Quick Programming Guide
App for Intellect™-enabled Systems
App for Intellect™-enabled Systems
Powering Next Generation Lighting
Best Install and Commissioning Practices
• One room at a time
• Install Intellect-enabled fixtures
• Install Keypad Room Controller
• Open Intellect App on a smart phone or tablet
• Press green or “Refresh” button
Identify Master Keypad Room Controller
1
• Stand next to the Keypad that will be the Master
Keypad Room Controller
• Device at the top of the list will have the strongest
signal—this should be the Keypad closest to you
• Use the button to flash LEDs on
the Keypad to confirm you have the correct one
• Enter PIN if required
• Default PIN is 123123
• NOTE: Customer should change the PIN
from the default for a secure system
2
Create Master Room Controller
• Select “Create New Room” to designate this
Keypad
as the Master Room Controller
• Note: To create a Remote Room Controller for
multi-way switching applications, select “Join
Existing Room”
Name Room
• Select the “Room Settings” gear icon
• Enter the name of the room
Page 2
3
Enroll Devices
• Familiarize yourself with the Main
Configuration screen
• Topics should be addressed from
top to bottom
Add Devices
• Select “Start Enrollment” to scan for lamps and other
Keypads
• As lamps and Keypads are found, they will be added to the
list and the Found Devices counter will increase
• Lamps will dim when enrolled to the network
• Stop enrollment should be pressed when all lamps are
found—enrollment ends at 2 minutes
Verify Devices
• NOTE: Verify that all devices have
been enrolled/added to the system
before moving on to Step 5
• Select the button to identify/flash device. Any device
that is in the room should be named. Delete any device that
is not in the room by “swiping left” and clicking “Delete.”
Room Controller Screen
Back to Search for
App Menu
Room Settings
Toggle between
Control and
Configuration
Mode
Main
Configuration
Topics
4
Create Groups
• Groups are the way the user interacts with the system and
represent a collection of lamps
• Common groups:
• Front of room
• Back of room
• Side lights
• Buet lights
• White board light
• Entry way
• Closet
• Corridor
• Select “Groups” to create groups
Group Programming
• Select “Add Group” button
• Give the Group a name
• Use the buttons to determine which devices to include
• Check the box(es) to include the device in the Group
• Click “Save” when done
• Use the button to visually confirm the correct devices
were added to the Group
Page 3
5
Create Daylighting Zones
• Daylighting Zones are groups of lights that work
together in response to ambient light in a space to
maintain a lighting target
• Common daylighting zones:
• Front of room
• Back of room
• Front of windows
• Far from windows
• Atrium
• Skylit area
• In Room Settings, press the “Enable Daylighting” slider
to enable capabilities
• Return to the main menu and select “Daylighting Zones”
Daylighting Zone Programming
• Select “Add Daylighting Zone” button
• Give the Daylighting Zone a name
• Use the buttons to determine which devices to include
• Check the box(es) to include the device in the Daylighting
Zone
• Click “Save” when done
• Use the button to visually confirm the correct devices
were added to the Daylighting Zone
Page 4
6
Create Scenes
• Scene is a collection of Groups with a fade time and
predetermined level for assignment to a Keypad button
or recall from the control screen:
• Presentation
• Movie
• Lunch
• Meeting
• Cleaning
• Test taking
• Select “Scenes” to create scenes
Scene Programming
• Select “Add Scene”
• Give Scene a meaningful name
• Set Fade Duration or fade time, 2-5 seconds is common
• Select Groups to include
• Set desired Target Levels for each Group selected
• Hit Save
• Note: Saves could fail if not all devices in all Groups are
contacted; try again if it fails
7
Program Keypad(s)
• Multiple Keypads may coexist—
• The first Keypad you identified in Step 1 is the “Master
Room Controller”
• Other Keypads will be “Remotes” and are added using the
Devices screen
• Select “Keypads” and select the Keypad you want to
configure
Keypad Programming
• Select the gear icon on the Keypad button you want to
configure, then assign the action and any other necessary
parameters
• On/O—impacts entire room
• Toggle Room—turns the room on/o from the same
button
• Toggle Group—turns a Group on/o from the same
button
• Scene—executes a scene
• Raise/Lower—multi-press raise/lower
Page 5
8
Configure Room Settings
• Room settings impact the entire room instead of a single
device
• Select the “Room Settings” gear icon
• Occupancy Sensor Settings
• Use the slider to enable/disable occupancy sensor
capabilities
• General > Sensitivity indicates how sensor responds
Mode determines lighting behavior
• Primary/Secondary Timeouts available
• Daylighting Settings
• Use the slider to enable/disable daylight harvesting
capabilities
• Cap Target—lights always return to target
• Override Allowed—user can set lights to any level until
the override time elapses
• Target Mode—auto or manual
• Set Pin—allows user to change pin
• Your phone may require you to “Forget Device” and
reconnect on change
LED Indicators on Sensors
9
Solid Red Blinks red on occupancy
FAST Blink Green Searching for network to join
SLOW Blink Blue Auto-cal in process (typically only an out-of-box behavior)
FAST Blink Blue Failed auto-calibration
Alternate Blue/Green Software update in progress
Solid White Factory default
Leviton Manufacturing Co., Inc. Lighting & Controls
20497 SW Teton Avenue, Tualatin, O R 97062 tel 800-736-6682 fax 504-404-5594
tech line (6:00AM-4:00PM PT Monday-Friday) 800-954-6004
Leviton Manufacturing Co., Inc. Global Headquarters
201 North S ervice Road, Melville, NY 11747-3138 tel 800-323-8920 fax 800-832-9538
tech line (8:30AM-7:00PM ET Monday-Friday) 800-824-3005