Leviton 4DUBM-24R, 4DUMR-18R, 41OUM-R24, 4DUMR-12R, 4DUBM-18R User manual

...
Page 1
VerifEye™
Alarm
ne
r
gy
O
)
X2 X1
X
X2
S
WEB VERSION
Series 4100
Compact Power and Energy Meter
Modbus and BACnet
Quick Install Guide
PK-A3130-10-00-0A
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
WARNING: TO AVOID FIRE, SHOCK OR DEATH, turn off all sources of power
supplying equipment before working on or inside the equipment.
• Follow safe electrical work practices. See NFPA 70E in the USA, CSA Z462 in Canada, or applicable local codes.
• Installation, wiring, testing or service must be performed only by qualified persons in accordance with all applicable local codes.
• Read and understand the instructions before installing the product. Follow the instructions during installation.
• Install the product in an appropriate electrical and fire enclosure per local regulations.
• DO NOT use the product for life or safety applications.
• DO NOT install the product in hazardous or classified locations.
• DO NOT exceed the product’s ratings or maximum limits.
• The product may use multiple voltage/power sources.
• Use a properly rated voltage sensing device to confirm that all power is off.
• DO NOT depend on the product for voltage indication.
• Products rated only for basic insulation must be installed on insulated conductors.
• Current transformer secondaries (current mode) must be shorted or connected to a burden at all times.
• Remove all wire scraps and tools, replace all doors, covers and protective devices before powering the equipment.
A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and installations, and has received safety training to recognize and avoid the hazards involved (NEC Article 100).
If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by the manufacturer for any consequences arising out of the use of this material.
WARNING: LOSS OF CONTROL. Networked devices can interfere with critical control functions. Refer to NEMA ICS 1.1 (latest edition). Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Controls or its equivalent in your country, language, and/or location.
Provide a device to disconnect this product from the supply. Place it in close, easy reach of the product, and mark it as the disconnecting device. The device shall meet IEC 60947-1 and IEC 60947-3 and be suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide overcurrent protection for supply conductors with approved current limiting devices suitable to protect the wiring.
For use in an Installation Category III or II, Pollution Degree 2 or better environment only.
Page 2
SPECIFICATIONS
Measurement Accuracy:
Real Power and Energy IEC 62053-22 Class 0.2S, ANSI C12.20 0.2%
Input Voltage Characteristics:
Measured AC Voltage Minimum 90 V L-N (156 V L-L ) for stated accuracy; UL Maximums: 600 V
Impedance 2.5 M1
/5 M1
L-N
Frequency Range 45 to 65 Hz
Input Current Characteristics:
Measurement Input Range 0 to 0.333 Vac or 0 to 1.0 Vac (+20% over-range) Impedance 10.6 k1 (1/3 V mode) or 32.1 k1 (1 V mode)
Control Power:
AC 5 VA max.; 90 V min. UL Maximums: 600 VL-L (347 V
CE Maximum: 300 V DC* 3 W max.; UL and CE: 125 to 300 Vdc Ride Through Time 100 msec at 120Vac
Mechanical Characteristics:
IP Degree of Protection (IEC 60529) IP40 front display; IP20 Meter Terminal Block Screw Torque 0.37 ft-lb (0.5 N-m) nominal/0.44 ft-lb (0.6 N·m) max. Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2) Rail T35 (35 mm) DIN Rail per EN50022
Environmental Conditions:
Operating Temperature -30 to 70 °C (-22 to 158 °F) Storage Temperature -40 to 85 °C (-40 to 185 °F) Humidity Range <95% RH (non-condensing) Altitude of Operation 3 km max.
Metering Category:
North America CAT III; for distribution systems up to 347 V CE CAT III; for distribution systems up to 300 V Dielectric Withstand Per UL 508, EN61010 Conducted and Radiated Emissions FCC part 15 Class B, EN55011/EN61000 Class B
(residential and light industrial) Conducted and Radiated Immunity EN61000 Class A (heavy industrial)
Agency Approvals:
US and Canada (cULus) UL508 (open type device)/CSA 22.2 No. 14-05 Europe (CE) EN61010-1
* External DC current limiting is required, see fuse recommendations.
Page 3
(347 V
); CE Maximum: 300 V
L-L
L-L
L-N
)
L-N
L-N
L-N
L-N
/600 Vac
L-N
L-L
DIMENSIONS
(91 mm)
0.2 "
(4 mm)
2.3"
(59mm)
4.2"
(107mm)
Bottom View
(DIN Mount Configuration)
(107 mm)
4.3 "
(109 mm)
1.8”
(45mm)
1.9”
(48mm)
1.5"
(39mm)
3.6"
(91mm)
Bottom View
(Screw Mount Configuration)
2.4 "
(61 mm)
3.9"
(99 mm)
+
1.2 "
(31 mm)
++
PRODUCT IDENTIFICATION
Series 4100-K Bidirectional metering, Modbus full data set, pulse and alarm outputs. Series 4100-S Bidirectional metering, BACnet full data set, pulse input and
alarm outputs.
Page 4
0.3 "
(8 mm)
0.4 "
(10 mm)
INSTALLATION
WARNING: TO AVOID FIRE, SHOCK, OR DEATH, disconnect power prior to installation.
Reinstall any covers that are displaced during the installation before powering the unit.
Mount the meter in an appropriate electrical enclosure near equipment to be monitored.
Do not install on the load side of a Variable Frequency Drive (VFD). For all S4100 Series (bidirectional) models, observe correct CT orientation.
The meter can be mounted in two ways: on standard 35 mm DIN rail or screw-mounted to the back of the enclosure.
A. DIN Rail Mounting
1. Attach mounting clips to the underside of the housing by sliding them into the slots from the inside. The stopping pegs must face the housing, and the outside edge of the clip must be flush with the outside edge of the housing.
2. Snap the clips onto the DIN rail. See diagram of the underside of the meter.
3. To reduce horizontal shifting across the DIN rail, use two end stop clips.
B. Screw Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside. The stopping pegs must face the housing, and the screw hole must be exposed on the outside of the housing.
2. Use three #8 screws (not supplied) to mount the meter to the back of the enclosure. See diagram of the underside of the meter.
Insert clips from inside
Insert clips from outside
Clip flush with outside edge
Snap onto DIN rail
Screw holes exposed for mounting
SUPPORTED SYSTEM TYPES
The meter has a number of different possible system wiring configurations (see Wiring Diagrams, page 9-10). To configure the meter, set the System Type via the User Interface, Modbus register 130. The System Type tells the meter which of its current and voltage inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power, and determines which phase loss algorithm is to be used. The phase loss algorithm is configured as a percent of the Line-to-Line System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that have Neutral (12 & 40).
Values that are not valid in a particular System Type will display as "----" on the User Interface or as QNAN in the Modbus registers.
CTs Voltage Connections System Type Phase Loss
Measurements
Number of wires
Qty ID
Qty ID Type Modbus
Register 130
User Interface: SETUP>
VLL VLN Balance Diagram
S SYS
Single-Phase Wiring
2 1 A 2 A, NL-N 10 1L + 1n AN 1
2 1 A 2 A, BL-L 11 2L AB 2
3 2 A, B3A,
B,
L-L with N
12 2L + 1n AB AN, BNAN-BN 3
N
Three-Phase Wiring
3 3 A,
4 3 A,
3A, B, C
4A, B, C
Delta 31 3L AB, B, C
B,
Grounded
Wye
40 3L + 1n AB,
C,
BC, CA
BC, CA
AN, BN, CN
AB-BC-CA4
AN-BN­CN & AB­BC-CA
N
Wiring
Diagram
number
5, 6
To avoid distortion, use parallel wires for control power and voltage inputs.
The following symbols are used in the wiring diagrams on the following pages:
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible fro ensuring compliance with local requirements. No fuses are included with the meter).
Earth Ground
X1
Current Transducer
X2
Potential Transformer
Protection containing a voltage disconnect switch with a fuse or disconnect circuit breaker. The protection device must be rated for the available short­circuit current at the connection point.
NOTICE
• This product is designed only for use with 1V or 0.333V current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
• Failure to follow these instructions can result in overheating and permanent equipment damage.
RISK OF EQUIPMENT DAMAGE
PRODUCT DIAGRAM
S4100-K S4100-S
Pulse Loss
Alarm Output
Pulse Output
Alarm
Energy
NC
NO
A
IA
X2 X1 X2 X1 X2 X1
(X2) A (X1) (X2) B (X1) (X2) C (X1)
Two 5-character rows
CT Inputs 1 or 0.333 VAC
of display text. Top row alphanumeric;
Bottom row numeric only
The red alarm LED lights when any of the 3 phase voltages drop below the selected threshold:
• On models with two pulse outputs
(S4100-K), the green Energy LED lights
VOLTAGE INPUTS CAT III 50/60 Hz
ABCN 12
VA
when the energy pulse output contacts are closed.
On models with one pulse input
(S4100-S), the green Energy LED is not used.
Alarm Output
Pulse Input 1
IB
IC
2 X1
(X1
Alarm Energy
UL: 90V
- 600V
L-N
L-L
VB
VC
Neutral
Alarm Energy
E
NC NO + - S
NCN
CE: 90V
- 300V
L-N
L-N
Functions
+
Earth
vary by
model
OUTPUT
-
CONTROL POWER
0.1A 50/60 Hz
S4100-K
Modbus
Shield
+ - S
RS-485
S4100-S
BACnet
Shield
+ - S
RS-485
Control
Power
Page 5
Page 6
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 7
Page 8
Page 2
T
WIRING
b
WARNING
CT terminals are referenced to the meter’s neutral and may be at elevated voltages.
TO AVOID DEATH OR SERIOUS PERSONAL INJURY:
• Do not contact meter terminals while the unit is connected
• Do not connect or short other circuits to the CT terminals
For all Series 4100 meters, CTs are polarity sensitive. Observe orientation.
1-Phase Line-to-Neutral 2- Wire System 1 CT
NL1
X1
X2
1-Phase Direct Voltage Connection 2 CT
L1 L2
N
X1
X2
Diagram 1:
White
Black
A B C N
X1
A
X2 X1
B
X2 X1
C
X2
Diagram 3:
Use System Type 12 (2L + 1n) Use System Type 31 (3L)
A B C N
White
X1
X2
Black
White Black
X1
A
X2 X1
B
X2 X1
C
X2
1-Phase Line-to-Line 2-Wire System 1 C
L1 L2
X1
X2
L1 L2 L3
Page 9
Diagram 2:
Use System Type 11 (2L)Use System Type 10 (1L + 1n)
White Black
Diagram 4:
3-Phase 3-Wire 3 CT no PT
X1
X1
X2
X2
White Black
White
X1
X2
Black
White Black
3-Phase 4-Wire Wye Direct Voltage Input Connection
L1NL2L3
X1
X2
X1
X2
A B C N
X1
A
X2 X1
B
X2 X1
C
X2
A B C N
X1
A
X2 X1
B
X2 X1
C
X2
Diagram 5:
3 CT
Use System Type 40 (3L + 1n)
White Black
White
X1
X2
Black
White Black
CONTROL POWER
3-Phase 4-Wire Wye Connection 3 CT 3 PT
L1NL2L3
A B C N
X1
A
X2 X1
B
X2 X1
C
X2
X1
X2
Diagram 6:
Use System Type 40 (3L + 1n)
White
X1
X2
Black
White
X1
X2
Black
White Black
A B C N
X1
A
X2 X1
B
X2 X1
C
X2
Direct Connect Control Power
(Line to Line)
L1
L2 L3
Line to Line from 90 Vac to 600 Vac (UL). In UL installations the lines may
be floating (such as a delta). If any lines are tied to an earth (such as a corner grounded delta), see the Line to Neutral installation limits. In CE compliant installations, the lines must be neutral (earth) referenced at
less than 300 Vac
Direct Connect Control Power
(DC Control Power)
L-N
12G
12G
Direct Connect Control Power
(Line to Neutral)
L1NL2L3
Line to Neutral from 90 Vac to 347 Vac (UL) or 300 Vac (CE)
12G
Control Power Transformer (CPT) Connection
L1NL2L3
12G
PULSE CONTACT INPUTS (S4100-S
The S4100-S has one pulse input. This input is isolated from the measured circuits. On models with BACnet communication (S4100-S), they are referenced to the communication signal ground and the comm output shield terminal. Use with contacts that do not require current to remove oxidation.
Pulse Input
Contacts
S4100-S
The Comm Shield terminal is connected to the pulse input common on BACnet models only (S4100-S)
SComm
Output
Comm
Ground
Equivalent
Circuit
4-10 VDC
nominal
~10 kΩ
+
SOLID STATE PULSE OUTPUTS (S4100-K)
The Series 4100-K has one normally open (N.O.) KY Form A output and one normally closed (N.C.) output. One is dedicated to energy (Wh), and the other to alarm.
Over-Current Protective Device* (not supplied)
DC Control Power from 125 Vdc to 300 Vdc (UL and CE max.)
The Control Power Transformer may be wired L-N or L-L. Output to meet
meter input requirements
100 mA
LOAD
Power Source**
3 to 30 Vdc
~
=
6 to 30 Vac
Fuse Recommendations:
Page 10
Keep the fuses close to the power source (obey local and national code requirements). For selecting fuses and circuit breakers, use the following criteria:
• Select current interrupt capacity based on the installation category and fault current capability.
• Select over-current protection with a time delay.
• Use a voltage rating sufficient for the input voltage applied.
• Provide over-current protection and disconnecting means to protect the wiring. For DC installations, provide external circuit protection. Suggested: 0.5 A, time delay fuses rated for DC operation at or above the supply voltage.
• Use the earth connection (G) for electromagnetic compatibility (EMC), not a protective earth ground.
Page 11 Page 12
+ – S
Energy Output
Alarm
The solid state pulse outputs are rated for 30 Vac/dc nom. Maximum load current is 100 mA at 25 °C. Derate 0.56 mA per °C above 25 °C (e.g. 86 mA@50 °C). * The over-current protective device must be rated for the short circuit current at the connection point. ** All pulse outputs and communication circuits are only intended to be connected to non-hazardous circuits (SELV or Class 2). Do not connect to hazardous voltages.
100 mA
LOAD
Power Source**
3 to 30 Vdc
~
=
6 to 30 Vac
RS-485 COMMUNICATIONS (S4100-K & S4100-S) DISPLAY SCREEN DIAGRAM
Daisy-chaining Devices to the Power Meter
The RS-485 slave port allows the power meter to be connected in a daisy chain with up to 63 two-wire devices. In this bulletin, communications link refers to a chain of devices that are connected by a communications cable.
LCD Screen:
Screen Name or Units
Diagnostic Alert
120 Ω terminators on the first and last devices of the daisy cha in
+
S
Numeric Data
INITIAL SETUP INSTRUCTIONS
Use this section to enter:
• Modbus or BACnet communication parameters
Shield wire
• CT (Current Transducer) input current ranges
• The service type to be monitored
NOTES:
• The terminal’s voltage and current ratings are compliant with the requirements of the EIA RS-485 communications standard.
• The RS-485 transceivers are ¼ unit load or less.
• RS-485+ has a 47 k1 pull-up to +5V, and RS-485- has a 47 k1 pull-down to Shield (RS-485 signal ground).
• Wire the RS-485 bus as a daisy chain from device to device, without any stubs. Use 120 1 termination resistors at each end of the bus (not included).
• Shield is not internally connected to Earth Ground.
• Connect Shield to Earth Ground somewhere on the RS-485 bus (only at one point).
For all terminals on Series 4100 meters:
• When tightening terminals, apply the correct torque:
0.37 to 0.44 ft-lb (0.5 to 0.6 N-m).
• Use 14 to 24 gauge (2.1 to 0.2 mm
2
) wire.
0.37 to 0.44 ft-l (0.5 to 0.6 N-m)
A. To Navigate to the Setup screens:
1. Press or repeatedly until screen appears.
2. Press to get to the screen.
3. Press to move through the digits. Use the or buttons to enter your
password (the default is ).
4. Press to move to the first Setup screen ( ) on S4100-K, ( )
on S4100-S.
5. Use or to select the parameter screen you want to set.
6. After you set the parameters you want, use or to select the next Setup
screen or to exit the Setup screens (return to ).
Page 13
B. To Enter Modbus communication parameters:
Alive Indicator
Tx
Transmit Data
Rx ERR
Receive Data Receive Data Error
Buttons:
(Left) Back
(Up)
Select
+
(Down)
Select
(Right)
Next
1. Navigate to the (set communications) Setup screen (see section A).
2. Press to go to the screen and through the address digits.
Use or to select the Modbus address (default is ).
3. Press to accept the value and go to the screen. Use or to
select the baud rate (default is ).
4. Press to go to the screen. Use or to select the parity
(default is ).
5. Press to go back to the screen.
C. To Enter BACnet communication parameters (S4100-S models only):
1. Navigate to the (set BACnet) Setup screen (see section A).
2. Press to go to the screen and through the address digits. Use or
to select the BACnet MAC address (default is ).
3. Press to accept the value and go to the screen. Use or to
select the baud rate (default is ).
4. Press to go to the screen and through the upper four digits of the Device
Instance. Use or to select the ID digits (default is a pseudo-random number).
5. Press to accept the value and go to the screen and through the lower
three digits of the Device Instance. Use or to select the ID digits (default
is a pseudo-random number).
6. Press to accept the value and go back to the screen.
D. To Enter the CT (Current Transducer) output voltage and input current ranges:
1. Navigate to the (Set Current Transducer) Setup screen
(see section A above).
2. Press to go to the screen. Use or to select the voltage
mode Current Transducer output voltage (default is ).
Page 14 Page 15
3. Press to go to the screen and through the digits. Use or to
select the CT size in amps (default is ).
4. Press to accept the value and go back to the screen.
E. To Enter the service type to be monitored:
1. Navigate to the (Set System) Setup screen (see section).
2. Press to go to the screen. Use or to select the
configuration (see wiring diagrams - default is ).
3. Press to go back to the screen.
CHINA RoHS COMPLIANCE INFORMATION (EFUP Table)
ӗ૱ѝᴹ∂ᴹᇣ⢙䍘ᡆݳ㍐Ⲵ〠৺䟿6XEVWDQFHV
䜘Ԧ〠
䫵3E ⊎+J 䭹&G ޝԧ䬜&U9, ཊⓤ㚄㤟3%% ཊⓤҼ㤟䟊3%'(
⭥ᆀ㓯䐟ᶯ ; 2 2 2 2 2
2 㺘⽪䈕ᴹ∂ᴹᇣ⢙䍘൘䈕䜘Ԧᡰᴹ൷䍘ᶀᯉѝⲴ䟿൷൘6-7ḷ߶㿴ᇊⲴ䲀䟿㾱≲ԕл ; 㺘⽪䈕ᴹ∂ᴹᇣ⢙䍘㠣ቁ൘䈕䜘ԦⲴḀа൷䍘ᶀᯉѝⲴ䟿䎵ࠪ6-7ḷ߶㿴ᇊⲴ䲀䟿㾱≲
Z000057-0A
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found to comply with the limits for a class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a residential environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Modifications to this product without the express authorization of the manufacturer nullify this statement.
TRADEMARK DISCLAIMER: Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, are/may be the trademarks of their respective owners; such use is not meant to imply affiliation, sponsorship, or endorsement.
PK-A3130-10-00-0APage 16
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Loading...