Programming Analog Transmitter Range Output 4-20mA
Range : 0.1 - 999.9 4 mA = 0 20 mA = Entered Number.
TR 100 (Default) 4 mA = 0 GPM 20mA =100 GPM
This can be Change to Conform to Customers Application (Ex. Number Changed to 150)
6.1 Programming NPN Pulse Output
Models TKP | TKM Only
Steps Only Necessary If NPN Pulse Output is Required
STEPS
Step-1
Home Screen
Press
Step-2
Programming Flow Rate
Pulse Output
Press
To
Change
Value
Flow Meter & Transmitter
OP2OP1
TKP
SET
F
Flow Meter & Transmitter
OP2OP1
TKP
SET
F
CV
SV
LPM
FTM
CV
SV
LPM
FTM
TKP | TKM Series
Only
1000 Default
One Pulse Per Gallon
Default
(Flow Rate) Pulse
Press SET to Save and Proceed to the Next Screen
Step-3
Programming Flow T otal
Pulse Output
Press
Flow Meter & Transmitter
OP2OP1
TKP
SET
F
CV
SV
LPM
FTM
2000 Factory Default
One Pulse Per Gallon
Default
2000 Default this can be Changed to Desired Value Refer to Next Page Programming OP2 Output for Options for Totalizer
Flow Totalizer Pulse (Step #2-Next)
Press SET Button to Save and Proceed to Next Screen
Change to a Value that meets your Flow Rate Pulse Output
CV > SV Flow Rate Pulse Output ON
SV
CV < SV Flow Rate Pulse Output OFF
Program Value of Flow Totalizer Pulse (NPN) Output
CV
SV : Preset value of Flow Total
SV
CV > SV Flow Rate output ON
Op1 & Op2 = 150mA Max Switching Currency
Current + Consumption is 60mA Max.
CV = Current Value = Current Flow Rate on Display
SV = Selected Value (Programmed Value Customer Entered)
NPN Pulse is a Transistor
6.2 Programming NPN Pulse Control Function
Models TKP | TKM Only
STEPS
Step-1
Home Screen
Press
Step-2
Programming OP2 Output
Pulse Control (Totalizer)
Press
Step-3
Programming OP1 Output
Pulse Option (Flow Rate)
Press
Step-4
Programming Hysteresis
of Output Flow Rate Pulse
Press
Step-5
Programming OP1 Power On Delay
Time For Initial Start UP (Sec)
Press
(HOLD)
3
(HOLD)
3
(HOLD)
3
(HOLD)
3
Flow Meter & Transmitter
OP2OP1
TKP
SET
F
Flow Meter & Transmitter
OP2OP1
TKP
SET
F
Flow Meter & Transmitter
OP2OP1
TKP
SET
F
Flow Meter & Transmitter
OP2OP1
TKP
SET
F
Flow Meter & Transmitter
OP2OP1
TKP
SET
F
CV
SV
LPM
FTM
Power On Flow Meter With 10-30 V DC
0 Flow Totalizer
Program Hysteresis of NPN Output Pulse
Range 0.1-999.99 (GAL) Hysteresis
HYS ± 1.0 GPM (Default)
Hys - Hysteresis is a buff
er around the Programmed Set Point Example
(Example) Liquid Caused by Pump Stopping or Va
Flow Rate
Program Time Delay for NPN Pulse (OP1) on Initial Start Up
Range : 0-9999 (Secs)
Ti
me Delay of Pulse Output (Flow Rate)
T2 = 20 (Secs) (Default) Flow Rate
OPERATIONDISPLAY
Con = n : Manual Reset;
Con = c : time (1=10 Secs) A
uto Reset Using Timer
Con = c : time (secs) Auto Reset Using Timer i.e 5 =Pulse On (5 secs)
Con = r : Auto Reset when Total Volume Value = Selct Value (SV)
Con = E : Pulse Output of Unit volume (Default) = One Gal/Pulse
Con = F Paddle Pulse Frequency Max 5 KHZ
Con = E (Default)
CV > SV Pulse (NPN) ON
CV < SV - HYS Pulse (NPN) OFF
CV > SV Pulse (NPN) ON
CV > SV + HYS Pulse (NPN) OFF
ALT
0 (Default) Most Common
CV = C urrent Value
SV = P rogrammed Value
Hys = See below
Programming Relay Setpoint ON - OFF Options
Select - ALt.0, ALt.1, ALt.2, ALt.3,
Alarm
F
GPM
Alarm
F
ALt.0 (Default)
See Next Page for Relay A
larm Options-
Programming Initial Start-Up Relay Time Delay
Range : 0-99 sec Delay Time to Power on Alarm Output Relay
t.20 (Default) (20 Seconds)
Initial Start up of Flow Meter or Process (Allows for System
Steady State before Relay Switch becomes A
6.6 Programming TKS Model Only
Program Relay Set Point and Relay Delay (Prevents Relay Chatter)
STEPS
Step-1
Home Screen
Press
Step-2
Programming Relay
Set Point
Press
Step-3
Programming Relay
Hysteresis
Press
(HOLD)
3
TKS
TKS
TKS
Flow Meter
SET
Flow Meter
SET
Flow Meter
SET
GPM
Power On Flow Meter - 24VDC
Alarm
F
GPM
Home Screen 000.0 (Defaut)
Programming Relay Set Point. (When Relay Switches)
Range : 0.1 - 999.9 GPM
Alarm
F
GPM
100.0 GPM (Defaut)
Relay will Activate when this Set Point or (Flow Rate) is Reached
Program Relay Hysteresis - Prevents Relay Chatter - Due to Constant Flow Rate Change
around Setpoint in Dynamic Flow Process (Cushion ±) Prevents Relay
Alarm
F
d = Delay 0.10 GPM
d.0.10 (Defaut)
6.7 Relay ON - OFF Options For TKS Series Only
DESCRIPTIONALT NO.
ALt = 0
ALt = 1
CV > SV Relay ON : CV < SV - d Relay OFF
CV < SV Relay ON : CV > SV + d Relay OFF
OPERATIONDISPLAY
24V DC POWER ONLY
In the Programming Stage, the Display will Flash
(Not for TKP | TKM Series)
ALt = 2
ALt = 3
CV = Current Display Value = Flow Rate
SV + d > CV > SV - d Relay ON: CV > SV + d or CV < SV - d Relay OFF
SV + d > CV > SV - d Relay OFF: CV > SV + d or CV < SV - d Relay ON
SV = Selected Value = Programmed Value
d = (GPM) Hysteresis Measured around Relay Set Point (± Measured in Gallons)
6.8 General Terms
1) K : Coefficient of Flow Volume,Note : Factory Set Do Not Change
2) tr : TKM Range of Transmitter - Flow Rate 4-20 mA (4mA = 0) (20mA = Max Range)
TKP - RS 485 Option
3) NPN :
4) Con :
Transistor Relay - No Moving Parts
Output Control of Flow Total OP2,
Con = n Manual Reset,
Con = c Time Reset (1=10 Secs) Auto Reset,
Con = r Auto Reset, Based on Volume (GPM)
Con = E Pulse Output of Unit Volume,
Con = F Pulse Output of Paddle = 5 KHZ Max
Black Wire is a Unit Volume NPN Pulse Output-1 Pulse for every Gallon
TKP - Yellow & Grey wires with RS - 485 Option Only
Current output (4 - 20mA) : 120 max.
Voltage output (0 - 5V) : 10K min.
TKM Series (0-5VDC) Optional 4-20mA is Standard
Please make sure the pipe is filled with the fluid under normal operation.
TK Series can be installed in a horizontal or vertical direction.
Please ensure enough length of straight pipe to avoid turbulence that can effect readings.
Note: Min 10x Pipe Diameters Upstream 3x Pipe Diameters Downstream.
A Plastic Basket Strainer, Bag Filter or Y Strainer Filtering Device upstream to Avoid the Paddle Wheel from being damaged by the solids
or fibers - max 10% Particle Size - Not to Exceed .5mm Cross Section or Length.
Please do not flush the pipe after the Flow Meter is installed with Compressed Air this may damage the ceramic shaft and will Void Warranty
11. Warranty, Returns and Limitations
Warranty
Icon Process Controls Ltd warrants to the original purchaser of its products that such products will be free from defects in material and
workmanship under normal use and service in accordance with instructions furnished by Icon Process Controls Ltd for a period of one
years from the date of sale of such products. I
to the repair or replacement, at Icon Process Controls Ltd option, of the products or components, which Icon Process Controls Ltd
examination determin
Ltd must be notified pursuant to the instructions below of any claim under this warranty within thirty (30) days of any claimed lack of
conformity of the product. Any product repaired under this warranty will be warranted only for the remainder of the original warranty
period. Any product provided as a replacement under this warranty will be warranted for the one year from the date of replacement.
es to its satisfaction to be defective in material or workmanship within the warranty period. Icon Process Controls
con Process Controls Ltd obligation under this warranty is solely and exclusively limited
Limitations
This warranty does not apply to products which: 1) are beyond the warranty period or are products for which the original purchaser does
not follow the warranty procedures outlined above; 2) have been subjected to electrical, mechanical or chemical damage due to
improper, accidental or negligent use; 3) have been modified or altered; 4) anyone other than service personnel authorized by Icon Process Controls Ltd have attempted to repair; 5) have been involved in accidents or natural disasters; or 6) are damaged during return
shipment to Icon Process Controls Ltd reserves the right to unilaterally waive this warranty and dispose of any product returned to Icon Process Controls Ltd where: 1) there is evidence of a potentially hazardous material present with the product; or 2) the product has
remained unclaimed at Icon Process Controls Ltd for more than 30 days after Icon Process Controls Ltd has dutifully requested
disposition. This warranty contains the sole express warranty made by Icon Process Controls Ltd in connection with its products. ALL
IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, ARE EXPRESSLY DISCLAIMED. The remedies of repair or replacement as stated above are the exclusive remedies for the breach of this warranty. IN NO EVENT SHALL Icon Process Controls Ltd BE LIABLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING PERSONAL OR REAL PROPERTY OR FOR INJURY TO ANY PERSON.
THIS WARRANTY CONSTITUTES THE FINAL, COMPLETE AND EXCLUSIVE STATEMENT OF WARRANTY TERMS AND NO
PERSON IS AUT HOR IZED T O MAKE ANY OTHER WARRAN TIES OR REPRESE
Controls Ltd. This warranty will be interpreted pursuant to the laws of the province of Ontario, Canada.
If any portion of this warranty is held to be invalid or unenforceable for any reason, such finding will not invalidate any other provision of
this warranty.