Leviton 330R4WLEV, 360R6WLEV Installation Manual

Page 1
Watertight Pin and Sleeve
WEB VERSION
Inlets and Receptacles
20A, 30A, 60A and 100A
WARNINGS
TO AVOID FIRE SHOCK, OR DEATH, TURN OFF POWER AT CIRCUIT BREAKER OR FUSE,
• These devices conform to IEC standards 60309-1 and 60309-2. The construction is such that each device cannot be mated with another IEC device of different specifications (i.e., voltage, amperage or system rating). For safety purposes, do not use a non-IEC device with these pin and sleeve devices. The specifions for non-IEC devices are established by the individual manufacturers, and may not meet IEC standards. IMPROPER MATING OF DEVICES MAY CAUSE AN ELECTRICAL
HAZARD WHICH MAY CAUSE FIRE, SHOCK OR DEATH.
PK-A3279-10-00-0A
• Examine devices periodically for any foreign matter that may contaminate the contacts or the insulation material separating the contacts. Contamination decreases the device’s insulation properties. This increases the potential for arcing and possibly decreases the product’s life and may cause fire and/or shock hazard. The frequency of inspection depends upon the degree of contamination.
• If you are unsure about any part of these instructions, consult an electrician.
• To be installed and/or used in accordance with electrical codes and regulations (Including NEC/CEC, as applicable).
CAUTION
• Use this device only with copper or copper clad wire.
20A and 30A Inlet Installation
1. Unscrew contact carrier.
assembly screws
gasket
(pre-attached)
2. Wire.
Cut and strip cable jacket and conductors (Table 1 and Stripping and Wiring Diagram). WARNING: TO AVOID FIRE, SHOCK OR DEATH, connections must be made in the same sequence as existing device connections. Thread and connect wires (Table 2 and Stripping and Wiring Diagram). Tighten terminal screws (Table 4). NOTE: Allen key included.
NOTE: Separate grounding wire has been pre-installed. Connect ground wire first.
grounding wire
(pre-attached)
QUICK INSTALL GUIDE
1. Wire.
Cut and strip cable jacket and conductors (Table 1 and Stripping and Wiring Diagram). WARNING: TO AVOID FIRE, SHOCK OR DEATH, connections must be made in the same sequence as existing device connections. Connect wires (Table 2 and Stripping and Wiring Diagram). Tighten terminal screws (Table 4).
NOTE: Separate grounding wire has been pre-installed. Connect ground wire first.
2. Mount.
Mount (Table 5) and tighten mounting screws (Table 4).
ENGLISH
20A and 30A Receptacle Installation
Allen key (included)
gasket
(pre-attached)
grounding wire
(pre-attached)
terminal screws
mounting screws
(not included)
3. Reconnect contact carrier.
Tighten terminal screws (Table 4).
4. Mount.
Mount (Table 5) and tighten mounting screws.
NOTE: Line up key with
key notch.
mounting screws
(not included)
60A and 100A Receptacle Installation
1. Wire.
Cut and strip cable jacket and conductors (Table 1 and Stripping and Wiring Diagram).
WARNING: TO AVOID FIRE, SHOCK OR DEATH, connections must be made in the same sequence as existing device connections. Connect wires (Table 2 and Stripping and Wiring Diagram). Tighten terminal screws (Table 4).
NOTE: Separate grounding wire has been pre-installed. Connect ground wire first.
gasket
(pre-attached)
grounding wire
(pre-attached)
terminal screws
Allen key (included)
If mounting to a backbox,
use Leviton:
BX230LEV - non-metallic
BX230LEVM metallic
© 2019 Leviton Mfg. Co., Inc.
2. Mount.
Mount (Table 5) and tighten mounting screws.
mounting screws
(not included)
Page 2
60A and 100A Inlet Installation
WEB VERSION
1. Wire.
Cut and strip cable jacket and conductors (See Table 1 and Stripping and Wiring Diagram). WARNING: TO AVOID FIRE, SHOCK OR DEATH, connections must be made in the same sequence as existing device connections. Connect wires. (See Table 2 and Stripping and Wiring Diagram). Tighten terminal screws (Table 4).
NOTE: Separate grounding wire has been pre-installed. Connect ground wire first.
grounding wire
(pre-attached)
terminal screws
1
Device
20A
30A 1.625 41 0.625 16
60A 3 76 1 25
100A 3.5 89 1 25
No.
Wires
All All
Cable Stripping Guide
No.
Conductors
Cable Jacket (A) Conductor (B)
Inches mm Inches
1.375 35 0.375 10
gasket
(pre-attached)
Allen key (included)
mm
2. Mount.
Mount (Table 5) and tighten mounting screws.
BX60LEV (60A), BX100LEV (100A) - non-metallic
BX60LEVM (60A), BX100LEVM (100A) - metallic
Stripping and Wiring Diagram
Cable Jacket
Green equipment grounding conductor only (or green with yellow stripes).
White or gray, system ground or neutral conductor only.
If mounting to a backbox, use Leviton:
Hot conductors (no specific color identification)
B
A
(SeeTable 1)
White dot and N
mounting screws
(not included)
L2
L1
L3
Green dot and
2
and green color
N and white color Grounded circuit conductors (neutral)
L1, L2, L3 Ungrounded circuit conductors (line, hot)
Pilot Control circuit conductor.
3
Device
20A
30A #12
60A #8
100A #6
4
Device
20A
30A 20 (2.26) N/A 8 (0.9)
60A 50 (5.65) 20 (2.26) N/A
100A 50 (5.65) 20 (2.26) N/A
From To
AWG COND TYPE AWG COND TYPE
3
#14
55
3
55
3
55
3
55
Screw Tightening Guide in-lbs (N-m)
Terminal
Screws
20 (2.26) N/A 8 (0.9)
Terminal Identification Chart
Wire Sizes
S #10
S#83S or W 0.580/1.125 15/2944
S or W #2
W#0
Pilot Terminal
Screws
Equipment ground conductor
3
S
3
W 0.875/1.450 22/3744
3
W 0.725/1.600 18/4144
Assembly
Screws
Grip Range
Min./Max.
Wire Diam.
(in)
0.330/0.830 8/2144
Grip Range
Min./Max.
Wire Diam.
(mm)
5
B
Drilling Plan
Receptacles & Inlets
B
A
clearance hole for “D” size screw
C
No. Wires; Device
20A;3 Receptacle 3.26 83 3.12 79.5 3.94 100 #10
20A;3 Inlet 3.26 83 3.12 79.5 3.94 100 #10
20A;4 Receptacle 3.26 83 3.12 79.5 4.33 110 #10
20A;4 Inlet 3.26 83 3.12 79.5 4.33 110 #10
20A;5 Receptacle 3.26 83 3.12 79.5 4.92 125 #10
20A;5 Inlet 3.26 83 3.12 79.5 4.92 125 #10
30A;3 Receptacle 3.26 83 3.12 79.5 5.12 130 #10
30A;3 Inlet 3.26 83 3.12 79.5 5.12 130 #10
30A;4 Receptacle 3.26 83 3.12 79.5 5.12 130 #10
30A;4 Inlet 3.26 83 3.12 79.5 5.12 130 #10
30A;5 Receptacle 3.26 83 3.12 79.5 5.71 145 #10
30A;5 Inlet 3.26 83 3.12 79.5 5.71 145 #10
60A; All 2.76 70 3.86 98 6.69 170 #10
100A; All 3.47 88 4.88 124 7.87 200 #10
A B C (min) D
Inches mm Inches
mm Inches mm
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada ULC to the attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for three years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www. leviton.com or call 1-800-824-3005. is installed impro perly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in
This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product
accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. Leviton
is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
For Technical Assistance Call: 1-800-824-3005 (USA Only) or 1-800-405-5320 (Canada Only) www.leviton.com