Leviton O2C Series, O2C10-MDW, O2C20-MDW, O2C05-MDW Product Data

PRODUCT DATA
O2C Dual Relay Multi-Technology Occupancy Sensors
Light Pipe
DESCRIPTION
combines line voltage occupancy sensors and photocells into a self-contained unit. The integrated design alleviates the need for separate power pack and occupancy sensor wiring making it a low-cost, efficient energy solution for new construction and retrofits. For true Daylight Harvesting applications, an integrated photocell provides consistent Daylight Design Levels by actively switching the connected load(s) ON and OFF in response to available natural light to maximize energy savings. Vacancy timers continually analyze and adjust to changing conditions using the latest microprocessor-based technology to optimize performance. Auto ON/ Auto OFF automatically turns lights ON and keeps them ON when occupancy is detected and automatically turns lights OFF when the space is vacant or unoccupied. Wire terminals allow for simple connection to a line-voltage circuit and are ideal for existing buildings with limited access to wiring and new construction.
APPLICATIONS
• Daylight Harvesting
• CA Title 20/24 Compliant Occupancy Sensor
• Auto-ON/Auto-OFF
• Manual-ON/Auto-OFF
• Dual Relay Modes Include:
- Fan Control
- Auto ON/Manual ON
- Stairwell Control
- Step Dimming - Alternating Daylighting Levels
- Step Dimming - Load 1 Primary
Leviton Mfg. Co., Inc. Lighting & Energy Solutions
20497 SW Teton Avenue, Tualatin, OR 97062 1-800-736-6682 Tech Line: 1-800-959-6004 Fax: 503-404-5594 www.leviton.com/les
© 2013 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
FEATURES
• Sensors combine both PIR and U/S technol- ogy for unrivaled performance and reliability
• Sensors use PIR technology to initially turn lights ON, and use U/S technology to keep
the lights ON
• Exclusive false-detection software assures
lights are ON only when needed
Auto temperature – adjusts tech sensitivity for optimal detection/operation
Auto-Adapting: Time delay and sensitivity are continually adjusted to occupancy pattern of use
• Vacancy Sensing Time Outs
- Delayed OFF Timer
- Exclusive Walk-through Feature
• False Detection Timer: (M/T) PIR scans for
movement and shuts lights off after 31 minutes without movement, preventing false triggers from HVAC systems
- Time delay and saved settings are protected during power outages and will return to the last known state
• Output short circuit protection
• Industry-exclusive self-configuring local
manual switch input: Momentary or maintained switches are supported
• Presentation Mode allows user to turn lights
OFF and keep them OFF while the room is occupied
• Adjustable Time Delay: 30s, 5min, 10min,
20min, 30min
• Test Mode for simplified commissioning
• Manual Switch and Emergency Override are
Class 1 and Class 2 circuits. Class 2 circuits provided for flexibility
• Industry-exclusive “fail-safe” circuitry: In the
event of product failure, Return-to-Closed feature causes the relay to default ON which eliminates life safety concerns
O2C Dual Relay Multi-Technology Occupancy Sensors
PRODUCT DATA
Window
Peak Sensitivity
68°
O2C04
Typical Dayligt Zone, about 10’
Light Fixture
9’
4’
FEATURES
• Industry-exclusive H.I.S. (High Inrush Stability) technology designed to handle today’s high inrush electronic ballast loads and offer unmatched durability and service
• Robust and reliable mechanically held latching relay provides dependability and robust performance for all load types and provides energy savings over electronically held relays
• Field of View: Units from 500 to 2000 square feet available
• Lenses are easily replaceable and color-coded red
(mid-range), black (extended range) and blue (high denisty) for contractors and end-users to easily iden­tify lenses from the ground
• Visual LED indicators for all states:
- Red - Blinks when infrared is detecting motion and during photocell manual calibration; solid during device malfunction
- Green - Blinks when U/S is detected; solid during auto calibration
- Yellow - Blinks during test mode; solid with emergency/BMS input
- Blue - Blinks when knob settings are changed and during photocell override
RATINGS AND TESTING
• Zero-crossing circuitry for extended life of the relay
• Tested to exceed 1 million switching cycles under
standard loads
• Multiple compliance and regulatory UL testing - consult factory for details
• Passed rigorous NEMA 410 testing for electronic ballast
rating
• BMS Input/Emergency Override: UL 924 listed for Emergency and Egress lighting control
Photocell Features
• Daylight Harvesting Applications:
• Auto-Calibration (Automatic Daylight
Calibration): Photocell intelligently measures light levels to determine optimal daylight design levels for closed loop applications
- Closed loop: Photocell detects total photometric light from daylight or electric sources in the space
- Open loop: Photocell detects measurement of natural light only (sunlight from window or skylight)
• Adjustable daylight design levels: Normal (OFF),
Manual (ON/OFF) and Auto Calibration
• Integrated photocell tested to less than 1 Fc
accuracy
INSTALLATION
• Easy installation into junction boxes with Leviton- exclusive screw guides, coasters and terminal blocks
• Front cover snaps on and off for ease of installation
PHOTOCELL PLACEMENT*
Open Loop Application - Angled Light Pipe
O2C04
45°
Peak Sensitivity
4’
Light Fixture
9’
PHOTOCELL OPERATION
Open Loop - Angled Light Pipe
Closed Loop - Flat Light Pipe
O2C Dual Relay Multi Technology Occupancy Sensors
7 6 5 4 3 2
Lights ON
1
Night time
0
7 6 5 4 3 2
Lights ON
1
DDL
0
OFF trigger point Lights turn OFF
Dawn
Note: Long side of angled light pipe must face toward natural light source (window)
OPEN LOOP
DDL
Dawn
Noon
2.5x DDL Zone OFF
CLOSED LOOP
Noon
ON trigger point Lights turn ON
1.25x DDL Zone ON
Closed Loop Application - Flat Light Pipe
Dusk
Dusk
*May require more than one occupancy sensor for total room coverage
Loading...