Leuze electronic RotoScan, RotoScan ROD4-36, RotoScan ROD4-38, RotoScan ROD4-30 Technical Description

Page 1
rotoScan ROD4-30 / ROD4-36 / ROD4-38
Area Scanning Distance Sensor
DE/GB 00-09/08 50110396
TECHNICAL DESCRIPTION
Page 2
Nortécnica S. R. L. T
Fax Int.
+ 54 1147 57-1088
Tel. Int. + 43 732 76460 Fax Int. + 43 732 785036
Balluff-Leuze Pty. Ltd. Tel. Int. + 61 3 9720 4100 Fax Int. + 61 3 9738 2677
Leuze electronic nv/ sa Tel. Int. + 32 2253 16-00 Fax Int. + 32 2253 15-36
ATICS Tel. Int. + 359 2 847 6244 Fax Int. + 359 2 847 6244
Leuze electronic Ltda. Tel. Int. + 55 11 5180-6130 Fax Int. + 55 11 5181-3597
Leuze electronic AG Tel. Int. + 41 44 834 02-04 Fax Int. + 41 44 833 26-26
Imp. Tec. Vignola S.A.I.C. Tel. Int. + 56 3235 11-11 Fax Int. + 56 3235 11-28
Leuze electronic Trading (Shenzhen) Co. Ltd. Tel. Int. + 86 755 862 64909 Fax Int. + 86 755 862 64901
Componentes Electronicas Ltda. Tel. Int. + 57 4 3511049 Fax Int. + 57 4 3511019
Schmachtl CZ s.r.o. Tel. Int. + 420 244 0015-00 Fax Int. + 420 244 9107-00
Desim Elektronik APS Tel. Int. + 45 7022 00-66 Fax Int. + 45 7022 22-20
SKS-automaatio Oy Tel. Int. + 358 20 764-61 Fax Int. + 358 20 764-6820
Leuze electronic sarl. Tel. Int. + 33 160 0512-20 Fax Int. + 33 160 0503-65
Leuze Mayser electronic Ltd. Tel. Int. + 44 14 8040 85-00 Fax Int. + 44 14 8040 38-08
UTECO A.B.E.E. Tel. Int. + 30 211 1206 900 Fax Int. + 30 211 1206 999
Sensortech Company Tel. Int. + 852 26510188 Fax Int. + 852 26510388
Leuze electronic OOO Tel. Int. + 7 495 933
75
05
Fax Int. + 7 495 933
75
05
Leuze electronic AB Tel. + 46 8 7315190 Fax + 46 8 7315105
Ingermark (M) SDN.BHD Tel. Int. + 60 360 3427-88 Fax Int. + 60 360 3421-88
Leuze Lumiflex México, S.A. de C.V. Tel. Int. + 52 8183 7186-16 Fax Int. + 52 8183 7185-88
Leuze electronic BV Tel. Int. + 31 418 65 35-44 Fax Int. + 31 418 65 38-08
LA2P, Lda. Tel. Int. + 351 214 447070 Fax Int. + 351 214 447075
Balluff Sp. z o. o. Tel. Int. + 48 71 338 49 29 Fax Int. + 48 71 338 49 30
O`BOYLE s.r.l Tel. Int. + 40 2 56201346 Fax Int. + 40 2 56221036
Elteco A/S Tel. Int. + 47 35 56 20-70 Fax Int. + 47 35 56 20-99
Great Cofue Technology Co., Ltd. Tel. Int. + 886 2 29 83 80-77 Fax Int. + 886 2 29 85 33-73
Countapulse Controls (PTY.) Ltd.
07/2008
Tel. Int. + 27 116 1575-56 Fax Int. + 27 116 1575-13
Schmachtl SK s.r.o. Tel. Int. + 421 2 58275600 Fax Int. + 421 2 58275601
Tipteh d.o.o. Tel. Int. + 386 1200 51-50 Fax Int. + 386 1200 51-51
Industrial Electrical Co. Ltd. Tel. Int. + 66 2 6426700 Fax Int. + 66 2 6424249
Leuze electronic San.ve.Tic.Ltd.Sti. Tel. Int. + 90 216 456 6704 Fax Int. + 90 216 456 3650
Balluff Asia pte Ltd Tel. Int. + 65 6252 43-84 Fax Int. + 65 6252 90-60
Leuze electronic, Inc. Tel. Int. + 1 248 486-4466 Fax Int. + 1 248 486-6699
SV Altera OOO Tel. Int. + 38 044 4961888 Fax Int. + 38 044 4961818
C. illies & Co., Ltd. Tel. Int. + 81 3 3443 4143 Fax Int. + 81 3 3443 4118
Profa-Tech Ltd. Tel. Int. + 254 20 828095/6 Fax Int. + 254 20 828129
Leuze electronic Co., Ltd. Tel. Int. + 82 31 3828228 Fax Int. + 82 31 3828522
KazPromAutomatics Ltd. Tel. Int. + 7 7212 50 11 50 Fax Int. + 7 7212 50 11 50
Leuze electronic S.A. Tel. Int. + 34 93 4097900 Fax Int. + 34 93 4903515
Logoprom ODO Tel. Int. + 375 017 235 2641 Fax Int. + 375 017 230 8614
Schmachtl GmbH
SABROW HI-TECH E. & A. LTD. Tel. Int. + 234 80333 86366 Fax Int. + 234 80333 84463518
Tipteh d.o.o. Beograd Tel. Int. + 381 11 3131 057 Fax Int. + 381 11 3018 326
Leuze electronic S.r.l. Tel. Int. + 39 02 26 1106-43 Fax Int. + 39 02 26 1106-40
Kvalix Automatika Kft. Tel. Int. + 36 272 2242 Fax Int. + 36 272 2244
P.T. Yabestindo Mitra Utama Tel. Int. + 62 21 92861859 Fax Int. + 62 21 6451044
Galoz electronics Ltd. Tel. Int. + 972 3 9023456 Fax Int. + 972 3 9021990
Global- Tech (India) Pvt. Ltd. Tel. Int. + 91 20 24470085 Fax Int. + 91 20 24470086
Tavan Ressan Co. Ltd. Tel. Int. + 98 21 2606766 Fax Int. + 98 21 2002883
Tipteh Zagreb d.o.o. Tel. Int. + 385 1 381 6574 Fax Int. + 385 1 381 6577
Tipteh d.o.o. Skopje Tel. Int. + 389 70 399 474 Fax Int. + 389 23 174 197
Leuze electronic GmbH + Co. KG P.O. Box 1111, D- 73277 Owen / Teck Tel. +49(0) 70 21/ 573-0, Fax +49(0 )7021 / 573-199 info@leuze.de • www.leuze.com
Sales Region East
Phone 035027/629-106 Fax 035027/629-107
Postal code areas 01000-19999 39000-39999 98000-99999
Sales Region North
Phone 07021/573-306 Fax 07021/9850950
Postal code areas 20000-38999 40000-65999 97000-97999
Sales Region South
Phone 07021/573-307 Fax 07021/9850911
Postal code areas 66000-96999
Sales and Service
Worldwide
AT (Austria)
AR (Argentina)
AU + NZ (Australia + New Zealand)
BE (Belgium)
BG (Republic of Bulgaria)
BR (Brasil)
CH (Switzerland)
CO (Colombia)
CZ (Czech Republic)
CL (Chile)
CN (People’s Republic of China)
DK (Denmark)
FI (Finland)
GB (United Kingdom)
GR (Greece)
HK (Hong Kong)
IT (Italy)
HU (Hungary)
ID (Indonesia)
IL (Israel)
IN (India)
IR (Iran)
FR (France)
RU (Russian Federation)
SE (Sweden)
MY (Malaysia)
MX (Mexico)
NL (Netherlands)
PT (Portugal)
PL (Poland)
RO (Romania)
NO (Norway)
TW (Taiwan)
ZA (South Africa)
SK (Slowakia)
SI (Slovenia)
TH (Thailand)
TR (Turkey)
SG + PH (Singapore + Philippines)
US + CA (United States + Canada)
UA (Ukraine)
JP (Japan)
KR (South Korea)
KZ (Republic of Kazakhstan)
ES (Spain)
BY (Republic of Belarus)
Germany
KE (Kenia)
NG (Nigeria)
RS (Republic of Serbia)
HR (Croatia)
MK (Macedonia)
© All rights reserved, especially the right of reproduction, distribution and translation. Copying or
reproductions in any form require the written consent of the manufacturer. Changes due to technical improvement may be made.
Page 3
Leuze electronic rotoScan ROD4-3… 1
Table of contents
1 General information........................................................................................................... 4
1.1 Explanation of symbols ........................................................................................................ 4
1.2 Declaration of conformity .....................................................................................................4
2 Safety notices..................................................................................................................... 5
2.1 Safety standards .................................................................................................................. 5
2.2 Application conditions and intended use.............................................................................. 6
2.3 Restrictions with regards to use........................................................................................... 7
2.4 Working safely ..................................................................................................................... 8
2.5 Organisational measures ..................................................................................................... 9
3 Description .......................................................................................................................10
3.1 Technical overview ............................................................................................................ 10
3.2 Operating principle............................................................................................................. 11
3.3 Special features of the ROD4-3… ..................................................................................... 12
3.4 Detection fields / detection field pairs ................................................................................ 12
3.4.1 Changing over between detection field pairs............................................................................... 12
3.4.2 4-field mode ................................................................................................................................. 15
3.5 Application examples .........................................................................................................16
3.5.1 Object detection........................................................................................................................... 16
3.5.2 Object measurement: .................................................................................................................. 18
4 Mounting........................................................................................................................... 19
5 Electrical connection....................................................................................................... 20
5.1 Connecting the rotoScan ROD4-3….................................................................................. 20
5.1.1 Pin assignments X1 and X2......................................................................................................... 21
5.1.2 Connector assignments for connection X1 .................................................................................. 22
5.1.3 Connector assignments for connection X2 (RS 232)................................................................... 24
5.1.4 Connector assignments for connection X2 (RS 422)................................................................... 24
5.2 Functions of connection X1................................................................................................ 25
5.2.1 Input circuit .................................................................................................................................. 25
5.2.2 Output circuit................................................................................................................................ 27
5.2.3 RESTART / resetting the data transmission rate to 57600 baud................................................. 28
5.3 Functions of connection X2................................................................................................ 29
5.4 Connection......................................................................................................................... 29
5.4.1 Electrical supply........................................................................................................................... 29
5.4.2 Fabricating the cable on the sensor side ..................................................................................... 29
5.4.3 Structure of the connector ...........................................................................................................30
5.4.4 Points to be observed when fabricating and laying the cable...................................................... 31
5.5 Integration in the control system ........................................................................................ 32
5.5.1 Connection example 1: without detection field pair switch ..........................................................32
5.5.2 Connection example 2: with detection field pair switch ...............................................................33
Page 4
2 rotoScan ROD4-3… Leuze electronic
Table of contents
6 Commissioning ................................................................................................................ 34
6.1 Hardware and software requirements................................................................................ 34
6.2 Device configuration .......................................................................................................... 34
6.3 Device configuration with ext. configuration memory / device exchange........................... 36
6.4 Screwing down and aligning the device............................................................................. 37
6.5 Switching on the device .....................................................................................................37
7 Testing and maintenance................................................................................................ 38
7.1 Testing ...............................................................................................................................38
7.2 Cleaning............................................................................................................................. 38
8 Delivery contents and accessories ................................................................................ 39
8.1 Scope of delivery ............................................................................................................... 39
8.2 Accessories........................................................................................................................ 39
8.2.1 Pin assignment for connection cables KB-ROD4-5000 and KB-ROD4-10000 ............................40
8.2.2 BT ROD4 mounting system..........................................................................................................41
9 Technical data .................................................................................................................. 42
9.1 Detection field data ............................................................................................................42
9.2 Electrical data .................................................................................................................... 43
9.3 Software............................................................................................................................. 43
9.4 Optical data........................................................................................................................ 44
9.5 Environmental data ............................................................................................................ 46
9.6 Dimensioned drawing ROD4-3…....................................................................................... 47
10 Status messages, errors and error rectification ........................................................... 48
10.1 LED indicators.................................................................................................................... 48
10.2 Status displays................................................................................................................... 50
10.3 Diagnostic codes and causes ............................................................................................51
11 Appendix........................................................................................................................... 56
11.1 Terms and abbreviations used with ROD4-3… and the RODsoft software ....................... 56
Page 5
Leuze electronic rotoScan ROD4-3… 3
Figures and tables
Table 2.1: Standards and directives..............................................................................................5
Figure 2.1: Attachment of the stick-on label with warning notices.................................................. 8
Table 3.1: Device types............................................................................................................... 10
Figure 3.1: Measurement ranges and detection fields ................................................................. 10
Figure 3.2: Working range and angular resolution .......................................................................11
Figure 3.3: Operating principle .....................................................................................................11
Figure 3.4: Configuring detection field pairs 1 through 4 only ......................................................13
Table 3.2: Changeover of the detection field pairs via the control inputs.................................... 13
Figure 3.5: Also configuring detection field pairs 5 through 8....................................................... 14
Table 3.3: Changeover of the detection field pairs via the control inputs.................................... 14
Table 3.4: Assignment of detection field to switching output in 4-field mode .............................. 15
Figure 3.6: Application example - height/position detection .........................................................16
Figure 3.7: Application example - Protusion detection in high-bay warehouses ..........................16
Figure 3.8: Application example - automatic parking system .......................................................17
Figure 3.9: Application example - 4-field mode ............................................................................17
Figure 3.10: Application example - measurement of pallets........................................................... 18
Figure 3.11: Application example - gripping system....................................................................... 18
Figure 5.1: Connecting the rotoScan ROD4-3… .......................................................................... 20
Table 5.1: Connections of the ROD4-3… – X1 and X2............................................................... 21
Table 5.2: SUB-D 15-pin – pin assignments for connection X1 ..................................................22
Table 5.3: SUB-D 9-pin – pin assignments for connection X2 as RS 232 port ...........................24
Table 5.4: SUB-D 9-pin – pin assignments for connection X2 as RS 422 port ...........................24
Figure 5.2: Inputs of interface X1 .................................................................................................25
Figure 5.3: Example: Detection field pair switch for a DTS application ........................................ 26
Figure 5.4: Outputs of interface X1............................................................................................... 27
Figure 5.5: Plug wiring.................................................................................................................. 30
Figure 5.6: Connection example without detection field pair switch ............................................. 32
Figure 5.7: Connection example with detection field pair switch .................................................. 33
Figure 6.1: User interface of the configuration software............................................................... 35
Figure 6.2: Switch in the config. connector................................................................................... 36
Figure 6.3: LEDs........................................................................................................................... 37
Figure 8.1: Dimensioned drawing BT ROD4…............................................................................. 41
Table 9.1: Technical data - detection fields................................................................................. 42
Table 9.2: Technical data - electrical data................................................................................... 43
Table 9.3: Technical data - software ...........................................................................................43
Table 9.4: Technical data - optical data ......................................................................................44
Figure 9.1: Object size/diffuse reflection as a function of distance for the ROD4-30/ROD4-36 ... 44
Figure 9.2: Typical beam dimensions for the ROD4-3….............................................................. 45
Table 9.5: Technical data - environmental data ..........................................................................46
Figure 9.3: Dimensioned drawing ROD4-3… ............................................................................... 47
Figure 10.1: ROD4-3… LED indicators ..........................................................................................48
Table 10.1: Status displays on the rotoScan ROD4-3................................................................... 50
Table 10.2: ROD4-3… – diagnostic codes, causes and measures............................................... 51
Figure 11.1: Components of the object speed................................................................................ 59
Page 6
General information
4 rotoScan ROD4-3... Leuze electronic

1 General information

1.1 Explanation of symbols

The symbols used in this technical description are explained below.
Attention!
This symbol appears before text passages which must absolutely be observed. Failure to heed this information may lead to injuries to personnel or damage to the equipment.
Attention Laser!
This symbol warns of possible danger through hazardous laser radiation. The laser used in the rotoScan ROD4-3… is an infrared laser device of laser class 1 acc. to DIN EN 60825-1. Observe the legal and local regulations applicable to the operation of laser units.
Notice!
This symbol indicates text passages containing important information.

1.2 Declaration of conformity

The rotoScan ROD4-30, rotoScan ROD4-36 and rotoScan ROD4-38 distance sensors have been developed and produced in accordance with the applicable European standards and directives.
The rotoScan ROD4-3… distance sensors also fulfil the UL requirements (Underwriters Laboratory Inc.) for the USA and Canada.
Notice!
The corresponding declaration of conformity can be requested from the manufacturer.
The manufacturer of the product, Leuze electronic GmbH + Co. KG in D-73277 Owen/Teck, possesses a certified quality assurance system in accordance with ISO 9001.
U
L
US
C
LISTED
Page 7
Safety notices
Leuze electronic rotoScan ROD4-3... 5
TNT 35/7-24V

2 Safety notices

2.1 Safety standards

The rotoScan ROD4-30/rotoScan ROD4-36/rotoScan ROD4-38 distance sensor (abbrevi­ated as ROD4-3… in the following) has been developed, produced and tested subject to the applicable safety standards. It represents the state of the art.

Standards and directives

The standards and directives which apply in Europe and which are to be observed during the use and installation of the rotoScan ROD4-3… are listed below:
Table 2.1: Standards and directives

Laser

If the functionality is not ensured, the error output is immediately activated. The laser output power and the rotational speed of the mirror are continuously monitored by the built-in control system to ensure that the requirements of laser class I are satisfied.

Reference measurement

A reference measurement cyclically controls the measurement function. The following func­tions are checked on each rotation of the mirror by means of a test object located inside of the device:
• optical systems (e.g. transmitter and receiver)
• hardware, software, etc.

Window monitoring

A total of six light axes monitor the degree of soiling of the window. During this procedure, the results are compared with two reference sensors. Moreover, these reference sensors are used for temperature compensation and ageing monitoring.

Software test

The system is tested when first switched on and during operation.
Standard or EC directive Designation
98/37/EC
1)
1) Beginning December 29, 2009, the new edition of machine directive 2006/42/EC is to be applied.
Machine directive
2006/95/EU, Low voltage directive
2004/108/EU EMC - directive
Page 8
Safety notices
6 rotoScan ROD4-3... Leuze electronic

2.2 Application conditions and intended use

Attention!
The protection of personnel and the device cannot be guaranteed if the device is operated in a manner not corresponding to its intended use.
The relevant regulations for machine safety apply to the use of the ROD4-3… The respon­sible authorities (e.g. the employer's liability insurance association, OSHA) are available for questions related to issues of safety. In general, the following application conditions are to be maintained:
• If a protective housing is provided for the sensor, the detection must not occur through additional window material (plastic, glass, etc.).
• Physical contact with the front cover of the sensor and the six diffused-light windows is to be avoided.
• The electrical integration of the ROD4-3… in the control must only be performed by electricians.
• The ROD4-3-… is designed in accordance with safety class III for supply by PELV (protective extra-low voltage with reliable disconnection). For UL applications: only for use in class 2 circuits according to NEC.
• The 24VDC power supply must be fed into the sensor via a separate branch by means of a 2.5A fuse (without heating) or a 4A fuse (with heating), semi time-lag, installed in the switch cabinet.
• Operation is permitted only with screwed-on control cable (X1) and PC cable (X2) or dummy connector (X2). This also applies for transport and storage.
• Alarm output 1 (pin 5 at X1) must not be used to switch safety-relevant signals.
• The system (sensor, machine, control and switching components) must only be tested if no persons are placed at risk by the test.
• Access to or changes on the ROD4-3… could result in the loss of proper device func­tion.
• Commissioning, maintenance, parameter settings and detection-field configurations are only to be performed by trained personnel. Knowledge of the safety notices in these connection and operating instructions and the operating manual for the RODsoft program is a part of the required skills.
• If the start disable/manual restart is provided, a test of all detection fields should be performed prior to release - there must not be any objects in the detection fields.
Page 9
Safety notices
Leuze electronic rotoScan ROD4-3... 7
TNT 35/7-24V

2.3 Restrictions with regards to use

• Glass, highly reflective materials such as mirrors (luminosity coefficient > 10,000%) as well as objects which do not reflect any light back to the sensor could falsify the measurement value. Additional notices can be found in chapter 9.4.
• Do not expose the ROD4-3… to flying sparks (e.g. welding sparks); the front cover, among other parts of the system, will be damaged.
• Vapours, smoke, dust and all particles visible in the air could affect the measurement values and cause the semiconductor outputs to switch off.
• Avoid large temperature fluctuations.
Page 10
Safety notices
8 rotoScan ROD4-3... Leuze electronic

2.4 Working safely

Attention: Invisible laser radiation!
The ROD4-3… distance sensor operates with an invisible infrared laser of class 1 acc. to EN 60825-1.
The maximum output power of the laser is 15W at a pulse duration of 3 ns. The aver­age laser power is less than 0.39mW in accordance with laser class 1 acc. to EN 60825-1.
The ROD4-3… complies with US rules 21 CFR 1040.10 except for deviations pursuant to Laser Notice No. 50, dated July 2001.
The use of operating and adjusting devices other than those specified in this techni­cal description, carrying out of differing procedures, or improper use of the distance sensor may lead to dangerous exposure to radiation!
The use of optical instruments or devices in combination with the device can increase the danger of eye damage!
Adhere to the applicable legal and local regulations regarding protection from laser beams acc. to EN 60825-1 in its latest version. Avoid mounting the distance sensor at eye level.
The front cover is the only opening through which the laser radiation can escape from the device. The housing of the ROD4-3… distance sensor is sealed and has no parts that need to be adjusted or maintained by the user. The device must not be tampered with and must not be changed in any way!
Figure 2.1: Attachment of the stick-on label with warning notices
Attention!
Access and changes to the device
, except where expressly described in this operating man-
ual, are not authorised.
Page 11
Safety notices
Leuze electronic rotoScan ROD4-3... 9
TNT 35/7-24V

2.5 Organisational measures

Documentation

All entries in this technical description must be observed, in particular those in chapter 2. Keep this technical description in a safe place. It should be accessible at all times.

Safety regulations

Observe the locally applicable legal regulations and the rules of the employer's liability insur­ance association.

Qualified personnel

Mounting, commissioning and maintenance of the device may only be carried out by quali­fied personnel. Electrical work must be carried out by a certified electrician.
Attention!
Adjustment and change of the detection fields by means of the RODSoft configuration soft­ware may only be carried out by an authorised person. The password required is to be stored under lock and key by the designated person.

Repair

Repairs must only be carried out by the manufacturer or an authorised representative.
Page 12
Description
10 rotoScan ROD4-3... Leuze electronic

3 Description

3.1 Technical overview

Table 3.1: Device types
The ROD4-3… is an optical, two-dimensional measuring distance sensor. It could also be referred to as an optical, area radar unit. The device periodically transmits light pulses within an angular range of 190° via a rotating deflector unit.
If the pulses are incident upon objects or obstacles, the light is reflected and then received and analysed by the ROD4-3…. From the propagation time of the radiated light and the current angle of the deflector unit, the ROD4-3… unit calculates the exact coordinates of the object. If the object or obstacle is located within defined detection fields, a stop function is executed. In this case, the semiconductor switch outputs are switched off within the system reaction time. The stop function is automatically reset once the detection field is clear or upon acknowledgement, depending on the operating mode (software configuration: manual/ automatic).
The ROD4-3… can detect objects with diameters greater than 20mm at a distance of up to
4.0m, even if the surface of the given object is dark. Larger objects are detected in the far detection field at a distance of up to 50m.
Eight reversible detection field pairs (7 configurable + 1 permanently defined) enable optimal adaptation to the applications.
Figure 3.1: Measurement ranges and detection fields
The ROD4-3… can be used both on vehicles (mobile object detection for vehicles) as well as in stationary applications on systems and machines (object detection/measurement). The long-range and contact-less measurement principle makes the ROD4-3… unit a universally applicable monitoring device.
Designation Typ e Part No.
rotoScan ROD4-30 without heater 501 10238
rotoScan ROD4-36 with integrated heater 501 10666
rotoScan ROD4-38
with integrated heating, dust-insensitive version
501 10667
Measurement range ROD4-38: max. 25m
Measurement range ROD4-30/ROD4-36: max. 65m
Radius of near detection field: max. 30m
Radius of far detection field: max. 50m
Page 13
Description
Leuze electronic rotoScan ROD4-3... 11
TNT 35/7-24V

3.2 Operating principle

The working range of the ROD4-3… (190°) is divided into 0.36 ° angular segments (corre­sponds to 529 measurement values).
Figure 3.2: Working range and angular resolution
Bundled light pulses are generated by a laser diode with coupled transmission optics. These light pulses are reflected by a rotating mirror in such a way that a light pulse is emitted every 40ms in all angular segments (scanning rate: 25 scans/s). If the light pulse is incident upon an object, it is reflected and subsequently detected and analysed by the ROD4-3….
Figure 3.3: Operating principle
The ROD4-3… works on the principle of pulse propagation time measurement. The light pulse propagation time is a direct measurement of the distance to the object.

Combination of hardware and software

You can configure the ROD4-3… yourself using the supplied RODsoft software. In addition to the device configuration, the software can also be used to adapt the field pairs to the given application and to save them in the ROD4-3…
The image of the surroundings generated during the scan process is compared with the specified detection field contours. If an object violates a detection field for a least one scan (40ms), a corresponding, user-specific reaction is triggered.
0.36°
Working range
Page 14
Description
12 rotoScan ROD4-3... Leuze electronic

3.3 Special features of the ROD4-3…

• Seven freely configurable near detection fields (up to maximum 30m)
• Seven freely configurable far detection fields (up to maximum 50m)
• Monitoring range up to 190°
• Small construction size (W x D x H: 140mm x 135mm x 155mm)
• Low weight (2kg)
• Low current consumption (ROD4-30 without heating)
• Two interface types on the X2 SUB-D socket (RS 232 and RS 422)
• Easy-to-use RODsoft configuration software
• Measurement value transmission from distances of up to 65m
• Device plug with configuration memory facilitates simple exchange of devices

3.4 Detection fields / detection field pairs

Eight reversible detection field pairs (7 configurable + 1 permanently defined) enable optimal adaptation to the applications. A detection field pair is considered to be the combination of both a near and far detection field. The following designations are used in the RODsoft configuration software:
Detection field pair x consists of detection_field_near x and detection_field_far x.
The near and far detection fields are represented by different colours in the RODsoft config­uration software: near = red, far = green.
Detection field pairs 1 … 7 can be freely defined by the user. Detection field pair 8 is perma­nently defined: both detection_field_near 8 as well as detection_field_far 8 are set to zero here. This means that no area monitoring takes place upon activation of detection field pair 8.

3.4.1 Changing over between detection field pairs

Attention! 1 or 2 detection field pairs may be simultaneously active and simultaneously moni-
tored!
Only detection field pairs 1 through 4 are configured
If only detection field pairs 1 through 4 are configured in the RODsoft configuration software, i.e. it is only possible to start with a field pair between 1 and 4 and it is only possible to changeover between a field pair between 1 and 4, then a maximum of 2 detection field pairs may be simultaneously active and monitored.
Page 15
Description
Leuze electronic rotoScan ROD4-3... 13
TNT 35/7-24V
Figure 3.4: Configuring detection field pairs 1 through 4 only
The four control inputs FPS1 … FPS4 can be used to change over between the detection field pairs. The following table shows the admissible control options.
Table 3.2: Changeover of the detection field pairs via the control inputs
If an inadmissible state exists at the control inputs for more than 80ms, the sensor switches to the error state.
Control input
Meaning
FPS1 FPS2 FPS3 FPS4
0000 Detection field pair 1 is active 1000 Detection field pair 1 is active 0
100 Detection field pair 2 is active 1 100 Detection field pairs 1 and 2 are active 00
10 Detection field pair 3 is active 1010 Detection field pairs 1 and 3 are active 0
1 10 Detection field pairs 2 and 3 are active 1 1 1 0 Not permitted 000
1 Detection field pair 4 is active 1001 Detection field pairs 1 and 4 are active 0 101 Detection field pairs 2 and 4 are active 1 101 Not permitted 001 1 Detection field pairs 3 and 4 are active 101 1 Not permitted 0 1 1 1 Not permitted 1 1 1 1 Not permitted
Page 16
Description
14 rotoScan ROD4-3... Leuze electronic
One of detection field pairs 5 through 8 is also configured
If, in addition detection field pairs 1 through 4, at least one of detection field pairs 5 through 8 is also configured in the RODsoft configuration software, i.e. it is possible to start with a field pair between 1 and 7 and it is possible to changeover between a field pair between 1 and 8, then only 1 detection field pair may be simultaneously active and monitored.
Figure 3.5: Also configuring detection field pairs 5 through 8
In this case, the four control inputs can be used to change over between the detection field pairs as follows.
Table 3.3: Changeover of the detection field pairs via the control inputs
Control input
Meaning
FPS1 FPS2 FPS3 FPS4
0000 Detection field pair 1 is active 1000 Detection field pair 1 is active 0
100 Detection field pair 2 is active 0010 Detection field pair 3 is active 0001 Detection field pair 4 is active 1 1 10 Detection field pair 5 is active 1 101 Detection field pair 6 is active 101 1 Detection field pair 7 is active 0 1 1 1 Detection field pair 8 is active 1 1 0 0 Not permitted 1 0 1 0 Not permitted 0 1 1 0 Not permitted 1 0 0 1 Not permitted 0 1 0 1 Not permitted 0 0 1 1 Not permitted 1 1 1 1 Not permitted
Page 17
Description
Leuze electronic rotoScan ROD4-3... 15
TNT 35/7-24V
While changing over between 2 detection field pairs, inadmissible states at the control inputs are tolerated for a duration of 40ms; after this period the sensor switches to the error state. The changeover between 2 detection field pairs occurs within a system reaction time of 80ms.

3.4.2 4-field mode

In 4-field mode (configuration via RODsoft), all 4 detection fields of detection field pairs 1 and 2 are simultaneously activated and evaluated. In this case, a separate output is assigned to each detection field pair.
Table 3.4: Assignment of detection field to switching output in 4-field mode
Inputs FPS1 … FPS4 are not evaluated in 4-field mode. Detection field changeover is not possible in 4-field mode.
Attention!
Depending on the configuration, output ALARM1, in some cases, also signals device warn­ings. This means that a violation of detection_field_far 1 is not uniquely signalled under cer­tain circumstances. All outputs are switched off during start-up. Outputs ALARM1 and ALARM2 are activated during configuration.
Notice! Operation with 3 detection fields
If only three detection fields are to act on three outputs, only use detection_field_near 1, detection_field_near 2 and detection_field_far 2 and set the alarm signal type for ALARM1 to "Device warning". The output will then only signal device warnings and is, as a result, unique.
Operation with 2 detection fields
If only two or fewer independent outputs are needed, 4-field mode is not required and should be deactivated with the appropriate RODsoft parameter.
Detection field
Switching output
Fn1 Fn2 ALARM1 ALARM2
Detection_field_near 1
X
Detection_field_near 2 X
Detection_field_far 1
(X)
Detection_field_far 2
X
Page 18
Description
16 rotoScan ROD4-3... Leuze electronic

3.5 Application examples

The following examples can be considered typical areas of application for the ROD4-3….

3.5.1 Object detection

Height/position detection
Height and position detection of objects for collision prevention.
Figure 3.6: Application example - height/position detection
Protusion detection in high-bay warehouses
Overshoot detection for collision prevention with high-bay storage devices.
Figure 3.7: Application example - Protusion detection in high-bay warehouses
Page 19
Description
Leuze electronic rotoScan ROD4-3... 17
TNT 35/7-24V
Automatic parking system
Protrusion detection in parking systems under changing environmental conditions.
Figure 3.8: Application example - automatic parking system
4-field mode
Presence detection on the transport system with 4 independent detection fields.
Figure 3.9: Application example - 4-field mode
Page 20
Description
18 rotoScan ROD4-3... Leuze electronic

3.5.2 Object measurement:

Measurement of pallets
Contour measurement, determination of X, Y coordinates.
Figure 3.10: Application example - measurement of pallets
Manipulator positioning
Compact construction and low weight enable use on gripping head.
Figure 3.11: Application example - gripping system
Other applications
• Buffing protection (e.g. for telpher lines)
• Overshoot detection (e.g. in fully automatic parking systems)
• Detection / counting of persons
• Room security / façade monitoring
• Access control
• Contour measurement
• Packet measurement / volume measurement
•etc.
Page 21
Mounting
Leuze electronic rotoScan ROD4-3... 19
TNT 35/7-24V

4 Mounting

The ROD4-3… should be mounted so that the area which is to be monitored is covered by the corresponding detection field.
Attention!
Because of the optical scanning principle, only objects with good reflective properties are detected directly in front of the sensor window.
Physical damage to the sensor (e.g. due to collision or climbing on) should be prevented by using a protective enclosure. If using an enclosure, the entire front cover of the device must, however, remain unobstructed.
In order for the ROD4-3… to function optimally, it must be mounted in a favourable position. You should make every effort to observe the following points:
• Position the ROD4-3… in a protected location.
• The mounting location and the electrical supply should be located as close as possi­ble to one another.
• The ROD4-3… is to be mounted so that the area which is to be monitored is com­pletely covered by the detection field.
• The mounting position of the sensor must offer protection from humidity, soiling, as well as temperatures below 0°C (ROD4-30) or -20°C (ROD4-36, ROD4-38) and above 50°C.
• The mounting location is to be selected such that the possibilities for mechanical damage are minimised. Exposed locations are to be equipped with additional protec­tive guards or loop guards.
• Reinforcements, enclosures, mounting alcoves and other machine elements must not result in an obstruction in the sensor's field of vision.
• Retro-reflectors or very reflective surfaces, such as certain metals or ceramics, are to be avoided near the detection fields and at the height of the scanning plane as these may result in measurement errors.
• To ensure a constant detection height at every point in the detection field, the sensor, and thus the beam plane, is to be mounted parallel to the reference plane.
• If the sensor is used without start disable or start test with automatic start/restart, a start warning (optical/acoustic) is to be provided.
• The sensor must not be used as a climbing aid. If there is a risk of this, a suitable, inclined (45°) protector is to be mounted.
• If two sensors are used, they should be angled slightly with respect to one another or be mounted at different heights.
The device dimensions and the reference of the scanning plane to the device edges can be found in the dimensioned drawing (see figure 9.3 on page 47). Here, the zero point for the distance measurement is the axis of rotation of the rotating mirror (a in figure 9.3). BT ROD4… mounting system see chapter 8.2.2.
Notice!
Under certain circumstances, a larger measurement inaccuracy may occur with strongly re­flective backgrounds (e.g. retro-reflectors, polished metal, etc.).
Page 22
Electrical connection
20 rotoScan ROD4-3... Leuze electronic

5 Electrical connection

5.1 Connecting the rotoScan ROD4-3…

To configure the sensor, connect the control cable (KB-ROD4-…, socket X1) to the power supply and the interface cable (KB-ROD4PC-…, socket X2) to the PC or laptop. Before commissioning the system, please check the pin assignments, the wiring, the supply voltage and the safeguarding. In spite of the sensor's robust housing and fittings, which include various internal safety mechanisms, damages resulting from misconnection cannot be excluded.
Figure 5.1: Connecting the rotoScan ROD4-3…
Attention!
In normal operation, you must permanently connect the two Sub-D connectors to the ROD4-3…. If one of the two connectors is missing, the ROD4-3… no longer has protection class IP 65.
d
a
c
b
S
TO
P
o
k
.
ok.
Leuz
e
electronic
a Connection for configuration only b Dummy connector c Connector X1 (15-pin, SUB-D) d Connector X2 (9-pin, SUB-D)
Page 23
Electrical connection
Leuze electronic rotoScan ROD4-3... 21
TNT 35/7-24V

5.1.1 Pin assignments X1 and X2

Table 5.1: Connections of the ROD4-3… – X1 and X2
Connection Connector Signals
X1 SUB-D 15-pin
• Power supply
• Switching outputs/alarm output
• Inputs for field pair switch
• Restart/reset input
• Configuration connector
X2 SUB-D 9-pin
rotoScan ROD4-3… <–> PC interface
• Parameter configuration
• Detection field definition
• Measurement data transmission
• Diagnostics
Page 24
Electrical connection
22 rotoScan ROD4-3... Leuze electronic

5.1.2 Connector assignments for connection X1

Table 5.2: SUB-D 15-pin – pin assignments for connection X1
PIN Signal Description Wire colour
KB-ROD4-…
1 GND Supply voltage ground black
2 Restart
Safe input "restart-disable", reset the sensor and connection of the restart button
blue
3 UB Supply voltage +24VDC red
4 FPS1 Changeover of detection field pairs orange
5 ALARM1
Output for object detection in the far detection field and for warning mes­sages such as "Window lightly soiled" or "Window heavily soiled" (configura­ble). 4-field mode: Output for object detec­tion in detection_field_far 1
yellow
6 FPS2 Changeover of detection field pairs green
7 FPS3 Changeover of detection field pairs violet
8 FPS4 Changeover of detection field pairs grey
9 NC Do not use!
10 NC Do not use!
11 Fn1
Semiconductor output, shutdown on object detection in the near detection field, channel 1. 4-field mode: Output for object detec­tion in detection_field_near 1
white
12 Fn2
Semiconductor output, shutdown on object detection in the near detection field, channel 2. 4-field mode: Output for object detec­tion in detection_field_near 2
white/black
13 NC Do not use!
14 NC Do not use! white/brown
15 ALARM2
Warning and error output 4-field mode: Output for object detec­tion in detection_field_far 2
brown
8
15
1
2
3
4
5
6
7
14
13
12
11
10
9
Page 25
Electrical connection
Leuze electronic rotoScan ROD4-3... 23
TNT 35/7-24V
Attention!
Any additionally used switching components (e.g. button for restarting) must be permanently mounted.
• Loosely position the button at the intended position.
• Switch on the voltage supply of the ROD4-3… which has been configured for the application.
• Violate the active near detection field, e.g. by entering it. The violation is indicated by the following status display (see also chapter 10.1):
• Now actuate the restart button and observe the left, green LED. If this LED illumi­nates, you are no longer in the near detection field and the location of the button is suitable. If the LED does not illuminate, there are still objects located within the near detection field. In this case, change the location of the button and perform the test again.
Yellow LED with continuous light: restart-disable active
Red LED illuminated: outputs Fn1 and Fn2 disabled
Page 26
Electrical connection
24 rotoScan ROD4-3... Leuze electronic

5.1.3 Connector assignments for connection X2 (RS 232)

Table 5.3: SUB-D 9-pin – pin assignments for connection X2 as RS 232 port

5.1.4 Connector assignments for connection X2 (RS 422)

Notice!
If you would like to work with an RS 422 interface, you must connect PIN 6 with PIN 5 (GND) by means of a bridge.
Table 5.4: SUB-D 9-pin – pin assignments for connection X2 as RS 422 port
PIN Signal Description
1 NC Do not use!
2 TxD Data communication, transmission
3 RxD Data communication, reception
4 NC Do not use!
5 GND/shield
Ground/shielding (to be connected only on the cabinet side with PE)
6 RS 232
Selection RS 232/RS 422, selection as RS 232 interface: do not use!
7 NC Do not use!
8 NC Do not use!
9 Reserved Reserved for test purposes, not wired
1
6
4
3
2
7
8
9
5
PIN Signal Description
1 TxD+
RS 422 transmitted data
2 TxD-
3 RxD-
RS 422 received data
4 RxD+
5 GND/shield
Ground/shielding (to be connected only on the cabinet side with PE)
6 RS 422
Selection RS 232/RS 422, selection as RS 422 interface: bridge to PIN 5!
7 NC Do not use!
8 NC Do not use!
9 Reserved Reserved for test purposes, not wired
6
3
2
7
8
9
5
1
4
Connection PIN 5 to PIN 6
Page 27
Electrical connection
Leuze electronic rotoScan ROD4-3... 25
TNT 35/7-24V

5.2 Functions of connection X1

5.2.1 Input circuit

There are two Sub-D connections on the top of the device. At connection X1 with the 15-pin Sub-D connector, a ready-made cable (KB-ROD4-…) or a cable self-made by the customer is attached to the solder connections of the connector (connector set KD-ROD4-X1) by means of soldered connections (see figure 5.5).
Figure 5.2: Inputs of interface X1
Inputs FPS1 … FPS4
With the ROD4-3…, it is possible to work with up to eight detection field pairs. Use inputs X1-4 (FPS1), X1-6 (FPS2), X1-7 (FPS3) and X1-8 (FPS4) to switch between the detection field pairs.
Detection field pairs are activated by applying +24V DC (logic: 1) to the appropriate inputs. If no input is wired, detection field pair 1 is activated.
Notice!
The configuration-dependent changeover of detection field pairs is described in chapter
3.4.1 on page 12.
Attention! If an inadmissible signal combination (e.g. 1-1-1-1) is applied at inputs FPS1 …FPS4, a
warning is output at output ALARM2 and outputs Fn1/Fn2 are switched off. In addition,
an error is transmitted via the serial interface and stored in the error memory.
X1-...
3,3k
1k
0,1uF
X1-3
Page 28
Electrical connection
26 rotoScan ROD4-3... Leuze electronic
The following situation would be possible with a DTS application (see figure 5.3):
The vehicle enters an intersection area while detection field pair 1 (I) is activated (|). To prevent objects from colliding, detection field pair 2 (II) is switched on as well before the curve (A). Both detection fields (I + II) are now active. Detection field pair 1 (I) is switched off. The vehicle travels around the curve with detection field pair 2 (II) active (A). Afterward, detection field pair 1 (I) is switched back on as well (A). Both detection fields (I + II) are active. Detection field pair 2 (II) is switched off. The vehicle continues to travel with detection field pair 1 (I) active (A).
Figure 5.3: Example: Detection field pair switch for a DTS application
Movement path
Direction of movement
I + II
DT
DT
DT
A
|
A
AA
DT
DT
I + II
I II
I
Page 29
Electrical connection
Leuze electronic rotoScan ROD4-3... 27
TNT 35/7-24V

5.2.2 Output circuit

The signal outputs are used to control indicator lamps or relays which indicate the device status. This is switched by a transistor output with open collector set to "active high" (oper­ating voltage).
Figure 5.4: Outputs of interface X1
"Fn1" (X1-11) and "Fn2" (X1-12)
These two semiconductor outputs report violation of the near detection field. X1-11 and X1-12 = "active high" signals that no object is located in the near detection field. The "low" state signals the detection of an object in the near detection field (see chapter 3.4 "Detection fields / detection field pairs").
Attention!
Outputs "Fn1" and "Fn2" are tested alternately. For this purpose, the output signals are re­moved alternately every 20ms for a duration of 100µs. For this reason, the load must dem­onstrate lowpass characteristics, limit frequency f
g
1kHz. The outputs must not be short-circuited. It is not permissible to connect together the outputs of two sensors.
"ALARM1" (X1-5)
This output is configured via the RODsoft configuration software.
X1-5 = "active high" signals that the device is ready for operation. The "low" output state signals one of the following states:
1. Possibility: Object detection in the far detection field.
2. Possibility: Device warning, e.g light window contamination, etc.
3. Possibility: Object detection in the far detection field or device warning, e.g. light win-
dow contamination, etc.
4. Possibility: No signalling.
5. Possibility: Device error, e.g. faulty reference measurement.
Notice!
A device error output at alarm output "ALARM2" is also always output at alarm output "ALARM1", independent of how alarm output "ALARM1" was configured.
X1-2
X1-...
10 k
GND
20 - 30 VDC
100 mA (max. 250 mA)
X1-1
Page 30
Electrical connection
28 rotoScan ROD4-3... Leuze electronic
Notice!
In 4-field mode, output "ALARM1" (X1-5) signals object detection in detection_field_far 1. To ensure the uniqueness of the signal, you should configure alarm output "ALARM1" so that only "object detection in the far detection field" is signalled.
"ALARM2" (X1-15)
The "low" output state always signals a device warning or device error, independent of how output "ALARM1" (X1-5) is configured.
Notice!
A device error output at alarm output "ALARM2" is also always output at alarm output "ALARM1", independent of how alarm output "ALARM1" was configured.
In 4-field mode, output "ALARM2" (X1-15) signals object detection in detection_field_far 2.

5.2.3 RESTART / resetting the data transmission rate to 57600 baud

The RESTART input X1-2 has, depending on operating status, several functions:
• Release of the restart-disable following object detection in the detection field.
• Release of the start disable following a system start.
The functions are activated by applying +24VDC to input X1-2 of an operationally ready ROD4-3…. Outputs Fn1 and Fn2 are switched off in the meantime; the display on the sensor (LED No. 3) illuminates red. A voltage of +24VDC must be applied to the RESTART input for between 0.12s and 3 s.
Restart input X1-2 must be connected to an external, permanently mounted button. X1-2 must not be connected to the rest of the control as, under certain conditions, the application of a restart pulse could result in an unintended release.
Hardware reset/resetting the data transmission rate to 57600 baud
For this purpose, the ROD4-3… must first be de-energised. By applying +24VDC for a duration of 2 … 4 s at input X1-2 during the power-on procedure, the data transmission
rate of the RS 232/RS 422 is reset to 57600 baud.
Attention!
Do not interrupt the supply voltage during this reset procedure under any circumstances! Prematurely interrupting the reset procedure for resetting the data transmission rate can put
the ROD4-3… in an irreversible error state which can only be corrected by the manufacturer!
Page 31
Electrical connection
Leuze electronic rotoScan ROD4-3... 29
TNT 35/7-24V

5.3 Functions of connection X2

At connection X2 (9-pin Sub-D socket), either an RS 232 or 422 interface is available. It is used to
• configure the ROD4-3…,
• transfer measurement data during scanner operation.
• analyse the coordinates during the configuration (e.g. for DTS applications).
• diagnose errors and perform troubleshooting.
By default, the connector housing for the X2 9-pin Sub-D connection is delivered with a PG dummy cable gland. If the connection is not used, this connector housing ensures protection class IP 65.
We recommend using the prefabricated cable KB-ROD4PC-… (accessory) for configuring the ROD4-3… For information on fabricating cables yourself, please proceed according to chapter 5.4.2. After configuring, remount the connector housing with the PG dummy cable gland.

5.4 Connection

5.4.1 Electrical supply

The ROD4-3… requires a DC voltage of +24V DC for its electrical supply. The power consumption is
• for the ROD4-30 (without heating) max. 8W
• for the ROD4-36 and ROD4-38(with heating) max. 50W
plus the load at the outputs (max. 20W).
The power supply must be fed in via an external fuse (e.g. in a switch cabinet) 2.5A semi time-lag (ROD4-30) or 4A semi time-lag (ROD4-36, ROD4-38). Furthermore, upstream of the safeguarding, a constant current of 2.5A or 4A, respectively, is to be provided to ensure that the fuse can be tripped in the event of failure.

5.4.2 Fabricating the cable on the sensor side

The delivery contents include three connector housings with screwed cable gland. Two are required for holding the 9-pin SUB-D-connector and the 15-pin SUB-D-socket (PC and control cable). One housing serves to protect interface X2 if no data communication is desired with the PC.
The cable screw fittings can be used with cable diameters from 6.5mm to 10.5mm.
Page 32
Electrical connection
30 rotoScan ROD4-3... Leuze electronic
Figure 5.5: Plug wiring
Attention!
Please note that the connector housing of the control cable must be securely screwed to in­terface X1, and the connector housing of cable X2, or the X2 dummy cap (without cable), must be securely screwed to the ROD4-3… Corresponding threaded pins can be found on the top side of the sensor housing.
If one of the two connector housings is missing, the ROD4-3… no longer meets protection class IP 65. The connector assignments can be found in chapter 5.1.

5.4.3 Structure of the connector

Each connector housing consists of the following individual parts:
• Housing with sealing ring and locating pins.
• Cable screw fittings (M16) with dummy plugs.
• Sub-D 9-pin plug or Sub-D 15-pin socket, each with solder connection
Notice!
Information on using the config. connector at connection X1 can be found in chapter 6.3.
35
3
X 1
X 2
35
3
Page 33
Electrical connection
Leuze electronic rotoScan ROD4-3... 31
TNT 35/7-24V

5.4.4 Points to be observed when fabricating and laying the cable

• The core cross section of the individual cable strands for connection X1 must be at least 0.5 mm2.
• Select a cable outer diameter between 6.5mm and 10mm.
• Maximum length of the cable for connection X1: 50m.
• Maximum length of the cable for connection X2: 10m (for RS 232).
• Maximum length of the cable for connection X2: 50m (for RS 422, twisted pair).
• Use shielded cable.
On the switching cabinet side of the system, the cable shielding must only be connected to PE.
• The cables must not be laid unsecured.
Sensor control cables must not be laid bunched together parallel to the power supply lines for machines. Inductive interference factors related to high-current-carrying motors are reduced in this way. Furthermore, the cables are to be routed in such a way that no damage (e.g. due to crushing) can occur.
As an option, sensor-side prefabricated cables are available in various lengths and for both interfaces.
Page 34
Electrical connection
32 rotoScan ROD4-3... Leuze electronic

5.5 Integration in the control system

The two following examples illustrate possibilities for connection to a control system.
After connecting the operating voltage PIN X1-3 (+U
B
) to PIN X1-1 (GND) and activating at least one of the detection field pairs (X1-4, X1-6, X1-7 or X1-8, see chapter 5.2.1), the device is ready for operation.

5.5.1 Connection example 1: without detection field pair switch

Integrating the ROD4-3… with discrete external wiring with relay or contactor without detection field pair switch:
Figure 5.6: Connection example without detection field pair switch
With this connection example, the restart-disable is realised by means of the command device "WA" connected at the RESTART input (X1-2). The device must, in this case, be configured with the software in such a way that the operating mode "with restart-disable" is active.
In this example, no detection field changeover is provided; only detection field pair 1 is active. For this purpose, directly connect FPS1 (X1-4) to the operating voltage VCC. The relays K1 and K2 used here have overlapping contacts (make before break) and are oper­ated directly at the two semiconductor outputs Fn1 (X1-11) and Fn2 (X1-12).
The two semiconductor outputs possess an internal electronic current limit and are protected in the event of errors by fuse SI 2.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
GND
RESTART
VCC
FPS1
ALARM1
FPS2
FPS3
FPS4
Fn1
Fn2
ALARM2
WA
K1
24VDC
+20% / -30%
0V
Sl 2
K2
k2
k1
k2k1
X1
Y1
Z1
k2k1
k1
k2
rotoScan ROD4-3…
Page 35
Electrical connection
Leuze electronic rotoScan ROD4-3... 33
TNT 35/7-24V

5.5.2 Connection example 2: with detection field pair switch

Integrating the ROD4-3… with discrete external wiring with relay or contactor with detection field pair switch:
Figure 5.7: Connection example with detection field pair switch
In this example, a detection field changeover between up to 8 detection field contours is possible via inputs X1-4 (FPS1), X1-6 (FPS2), X1-7 (FPS3) and X1-8 (FPS4) (one near and one far contour for each). The restart-disable and contactor monitoring are realised via the RESTART input.
The ROD4-3… is operated in this case in the operating mode "with restart-disable". The currently active, violated detection field is released by the command device "WA". The relays K1 and K2 used here have overlapping contacts (make before break) and are operated directly at the two secure semiconductor outputs Fn1 (X1-11) and Fn2 (X1-12).
X1
Y1
Z1
k2k1
k1
k2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
GND
RESTART
VCC
FPS1
ALARM1
FPS2
FPS3
FPS4
Fn1
Fn2
ALARM2
24VDC
+20% / -30%
WA
SI 2
S3S2 S4S1
K1
0V
K2
k2
k1
k2k1
rotoScan ROD4-3…
Page 36
Commissioning
34 rotoScan ROD4-3... Leuze electronic

6 Commissioning

By means of appropriate configuration with the aid of the RODsoft configuration software, the ROD4-3… can be adapted to the given application conditions.
Notice! The ROD4-3… models can only be configured with version 1.16 of the RODsoft config-
uration software and higher.

6.1 Hardware and software requirements

First steps with the device require the basis ROD4-3… unit, an interface cable and a PC. For the voltage supply, a power supply unit possessing the characteristics described in chapter "Technical data" on page 42 is required.
The PC used should meet the following requirements:
•Intel
®
processor at Pentium® level or faster (or compatible models, e.g. AMD®)
• At least 16 MB RAM
•CD-ROM drive
• Hard disk with at least 20 MB available memory.
• Free RS 232 interface (serial) or alternatively RS 422
•Microsoft
®
Windows 95/98/NT/2000/XP
The supplied installation CD-ROM is required for installing the RODsoft configuration soft­ware. The setup program is located on the CD-ROM. This program launches a self-explan­atory installation routine. After the installation, the program is ready to be started.

6.2 Device configuration

For the device configuration, you require the configuration software "ROD-Soft", which is included in the delivery contents.
Notice!
The description of the program can be found in the user manual, which is also included in the delivery contents.
Attention!
We assume here, that you perform the user-specific configuration of the ROD4-3… using this user manual.

Commissioning procedure:

• Install the configuration software on the PC (setup.exe)
• Connect the ROD4-3… to the PC using a standard 9-pin sub-D cable
• Enter password "ROD4LE" in level "authorised customer"
Page 37
Commissioning
Leuze electronic rotoScan ROD4-3... 35
TNT 35/7-24V

Short description:

The current measurement values and detection fields can be displayed under "Display measurement diagram". Under "Configuration" the response times, the detection field switches and other parameters are defined. To configure the detection fields, select the "Define detection fields" field. Error codes and other information are contained in the "system data".
A detailed description can be found in the user manual for the RODsoft configuration soft­ware.
Figure 6.1: User interface of the configuration software
Attention!
Before commissioning the device, you must adjust the device parameters and the detection fields for your application. To do this, configure the ROD4-3… using the software user man­ual so that the detection fields are optimised for the monitoring task.
Current measurement values (yellow line)
Far detection field (green line)
Near detection field (red line)
Page 38
Commissioning
36 rotoScan ROD4-3... Leuze electronic

6.3 Device configuration with ext. configuration memory / device exchange

The optional connection cable with configuration memory is used for supplemental, perma­nent storage (backup) of the ROD4-3… device configuration in a memory module (EEPROM) which is integrated in the connector housing.
The ROD4-3… can be connected via the standard X1 connection cable or the connection cable with integrated configuration memory (see chapter 8.2 "Accessories"). The cable with configuration memory has the same assignments as the standard connection cable.
If the cable with configuration memory is used, note the position of the slide switch which is integrated in the connector.
Figure 6.2: Switch in the config. connector
The switch position (see figure 6.2) defines how the configuration memory functions:
Position "1" - left: the ROD4-3… loads the configuration stored in the configura­tion memory of the cable when the device is switched on (standard setting).
Position "X" - right: the configuration memory of the cable loads the configuration stored in the ROD4-3… when the device is switched on.
Notice!
The default position of the slide switch is position "1". Position "X" is only necessary in ex­ceptional cases; this is used to copy the sensor configuration to the cable.
When the device is switched on, a check is performed to determine whether the configura­tion in the sensor matches that in the configuration memory. If this is the case, the sensor starts up as usual.
If the configurations do not match, then, depending on the position of the switch in the connector, the configuration is either transferred from the configuration memory to the ROD4-3… or vice versa.
Successful transfer is signalled by brief flashing of the two yellow LEDs 2 and 5 on the ROD4-3…. The configurations stored in the configuration memory and in the ROD4-3… now match. Afterward, the sensor starts up again as usual.
LR
1X
Page 39
Commissioning
Leuze electronic rotoScan ROD4-3... 37
TNT 35/7-24V
Notice!
The configuration memory of a ROD4-3… is incompatible with that of a ROD4…/ROD4-2… and, after used once, cannot be used in the respective device of the other type.

Using the external configuration memory / exchanging devices

If you configure the ROD4-3… with the RODsoft software and save the configuration in the ROD4-3…, the old configuration in the configuration memory is set to "invalid" and the new configuration is automatically loaded in the configuration memory of the connection cable the next time the sensor is started.
In the event of a device failure, disconnect the defective ROD4-3… from power, install the replacement device and switch the operating voltage back on. The configuration saved in the configuration memory is now transferred to the new device as described above.
Notice!
You can also use the connection cable with configuration memory to load the same config­uration in several ROD4-3… devices without having to connect a PC/notebook.

6.4 Screwing down and aligning the device

The ROD4-3… is to be mounted and aligned as described in chapter 4.

6.5 Switching on the device

Once the device is installed, the required device parameters set and the detection fields defined, the ROD4-3… can be put into operation.
After you have switched on the voltage supply for the ROD4-3…, the red LED illuminates at first. After the red LED switches off (for free near detection field only), the ROD4-3… is ready.
Figure 6.3: LEDs
Page 40
Testing and maintenance
38 rotoScan ROD4-3... Leuze electronic

7 Testing and maintenance

7.1 Testing

The response of the detection field should be checked annually to ensure availability.

7.2 Cleaning

The front cover and the aperture plates of the window-monitoring photoelectric sensors should be cleaned at regular intervals (application dependent) with a soft cloth and commer­cially available, non-aggressive glass cleaner.
Attention!
Do not use solvents or cleaning agents containing acetone. Use of improper cleaning agents can damage the optical window.
If window monitoring continues to report a soiled cover even after cleaning the front cover and the aperture plates of the window-monitoring photoelectric sensors, the front cover must be replaced. In this case, please contact the Leuze electronic service department.
Attention!
When replacing the front cover, the ROD4-3… must always be disconnected from the volt­age supply. The replacement must only be performed by trained personnel in a clean envi­ronment.
Page 41
Delivery contents and accessories
Leuze electronic rotoScan ROD4-3... 39
TNT 35/7-24V

8 Delivery contents and accessories

8.1 Scope of delivery

The basic unit consists of:
• rotoScan ROD4-3…
• 2 hoods with integrated connectors with dummy plugs, including plugs for solder con­nection
RODsoft configuration software
• rotoScan ROD4-3… technical description
• user manual for RODsoft configuration software

8.2 Accessories

The following accessories are available:
Part No. Type designation Remark
501 08138 KB-ROD4-CP-5000
Connection cable for ROD4-3x, Sub-D socket on one end, 15-pin, with configuration memory, cable length 5m
501 08139 KB-ROD4-CP-10000
Connection cable for ROD4-3x, Sub-D socket on one end, 15-pin, with configuration memory, cable length 10m
500 38069 KB-ROD4PC-3000
Configuration cable for ROD4-3, Sub-D socket/Sub-D connector, 9-pin, cable length 3m
500 38070 KB-ROD4PC-10000
Configuration cable for ROD4-3, Sub-D socket/Sub-D connector, 9-pin, cable length 10m
500 38067 KB-ROD4-5000
Connection cable for ROD4-…, Sub-D socket on one end, 15-pin, cable length 5m
500 38068 KB-ROD4-10000
Connection cable for ROD4-…, Sub-D socket on one end, 15-pin,
cable length 10m 500 38072 KD-ROD4-X1 Sub-D socket with housing, 15-pin, for connection X1 500 38073 KD-ROD4-X2 Sub-D socket with housing, 9-pin, for connection X2 500 38066 BT ROD4 Mounting system for ROD4-3…
–RODsoft
RODsoft configuration software for ROD4-3…,
free download from
www.leuze.de
Page 42
Delivery contents and accessories
40 rotoScan ROD4-3... Leuze electronic

8.2.1 Pin assignment for connection cables KB-ROD4-5000 and KB-ROD4-10000

12-wire connection cable (15-pin Sub-D socket, one end)
PIN Signal Core colour
1GND black
2Restart blue
3UB red
4 FPS1 orange
5ALARM1 yellow
6 FPS2 green
7 FPS3 violet
8 FPS4 grey
9NC
10 NC
11 Fn1 white
12 Fn2 white-black
13 NC
14 NC white-brown
15 ALARM2 brown
8
15
1
2
3
4
5
6
7
14
13
12
11
10
9
Page 43
Delivery contents and accessories
Leuze electronic rotoScan ROD4-3... 41
TNT 35/7-24V

8.2.2 BT ROD4 mounting system

The ROD4-3… can be fastened using the holes on the rear of the device. No mounting kit is necessary in this case.
It is, however, recommended that the ROD4-3… be mounted with the aid of the BT ROD4 mounting system. The advantage of this mounting variant lies in the exchangea­bility of the device. The device can, in this way, be removed from the mounting system and returned at a later time without readjusting the device.
With the aid of the BT-ROD4 mounting system, pitches of maximum 8° downward or upward are possible. In addition, the mounting kit allows lateral inclinations of up to ±4 °.
Figure 8.1: Dimensioned drawing BT ROD4…
Lateral view
Sensor mounting surface Part overview
All dimensions in mm
Page 44
Technical data
42 rotoScan ROD4-3... Leuze electronic

9 Technical data

9.1 Detection field data

Table 9.1: Technical data - detection fields
Near detection field
Radius of near detection field 0 … 30m
1)
Reflectivity
ROD4-30/ROD4-36: from min. 1.8 % (matte black) ROD4-38: from min. 6%
Object size see figure 9.1
Response time at least 40 ms (corresponds to 1 scan)
Number of detection field pairs 8 (selectable via switching inputs)
Output two PNP transistor outputs, 24V/250 mA
Start-up
the start-up testing and start disable are configured separately.
Far detection field
Radius of far detection field 0 … 50m
1)
1) Particularly in the far range, the ROD4-38 only detects large objects and objects with high diffuse reflection
Reflectivity
ROD4-30/ROD4-36: from min. 1.8 % (matte black) ROD4-38: from min. 6%
Object size see figure 9.1
Response time at least 40 ms (corresponds to 1 scan)
Number of detection field pairs 8 (selectable via switching inputs)
Output
max. 2 PNP transistor outputs, max. 100mA (configurable)
Object measurement
Measurement range
ROD4-30/ROD4-36: 0 … 65 m ROD4-38: 0 … 25m
Luminosity coefficient see figure 9.1
Object size see figure 9.1
Output serial interface RS 232, RS 422
Distance resolution 5 mm
Angular resolution 0.36 °
Repeatability ± 15mm
Page 45
Technical data
Leuze electronic rotoScan ROD4-3... 43
TNT 35/7-24V

9.2 Electrical data

Table 9.2: Technical data - electrical data

9.3 Software

Table 9.3: Technical data - software
Power supply
Voltage supply
1)
1) Protective Extra Low Voltage (PELV) - protective extra-low voltage with reliable disconnec­tion. For UL applications: only for use in class 2 circuits according to NEC.
+24V DC +20 % / -30 %, safety class III
Overcurrent protection
via fuse 2.5A (4 A with heating) semi time-lag in the switch cabinet
Current consumption approx. 400mA (approx. 2.5A with heating)
Power consumption 10 … 50W at 24 V DC
Overvoltage protection overvoltage protection with protected limit stop
Voltage dips acc. to EN 61496-1 (VDE 0113, part 201)
Inputs
Restart/Reset
Release of the restart-disable following object detec­tion in the detection field or release of the start disable following a system start or reset of the data transmis­sion rate to 57600 baud. See chapter 5.2.3.
Detection field pair switch
selection between max. 8 detection field pairs via four control lines with internal monitoring, 24 VDC opto­decoupled
Outputs
For near detection field (Fn1, Fn2)
2x semiconductor output, PNP max. 250mA short-circuit monitored, overcurrent protected, load must demonstrate lowpass characteristics, limit frequency f
g
1kHz
For far detection field / soiling (ALARM1)
PNP transistor output, max. 100mA, configurable
For far detection field / warning and error output (ALARM2)
PNP transistor output, max. 100mA, configurable
Configuration
Configuration software
"RODsoft" configuration software under Windows 9x/NT/ 2000/XP
Interfaces
RS 232, RS 422 device configuration and measurement data transmission
Page 46
Technical data
44 rotoScan ROD4-3... Leuze electronic

9.4 Optical data

Table 9.4: Technical data - optical data
Figure 9.1: Object size/diffuse reflection as a function of distance for the ROD4-30/
ROD4-36
Optical properties
Angular range max. 190°
Angular resolution 0.36 °
Scanning rate 25scans/s or 40 ms/scan
Laser class
1 acc. to EN 60825-1, infrared laser diode, wavelength: 905nm, P
max
: 15W, pulse duration: 3ns,
average output power: 12µW
Laser beam
approx. 15mm diameter, distance dependent, see figure 9.2
1
10
100
10
1.8
100
1000
10000
2015
8
4
2
1 10
100
10
100
1000
10000
2015
8
4
2
12,5
25
50
Remission [%]
Distance [m]
Object size [mm]
Distance [m]
Reflector
White plaster, writing paper
Grey cardboard (18%)
Black cord
Page 47
Technical data
Leuze electronic rotoScan ROD4-3... 45
TNT 35/7-24V
Figure 9.2: Typical beam dimensions for the ROD4-3…
140
120
100
80
60
40
20
0
0
25 3051015
20
Y
X
Distance [m]
Beam dimensions in mm
Light spot height Y
Light spot width X
Page 48
Technical data
46 rotoScan ROD4-3... Leuze electronic

9.5 Environmental data

Table 9.5: Technical data - environmental data
Environmental and material data
Protection class IP 65 acc. to IEC 60529
Contact protection all-insulated, safety class III
Operating temperature 0°C … +50 °C, with heating -20°C … +50°C
Storage temperature -20°C … +60°C
Dimensions 140 x 155 x135 (WxHxD) in mm
Distance from scanning plane to bottom edge of housing
48.75mm
Connection
2 connectors (can be plugged from above, solder con­nection)
Cable length
max. 50m with conductor cross-section 0.5 mm2 (valid for X1 and X2 as RS 422)
Transmitter infrared laser diode (λ = 905nm)
Housing diecast aluminium, plastic
Weight approx. 2kg
Vibrating stress
acc. to IEC 60068 part 2 - 6, 10 … 55Hz max. 5G
Continuous shock acc. to IEC 60068 part 2 - 29, 10 G, 16 ms
Interference rejection
as per DIN EN 61496-3 (in accordance with the requirements for type 4) as well as per DIN 40839-1/3 test impulse 1, 2, 3a, 3b and 5 (no application for vehi­cles with combustion motors)
Rotating mirror drive brushless DC motor
Rotating mirror bearings maintenance-free ball bearing
Page 49
Technical data
Leuze electronic rotoScan ROD4-3... 47
TNT 35/7-24V

9.6 Dimensioned drawing ROD4-3…

Figure 9.3: Dimensioned drawing ROD4-3…
a Zero point for measuring b Scanning plane R Smallest bending radius = 50mm
All dimensions in mm
Page 50
Status messages, errors and error rectification
48 rotoScan ROD4-3... Leuze electronic

10 Status messages, errors and error rectification

10.1 LED indicators

The status of the ROD4-3… can be read using the five LEDs located on the front side. A transparent cover protects the LEDs from contamination and guarantees protection class IP 65. When in a voltage-free state, the LEDs are hidden from view by this cover.
Figure 10.1: ROD4-3… LED indicators
3
4
52
1
1
(green)2(yellow)3(red)
5
(yellow)
4
(green)
Page 51
Status messages, errors and error rectification
Leuze electronic rotoScan ROD4-3... 49
TNT 35/7-24V

Overview of LED indicators

LED Colour Function / Meaning
1 green Sensor functions active, near detection field is free
2yellow
• Continuous light (CL): far detection field is occupied
• Flashing fast (FF) at approx. 4Hz Configuration from config. for a duration of 1s: connector successfully loaded
(together with LED 5).
3redNear detection field is occupied, Fn outputs are switched off
4 green Near detection field is free, Fn outputs are active
5yellow
• Slowly flashing (SF) at approx. 1Hz: warning message
• Flashing fast (FF) at approx. 4Hz: error message
• Flashing fast (FF) at approx. 4Hz Configuration from config. for a duration of 1s: connector successfully loaded
(together with LED 2).
• Continuous light (CL): restart-disable locked
Page 52
Status messages, errors and error rectification
50 rotoScan ROD4-3... Leuze electronic

10.2 Status displays

Notice!
The rotoScan ROD4-3… outputs two different types of messages at output "ALARM1": Warning message - Information for the user indicating that a non-critical danger area (e.g. window contamination) has been detected in the device. Error message - System has detected a critical device error and switches off all outputs.
Table 10.1: Status displays on the rotoScan ROD4-3
LED indicators Status
Near detection field is free,
• Fn outputs (X1-11, X1-12) are enabled.
Near detection field is free,
• Fn outputs (X1-11, X1-12) are enabled,
• Far detection field is occupied, (output X1-5 "ALARM1" is enabled)
Near detection field is free,
• Fn outputs (X1-11, X1-12) are enabled,
• Warning message due to e.g. soiled front cover
Near detection field is occupied,
• Fn outputs (X1-11, X1-12) are disabled,
• Restart-disable is active
Near detection field is free,
• Fn outputs (X1-11, X1-12) are disabled,
• Restart-disable is switched on
Near detection field is occupied,
• Fn outputs (X1-11, X1-12) are disabled,
• Output "ALARM1" (X1-5) is enabled
• Fn outputs (X1-11, X1-12) are disabled,
• Output "ALARM1" (X1-5) is enabled
• for a duration of 1s, configuration successfully transferred from the config. connector,
SF
CL
CL
FF
FFFF
Page 53
Status messages, errors and error rectification
Leuze electronic rotoScan ROD4-3... 51
TNT 35/7-24V

10.3 Diagnostic codes and causes

All errors which occur in the ROD4-3… during operation are stored in a diagnostic list in the device. You can call up this list with the RODsoft software. On the toolbar, click or select System data Load diagnostic data from sensor on the menu bar.
The messages from the last 8 events are documented. This first memory slot always contains the most recent error message.
Listed in the following table are all errors together with corresponding troubleshooting notices:
Code No.Meaning Measure
102 2 Data transfer error on interface X2.
Ç Check the interface parameters and start
the transfer again.
103 2 Data transfer error on interface X2.
Ç Check the interface parameters and start
the transfer again.
104 2 Data transfer error on interface X2.
Ç Check the interface parameters and start
the transfer again.
105 6
Function, access, command not per­mitted at currently selected access level.
Ç Change the access level and start the
transfer again.
201 4
Interface X2 time specifications not complied with, last message overwrit­ten.
Ç Check the interface parameters and start
the transfer again.
302 2
Interface X2 time specifications not complied with, send data not acknowl­edged.
Ç Check the interface parameters and start
the transfer again.
306 5
Previous message not completely issued, interface X2 time specifica­tions not complied with.
Ç Check the interface parameters and start
the transfer again.
801 2
Error memory cannot be read, internal defect
Ç If reset is not successful, contact customer
service.
805 6
Error memory cannot be transferred, transmission error at interface X2
Ç Check the interface parameters and start
the transfer again.
1002 1
Motor does not reach nominal rota­tional speed after start-up; internal defect.
Ç If reset is not successful, contact customer
service.
1002 2
Motor speed not constant after start­up; internal defect.
Ç If reset is not successful, contact customer
service.
1003 1
Motor does not reach nominal rota­tional speed after start-up; internal defect.
Ç If reset is not successful, contact customer
service.
1003 2
Motor speed not constant after start­up; internal defect.
Ç If reset is not successful, contact customer
service.
Table 10.2: ROD4-3… – diagnostic codes, causes and measures
Page 54
Status messages, errors and error rectification
52 rotoScan ROD4-3... Leuze electronic
1003 3
Motor speed not constant after start­up; time-out.
Ç If reset is not successful, contact customer
service.
1110 4
Switching outputs Fn1/Fn2 cannot be switched, short-circuit with 0 V DC or +24 V DC.
Ç Check the connection/wiring of Fn1/Fn2.
1110 5
Switching outputs Fn1/Fn2 cannot be switched, short-circuit between Fn1 and Fn2.
Ç Check the connection/wiring of Fn1/Fn2.
1110 6
Switching outputs Fn1/Fn2 cannot be switched, short-circuit with 0 V DC or +24 V DC.
Ç Check the connection/wiring of Fn1/Fn2.
1111 7
Short-circuit between switching out­puts Fn1/Fn2.
Ç Check the connection/wiring of Fn1/Fn2.
1111 8
Short-circuit of one switching output (Fn1 or FN2) with 0 V DC.
Ç Check the connection/wiring of Fn1/Fn2.
1111 9
Short-circuit of one switching output (Fn1 or FN2) with +24 V DC.
Ç Check the connection/wiring of Fn1/Fn2.
1606 4
Angle error detected, poss. rotation of the sensor housing; switch-off and reset followed.
Ç If reset is not successful, contact customer
service.
1607 5
Angle error detected, poss. rotation of the sensor housing; switch-off and reset followed.
Ç If reset is not successful, contact customer
service.
1608 8
Motor speed not constant during operation, poss. rotation of the sensor housing.
Ç If reset is not successful, contact customer
service.
1608 9
Motor speed not constant during operation, poss. rotation of the sensor housing.
Ç If reset is not successful, contact customer
service.
1608 10
Motor speed not constant during operation, poss. rotation of the sensor housing.
Ç If reset is not successful, contact customer
service.
1705 1
Signal of a photoelectric sensor of the window monitoring below the bottom limit, dirty front cover.
Ç Clean the front cover according to instruc-
tions (see chapter 7.2 "Cleaning" on page 38).
1705 2
Signal from a photoelectric sensor of the window monitoring above the upper limit, oil/grease on the front cover.
Ç Clean the front cover according to instruc-
tions (see chapter 7.2 "Cleaning" on page 38).
Code No.Meaning Measure
Table 10.2: ROD4-3… – diagnostic codes, causes and measures
Page 55
Status messages, errors and error rectification
Leuze electronic rotoScan ROD4-3... 53
TNT 35/7-24V
1906 1
Switching outputs Fn1/Fn2 cannot be switched, internal or external short­circuit.
Ç Check the connection/wiring of Fn1/Fn2. If
reset is not successful, contact customer service.
1906 2
Switching outputs Fn1/Fn2 cannot be switched, internal or external short­circuit.
Ç Check the connection/wiring of Fn1/Fn2. If
reset is not successful, contact customer service.
1906 5
Read back error on switching outputs Fn1/Fn2, internal or external short-cir­cuit.
Ç Check the connection/wiring of Fn1/Fn2. If
reset is not successful, contact customer service.
1906 6
Error on the laser's switch-off path, switch-off because of eye safety, inter­nal defect.
Ç If reset is not successful, contact customer
service.
1907 4
Angle error detected, poss. rotation of the sensor housing; switch-off and reset followed.
Ç If reset is not successful, contact customer
service.
1907 7
Angle error detected, poss. rotation of the sensor housing; switch-off and reset followed.
Ç If reset is not successful, contact customer
service.
2002 12
Configuration data displayed for inspection not acknowledged quickly enough
Ç Start the transfer again.
2007 18
Date of the currently transmitted detection field is older than the date of the detection field stored in the sensor.
Ç Update the PC's date and time setting.
2017 19 Data transfer error with ConfigPlug.
Ç Replace the ConfigPlug or the complete
cable with plug.
2017 23
The connected sensor does not sup­port the configuration file in the Con­figPlug.
Ç Change the sensor, observe the device
type.
2017 24
The connected sensor does not sup­port the configuration file in the Con­figPlug.
Ç Change the sensor, observe the device
type.
2017 26
Date of the currently transmitted con­figuration is older than the date of the configuration stored in the sensor.
Ç Update the PC's date and time setting.
2201 5
Number of measurements in the scan too small due to rotational speed error in the motor or because internal fuse was blown.
Ç If reset is not successful, contact customer
service.
2302 1 Error occurred during sensor start-up. Sequential error.
Code No.Meaning Measure
Table 10.2: ROD4-3… – diagnostic codes, causes and measures
Page 56
Status messages, errors and error rectification
54 rotoScan ROD4-3... Leuze electronic
2401 10
Reference measurement failed; glare from another light source (905 nm) or rotation speed error.
Sensor performed reset.
2401 13
Reference measurement failed, dust in the device, due to the plug housing or dummy cap not being screwed on.
Ç Screw the plugs of interfaces X1 and X2.
2401 41
Reference measurement failed; glare from another light source (905 nm) or rotation speed error.
Sensor performed reset.
2402 10
Reference measurement failed; glare from another light source (905 nm) or rotation speed error.
Sensor performed reset.
2402 41
Reference measurement failed; glare from another light source (905 nm) or rotation speed error.
Sensor performed reset.
2701 1
Invalid diagnostic command received, software incompatible with firmware.
Ç Use a newer version of the configuration
software.
2702 3
Invalid diagnostic value requested, software incompatible with firmware.
Ç Use a newer version of the configuration
software.
2800 2
2 field pair control inputs activated longer than 1s.
Ç Check the switchover times of the control
inputs FPS1 - FPS4.
2800 3
The detection field changeover which occurred does not match the preset which was programmed in the sensor.
Ç Check the activation of the detection fields
in the program wizard.
2800 4
More than 2 detection fields activated during operation.
Ç Check the activation of the control inputs
FPS1 - FPS4.
2800 6
Unusable or defective control voltage for the detection field activation.
Ç Check the activation of the control inputs
FPS1 - FPS4.
2800 8
No detection field activated. Can occur during operation and switching off the device.
Ç If detected during running operation, check
the activation of the control inputs FPS1 ­FPS4.
2801 1
Error while testing the inputs for detection field changeover; internal defect.
Ç Contact the customer service.
2802 3
The detection field activation which occurred does not match the preset which was programmed in the sensor.
Ç Check the activation of the detection fields
in the program wizard.
2802 4
More than 2 detection fields selected when starting the sensor.
Ç Only activate one of the control inputs
FPS1 - FPS4.
2802 6
Unusable or defective control voltage for the detection field activation.
Ç Check the activation of the control inputs
FPS1 - FPS4.
Code No.Meaning Measure
Table 10.2: ROD4-3… – diagnostic codes, causes and measures
Page 57
Status messages, errors and error rectification
Leuze electronic rotoScan ROD4-3... 55
TNT 35/7-24V
2802 8
No detection field activated during start-up of the sensor.
Ç Activate one of the control inputs FPS1 -
FPS4.
2804 3
The detection field activation which occurred does not match the preset which was programmed in the sensor.
Ç Check the activation of the detection fields
in the program wizard.
2804 4 No detection field clearly selected.
Ç Check the activation of the control inputs
FPS1 - FPS4.
2804 6
Unusable or defective control voltage for the detection field activation.
Ç Check the switchover times of the control
inputs FPS1 - FPS4.
3016 11
Confirmed single password entered wrong.
Ç Repeat the password entry.
3203 6
Sensor has optical glare caused by another device.
Ç Switch off the supply voltage and start the
sensor again.
3203 7
Sensor has optical glare caused by another device.
Ç Switch off the supply voltage and start the
sensor again.
Code No.Meaning Measure
Table 10.2: ROD4-3… – diagnostic codes, causes and measures
Page 58
Appendix
56 rotoScan ROD4-3... Leuze electronic

11 Appendix

11.1 Terms and abbreviations used with ROD4-3… and the RODsoft soft­ware
Alarm output ALARM1
Semiconductor output which signals a device warning and error and/or occupancy of a detection field. The function can be selected in RODsoft via the "alarm signal type". The output is at pin 5 of interface X1 and is designated in the ROD4 handbook as ALARM.
Alarm output ALARM2
Semiconductor output which signals a device warning and error. The output is at pin 15 of interface X1 and is designated in the ROD4 handbook as WARN.
Start disable
Following device start-up, the restart button must be actuated in order to activate the outputs.
Start-up test
Following device start-up, the near detection fields must be clear after the start-up delay period has passed; the outputs are switched off. To activate the outputs, at least one near detection field must be occupied and then again be cleared.
Start-up delay
Configurable time which must pass before a permanently clear near detection field activates the corresponding switching output. The start-up delay for far detection fields is permanently set to 80ms.
Response time
Time which must pass before a permanent detection field occupancy switches off the corresponding switching output (separately configurable for near and far detection fields).
Output start-stop segment, output resolution
Used to configure the measurement value transmission at serial interface X2. The configuration is made in multiples of 0.36°. A detection range of 180° corresponds to a start segment of 14*0.36 ° and a stop segment of 514*0.36°. If the output resolution is > 1*0.36°, the minimum value within the resolution interval is transferred/displayed. Notice: Monitoring of the detection fields also occurs outside of the configured trans­mission range.
F
Field
Detection field
Long version of the term field.
Page 59
Appendix
Leuze electronic rotoScan ROD4-3... 57
TNT 35/7-24V
Near detection field
Max. detection range 30m, object detection within the near detection field affects out­puts Fn1 (pin X1-11) and Fn2 (pin X1-12). The near detection field is represented in the user interface of the RODsoft configuration software by the colour red.
Fn
Short version of the term near detection field.
Far detection field
max. detection range 50m, object detection within the far detection field affects out­put ALARM1 (pin X1-5, depending on the configuration). The far detection field is represented in the user interface of the RODsoft configuration software by the colour green.
Ff
Short version of the term far detection field.
FP
Field pair, detection field pair; the configuration software can be used to configure up to 7 field pairs in the ROD4­3…, each with two detection fields (near and far).
FP1
Field pair 1.
FPS
Field pair switch.
Minimum object size
This parameter is permanently stored and is calculated from the maximum radius of the detection field. Objects are detected if at least the minimum number of consecu­tive scanning beams (multiple of 0.36°) is incident on an object.
Scanning rate
Rotational frequency of the scanner deflection mirror = 25Hz.
Sector size
This parameter can be changed. If the value for the sector size is > 1, objects are detected if the minimum number of consecutive scanning beams (multiple of 0.36°) is incident on an object. If the sector size is > 1, the entry for minimum object size is immaterial.
Page 60
Appendix
58 rotoScan ROD4-3... Leuze electronic
Serial interface baud rate
Used to configure the transmission rate (9.6 … 687.5 kBit/s) at serial interface X2 of the sensor. The baud rate is continuously changed in the sensor.
Important notice: If the baud rate is changed, a PC cannot initially be connected to the sensor via ROD­soft. This must first be adjusted in RODsoft with the Settings –> PC configuration – > Interface menu command (max. 115200Baud at RS 232). We recommend working with the factory setting of 57600 Bd.
If the baud rate at X2 is set to a value higher than 115200Baud, a connection is no longer possible with RODsoft via the RS 232. Resetting to 57600 Bd can then only be performed via an external connection at pin X1-2 (see chapter 5.2.3 "RESTART / resetting the data transmission rate to 57600 baud").
Dust suppression
With the introduction of the new ROD4-3… models, considerably more effective dust suppression was implemented in the devices. With activated dust suppression (rec­ommended), sensor availability is significantly increased in the event of small parti­cles in the air, such as insects. This also maximises the time which may pass before cleaning of the front cover becomes necessary.
Dust suppression is implemented globally, i.e. it is used in all detection fields. In the RODsoft configuration software, 3 parameters determine the function of the dust sup­pression (factory setting: activated):
• the object size (factory setting: 70mm)
• the object speed (factory setting: 1600mm/s)
• the response time (factory setting: 80ms)
Object size
This dust suppression parameter defines the maximum size up to which interfering objects (e.g. particles in the air) should not be detected. Values that are too large pre­vent object detection. Values that are too small increase the sensitivity to interfering objects. The 'Automatic' setting results in less efficient dust suppression.
Object speed
The object speed specifies the maximum speed of the objects that are to be detected; if necessary, the speed of the sensor itself is to be taken into account. Values that are too small prevent object detection. Values that are too large and the value '0 mm/s' increase the sensitivity to interfering objects.
Page 61
Appendix
Leuze electronic rotoScan ROD4-3... 59
TNT 35/7-24V
Comment:
Speed refers not only to the speed at which an object moves toward the sensor (speed component v
x
in figure 11.1); it generally refers to the maximum speed with which objects may move in the detection field (speed components vx and vy in figure 11.1). As area scanning occurs in the XY plane, speed component v
z
cannot be detected and evaluated. The maximum object speed can be best optimised through testing.
Figure 11.1:Components of the object speed
Response time
Another important parameter is the response time. The longer the selected response time, the more calculating time is available for the dust-suppression algorithm and, thus, the more powerful the dust suppression. With a response time < 80ms, only the object size is evaluated.
Dust suppression is more efficient the:
• greater the selected object size
• lower the selected object speed
• longer the response time
It is a good idea to optimise the values preset ex works (object size: 70mm, object speed: 1600mm/s, response time: 80ms) for the respective application through prac­tical tests.
Notice!
Compatibility mode for old ROD4/ROD4-2… models:
• Object size ’automatic’
• Object speed: 0 mm/s
Config. connector:If a ConfigPlug with ROD4-3x configuration (with new dust sup-
pression) is plugged into a ROD4/4-2x, the configuration is accept­ed, but the old dust suppression used!
v
x
v
y
v
z
Page 62
Appendix
60 rotoScan ROD4-3... Leuze electronic
RODsoft: If a ROD4-3x configuration with new dust suppression is loaded
from a file while a ROD4 or ROD4-2x is plugged in, the new dust suppression parameters are not displayed. The sensor uses the old dust suppression following the transfer. The ROD4-3x configuration becomes a ROD4-2x compatible configuration.
A ROD4-3x configuration can also be loaded if a ROD4/4-2x was selected. The new dust suppression parameters are not displayed in this case. The scanner uses the old dust suppression following the transfer.
Restart
Determines how switching outputs are switched following object detection in a near detection field in the event of subsequent non-occupancy.
• Manual restart: The restart button must be actuated and start disable must be active.
• Automatic restart: Following a start-up delay, the outputs are activated.
Angular resolution
Smallest technically possible resolution of the sensor in angular degrees.