Copyright © 2001, 2002, Leviton Mfg. Co., Inc.
These UL listed commercial dimmer packs feature input ports for all the communication protocols you’ll need, including NSI’s Micro-Plex, DMX512, NSI Luma-Net®and 0-10V analog. The 2408 also features epoxy encased toroidal filters, which minimize noise and have a rise time of 400 micro-seconds. Combine with Luma-Net control stations or any Leviton-NSI control console for a totally integrated lighting system.
2408 CD Commercial Dimmer Pack
Dimensional Data
in. [cm] lbs.[kg]
2408 CD 2404 CD 2408 CR
Width 16.75 [42.54] 16.75 [42.54] 16.75 [42.54] Depth 5.00 [12.7] 5.00 [12.7] 5.00 [12.7] Height 20.25 [51.43] 20.25 [51.43] 20.25 [51.43] Shipping Wt. 62.00 [28.12] 35.00 [15.87] 31.00 [14.06]
Applications
• Churches
• Schools
• Clubs
• Restaurants
Page 2
Literature # 010-MKNSI-000 G-6619C
P.O. Box 2210 • Tualatin, Oregon 97062 Phone: (503) 404-5500 • Fax: (503) 404-5594
Copyright © 1995, 2001, 2002 Leviton Mfg. Co. Inc.
Architectural Commercial Dimmer Pack
2408 CD
............................
Description Cat. No.
2408 CD 8 Channel Dimmer FGP-24081-0
2408 CD, 240V FGP-24081-9
2404 CD 4 Channel Dimmer FGP-24041-0
2408 CR 8 Channel Relay FGP-24082-0
2408 CR, 240V FGP-24082-9
Specifications subject to change without notice
Features
• 4 or 8 individual dimmer channels
• 2400 watts per channel, 19,200 watt maximum
(8 dimmer version)
9,600 watt maximum
(4 dimmer version)
• Microprocessor controlled
• 8 fully magnetic circuit breakers
• 120/240 volt operation
• Dual SCR circuit design
• Toroidal choke filtering for each channel
• 400 micro-second rise time
• 512 channel program capability
• Channel address select switch
• Soft start operating mode reduces thermal shock and buffers inrush current to extend lamp life
• Extruded aluminum passive heat dispersion
• NSI Micro-Plex, DMX512 and 0-10 volt analog inputs
• Luma-Net
®
architectural control
system capable
• Pressure screw terminals for hardwire inputs/outputs
• Test switch for dimmer or load testing
• Remote operation with Luma-Net
®
control panels
• Individual channels may be converted to non-dim relays
• Steel chassis construction, wall mountable
• Power LED
• Channel status indicator LED
• Signal status LED
Control Input Terminals
• NSI Micro-Plex
• DMX512
• 0-10 volt analog inputs
• Luma-Net
Power Feed
• 80A 120/240 or 120/208Y VAC, 3-wire service plus ground (single phase)
• #4 AWG THWN or equivalent copper wire rated for at least 75°C
Mounting & Ventilation
• Minimum 36” from top to ceiling
• Minimum 12” from top to other equipment
• Minimum 12” from side to wall
• Minimum 6” from side to other equipment
• If multiple units installed in a small space, ambient air temperature should not exceed 100°F