Leuze electronic MSI-MD-FBX Original Operating Instructions

Page 1
MSI-MD-FBX
Muting Controller
EN 2017/03 - 50136367
We reserve the right to
make technical changes
S A F E I M P L E M E N T A T I O N A N D O P E R A T I O N
O r i g i n a l o p e r a t i n g i n s t r u c t i o n s
Page 2
© 2017 Leuze electronic GmbH & Co. KG In der Braike 1 D-73277 Owen / Germany Phone: +49 7021 573-0 Fax: +49 7021 573-199 http://www.leuze.com info@leuze.de
Leuze electronic MSI-MD-FBX 2
Page 3

Table of contents

Table of contents
1 About this document ............................................................................................5
1.1 Checklists................................................................................................................................ 5
1.2 Downloading the diagnostics software from the Internet ........................................................ 5
1.3 Used symbols and signal words .............................................................................................5
2 Safety .....................................................................................................................7
2.1 Intended use and foreseeable misuse.................................................................................... 7
2.1.1 Intended use........................................................................................................................ 7
2.1.2 Foreseeable misuse ............................................................................................................8
2.2 Necessary competencies........................................................................................................ 8
2.3 Responsibility for safety.......................................................................................................... 9
2.4 Disclaimer ............................................................................................................................... 9
3 Device description ..............................................................................................10
3.1 Device construction .............................................................................................................. 11
3.2 Display elements .................................................................................................................. 12
3.3 Connection technology .........................................................................................................13
4 Functions.............................................................................................................14
4.1 Timing controlled 2-sensor muting........................................................................................ 14
4.1.1 Timing controlled 2-sensor muting with Muting-enable .....................................................15
4.2 Overriding and muting restart ...............................................................................................15
4.3 Error reset............................................................................................................................. 16
4.4 Restart ..................................................................................................................................17
4.5 Acknowledging/resetting....................................................................................................... 17
5 Applications ........................................................................................................18
5.1 Access guarding with timing controlled muting..................................................................... 18
6 Mounting..............................................................................................................19
6.1 Mounting the muting controller ............................................................................................. 19
6.1.1 Mounting in the UDC device column .................................................................................19
6.1.2 Mounting on the UDC device column................................................................................20
6.1.3 Mounting on the system ....................................................................................................20
6.2 Arrangement of the muting sensors...................................................................................... 20
6.2.1 Basic information...............................................................................................................21
6.2.2 Selecting optoelectronic muting sensors...........................................................................21
6.2.3 Minimum distance for optoelectronic muting sensors .......................................................21
6.2.4 Arrangement of the muting sensors for timing controlled 2-sensor muting .......................22
7 Electrical connection..........................................................................................25
7.1 Connecting the muting controller .......................................................................................... 25
7.2 Pin assignment of the machine interface.............................................................................. 27
7.3 Pin assignment of safety sensor........................................................................................... 27
7.4 Pin assignment of the acknowledgment unit ........................................................................ 28
7.5 Pin assignment of muting indicator....................................................................................... 28
7.6 Pin assignment of muting sensors........................................................................................ 29
7.7 Circuit diagram examples .....................................................................................................29
7.7.1 Timing controlled 2-sensor muting ....................................................................................29
Leuze electronic MSI-MD-FBX 3
Page 4
Table of contents
8 Starting up the device - Configuration..............................................................30
8.1 Overview............................................................................................................................... 30
8.2 Setting the operating mode................................................................................................... 31
9 Testing .................................................................................................................33
9.1 Before the initial start-up and following modifications........................................................... 33
9.2 Regularly by qualified persons.............................................................................................. 33
9.3 Periodically by the operator ..................................................................................................34
9.3.1 Checklist – periodically by the operator............................................................................. 34
10 Care, maintenance and disposal .......................................................................35
11 Diagnostics and troubleshooting ......................................................................36
11.1 What to do in case of failure? ...............................................................................................36
11.2 Error messages 7-segment display ......................................................................................36
12 Service and support ...........................................................................................40
13 Technical data .....................................................................................................41
13.1 General specifications .......................................................................................................... 41
13.2 Dimensioned drawings ......................................................................................................... 43
13.3 Dimensioned drawings - Accessories................................................................................... 43
14 Order guide and accessories.............................................................................45
14.1 Type overview....................................................................................................................... 45
14.2 Accessories........................................................................................................................... 45
15 EC Declaration of Conformity ............................................................................47
Leuze electronic MSI-MD-FBX 4
Page 5

1 About this document

1.1 Checklists

The checklists (see chapter 9 "Testing") serve as a reference for the machine manufacturer or supplier. They replace neither testing of the complete machine or system prior to the initial start-up nor their periodic testing by a competent person. The checklists contain minimum testing requirements. Depending on the application, other tests may be necessary.

1.2 Downloading the diagnostics software from the Internet

Ä Call up the Leuze home page: www.leuze.com Ä Enter the type designation or part number of the device as the search term. Ä The diagnostics software can be found on the product page for the device under the Downloads tab.

1.3 Used symbols and signal words

Tab.1.1: Warning symbols and signal words
Symbol indicating dangers to persons
About this document
Symbol indicating possible property damage
NOTE Signal word for property damage
Indicates dangers that may result in property damage if the measures for dan­ger avoidance are not followed.
CAUTION Signal word for minor injuries
Indicates dangers that may result in minor injury if the measures for danger avoidance are not followed.
WARNING Signal word for serious injury
Indicates dangers that may result in severe or fatal injury if the measures for danger avoidance are not followed.
DANGER Signal word for life-threatening danger
Indicates dangers with which serious or fatal injury is imminent if the measures for danger avoidance are not followed.
Tab.1.2: Other symbols
Symbol for tips
Text passages with this symbol provide you with further information.
Symbol for action steps
Text passages with this symbol instruct you to perform actions.
Symbol for action results
Text passages with this symbol describe the result of the preceding action.
Leuze electronic MSI-MD-FBX 5
Page 6
About this document
Tab.1.3: Terms and abbreviations
AOPD Active Optoelectronic Protective Device
(Active Optoelectronic Protective Device)
Blanking Deactivation of the protective function of individual beams or beam areas with
monitoring for interruption
CS Switching signal from a control or a machine interface
(Controller Signal)
EDM Contactor monitoring
(External Device Monitoring)
FG Function group
(Function Group)
LED LED, display element in transmitter and receiver
MS1, MS2 Muting sensor1,2
MTTF
d
Mean time to dangerous failure
(Mean Time To dangerous Failure)
Muting Temporary automatic suppression of the safety functions
OSSD Safety-related switching output
(Output Signal Switching Device)
PFH
d
Probability of a dangerous failure per hour
(Probability of dangerous Failure per Hour)
PL Performance Level
Reduced resolution Reduction of the detection capability of the protective field without monitoring
for tolerating small objects in the protective field
RES Start/restart interlock
(Start/REStart interlock)
Scan Consecutive scans of the protective field from the first to the last beam
Safety sensor System consisting of transmitter and receiver
SIL Safety Integrity Level
State ON: device intact, OSSD switched on
OFF: device intact, OSSD switched off
Locking: device, connection or control / operation faulty, OSSD switched off (lock-out)
Leuze electronic MSI-MD-FBX 6
Page 7

2 Safety

For mounting, operating and testing, this document as well as all applicable national and international stan­dards, regulations, rules and directives must be observed. Relevant and supplied documents must be ob­served, printed out and handed to affected persons.
Ä Before working with the safety relay, completely read and understand the documents applicable to your
task.
In particular, the following national and international legal regulations apply for the start-up, technical in­spections and work with safety relays:
• Machinery directive 2006/42/EC
• Low voltage directive 2014/35/EU
• EMC directive 2014/30/EU
• Use of work equipment directive 89/655/EEC supplemented by directive 95/63EC
• OSHA 1910 Subpart O
• Safety regulations
• Accident-prevention regulations and safety rules
• Ordinance on Industrial Safety and Health and employment protection act
• Product Safety Law (ProdSG and 9. ProdSV)
Safety
NOTICE
For safety-related information you may also contact local authorities (e.g., industrial inspec­torate, employer's liability insurance association, labor inspectorate, occupational safety and health authority).

2.1 Intended use and foreseeable misuse

DANGER
Electrically live systems pose a risk of electric shock!
Ä Make certain that, during all conversions, maintenance work and inspections, the system is
securely shut down and protected against being restarted.
Ä Only have work on the electrical system and electronics performed by a competent person
(see chapter 2.2 "Necessary competencies").

2.1.1 Intended use

WARNING
A running machine may result in serious injury!
Ä Make certain that the safety relay is correctly connected and that the protective function of
the protective device is ensured.
Ä Make certain that, during all conversions, maintenance work and inspections, the system is
securely shut down and protected against being restarted.
Only if the safety relay is correctly connected and correctly started up is the protective function of the pro­tective device ensured. To prevent misuse and resulting dangers, the following must be observed:
• These operating instructions are included in the documentation of the system on which the protective device is mounted and are available to the operating personnel at all times.
• The safety relay is used as a safety monitoring device in combination with one or more safety sensors for safeguarding danger zones or points of operation on machines and systems.
• The safety relay may only be used after it has been selected in accordance with the respectively appli­cable instructions and relevant standards, rules and regulations regarding labor protection and safety at work, and after it has been installed on the machine, connected, commissioned, and checked by a competent person (see chapter 2.2 "Necessary competencies").
• The safety relay must only be connected and commissioned in accordance with its specifications (tech­nical data, environmental conditions, etc.).
Leuze electronic MSI-MD-FBX 7
Page 8
• The acknowledgment unit for unlocking the start/restart interlock must be located outside of the danger zone.
• The entire danger zone must be visible from the installation site of the acknowledgment unit.
• When selecting the safety relay it must be ensured that its safety-related capability meets or exceeds the required performance level PLr ascertained in the risk assessment (see chapter 13 "Technical data").
• The machine or system control must be electrically influenceable so that a switch command sent by the safety relay results in the immediate shutdown of the dangerous movement.
• The construction of the safety relay must not be altered. When manipulating the safety relay, the pro­tective function is no longer guaranteed. Manipulating the safety relay also voids all warranty claims against the manufacturer of the safety relay.
• The safety relay must be inspected regularly by a competent person to ensure proper integration and mounting (see chapter 2.2 "Necessary competencies").
• The safety relay must be exchanged after a maximum of 20years. Repairs or the exchange of wear parts do not extend the mission time.

2.1.2 Foreseeable misuse

Any use other than that defined under the “Approved purpose” or which goes beyond that use is consid­ered improper use.
Alone, the safety relay is not a complete protective device. It is not suitable for use in the following cases:
• Applications in explosive or easily flammable atmospheres
• On machines or systems with long stopping times
Safety

2.2 Necessary competencies

The safety relay may only be configured, installed, connected, commissioned, serviced and tested in its re­spective application by persons who are suitably qualified for the given task. General prerequisites for suit­ably qualified persons:
• They have a suitable technical education.
• They are familiar with the relevant parts of the operating instructions for the safety relay and the operat­ing instructions for the machine.
Task-specific minimum requirements for suitably qualified persons:
Configuration
Specialist knowledge and experience in the selection and use of protective devices on machines as well as the application of technical rules and the locally valid regulations on labor protection, safety at work and safety technology.
Mounting
Specialist knowledge and experience needed for the safe and correct installation and alignment of the safety relay with regard to the respective machine.
Electrical installation
Specialist knowledge and experience needed for the safe and correct electrical connection as well as safe integration of the safety relay in the safety-related control system.
Operation and maintenance
Specialist knowledge and experience needed for the regular inspection and cleaning of the safety relay – following instruction by the person responsible.
Servicing
Specialist knowledge and experience in the mounting, electrical installation and the operation and mainte­nance of the safety relay in accordance with the requirements listed above.
Leuze electronic MSI-MD-FBX 8
Page 9
Commissioning and testing
• Experience and specialist knowledge in the rules and regulations of labor protection, safety at work and safety technology that are necessary for being able to assess the safety of the machine and the use of the safety relay, including experience with and knowledge of the measuring equipment necessary for performing this work.
• In addition, a task related to the subject matter is performed in a timely manner and knowledge is kept up to date through continuous further training ‑ Competent person in terms of the German Betrieb­ssicherheitsverordnung (Ordinance on Industrial Safety and Health) or other national legal regulations.

2.3 Responsibility for safety

Manufacturer and operating company must ensure that the machine and implemented safety relay function properly and that all affected persons are adequately informed and trained.
The type and content of all imparted information must not lead to unsafe actions by users.
The manufacturer of the machine is responsible for:
• Safe machine construction
• Safe implementation of the safety relay, verified by the initial test performed by a competent person (see chapter 2.2 "Necessary competencies")
• Imparting all relevant information to the operating company
• Adhering to all regulations and directives for the safe commissioning of the machine
The operator of the machine is responsible for:
• Instructing the operator
• Maintaining the safe operation of the machine
• Adhering to all regulations and directives for labor protection and safety at work
• Periodic testing by a competent person (see chapter 2.2 "Necessary competencies")
Safety

2.4 Disclaimer

LeuzeelectronicGmbH+Co.KG is not liable in the following cases:
• Safety relay is not used as intended.
• Safety notices are not adhered to.
• Reasonably foreseeable misuse is not taken into account.
• Mounting and electrical connection are not properly performed.
• Proper function is not tested (see chapter 9 "Testing").
• Changes (e.g., constructional) are made to the safety relay.
Leuze electronic MSI-MD-FBX 9
Page 10

3 Device description

The MSI-MD-FB muting controller is used as a safety-relevant link between an active opto-electronic pro­tective device (AOPD) and the machine control. The muting controller enables muting through intentional and temporary suppression of the protective function of the safety sensor, e.g., if objects are to be trans­ported through the protective field.
The muting controller is mounted on machine parts or on a device column.
Safety sensors and muting sensors
The muting controller supplies the safety sensor and the muting sensors with 24V supply voltage.
The following safety sensors from Leuze electronic are released for connection to the muting controller:
• Safety light barriers of the MLD series
• Safety light curtains of the MLC series
NOTICE
The MSI-MD-FB muting controller is only released for the connection of the safety sensors from Leuze electronic, e.g., MLC510 or MLD510.
The following muting sensors from Leuze electronic are released for connection to the muting controller:
• All common series: 3 series, 5 series, 8 series, 25 series, 46 series, 49 series, 96 series
Device description
Degree of protection and standards
The muting controller is designed in degree of protection IP67
The muting controller meets the following standards:
• Performance Level PLe in accordance with ENISO13849
• Safety Integrity Level SIL3 in accordance with IEC61508
Leuze electronic MSI-MD-FBX 10
Page 11

3.1 Device construction

2
4
5
7
8
6
3
1
Device description
1 Mounting eyes for M4 screws
2 Cover for the DIP switch blocks for configuring the muting function and the Micro USB connection for reading
out diagnostics.
3 7‑segment display
4 Connection for the safety sensor
5 Connection for acknowledgment unit
6 Connections for muting sensors
7 Connection for external muting indicator
8 Connection to the machine interface (OSSDs and supply voltage)
Fig.3.1: Device construction of the muting controller
Leuze electronic MSI-MD-FBX 11
Page 12

3.2 Display elements

1
3
2
7
4
9
11
10
5
8
11
6
The muting controller is equipped with the following display elements:
• LED indicators for the status of the assigned input signals
Device description
1 PWR LED
2 OSSD LED
3 RI LED
4 ERR LED
5 SC LED (1)
6 SC LED (2)
7 LC/LG LED
8 ML LED
9 RES LED (1)
10 RES LED (1)
11 LED MS1…MS4
Leuze electronic MSI-MD-FBX 12
Page 13
Fig.3.2: LED indicators of the muting controller
LED Color Description
1 PWR Green Power (PWR)
2 OSSD Red OSSDs in the OFF state
Green OSSDs in the ON state
3 RI Yellow Restart active
Safety sensor on
The system is waiting for actuation of the acknowledgment unit
4 ERR Red Fault
5 SC Green Muting sensor alternative active
6 White Muting signal from the machine interface active
7 LC/LG OFF OSSDs of the safety sensor in the OFF state
Green OSSDs of the safety sensor in the ON state
8 ML Blue Muting indicators:
• OFF: no muting active
• Continuous light: muting active; safety sensor is bypassed by means of muting
• Flashing: muting error; e.g., timeout
Device description
9 RES Yellow Acknowledgment unit pressed (reset signal)
10 Red Ready for reset (ReadyForReset signal)
11 MS1…MS4 Green Muting sensor 1…4 active

3.3 Connection technology

NOTICE
Sockets and connectors that are not connected are to be covered with end caps!
Ä Cover unconnected sockets and connectors with end caps.
The system is waiting for actuation of the acknowledgment unit
Leuze electronic MSI-MD-FBX 13
Page 14

4 Functions

MS2
MS1
1
2
3
By means of muting, the protective function of the safety sensor can be temporarily and properly sup­pressed, e.g. if objects are to be transported through the protective field. The OSSDs of the muting con­troller remain in the ON state in spite of interruption of one or more beams of the safety sensor.
Muting mode
The muting controller supports the following muting mode:
• Timing controlled 2-sensor muting (see chapter 4.1 "Timing controlled 2-sensor muting")
Muting timeout
Configurable time limit for the muting function (muting timeout):
• 20seconds
• 2minutes
• 10minutes
• 100hours
Muting timeout is set via the DIP switch blocks (see chapter 8 "Starting up the device - Configuration").
Muting sensors
Muting is initiated automatically and via mutually independent muting signals by muting sensors.
• Photoelectric sensors or scanning sensors can be connected to the muting controller as muting sen­sors (see chapter 14 "Order guide and accessories").
• The state of a muting sensor is transferred on pin4 of the connection on the muting controller.
• The muting signals of the muting sensors are debounced:
• Pickup delay: 60ms
• Slow release: 300ms
Functions
NOTICE
Do not use muting signal MS1 via machine interface and local socket simultaneously!
Ä If muting signal MS1 is used via the machine interface, MS1 must not be used simultane-
ously on the local socket.

4.1 Timing controlled 2-sensor muting

Muting is initiated automatically and via two mutually independent muting signals. These signals must be active during the entire duration of the muting operation. Muting may not be initiated by a single sensor sig­nal, nor may it be fully initiated by software signals.
The protective function of the entire protective field is deactivated during timing controlled muting.
1 Danger zone
Leuze electronic MSI-MD-FBX 14
2 Receiver of the safety sensor
3 Transmitter of the safety sensor
MS1 Muting sensor1
MS2 Muting sensor2
Fig.4.1: Arrangement of muting sensors for timing controlled 2-sensor muting in an exit application
Page 15
Functions
MS1
MS2
< 4s
< 0,3 s
MUTE
OSSD
PFF
< 4s
> 4s
MS1 Muting signal1
MS2 Muting signal2
PFF Protective field free
MUTE Bridging through muting
OSSD OSSD status
Fig.4.2: Timing controlled muting - timing
The material can move in both directions. Often, an arrangement consisting of crossed beams from retro­reflective photoelectric sensors is used (see chapter 6.2 "Arrangement of the muting sensors").
Timing controlled muting is used in the following cases:
• Moving-in applications: diffuse sensors in the danger zone detect the muting object through the protec­tive field. The scanning range must be set to a sufficiently small value (see chapter 6 "Mounting").
• Exit applications: a photoelectric sensor in the danger zone works diagonally to the transport direction together with a simultaneously activated machine interface signal, which derives from the drive of the transport equipment, for instance (see chapter 6 "Mounting").
DANGER
Risk of death if installation is not performed correctly!
Ä Follow the instructions for the correct arrangement of the muting sensors (see chapter 6.2
"Arrangement of the muting sensors").

4.1.1 Timing controlled 2-sensor muting with Muting-enable

With the muting enable function, muting is enabled or disabled via an external muting enable signal. The muting enable function is activated and deactivated via the DIP switch blocks (Starting up the device - Con­figuration).
• If the muting enable signal is applied, a valid muting sequence initiates muting.
The muting enable signal must be applied at least 60ms before muting is initiated.
The muting enable signal must not be applied for more than 100hours.
• If the muting enable signal is not applied, no muting is possible, even with a valid muting sequence.

4.2 Overriding and muting restart

Following malfunctions or operationally related interruptions (e.g. power failure, violation of the simultaneity condition during timing controlled 2-sensor muting on activation of the muting sensors), the system can be manually reset with the acknowledgment unit and overridden.
• Muting override must only be initiated if at least one muting sensor is activated and the OSSDs of the muting controller are switched off.
• Muting override is maintained only if at least one muting sensor is activated.
• The muting controller switches on its OSSDs when muting override is activated.
• For muting override or muting restart, the maximum muting timeout time is 10minutes.
Leuze electronic MSI-MD-FBX 15
Page 16
WARNING
Unauthorized muting restart may result in serious injury!
Ä A qualified person (see chapter 2.2 "Necessary competencies") must observe the procedure
exactly.
Ä Make certain that the danger zone can be viewed from the acknowledgment unit and that
the entire process can be observed by the responsible person.
Ä Before and during the muting restart, ensure that there are no people in the danger zone.
NOTICE
If the safety sensor or the muting controller responds with an error message, perform an error reset (see chapter 4.3 "Error reset").
Ä Press and release the acknowledgment unit within 0.2 to 4s. Ä Press the acknowledgment unit again and keep the acknowledgment unit pressed down. ð The muting controller switches on.
Both muting signals are activated:
The muting controller switches to muting mode.
Functions
A muting signal is activated:
Muting is initiated when the acknowledgment unit is released. The second muting signal must be activated within a maximum of 4s in order to continue muting. If the second muting signal is not activated within this time, muting is ended.
No muting signal is activated:
Muting is ended immediately even if the acknowledgment unit is not released.
Muting controller with muting enable; a muting signal is activated:
Muting is initiated when the acknowledgment unit is released. The second muting signal must be activated within a maximum of 4s in order to continue muting. If the second muting signal is not activated within this time, muting is ended.
Muting controller with muting enable; without extension of the muting timeout:
Overriding is only possible with acknowledgment unit permanently pressed down.

4.3 Error reset

If an internal or external error is detected by the safety sensor or the muting controller, the muting controller switches to the interlock state.
To reset the safety circuit to the initial state, reset the muting controller via the reset signal.
• The reset signal can be set via the connected acknowledgment unit or via a component in the machine interface.
• When overriding, the reset signal may only come from one source, i.e., either from the connection socket of the acknowledgment unit or from the RES signal of the machine interface.
• Duration of the reset signal: 0.2s to 4s
Manual error reset
Reset signal via the connected acknowledgment unit
Ä Press and release the acknowledgment unit within 0.2 to 4s.
Leuze electronic MSI-MD-FBX 16
Page 17

4.4 Restart

Following a violation of the protective field, the OSSDs are re-enabled via the reset signal.
• The restart can be started manually via the connected acknowledgment unit or via a component in the control (Starting up the device - Configuration).
• The reset signal can be set via the connected acknowledgment unit or via a component in the machine interface.
• Duration of the reset signal: 0.2s to 4s

4.5 Acknowledging/resetting

The ReadyForReset signal signals via the RES LED that the system is waiting for actuation of the acknowl­edgment unit/reset button.
• The RES LED illuminates red if the OSSDs of the safety sensor are switched on and the OSSDs of the muting controller are switched off.
• The RES LED flashes red if the system is expecting a muting restart, depending on the status of the muting sensors. The OSSDs of the safety sensor must be switched off.
• The RES LED flashes red if a muting error occurs.
• If a muting error occurs together with a protected field violation, the OSSDs are switched off when muting is terminated.
• If a muting error occurs in a free protective field, the OSSDs remain switched on.
Functions
Leuze electronic MSI-MD-FBX 17
Page 18

5 Applications

3
2
1
4

5.1 Access guarding with timing controlled muting

Applications
1 Safety sensor
2 Muting controller
3 Muting sensors
4 Acknowledgment unit
Fig.5.1: Access guarding with timing controlled muting for an application with a pallet wrapping machine
Leuze electronic MSI-MD-FBX 18
Page 19

6 Mounting

1
2
3
Ä Mount the muting sensors (see chapter 6.2 "Arrangement of the muting sensors"). Ä Mount the muting controller (see chapter 6.1 "Mounting the muting controller"). Ä Make the electrical connection of the muting controller (see chapter 7 "Electrical connection").
NOTICE
Ä When mounting and aligning the safety sensor, observe the respective operating instruc-
tions.

6.1 Mounting the muting controller

You can mount the muting controller as follows:
• Mount in the UDC device column of the receiver of the safety sensor
• Mount on the UDC device column of the receiver of the safety sensor
• Mount on the system via M4 fastening holes

6.1.1 Mounting in the UDC device column

Mount the muting controller in the UDC device column of the receiver of the safety sensor, e.g., below the receiver. The necessary mounting bracket is available as an accessory (see chapter 14 "Order guide and accessories").
Mounting
1 Mounting bracket BT-MSI-MD-FB-L
2 Muting controller
3 UDC device column
Fig.6.1: Mounting in the UDC device column
Leuze electronic MSI-MD-FBX 19
Page 20

6.1.2 Mounting on the UDC device column

1
2
3
Mount the muting controller on the side or on the rear of the UDC device column of the receiver of the safety sensor. The required mounting plate is available as an accessory (see chapter 14 "Order guide and accessories").
Mounting
1 Mounting plate BT-MSI-MD-FB
2 Muting controller
3 UDC device column
Fig.6.2: Mounting on side/rear on the UDC device column

6.1.3 Mounting on the system

Mount the muting controller on the system via three mounting eyes for M4 screws.

6.2 Arrangement of the muting sensors

Muting sensors detect material and supply the signals necessary for muting. Standard IEC/TS62046 pro­vides basic information on arranging the muting sensors. This information must be observed when mount­ing the muting sensors.
WARNING
Improper installation may result in serious injury!
If the distance between transmitter and receiver is larger than the width of the object so that gaps of more than 180mm are created, suitable measures, e.g. through additional guarding, must be taken to stop the dangerous movement before persons enter the area.
Ä Make sure that no persons can reach the danger zone alongside the transport material dur-
ing muting.
Ä Make sure that muting is only temporarily activated and only as long as the access to the
danger zone is blocked by the transport material.
NOTICE
If accessible distances exist between the transport material and the safety sensor, PS mats or wicket gates monitored with safety switches have been tried, tested and proven as additional safeguards. Such measures prevent injuries caused, for example, by crushing in the access area.
Leuze electronic MSI-MD-FBX 20
Page 21

6.2.1 Basic information

Before you begin with the selection and mounting of the muting sensors (Selecting optoelectronic muting sensors), please note the following:
• Muting must be triggered by two independent muting signals and must not be fully dependent on soft­ware signals, e.g. from a PLC.
• Always mount muting sensors so that the minimum distance to the protective device is maintained (see chapter 6.2.3 "Minimum distance for optoelectronic muting sensors").
• Always mount the muting sensors so that the material is detected and not the transport device, e.g. the pallet.
• Material must be allowed to pass through unimpeded.
WARNING
Unintentionally triggered muting may result in serious injury!
Ä Mount the muting sensors in such a way that muting cannot be unintentionally triggered by a
person, e.g. by simultaneously activating the muting sensors with a foot.
Ä Mount the muting indicator so that it is always visible from all sides.

6.2.2 Selecting optoelectronic muting sensors

Muting sensors detect material and supply the signals necessary for muting. If muting conditions are ful­filled, the safety sensor can use the signals from the muting sensors to bridge the protective function. The signals can be generated by e.g. optoelectronic sensors from Leuze electronic.
Any transducers which output a +24VDC switching signal when detecting the permitted transport material can still be used as muting sensors:
• Photoelectric sensors (transmitter/receiver or retro-reflective photoelectric sensors) whose beam paths intersect behind the protective field within the danger zone.
• Diffuse sensors that scan along the side of the transport material (make sure scanning range is set cor­rectly).
• A photoelectric sensor and an acknowledgment signal from the conveyor drive or a PLC signal, pro­vided they are activated independently of each other and fulfill the simultaneity conditions.
• Switching signals from induction loops that are activated e.g. by a high-lift truck.
• Roller conveyor switches which are activated by the transport material and arranged so that they can­not be simultaneously actuated by a person.
Ä When arranging the muting sensors, take the filter times of the signal inputs into account (switch on fil-
ter time approx.60ms, switch-off filter times approx.300ms).
Mounting
NOTICE
When using muting sensors with push-pull output, a time difference of at least 20ms is neces­sary for the muting signals.

6.2.3 Minimum distance for optoelectronic muting sensors

The minimum distance is the distance between the protective field of the AOPD and the detection points of the muting sensor light beams. This distance must be maintained when mounting the muting sensors to prevent the pallet or material from reaching the protective field before the muting signals can bridge the protective function of the AOPD. The minimum distance is dependent on the time needed by the system to process the muting signals (approx. 120ms).
Ä Calculate the minimum distance depending on the application case for the timing controlled 2-sensor
muting (see chapter 6.2.4 "Arrangement of the muting sensors for timing controlled 2-sensor muting").
Ä When arranging the muting sensors, make certain that the calculated minimum distance to the protec-
tive field is maintained.
Leuze electronic MSI-MD-FBX 21
Page 22

6.2.4 Arrangement of the muting sensors for timing controlled 2-sensor muting

a
b
MS2
MS1
1
2
3
4
a
b
S
MS2
MS1
1
2
3
4
d
When doing so, both the MS1 and MS2 sensors must be arranged so that they can be activated simultane­ously within 4s by the transport material but cannot be simultaneously activated by a person within this time. Arrangements with crossed beams are often used. The intersection point is located here within the danger zone. This prevents muting from being triggered unintentionally. With this arrangement, an object can be transported through the protective field in both directions.
NOTICE
Muting accessories from Leuze electronic, for example muting sensor sets and matching device columns, facilitate the installation of muting applications significantly.
Mounting
1 Danger zone
2 Receiver
3 Transmitter
MS1 Muting sensor1
MS2 Muting sensor2
S Minimum distance between the protective field of the AOPD and the detection points of the muting-sensor
light beams
a,b Distance between muting object and other fixed edges or objects (<200mm)
d Distance from the intersection point of the muting-sensor light beams to the protective-field plane
(<50mm)
Fig.6.3: Typical arrangement of the muting sensors for timing controlled 2-sensor muting (example acc. to
IECTS62046)
With timing controlled 2-sensor muting, the beams from the muting sensors should intersect behind the protective field of the safety sensor, i.e. within the danger zone, to prevent muting from being triggered un­intentionally.
Distances a and b between fixed edges and the muting object (e.g. transport material) must be such that a person cannot enter through these openings undetected while the pallet passes through the muting zone. However, if it is assumed that persons are located here, the risk of crushing must be prevented, e.g. with wicket gates, which are integrated electrically into the safety circuit.
Leuze electronic MSI-MD-FBX 22
Page 23
Mounting
MS2
MS1
1
2
3
4
a
b
Minimum distance S
S [mm] = Minimum distance between the protective field of the AOPD and the detection points of the mut-
ing-sensor light beams
v [m/s] = Speed of the material
Distanced should be as small as practical
d [mm] = Distance from the intersection point of the muting-sensor light beams to the protective-field
plane<200mm
Arrangement of diffuse sensors
An additional option for arranging the muting sensors is shown in the following figure. The diffuse sensors are arranged and set within the danger zone so that their scanning points detect a valid, approaching mut­ing object within the danger zone, but a person is not able to reach both scanning points simultaneously.
1 Danger zone
2 Receiver
3 Transmitter
MS1 Muting sensor1
MS2 Muting sensor2
a,b Distance between muting object and other fixed edges or objects (<200mm)
Fig.6.4: Muting with two diffuse sensors
Leuze electronic MSI-MD-FBX 23
Page 24
Height of the muting-sensor light beams
H
MS1
MS2
The two light beams of the muting sensors must have a minimum height ofH.
Mounting
Fig.6.5: Arrangement of the muting sensors with respect to height
Ä Mount the muting sensors so that the intersection point of their light beams is at the same height or
higher than the lowest light beam of the safety sensor.
ð This prevents—or hinders—manipulation with the feet since the protective field is interrupted before the
muting-sensor light beam.
NOTICE
To increase safety and make manipulation more difficult, MS1 and MS2 should, if possible, be mounted at different heights (i.e. no point-shaped intersection of the light beams).
Leuze electronic MSI-MD-FBX 24
Page 25

7 Electrical connection

WARNING
Faulty electrical connection or improper function selection may result in serious injury!
Ä Only allow qualified persons (see chapter 2.2 "Necessary competencies") to perform the
electrical connection.
Ä For access guarding, activate the start/restart interlock and make certain that it cannot be
unlocked from within the danger zone.
Ä Select the safety-relevant functions for the safety sensor. Observe the operating instructions
for the safety sensor.
Ä Always loop both safety-related switching outputs OSSD1 and OSSD2 of the muting con-
troller into the work circuit of the machine.
WARNING
Muting faults may result in serious injury!
Ä Connect the muting signals so that they are separated and protected and a short circuit be-
tween the cables is impossible.
Electrical connection
NOTICE
Laying cables!
Ä Lay all connection cables and signal lines within the electrical installation space or perma-
nently in cable ducts.
Ä Lay the cables and lines so that they are protected against external damages. Ä For further information: see EN ISO 13849-2, Table D.4.
NOTICE
Protective Extra Low Voltage (PELV)
The muting controller is designed in accordance with protection classIII for supply with PELV (Protective Extra-Low Voltage).
NOTICE
Use in the USA and Canada
For use in the USA and Canada, use is only permitted in Class 2 circuits in accordance with the NEC (National Electric Code).

7.1 Connecting the muting controller

The muting controller is equipped with the following connections:
• One connection for the OSSDs of the safety sensor
M12 socket, 5-pin, A-coded
• A connection for the machine interface
M12 plug, 8-pin, A-coded
• Four connections for muting sensors 1…4
M12 socket, 5-pin, A-coded
• One connection for the reset button/acknowledgment unit
M12 socket, 5-pin, A-coded
• One connection for an external muting indicator
M12 socket, 5-pin, A-coded
• One service USB connection for reading out diagnostics
USB port of type Micro-B
Leuze electronic MSI-MD-FBX 25
Page 26
Electrical connection
2
5
7
6
4
8
3
1
1 Mounting eyes for M4 screws
2 Cover for the DIP switch blocks for configuring the muting function and the Micro USB connection for reading
out diagnostics.
3 7‑segment display
4 Connection to the machine interface (OSSDs and supply voltage)
5 Connection for the safety sensor
6 Connection for external muting indicator
7 Connection for acknowledgment unit
8 Connections for muting sensors
Fig.7.1: Muting controller connections
Ä Connect the muting controller to the machine interface (see chapter 7.2 "Pin assignment of the ma-
chine interface").
Ä Connect the safety sensor to the muting controller (see chapter 7.3 "Pin assignment of safety sensor"). Ä Connect the acknowledgment unit to the muting controller (see chapter 7.4 "Pin assignment of the ac-
knowledgment unit").
Ä If necessary, connect the external muting indicator to the muting controller (see chapter 7.5 "Pin as-
signment of muting indicator").
Ä Connect the muting sensors to the muting controller (see chapter 7.6 "Pin assignment of muting sen-
sors").
Leuze electronic MSI-MD-FBX 26
Page 27

7.2 Pin assignment of the machine interface

FE
1
2
3
4
5
6
7
8
2
3
1
4
5
FE
SC: M12 plug, 8-pin, A-coded
Tab.7.1: Pin assignment of the machine interface
Pin Color Signal IN/OUT Description
1 White Reset IN Reset signal from the machine interface
2 Brown +24V Supply voltage
3 Green MS1 IN +24V if muting 'good' detected
4 Yellow Error OUT Fault in the muting controller:
Electrical connection
Muting signal from the machine interface
• +24V: fault in the muting controller
• 0V: no fault; muting controller in operation
5 Gray OSSD1 OUT +24V if OSSD1 of the muting controller is active
6 Pink OSSD2 OUT +24V if OSSD2 of the muting controller is active
7 Blue 0V Supply voltage
8 Red M-EN/TO IN Signal muting enable/muting timeout
FE Housing of the M12 plug

7.3 Pin assignment of safety sensor

LC/LG: M12 socket, 5-pin, A-coded
Tab.7.2: Pin assignment of safety sensor
Pin Color Signal IN/OUT Description
1 Brown +24V Supply voltage for safety sensor, short-circuit proof
2 White OSSD1 IN OSSD1 of the safety sensor; +24V if OSSD1 is active
Functional earth/shield
3 Blue 0V Supply voltage for safety sensor
4 Black OSSD2 IN OSSD2 of the safety sensor; +24V if OSSD2 is active
5 Gray FE FE - functional earth, shield
FE Housing of the M12 socket
FE - functional earth, shield
Leuze electronic MSI-MD-FBX 27
Page 28

7.4 Pin assignment of the acknowledgment unit

2
3
1
4
5
FE
2
3
1
4
5
FE
RES: M12 socket, 5-pin, A-coded
Tab.7.3: Pin assignment of the acknowledgment unit
Pin Color Signal IN/OUT Description
1 Brown +24V Supply voltage
2 White ReadyForReset OUT LED lighting for the acknowledgment unit
3 Blue GND Supply voltage
4 Black Reset IN Switching signal reset
5 Gray n.c. This pin is not contacted at the device
Electrical connection
Signal indicating that the system is waiting for actu­ation of the acknowledgment unit.
FE Housing of the M12 socket

7.5 Pin assignment of muting indicator

ML: M12 socket, 5-pin, A-coded
Tab.7.4: Pin assignment of muting indicator
Pin Color Signal IN/OUT Description
1 Brown +24V Supply voltage
2 White Muting OUT +24V if muting active
3 Blue GND Supply voltage
4 Black Muting OUT +24V if muting active
5 Gray n.c. This pin is not contacted at the device
FE Housing of the M12 plug
FE - functional earth, shield
Functional earth/shield
Leuze electronic MSI-MD-FBX 28
Page 29

7.6 Pin assignment of muting sensors

2
3
1
4
5
FE
S
E
1 3 4
-MS1
1
-MS2
1
-MS1
S
E
1 3 4
-MS2
2
2334455
1
-MS4
1
-MS3
22334
455
1
-ML
1
-RES
-S1/H1
-H1
2
2334455
1
-SC
1
-LC/LG
2
2334455
6 7 8
Schaltsignal
BN
SH
OSSD2
VIN2
5
GND
electronic
BK
RD
A2
Muting aktiv
V42+V42+
2 4
WH
2
Schaltsignal
VIN2
n.c.
electronic
BU
FE
VIN1
BU
PE
OSSD1
OSSD2
GND
GY
7
-W3
PK5BU
1
BN
SH
A3
WH
YE
n.c.
GN
3
BK
MLC/MLD500
+24V
PE
OSSD OSSD
0V
MLC/MLD510
FE
ON
n.c.
GND
Reset
ReadyForReset
1
n.c.
Leuze
electronicLeuze
+24V
0V
GND
OSSD1
Schaltsignal
0V
Sensor 1 in
4
2
ON
teseRV42+
M EN/TO
OSSD2
MSI-MD-FBX
n.c.
+24V
-W1
+24V
+24V
-W2
-W2
GND
+24V
Störung
n.c.
n.c.
-W1
n.c.
n.c.
PE
Schaltsignal
OSSD1
5
n.c.
0V
BN
3
RNG
1
GND
Muting aktiv
0V
SH
GND
6
OFF
PE
4
n.c.
+24V
VIN1
3
FE
OFF
8
Leuze
A1
MS1, MS2, MS3, MS4: Four connections for muting sensors MS1…MS4; M12 socket, 5-pin, A-coded
Tab.7.5: Pin assignment of muting sensor
Pin Color Signal IN/OUT Description
1 Brown +24V Supply voltage
2 White n.c. This pin is not contacted at the device
3 Blue GND Supply voltage
4 Black Muting IN +24V if muting 'good' detected
5 Gray n.c. This pin is not contacted at the device
FE Housing of the M12 socket
Electrical connection
FE - functional earth, shield

7.7 Circuit diagram examples

7.7.1 Timing controlled 2-sensor muting

Fig.7.2: Circuit diagram example: timing controlled 2-sensor muting
• Muting controller MSI-MSI-MD-FB and safety sensor MLC510 or MLD510
Leuze electronic MSI-MD-FBX 29
• Muting timeout: 10minutes
Page 30

8 Starting up the device - Configuration

8.1 Overview

The function of the muting controller is set via two DIP switch blocks, each of which has eight switches. The DIP switch blocks are located behind a cover in the housing of the muting controller and are not accessible in normal operation.
NOTICE
This muting controller can only be operated in operating mode 7 (see chapter 8.2 "Setting the operating mode").
Parameter
You can set the following parameters for the function of the muting controller:
DIP switch Function Settings
1 Number of the muting sensors 2-sensor muting
2 Muting mode Timing controlled muting
Starting up the device - Configuration
4-sensor muting (not permissible)
Sequence controlled muting (not permissible)
3 EDM With EDM
Without EDM
4 Restart Automatically via machine interface signal
Manually via acknowledgment unit
5 Muting-enable With muting-enable
Without muting-enable
6 Muting timeout With muting-timeout extension
Without muting-timeout extension
Procedure
Ä Disconnect the muting controller from voltage. Ä Remove the cover from the housing of the muting controller (four screws; Operational controls). Ä Set the operating mode of the muting controller via the DIP switch blocks (see chapter 8.2 "Setting the
operating mode").
Ä Remount the cover on the housing on the muting controller.
ð Tighten the screws with a torque wrench. Torque: 0.6…0.8Nm Ä Connect the muting controller to the voltage supply Ä Restart the muting controller.
ð After the device is started, the 7-segment display shows the set operating mode.
NOTICE
Error when configuring the muting controller in process mode!
If the switch position of the DIP switch blocks is changed in process mode, an error is triggered and the OSSDs switch off.
Ä Only set the configuration of the muting controller while the device is in a voltage-free state.
Leuze electronic MSI-MD-FBX 30
Page 31

8.2 Setting the operating mode

1
2
1 2 3 4 5 6 7 8
A
B
1
1
2
2
The muting controller is equipped with two DIP switch blocks, each with eight switches for setting the con­figuration.
1 DIP switch blocks
2 Service USB connection
Fig.8.1: Muting controller without cover
Switch position of the DIP switch blocks
NOTICE
Error for different switch positions in the DIP switch blocks!
An error is triggered for different switch positions in the DIP switch blocks and the OSSDs switch off.
Ä When configuring, make certain that the switch position is identical in both DIP switch
blocks.
Starting up the device - Configuration
A DIP switch block A
B DIP switch block B
1 Switch position ON
2 Switch position OFF
Fig.8.2: Example: switch position of the DIP switch blocks
Tab.8.1: Assignment of the DIP switches
DIP
Function ON OFF
switch
1 Number of the muting sen-
sors
2 Muting mode Sequence controlled muting
4-sensor muting
(not permissible)
2-sensor muting
Timing controlled muting
(not permissible)
3 EDM With EDM Without EDM
4 Restart Manual restart Automatic restart
Leuze electronic MSI-MD-FBX 31
5 Muting-enable With muting-enable Without muting-enable
6 Muting timeout With muting-timeout exten-
sion
Without muting-timeout exten­sion
Page 32
Starting up the device - Configuration
DIP
Function ON OFF
switch
7/8 Muting timeout OFF/OFF: 20seconds
OFF/ON: 2minutes
ON/OFF: 10minutes
ON/ON: 100hours
Setting the operating mode
The following table lists the permissible operating modes that can be set via the DIP switch blocks.
After the device is started, the 7-segment display of the muting controller shows the set operating mode.
NOTICE
This muting controller can only be operated in operating mode 7.
NOTICE
Error in event of impermissible setting of DIP switches!
If a DIP switch configuration is set that does not correspond to that of a permissible operating mode, an operating mode error is triggered and the OSSDs switch off.
Ä Only set one of the DIP-switch configurations listed in the operating mode table.
NOTICE
Restart interlock for access guarding!
For access guarding, a restart interlock is required.
Ä If the automatic restart interlock is configured in the muting controller, you must carry out the
restart interlock, e.g. via the machine interface.
Tab.8.2: Operating modes
DIP
1 2 3 4 5 6
switch
Function Number of
muting sen-
sors
Operating
mode
7 2-sensor Timing con-
Muting mode EDM Restart Muting-en-
able
Without Manual With Without
trolled
Muting-time-
out exten-
sion
Leuze electronic MSI-MD-FBX 32
Page 33

9 Testing

WARNING
A running machine may result in serious injury!
Ä Make certain that, during all conversions, maintenance work and inspections, the system is
securely shut down and protected against being restarted.
NOTICE
Ä The safety relays must be exchanged after a maximum of 20years. Ä Always exchange the entire safety relay. Ä Observe any nationally applicable regulations regarding the tests. Ä Document all tests in a comprehensible manner.

9.1 Before the initial start-up and following modifications

WARNING
Unpredictable machine behavior during initial start-up may result in serious injury!
Ä Make certain that there are no people in the danger zone.
Testing
Ä Before they begin work, train the operators on their respective tasks. The training is the responsibility of
the operating company.
Ä Attach notes regarding daily testing in the respective national language of the operator on the machine
in a highly visible location, e.g. by printing out the corresponding chapter (see chapter 9.3 "Periodically by the operator").
Ä Test the electrical function and installation according to this document.
Acc. to IEC/TS62046 and national regulations (e.g. EU directive2009/104/EC), tests are to be performed by qualified persons (see chapter 2.2 "Necessary competencies") in the following situations:
• Prior to initial commissioning
• Following modifications to the machine
• After longer machine downtime
• Following retrofitting or new configuration of the machine
Ä Before preparing, check the most important criteria for the optoelectronic safety device and the safety
relay. This check does not replace testing by qualified persons (see chapter 2.2 "Necessary competen­cies").
ð Not until proper function of the optoelectronic safety device and the safety relay is ascertained may
they be integrated in the control circuit of the system.

9.2 Regularly by qualified persons

The reliable interaction of safety sensor, safety relay and machine must be regularly tested by qualified per­sons (see chapter 2.2 "Necessary competencies") in order to detect changes to the machine or impermissi­ble tampering.
Acc. to IEC/TS 62046 and national regulations (e.g., EU directive 2009/104/EC), tests of elements which are subject to wear must be performed by qualified persons (see chapter 2.2 "Necessary competencies") at regular intervals. Testing intervals may be regulated by nationally applicable regulations (recommendation acc. to IEC/TS62046: 6months).
Ä Only allow testing to be performed by qualified persons (see chapter 2.2 "Necessary competencies"). Ä Observe the nationally applicable regulations and the time periods specified therein.
Leuze electronic MSI-MD-FBX 33
Page 34

9.3 Periodically by the operator

The function of the safety relay must be checked depending on the given risk according to the following checklist so that damage or prohibited tampering can be detected.
Depending on the risk assessment, the test cycle must be defined by the integrator or operating company (e.g., daily, on shift changes, ...) or is specified by national regulations or regulations of the employer's lia­bility insurance association and may be dependent on the machine type.
Due to complex machines and processes, it may be necessary under certain circumstances to check some points at longer time intervals. Observe the classification in “Test at least” and “Test when possible”.
NOTICE
For larger distances between transmitter and receiver of the safety sensor and when using de­flecting mirrors, a second person may be necessary.
WARNING
Unpredictable machine behavior during the test may result in serious injury!
Ä Make certain that there are no people in the danger zone. Ä Before they begin work, train the operators on their respective tasks and provide suitable
test objects and an appropriate test instruction.
Testing

9.3.1 Checklist – periodically by the operator

NOTICE
Ä If you answer one of the items on the following check list with no, the machine must no
longer be operated.
When possible, test during running operation: Yes No
Protective device with approach function: during machine operation, the protective field is interrupted with the test object – are the obviously dangerous machine parts stopped with­out noticeable delay?
Protective device with presence detection: the protective field is interrupted with the test object – does this prevent operation of the obviously dangerous machine parts?
Leuze electronic MSI-MD-FBX 34
Page 35

10 Care, maintenance and disposal

Cleaning
Ä Clean the device with a soft cloth as needed; use a cleaning agent (commercially available glass
cleaner) if necessary.
NOTICE
Do not use aggressive cleaning agents!
Ä Do not use aggressive cleaning agents such as thinner or acetone for cleaning the device.
Use of improper cleaning agents can damage the 7-segment display.
Maintenance
The device does not normally require any maintenance by the operator.
Repairs to the device must only be performed by the manufacturer.
Ä For repairs, contact your responsible Leuzeelectronic subsidiary or Leuzeelectronic customer service
(see chapter 12 "Service and support").
Disposing
Ä For disposal observe the applicable national regulations regarding electronic components.
Care, maintenance and disposal
Leuze electronic MSI-MD-FBX 35
Page 36

11 Diagnostics and troubleshooting

11.1 What to do in case of failure?

After switching on the muting controller, the display elements (see chapter 3.2 "Display elements") assist in checking the correct functionality and in fault-finding.
In case of failure, you can read a message from the 7-segment display. With the error message you can determine the cause of the error and initiate measures to rectify it.
NOTICE
If the light curtain responds with an error display, you will often be able to eliminate the cause yourself!
Ä Switch off the machine and leave it switched off. Ä Analyze and eliminate the cause of the fault using the following table. Ä If you are unable to rectify the fault, contact the Leuzeelectronic branch responsible for you
or call the Leuze electronic customer service (see chapter 12 "Service and support").
With the SensorStudio diagnostics software, you can create a service file that you can send to Leuze elec­tronic customer service in the event of service requests (Diagnostics software SensorStudio). The service file contains all available information on the muting controller, as well as configuration and settings.
Diagnostics and troubleshooting

11.2 Error messages 7-segment display

User messages/notes and error messages are indicated by the alternating display of a letter and a two-digit number.
Tab.11.1: Messages of the 7-segment display (F:internal device error, E:external error, U:usage info during appli-
cation errors)
Error Cause/description Remedies and measures Behavior of the
F[No. 0-255] Internal error In the event of an unsuccessful
OFF Very high overvoltage (±40V) Supply the device with the correct
E01 Cross connection between
OSSD1 and OSSD2
E02 Overload on OSSD1 Check the wiring or exchange the
E03 Overload on OSSD2 Check the wiring or exchange the
E04 High-impedance short circuit to
VCC OSSD1
restart, contact customer service.
voltage.
Check the wiring between OSSD1 and OSSD2.
connected component (reducing the load).
connected component (reducing the load).
Check the wiring. Exchange the cable, if applicable.
muting controller
Automatic reset
Automatic reset
Automatic reset
Automatic reset
E05 High-impedance short circuit to
VCC OSSD2
E06 Short circuit against GND at
OSSD1
E07 Short circuit against +24V at
OSSD1
E08 Short circuit against GND at
OSSD2
E09 Short circuit against +24V at
OSSD2
Leuze electronic MSI-MD-FBX 36
Check the wiring. Exchange the cable, if applicable.
Check the wiring. Exchange the cable, if applicable.
Check the wiring. Exchange the cable, if applicable.
Check the wiring. Exchange the cable, if applicable.
Check the wiring. Exchange the cable, if applicable.
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Page 37
Diagnostics and troubleshooting
Error Cause/description Remedies and measures Behavior of the
muting controller
E10, E11 OSSD error, source unknown Check the wiring. Exchange the
cable and the receiver if neces­sary.
E14 Undervoltage (<+16V) Supply the device with the correct
voltage.
E15 Overvoltage (>+31V) Supply the device with the correct
voltage.
E16 Overvoltage (>+40V) Supply the device with the correct
voltage.
E18 Ambient temperature too high
(>90°)
E19 Ambient temperature too low
(<-35°)
E39 Actuation duration for the ac-
knowledgment unit exceeded (local socket)
E40 Actuation duration for the ac-
knowledgment unit exceeded (cabinet socket)
E42 Muting enable signal on +24V
for too long
Ensure correct environmental con­ditions
Ensure correct environmental con­ditions
Press the acknowledgment unit. If the restart is unsuccessful, check the wiring of the reset button.
Press the acknowledgment unit. If restart is unsuccessful, check the wiring.
Check the actuation of the muting enable signal
Automatic reset
Automatic reset
Automatic reset
Locking
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Acknowledgment unit
E80 Invalid operating mode Check the configuration of the op-
erating mode and restart.
E87 Operating mode changed Check the configuration of the op-
erating mode and restart.
E89 Switch position of the DIP
switch blocks changed during
Check the configuration of the op­erating mode and restart.
operation.
E97 Linkage of electronic safety-re-
Check the wiring. Locking lated switching outputs: OSSDs did not switch simulta­neously
U10 Invalid command received via
the interface
U30 Sequence error between mut-
ing sensor1 and muting sen-
Check the connection
to the USB interface
Check the arrangement and align-
ment of the muting sensors. sor2
U31 Sequence error between mut-
ing sensor2 and muting sen-
Check the arrangement and align-
ment of the muting sensors sor3
U32 Sequence error between mut-
ing sensor3 and muting sen-
Check the arrangement and align-
ment of the muting sensors sor4
Locking
Locking
Locking
Automatic reset
Automatic reset
Automatic reset
Automatic reset
U33 Sequence error if all muting
sensors are activated and mut-
Check the arrangement and align-
ment of the muting sensors
Automatic reset
ing sensor1 should be free
U34 Sequence error if muting sen-
sors2 to4 are activated and
Check the arrangement and align-
ment of the muting sensors
Automatic reset
muting sensor2 should be free
Leuze electronic MSI-MD-FBX 37
Page 38
Diagnostics and troubleshooting
Error Cause/description Remedies and measures Behavior of the
muting controller
U35 Sequence error if muting sen-
sor3 and muting sensor4 are activated and muting sensor3 should be free
U41 Concurrency expectation of
the muting signals not met: second signal outside toler­ance of 4s
U43 Muting end before protective
field release
U44 Sequence error if muting sen-
sor1 and muting sensor2 are activated and muting sensor2 should be free
U45 Sequence error if muting sen-
sors1 to3 are activated and muting sensor3 should be free
U46 Sequence error if all muting
sensors are activated and mut­ing sensor4 should be free
U47 Sequence error between mut-
ing sensor2 and muting sen­sor1
Check the arrangement and align-
Automatic reset
ment of the muting sensors
Check the arrangement of the mut-
Automatic reset ing sensors or the programming of the machine interface if required.
Select a valid muting condition. Automatic reset.
Check the arrangement and align-
Automatic reset ment of the muting sensors
Check the arrangement and align-
Automatic reset ment of the muting sensors
Check the arrangement and align-
Automatic reset ment of the muting sensors
Check the arrangement and align-
Automatic reset ment of the muting sensors
U48 Sequence error between mut-
ing sensor3 and muting sen­sor2
U49 Sequence error between mut-
ing sensor4 and muting sen­sor3
U50 Muting restart without valid
muting configuration of the muting sensors
U51 Only one muting signal active
in case of protective field viola­tion, the second muting signal is missing
U52 Oscillating muting sensor de-
tected
U55 Time limit for override ex-
ceeded
U56 Acknowledgment unit was ac-
tuated with interrupted protec­tive field and without activated muting sensor
Check the arrangement and align­ment of the muting sensors
Check the arrangement and align­ment of the muting sensors
Check the mounting of the muting sensors and the activation of the muting signals.
Check the mounting of the muting sensors and the activation of the muting signals.
Check the wiring or whether the muting sensor is defective. Ex­change the muting sensor if nec­essary.
Check the further processing of the OSSD signals and the design of the muting system.
Check the arrangement and con­nections of the muting sensors and carry out muting restart again if re­quired.
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset.
Automatic reset
Automatic reset
U58 Muting timeout elapsed Actuate the acknowledgment unit Automatic reset
U59 A muting sensor has switched
on and off again multiple times
Check the arrangement and align­ment of the muting sensors.
Automatic reset
without muting having been triggered
Leuze electronic MSI-MD-FBX 38
Page 39
Diagnostics and troubleshooting
Error Cause/description Remedies and measures Behavior of the
muting controller
U60 Error at transition from one ac-
tivated muting sensor to two
Check the arrangement and align­ment of the muting sensors.
activated muting sensors
U61 Sequence error when clearing
the first muting sensor
U62 Sequence error when clearing
the second muting sensor
U63 Time limit from the activation
of the first muting sensor to the
Check the arrangement and align­ment of the muting sensors
Check the arrangement and align­ment of the muting sensors
Check the arrangement and align­ment of the muting sensors
activation of the second muting sensor exceeded
U64 Time limit for override ex-
ceeded
Check the further processing of the OSSD signals and the design of the muting system.
U66 Sequence error Check the connection of the mut-
ing sensors
U67 No muting-enable signal be-
fore start of muting
Activate muting-enable before muting
U73 Restarting the device Only an entry in the error memory
- no display
U80 Acknowledgment unit actuated
although none is configured
Check the setting for the acknowl­edgment unit
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
U81 Incorrect reset signal, e.g., re-
set signal via acknowledgment unit, even though reset signal is configured via machine in­terface
U82 Muting enable activated even
though not configured
U83 Muting sensor 1 signal via
muting sensor even though configured via machine inter­face
U84 Muting sensor 1 signal via ma-
chine interface even though configured via muting sensor
U85 Signals from muting sensor3
or muting sensor4 in 2-sensor muting
Check the setting for the reset sig­nal.
Check the setting for muting en­able.
Check the setting for muting sen­sor1.
Check the setting for muting sen­sor1.
Check the design of the muting system.
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Automatic reset
Leuze electronic MSI-MD-FBX 39
Page 40

12 Service and support

24-hour on-call service at: +49 7021 573-0
Service hotline: +49 7021 573-123
E-mail:
service.protect@leuze.de
Return address for repairs: Servicecenter Leuze electronic GmbH + Co. KG InderBraike1 D-73277Owen/Germany
Service and support
Leuze electronic MSI-MD-FBX 40
Page 41

13 Technical data

13.1 General specifications

Tab.13.1: Safety-relevant technical data
Performance Level (PL) PLe, Cat.4 in accordance with ENISO13849
Safety Integrity Level (SIL) SIL3 in accordance with IEC61508
SIL Claim Limit (SILCL) SILCL3 in accordance with IEC/EN62061
Probability of a dangerous failure per hour (PFHd) 2.5+10E-9
Mission time (TM) 20 years
Tab.13.2: General system data
Connection technology M12 connectors, 5-pin, female
Technical data
M12 connectors, 8-pin, male
Supply voltage U
v
+24V, ± 20%, compensation necessary at 20ms voltage dip, min.250mA (+external load)
Residual ripple of the supply voltage ± 5% within the limits of U
v
Current consumption 150mA (without load)
Protection class III
Degree of protection IP 67 acc. to EN60529
Reaction time ≤ 5 ms
Ambient temperature, operation -30…+60°C
Ambient temperature, storage -40…+70°C
Relative humidity (non-condensing) 0…95%
Vibration resistance 10-55 Hz in acc. with IEC/EN60068-2-6; 0.35mm
amplitude
Shock resistance 100m/s2 acceleration, 16ms acc. to IEC/
EN60068-2-6
Dimensions (LxWxH) 225mmx60mmx37mm
Weight 560g
Maximum length of the connection cable to the ma­chine interface
50 m
Only permissible with a maximum additional current demand ≤160mA
Torque for the screws of the cover 0.6…0.8Nm
Leuze electronic MSI-MD-FBX 41
Page 42
Tab.13.3: Technical data of the electronic safety-related switching outputs (OSSDs)
Technical data
Safety-related PNP transistor outputs (short-
Minimum Typical Maximum
circuit monitored, cross-circuit monitored)
Switching voltage high active (Uv-1.5V) 18V 24V 27 V
Switching voltage low 0V +2.5V
Switching current 300mA 380mA
Residual current <2µA 200µA
Load capacity 0.3µF
Load inductivity 2H
Permissible wire resistance for load <200Ω
Note the additional restrictions due to cable length and load current.
Permissible wire cross section 0.25mm
2
Test pulse width 60μs 340μs
Test pulse distance (5ms) 60 ms
OSSD restart delay time 100ms
Tab.13.4: Status signals and control signals
Signal Input/Output Values
Reset Input 24V, 15mA
ReadyForReset Output 24V, 80mA
ML Output 24V, 80mA
Input and output currents
MS1…MS4 Input 24V, max. 250mA
Sum of the input/output currents: < 1A
Permissible leakage current for control outputs: max. 0.7mA
NOTICE
The safety-related transistor outputs perform the spark extinction. With transistor outputs, it is therefore neither necessary nor permitted to use the spark extinction circuits recommended by contactor or valve manufacturers (RC elements, varistors or recovery diodes), since these con­siderably extend the decay times of inductive switching elements.
Leuze electronic MSI-MD-FBX 42
Page 43

13.2 Dimensioned drawings

60
225
36
4,5
106,75
4,3
16,3
38,3
all dimensions in mm
Fig.13.1: Dimensioned drawing of MSI-MD-FB muting controller
Technical data

13.3 Dimensioned drawings - Accessories

Mounting plate BT-MSI-MD_FB
all dimensions in mm
Fig.13.2: Mounting plate BT-MSI-MD_FB
Leuze electronic MSI-MD-FBX 43
Page 44
Mounting bracket BT-MSI-MD_FB-L
all dimensions in mm
Fig.13.3: Mounting bracket BT-MSI-MD_FB-L
Technical data
Leuze electronic MSI-MD-FBX 44
Page 45

14 Order guide and accessories

14.1 Type overview

Tab.14.1: Part numbers
Part no. Part designation Description
549954 MSI-MD-FBX Muting controller

14.2 Accessories

Tab.14.2: Connection cables
Part no. Article Description
Connection cables for connecting muting controller MSI-MD-FB to the machine interface
678060 CB-M12-5000E-8GF 5m connection cable with straight socket
678061 CB-M12-1000E-8GF 10m connection cable with straight socket
678062 CB-M12-15000E-8GF 15m connection cable with straight socket
Order guide and accessories
678063 CB-M12-55000E-8GF 25m connection cable with straight socket
678064 CB-M12-50000E-8GF 50m connection cable with straight socket
678070 CB-M12-5000E-8WF 5m connection cable with angled socket
678071 CB-M12-10000E-8WF 10m connection cable with angled socket
678072 CB-M12-15000E-8WF 15m connection cable with angled socket
678073 CB-M12-25000E-8WF 25m connection cable with angled socket
678074 CB-M12-50000E-8WF 50m connection cable with angled socket
Tab.14.3: Interconnection cables
Part no. Article Description
Interconnection cables (Y-cable) for connecting transmitter and receiver of safety light barrier MLD and safety light curtain MLC to the muting controller
548951 CB-M12-Y1A Y interconnection cable with pin4 on 24V
548952 CB-M12-Y1B Y interconnection cable with pin4 open
678033 CB-M12-2500S-5GF/GM Interconnection cable
recommended for MLDx10-RTx connection
678035 CB-M12-5000S-5GF/GM Interconnection cable
recommended for MLDx10-RTx connection
Tab.14.4: Display and confirmation units
Part no. Article Description
426290 AC-ABF10 Display and confirmation unit
Leuze electronic MSI-MD-FBX 45
Page 46
Order guide and accessories
Tab.14.5: Mounting technology
Part no. Article Description
427302 BT-MSI-MD-FB Mounting plate for mounting muting controller
MSI-MD-FB on side or rear on UDC/DC columns or for wall mounting
427303 BT-MSI-MD-FB-L Mounting bracket for interior mounting of muting
controller MSI-MD-FB in UDC/DC columns
Tab.14.6: Muting indicators
Part no. Article Description
660611 MS70/LED-M12-2000-4GM LED muting indicator with connection cable 2m
Leuze electronic MSI-MD-FBX 46
Page 47

15 EC Declaration of Conformity

EC Declaration of Conformity
Leuze electronic MSI-MD-FBX 47
Loading...