PRODUCT SPECIFICATIONS FOR PR150-1L/PR180-1L
TOP VIEW
SIDE VIEW
10
10
4
5
0
0
200
TOP VIEW
SIDE VIEW
10
10
4
5
0
0
200
Wall Switch PIR Occupancy Sensor
APPLICATION
Leviton’s Cat. Nos. PR150-1L and PR180-1L fit in standard wallboxes and are equipped with passive infrared (PIR) sensing technology. These versatile, top-quality devices turn lights ON when a person enters a room and OFF when they leave – automatically. They can be used in a variety of residential applications, including:
Bathrooms Basements Pantries Garages Utility/Laundry Rooms Dining Rooms Hallways Closets Kitchens
The PR150 installs in place of a single pole switch. The PR180 installs in place of a single pole or 3-way wall switch. Both PR150 and PR180 can be used with incandescent and fluorescent lighting (Rapid Start Magnetic ballast ONLY).
R150-1L
P PR180-1L
OPERATION
The PR150-1L and PR180-1L use passive infrared (PIR) detection technology to monitor a room for occupancy. The devices automatically turn lights ON when a person enters a room and OFF when they leave. This saves energy, provides convenience and lowers electric bills. The PR150-1L and PR180-1L are suitable for indoor use only. The occupancy sensors are ideal for any room in the home that would
SINGLE POLE OR 3-WAY CONTROL
The PR150-1L provides single pole control only. The PR180-1L offers single pole or 3-way control. This allows control of one light from two locations, which is ideal for stairways, hallways and rooms with two entrances.
Wall Switch PIR Occupancy Sensors
®
benefit from automatic “hands-free” light control, such as in bathrooms, closets, laundry rooms and garages.
FIELD OF VIEW
The PR150 provides a 150˚ field of view and
Automatic ON/OFF Operation
The units turn lights ON automatically when motion is detected. When motion is no longer detected, lights remain ON for a selected time (from 15 sec. to 15 min.)
350 sq. ft. of coverage. The PR180 provides a 180˚ field of view and 400 sq. ft. of coverage. Both are perfect for use in a variety of residential and light commercial applications.
Decora
then automatically switch off.
Passive Infrared (PIR)
PR150-1L
Field of View
PR180-1L
Field of View
Infrared occupancy sensors are passive devices designed to detect the movement of heat-emitting bodies. They are installed to monitor areas where there are no physical obstructions to block the sensor’s field of view.
How It Works: People naturally emit a small amount of infrared heat. As a person passes through the field of view, the sensor detects the motion as a change in the infrared background and responds by switching ON area lights. After the field of view is unoccupied for a user defined time, the sensor will automatically turn OFF the lights.
Leviton Mfg. Co., Inc.
59-25 Little Neck Pkwy, Little Neck, NY 11362-2591 Tech Line: 1-800-824-3005 Fax: 1-800-832-9538 www.leviton.com
© 2007 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
Page 2
PRODUCT SPECIFICATIONS FOR PR150-1L/PR180-1L
Hot (Black)
Switch #1
Neutral (White)
B
lack
Black
C
ommonTerminal
(
Black Screw)
J
umper
Yellow/Red
Green
(
Ground)
Red
White
L
oad
Green (Ground)
PR180
+
+
+
+
+
+
+
+
Traveler A
Traveler B
N
eutral (White)
B
lack
B
lack
Yellow/Red
R
ed
White
Load
Green (Ground)
PR180
+
+
+
+
+
+
+
+
Capped
Off
Hot
L
ine
1
20VAC 6
0 Hz
Line
120VAC
6
0 Hz
1.73
(44.0)
1.35
(34.3)
2.72 (69.0)
4.13 (105.0)
3.82
(97.0)
3.29
(83.5)
ADJUSTMENT OPTIONS (CAT. NOS. PR150-1L and PR180-1L)
The units are equipped with sensitivity and time adjustment controls, which enable the
ser to control the light and time settings.
u These adjustment options will customize the performance to meet the needs of a specific installation. To adjust, remove the wallplate and use a small screwdriver to turn the adjustment wheels.
Light level adjustment:
• Turning the control toward the + sign adjusts lights to turn ON in bright conditions
• Turning the control toward the – sign adjusts lights to turn ON in darker conditions
Time selection:
• Adjust the time selector to the desired length of time the lights are to remain ON. Lights will remain ON from 15 seconds to 15 minutes after the room is vacated
FEATURES AND BENEFITS
• PR150 with 150˚ field of view and 350 sq. ft. of coverage is perfect for use in residential applications
• PR180 with 180˚ field of view and 400 sq. ft. of coverage is perfect for use in large rooms, home offices and a variety of light commercial and residential applications Ambient light override prevents these devices from
• switching lights ON when there is ample natural sunlight
• Manual override is available for use as a standard ON/OFF switch
• Adjustable delayed OFF time interval (15 seconds to 15 minutes)
• Fits in standard wallbox
• Streamlined popular Decora
®
styling complements any
interior and is compatible with other Decora®devices
• Compatible with Decora Plus™ screwless wallplates and Decora wallplates
INSTALLATION
Occupancy Sensors should be positioned at least 6 feet away from HVAC registers. Obstructions such as furniture,windows, glass shower doors, etc. may prevent the sensor fromdetectingmotion.
PR150/180
iring Diagram 1:
W Single Pole Installation
PR180
Wiring Diagram 2:
-Way Installation
3
SPECIFICATIONS
The devices listed herein (PR150-1L and PR180-1L) shall be Decora®passive infrared (PIR) occupancy sensors capable of detecting infrared emissions from human presence and responding byturning ON incandescent and Rapid Start Magnetic fluorescent ballast lighting loads.
Wall Switch PIR Occupancy Sensors
If these units do not detect movement after a
®
preset time period,they will respond byswitching their assigned loads OFF. Manual override permits normal ON/OFF operation.
Cat. No.PR150-1L shall be capable of controlling
Decora
the load in a single pole application. Cat. No. PR180-1L shall be capable of controlling the load in single pole or 3-way applications.
PR150-1L/PR180-1L
Leviton Manufacturing Co., Inc.
59-25 Little Neck Parkway, Little Neck, NY 11362-2591 Telephone: 1-800-323-8920 • FAX: 1-800-832-9538 • Tech Line (8:30AM-7:30PM E.S.T. Monday-Friday): 1-800-824-3005
Leviton Manufacturing of Canada, Ltd.
165 Hymus Boulevard, Pointe Claire, Quebec H9R 1E9 • Telephone: 1-800-469-7890 • FAX: 1-800-563-1853
Leviton S. de R.L. de C.V.
Lago Tana 43, Mexico DF, Mexico CP 11290 • Tel. (+52) 55-5082-1040 • FAX: (+52) 5386-1797 • www.leviton.com.mx
Visit our Website at: www.leviton.com
© 2007 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
PHYSICAL SPECIFICATIONS PR150-1L and PR180-1L
Operating Temperature Range 32˚F to 122˚F Storage Temperature Range 14˚F to 185˚F Relative Humidity 20% to 90% non-condensing Agency Approval UL Listed (File #E-118904)
ELECTRICAL REQUIREMENTS
Line Voltage 120VAC Operating Frequency 60HZ Load Rating Incandescent: 500W @ 120V
ORDERING INFORMATION
CAT. NO. DESCRIPTION COLORS
PR150-1L Decora Wall Switch PIR Occupancy Sensor, -W (White)
single pole, 150˚ field of view, 350 sq. ft. -I (Ivory)
PR180-1L Decora Wall Switch PIR Occupancy Sensor, -W (White)
single pole or 3-way, 180˚ field of view, -I (Ivory) 400 sq. ft. -A (Almond)
Warranty Information: Limited Five-Year Warranty
CSA Certified (File #LR-91148M)
Rapid Start Magnetic Fluorescent Ballasts Only: 400VA @ 120V
-A (Almond)
G-7101B/A9-dp