Leviton ILLUMATECH IPE04-1L Installation Instructions Manual

Page 1
LIMITED 2 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for two years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option, if within such two year period the product is returned prepaid, with proof of purchase date, and a description of the problem to Leviton Manufacturing Co., Inc.,
is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to two years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call:
1-800-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only)
www.leviton.com
Single Pole (One location) or
3-Way (Multi-location)
120VAC, 60Hz
Electronic Low-Voltage
Cat. No. IPE04-1L (Lighted)
Rated: 400VA
INSTALLATION INSTRUCTIONS
FEATURES
• Leviton's Decora® style design • Color conversion available
• Minimum Brightness Adjustment • ON/OFF LED indicates status of load
• Large ON/OFF switch
INSTALLATION INSTRUCTIONS
WARNING: TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH APPROPRIATE ELECTRICAL CODES AND
REGULATIONS.
WARNING: IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT A QUALIFIED
ELECTRICIAN.
WARNING: TO AVOID OVERHEATING AND POSSIBLE DAMAGE TO THIS DEVICE AND OTHER EQUIPMENT, DO
NOT INSTALL TO CONTROL A RECEPTACLE, FLUORESCENT LIGHTING, A MOTOR- OR A TRANSFORMER­OPERATED APPLIANCE OTHER THAN APPROPRIATE LOW-VOLTAGE LIGHTING.
CAUTION (For Electronic Low-Voltage Only):
1. USE WITH ELECTRONIC LOW-VOLTAGE TRANSFORMERS ONLY. DO NOT USE TO CONTROL A MAGNETIC
LOW-VOLTAGE TRANSFORMER. USE A LEVITON MAGNETIC LOW-VOLTAGE DIMMER TO CONTROL MAGNETIC LOW-VOLTAGE TRANSFORMERS.
2. THIS DIMMER PROVIDES PROTECTION FROM OVERHEATING. AN EXCESSIVE LOAD APPLIED TO THE DIMMER WILL CAUSE THE DIMMER TO OVERHEAT. THE EXCESS LOAD MUST BE REMOVED TO RESUME PROPER OPERATION.
OTHER CAUTIONS:
1. USE ONLY ONE (1) DIMMER PER LOAD. THE SWITCH(ES) WILL TURN THE LIGHT ON AT THE BRIGHTNESS
LEVEL SELECTED AT THE DIMMER.
2. DISCONNECT POWER WHEN SERVICING FIXTURE OR CHANGING LAMPS.
3. USE THIS DEVICE ONLY WITH COPPER OR COPPER CLAD WIRE. WITH ALUMINUM WIRE USE ONLY DEVICES
MARKED CO/ALR OR CU/AL.
MULTI-GANG INSTALLATION:
When ganging dimmers, the side sections of the mounting strap must be removed. Use pliers to carefully bend side sections back and forth until they break off (see Figure 1). The side sections dissipate heat, so removing them requires a derating of the dimmer's capacity (see chart).
MAXIMUM BULB WATTAGE (For Electronic Low-Voltage Only):
Low-voltage dimmers are rated in Volt-Amps (VA). The maximum bulb wattage is determined by the efficiency of the transformer in the low-voltage lighting system. Transformer efficiencies will vary from different manufacturers; consider 90% efficient as average. Use the chart to determine maximum bulb wattage for typical transformer efficiency ratings.
TO INSTALL:
1.
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN
OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
2. Remove existing wallplate and switch, if applicable.
3. Remove 3/4¨ (1.9 cm) of insulation from each circuit
conductor. Make sure the ends of wires are straight.
4. Connect wires per appropriate WIRING DIAGRAM as follows:
WARNING: CONNECT AN ELECTRONIC LOW-VOLTAGE
DIMMER ONLY TO THE PRIMARY (HIGH-VOLTAGE) SIDE OF AN ELECTRONIC LOW-VOLTAGE TRANSFORMER. NOTE: Common terminal of 3-Way Switch is usually labeled and/or BLACK. Twist strands of each lead tightly
and, with circuit conductors push firmly into appropriate wire connector. Screw connectors on clockwise making sure no bare wires show below the wire connectors. Secure each connector with electrical tape.
NOTE: For single pole applications, cap one BLACK lead with an appropriate size wire connector. Secure connector with electrical tape.
NOTE: This model incorporates a trim adjustment which will allow the installer to precisely set the low end of the dimming range to suit each installation. This adjustment is preset at the factory and should require no further adjustments for most installations. If adjustment is required proceed as follows, otherwise continue with step 8:
R
DI-000-IPE04-00A
DI-000-IPE04-00A
R
Two More than
Cat. No. Single Gang 2 Gang
IPE04-1L 400VA 350VA 250VA
MAXIMUM LOAD PER CONTROL FOR MULTI-GANG
Two More than
Rating Single Gang
2 Gang
400VA 360W 315W 225W
MAXIMUM BULB WATTAGE AT 90% EFFICIENCY
C O L L E C T I O N B Y L E V I T O N
/
/
Figure 1 - Dimmer Functions
Slider
ON/OFF
LED
ON/OFF
Push-Button
Switch
Trim Adjustment
Screw
Mounting Strap
Side Sections
Page 2
Hot (Black)
Neutral (White)
Dimmer
3-Way Switch
Black
White
Black
Green
Ground
Red
Line
120VAC, 60Hz
Common Terminal
(Black Screw)
Black
White
Electronic Low-Voltage Transformer
Primary
Side
5. Restore power at circuit breaker or fuse. Press the ON/
OFF push-button switch several times (see Figure 1). The GREEN LED will turn ON and OFF indicating power to the switch. Position the slider to the minimum brightness level (bottom of stroke).
6. The brightness adjustment is located at the top of the dimmer back cover (see Figure 1). Using a small, insulated screwdriver, rotate the trim adjustment until the desired level of minimum brightness is obtained.
7. Check for proper operation by raising the slider to it’s maximum position and returning to minimum (bottom of stroke). If operation is not satisfactory, repeat step 6. When the brightness level is adjusted to satisfaction,
TURN OFF POWER.
8. Installation may now be completed by carefully
positioning all wires to provide room in outlet box for dimmer. Mount dimmer into box with mounting screws supplied. Attach Decora
®
wallplate.
9. Restore power at circuit breaker or fuse. INSTALLATION IS COMPLETE.
COLOR CONVERSION PROCEDURE
The color of this device can be changed to suit your interior design requirements. Simply obtain a color conversion kit of the appropriate color from your Leviton distributor and proceed as follows (please note that wallplate must be removed).
1. Select the color of the face you desire.
2. The frame has snaps on its sides. Using your fingers,
grip around the Decora
®
frame and push on one side to
release it from the strap (see Figure 2).
3. Take the new frame and position it properly to the strap. Line up the plastic snaps with the square holes in the strap. Insert the snaps on one side of the frame into the strap.
4. Firmly press sideways and down to slip the other snaps into place. The frame snaps in with a audible click. Ensure that all four snaps are secure.
5. Moving the slider up or down will automatically engage the slider control mechanism. Replace Decora
®
wallplate. The color conversion is complete.
TO OPERATE
GREEN LED will remain ON when the lights are OFF
- Facilitates access to switch in the dark.
Depress push-button switch to ON position
- Lights will turn ON (GREEN LED will turn OFF).
Move slider - Lights will brighten or dim to level set.
Depress push-button switch to OFF position
- Lights will turn OFF (GREEN LED will turn ON).
Lights will turn ON at set brightness level (from either switch location in a 3-way installation).
TROUBLESHOOTING
Light does not turn ON and ON/OFF LED does not turn ON
- Circuit breaker or fuse has tripped.
- Lamp is burned out.
- Lamp is not connected to line Neutral.
Lights Flickering
- Lamp has a bad connection.
- Wires not secured firmly with wire connectors
Figure 2 - Color Conversion
Hot (Black)
Neutral (White)
Dimmer
Black
Black
Green
Ground
Black
White
Red White
Line
120VAC, 60Hz
Cap with
Wire Connector
Electronic Low-Voltage Transformer
Primary
Side
Wiring Diagram 3 - Three Location Control Application
Wiring Diagram 1 - Single Location Control Application
Wiring Diagram 2 - Two Location Control Application
Hot (Black)
Neutral (White)
Dimmer
3-Way Switch
Black
Black
Green
Ground
Green
Ground
Black
White
White
Red
Line
120VAC, 60Hz
Common Terminal
(Black Screw)
4-Way Switch
Green
Ground
1
1
Travelers between switches "IN" Travelers between switches "OUT"
2
1
2
2
Primary
Side
Electronic Low-Voltage Transformer
Frame
Strap
Snaps
Push in 2 Locations
ON/OFF
LED
Slider
Loading...