Leviton LVODS10IDW_OB Leviton LVODS10ID Decora Wall Switch PIR Occupancy Sensor Instruction Sheet

Control Panel
Cover
Push Button
Lens
Mounting Yoke
LED
Window
Bottom
Blinders
60 ft. (18.3 m)
40 ft. (12.2 m)
30 ft. (9.1 m)
20 ft. (6.1 m)
27 ft.
(8.2 m)
38 ft.
(11.7 m)
4 ft.
(1.2 m)
4.5 ft.
(1.4 m)
1
0
8.3
0
Sensor Unit
C O L L E C T I O N B Y L E V I T O N
Designer Wall Switch
Occupancy Sensor
Single Pole (One Location)
or Multi-Location
Rated: 120/277V, 60Hz
Ø
Cat. No. ODS1
Incandescent
800W - 6.67A @ 120V
Fluorescent
1200VA - 10A @ 120V
2700VA - 10A @ 277V
Supplemental
1/4hp - 5.8A @ 120V
No Minimum Load Required
Compatible with electronic and magnetic ballasts,
electronic and magnetic low-voltage ballasts,
incandescent lamps, and fans.
-IDx
FEATURES
• Leviton's Decora® style design • Switches electronic ballasts
• Low Profile, tamper-resistant lens • Ambient Light Override
INTRODUCTION
Leviton Cat. No. ODS1Ø-IDx, Designer Wall Switch Occupancy Sensor, is designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view (monitored space) and automatically switch lights ON and OFF. The controlled lights will remain ON until no motion is detected and the scheduled time-delay has expired.
Cat. No. ODS1
Ø
-IDx is UL listed, CSA certified and conforms to California Title 24 requirements.
DESCRIPTION
The Occupancy Sensor senses motion within its coverage area of 2400 sq. ft. (223.3 m2) maximum and controls the connected lighting. This is a self-contained device which provides sensing and light control. The Occupancy Sensor will turn the lights ON when motion is initially detected, and keep the lights ON for as long as motion is detected.
The Occupancy Sensor uses a small semiconductor heat detector that resides behind a multi-zone optical lens. This
Fresnel
lens establishes dozens of zones of detection. The sensor is sensitive to the heat emitted by the human body. In order to trigger the sensor, the source of heat must move from one zone of detection to another. The device is most effective in sensing motion across its field-of-view, and less effective sensing motion towards or away from its field-of­view (refer to figures 1 and 1A). Keep this in mind when selecting the installation location (refer to figures 1 and 1A).
Note that occupancy sensors respond to rapid changes in temperature, so care should be taken not to mount the device near a climate control source (i.e. radiators, air exchanges, and air conditioners). Hot or cold drafts will look like body motion to the device and will trigger it if the unit is mounted too close. It is recommended to mount the Occupancy Sensor at least 6 ft. away from then climate control source. The device can be mounted in a single gang wallbox.
In addition, it is also recommended NOT to mount the Occupancy Sensor directly under a large light source. Large wattage bulbs (greater than 100W incandescent) give off a lot of heat and switching the bulb causes a temperature change that can be detected by the device. Mount the Occupancy Sensor at least 6 ft. away from large bulbs. If it necessary to mount the device closer, lower the wattage of the bulb directly overhead.
Figure 1: Field-of-View (Horizontal)
Figure 1A: Side (Vertical) Field-of-View
Installation Instructions
DI-000-ODS10-02A
LIMITED FIVE YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Levitons only obligation is to correct such defects by repair or replacement, at its option, if within such five year period the product is returned prepaid, with proof of purchase date, and a description of the problem to Leviton Manufacturing Co., Inc.,
Att: Quality Assurance Department, 59-25 Little Neck Parkway, Little Neck, New York 11362-2591. (In Canada send to Leviton Mfg. of Canada Ltd., 165 Hymus Blvd., Point Claire, (Quebec), Canada, H9R 1E9). This warranty excludes
and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call:
1-800-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only)
www.leviton.com
DI-000-ODS10-02A
FCC COMPLIANCE STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device must not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
INSTALLATION INSTRUCTIONS
WARNING: TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH APPROPRIATE ELECTRICAL CODES AND
REGULATIONS.
WARNING: IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT A QUALIFIED
ELECTRICIAN.
WARNING: CONTROLLING A LOAD IN EXCESS OF THE SPECIFIED RATINGS WILL DAMAGE THE UNIT AND
POSE RISK OF FIRE, ELECTRIC SHOCK, PERSONAL INJURY OR DEATH. CHECK YOUR LOAD RATINGS TO DETERMINE SUITABILITY FOR YOUR APPLICATION.
WARNING: DO NOT INSTALL THIS UNIT TO CONTROL A RECEPTACLE. OTHER CAUTIONS AND NOTES:
1. DISCONNECT POWER WHEN SERVICING FIXTURE OR CHANGING BULBS.
2. USE THIS DEVICE WITH COPPER OR COPPER CLAD WIRE ONLY. WITH ALUMINUM WIRE, USE
DEVICES MARKED CO/ALR OR CU/AL ONLY.
3. DO NOT TOUCH THE SURFACE OF THE LENS. CLEAN OUTER SURFACE WITH A DAMP CLOTH ONLY.
4. THE CAT. NO. ODS1
Ø
-IDx OCCUPANCY SENSOR IS INTENDED TO REPLACE A STANDARD LIGHT SWITCH.
TO INSTALL:
NOTE: Cat. No. ODS1Ø-IDx requires a ground connection in order to operate. Use the ground wire in the electrical box
for ground connection. If there is no ground wire, make sure the electrical box is grounded and attach the ground wire to the box with a screw.
1.
WARNING: TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST
THAT THE POWER IS OFF BEFORE WIRING.
2. Connect wires per appropriate WIRING DIAGRAM as follows (refer to wiring diagrams 1 & 2): BLACK lead to LINE.
BLUE lead to LOAD. GREEN lead to GROUND. Twist strands of each lead tightly and, with circuit conductors, push firmly into the appropriate wire connector. Screw connector on clockwise making sure that no bare wire shows below the connector. Secure each wire connector with electrical tape.
3. Carefully position the wires into the wallbox, then mount the Sensor Unit into the wallbox.
4. Secure device using long mounting screws provided.
5. Restore power at circuit breaker or fuse.
NOTE:
Allow approximately thirty (30) seconds after power is supplied for warm-up. After this, the device will
turn the lights ON and the LED will blink.
Figure 2: Sensor Features
Figure 2A: Control Features
Blinder
Adjustment
Levers
1234
Time
Slash Mark
71047
Range
Light
10
6. Perform the adjustments for the time-out and the light setting (refer to Time Delay and Ambient Light sections).
If necessary, adjust the range control and the blinders to stop any unwanted activation of the lights.
NOTE: To avoid PERMANENT DAMAGE to the unit, be careful NOT TO OVERTURN the control knobs or levers when setting Cat. No. ODS1 small straight blade screwdriver to adjust knobs and a finger to adjust the blinder levers.
NOTE: DO NOT press in on blinder levers or use excessive force (refer to figures 2 & 2A).
7. Attach the Control Panel cover, and a Decora
room and the lights will turn OFF after the selected time-out expires.
Ø
-IDx. The controls can be accessed by removing the wallplate and control panel cover. Use a
®
Wallplate (not included). INSTALLATION IS COMPLETE. Leave the
FEATURES
BLINDERS: The blinders can narrow the field-of-view of the device to prevent unwanted activation from traffic in adjacent
space. There are two blinders, and each operate independently. To operate the blinders, use a finger or small screwdriver to move the blinder adjustment levers toward or away from the center of the device.
The blinder levers are found above the control knobs and below the text BLINDERS on the control panel. With both levers moved fully towards the center, the field-of-view is narrowed to 32°. With both levers moved fully away from the center, the field-of-view is at a maximum 180° (refer to figure 2A).
TIME-DELAY: Cat. No. ODS1 Sensor Unit will wait a certain amount of time and then turn the lights OFF. This wait time is called time-out’.
The time-out is selected from four (4) preset values. Pointing the arrow at one of the markings on the face chooses the value of time. The following selections are available:
Face Marking Value of Time
(/) Slash Mark 30 second fixed time-out used for performing a walk-test. 1 10 minute time-out 2 20 minute time-out 3 30 minute time-out
The “time-out” is factory preset to ten (10) minutes. Refer to figure 2A. NOTE: All time durations mentioned in the instructions are approximate within 10 seconds. AMBIENT LIGHT: The Ambient Light Level is the amount of light present in a room without any artificial light added. If
there is already enough light in a room, the occupant may not need further artificial light. Cat. No. ODS1 adjustment to keep the lights from turning ON if there is enough light already present.
when the ambient light is at the level where artificial light is needed
adjustment of the Light Control.
AMBIENT LIGHT SETTING:
1. With the lights ON, rotate the Time Control fully counter-clockwise (CCW) to set the time-out to the thirty (30) second test mode (refer to figure 2A).
2. Rotate the Light Control fully CCW.
3. Cover the Sensor Unit with an opaque material, or leave the room and let the Sensor Unit time-out and turn the lights
OFF.
4. Rotate the Light Control clockwise (CW) SLOWLY, until the light turns ON. This is the setting for the current level of light in the room.
5. Adjustments are finished.
Manual ON Mode: When the light control is in the fully CCW position the lights will never automatically turn ON. In this
mode the lights need to be manually turned ON by the push-button, and will turn OFF with the absence of motion. If the light control is in the fully CW position, the lights will turn ON whenever motion is detected, even in full daylight.
Intermediate settings will cause the lights to turn ON only when the ambient light is below the level selected by the light control.
NOTE: The ambient light in a room will change with the time of day and the season of the year. RANGE: To decrease detection range and sensitivity, rotate the knob CCW (refer to figure 2A). The detection range can
be adjusted from 100% down to 36%.
Ø
-IDx will turn lights ON when motion is detected. When motion is no longer detected, the
Ø
. Follow these steps to make a more accurate
The adjustment should be made
-IDx has an
TO OPERATE
PUSH-BUTTON: Cat. No. ODS10-IDx has a push-button switch that will toggle the lights (refer to figure 2). If the lights
are OFF, the lights will turn ON when the button is pressed, and remain ON in the presence of motion. In the absence of motion, the Sensor Unit will time-out and turn the lights OFF.
If the lights are ON, the lights will turn OFF when the button is pressed. The lights will stay OFF regardless of motion detected, until the time-out expires. After the time-out expires, the lights will turn ON with the next detected motion. This is useful for slide or film presentations.
NOTES:
The Motion Indicator LED will blink every 2 seconds while motion is detected.
In Manual-On mode, the button must be pressed to turn the lights ON. In the absence of motion, the unit will time-out
and turn the lights OFF.
If Manual-On mode is desired, keep the Light knob in the fully counter-clockwise (CCW) position.
TROUBLESHOOTING GUIDE
1. If there is no response from the unit (the light never turns ON and the LED never blinks) 1 1/2 minutes after power is
applied, then uninstall device and verify there is a ground connection at the wallbox. If there is a ground connection, verify wiring.
2. If the lights never turn ON, but the LED blinks, check if the Ambient Light Control Knob is pointed fully counter­clockwise (CCW). Rotate it clockwise (CW) until the lights turn ON.
3. If the lights constantly stay ON, even when the room is unoccupied:
A. Check the Time setting. See how this time compares to how long the lights stay ON. B. Try lowering the Range Control. Rotate the knob CCW about 30˚. C. If the problem persists, try reducing again. Note: Do Not reduce so much that Cat. No. ODS1
normal occupancy.
Be sure to use the Blinders to block any unwanted hallway traffic.
D. E. Check for reflected heat/motion as Sensor Unit may be seeing motion through a window. F. Check for adjacent HVAC and/or heater ducts.
4. For additional information call Levitons Technical Support Line.
Ø
-IDx cannot see
Wiring Diagram 1: Single Control Application
Sensor
Blue
Hot (Black)
Black
Black
Line
120/277VAC, 60Hz
Green
Ground
Load
White
Neutral (White)
Wiring Diagram 2: Two Location Control Application
Blue
Black
Sensor
Black
Load
Green
Ground
White
Hot (Black)
Line
120/277VAC, 60Hz
Neutral (White)
Black
Sensor
Blue
Green
Ground
DI-000-ODS10-02A
NOTE: Either Sensor can turn the lights ON. Either Sensor must time-out to OFF, or both manual buttons must be pressed for the lights to turn OFF.
FOLD SCHEME
DOCUMENTATION
LEVITON INSTRUCTION SHEET/MANUAL
SPECIFICATIONS
ilka 10/07/03
Helvetica
DI-000-ODS10-02A
Black
N/A
Final fold size:
50 Lb. offset
2.875" x 4.25"
Overall size:
11.5" x 8.5"
Paper size:
Front Panel
Cat. No.
8.5¨
11.5¨
Front Panel
Cat. No.
Front Panel
Cat. No.
Fold Line
Panel Line
Front Panel
Cat. No.
Loading...