Plate mounted versions are ready to be mounted inside a customer supplied NEMA enclosure.
CAUTION: Care should be taken not to flex the circuit board during mounting.
Enclosure
Cat. 71D48 (pictured)
Plate Mounted
Cat. 70D48 (pictured)
Cat. 70N48
17
Page 24
4 METER INSTALLATION
4.2 Installation Sequence
For Enclosure Model Only (Cat. 71D48)
1. Remove covers.
Screws provided.
2. Mount.
Use the enclosure as a template.
NOTE: If meter is not available to use as a template, see the
mechanical specifications drawing in the appendix.
18
Page 25
4 METER INSTALLATION
3. Connect.
• Conduit fittings
• Conduits
• Blanking plugs
4. Connect voltage leads.
WARNING: RISK OF ELECTROCUTION, SHOCK, EXPLOSION, OR ARC FLASH. DO NOT ENERGIZE METER WITH VOLTAGE COVER REMOVED. CAREFULLY READ AND FOLLOW INSTRUCTIONS.
Connect the voltage leads (L1, L2, L3 and N as necessary) to the meter through a dedicated disconnect or circuit breaker.
NOTE: Verify the circuit breaker is marked as the disconnect breaker for
the meter.
19
Page 26
4 METER INSTALLATION
5. Attatch high voltage cover.
NOTE: IP30 TOUCH SAFE
(with internal cover installed)
6. Connect CT and communications wiring.
20
Page 27
4 METER INSTALLATION
4.3 Wiring in a 3-wire, Split Phase Service Panel
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at
circuit breaker or fuse and test that power is off before wiring!
WARNING: HIGH VOLTAGE MAY BE PRESENT. To be installed by qualified personnel only.
Configurations shown are for service types available in the METER SETUP drop down menu.
3-wire, 1 phase used
on MAINS L1-N, L2-N
(Rogowski coils shown)
Connect the Neutral
wire to V INPUT 1 (N)
on the meter
L1NL2
CT
CT
CT
CT
CT
CT
Single phase
110VAC plug loads
L1-N or L2-N
EXAMPLE LOADS:
Single phase L1-N or L2-N 110 VAC: lighting, appliance, living zone
Single phase L1-L2 220 VAC: water heater, clothes dryer, equipment with no neutral wire
Split phase L1-L2 220 VAC: service entrance, equipment with neutral wire
Meter is powered
from L1 to L2 on
the V input 1
terminal (label as
disconnect)
Single phase
220 VAC Plug Load
L1-L2
3-wire, 1 phase
split load
L1-N, L2-N
21
Page 28
4 METER INSTALLATION
4.4 Wiring in a 3 Phase, 4 Wire Service Panel
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at
circuit breaker or fuse and test that power is off before wiring!
WARNING: HIGH VOLTAGE MAY BE PRESENT. To be installed by qualified personnel only.
Configurations shown are for service types available in the METER SETUP drop down menu.
3-wire, 3 phase used on
MAINS L1-N, L2-N, L3-N
(Rogowski Coils shown)
Single phase branch loads
L1-N
4-wire, 3 phase
WYE load
(Neutral current)
L1-N, L2-N, L3-N
CT
CT
CT
CT
(Label as disconnect)
CT
CT
L1-N, L2-N(est), L3-N
Connect the Neutral wire
or Ground wire
to V INPUT 1(N)
on the meter
Meter power
connect all phases
to V INPUT 1
terminal
3-wire, 3 phase
delta load
(no possibility of
neutral current)
NOTE: The VerifEye Meter Series uses the NEUTRAL terminal as a voltage
reference. For systems without a neutral conductor, Leviton suggests connecting a ground wire to this terminal. If the neutral terminal is left open, L-L measurements will be accurate, but L-N measurements may not be symmetric. If a ground wire is connected to the NEUTRAL terminal, <2mA will flow into the ground wire.
22
Page 29
4 METER INSTALLATION
4.5 Current Transformers Basics
Ensure CTs meet the following criteria by referrng to label on CT:
• 600 VAC UL Rated
UL2808 Listed
• 1/3 (333 mV) output voltage
Appropriate range for the circuts (5-120% of CT Rating Recommended
• Arrow points toward load (or as instructed by CT label)
• Arrow points away from panel (or as instructed by CT label)
Placed on first conductor of voltage reference (L1-L2) circuits are placed
• Observe wiring color and polarity
• Use the Shield wire if provided (connect to PCB terminal marked S)
Ensure CT orientation & placement:
on L1
Current Transformers Basics
White: Positive
Black: Negative
(no shield)
Rogowski Coil CTs
White: Positive
Brown: Negative
Bare Wire: Shield
23
Page 30
4 METER INSTALLATION
4.6 Wiring the CTs to the VerifEye Meter
The image below shows how to connect CTs to the input terminals on the
S7000/7100 for each service type. For service types that are not specifically listed, choose SINGLE PHASE service from the drop down menu and configure each channel individually. The three phase loads that are illustrated on the left and split phase loads on the right are shown as examples only. Elements are fully interchangeable on the meter.
NOTE: Current and voltage inputs must be installed ‘in phase’ for accurate
readings (e.g. CT1 on Line 1, CT2 on Line 2) Orientation is critical. Ensure that all CTs are properly oriented with the line and load, as marked.
CAUTION: Failure to install CTs in the correct orientation and on the correct
phase will lead to inaccurate meter readings.
NL1L2 NL1L2L3
C
G
K L
D
CH1
H
CH2
CH1
CH1
CH2
CH3
CH1
CH3
CH1
A B
4-Wire, 3-Phase Wye Load
L1-N, L2-N, L3-N
E F
3-Wire, 3-Phase
Delta
I J
2-Wire
1 Phase Load
Single Phase, 2-Wire Load
L1-N
Single Phase, 2-Wire Load
L2-N
2-Wire, 220 VAC Load
L1-L2
PRIMARY SECONDARY
M N
White
Black
Red
Blue
3-wire, 1-phase, Split Load
L1 L2 L3 L1 L2 L3
N
N
HIGH
VOLTAGE
VOLTAGE
24
L1-N, L2-N
Red
Black
White
O P
CH1
CH2
Page 31
5 COMMUNICATION & VERIFICATION
This section is intended to support the commissioning of the meter by an instrumentation technician. In many cases, the electrical installation is conducted ahead of the availability of the RTU or was performed by a different installer. Often the technician is working in concert with a remote programmer who is confirming the connectivity with a remote host system. A Digital Multimeter (DMM) can be used to confirm measurements at the board terminals, if necessary.
WARNING: It is assumed that the meter is now powered up from the line voltage. ONLY IF THE INTERNAL HIGH VOLTAGE COVER IS INSTALLED is it safe to touch
the meter (including the user buttons) with the top cover removed.
NOTE: Communications settings and real-time data values can be confirmed quickly using the LCD interface if equipped. When significant setup modifications are anticipated, a computer interface is recommended.
5.1 Physical Connections on an RS-485 Multidrop Network
The VerifEye meter uses a 2-Wire Half Duplex RS-485 Implementation.
Tx
MASTER
Rx
120 ї
Tx
Slave 1
Rx
Tx
Slave 2
Slave n
120 ї
Tx
Rx
Rx
680ї
120ї
680ї
+
-
Termination Resistors — These are NOT included on the VerifEye meter.
If the VerfiEye meter is at the end of a daisy-chain, then connect a 120-ohm leaded resistor between the + and – terminal at the connector.
Bias Resistors — These are NOT included on the VerifEye meter. Bias
resistors are needed if the idle conditions of the bus are in an indeterminant logic voltage. Bias resistors are usually located at the master node and are usually 680 ohms for a RS-485 network.
Network Topology — RS-485 is designed to be implemented as a daisy
chain (series connections) rather than star or cascade topologies.
Signal Names — Some RS-485 devices use the terminology A/B while
others use +/-. Note that A is (-) and B is (+). Many manufacturers incorrectly label the terminals.
Bus Loading — The VerifEye meter is a 1/8th unit load allowing up to 256
like devices in parallel.
25
Page 32
5 COMMUNICATION & VERIFICATION
5.2 Communication Verification
NOTE: Verification includes confirmation of BOTH the physical interface settings
(Serial or Ethernet) and the protocol (Modbus or BACnet) settings.
The LCD User interface can be used to quickly confirm the settings required for
each combination of interface and protocol. The interface is intuitive and groups together commonly associated registers. Arrows indicate how to move from one menu display to the next. The active menu item is indicated by a blinking character on the LCD. The ENTER button is used to select a property and up / down buttons are used to select among the values supported by the meter.
NOTE: Changes to the meter configuration are limited to the communication
interface using the LCD. If additional changes (such as CT type) are required they must be made using a software interface.
Main Menu
View Communications
Real Time Values View Meter Setup Verify Installation Log In/Out About Meter
View Communications
Real Time Values
iew Meter Setup
V Verify Installation Log In/Out About Meter
NOTE: A full navigational map is available in Appendix A of this user guide.
S7 Configuration Utilities / VerifEye Web App
If your VerifEye model does not include the LCD User Interface, or if you prefer
to verify the installation using software, then verification is facilitated through the S7 Configuration Utilities PC application or the VerifEye Web App which shares a common design. Refer to the section on Configuration Details for an overview and list of instructional videos for S7 Configuration Utilities or the VerifEye Web App.
View Communications
Protocol: BACnet Baud Rate: 9600 Bits: 8N1
Real Time Values
Element A Channels
V A
kW
Element A Channels
kVA
kVAR
kWH
100
23.2
2.0
100 100
1234
101
22.9
2.0
110
-110 ***
99.9
22.0
2.0
111 123 100
26
Page 33
5 COMMUNICATION & VERIFICATION
5.3 Physical Interface Verification
Serial Setup Verification
In a multidrop serial network, the host data format settings are typically known or
specified and the slave is adjusted to match. In some cases (long wiring runs, etc.), it may be necessary to experiment in determining the fastest allowable baud rate for a given wiring configuration by changing BOTH the host and slave devices. Configurations other than 8N1 are rare and it is advised to use this configuration for Data Bits, Parity, and Number of Stop bits, if possible.
LAN Ethernet Network Verification
The VerifEye meter communicates using IEEE 802.3 Ethernet connectivity
running at a 10/100 Mbps. Verification of the meter settings over Ethernet includes ensuring that the IP address of the meter is within a range that allows communication with a host (if static) or is set for DHCP, allowing the meter to be assigned an address by a DHCP server as described below.
DHCP
If the VerifEye meter is configured for DHCP when the meter is powered on,
or the Ethernet cable is inserted, the meter is assigned an IP address by the DHCP server. This address appears on the meter LCD or can be found through connection with S7 Configuration Utilities or the VerifEye Web App. The IP address assigned to the meter should be regarded as a temporary address as the address may change between power cycles making it difficult for the host system to know how to find the meter on the network. One common approach is to set the VerifEye for DHCP so that the address can be assigned by a DHCP server and then change that IP address to static once the connection is made. VerifEye meters are set to use DHCP as a default setting to facilitate this approach.
Static IP
If the VerifEye meter is set to a static IP then its address should be assigned by
an IT department to avoid multiple devices on the same network. This scheme is usually used when an RTU is expecting to find the meter at a specific IP address.
5.4 Protocol Verification
The network protocol is typically specified as part of the installation. BACnet MS/
TP and Modbus RTU are the two communication protocols that operate over an RS-485 serial network and BACnet IP and Modbus TCP are the protocols over Ethernet. Each combination of interface and protocol require specific registers settings described below. The scope of this section is to use either the LCD interface or software tools to quickly confirm or change settings to match an existing specification. Further information and optimization tips are covered in the section on RTU programming.
27
Page 34
5 COMMUNICATION & VERIFICATION
5.5 Modbus Settings
Modbus RTU Settings
Device Address: In a Modbus network each device must be assigned a unique
slave address. Valid Modbus addresses are 1-240 (the VerifEye 48 channel meter requires 15 addresses beyond Element A). The slave address of the power meter sets the register address for Element A. Adjacent elements B, C, D, etc. are accessed by incrementing the slave address by 1. The slave address of the VerifEye meter needs to be set to match the address expected by the RTU and is normally part of the network specification. The default address for element A is 1.
Modbus TCP Settings
Modbus Port: The VerifEye meter uses the industry standard Port 502 for
Modbus. This port number can be changed, although this is considered an advanced setting and should be left at 502 unless this generates a conflict on the host system. The port number can only be changed through the S7 Configuration Utilities software interface.
5.6 BACnet Settings
BACnet Device ID: In a BACnet network, each device must be assigned
a unique Device ID and is common to BACnet MS/TP and BACnet IP protocols. Besides the standard ability to change this from a BACnet explorer
tool it may be changed via S7 Configuration Utilities, VerifEye Web App, or LCD.
BACnet MSTP
Device Address: VerifEye meters are Master devices and as such must use
MS/TP addresses in the range from 0-127. This address must be unique on the network.
Max Masters: The default setting is 127 and does not usually need to
be changed.
Max Info Frame: The default setting is 1 and does not usually need to
be changed.
BACnet IP
BACnet Port: The BACnet default port is 47808 and does not usually need to
be changed.
BBMD: The BACnet/IP Broadcast Management Device is set to 0.0.0.0 at
default and can be changed through a software tool to allow discovery across networks.
28
Page 35
5 COMMUNICATION & VERIFICATION
5.7 Pulse Inputs
Series 7000/7100 meters are equipped with 2 pulse inputs.
Pulse counting supports accumulation of consumption data from any external meter using a dry contact (Form A Relay) or open collector outputs. The pulse inputs are compatible with “low speed” meters. The pulse duration must exceed 50mS in both the logic low and high state allowing for a maximum input frequency of 10 Hz.
Pulse scaling, resetting and accumulated values are accessed through registers
and are “system” in scope.
Refer to the register list or S7 Configuration Utilities for more information.
5.8 Alarms (SPDT)
The VerifEye meter supports user-configurable alarms for over-current, under-
current, over-voltage, and under-voltage. S7 Configuration Utilities helps users set these values by allowing for values to be entered using direct entry mode or specifying the limits as a percentage of nominal.
Alarm persistence settings are used to allow for temporary conditions, such as a
motor starting, that are beyond trigger limits.
EXAMPLE: In the case of meter upset from ESD events, short persistence
settings may lead to false alarm triggers. When any alarm condition has been satisfied throughout the persistence interval, the VerifEye trips the Master Alarm relay, which is an electromechanical relay on the PCB.
Once tripped, the relay can only be reset by clearing the alarm through Modbus
register/ BACnet object 2451.
The Master Alarm relay can be hard wired to an interrupt or polling circuit in a
host system allowing for a more rapid response than the data polling frequency, if desired. The status of each alarm is determined by reading status registers.
Refer to the register list or S7 Configuration Utilities for more information.
NOTE: The Master Alarm relay is intended for low voltage DC connections.
The user must protect the switch from over-current conditions when closed.
C(+) E(-) C(+) E(-)
PULSE INPUT12
5.9 12 Volt Auxillary Power
The VerifEye meter provides an auxiliary 12 volt output that is derived from an
auxiliary winding on the VerifEye meter’s line-connected power supply. The 12 volt supply voltage is unregulated but protected by a self-resetting fuse. The purpose of the supply is to power external radio equipment or provide supply voltage for analog sensors, such as 4-20 mA current loop devices. If full-rated current is drawn from this terminal, the minimum operating voltage of the L1-L2 power supply is 100 VAC.
29
Page 36
5 COMMUNICATION & VERIFICATION
5.10 Access Restriction Limitations
If security levels have been set up in the meter, no data is accessible through
the LCD user interface or VerifEye Web App without entering the PIN credentials.
NOTE: Protocols such as Modbus DO NOT SUPPORT ANY LEVEL OF security
such that any network traffic acting as a master can retrieve and write data from the registers. Generally, this will require knowledge of the IP address or slave ID and the register list which discourages casual intrusion.
5.11 Security PIN Protection
VerifEye meters have two levels of PIN protection that users can choose to
assign for restricting access to meter information. The PIN logic is described in the figure below. The default user entry (on power up or time-out) is 0000 which satisfies both the Read Only and the Read / Write default register settings.
PIN
(0000 Default)
Read Write Register
(0000 Default)
Read Only Register
(0000 Default)
VALUE MATCH?
VALUE MATCH?
No Data
Access
Yes
No
Yes
No
Read Only
Mode
Read / Write
Mode
Using the Permission Registers
The VerifEye meter uses both a Read Only register and a Read/Write register
to compare against user entries from the LCD keypad or VerifEye Web App form entry. Both internal permission registers have a default value of [0000]. A consequence of this is that both PIN registers need to be configured (i.e. changed from defaults) to implement a read only PIN, otherwise the situation may occur where a user intends to restrict access to Read Only by setting only this PIN unaware of the fact that the default PIN still matches the criteria for Read/Write which will accidentaly promote the user. S7 Configuration Utilities and the VerifEye Web App disallow this condition, but remote programmers using direct register access may create this condition.
30
Page 37
5 COMMUNICATION & VERIFICATION
Read Only Permission Register
Configuring the meter for a Read Only user allows data or configuration items
to be viewed, but not changed. This level of authorization might be appropriate for general end-users such as building owners who may not be aware of the details of the installation. It is recommended to use S7 Configuration Utilities to configure permissions, although it is also possible to set up a Read Only PIN using the VerifEye Web App if a Read/Write PIN has already been entered (either through the LCD or the VerifEyev Web App itself).
Read/Write Permission Register
Read/Write permissions allow users to read and write configuration items and to
reset the PINs. This level of authorization will be required by any technician or user who needs the ability to correct setup errors in the meter. The default PINs (0000) allow new users to reset the Read/Write PIN from either the VerifEye web app or S7 configuration utilities. Permissions cannot be set through the LCD interface.
Reading PINs Over Modus or BACnet
S7 Configuration Utilities can be used to directly report the Read Only and
Read/Write PINS under the Advanced Tab (passwords). The value reported by
S7 Configuration Utilities is the value as entered in the web page or LCD interface.
PINs are also accessible as registers, but are encoded so that reading the value
of the register through an RTU does not inform a user what the password is. This feature allows Leviton Manufacturing to support looking up forgotten PINs, if network access is available.
S7 Configuration Utilities - Unrestricted Access
The S7 Configuration Utilities software tool can be used to read & write
configuration information to the meter without entering credentials.
NOTE: S7 Configuration Utilities is the recommended tool for setting up access
restrictions. It allows users to test the function of the PINs without locking themselves out from the ability to change the PIN.
31
Page 38
5 COMMUNICATION & VERIFICATION
5.12 Verification of Installation
Once the VerifEye meter is configured and communicating with the RTU, it is a
good idea to perform some simple checks to ensure that all the CTs are on the correct voltage phases and that the CTs are facing the correct direction. The following are recommendations that work for typical installations. Special circuit conditions, like unloaded motors, may indicate an installation error when none exists. A Digital Multimeter (DMM) can be used to confirm these cases.
5.12.1 Installation Phase Verification
The VerifEye meter includes a PhaseChek™ algorithm that identifies any
element that the meter suspects may be incorrectly phased (i.e., the CT is associated with the wrong voltage source or is physically on the wrong wire) based on power factors below 0.55. This feature is accessed using the LCD interface by navigating to [VERIFY INSTALLATION] and pressing [ENTER]. The LCD display will list the elements having at least one channel with a low power factor.
CHECK ELEMENTS
A EF
Use the navigation buttons to highlight a specific element and hit enter or just
hit enter and move from element to element using the <- / -> keys. Within each element (identified on the top line of the display) the status of each channel is identified as good (PF > 0.55) or bad (PF < 0.55).
ELEMENT F
CH1 Good
CH2 Bad
CH3 Bad
Two “Bad” channels are often an indication that two CTs are inadvertently
swapped. When the power factor for all enabled channels is greater than 0.55, the meter reports:
CHECK ELEMENTS
ALL CHANNELS GOOD
NOTE: PhaseChek is only applied for elements that are enabled. [VIEW METER
SETUP] on the LCD screen can be used to ensure that all intended elements are active. PhaseChek is advisory only. It is possible that the power factor for a particular load is truly less than 0.55, as may be observed in a free running motor.
The S7 Configuration Utilities and the VerifEye Web App run PhaseChek
continuously on all enabled elements and report low power factor in the real time values table by turning the text RED or by a using a red indicator.
32
Page 39
5 COMMUNICATION & VERIFICATION
5.12.2 Phase Checking by Phasor Plot
When a CT is installed on the incorrect phase, the indicated current vector is
pointing either 180 degrees away (a split phase system) or 120 degrees away (a three-phase system) from the true displacement angle. In the latter case, this usually causes a significant decrease in the reported power factor, even if the CT is also on backwards. When the absolute displacement power factor of a load is below 0.55 (an angle greater than 57 degrees between voltage and current), the VerifEye meter will flag it as a phasing error. S7 Configuration Utilities has a Phasor Plot feature that can be used to study the voltage and current vectors of a given meter element.
Check for Low Power Factor
S7 Configuration Utilities: Real Time Values > (All power factors < 0.55
VerifEye Web App: Real Time Values > (All power factors < 0.55 are
LCD: Verify Installation > (LCD will list all elements having a PF < 0.55)
+
are shown in RED)
shown in RED)
-
Export Active Power
Quadrant II Quadrant I
Import Reactive PowerExport Reactive Power
Quadrant III
I Ref (Indicated)
+
Import Active Power
dPF
+
Quadrant IV
+
V Ref
1 Ref
-
Electrical Power Quadrants with Incorrect CT Phase
33
Page 40
5 COMMUNICATION & VERIFICATION
5.12.3 CT Orientation Check
The VerifEye meter reports power and energy in each electrical quadrant under
a different register. When CTs are installed backwards, the indicated current vector is oriented 180 degrees away from the true displacement angle. In accordance with standard definitions, the Wattage and VARs of the effected channel report with a sign opposite from what is expected. Often this means that the import registers will be reading zero while the export registers are showing a value.
NOTE: Backward CTs have no impact on the amplitude of the power factor.
A moderate power factor (>0.7) in concert with a negative power is a clue that the CT is on backwards, but is on the correct phase. If a CT is discovered to be on backwards after the installation is complete, the direction of the CT can be reversed through a user configuration register designed for this purpose, called the Flipper, located at 2226, 2234, and 2235 or use the meter setup within S7 Configuration Utilities’ meter setup.
Check that the wattage has the correct sign (Designated + for loads)
S7 Configuration Utilities: Real Time Values > (Confirm Sign of Power
VerifEye Web App: Real Time Values > (Confirm Sign of Power For All
LCD: Real Time Values > (Confirm Sign of Power For All Elements)
+
For All Elements)
Elements)
-
Export Active Power
Quadrant II Quadrant I
+
Import Reactive PowerExport Reactive Power
I Ref (Indicated)
Quadrant III
Import Active Power
dPF
+
Quadrant IV
+
V Ref
1 Ref
-
Electrical Power Quadrants with Reversed CT Phase
34
Page 41
5 COMMUNICATION & VERIFICATION
5.13 Power Factor Convention
Power Factor is the ratio of a signed number (true power) and an unsigned
number (apparent power). This discrepancy has led to some customer confusion. The VerifEye meter allows users to select between two conventions (ANSI & IEEE). In the IEEE convention the sign of PF follows the sign of power itself. In the ANSI convention a [+] PF indicates a lagging current (inductive load) while a [–] PF indicates a leading current (capacitive load). The sign relationships are shown below for these conventions in each electrical quadrant.
P.F. Q1 Q2 Q3 Q4
ANSI +
IEEE +
5.14 Total Harmonic Distortion
The Verifeye meter reports overall harmonic content in power (% T) based on
its measurement of Power, Var and Apparent Power as illustrated in the figure below. This method cannot indicate the harmonic number or distribution but provides the overall harmonic content.
–.
––
+
+
Total Apparent Power (KVA)
THD
Harmonic Apparent Power
Reactive Power
Displacement Apparent Power (dKVA)
Φ
(KVAR)
Real Power
(KW)
Power Triangle
(for active loads)
In many circumstances users are interested in the harmonic content of current.
In cases where the voltage is very sinusoidial, the T measurement is a good estimate of both power and current. However, if the voltage waveform is distorted, the reported T in power can be misleading. S7 Configuration Utilities can provide additional analysis of harmonic content in voltage and current by sampling the VerifEye raw data and performing digital signal processing on the signal. Using this method, the individual harmonics levels can be observed. The results are presented in a bar graph.
35
Page 42
5 COMMUNICATION & VERIFICATION
5.15 Pre-Processing Aids
The meter has several registers that can aid in pre-processing or post-
processing data that otherwise may need seconday operations.
Snap Thresholds
The signal to noise ratio of the meter is above 80 db at full scale (1 part in
10,000). When the signal amplitude becomes so small that it is indistinguishable from noise it is often better to record 0 than a small random value. Snap Threshold registers (Advanced tab in S7 Configuration Utilities) tell the meter when to record 0 instead of the measurement result. The factory defaults for CT’s are expressed in percent and have a default value of 0.04% Full Scale. The voltage thresholds are in absolute value, the recommended minimum voltage is 1.0 volt
Multipliers
The meter has registers that allow potential transformers and series current
transformers to be used with the VerifEye meter. These registers allow for transformer winding ratios or other scaling adjustments to be included in the meter processing to eliminate post process scaling. Adjustments for voltage are global to the meter while CT’s can be adjusted on a channel by channel basis. The multiplier is a floating-point number and can also be used for post installation calibration if desired. Default values are 1.0
CT Phase Shifts
Current transformers like all other transformers experience a small magnetizing
current that is out of phase with the measurement current. Phase shift registers are available on a per channel basis and allow corrections of +/- 3 degrees. S7 Configuration Utilities loads the default phase shift for the CT types available in the picker list. If no phase shift information is available then enter the accuracy class in degrees (i.e. 1% = 1.0 degree).
Demand
VerifEye meters keep track of electrical demand using a 15 minute sliding
window. The Peak Demand and Present Demand registers contain the highest average power consumption in any 15 minute interval and the average power consumption in the last 15 minute interval respectively. The Clear Peak Demand register is used to reset the peak demand detector.
36
Page 43
6 RTU PROGRAMMING & SCRIPTING
This section is intended for the programmer of the RTU or host system and includes details about meter and element addressing, register locations, data formats and protocol examples.
6.1 Register Organization
The VerifEye meter communicates through the reading and writing of registers.
Registers are organized into functional groups and are compliant with the SunSpec Modbus interface model.
• SunSpec Common Registers
• SunSpec TCP Network Stack Registers
• SunSpec Serial Interface Registers
• SunSpec Energy Meter
The complete register set is included as an Excel file on the supplied thumb
drive or at:
https://www.leviton.com and go to the S7000/7100 product page's
Support/Downloads section.
6.2 Element vs. System Scope
Element
The term “element” is used in two contexts. Physically the term Element is
used to describe groups of three channel sections identified by alphabetic letter on the silk screen of the PCBA (ie A,B,C,D). In a three phase power system these correspond to electric circuits. Logically the term Element describes the scope of a data item, register or point (Modbus register or BACnet object). Each Element based point is accessed by choosing the appropriate Modbus address, BACnet object range, or BACnet structured view. Elements in turn have points that refer to individual channels or to SUMS or AVERAGES of those channels. Registers that contain data inclusive of more than one channel are identified as being either SUMS or AVERAGES of the enabled channels within an element. In a BACnet structured view an Element represents a level of organization for related points.
Channel
Channels are identified on the circuit board as CH1, CH2, or CH3 and represent
physical CT inputs. In three phase system configurations, these correspond to a current load on a corresponding line voltage. In single phase configurations, they are just used to identify a CT location. Registers providing data for an individual channel are also described as elements in their scope as a unique value exists for each Slave Address or BACnet object instance.
System
The term “System” refers to registers defining the characteristics of the entire
circuit board. System registers report the same value independent of the slave address. Under BACnet structured view the system points are grouped together.
37
Page 44
6 RTU PROGRAMMING & SCRIPTING
6.3 Configuring Element and Channel Register for Service Types
The S7 Configuration Utilities software enforces all element configurations to
form a valid electrical system. Configurations performed by remote systems may produce unexpected results if configurations are internally inconsistent. The following tables document how to configure element and channel registers for each service type. Every register should be explicitly written.
RED Text indicates Required Values, PURPLE Text indicates Suggested
Defaults, if this data is not known.
Absolute Address/BACnet Object Assignments for Setting up Service Types
Modbus
Register Template
Service Type 2207
V_Input
Description 2617
Channels Volt Ref CT Type Range Phase Shift CT Multiplier CT Sign
CH1 2220 2223 2224,2225 2224,2225 2221,2222 2226
CH2
CH3 2238 2241 2236,2237 2242,2243 2239,2240 2244
4 Wire, 3 Phase (Wye)
Service Type 1
V_Input 1 or 2
Description
Channels Volt Ref CT Type Range Phase Shift CT Multiplier CT Sign
CH1 L1 – N [1] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH2 L2 – N [2] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH3 L3 – N [3] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
2217
2229 2232 2227,2228 2233,2234 2230,2231 2235
Configurations
31 Char
3 Wire, 3 Phase (Delta)
Service Type 2
V_Input 1 or 2
Description
Channels Volt Ref CT Type Range Phase Shift CT Multiplier CT Sign
CH1 L1 – N [1] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH2 L2 – N [2] mV [1] or RoCoil [2] Same as 1 Same as 1 Same as 1 0 or 1
CH3 L3 – N [3] mV [1] or RoCoil [2] Same as 1 Same as 1 Same as 1 0 or 1
31 Char
Even though CH2 is calculated internally, it is recommended that the CT settings reflect those from CH1, rather than being left at factory default, to facilitate configuration validation from the RTU.
38
Page 45
6 RTU PROGRAMMING & SCRIPTING
2 Wire, 1 Phase (Plug Load)
Service Type 3
V_Input 1 or 2
Description
Channels Volt Ref CT Type Range Phase Shift CT Multiplier CT Sign
CH1 ANY [1-6] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH2 ANY [1-6] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH3 ANY [1-6] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
3 Wire, 1 Phase (Split Phase)
Service Type 4
V_Input 1 or 2
Description
Channels Volt Ref CT Type Range Phase Shift CT Multiplier CT Sign
CH1 L1 – N [1] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH2 L2 – N [2] mV [1] or RoCoil [2] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH3 L3 – N [3] OFF [0] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
Disabled (OFF)
Service Type 5
V_Input 1 or 2
Description
Channels Volt Ref CT Type Range Phase Shift CT Multiplier CT Sign
CH1 L1 – N [1] OFF [0] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH2 L2 – N [2] OFF [0] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
CH3 L3 – N [3] OFF [0] Any > 0A -3.0˚ to +3.0˚ Any > 0 [1] 0 or 1
31 Char
31 Char
31 Char
Any channel that needs to be turned OFF should set the CT Type to OFF.
Even though CH3 is not used for computation it is recommended that the CT settings reflect those from CH1 rather than being left at factory default to facilitate configuration validation from the RTU.
Even though disabled channels are not used in calculations and report 0.0 they still contain configuration information. It is suggested that they be set to a known value rather than left at defaults to facilitate configuration validation by the RTU
39
Page 46
6 RTU PROGRAMMING & SCRIPTING
6.4 Configuring System Registers
Modbus Absolute Address/
BACnet Object Assignment
Register Template
Description 2601
PF Sign Convention
V1 Multiplier 2203,2204
V2 Multiplier 2205,2206
6.5 Modbus Protocol Commands
If configured for Modbus, the Verifeye networked power meter family follows the
Modbus RTU protocol and supports the following command set.
Supported Modbus Commands
Command Name Command Number
Read Holding Registers
Write Single Register 06 Used to write a single holding register to a VerifEye meter
Report Slave ID 11 Used to read information from the identified VerifEye meter
Slave Address
For Modbus/TCP the base slave address (or unit address as the Modbus TCP
spec. calls it) is fixed at 1.
Refer to the section Serial Protocols for additional information on setting the
Slave Address and finding the address of a specific meter element.
Modbus String Entry
Registers that are identified as strings are handled uniquely by the VerifEye
power meter. Each register in the string block must be written to sequentially without interruption either by using a write multiple command or by sending single register commands back to back. The final character in the string MUST be a NUL character (ASCII 0). The meter will process the entire string only if these two conditions are met, otherwise the data is ignored. This special processing has been implemented to protect partial updates for network settings.
Commands Requiring a Processor Reset
Register manipulation of communication protocols or addressing require that
the VerifEye meter performs a soft reset in order to take effect. Register 2100 can receive a user command to facilitate this process. BACnet users write a [1] and Modbus users write [1234] to effect a soft reset. The meter reboot time is approximately 10 seconds.
See the Modbus examples document on the Leviton Manufacturing web
site or included with your electronic documentation for additional support on programming Modbus.
2248
(Hex)
03 Used to read the data values from the VerifEye meter
System
Description 31 Char
PF Sign Convention
V1 Multiplier Any > 0 [1]
V2 Multiplier Any > 0 [1]
Configurations
ANSI [1] or IEEE[2]
Description
40
Page 47
6 RTU PROGRAMMING & SCRIPTING
6.6 BACnet
Building Automation and Control Network (BACnet) protocol was developed under
the auspices of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) and is recognized as an American National, European, and ISO global standard.
BACnet Device ID: All device IDs on a BACnet network must be unique. Refer to
the section Serial Protocols and refer to the Register List for additional information.
Serial: The VerifEye Serial version supports writable max_master, MS/TP address,
max_info_frames properties in the device object for MS/TP networks. For best network performance, the max_master should be set to the highest MS/TP MAC address on the network. The MS/TP address (object 1069) must be unique on the MS/TP network. The max_info_frames does not need to be changed in most installations.
Ethernet: Ethernet versions can register as Foreign Devices to a BBMD. BBMD
stand for BACnet/IP Broadcast Management Device. The BBMD IP address can be set from S7 Configuration Utilities or through character string object 2264. A value of
0.0.0.0 disables foreign device registration. This process requires a processor soft reset.
BACnet Structured View
The VerifEye meter supports the Structured View (SV) object container. If this option
is supported in the BACnet exploring tool, objects will be grouped logically into elements which can be named to reflect electrical or physical locations, followed by system objects, as shown below for a VerifEye 12 having elements A-D.
Within each element, Structured View lists the BACnet objects by Object Type and then by numeric number as shown below. In addition objects for elements are grouped in a “hotel room” scheme. That is Element A (and system objects) have a range from 0-9999, Element B 10000-19999, Element C 20000-29999, to Element P on the VerifEye 48 circuit meter 150000-15999. Some BACnet explorer tools have additional sorting capabilities.
41
Page 48
6 RTU PROGRAMMING & SCRIPTING
VerifEye Supported BACnet Object Types
Object Type Abbreviation Typical Usage
Analog Input: AI Meter Readings (floating point numeric inputs)
Analog V
alue: AV Analog User Settings (floating point numeric outputs)
Binary Value: BV User Boolean Settings
Multi State Value: MSV Enumerated Settings
BitString Value: BSV Bitfield Status Words and Settings
Positive Integer Value: PIV Restricted Range User Settings
Character String Value: CSV User Text string settings
42
Page 49
APPENDIX A: LCD MENU NAVIGATION
About Meter
The complete LCD navigation map is shown in diagram form in the next few
pages. The “About Meter” menu is the most commonly accessed item which requires 5 down presses or 1 up (rolling menu) to access.
Main Menu
View Communications Real Time Values View Meter Setup Verify Installation Log In/Out
About Meter
The About Meter menu contains the following items which are displayed 4 lines
at a time and accessed by using the up and down keys on the front display.
S7000 v2.00
Serial: P121501001 LAN: Connected IP: 10.1.1.1 MC 00:0D:63:00:00:00 Line Frequency: 60.0
Obvius
Copyright (c) 2018 Protocol: Modbus Modbus Address: 1 Modbus Port: 502 MSTP Address: 1 Baud Rate: 9600
DHCP: ON
BACnet Port: 47808 BACnet DevID: 527000 Pulse In 1: 0.0 Pulse In 2: 0.0 System Descriptor:
70x48
UTC Date / Time:
2018-04-24 10:04:08
Model and version Serial number State of LAN connection Current IP address MAC Address Current line frequency Manufacturer name Copyright notice Communication protocol Modbus address Modbus port MSTP address RS485 baud rate Current DHCP Setting BACnet Port BACnet Device ID Channel 1 pulse accumulator Channel 2 pulse accumulator System description
set by user
Current time in UTC (GMT)
43
Page 50
APPENDIX A: LCD MENU NAVIGATION
Menu Navigation
Leviton
If Enter button
Enter PIN Code
0 0 0 0
Main Menu
View Communications
&"4"1"/"12­"/+01))1&,+
Log In / Out
,21"1"/
View Communications
eal-Time Values
&"4"1"/"12­"/+01))1&,+
Log In / Out
,21"1"/
View Communications
")Ǧ&*")2"0
V&"4"1"/"12-
"/+01))1&,+
Log In / Out
,21"1"/
View Communications
")Ǧ&*")2"0 &"4"1"/"12-
V"/+01))1&,+
Log In / Out
,21"1"/
View Communications
")Ǧ&*")2"0 &"4"1"/"12­"/+01))1&,+
Log In / Out
A,21"1"/
OK
Idle Screen
Login if enabled
2!1"Ǔdžǃƽƽ 1&10ǓDžƾ !!/"00Ǔƾ
Serial Settings
Measurement Display
)"*"+1%++")0
V
ƾƽƽƾƽƾdždžǑdž
A
ƿǀǑƿƿƿǑdžƿƿǑƽ
KW
ƿǑƽƿǑƽƿǑƽ
)"*"+1%++")0
kVA
100 110 111
(
ƾƽƽǦƾƾƽƾƿǀ
kWH
ƾƿǀǁǹǹǹƾƽƽ
)"*"+1%++")0
ƾǑƽƿǑƽƾǑƾ
)"*"+12*
V 100
ƿǀǑƿ (ƿǑƽ
Element A
Type: CT CT CT
+$"Ǔƾƽƾƽƾƽ %0"ǓƽǑƽƽǑƽƽǑƽ )-)/ǓƾǑƽƾǑƽƾǑƽ
V In: 1 1 1
"#Ǔƾƿǀ
Element A
%ƾǓ,,! %ƿǓ,,! %ǀǓ,,! 60Ǔ,,!
3ƾǑƽƾƾ
S7000
ǓƾdžƿǑƾǃDžǑƾǑƾǁƾ ǓƽƽǓƽƽǓƾƿǓǀǁǓǂǃǓDŽDž
Network Connected
&+"/".2"+ 6ǓǃƽǑƾ ,-6/&$%1ǯ ǰƿƽƾDŽ
DHCP: ON
ǓƾdžƿǑƾǃDžǑƾǑƾ
or
+"1,/1ǓǁDŽDžƽDž
Ethernet Settings
Installation Check
About Box
Protocol
,!20
ʕ
BACnet
2!1"
ʕdžǃƽƽ
19200
)"*"+1%++")0
V
ƾƽƽƾƽƾdždžǑdž
ƿǀǑƿƿƿǑdžƿƿǑƽ
A
ƿǑƽƿǑƿǑƽ
KW
)"*"+1%++")0
kVA
100 110 111
ƾƽƽǦƾƾƽƾƿǀ
(
ƾƿǀǁǹǹǹƾƽƽ
kWH
)"*"+1%++")0
ƾǑƽƿǑƽƾǑƾ
)"*"+12*
V 100
ƿǀǑƿ (ƿǑƽ
No
Logged
in?
PIN Entry:
Enter PIN Code
1 2 4 5 OK
Logged Out
,ƛ/01&")!
To enter 1
,+"51&")!
To enter 9
,+"51&")!Ǒ+1"/ǃ+!ǁ#,/ǀ
To OK
,&+&0%ǯ,/ǰ
Yes
Communication settings can only be changed if logged in.
Enter IP Address
ƾdžƿǑ1ǃDžǑƾǑƾ
and changes a digit.
selects digit to change.
returns to main menu.
Next Element
and move between fields. and move between elements. Hold button to go faster. Enter returns to main menu.
rd
1%
and 4
ƛ")!
44
Page 51
APPENDIX A: LCD MENU NAVIGATION
Communication Navigation
Main Menu
Communications
Real-Time Values View Meter Setup Verify Installation Log In / Out About Meter
Protocol: Modbus Serial Settings Ethernet Settings LAN Connected
Modbus Ethernet Settings
DHCP: On
ǓƾdžƿǑƾǃDžǑƾǑƾ
Modbus Port: 502
Modbus Serial Settings
2!1"Ǔdžǃƽƽ &10ǓDžƾ ,!20!!/"00Ǔƾ
Modbus Settings
Protocol
ʕ Modbus
BACnet
Set DHCP:
ʕ On
Off
Enter IP Address
ƾdžƿǑƾǃDžǑƾǑƾ
Enter Modbus Port:
502 OK
Select a Baud Rate:
ʕƽǃƽƽ
ƾdžƿƽƽ
38400
ǂDŽǃƽƽ DŽǃDžƽƽ ƾƾǂƿƽƽ
ʕDžƾ
8N2
Džƾ
8E2
Džƽƾ
802
BACnet Settings
Protocol: BACnet Serial Settings Ethernet Settings LAN Connected BACnet Dev ID: 52700
BACnet Ethernet Settings
DHCP: On
ǓƾdžƿǑƾǃDžǑƾǑƾ
BACnet Port: 47808
BACnet Serial Settings
2!1"Ǔdžǃƽƽ &10ǓDžƾ !!/"00Ǔƾ
Protocol
Modbus
ʕ BACnet
Set DHCP:
ʕ On
Off
Enter IP Address
ƾdžƿǑƾǃDžǑƾǑƾ OK
Enter BACnet Port:
47808 OK
Enter BACnet ID:
47808 OK
and changes a digit.
selects digit to change.
returns to main menu.
Enter Address:
00ƾ OK
45
Page 52
APPENDIX B: TECHNICAL SPECIFICATIONS
Main Specifications
Specification Description
Service Types Single phase, split phase, three phase-four wire (WYE), three
oltage Input Channels 90-346 VAC line-to-neutral, 600V line-to-line, CAT III,
V
Current Channels 48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps
Maximum Current Input 150% of current transducer rating (mV CTs) to maintain accuracy.
Measurement Type True RMS using high-speed digital signal processing (DSP) with
Line Frequency 50-60 Hz (45 – 70 Hz measureable range) – measurement taken
Power From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz,
AC Protection
Power Out
Waveform Sampling
Parameter Update Rate
Measurements
Accuracy
Resolution
Indicators
Pulse Inputs
Alarm Output
phase-three wire (Delta)
two independent voltage reference inputs.
depending on current transducer.
Measure up to 4000A with RõCoil CTs.
continuous sampling.
L1-N
500mA AC Max Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.
0.5A Fuse 200kA interrupt capacity
Unregulated 12VDC output, 200 mA, self-resetting fuse
1.8 kHz
1 second
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and system total.
0.2% ANSI C12.20-2010 Class 0.2
Values reported in IEEE-754 single precision floating point format (32 bit).
4-line display, tri-color backlight (PhaseChek™)
VerifEye 70D48, 70N48, 71D48 – 2 inputs
3.3V sourcing voltage (current limited) to customer dry contact pulse output Maximum Pulse Rate 10 HZ (50 msec minimum transition time)
Over/Under Voltage & Current (SPDT Relay - 30 VDC)
46
Page 53
APPENDIX B: TECHNICAL SPECIFICATIONS
Communication Specifications
Specification Description
Hardware RS-485, Ethernet, & USB (for configuration only)
Modbus R
TU or BACnet Master Slave Token Passing protocol
(MS/TP)
Supported Protocols
Max Communication Length (RS485)
RS-485 Loading 1/8 unit
Communication Rate (baud)
Data Bits 8
Parity None, Even, Odd
Stop Bit 2, 1
Termination None provided
Mechanical Specifications
Specification Description
Wire Connections & Voltage
Mounting Enclosure or Panel Mount
High Voltage Cover IP40 (embedded version)
Operating Temperature
Humidity 5% to 95% non-condensing
Enclosure
Dimensions
PCBA Dimensions (L) 21.6cm x (W) 21.6cm x (H) 6.4 cm (8.5” x 8.5” x 2.5”)
Modbus (using SunSpec IEEE-754 single precision floating point model) Modbus TCP BACnet IP
1200 meters total length, with Data Range of 100K bits/second or less
Modbus: 9600 (Default), 19200, 38400, 57600, 76800, 115200 BACnet: 9600 (Default), 19200, 38400, 76800
12-22 AWG 600 VAC, Voltage connection must be #14 AWG or larger & 600 VAC rated
o
-20 to + 60 voltage needed to power the board)
ABS Plastic, 94-V0 flammability rating, connections sized for 1– inch EMT conduit
(L) 33.7cm x (W) 25.1cm x (H) 8.0 cm (13.3” x 9.8” x 3.1”) (enclosure version) (L) 26.2cm x (W) 24.1cm x (H) 8.0 cm (10.3” x 9.5” x 3.1”) (mounting plate version)
C (-4 to 140oF) (the colder the temperature the more
S7 Configuration Utilities Minimum System Requirements
Specification Description
Operating System Windows® 7, Windows® 8, Windows® 10
Communications Port
USB or Ethernet connectivity
47
Page 54
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed impro perly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada Ltd to the attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
FCC STATEMENT:
This device complies with Part 15 of the FCC Rules and ISED License-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. Changes or modifications not expressly approved by Leviton could void the user’s authority to operate the equipment. These limits are designed to provide reasonable protection against harmful interference in a commercial installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help. This Class A digital apparatus complies with Canadian CAN ICES-3(A)/NMB-3(A)
FCC SUPPLIER’S DECLARATION OF CONFORMITY:
Models 70D48, 70N48, & 71D48 are sold by Leviton Manufacturing Inc. 201 N Service Rd, Melville, NY 11747.This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
TRADEMARK DISCLAIMER:
Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, are/may be the trademarks of their respective owners; such use is not meant to imply affiliation, sponsorship, or endorsement. PhaseChek is a trademark of DENT Instruments.
FOR TECHNICAL ASSISTANCE CALL:
1-800-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only)
48
Page 55
Leviton Manufacturing Co., Inc.
201 North Service Road, Melville, NY 11747
Telephone : 1-800-824-3005
Visit Leviton’s Web site at http://www.leviton.com
© 2019 Leviton Manufacturing Co., Inc. All rights reserved.
Specifications and price subject to change at any time without notice.
49
Loading...