Leviton ACS15-1L User Manual

Page 1
Single Pole (One location) or 3-Way (Multi-location)
DI-000-ACS15-00A-X0
Electronic Low-Voltage-1800W – Fluorescent-1800VA – Supplemental-1/2 HP
WARNINGS AND CAUTIONS:
To be installed and/or used in accordance with appropriate electrical codes and regulations.
If you are unsure about any part of these instructions, consult a qualified electrician.
Acenti™ electronic switches are not compatible with standard 3-way or 4-way switches. They must be used with compatible Acenti™ on/off remotes.
Recommended minimum wall box depth is 2-1/2".
Tools needed to install your Switch:
INSTALLING YOUR SWITCH
NOTE: Use check boxes when Steps are completed.
Step 1
WARNING: TO AVOID FIRE, SHOCK, OR DEATH;
TURN OFF POWER at circuit breaker or fuse and test
that power is off before wiring!
ONOFF ONOFF ONOFF ONOFF ONOFF
Step 2
Identifying your wiring application (most common):
NOTE: If the wiring in the wall box does not resemble
any of these configurations, consult a qualified electrician.
ONOFF ONOFF ONOFF ONOFF ONOFF ONOFFONOFF
IMPORTANT:
terminals from the old switch being removed will usually be a different color (Black) or labeled Common. Tag that wire with electrical tape and identify as the common (Line or Load) in both the switch wall box and remote wall box.
Step 3
Side Wire Connection
Side wire terminals accept #14 AWG
• Make sure that the ends of the wires from the wall box are straight (cut if necessary).
For 3-Way applications, note that one of the screw
Preparing and connecting wires:
This switch can be wired using side wire terminal screws or through backwire openings. Choose appropriate wire stripping specifications accordingly.
Cut
(if necessary)
solid copper wire only.
*
• Remove insulation from each wire in the wall box as shown.
1
3 4
2
1
3 4 5
2
Step 4
Installing your Alignment Plate:
Important Notice for Installer
To achieve proper aesthetic installation of the Acenti products, the wall surface surrounding the wall box opening must be fairly flat and free of irregularities. The wall box must be level
Single-Pole
1. Line (Hot)
2. Neutral
3. Ground
4. Load
3-Way
1. Line or Load
instruction)
2. Neutral
3. Ground
4. First Traveler note color
5. Second Traveler note color NOTE: For matching remote w/LEDs
installation, the First Traveler becomes Line Hot.
(See important
*
and recessed or flush to the wall surface. The Acenti installa­tion system allows for adjustments that will correct minor flaws that may be present in the installation area.
This device must be installed with the Acenti Alignment Plate. The Alignment Plate is packaged with the Acenti Wallplate, which is sold separately from this device.
The Alignment Plate will function properly only if it is mounted to a flat wall surface as described above.
Incandescent-1800W – Magnetic Low-Voltage-1800VA (1440W)
5/8"
(1.6 cm)
Strip Gage (measure bare wire here)
Back Wire (either hole may be used)
Back wire openings use #14-12 AWG
solid copper wire only.
Electronic Switch
Cat. No. ACS15-1L (Lighted)
120VAC, 60Hz
INSTALLATION INSTRUCTIONS
WARNINGS AND CAUTIONS:
Use only one (1) electronic switch in a multi-location circuit with up to 9 coordinating remotes without LEDs or up to 4 matching remotes with LEDs.
Maximum wire length from dimmer to all installed remotes cannot exceed 300 ft.
Disconnect power at circuit breaker or fuse when servicing, installing or removing fixture.
Use this device only with copper or copper clad wire. With aluminum wire use only devices marked CO/ALR or CU/AL.
Step 4 contd
Leviton recommends to temporarily position the Alignment Plate prior
to wiring the device. If the wall box wires extend at least 6 inches out of the wall box, it is also possible to install the Alignment Plate after the device has been wired (refer to Wallplate instruction sheet).
The Alignment Plate must be installed with the tab towards the bottom.
Leviton recommends the following 3 methods to temporarily hold the
Alignment Plate – use of device mounting screw, use of wall box wires, or use of electrical tape (refer to the following figures):
Alignment Plate Held
By Mounting Screw
Alignment Plate
Held By Wires
Alignment Plate
Held By Tape
For Single-Pole Application, go to Step 5a.
For 3-Way Coordinating Remote (no LEDs) Application, go to Step 5b.
For 3-Way Matching Remote (with LEDs) Application, go to Step 5c.
A
B
C
Step 5a
Mounting
P
O
T
Screw Alignment
Plate
Installing your Switch – Single-Pole Wiring Application:
Terminal
Screw marked
White (WH)
1
WH
Terminal
Screw marked
Black (BL)
Terminal
Screw marked
Yellow/Red
(YL/RD)
BL
2
3
RD
YL/RD
4
Terminal
Screw marked
Red (RD)
Terminal Label: Use Terminal for 3-Way or More Applications Only. For Single-Pole Applications, Do Not Remove This Label.
Switch
Green Ground Screw
TOP
Electrical
TOP
Tape
Black
Load
White
WIRING SWITCH: Connect wires per WIRING DIAGRAM as follows:
Green or bare copper wire in wall box to Green terminal screw.
Line Hot wall box wire to terminal screw marked "BL".
Load wall box wire to terminal screw marked "RD".
Line Neutral wall box wire to terminal screw marked WH”.
Switch terminal screw marked "YL/RD" should have Red insulation label affixed. NOTE: If insulating label is not affixed to terminal screw marked "YL/RD", use electrical tape to cover.
Proceed to Step 6.
RD
BLWH
YL/RD
Use Terminal for 3-Way or More Applications Only. For Single-Pole Applications, Do Not Remove This Label.
Hot (Black)
120VAC, 60Hz
Neutral (White)
Line
Page 2
Step 5b
Black
White
3-Way Wiring with Coordinating Remote (no LED) Application:
Coordinating Remote Switch
WH
BL
3
D
R
D
/R
L
Y
5
2
1
4
Coordinating Remote (no LED)
BLWH
(unused)
YL/RD
Load
Green Ground
(unused)
RD
Terminal
Screw marked
Black (BL)
Terminal
Screw marked
Yellow/Red
(YL/RD)
WH
Green Ground
RD
Switch
BL
YL/RD
Terminal
Screw marked
White (WH)
1
WH
L
B
3
D
4
R
D
R
/
L
Y
5
Terminal
Screw marked
Red (RD)
Hot (Black)
Neutral (White)
Line
120VAC, 60Hz
2
WIRING SWITCH: Connect wires per WIRING DIAGRAM as follows:
NOTE: The switch must be installed in a wall box that has a Line Hot connection. NOTE: Maximum wire length from switch to all installed remotes cannot exceed 300 ft.
Green or bare copper wire in wall box to Green terminal screw.
Line Hot (common) wall box wire identified (tagged) when removing old switch
to terminal screw marked BL”.
First Traveler wall box wire to terminal screw marked RD(note wire color).
Remove Red insulating label from terminal screw marked YL/RD”.
Second Traveler wall box wire to terminal screw marked YL/RD
(note wire color). This traveler from the switch must go to the terminal screw on the remote marked YL/RD”.
Line Neutral wall box wire to terminal screw marked WH.
WIRING COORDINATING REMOTE: Connect wires per WIRING DIAGRAM as follows:
NOTE: "BL" and "RD" terminals on coordinating remote are unused.
Tighten both screws. NOTE: Maximum wire length from switch to last remote is 300 ft.
Green or bare copper wire in wall box to Green terminal screw.
Load wall box wire identified (tagged) when removing old switch to First
Traveler (note color as above).
Second Traveler wall box wire (note color as above) to terminal screw marked "YL/RD". This traveler from the remote must go to the terminal screw on the switch marked "YL/RD".
Remove White insulating label from terminal screw marked "WH".
Line Neutral wall box wire to terminal screw marked "WH".
Proceed to Step 6.
Step 5c
120VAC, 60Hz
NOTE: The switch must be installed in a wall box that has a Load
connection. The matching remote must be installed in a wall box with a Line Hot connection and a Neutral connection. A Neutral wire to the matching remote needs to be added as shown.
If you are unsure about any part of these instructions, consult a qualified electrician.
NOTE: Maximum wire length from switch to all installed remotes cannot exceed 300 ft.
3-Way Wiring with Matching Remote (w/LED) Application:
Matching Remote
2
WH
L
B
1
4
3
YL/RD
5
Matching Remote (with LED)
Hot (Black)
Line
Neutral (White)
WH BL BL
Green
Ground
YL/RD
Additional Neutral Wire
Screw marked
Screw marked
Terminal
Black (BL)
Terminal
Yellow/Red
(YL/RD)
Green
Ground
Switch
Switch
WH
RD
Terminal
Screw marked
White (WH)
H
W
L
B
RD
1
YL/RD
Terminal
Screw marked
Red (RD)
YL/RD
4
2
3
5
Black
Load
White
WIRING MATCHING REMOTE (wall box with Line Hot connection): Connect wires per WIRING DIAGRAM as follows:
Green or bare copper wire in wall box to Green terminal screw. Line Hot (common) wall box wire identified (tagged) when removing
old switch and First Traveler to switch terminal screw marked "BL".
Second Traveler wall box wire from switch to remote terminal screw marked "YL/RD" (note wire color). This traveler from the remote must go to the terminal screw on the switch marked "YL/RD".
Line Neutral wall box wire to remote terminal screw marked "WH".
WIRING SWITCH (wall box with Load connection): Connect wires per WIRING DIAGRAM as follows:
Green or bare copper wire in wall box to Green terminal screw.
Load wall box wire identified (tagged) when removing old switch to
terminal screw marked "RD".
First Traveler Line Hot to terminal screw marked "BL".
Remove Red insulating label from terminal screw marked "YL/RD".
Second Traveler wall box wire (note color as above) to terminal
screw marked "YL/RD". This traveler from the switch must go to the terminal screw on the remote marked "YL/RD".
Line Neutral wall box wire to remote terminal screw marked "WH".
Proceed to Step 6.
Step 6
Testing your Switch prior to completely mounting in wall box:
Wall Surface
Alignment Pin
P
O
T
If Alignment Plate is temporarily positioned using screw as in
Step 4A, remove screw at this point.
(2 places)
Mounting Screw (remove if applicable)
Alignment Hole
P
O
T
(2 places)
Mounting Screw (2 places)
Position all wires to provide room in outlet wall box for device.
Ensure that the word "TOP" is facing up on the device strap.
Partially screw in mounting screws in wall box mounting hole.
P
O
T
P
Step 7
TO
Switch Mounting:
Restore power at circuit breaker or fuse.
Lights should turn ON. If lights do not
turn ON, tap push pad.
If lights still do not turn ON, refer to the TROUBLESHOOTING section.
Locator
Light
To complete the Acenti™ Switch and Wallplate installation, please refer to the instructions included with the Acenti™ Wallplate and Alignment Plate.
OPERATION
NOTE: The locator light will illuminate when the load is in the OFF
position to facilitate access in the dark.
Push Pad (Default settings) Turn ON from OFF position:
Tap – Lights turn ON.
Turn OFF from ON position:
Tap – Lights turn OFF. If there is a power outage, the lights will
return to the last state before the power interruption, when the power is restored.
Push
Pad
NOTE: This device has a removable push pad. If there is a need to
re-install the push pad, proceed as follows:
Locator
Light
Line up tabs located on top back of pad with openings in the top of strap and gently press in.
Line up tab located on bottom back of pad with opening in the bottom of strap and gently press in.
Press bottom of push pad to re-engage.
Cleaning: Clean with a damp cloth. DO NOT use chemical cleaners.
TROUBLESHOOTING
Lights Flickering
- Lamp has a bad connection.
- Wires not secured firmly under terminal screws of switch and/or remote.
Light does not turn ON and Locator LED does not
turn ON
- Circuit breaker or fuse has tripped.
- Lamp is burned out.
- Lamp Neutral connection is not wired.
Remote does not operate lights
- Ensure that total wire length does not exceed 300 ft.
For additional information, contact the Acenti Information Hotline at Leviton's website at
www.leviton.com/acenti
1-888-4-ACENTI
or visit
U.S. & Foreign Patents Pending
Copyright
©
2004 Leviton Manufacturing Co., Inc.
All Rights Including Trade Dress Rights Reserved
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Levitons only obligation is to correct such defects by repair or replacement, at its option, if within such five year period the product is returned prepaid, with proof of purchase date, and a description of the problem to Leviton Manufacturing Co., Inc., Att: Quality Assurance Department, 59-25 Little Neck Parkway, Little Neck, New York 11362-2591. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS