Leviton ODCOP, ODC0P Installation Instructions Manual

Page 1
Photocell
1 WATT, 24VDC
Cat. No. ODCØP
INSTALLATION INSTRUCTIONS
DESCRIPTION
The Cat. No. ODC
P Photocell responds to ambient light levels in the viewing area and provides an output that is representative of the ambient light intensity. The output is an analog voltage proportionate to the ambient light level.
The ambient light measured is the light from any light source in the visible spectrum. The Photocell does not distinguish between natural sunlight and artificial light. It contains a sensor which is color and spatially corrected to provide a true representation of changes in lighting levels which a person perceives.
The Photocell operates off of low-voltage power. The input voltage needed is 24VDC with approximately 10mA current consumption. The photocell measures ambient light between 0 and 70 footcandles, and the output voltage has a range between 0 and 10VDC. An output of 0VDC corresponds to 0 footcandles, and an output of 10VDC corresponds to 70 footcandles. This sensor can be used to enable Daylight Harvesting, using specific Leviton Power Packs.
The sensor measures the ambient light that actually falls upon it within a 60° cone extending downward from the sensor (refer to Figure 1). This is the light that gets reflected to the ceiling from the walls, floor and furniture. NOTE: Care must be taken when choosing the mounting location. It is recommended that the sensor be mounted directly above the work space, such as the desk, conference table or computer terminal.
Mounting location is important because the ambient light level will be different at different points in the room, depending on the location of the windows, lighting fixtures, wall colors, etc. The ambient light at the doorway can be much less than that at the windows, corners of the room, or especially on the ceiling. Therefore, it is important to measure the ambient light level over the workplace.
Cat. No. ODC
P Photocell is compatible with specific Leviton Power Packs. The Photocell is to be mounted in an appropriate ceiling location and is connected to the Power Pack through low-voltage wires.
INSTALLATION INSTRUCTIONS
Before installing, carefully read the following instructions to determine the ceiling location of the Photocell. The ideal location should provide a full view of the area to be illuminated.
WARNING: TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH
APPROPRIATE ELECTRICAL CODES AND REGULATIONS.
WARNING: IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS,
CONSULT A QUALIFIED ELECTRICIAN.
CAUTION: USE THIS DEVICE ONLY WITH COPPER OR COPPER CLAD WIRE. WITH
ALUMINUM WIRE USE ONLY DEVICES MARKED CO/ALR OR CU/AL.
TO INSTALL:
1.
WARNING: TO AVOID FIRE, SHOCK OR DEATH; TURN OFF POWER AT CIRCUIT
BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
2. The Photocell can either be fastened onto the ceiling surface, flush mounted into the
ceiling, or installed in a 4" (10.2 cm) round or octagonal outlet box, depending on ceiling material and local codes.
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option, if within such five year period the product is returned prepaid, with proof of purchase date, and a description of the problem to Leviton Manufacturing Co., Inc.,
Att: Quality Assurance Department, 59-25 Little Neck Parkway, Little Neck, New York 11362-2591. This warranty
excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on
DI-000-ODC0P-00A-Pilot
Page 2
Make all connections as described in Steps 4 through 9. Carefully feed the wires into the hole and press the Photocell body into the outer shell until the rim is flush with the shell.
NOTE: If wiring is to be run exposed along the ceiling, carefully trim the plastic from the indentation in the side of the outer shell and lay the Photocell wires through it before tightening the shell onto the ceiling.
3B. TO FLUSH MOUNT INTO THE CEILING (ONLY ALLOWS CONCEALED WIRING, THE OUTER SHELL IS NOT USED): Cut a
2" (5.1 cm) diameter hole through the ceiling. Make all connections as described in Steps 4 through 9. Carefully feed the wires back through the hole and press the Photocell into the hole until the rim is flush with the ceiling.
4. Prepare the Photocell lead wires by removing 3/4" (1.9 cm) of insulation from each lead to expose bare copper wire. Make sure the ends of wires are straight.
5. Determine length of low-voltage wires needed to connect Power Pack to Photocell. Use wires suitable for low-voltage wiring, according to local electrical code.
6. Route low-voltage wires from Photocell location(s) to Power Pack location(s). NOTE: Refer to Power Pack Installation Instructions for complete control unit wiring details.
7. Prepare low-voltage wires by removing 3/4" (1.9 cm) of insulation from each lead to expose bare copper wire. Make sure the ends of
wires are straight.
8. Connect low-voltage wires per Figure 2 as follows: BLACK to Ground, RED To Power and ORANGE to the Power Pack Photocell Input. Twist strands of each separate wire connection tightly, and push firmly into appropriate wire connector. Screw connectors on clockwise ensuring that no bare conductor shows below the wire connectors. Secure each connector with electrical tape.
9. Mount Photocell to ceiling. INSTALLATION IS COMPLETE.
TROUBLESHOOTING: Refer to the Installation Manual and User Guide of specific Lighting Control System utilized.
Power (RED)
Analog Output
(ORANGE)
Ground (BLACK)
Figure 2 - Wiring Depiction