The symbols used in this operating manual are explained below.
Attention!
This symbol precedes text messages which must strictly be observed. Failure to comply with
this information results in injuries to persons or damage to the equipment.
Notice!
This symbol indicates text passages containing important information.
1.2Declaration of Conformity
The MA 258i modular interfacing units have been designed and manufactured in accordance with applicable European directives and standards.
Notice!
The Declaration of Conformity for these devices can be requested from the manufacturer.
General information
The manufacturer of the product, Leuze electronic GmbH + Co. KG in D-73277 Owen,
possesses a certified quality assurance system in accordance with ISO 9001.
The MA 258i modular interfacing unit is "UL LISTED" in accordance with American and
Canadian safety standards and fulfills the requirements of Underwriter Laboratories Inc.
(UL).
Leuze electronicMA 258i5
TNT 35/7-24V
General information
1.3Description of functions
The MA 258i modular interfacing unit is used to connect Leuze devices directly to the
fieldbus.
Bar code reader:BCL 8, 22, 300i, 500i, 600i, 90, 900i
This is accomplished by transmitting the data from the DEV via an RS 232 (V.24) interface
to the MA 258i where a module converts it into the EtherNet/IP format. The data format on
the RS 232 interface corresponds to the Leuze standard data format (9600bd, 8N1 and STX,
data, CR, LF).
The integration of the EDS file in the hardware manager of the PLC is necessary to ensure
the correct function of the MA 258i.
The corresponding Leuze devices are selected using a rotary code switch on the circuit
board of the connector unit. Many additional RS 232 devices can be connected through a
universal position.
6MA258iLeuze electronic
1.4Definition of terms
For better understanding of the explanations provided in this document, a definition of terms
follows below:
General information
• Bit designation:
The 1st bit or byte begins with count number "0" and means bit/byte 2
• Data length:
Size of a valid, continuous data packet in bytes.
• EDS file (electronic data sheet):
Description of the device for the control.
• Consistent:
Data which belongs together with regard to content and which must not be separated
is referred to as consistent data. When identifying objects, it must be ensured that
the data is transmitted completely and in the correct order, otherwise the result is
falsified.
• Leuze device (DEV):
Leuze devices, e.g., bar code readers, RFID readers, VisionReader…
• Online command:
These commands refer to the respective, connected ident device and may be different depending on the device. These commands are not interpreted by the MA 258i,
but are instead transmitted transparently (see description of Ident device).
• CR:
Cross reference.
• Perspective of I/O data in the description:
Output data is data which is sent by the control to the MA. Input data is data which
is sent by the MA to the control.
• Tog g le b its :
Status toggle bit
Each change of state indicates that an action was performed, e.g., bit ND (new data):
each change of state indicates that new received data was transmitted to the PLC.
Control toggle bit
An action is performed on each change of state, e.g., bit SDO: on each change of
state, the registered data is sent by the PLC to the MA 258i.
0
.
TNT 35/7-24V
Leuze electronicMA 258i7
Safety
2Safety
This device was developed, manufactured and tested in line with the applicable safety standards. It corresponds to the state of the art.
2.1Intended use
The MA 258i modular interfacing unit is used for connecting Leuze devices such as bar code
or 2D-code readers, hand-held scanners, RFID read-write devices, etc. directly to the
fieldbus.
CAUTION
Observe intended use!
Only operate the device in accordance with its intended use. The protection of per-
sonnel and the device cannot be guaranteed if the device is operated in a manner not
complying with its intended use.
Leuze electronic GmbH + Co. KG is not liable for damages caused by improper use.
Read the technical description before commissioning the device. Knowledge of this
technical description is an element of proper use.
NOTICE
Comply with conditions and regulations!
Observe the locally applicable legal regulations and the rules of the employer's liability
insurance association.
Attention
For UL applications, use is permitted exclusively in Class 2 circuits according to NEC
(National Electric Code).
2.2Foreseeable misuse
Any use other than that defined under "Intended use" or which goes beyond that use is
considered improper use.
In particular, use of the device is not permitted in the following cases:
• Rooms with explosive atmospheres
• As stand-alone safety component in accordance with the machinery directive
• For medicinal purposes
1) Use as safety-related component within the safety function is possible, if the component combination is designed correspondingly by the machine manufacturer.
8MA258iLeuze electronic
1)
NOTICE
Do not modify or otherwise interfere with the device.
Do not carry out modifications or otherwise interfere with the device.
The device must not be tampered with and must not be changed in any way.
The device must not be opened. There are no user-serviceable parts inside.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
2.3Competent persons
Connection, mounting, commissioning and adjustment of the device must only be carried
out by competent persons.
Prerequisites for competent persons:
• They have a suitable technical education.
• They are familiar with the rules and regulations for occupational safety and safety at
work.
• They are familiar with the technical description of the device.
• They have been instructed by the responsible person on the mounting and operation
of the device.
Certified electricians
Electrical work must be carried out by a certified electrician.
Due to their technical training, knowledge and experience as well as their familiarity with
relevant standards and regulations, certified electricians are able to perform work on electrical systems and independently detect possible dangers.
In Germany, certified electricians must fulfill the requirements of accident-prevention regulations BGV A3 (e.g. electrician foreman). In other countries, there are respective regulations that must be observed.
Safety
2.4Disclaimer
Leuze electronic GmbH + Co. KG is not liable in the following cases:
• The device is not being used properly.
• Reasonably foreseeable misuse is not taken into account.
• Mounting and electrical connection are not properly performed.
• Changes (e.g., constructional) are made to the device.
Leuze electronicMA 258i9
TNT 35/7-24V
Fast commissioning / operating principle
PWR OUT
VOUT
123
4
SWIO_2
SWIO_1
GND
FE
5
PWR IN
SWIO_1
SWIO_2
321
4
5
GNDVIN
FE
HOST / BUS IN
TD+
123
4
RD+
RD-
TD-
LEUZE Device
BUS OUT
TD+
123
4
RD+
RD-
TD-
M12 connector
(A-coded)
M12 socket
(A-coded)
M12 socket
(D-coded)
M12 socket
(D-coded)
3Fast commissioning / operating principle
Notice!
Below you will find a short description for the initial commissioning of the EtherNet/IP
gateway MA 258i. Detailed explanations for the listed points can be found throughout the
handbook.
3.1Mounting
The gateway mounting plate MA 258i can be mounted in two different ways:
• using four threaded holes (M6) or
• using two M8x6 screws on the two lateral grooves.
3.2Device arrangement and selection of the mounting location
Ideally, the MA 258i should be mounted so that it is easily accessible near the Ident device
in order to ensure good operability, e.g., for configuring the connected device.
Detailed information can be found in chapter 6.3.1.
3.3Electrical connection
The devices from the MA 2xxi family feature four M12 connectors/sockets which are coded
differently depending on the interface.
The voltage supply (PWR IN) as well as the switching inputs/outputs (PWR OUT or PWR IN)
are connected there. The number and function of the switching inputs/outputs is dependent
on the connected end device.
An internal RS 232 interface is used for connecting the respective Leuze device. Another
internal RS 232 interface functions as a service interface for configuring the connected
device via a serial null modem cable.
Figure 3.1:MA 258i connections
Detailed information can be found in chapter 7.
10MA 258iLeuze electronic
Fast commissioning / operating principle
3.3.1Connecting the Leuze device
To connect the Leuze device to the internal RS 232 device interface, open the housing
of the MA 258i and lead the corresponding device cable (see chapter 14.6) through the
middle threaded opening.
Connect the cable to the internal device interface (X30, X31 or X32, see chapter 7.5.1).
Use rotary switch S4 (see chapter 8.2.5) to select the connected device.
Now screw the PG cable gland into the threaded opening to provide strain relief and
ensure protection class IP 65.
Attention!
Only then may the supply voltage be applied.
Upon startup of the MA 258i, the device selection switch is queried and the gateway
automatically sets itself to the Leuze device.
Connecting functional earth FE
Ensure that the functional earth (FE) is connected correctly.
Unimpaired operation is only guaranteed when the functional earth is connected properly.
All electrical disturbances (EMC couplings) are discharged via the functional earth connection.
3.3.2Connecting the power supply and the bus cable
Ideally, use the ready-made cables listed in chapter 14.4.3 to connect the gateway to the
power supply via the PWR IN connection.
The ready-made cables listed in chapter 14.5.4 are preferred for connecting the gateway
to the fieldbus via the HOST / BUS IN connection.
If applicable, use the BUS OUT connection if you would like to construct a network with
linear topology.
3.4Starting the device
Apply the supply voltage +18 … 30VDC (+24VDC model); the MA 258i starts up.
The MS LED displays that it is ready for operation.
Leuze electronicMA 258i11
TNT 35/7-24V
Fast commissioning / operating principle
3.5MA 258i on EtherNet/IP
Commissioning on the EtherNet/IP is performed according to the following scheme:
• Address assignment (automatically via DHCP, BootP or manually)
• Configuration of the participant depends on the control software version: either by
using the generic EtherNet module or by installing the EDS file
• Transfer the data to the control
• Adapting the device parameters depends on the version of the control software: either
by configuring the config assembly or by adapting the EDS file
• Use explicit messaging services
The MA 258i can be configured in the planning tool/control using the EDS file if the control
supports this. PLC software RSLogix 5000 from Rockwell offers EDS support for EtherNet/
IP from software version 20.00 and up. Without PLC support of the EDS integration, the
settings are made via the "generic EtherNet module". In this case, the respective configuration must be entered and adapted manually for each device.
After all parameters have been set in the planning tool/control, the download to the MA 258i
takes place. The set parameters are now stored on the MA 258i.
Afterwards, all MA 258i parameters should be stored via upload in the control. This aids in
retaining the parameters during device exchanges, as they a re now also stored centrally in
the control.
The EtherNet/IP baud rate is defined for the entire network in the planning tool/control.
Detailed information can be found in chapter 12.
12MA 258iLeuze electronic
Fast commissioning / operating principle
3.5.1Manually setting the IP address
To set the IP address manually, the DHCP operation via BootP or the Rockwell control must
be deactivated.
Figure 3.2: Manually setting the IP address
If your system does not include a DHCP server or if the IP addresses of the devices are to
be set permanently, proceed as follows:
Have the network administrator specify the data for IP address, net mask and gateway
address of the MA 258i.
Leuze electronicMA 258i13
TNT 35/7-24V
Fast commissioning / operating principle
Figure 3.3:Making network settings
Select the connected device via the device selection switch.
Apply the supply voltage +18 … 30VDC (+24VDC model); the MA 258i starts up.
Now switch the service switch to "MA".
Now start a web browser by entering the IP address into the navigation bar. You will be
shown a page for the direct setting of the addresses.
Note!
The service switch must be in switch position "MA" for the MA 258i to start in configuration
mode.
Connect the serial RS 232 Sub-D interface of the MA 258i to the serial interface of your
PC.
Make the respective settings on the configuration page opened in the web browser.
14MA 258iLeuze electronic
3.5.2Configure the participant
Configuration with the generic EtherNet module
In the RSLogix 5000 configuration tool for EtherNet/IP, software version <20.00, a so-called
"generic EtherNet module" is created for the MA 258i under the Communication path.
Fast commissioning / operating principle
Figure 3.4:Generic module
Leuze electronicMA 258i15
TNT 35/7-24V
Fast commissioning / operating principle
Figure 3.5:Assembly list
The input mask for the Generic module describes:
• The name of the participant (can be selected freely; e.g.MA 258i).
• The format of the I/O data (data - DINT = 32bit or data - SINT = 8bit).
• The IP address of the participant.
• The address and length of the input assembly (instance 106). *)
• The address and length of the output assembly (instance 107). *)
• Optional: The address and length of the configuration assembly (instance 118; 12 x
8bit).
*) The possible data lengths are shown in figure 3.5. You can select the suitable byte
number for your application here. Recommendations can be found in chapter "Specifications for Leuze end devices" on page 97.
Notice!
The available lengths (4, 8, 12, 16, 20, 32, 64, 128, 240 bytes) of the input/output data cannot
be freely combined. The MA can only process ONE combination (connection). Please select
the suitable combination for the data length and the connected device. Detailed information
on this topic can be found in chapter 12.6.2.
16MA 258iLeuze electronic
Fast commissioning / operating principle
Attention!
If the configuration assembly is addressed with instance 118 and length 12 in the input mask
for the generic module, all MA 258i parameters with the value 0 are occupied in the first
moment. All default parameters of the MA must be manually entered in the configuration
assembly. Changing the individual default values is possible at any time.
For the exact description of the assemblies for input/output and configuration, please refer
to chapter 12.6.2.
The query cycle of the input and output assemblies is subsequently defined in the Moduleproperties -> Connection path in the Request packet interval (RPI) input field.
The participant is thereby defined in offline mode; the data must subsequently be transferred
to the control.
Configuration of the participant using the EDS file
From RSLogix 5000 software version 20.00 and up, proceed as follows to create the
MA 258i as an EtherNet participant in your system:
First, load the EDS file for the device via EDS wizard into the PLC database.
Notice!
You can find the EDS file at www.leuze.com.
After loading, select the device via the device list and enter it into the HW manager via
Drag&Drop.
Open the input dialog for setting the address and additional parameters by double-click-
ing on the device symbol and make the desired entries here.
Finally, transmit the values to the device via download.
Leuze electronicMA 258i17
TNT 35/7-24V
Fast commissioning / operating principle
3.5.3Transfer the data to the control (RSLogix 5000 specific)
Activate online mode.
Select the EtherNet communication port.
Select the processor onto which the project is to be transferred.
Set the control to PROG.
Start the download.
Set the control to RUN.
3.5.4Adapting the device parameters
Configure the parameters via the config assembly
The MA 258i makes available a configuration assembly that allows the entire parameter set
of the MA 258i to be saved in the control and, if necessary, to be called up.
The config assembly must include all parameters that affect the MA 258i. The config
assembly is automatically written to the connected participants in cycles that the control
manufacturer defines.
The config assembly is implemented in class 4, under instance 118. By default, all parameters are preset to the value 0 (zero).
Attention!
If the config assembly is not adapted, the MA 258i displays a corresponding behavior acc.
to the parameters preset with 0.
Switch the control to offline mode.
Double-click
The configuration assembly can be recognized by the index "C" appended to the device
name.
Parameter entry is performed as described in section "Setting MA parameters manually via
the config assembly" on page 74.
Attention!
Activation of the config assembly as described above necessitates value entry in the corresponding parameter memory locations. When using the configuration assembly, the default
parameters must also be entered in the corresponding memory locations (see also "Setting
MA parameters manually via the config assembly" on page 74).
After all of the parameters relevant to the MA 258i are entered, the control is switched to
"online" and the project is downloaded again.
18MA 258iLeuze electronic
Controller tags
to edit the configuration assembly.
Fast commissioning / operating principle
Setting the parameters on the MA via the EDS file
After the EDS file has been integrated, the device must be created as a "module" to establish
a connection. It is also helpful to assign an IP address to the MA beforehand, e.g. via the
service interface.
To do this, double-click on the tree node EtherNet.
In the new window, select the desired device from the database and carry out the respec-
tive configuration.
Figure 3.6:Creating a module
First set the IP address.
Leuze electronicMA 258i19
TNT 35/7-24V
Fast commissioning / operating principle
Figure 3.1:Setting the IP address of the MA
Then, via the Change button, select the input/output data length of the module from a
list of possible combinations by clicking on Connection.
Notice!
The available lengths (4, 8, 12, 16, 20, 32, 64, 128, 240 bytes) of the input/output data are
stored here in "fixed" combinations. They cannot be freely combined. The MA can only process ONE combination (connection).
Please select the suitable combination for the data length and the connected device. For
further information, see chapter 16 "Specifications for Leuze end devices".
Figure 3.2:Select combination for the lengths of the input and output data
20MA 258iLeuze electronic
Fast commissioning / operating principle
Notice!
Since the combination of Produced/Consumed data contains 2 bytes for the control and
status bytes, the actual user data length is always 2 bytes smaller than specified in the
selected combination.
E.g., when using the combination with 12 bytes In/12 bytes Out, there are effectively 10 bytes
available for user data on the Leuze device after subtracting the 2 bytes for status and control
bytes.
Recommendation
A combination with 4 bytes of output data length is sufficient for most output data.
A longer length is needed, for example, if a BCL bar code scanner is to be configured by
means of PT-sequences, or an RFID transponder is to be described. In these cases, larger
combinations are usually advisable.
Select the appropriate combination and transmit the settings to the device.
Figure 3.7:MA settings in the controller tags
Leuze electronicMA 258i21
TNT 35/7-24V
Fast commissioning / operating principle
3.5.5Use explicit messaging services
Explicit messaging services (e.g., "get attributes …, set attribute …, and others) can be
used to acyclically access all data of the MA 258i
Attention!
If parameters are changed via explicit messaging services while simultaneously activating a
configuration assembly, the changed parameters must subsequently be entered in the configuration assembly.
22MA 258iLeuze electronic
4Device description
4.1General Information to the connector units
The modular interfacing unit of the MA 2xxi family is a versatile gateway for integrating Leuze
RS 232 devices (e.g., BCL 22 bar code readers, RFID devices, RFM 32, …) into the respective fieldbus. The MA 2xxi gateways are intended for use in industrial environments with a
high protection class. Various device versions are available for the conventional fieldbuses.
With a stored parameter structure for the connectable RS 232 devices, commissioning
could hardly be simpler.
4.2Characteristics of the connector units
A special characteristic of the MA 258i device family are three function modes:
1.Transparent mode
In this function mode, the MA 258i functions as a pure gateway with automatic communication from and to the PLC. Absolutely no special programming by the user is
necessary for this purpose. The data is not buffered or stored temporarily, however.
Instead, it is "passed on".
The programmer must make certain to retrieve the data from the input memory of the
PLC at the right time, as it is otherwise overwritten by new data.
2.Collective mode
In this operating mode, data and telegram parts are temporarily stored in the memory
(buffer) of the MA and sent to the RS 232 interface or to the PLC in a telegram by means
of bit activation. In this mode, however, all communication control must be programmed on the PLC.
This function mode is helpful, for example, for very long telegrams or when one or
more codes with long code lengths are read.
Device description
3.Command mode
With this special operating mode, it is possible to use the first bytes of the data range
to transmit predefined commands to the connected device by means of bit activation.
For this purpose, device-dependent commands (so-called online commands) are predefined via the device selection switch, see chapter 16 "Specifications for Leuze end
devices".
Leuze electronicMA 258i23
TNT 35/7-24V
Device description
Fieldbus
Fieldbus
MA 258i
Leuze
device
Either
network or other devices
with RS 232
RS 232
(V.24)
4.3Device construction
The MA 258i modular interfacing unit is used for interconnecting Leuze devices, such as
the BCL 8, BCL 22, etc., directly to the fieldbus. This is accomplished by transmitting the
data from the Leuze device via an RS 232 (V.24) interface to the MA 258i where a module
converts it into the fieldbus format. The data format of the RS 232 interface corresponds to
the standard Leuze data format.
Figure 4.1:Connection of a Leuze device (BCL, RFI, RFM, …) to the fieldbus
The cable of the respective Leuze device is guided through cable bushings with PG cable
glands into the MA 258i and connected there with the PCB connectors.
The MA 258i is intended as a gateway for any RS 232 devices, e.g., BCL 300i, hand-held
scanners, scales or for coupling a multiNet network.
The RS 232 cables are internally connectable using JST plug connectors. The cable can be
connected to the device using a stable PG cable gland which provide strain relief and protection against contamination.
With the help of adapter cables with Sub-D 9 or open cable end, other RS 232 devices can
also be connected.
24MA 258iLeuze electronic
4.4Operating modes
For fast commissioning, the MA 258i offers an additional operating mode, the "Service
mode", in addition to the "Standard mode". In this operating mode, the Leuze device can,
for example, be configured on the MA 258i and the network settings of the MA can be
displayed. To do this, you need a PC/laptop with a suitable terminal program, as BCL-Config
from Leuze or similar.
Service switch
Select between "operation" and "service" modes with the service switch. You have the
following options:
Pos. RUN:
Operation
The Leuze device is connected to the fieldbus and communicates with the PLC.
Pos. DEV:
Service Leuze device
The connection between the Leuze device and the fieldbus is interrupted. With this
switch position, you can communicate directly with the Leuze device at the fieldbus
gateway via RS 232. You can send online commands via the service interface, configure the Leuze device using the corresponding BCL- BPS-, …-Config configuration
software and have the read data of the Leuze device output.
Pos. MA:
Service fieldbus gateway
With this switch setting, your PC/terminal is connected with the fieldbus gateway.In
doing so, the current setting values of the MA (e.g. address, RS 232 parameters) can
be called up via a command.
Device description
Figure 4.2:Service-switch switch positions
Notice!
If the service switch is on one of the service settings, the MS LED flashes on the front side
of the device, see chapter 8.1.2 "LED indicators on the housing".
Furthermore, on the control, the SMA service bit of the status bytes signals that the MA is
in service mode.
Leuze electronicMA 258i25
TNT 35/7-24V
Device description
5 GND
3 TxD
2 RxD
GND 5
TxD 3
RxD 2
1
1
PC/terminal
COM interface
MA 258i
Service interface
Service interface
The service interface can be accessed once the MA 258i housing cover has been removed
and features a 9-pin Sub-D connector (male). A crossed RS 232 connection cable is required
to make the RxD, TxD and GND connections.
Figure 4.3:Connecting the service interface to a PC/terminal
Attention!
For the service PC to function, the RS 232 parameters must be the same as those of the
MA. The Leuze standard setting of the interface is 9600bd, 8N1 and STX, data, CR, LF.
4.5Fieldbus systems
Various product variants of the MA 2xxi series are available for connecting to different
fieldbus systems such as PROFIBUS DP, PROFINET-IO, DeviceNet and Ethernet or
EtherCAT.
4.5.1EtherNet/IP
The MA 258i is designed as an EtherNet/IP device (acc. to IEEE 802.3) with a standard baud
rate of 10/100 Mbit. The functionality of the device is defined via parameter sets which are
clustered in objects, classes and instances. These objects … are contained in an EDS file
which, depending on the version of the control software, can be used to configure and integrate the MA into the system. PLC software RSLogix 5000 from Rockwell offers EDS
support for EtherNet/IP from software version 20.00 and up. A fixed MAC ID is assigned to
each MA 258i by the manufacturer; this ID cannot be changed.
The MA 258i automatically supports the transmission rates of 10 Mbit/s (10Base T) and
100 Mbit/s (10Base TX), as well as auto-negotiation and auto-crossover.
The MA 258i features multiple M12 connectors / sockets for the electrical connection of the
supply voltage, the interface and the switching inputs and outputs. Additional information
on the electrical connection can be found in chapter 7.
26MA 258iLeuze electronic
Device description
MA 258i
"192.168.0.100"
PC / PLC host interface
Other network participants
PC / PLC host interface
MA 258i
"192.168.0.100"
to other network participants
MA 258i
"192.168.0.101"
MA 258i
"192.168.0.102"
The MA 258i supports the following protocols and services:
• EtherNet/IP
• DHCP
•ARP
•PING
Further information on commissioning can be found in chapter 12.
EtherNet/IP – star topology
The MA 258i can be operated as a single device (standalone) in an EtherNet star topology
with individual IP address. The setting is made via DHCP/ BootP.
Figure 4.4:EtherNet/IP with star topology
EtherNet/IP – linear topology
The innovative further development of the MA 258i with integrated switch functionality offers
the option of connecting multiple gateways of type MA 258i to one another without direct
connection to a switch. In addition to the classic "star topology", a "linear topology" is thus
also possible.
Leuze electronicMA 258i27
Figure 4.5:EtherNet/IP with linear topology
TNT 35/7-24V
Device description
Each participant in this network requires its own unique IP address, which must be assigned
to it via BootP or the control software. Alternatively, the DHCP procedure can be used.
The maximum length of a segment (connection from the hub to the last participant) is limited
to 100m.
Communication
The MA 258i gateway supports the CIP-based EtherNet/IP protocol and requires the setup
of a GENERIC module or the EDS file (Electronic Data Sheet), depending on the control soft-
ware used, for communication.
Notice!
Rockwell RSLogix 5000 supports EDS integration for EIP from software version 20.00 and
up.
The EDS file is available for download from the Leuze home page.
You can find the EDS file at www.leuze.com.
The EDS file is named "MA258i.eds"; the corresponding icon is named "MA258i.ico".
The EDS file includes all communication parameters of the participants as well as the
available objects.
The input/output data is addressed according to the following fundamental scheme:
1.Device address (MAC ID)
The participant is addressed with its MAC ID, which is unique in the network.
2.Object class identifier (class)
Used as the basis for addressing the desired object class.
3.Object instance identifier (instance)
Addressing of the object instance within the object class.
4.Attribute identifier (attribute)
Addressing of the attribute within the object instance.
5.Service code (get, set, reset, start, stop and others...)
The maintenance code ultimately describes the type of access to the data, e.g.,
reading or writing.
28MA 258iLeuze electronic
5Specifications
5.1General specifications
Electrical data
Interface type 1EtherNet/IP, integrated switch,
protocols EtherNet/IP communication
baud rate 10/100MBd
vendor ID 524Dec / 20CH
device type 12Dec / 0CH (communications adapter)
position sensor type Product type 04 (gateway)
Interface type 2RS 232
baud rate 300bit/s … 115200 bit/s
Service interface RS 232, 9-pin Sub-D connector, Leuze standard
data format data bit: 8, parity: none, even ODD; stop bit: 1
Operating voltage18 … 30VDC (PELV, Class 2)
Power consumptionMax. 5VA (without IDS, current consumption max.
Max stress on the connector
(PWR IN/OUT)
Indicators
LED LINK0 / ACT0green Connection possible
LED LINK1 / ACT1green Connection possible
yellow Data transmission
LED NS green Device in service mode
LED MSgreen/flashing Device ok/device in service mode
Mechanical data
Protection classIP 65 (with screwed-on M12 and connected Leuze
Weight700 g
Dimensions (Hx WxD)130 x 90 x 41mm / with plate: 180 x 108 x 41mm
HousingDiecast aluminum
Connection2 x M12: BUS IN / BUS OUT EtherNet/IP
BUS: 1x M12 socket (D-coded),
1x M12 socket (D-coded)
PWR/IO: 1x M12 connector (A-coded),
1x M12 socket (A-coded)
DHCP
ARP
PING
device-dependent voltage
300mA)
3A
yellow Data transmission
red Network error
red Configuration error
device)
1 connector: RS 232
Specifications
1)
TNT 35/7-24V
Leuze electronicMA 258i29
Specifications
Environmental data
Operating temperature range0 °C … +55°C
Storage temperature range-20°C … +60 °C
Air humidityMax. 90% rel. humidity, non-condensing
VibrationIEC 60068-2-6, test FC
ShockIEC 60068-2-27, test Ea
Electromagnetic compatibilityEN 61000-6-3:2007 (interference emissions for resi-
CertificationsUL 60950-1, CSA C22.2 No. 60950-1
1) For UL applications: only for use in "Class 2" circuits acc. to NEC.
5.2Dimensioned drawings
1 x M12: Power IN/GND and switching input/output
1 x M12: Power OUT/GND and switching input/output
dential, commercial and light-industrial environments)
EN 61000-6-2:2005 (interference rejection for industrial sectors)
1)
Figure 5.1:Dimensioned drawing MA 258i
30MA 258iLeuze electronic
5.3Type overview
The following versions of the MA 2xxi gateway family are available for facilitating the integration of Leuze RS 232 devices in the various fieldbus types.
FieldbusDevice typePart no.
PROFIBUS DP V0MA 204i50112893
Ethernet TCP/IPMA 208i50112892
PROFINET-IO RTMA 248i50112891
DeviceNet MA 255i50114156
CANopen MA 235i50114154
EtherCAT MA 238i50114155
EtherNet/IP MA 258i50114157
Table 5.1:Type overview MA 2xxi
Specifications
Leuze electronicMA 258i31
TNT 35/7-24V
Installation and mounting
6Installation and mounting
6.1Storage, transportation
Attention!
When transporting or storing, package the device so that it is protected against collision and
humidity. Optimal protection is achieved when using the original packaging. Heed the
required environmental conditions specified in the technical data.
Unpacking
Check the packaging for any damage. If damage is found, notify the post office or shipping
agent as well as the supplier.
Check the delivery contents using your order and the delivery papers:
• Delivered quantity
• Device type and model as indicated on the name plate
• Brief manual
The name plate provides information as to what MA 2xxi type your device is. For specific
information, please refer to the package insert or chapter 14.2.
Name plate of the connector unit
Figure 6.1:Device name plate MA 258i
Notice!
Please note that the shown name plate is for illustration purposes only; the contents do not
correspond to the original.
Save the original packaging for later storage or shipping.
If you have any questions concerning your shipment, please contact your supplier or your
local Leuze electronic sales office.
Observe the applicable local regulations when disposing of the packaging materials.
32MA 258iLeuze electronic
6.2Mounting
Fastening
options
The gateway mounting plate MA 258i can be mounted in two different ways:
•using four threaded holes (M 6) or
• using two M8 screws on the two lateral grooves.
Fastening by means of four M 6 or two M8 screws
Installation and mounting
Figure 6.2:Fastening options
TNT 35/7-24V
Leuze electronicMA 258i33
Installation and mounting
6.3Device arrangement
Ideally, the MA 258i should be mounted so that it is easily accessible near the Ident device
in order to ensure good operability, e.g., for configuring the connected device.
6.3.1Selecting a mounting location
In order to select the right mounting location, several factors must be considered:
• The permissible cable lengths between the MA 258i and the host system depending
on which interface is used.
• The housing cover should be easily accessible, so that the internal interfaces (device
interface for connecting the Leuze device via PCB connectors, service interface) and
other operational controls are easy to reach.
• Maintaining the required environmental conditions (temperature, humidity).
• Lowest possible chance of damage to the MA 258i by mechanical collision or jammed
parts.
6.4Cleaning
Clean the housing of the MA 258i with a soft cloth after mounting. Remove all packaging
remains, e.g. carton fibers or Styrofoam balls.
Attention!
Do not use aggressive cleaning agents such as thinner or acetone for cleaning the device.
34MA 258iLeuze electronic
7Electrical connection
The fieldbus gateways MA 2xxi are connected using variously coded M12 connectors.
An RS 232 device interface allows the respective devices to be connected with system
connectors. The device cables are equipped with a prefabricated PG cable gland.
Coding varies and the design is implemented as either socket or connector depending on
the HOST (fieldbus) interface and function. For the exact design, refer to the corresponding
description of the MA 2xxi device type.
Notice!
The corresponding mating connectors and ready-made cables are available as accessories
for all cables. For further information, see chapter 14 "Type overview and accessories".
Figure 7.1:Location of the electrical connections
7.1Safety notices for the electrical connection
Attention!
Before connecting the device please ensure that the supply voltage matches the value printed on the nameplate.
Connection of the device and cleaning must only be carried out by a qualified electrician.
Ensure that the functional earth (FE) is connected correctly. Unimpaired operation is only
guaranteed when the functional earth is connected properly.
If faults cannot be corrected, the device should be removed from operation and protected
against possible commissioning.
Attention!
For UL applications, use is only permitted in class 2 circuits in accordance with the NEC
(National Electric Code).
Electrical connection
TNT 35/7-24V
The fieldbus gateways are designed in accordance with safety class III for supply by PELV
(protective extra-low voltage with reliable disconnection).
Notice!
Protection class IP65 is achieved only if the connectors and caps are screwed into place!
Leuze electronicMA 258i35
Electrical connection
M12 connector
(A-coded)
M12 socket
(A-coded)
M12 socket
(D-coded)
M12 socket
(D-coded)
PWR IN
SWIO_1
SWIO_2
3
2
1
4
5
GNDVIN
FE
M12 connector
(A-coded)
7.2Electrical connection
The MA 258i features two M12 connectors/sockets for voltage supply; each is A-coded.
The voltage supply (PWR IN) as well as the switching inputs/outputs (PWR OUT or PWR IN)
are connected there. The number and function of the switching inputs/outputs is dependent
on the connected end device. Two additional M12 sockets are used for connection to the
fieldbus. Both of these connections are D-coded.
An internal RS 232 interface is used for connecting the respective Leuze device. Another
internal RS 232 interface functions as a service interface for configuring the connected
device via a serial null modem cable.
PWR IN
SWIO_2
GNDVIN
321
5
4
FE
SWIO_1
VOUT
PWR OUT
SWIO_2
123
5
4
SWIO_1
FE
GND
LEUZE Device
TD+
Figure 7.2:MA 258i connections
Described in detail in the following are the individual connections and pin assignments.
Attention!
Voltage supply and bus cable are coded in the same way. Please observe the printed connection designations
7.2.1PWR IN – voltage supply / switching input/output
PWR IN (5-pin connector, A-coded)
PinNameRemark
1VINPositive supply voltage +18 … +30VDC
2SWIO_2Switching input/switching output 2
3GNDNegative supply voltage 0VDC
4SWIO_1Switching input/switching output 1
5FEFunctional earth
HOST / BUS IN
RD+
123
4
RD-
BUS OUT
RD+
TD-
TD+
123
4
RD-
TD-
ThreadFEFunctional earth (housing)
Table 7.1:PWR IN pin assignment
36MA 258iLeuze electronic
Electrical connection
Notice!
The designation and function of the SWIO depends on the connected device. Please observe
the following table!
For UL applications, use is only permitted in class 2 circuits in accordance with the NEC
(National Electric Code).
configurable
(on SWIN_1, PWRIN)
The fieldbus gateways are designed in accordance with safety class III for supply by PELV
(protective extra-low voltage with reliable disconnection).
Connecting functional earth FE
Notice!
Ensure that the functional earth (FE) is connected correctly. Unimpaired operation is only
guaranteed when the functional earth is connected properly. All electrical disturbances (EMC
couplings) are discharged via the functional earth connection.
Switching input/output
The MA 258i is equipped with the SWIO_1 and SWIO_2 switching inputs/outputs. This is
located on the PWR IN M12 connector and on the PWR OUT M12 connector. The connection of the switching inputs/outputs from PWR IN to PWR OUT can be interrupted by means
of a jumper. In this case, only the switching input and output on PWR IN are active.
The function of the switching inputs and outputs is dependent on the connected Leuze
device. Detailed information on this topic can be found in the respective operating instructions.
Leuze electronicMA 258i37
TNT 35/7-24V
Electrical connection
PWR OUT
VOUT
1
2
3
4
SWIO_2
SWIO_1
GND
FE
5
M12 socket
(A-coded)
M12 socket
(D-coded)
7.2.2PWR OUT switching input/output
PWR OUT (5-pin socket, A-coded)
PinNameRemark
1VOUT
2SWIO_2Switching input/switching output 2
3GNDGND
4SWIO_1Switching input/switching output 1
5FEFunctional earth
ThreadFEFunctional earth (housing)
Table 7.2:PWR OUT pin assignment
Notice!
The maximum admissible current of the PWR OUT and IN connectors is maximum 3A. To
be subtracted from this is the current consumption of both the MA and of the connected
end device.
The function of the switching inputs and outputs is dependent on the connected Leuze
device. Detailed information on this topic can be found in the respective operating instructions.
On delivery, the SWIO 1/2 are connected in parallel on PWR IN/OUT. This connection can
be separated with a jumper.
Voltage supply for additional devices
(VOUT identical to VIN at PWR IN)
7.3BUS IN
The MA 258i provides an EtherNet/IP interface as a HOST interface.
BUS IN (4-pin socket, D-coded)
BUS IN
RD+
2
TD+
1
RD-
38MA 258iLeuze electronic
Table 7.3:EtherNet/IP BUS IN pin assignment
TD-
3
4
PinNameRemark
1TD+Transmit Data +
2RD+Receive Data +
3TD-Transmit Data -
4RD-Receive Data -
ThreadFEFunctional earth (housing)
Electrical connection
MA 258 HOST / BUS IN
RJ 45
TD+
1
2
3
4
RD+
RD-
TD-
TD+ (1)
TD- (2)
RD+ (3)
RD- (6)
1
8
Twisted Pair
Twisted Pair
max. 100m
shielded cable
RJ45 - assignment and wire colors
PinSignalName
Wire color according
to PROFINET
Wire color according
to EIA T568B
1TD+ Transmission Data + yellowwhite/orange
2TD
-
Transmission Data - orangeorange
3RD+ Receive Data + whitewhite/green
6RD
-
Receive Data
-
bluegreen
For the host connection of the MA 258i, the "KB ET - … - SA-RJ45" ready-made cables
are preferred, see table 14.4 Bus connection cable for the MA 258i on page 94.
EtherNet/IP cable assignment
Figure 7.3:HOST/BUS IN cable assignments on RJ-45 (shown here is the device connection)
Notice for connecting the EtherNet/IP interface!
Ensure adequate shielding. The entire connection cable must be shielded and earthed. The
RD+/RD- and TD+/TD- wires must be stranded in pairs.
Use CAT 5 cable for the connection.
Leuze electronicMA 258i39
TNT 35/7-24V
Electrical connection
BUS OUT
TD+
1
2
3
4
RD+
RD-
TD-
M12 socket
(D-coded)
7.4BUS OUT
Table 7.4:EtherNet/IP BUS OUT pin assignment
For the host connection of the MA 258i, the "KB ET - … - SSA" ready-made cables are
preferred, see table 14.4 Bus connection cable for the MA 258i on page 94.
Notice!
Ensure adequate shielding. For the devices and ready-made cables offered by
Leuze electronic, the shield is on PIN 1.
If you use user-configurable cables, note the following:
Notice!
Ensure adequate shielding. The entire connection cable must be shielded and earthed. The
signal lines must be stranded in pairs.
Use CAT 5 cable for the connection.
BUS OUT (4-pin socket, D-coded)
PinNameRemark
1TD+Transmit Data +
2RD+Receive Data +
3TD-Transmit Data -
4RD-Receive Data -
ThreadFEFunctional earth (housing)
Notice!
For the MA 258i as standalone device or as the last participant in a linear topology, termination on the BUS OUT socket is not mandatory!
40MA 258iLeuze electronic
Electrical connection
7.5Device interfaces
Figure 7.4:Open MA 258i
7.5.1RS 232 device interface (accessible after opening the device, internal)
The device interface is prepared for the system plugs (PCB connectors) for Leuze devices
RFI xx, RFM xx, BCL 22.
Figure 7.5:RS 232 device interface
The standard devices are connected with 6- or 10-pin connector piece to X31 or X32,
respectively. For hand-held scanners, BCL 8 and BPS 8 with 5 VDC supply (from the MA)
on pin 9, the 12-pin X30 PCB connection is available as well.
By using an additional cable (cf. "Type overview and accessories" on page 91), the system
connection can be established on M12 or 9-pin Sub-D, e.g., for hand-held scanners.
Leuze electronicMA 258i41
TNT 35/7-24V
Electrical connection
5 GND
3 TxD
2 RxD
GND 5
TxD 3
RxD 2
1
1
PC/terminal
COM interface
MA 258i
Service interface
7.5.2Service interface (internal)
Figure 7.6:RS 232 service switch and service interface
Following activation, this interface enables access via the RS 232 to the connected Leuze
device and the MA for configuration using the 9-pin Sub-D. The connection between the
fieldbus interface and the device interface is switched off during access. The fieldbus itself
is, however, not interrupted as a result.
The service interface can be accessed once the MA 258i housing cover has been removed
and features a 9-pin Sub-D connector (male). A crossed RS 232 connection cable is required
to make the RxD, TxD and GND connections. A hardware handshake via RTS, CTS is not
supported at the service interface.
Figure 7.7:Connecting the service interface to a PC/terminal
Attention!
For the service PC to function, the RS 232 parameters must be the same as those of the
MA. The Leuze standard setting of the interface is 9600Bd, 8N1 and STX, data, CR, LF.
Notice!
To configure the devices connected to the external interface, e.g., BCL 8 (JST plug connector "X30"), a cable specially configured for this purpose is necessary. The service switch must
be in the "DEV" or "MA" position (Service Leuze device/MA).
42MA 258iLeuze electronic
Status displays and operational controls
8Status displays and operational controls
Figure 8.1:LED indicators on the MA 258i
8.1LED status indicators
8.1.1LED indicators on the circuit board
LED (Status)
offDevice OFF
- no operating voltage or device defect
continuous green lightDevice ok
- readiness for operation
continuous orange lightDevice error / firmware available
flashing green-orangeDevice in boot mode
-no firmware
Leuze electronicMA 258i43
TNT 35/7-24V
Status displays and operational controls
MS
MS
MS
MS
NS
NS
8.1.2LED indicators on the housing
LED MS
offDevice OFF
continuous green lightDevice ok
flashing greenDevice ok, device in service mode
flashing redConfiguration error
LED NS
flashing greenDevice ok, device in service mode
continuous red lightNetwork error
- no operating voltage
for details, see chapter 15 "Diagnostics
and troubleshooting"
- self test successfully finished
- device monitoring active
- baud rate or address incorrect
LINK 0/ ACT 0 LED
continuous green light LINK 0
- connection exists
flashing yellow ACT 0
- data exchange
LINK 1/ ACT 1 LED
continuous green light LINK 1
- connection exists
flashing yellow ACT 1
- data exchange
44MA 258iLeuze electronic
Status displays and operational controls
CB
A
D
E
G
F
= Standard settings
A MA 258i: not equipped
B Rotary switch S4 for device selection
C Service switch
D RS 232
Sub-D service interface
E Jumper for bridging, separating switching input/output PWR IN/OUT
F 3 JST plug connectors: connection of the Leuze devices
G MA 258i: without function/not equipped
8.2Internal interfaces and operational controls
8.2.1Overview of operational controls of the
The operational controls of the MA 258i are described in the following. The figure shows
the MA 258i with opened housing cover.
Figure 8.2:Front view: operational controls of the MA 258i
Leuze electronicMA 258i45
TNT 35/7-24V
Status displays and operational controls
Circuit board element
desig.
X1
Operating voltage
X2
Output voltage
X4
HOST interface
X5
HOST interface
X30
Leuze device
X31
Leuze device
X32
Leuze device
X33
RS 232 service interface
S4
Rotary switch
S10
DIP switch
J1, J2
Jumper
Function
PWR IN
M12 connector for operating voltage (18 … 30V DC) MA 258i and connected
Leuze device xx
PWR OUT
M12 connector for other devices (MA, BCL, sensor, …)
VOUT = VIN max. 3A
BUS IN
HOST interface for connecting to the fieldbus
BUS OUT
Second BUS interface for creating a network with other participants in a linear
topology
JST plug connector with 12 pins
Connection of the Leuze devices with 5 V / 1A (BCL 8, BPS 8 and hand-held scanner)
JST plug connector with 10 pins
Connection of the Leuze devices (BCL, RFI, RFM,…)
Pin VINBCL with standard setting = V+ (18 - 30 V)
JST plug connector with 6 pins
Connection of the Leuze devices (BCL, RFI, RFM,…)
Pin VINBCL with standard setting = V+ (18 - 30 V)
9-pin SUB-D connector
RS 232 interface for service/setup operation. Enables the connection of a PC via
serial null modem cable for configuring the Leuze device and the MA 258i
Rotary switch (0 … F) for device selection
Standard setting = 0
Service switch
Switch between service Leuze device (DEV), service fieldbus gateway (MA) and
operation (RUN).
Standard setting = operation.
Bridging, separating switching input/output
(interruption of connection between the two PWR M12 connectors of the SWIO 1/
SWIO 2)
46MA 258iLeuze electronic
8.2.2Connector X30 … connectors
PCB connectors X30 … X32 are available in the MA 258i for connecting the respective
Leuze devices via RS 232.
Figure 8.3:Connections for Leuze devices
Attention!
Several Leuze devices may not be connected to the MA 258i simultaneously, as only one
RS 232 interface can be operated.
8.2.3RS 232 service interface – X33
The X33 RS 232 interface facilitates the configuration of the Leuze device and the MA 258i
via PC, which is connected by means of a serial null modem cable.
X33 pin assignment – service connector
SERVICE (9-pin SUB-D connector)
PinNameRemark
2RXDReceive Data
3TXDTransmit Data
Status displays and operational controls
5GNDFunctional earth
Table 8.1:SERVICE pin assignment
8.2.4S10 service switch
The S10 DIP switch can be used to select between the "operation" and "service" modes,
i.e. you switch between the following options here:
• Operation (RUN) = default setting
• Service Leuze device (DEV) and
• Service fieldbus gateway (MA)
Figure 8.4:DIP switch service - operation
For further information on the corresponding options, see chapter 4.4 "Operating modes".
Leuze electronicMA 258i47
TNT 35/7-24V
Status displays and operational controls
8.2.5Rotary switch S4 for device selection
The S4 rotary switch is used to select the Leuze end device.
Figure 8.5:Rotary switch for device selection
The following switch positions are assigned to the Leuze devices:
Leuze deviceSwitch positionLeuze deviceSwitch position
Standard setting
Other RS 232 devices such as
KONTURflex QUATTRO
BCL 8 1 Hand scanner8
BCL 22 2
n.c.3 BPS 8A
BCL 300i, BCL 500i,
BCL 600i
BCL 90, BCL 900i5 MA 3xC
LSIS 122, LSIS 2226 Reset to factory setting F
The gateway is set via the switch position on the Leuze device. If the switch position is
changed, the device must be restarted, since the switch position is only queried after
switching off completely and then restarting the device.
0 LSIS 4x2i, DCR 202i7
4
RFID (RFI xx,
RFM xx, RFU xx)
ODS 9, ODSL 30, ODSL 96B,
BPS 300i
9
B
Notice!
In switch position "0", a distance of >20ms must be maintained between two telegrams so
they can be distinguished from one another.
The parameters of the Leuze end devices are described in chapter 16.
48MA 258iLeuze electronic
9Configuration
The MA 258i can be configured using the EDS file via the device manager of the control. In
case the PLC does not (yet) offer this service (RSLogix 5000 supports it from version 20.00
and up), a generic module and the manual config assembly must be employed.
The connected device is normally configured via the service interface of the MA with the
help of a suitable configuration program.
The respective configuration programs – e.g. for bar code readers the BCL-Config, for RFID
devices the RF-Config etc. – and the associated documentation is provided on the Leuze
home page www.leuze.com in the respective Download area.
Notice!
In order to display the help texts, a PDF viewer program (not included in the delivery contents)
must also be installed. For important information on configuring and on the configurable
functions, please refer to the description of the respective device.
9.1Connecting the service interface
The RS 232 service interface is connected after opening the device cover of the MA 258i
via the 9-pin Sub-D and a cross-wired null modem cable (RxD/TXD/GND). For connection,
see chapter "Service interface (internal)" on page 42.
The service interface is activated with the help of the service switch and establishes a direct
connection to the connected device with the "DEV" (Leuze device) or "MA" (gateway)
setting.
Configuration
9.2Reading out information in Service mode
After starting up in the "RUN" switch position, set the service switch of the MA to the
"MA" position.
Now start one of the following terminal programs: e.g., BCL, RF, BPS Config.
Alternatively, you can also use the Windows tool "Hyperterminal".
Start the program.
Select the correct COM port (e.g., COM1) and set the interface as follows:
Leuze electronicMA 258i49
TNT 35/7-24V
Configuration
Figure 9.1:COM port settings
Notice!
Observe that STX, data, CR, LF framing must be set on the PC terminal program so that
communication is possible with the connected Leuze device.
Commands
You can now call up information on the MA 258i by sending the following commands.
vGeneral service information.
sEnable memory mode for the last frames.
lThe memory mode shows the last RX and TX frames for ASCII and fieldbus.
Table 9.1:Available commands
Information
VersionVersion information.
Firmware dateFirmware date.
Table 9.2:General firmware information
50MA 258iLeuze electronic
Configuration
Selected scannerCurrently selected Leuze device (selected via switch S4).
Gateway modeTransparent or Collective mode.
Ring buffer fill levelCurrent fill level of the ring memory in Collective mode (ASCII->Fieldbus).
Received ASCII FramesNumber of received ASCII frames.
ASCII Framing Error (GW)Number of received framing errors.
Number of Received CTB'sNumber of CTB commands.
Number of Received SFB'sNumber of SFB commands.
Command-Buffer fill levelCurrent fill level of the ring memory in Command mode (fieldbus->ASCII).
Number of received transparent framesNumber of received fieldbus frames without CTB/SFB.
Number of send fieldbus framesNumber of frames sent via the fieldbus.
Number of invalid commandsNumber of invalid commands.
Number of ASCII stack send errorsNumber of frames that the ASCII memory could not send.
Number of good ASCII send framesNumber of frames that the ASCII memory sent successfully.
Table 9.3:General gateway information
NDCurrent status of ND bit.
W-AckCurrent status of W-Ack bit.
R-AckCurrent status R-Ack bit.
Data lossCurrent status of data loss bit.
Ring buffer overflowCurrent status of ring buffer overflow bit.
Ring buffer overflow (internal) Current status of ring buffer overflow bit (internal status).
Ring buffer CTB/SFB (internal)Current status of CTB and SFB bits.
DEXCurrent status of DEX bit.
BLRCurrent status of BLR bit.
Table 9.4:Current states of the status and control bits
ASCII warm start statusIndicates whether the ASCII memory has detected and accepted a valid
(dependent on switch position S4).
(dependent on switch position S4).
(dependent on switch position S4).
(dependent on switch position S4).
configuration.
Table 9.5:ASCII configuration
EIS input data length Length of the data received (consumed data, default 4 bytes).
EIS output data length Length of the data supplied (produced data, default 18 bytes).
IP addressDisplays the set IP address.
Leuze electronicMA 258i51
TNT 35/7-24V
Configuration
Gateway addressDisplays the set gateway address.
Network maskDisplays the set network mask.
DHCPDHCP mode (ENABLED/DISABLED).
Table 9.6:Communication parameters MA 258i
52MA 258iLeuze electronic
10Telegram
10.1Structure of the fieldbus telegram
All operations are performed by control and status bits. Two bytes of control information
and two bytes of status information are available for this purpose. The control bits are a part
of the output module and the status bits are a part of the input bytes. The data starts with
the third byte.
If the actual data length is longer than the data length configured in the gateway, only part
of the data is transmitted; the remaining data is lost. In this case, the DL (data loss) bit is set.
The following telegram structure is used between PLC -> fieldbus gateway:
Data byte / parameter byte 0Data
Data byte / parameter byte 1
…
This telegram structure is used between fieldbus gateway -> PLC:
76543210
NDBODLBLRDEXSMAW-ACKStatus byte 0
mode
Telegram
Control byte 0
DLC7DLC6DLC5DLC4DLC3DLC2DLC1DLC0Status byte 1
Data byte / parameter byte 0
Data byte / parameter byte 1
…
Data
Only the data part with the corresponding frame (e.g., STX, CR & LF) is then transmitted
between the fieldbus gateway and the Leuze end device. The two control bytes are
processed by the fieldbus gateway.
The corresponding control and status bits and their meaning are specified in section 10.2
and section 10.3.
Further information on the broadcast control bytes and address bits 0 … 4 can be found in
chapter "Modular interfacing unit MA 3x (S4 switch position C)" on page 110.
Leuze electronicMA 258i53
TNT 35/7-24V
Telegram
10.2Description of the input bytes (status bytes)
10.2.1 Structure and meaning of the input bytes (status bytes)
76543210
NDBODLBLRDEXSMAW-ACKStatus byte 0
DLC7DLC6DLC5DLC4DLC3DLC2DLC1DLC0Status byte 1
Data byte / parameter byte 0
Data byte / parameter byte 1
…
Data
Table 10.1:Structure of the input bytes (status bytes)
Bits of the input byte (status byte) 0
Bit no.DesignationMeaning
0W-ACKWrite-Acknowledge (write confirmation when using buffer)
2SMAService mode active(service mode activated)
3DEXData exist (data in transmit buffer)
4BLRNext block ready (new block ready)
5DLData loss
6BOBuffer overflow
7NDNew data only in Transparent mode
Bits of the input byte (status byte) 1
Bit no.DesignationMeaning
0…7DLC0… DLC7Data Length Code (length of the following user data)
Notice!
T-bit means toggle bit, i.e. this bit changes its state on each event ("0" → "1" or "1" → "0").
54MA 258iLeuze electronic
10.2.2 Detailed description of the bits (input byte 0)
Bit 0: Write-Acknowledge: W-ACK
This bit is only relevant for writing slave data in blocks, see chapter 11.1.2 (buffer data on
RS 232). It toggles when data from the PLC are sent to the MA with CTB or SFB.
Telegram
Input dataDescriptionAddr. Data
Write-Acknowledge
(write confirmation)
Write handshake
Indicates that the data was successfully sent by the PLC to
W-ACK
the gateway.
Write-Acknowledge is indicated via this bit. The W-ACK bit
is toggled by the fieldbus gateway whenever a transmit command has been successfully executed. This applies both for
the transmission of data to the transmit buffer with the CTB
command and for sending the transmit buffer contents with
the SFB command.
0.0Bit
Value rangeDefault
type
0->1: Successfully
written
1->0: Successfully
written
0
Bit 2: Service mode active: SMA
Input dataDescriptionAddr. Data
Service mode active (SMA)
The SMA bit is set if the service switch is set to "MA" or
SMA
"DEV", i.e. if the device is in either fieldbus gateway or Leuze
device service mode. This is also indicated by a flashing PWR
LED on the front side of the device. Upon changing to the normal operating mode "RUN", the bit is reset.
0.2Bit
Value rangeDefault
type
0: Device in
operating mode
1: Device in service
mode
0h
Bit 3: Data exist: DEX
This bit is only relevant for reading slave data in Collective mode relevant, see chapter 11.1.1.
Input dataDescriptionAddr. Data
Data exist
(data in transmit buffer)
DEX
Indicates that further data is stored in the transmit buffer
which is ready for transmission to the control. This flag bit is
always set to high ("1") by the fieldbus gateway as long as
data is in the buffer.
0.3Bit
Value rangeDefault
type
0: No data in the
transmit buffer
1: Further data in
the transmit buffer
0h
TNT 35/7-24V
Leuze electronicMA 258i55
Telegram
Bit 4: Next block ready to transmit: BLR
This bit is only relevant for reading slave data in Collective mode relevant, see chapter 11.1.1.
Input dataDescriptionAddr. Data
Next block ready to transmit
(new block ready)
The Block Ready toggle bit changes its state whenever the
BLR
fieldbus gateway has removed received data from the
receive buffer and registered it in the corresponding receivedata bytes. This signals to the master that the quantity of data
indicated in the DLC bits to be present in the input data bytes
originated in the data buffer and is current.
0.4Bit
Value rangeDefault
type
0->1: Data
transmitted
1->0: Data
transmitted
0
Bit 5: Data loss: DL
This bit is important for monitoring data transmission in Transparent and Collective mode.
Input dataDescriptionAddr. Data
Data loss
(Data transmission monitoring)
This bit is set until the device is reset (bit pattern see chapter
10.4 "RESET function / deleting memory") in case gateway
DL
data was not able to be sent to the PLC and was lost. Furthermore, this bit is set in case the configured data frame,
e.g. 8 bit, should be smaller than the data to be transmitted
to the PLC, e.g. bar code with 20 digits. In this case, the first
8 digits are transmitted to the PLC, the rest are truncated and
are lost. In this process, the Data loss bit is also set.
0.6Bit
Value rangeDefault
type
0->1:
Data loss
0
Bit 6: Buffer overflow: BO
Input dataDescriptionAddr. Data
Buffer overflow
(buffer overflow)
This flag bit is set to high ("1") when the buffer overflows.
BO
The bit is automatically reset when the buffer again has
memory space available. While the BO bit is set, the RTS signal of the serial interface is deactivated.
The memory size of the gateway for the data of both the PLC
and the Leuze end device is 1 kByte.
0.6Bit
Value rangeDefault
type
0->1: Buffer
overflow
1->0:
Buffer o.k.
0
56MA 258iLeuze electronic
Bit 7: New data: ND
This bit is only relevant in Transparent mode.
Telegram
Input dataDescriptionAddr. Data
New data
ND
(new data)
This bit is toggled on each data set that is sent from the gateway to the PLC. This can be used to differentiate between
multiple, identical data sets that are sent to the PLC.
0.7Bit
Value rangeDefault
type
0->1; 1->0:
On each status
change for new data
10.2.3 Detailed description of the bits (input byte 1)
Bit 0 … 7: Data length code: DLC0 … DLC7
Input dataDescriptionAddr. Data
Data length code
DLC0 … DLC7
(number of user data in bytes)
Stored in these bits is the number of user data bytes
transmitted to the PLC which follow.
1.0 …
1.7
Value rangeDefault
type
1
Bit
FF
10.3Description of the output bytes (control bytes)
10.3.1 Structure and meaning of the output bytes (control bytes)
Table 10.2:Structure of the output bytes (control bytes)
Command
(00001b) …
h
(00255b)
h
mode
0
0h (00000b)
Control byte 0
DataData byte 2
TNT 35/7-24V
Bits of the output byte (control byte) 0
Bit no.DesignationMeaning
0Command modeCommand mode
1BroadcastBroadcast
(only relevant with a connected MA 3x)
2 … 6Address 0 .. 4 Address bits 0 .. 4
(only relevant with a connected MA 3x)
7NDNew data
Leuze electronicMA 258i57
Telegram
Bits of the output byte (control byte) 1
Bit no.DesignationMeaning
0R-ACKRead-Acknowledge
2SFBSend data from transmit buffer
3CTBCopy to transmit-buffer
10.3.2 Detailed description of the bits (output byte 0)
Bit 0: Command mode: Command mode
Output dataDescriptionAddr. Data
Command mode
This bit is used to activate Command mode. In Command
Command mode
mode, no data is sent by the PLC to the Leuze end device via
the gateway. In Command mode, various bits that execute
corresponding commands depending on the selected Leuze
device can be set in the data- or parameter field. For further
information, see chapter 11.1.3 "Command mode".
0.0Bit
Value rangeDefault
type
0: Default,
transparent data
transmission
1: Command mode
0
The following two control bits ("Bit 1: Broadcast: Broadcast" on page 58 and "Bits 2 … 6:
address bits 0 .. 4: address 0 .. 4" on page 58) are only relevant with a connected MA 3x.
With other devices, these fields are ignored.
Bit 1: Broadcast: Broadcast
Output dataDescriptionAddr. Data
Broadcast
Broadcast
A broadcast only functions with a multiNet network connected via the MA 3x. If this bit is activated, the gateway
automatically adds the broadcast command "00B" before
the data. This is directed at all participants in the multiNet.
0.1Bit
Value rangeDefault
type
0: No broadcast
1: Broadcast
0
Bits 2 … 6: address bits 0 .. 4: address 0 .. 4
Output dataDescriptionAddr. Data
Address bits 0 .. 4
Address 0..4
As with the broadcast command, individual devices in the
multiNet can also be addressed via the MA 3x . In this case,
the corresponding address of the device precedes the data
field telegram.
0.2
…
0.6
Value rangeDefault
type
00000: Addr. 0
00001: Addr. 1
Bit
00010: Addr. 2
00011: Addr. 3
…
0
Bit 7: New data: ND
Output dataDescriptionAddr. Data
ND
New data
This bit is needed if several identical pieces of data are to be
sent in sequence.
0.7Bit
Value rangeDefault
type
0->1; 1->0:
On each status
change for new data
0
58MA 258iLeuze electronic
10.3.3 Detailed description of the bits (output byte 1)
Bit 0: Read-Acknowledge: R-ACK
This bit is only relevant for writing slave data in blocks (Collective mode), see chapter 11.1.2.
Telegram
Output dataDescriptionAddr. Data
Read-Acknowledge
(read confirmation)
Toggle bit: Indicates to the fieldbus gateway that the "old"
data has been processed and that new data can be
received. At the end of a read cycle, this bit must be toggled
R-ACK
in order to be able to receive the next data set. This toggle
bit is switched by the master after valid received data has
been read out of the input bytes and the next datablock can
be requested. If the gateway detects a signal change in the
R-ACK bit, the next bytes are automatically written from the
receive buffer to the input data words and the BLR bit toggled. Further toggling erases the memory (to 00h).
1.0 Bit
Value rangeDefault
type
0->1 or
1->0: Successfully
written & ready for
the next transmission
0
Bit 2: Send data from buffer: SFB
This bit is only relevant for writing slave data in blocks (Collective mode), see chapter 11.1.2.
Output dataDescriptionAddr. Data
Send data from buffer
(send data from the gateway transmit buffer to the RS 232)
SFB
Toggle bit: changing this bit causes all data which was copied
to the transmit buffer of the fieldbus gateway via the CTB bit
to be transmitted to the RS 232 interface or the connected
Leuze device.
1.2Bit
Value rangeDefault
type
0->1: Data to
RS 232
1->0: Data to
RS 232
0
TNT 35/7-24V
Leuze electronicMA 258i59
Telegram
Bit 3: Copy to transmit buffer: CTB
This bit is only relevant for writing slave data in blocks (Collective mode), see chapter 11.1.2.
Output dataDescriptionAddr. Data
Copy to transmit buffer
(transmission data to transmit buffer)
Toggle bit: Changing this bit writes the data from the PLC to
CTB
the transmit buffer of the fieldbus gateway. This is used, for
example, for long command strings which must be transmitted to the connected ident device.
The CTB toggle bit is switched whenever transmit data is not
to be sent directly via the serial interface, but instead transferred to the transmit buffer.
Notice!
The state change of the CTB bit signals the MA that the data is going into the buffer; therefore,
it's essential to observe the order!
When the CTB is not used, the telegram (which fits in one cycle) is transmitted directly to
the RS 232 interface. Please make sure it is complete!
10.4RESET function / deleting memory
For many applications, it is helpful to be able to reset the MA buffer (in Collective mode) or
status bits.
The following bit pattern can be transmitted from the PLC for this purpose (if >20 ms is
pending):
Control byte 0:10101010 (AAh)
Control byte 1:10101010 (AAh)
OUT data byte 0/parameter byte 0: AAh
OUT data byte 1/parameter byte 1: AAh
1.3Bit
Value rangeDefault
type
0->1: Data in buffer
1->0: Data in buffer
0
This sets the memory or status/control bits to 00h.
Please observe that the data image may need to be updated by toggling in Collective mode.
60MA 258iLeuze electronic
11Modes
11.1Functionality of the data exchange
The fieldbus gateway has two different modes that can be selected via the PLC:
• Transparent mode (standard setting)
In Transparent mode, all data is sent 1:1 and directly by the serial end device to the
PLC. It is not necessary to use status and control bits here. However, only data bytes
possible for one transmission cycle are transmitted - all others are lost.
The distance between two successive telegrams (without frame) must be more than
20ms, since there is otherwise no clear separation between them.
ASCII characters are typically expected as data content; under certain circumstances,
the MA therefore detects different control characters as invalid characters in the data
range and truncates them. At 00
because unnecessary bytes are also filled with 00
• Collective mode
In Collective mode, the data of the serial end device is stored temporarily in the fieldbus
gateway by toggling the CTB bit and is not sent to the PLC in blocks until prompted
to do so by the PLC.
On the PLC, a status bit (DEX) then signals that new data is ready for retrieval. This
data is then read out from the fieldbus gateway in blocks (toggle bit).
In order to distinguish between the individual telegrams on the PLC, in Collective mode
the serial frame is sent to the PLC in addition to the data.
The size of the buffer is 1 kByte.
in the data range, the MA cuts the telegram off
h
Modes
.
h
Notice!
In Collective mode, the CTB and SFB bits are needed for communication handling via the
buffer. Telegrams that can also be completely transmitted in one cycle in Collective mode
(including data frame) go directly through. If PLC data is provided and transferred without a
state change of the CTB bit, it goes directly to the RS 232 interface with the set telegram
data length. Incomplete (incl. data frame) or faulty telegrams can cause error messages in
the connected device!
Combination with the Command mode is possible.
Data exchange in blocks must be programmed on the PLC.
Leuze electronicMA 258i61
TNT 35/7-24V
Modes
11.1.1 Reading slave data in Collective mode (gateway -> PLC)
If the Leuze device transmits data to the fieldbus gateway, the data is stored temporarily in
a buffer. The PLC is signaled via the "DEX" bit that data is ready for retrieval in the memory.
Data is not automatically transmitted.
If no further user data is present in the MA 258i ("DEX" bit = "0"), the "R-ACK" bit must be
toggled once as read confirmation to release data transmission for the next read cycle.
If the buffer still contains more data ("DEX bit = 1), the next remaining user data present in
the buffer is transmitted by toggling the "R-ACK" control bit. This process is to be repeated
until the "DEX" bit returns to "0"; all data has then been removed from the buffer. "R-ACK"
must be toggled here again once more as a terminating read confirmation in order to release
data transmission for the next read cycle.
Used status and control bits:
•DLC
•BLR
•DEX
•R-ACK
11.1.2 Writing slave data in Collective mode (PLC -> gateway)
Writing in blocks
The data sent by the master to the slave is first collected in a "transmit buffer" by setting
the "CTB" bit (Copy to transmit buffer). Please observe that data provided is transmitted
directly by toggling the bit.
The data is then sent in the order received from the buffer to the connected Leuze device
via the serial interface with the command: "SFB" (Send data from transmit buffer). Please
don't forget the suitable data frame!
Afterward, the buffer is again empty and can be written with new data.
Notice!
With this function, it is possible to temporarily store longer data strings in the gateway independent of how many bytes the used fieldbus can transmit at once. With this function, longer
PT sequences or RFID write sequences, for example, can be transmitted, since the connected devices can, in this way, receive their commands (e.g., PT or W) in a continuous string.
The respective frame (STX CR LF) is needed to differentiate between the individual telegrams.
Used status and control bits:
•CTB
•SFB
•W-ACK
If PLC data is provided and transferred without a state change of the CTB bit, it goes directly
to the RS 232 interface with the set telegram data length. Incomplete (incl. data frame) or
faulty telegrams can cause error messages in the connected device!
62MA 258iLeuze electronic
Modes
Examples for the activation of a Leuze device
In the data part (starting at byte 2) of the telegram to the gateway, a "+" (ASCII) is sent for
activation.
This means that the hex value "2B" (corresponds to a "+") is to be entered in control or output
byte 2. To deactivate the reading gate, a "2D" (hex) must be used instead (corresponds to
a "-" ASCII).
Send long online commands to the DEV, read RS 232 answer from DEV
64MA 258iLeuze electronic
Figure 11.1: Data transmission scheme with long online commands
11.1.3 Command mode
One specific feature is the so-called Command mode, which is defined via the output control
byte 0 (bit 0) ... and enables the control of the connected device per bit.
If the command mode is activated (command mode = 1), no data is sent by the PLC to the
Leuze end device via the gateway. The data from the MA to the PLC is transmitted in the
selected operating mode (Transparent/Collective).
With the Command mode, it is possible to set various device-specific bits in the data- or
parameter field that execute the corresponding serial commands (e.g., v, +, -, etc.). If, for
example, the version of the Leuze end device is to be queried, the corresponding bit is to
be set so that a "v" is sent to the Leuze device with the <STX> v <CR> <LF> frame.
The Leuze end device also answers the gateway with data (e.g. bar code content, NoRead,
device version, etc.) in response to most commands. The answer is immediately passed on
to the PLC by the gateway.
Notice!
The parameters available for the individual Leuze devices are listed in chapter 16.
Command mode cannot be used with hand-held scanners.
Examples for the activation of a Leuze device
In Command mode, control or output byte 0.0 is to be set for activating the Command mode.
Only the corresponding bit (control or output byte 2.1) then needs to be set for activating
and deactivating the reading gate.
Device executes the corresponding function (cf. chap. 16).
For function to be reestablished, the ND bit and the selected bit
in byte 2 must be toggled, byte 0.0 can stay.
No
No
Yes
Yes
Bit 0.0 =1?
Byte 2:
Bit set?
Connected device can only be
addressed via HW or PLC data
telegram
e.g. +
Bit 0.0 signals that the respective bit
is evaluated as a "control bit" in
byte 2, and according to the position of the device selection switch,
executes a corresponding function
on the device via the stored table.
No detectable function
Select bit, or incorrect byte
Command mode sequence diagram
Set control byte 0, bit 0.0 to 1
Figure 11.2: Execution of command after activation of the Command mode
66MA 258iLeuze electronic
Triggering the ident devices and reading the data
Triggering scanner
Reception of data
Has the slave re-
ceived data from the
RS 232?
BLR = ! BLR
Rescue data
e.g. data block
DLC = number of valid
binary-coded data bytes
Is there still data
in the receive buffer?
DEX = 1 set
(status bit 0.3)
Transmit the next
data with toggle bit
R-ACK = ! R-ACK
(control bit 1.0)
Confirm data retrieval
with toggle bit
R-ACK = ! R-ACK
(control bit 1.0)
No
No
Yes
Modes
Figure 11.3: Activating DEV and reading data
Notice!
Further information on fieldbus telegram structure can be found in chapter 10.1. A specification
of all usable commands can be found in chapter "Specifications for Leuze end devices" on
page 97.
Leuze electronicMA 258i67
TNT 35/7-24V
Commissioning and configuration
M12 connector
(A-coded)
M12 socket
(A-coded)
M12 socket
(D-coded)
M12 socket
(D-coded)
12Commissioning and configuration
12.1Measures to be performed prior to the initial commissioning
Before commissioning, familiarize yourself with the operation and configuration of the
MA 258i.
Before connecting the supply voltage, recheck all connections and ensure that they
have been properly made.
The Leuze device must be connected to the internal RS 232 device interface.
Connecting the Leuze device
Open the housing of the MA 258i and lead the corresponding device cable (see chapter
14.6) through the middle threaded opening.
Connect the cable to the internal device interface (X30, X31 or X32, see chapter 7.5.1).
Use rotary switch S4 (see chapter 8.2.5) to select the connected device.
Now screw the PG cable gland into the threaded opening to provide strain relief and
ensure protection class IP 65.
Finally, close the housing of the MA 258i.
Attention!
Only then may the supply voltage be applied.
Upon startup of the MA 258i, the device selection switch is queried and the gateway automatically sets itself to the Leuze device.
PWR IN
SWIO_2
GNDVIN
321
5
4
FE
SWIO_1
VOUT
PWR OUT
SWIO_2
123
5
4
SWIO_1
LEUZE Device
GND
FE
HOST / BUS IN
RD+
TD+
123
4
RD-
TD-
TD+
Figure 12.1: Connections of the MA 258i seen from below, device on mounting plate
Check the applied voltage. It must be in the range between +18V … 30VDC.
Connecting functional earth FE
Ensure that the functional earth (FE) is connected correctly.
Unimpaired operation is only guaranteed when the functional earth is connected properly.
All electrical disturbances (EMC couplings) are discharged via the functional earth connection.
On delivery, the SWIO 1/2 are connected in parallel on PWR IN/OUT. This connection can
be separated with a jumper.
68MA 258iLeuze electronic
BUS OUT
RD+
123
4
RD-
TD-
Commissioning and configuration
12.2Starting the device and setting the communication parameters
As a first step, you need to start the device and set the communication parameters of the
MA 258i. With the communication parameters, you determine how data is exchanged
between the MA and host system, monitor PCs etc.
The communication parameters are independent of the topology in which the MA 258i is
operated (see "EtherNet topologies" on page 34).
On delivery, the automatic address assignment via DHCP server is defined as the standard
setting of the MA 258i.
12.2.1 Manually setting the IP address
To set the IP address manually, the DHCP operation via BootP or the Rockwell control must
be deactivated.
Figure 12.2: Manually setting the IP address
If your system does not include a DHCP server or if the IP addresses of the devices are to
be set permanently, proceed as follows:
Have the network administrator specify the data for IP address, net mask and gateway
address of the MA 258i.
Leuze electronicMA 258i69
TNT 35/7-24V
Commissioning and configuration
Figure 12.3: Making network settings
Select the connected device via the device selection switch.
Apply the supply voltage +18 … 30VDC (typ. +24VDC); the MA 258i starts up.
Now switch the service switch to "MA".
Now start a web browser by entering the IP address into the navigation bar. You will be
shown a page for the direct setting of the addresses.
Notice!
The service switch must be in switch position "MA" for the MA 208i to start in configuration
mode.
Connect the serial RS 232 Sub-D interface of the MA 258i to the serial interface of your
computer.
Make the respective settings on the configuration page opened in the web browser.
70MA 258iLeuze electronic
Commissioning and configuration
12.3Configuration steps for a Rockwell control without EDS support
12.3.1 Integrating the hardware into the PLC using the generic EtherNet module
In the RSLogix 5000 configuration tool for EtherNet/IP, software version <20.00, a so-called
"generic EtherNet module" is created for the MA 258i under the Communication path.
Figure 12.4: Generic module
Leuze electronicMA 258i71
TNT 35/7-24V
Commissioning and configuration
Figure 12.5: Assembly list
The input mask for the generic module describes:
• The name of the participant (can be selected freely; e.g.MA 258i).
• The format of the I/O data (data - DINT = 32bit or data - SINT = 8bit).
• The IP address of the participant.
• The address and length of the input assembly (instance 107). *)
• The address and length of the output assembly (instance 106). *)
• Optional: The address and length of the configuration assembly (instance 118;
12 x 8bit).
*) The possible data lengths are shown in figure 12.5. You can select the suitable byte
number for your application here. Recommendations can be found in chapter
"Specifications for Leuze end devices" on page 97.
Notice!
The available lengths (4, 8, 12, 16, 20, 32, 64, 128, 240 bytes) of the input/output data cannot
be freely combined. The MA can only process ONE combination (connection). Please select
the suitable combination for the data length and the connected device. Detailed information
on this topic can be found in chapter 12.6.2.
72MA 258iLeuze electronic
Attention!
If the configuration assembly is addressed with instance 118 and length 12 in the input mask
for the generic module, all MA 258i parameters with the value 0 are occupied in the first
moment. All default parameters of the MA must be manually entered in the configuration
assembly. Changing the individual default values is possible at any time.
For the exact description of the assemblies for input/output and configuration, please refer
to chapter 12.6.2.
The query cycle of the input and output assemblies is subsequently defined in the Moduleproperties -> Connection path in the Request packet interval (RPI) input field.
The participant is thereby defined in offline mode; the data must subsequently be transferred
to the control.
12.3.2 Configure the config assembly
The MA 258i makes available a configuration assembly that allows the entire parameter set
of the MA 258i to be saved in the control and, if necessary, to be called up.
The config assembly must include all parameters that affect the MA 258i. The config
assembly is automatically written to the connected participants in cycles that the control
manufacturer defines.
The config assembly is implemented in class 4, under instance 118. By default, all parameters are preset to the value 0 (zero).
Commissioning and configuration
Attention!
If the config assembly is not adapted, the MA 258i displays a corresponding behavior acc.
to the parameters preset with 0.
Switch the control to offline mode.
Double-click
The configuration assembly can be recognized by the index "C" appended to the device
name.
Parameter entry is performed as described in section "Setting MA parameters manually via
the config assembly" on page 74.
Leuze electronicMA 258i73
Controller tags
to edit the configuration assembly.
TNT 35/7-24V
Commissioning and configuration
Attention!
Activation of the config assembly as described above necessitates value entry in the corresponding parameter memory locations. When using the configuration assembly, the default
parameters must also be entered in the corresponding memory locations (see also "Setting
MA parameters manually via the config assembly" on page 74).
After all of the parameters relevant to the MA 258i are entered, the control is switched to
"online" and the project is downloaded again.
Setting MA parameters manually via the config assembly
Notice!
If the device was integrated into an older-version control without EDS support using the
generic module, the following option exists to change parameters of the MA:
After setting up the device with the generic module, the MA appears in the RSlogix software
in the file structure on the left among the
Display the reserved control area (MA200.C in this case) by double-clicking on the MA
entry.
Now enter the parameters manually into bytes 00-11.
Subsequent adaptations may be made by changing the respective position.
Please find a detailed description of the Leuze-specific assembly in chapter 12.6.2.
Byte 00+01: DataMode (collective/transparent mode)
Byte 02+03: Serial line mode (rotary / EDS)
Byte 04+05: Baud rate (9600Bd)
Byte 06+07: Data bits (7/8 data bits)
Byte 08+09: Parity (N/E/O)
Byte 10+11: Stop bits (1/2)
Controller tags
.
74MA 258iLeuze electronic
Commissioning and configuration
Figure 12.6: Entering the byte parameters
Transfer the settings made to the device via EtherNet module -> Properties via Reset
module.
Figure 12.7: Transferring manual MA settings to the device
Leuze electronicMA 258i75
TNT 35/7-24V
Commissioning and configuration
12.4Configuration steps for a Rockwell control with EDS support
The following steps are necessary for commissioning with a Rockwell control:
• Creation of the EtherNet participants in PLC software RSLogix 5000 from Version
20.00 and up (with EDS support)
• Installation of the EDS file using the EDS wizard.
• Setting the parameters on the MA via the module.
12.4.1 Integrating the hardware into the PLC and installing the EDS file
To integrate the device and to establish a connection between the PLC and the device
MA 258i, proceed as follows:
First, load the EDS file for the device via EDS wizard into the PLC database.
Notice!
You can find the EDS file at www.leuze.com.
After loading, select the device via the device list and enter it into the HW manager via
Drag&Drop.
Open the input dialog for setting the address and additional parameters by double-
clicking on the device symbol and make the desired entries here.
Finally, transmit the values to the device via download.
12.4.2 Setting the parameters on the MA
After the EDS file has been integrated, the device must be created as a "module" to establish
a connection. It is also helpful to assign an IP address to the MA beforehand, e.g. via the
service interface.
To do this, double-click on the tree node EtherNet.
In the new window, select the desired device from the database and carry out the
respective configuration.
76MA 258iLeuze electronic
Figure 12.8: Creating a module
First set the IP address.
Commissioning and configuration
Figure 12.9: Setting the IP address of the MA
Attention!
The IN/OUT combinations can only be selected from the list!
Leuze electronicMA 258i77
TNT 35/7-24V
Commissioning and configuration
Then, via the Change button, select the input/output data length of the module from a
list of possible combinations by clicking on Connection.
Notice!
The available lengths (4, 8, 12, 16, 20, 32, 64, 128, 240 bytes) of the input/output data are
stored here in "fixed" combinations. They cannot be freely combined. The MA can only process ONE combination (connection).
Please select the suitable combination for the data length and the connected device. For
further information, see chapter 16 "Specifications for Leuze end devices".
Figure 12.10: Select combination for the lengths of the input and output data
Notice!
Since the combination of Produced/Consumed data contains 2 bytes for the control and
status bytes, the actual user data length is always 2 bytes smaller than specified in the
selected combination.
E.g., when using the combination with 12 bytes In/12 bytes Out, there are effectively 10 bytes
available for user data on the Leuze device after subtracting the 2 bytes for status and control
bytes.
Recommendation
A combination with 4 bytes of output data length is sufficient for most output data.
A longer length is needed, for example, if a BCL bar code scanner is to be configured by
means of PT-sequences, or an RFID transponder is to be described. In these cases, larger
combinations are usually advisable.
Select the appropriate combination and transmit the settings to the device.
78MA 258iLeuze electronic
Figure 12.11: MA settings in the controller tags
Commissioning and configuration
Variable configuration of the communication data width
The communication of the MA 2xxi with the fieldbus system can be configured with a variable data width; the upper limit is restricted by the fieldbus. For EtherNet/IP, a value between
4 and 480bytes (240bytes each for input and output data) can be set.
The small data lengths (< 28 bytes) are particularly of interest for use with bar code scanners
(BCL). The larger data lengths are, on the other hand, relevant for 2D-code scanners (handheld scanners, LSIS) and RFID.
Notice!
The representation of the (Rockwell) control is usually set to double word (DINT, 4 bytes).
Please observe that in this representation, the byte sequence can vary in contrast to the read
code. We thus recommend creating the settings using SINT.
After all parameters have been set in the planning tool/control, the download to the MA 258i
takes place. The set parameters are now stored on the MA 258i.
Afterwards, all MA 258i parameters should be stored via upload in the control. This aids in
retaining the parameters during device exchanges, as they a re now also stored centrally in
the control.
Leuze electronicMA 258i79
TNT 35/7-24V
Commissioning and configuration
Each time a connection is established between the control and the MA 258i, these parameters are now transmitted again to the MA 258i. Note that this function must be supported
by the control.
The EtherNet baud rate is defined for the entire network in the planning tool/control. The
baud rate is set on the MA 258i via the S3 baud rate selector switch.
Only if the baud rates are the same is communication with the MA 258i possible.
12.5EDS file - general info
The EDS file contains all identification and communication parameters of the device, as well
as the available objects. PLC software RSLogix 5000 from Rockwell offers EDS support for
EtherNet/IP from software version 20.00 and up.
The MA 258i is uniquely classified via a class 1 identity object (component of the
MA258i.eds file) for the EtherNet master.
The identity object contains, among other things, a manufacturer-specific vendor ID, as well
as an ID that describes the principle function of the participant.
The MA 258i has the following identity object (class 1):
Vendor ID: 524
Device type: 12
./ 20C
dec
H
/ 0CH (labels the MA 258i as "communications adapter")
dec
Position sensor type: product type 04 (specifies the MA 258i as "gateway")
The types of communication access to the data of the MA 258i described by the ODVA:
•Polling
•Cyclic
• Combinations of polling and cyclic
are supported by the MA 258i.
Communication access via change of state is not implemented and must not be activated
in the network configuration.
If accepting the objects without change, all parameters are set to default values. The default
settings are shown in the objects described in detail in the "Default" column.
Notice!
In the following tables, all attributes marked in the "Access" column with "Get" in the
individual objects are to be understood as inputs of the MA (control).
Attributes marked in the "Access" column with "Set" represent outputs or parameters.
In the network configuration (e.g., RSNetWorx, "generic module"), it is possible to specify
when entering the individual participants which attributes of the scanner are to be monitored
from the identity object.
12.6.1.1 Vendor ID
The Vendor ID assigned by ODVA for Leuze electronic GmbH + Co. KG is 524D.
12.6.1.2 Device type
The MA 258i is defined by Leuze electronic as a "communications adapter". According to
ODVA, the MA 258i is assigned number 12
12.6.1.3 Product Code
The product code is an ID assigned by Leuze electronic that has no further impact on other
objects.
12.6.1.4 Revision
Version number of the identity object.
Designation
Revision
(Major, minor)
Product name (max. 32)
Size
in bit
16Struct{
x 8
Data type
USINT major,
USINT minor};
SHORT_STRING"MA 258i"Get
=0CH.
D
Default
(dec)
Major = 1,
Minor = 1
Min
(dec)
Major = 1,
Minor = 1
Max
(dec)
Major = 127,
Minor = 999
Access
Get
TNT 35/7-24V
Leuze electronicMA 258i81
Commissioning and configuration
12.6.1.5 Status
The device status is displayed in the status byte, the first part of the telegram.
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
Bit 15Bit 14Bit 13Bit 12Bit 11Bit 10Bit 9Bit 8
ext. device state
12.6.1.6 Serial number
For use in EtherNet, the serial number receives a serial number converted according to CIP.
CIP describes a special format for the serial number. After conversion to a CIP code, the
serial number is, as before, unique, but no longer corresponds in its resolution to the serial
number on the name plate.
12.6.1.7 Product name
This attribute contains a short designation of the product. Devices with the same product
code may have different "product names".
12.6.2 Class 4 assembly object
Object class 4=04
Services:
• Get Attribute Single
• Set Attribute Single
Cl.Inst. Attr.
41003 Produced data size32SINT4 bytes--SET
101Consumed data size32SINT4 bytes--GET
102Produced data size64SINT8 bytes--SET
103Consumed data size64SINT8 bytes--GET
104Produced data size96SINT12 bytes--SET
105Consumed data size96SINT12 bytes--GET
106Produced data size128SINT16 bytes--SET
107Consumed data size128SINT16 bytes--GET
108Produced data size160SINT20 bytes--SET
109Consumed data size160SINT20 bytes--GET
110Produced data size256SINT32 bytes--SET
111Consumed data size256SINT32 bytes--GET
112Produced data size512SINT64 bytes--SET
113Consumed data size512SINT64 bytes--GET
114Produced data size1024SINT128 bytes--SET
115Consumed data size1024SINT128 bytes--GET
116Produced data size1920SINT240 bytes--SET
117Consumed data size1920SINT240 bytes--GET
PLC software RSLogix 5000 from Rockwell provides EDS support for EtherNet/IP from software version 20.00 and up only. For older versions without support for the EDS integration,
the respective device can only be created via the "generic module" in the PLC. When doing
so, the values of the input and output data lengths must be manually entered according to
the following table.
H
Designation
Size
in bit
reservedconfiguredreservedowned
reserved
Data type
Default
(dec)
Min
(dec)
Max
(dec)
Access
82MA 258iLeuze electronic
Commissioning and configuration
The following overview shows the combinations of input and output data lengths (Produced/
Consumed data size) available:
CombinationDescriptionInput dataOutput data
Data, 4 In/4 OutData content with max. 2 bytes44
Data, 8 In/8 OutData content with max. 6 bytes88
Data, 12 In/12 OutData content with max. 10 bytes1212
Data, 16 In/16 OutData content with max. 14 bytes1616
Data, 20 In/20 OutData content with max. 18 bytes2020
Data, 32 In/32 OutData content with max. 30 bytes3232
Data, 64 In/64 OutData content with max. 62 bytes6464
Data, 128 In/128 OutData content with max. 126 bytes128128
Data, 240 In/240 OutData content with max. 238 bytes240240
Data, 20 In/4 OutData content with max. 18 /2 bytes204
Data, 64 In/4 OutData content with max. 62 /2 bytes644
Data, 20 In/8 OutData content with max. 18 /6 bytes208
Data, 64 In/8 OutData content with max. 62 /6 bytes648
Table 12.1:Overview of all possible combinations of input and output data lengths
Leuze electronicMA 258i83
TNT 35/7-24V
Commissioning and configuration
12.6.2.1 Configuration instance
In addition, all values of the configuration (including changes) must be entered manually as
hex/bin values into the "ControlerTags" *.C of the respective device, see "Setting MA parameters manually via the config assembly" on page 74.
Cl.Inst. Attr.
41183 Data Mode8BYTE001Set
Designation
Serial line mode8BYTE
Baud Rate8BYTE
Data Bits8BYTE
Parity8BYTE
Stop Bits8BYTE
Size
in bit
Data type
Default
(dec)
0
see below
96
see below
8
see below
1
see below
1
see below
Min
(dec)
01Set
31152Set
78Set
13Set
12Set
Max
(dec)
Instance 118, attribute 3
Input assembly length 12 byte
Leuze-specific assembly
Byte 00+01: Data mode
Byte 02+03: Serial line mode
Byte 04+05: Baud rate
Byte 06+07: Data bits
Byte 08+09: Parity
Byte 10+11: Stop bits
Data Mode
Parameter value:
0000h = Transparent mode (default)
0
d
0100h = Collective mode
1
d
Byte 0+1: 0000
, LowByte first
h
Serial line mode
Parameter value:
0000h= Use rotary switch (default)
0
d
0100h= Use EDS settings
1
d
Byte 2+3: 0000
, LowByte first
h
Access
84MA 258iLeuze electronic
RS 232 Baud Rate
Parameter value:
0300h =300
3
d
0600h =600
6
d
12
24
48
96
192
384
576
1152
0C00h =1200
d
1800h =2400
d
3000h =4800
d
6000h =9600 (default)
d
C000h =19200
d
8010h =38400
d
4020h=57600
d
8040h =115200
d
Byte 4+5: 6000
RS 232 Data Bits
Parameter value:
0700h = 7 bits
7
d
0800h= 8 bits (default)
8
d
Byte 6+7: 0800
RS 232 parity
Parameter value:
0100h= None (default)
1
d
0200h= Even
2
d
0300h= Odd
3
d
Byte 8+9: 0100
, LowByte first
h
, LowByte first
h
, LowByte first
h
Commissioning and configuration
RS 232 Stop Bits
Parameter value:
0100h= 1 bit (default)
1
d
0200h= 2 bit
2
d
Byte 10+11: 0100
, LowByte first
h
Leuze electronicMA 258i85
TNT 35/7-24V
Commissioning and configuration
12.7Setting the read parameters on the Leuze device
Commissioning the Leuze device
To commission a read station, you must prepare the Leuze device on the MA 258i for its
reading task. Communication with the Leuze device occurs via the service interface.
Notice!
For further information on connecting and using the service interface, see chapter 9 "Configuration".
To do this, connect the Leuze device to the MA 258i.
Depending on the Leuze device, this occurs either via a connection cable (accessory no.:
KB 031-1000) or directly on the MA 258i. The service connector and corresponding
switches can be accessed with the housing cover open.
Select the "DEV" service switch position.
Connect the service interface; call up the terminal program
Connect your PC to the service connector via the RS 232 cable.
On the PC, call up a terminal program (e.g., BCL-Config) and check whether the interface
(COM 1 or COM 2) to which you have connected the MA 258i is set to the following Leuze
standard setting: 9600 baud, 8 data bits, no parity, 1 stop bit and STX, data, CR, LF.
You can download the config. tool from www.leuze.com for BCL, RFID, etc.
In order to communicate with the connected Leuze device, the STX, data, CR, LF framing
must be set on the PC terminal program, as the Leuze device is preconfigured ex works for
this frame character.
STX (02h):Prefix 1
CR (0Dh):Postfix 1
LF (0Ah):Postfix 2
Operation
Switch the MA 258i to switch position "RUN" (operation).
The Leuze device is now connected to the fieldbus. Activation of the Leuze device can now
occur via the switching input on the MA 258i, via the process data word Out bit 1 (bit 0.2)
or by transmitting a "+" command to the Leuze device (see chapter 16 "Specifications for
Leuze end devices"). For further information on the fieldbus transmission protocol, see
chapter 10 "Telegram".
86MA 258iLeuze electronic
Commissioning and configuration
Reading out information in service mode
Set the service switch of the gateway to switch position "MA" (gateway).
Send a "v" command to call up all service information of the MA 258i.
An overview of the available commands and information can be found in chapter "Reading
out information in Service mode" on page 49.
12.7.1 Specific feature for the use of hand-held scanners
(bar code and 2D devices, combi devices with RFID)
Notice!
For a description of device configuration and the required codes, please see the corresponding documentation at www.leuze.com.
12.7.1.1 Cable-connected hand-held scanners on the MA 258i
All hand-held scanners and mobile combi devices available in the Leuze electronic product
line can be used with the corresponding connection cable.
When using the MA 258i, the voltage supply of the hand-held scanner (5V/at 1A) can be
connected to the interface by means of a cable via the 9-pin Sub-D connector (voltage on
PIN 9). The corresponding cable is to be selected for the respective hand-held scanner and
ordered separately. The 9-pin Sub-D cable (KB JST-HS-300, part no. 50113397) is
connected to this cable, which is connected to the MA 258i. This cable must also be ordered
separately.
In this example, triggering occurs by means of a trigger button on the hand-held scanner.
12.7.1.2 Wireless hand-held scanners on the MA 258i
All wireless hand-held scanners and mobile combi devices available in the Leuze electronic
product line can be used with the corresponding connection cable via the base station.
A 230VAC connection (socket) is usually necessary for the charging station. Here, a data
connection of the charging station is established with the MA 258i. The corresponding cable
is to be selected for the respective hand-held scanner and ordered separately. Connect this
cable to the 9-pin Sub-D cable (KB JST-HS-300, part no. 50113397), which is connected
to the MA 258i. This cable must also be ordered separately.
In this example, triggering occurs by means of a trigger button on the hand-held scanner.
The following codes for configuring the devices are necessary for these devices as well.
Leuze electronicMA 258i87
TNT 35/7-24V
Commissioning and configuration
12.7.2 Specific features in the operation of an RFM/RFI
When using the MA 258i in connection with an RFID device, we recommend a data width
of at least 24 bytes to be able to transmit information to or from the reader in a telegram.
Shown here is a sample telegram for a write command in combination with an RFID device.
Notice!
Also note that all characters which are sent to a transponder are hex-encoded ASCII characters. Each of these (hexadecimal) characters is, in turn, to be handled as an individual ASCII
character and converted to hexadecimal format for transmission via the fieldbus.
If problems should occur during commissioning of the MA 258i you can refer to the following
table. Typical errors and their possible causes are described here as well as tips for their
elimination.
13.1General causes of errors
ErrorPossible error causesMeasures
Data loss
(DL bit)
Data in the RS 232
instead of in the
buffer
Data telegram longer than the bus
telegram in bus cycle/memory size.
Incorrect order.
Increase in bus telegram length.
Toggle out data earlier.
Correct order:
Provide data, toggle CTB.
PWR status LED on the circuit board
Off
Green/orange,
flashing
Continuous orange
light
MS LED on the housing (see figure 8.1 on page 43)
OffNo supply voltage connected to the device. Check supply voltage.
Red, flashingIncorrect baud rate / address.
NS LED on the housing (see figure 8.1 on page 43)
Red continuous light Network error.Check wiring.
LINK /ACT LEDs on the housing (see figure 8.1 on page 43)
OffNo connection.Check wiring/IP address.
Table 13.1:General causes of errors
No supply voltage connected to the device. Check supply voltage.
Hardware error.Send the device to customer service.
Device in boot mode.
Device error.
Firmware update failed.
No valid firmware, send device to customer service.
Send the device to customer service.
Check switch settings:
Check baud rate or address.
TNT 35/7-24V
Leuze electronicMA 258i89
Diagnostics and troubleshooting
13.2Interface errors
ErrorPossible error causesMeasures
No communication via
EtherNet/IP interface
Sporadic errors at the
EtherNet/IP interface
Figure 13.1: Interface error
Notice!
Please use chapter 13 as a master copy should servicing be required.
Cross the items in the "Measures" column which you have already examined, fill out the following address field and fax the pages together with your service contract to the fax number
listed below.
Customer data (please complete)
Device type:
Company:
Contact partner / department:
Phone (direct):
Fax:
Street / No:
ZIP code/City:
Country:
Incorrect wiring.Check wiring.
Different protocol settings.Check protocol settings.
Protocol not released.Activate TCP/ IP or UDP.
Incorrect wiring.
Effects due to EMC.
Overall network expansion
exceeded.
Check wiring.
In particular, check wire shielding.
Check the cable used.
Check shielding (shield covering in place up to
the clamping point).
Check grounding concept and connection to
functional earth (FE).
Avoid EMC coupling caused by power cables laid
parallel to device lines.
Check max. network expansion as a function of
the max. cable lengths.
Leuze Service fax number:
+49 7021 573 - 199
90MA 258iLeuze electronic
14Type overview and accessories
14.1Part number code
MA 2xx i
i = Integrated fieldbus technology
Interface04 PROFIBUS DP
08 Ethernet TCP/IP
35 CANopen
38 EtherCAT
48 PROFINET RT
55 DeviceNet
58 EtherNet/IP
MA Modular interfacing unit
14.2Type overview
Type designationDescriptionDescription
MA 204iPROFIBUS gateway50112893
MA 208iEthernet TCP/IP gateway50112892
MA 235iCANopen gateway50114154
MA 238iEtherCAT gateway50114155
MA 248iPROFINET-IO RT gateway50112891
MA 255iDeviceNet gateway50114156
MA 258iEtherNet/IP gateway50114157
Table 14.1:Type overview MA 2xxi
Type overview and accessories
14.3Accessory connectors
Type designationDescriptionDescription
KD 095-5AM12 socket for voltage supply50020501
KS 095-4AM12 connector for SW IN/OUT50040155
D-ET1RJ45 connector for user-configuration50108991
S-M12A-ETConnector, axial, M12 connector, D-coded, terminals50112155
Table 14.2:Connectors for the MA 258i
Leuze electronicMA 258i91
TNT 35/7-24V
Type overview and accessories
PWR IN
1
2
3
4
SWIO_2
SWIO_1
FE
5
GNDVIN
M12 socket
(A-coded)
M12 connector
(A-coded)
14.4Accessory ready-made cables for voltage supply
14.4.1 Contact assignment of PWR connection cable
PWR IN (5-pin socket, A-coded)
PinNameCore color
1VINbrown
2SWIO_2white
3GNDblue
4SWIO_1black
5FEgray
ThreadFEbare
PWR OUT (5-pin connector, A-coded)
PWR OUT
SWIO_2
2
GNDVOUT
3
FE
5
4
SWIO_1
1
PinNameCore color
1VOUTbrown
2SWIO_2white
3GNDblue
4SWIO_1black
5FEgray
ThreadFEbare
14.4.2 Specifications of the cables for voltage supply
Operating temperature range in rest state: -30° C … +70°C
in motion: 5° C … +70°C
Material sheathing: PVC
Bending radius > 50mm
92MA 258iLeuze electronic
Type overview and accessories
Ethernet
TD+
RD+
TD
RD
SH
M12 connector
(D-coded)
Core color
Conductor class: VDE 0295, EN 60228, IEC 60228 (class 5)
WH
YE
BU
OG
14.4.3 Order codes of the cables for voltage supply
Type designationDescriptionPart no.
K-D M12A-5P-5m-PVC
K-D M12A-5P-10m-PVC
Table 14.3:PWR cables for the MA 258i
M12 socket for PWR, axial plug outlet,
open cable end, cable length 5m
M12 socket for PWR, axial plug outlet,
open cable end, cable length 10m
14.5Accessory ready-made cables for bus connection
14.5.1 General information
• Cable KB ET… for connecting to Industrial EtherNet via M12 connector
• Standard cable available in lengths from 2 … 30m
The MA 258i does not require any maintenance by the operator.
15.2Repairs, servicing
Repairs to the device must only be carried out by the manufacturer.
Contact your Leuze distributor or service organization should repairs be required.
The addresses can be found on the inside of the cover and on the back.
Notice!
When sending devices to Leuze electronic for repair, please provide an accurate description
of the error.
15.3Disassembling, packing, disposing
Repacking
For later reuse, the device is to be packed so that it is protected.
Notice!
Electrical scrap is a special waste product! Observe the locally applicable regulations
regarding disposal of the product.
96MA 258iLeuze electronic
Specifications for Leuze end devices
16Specifications for Leuze end devices
Serial interface and Command mode
The corresponding Leuze end device can be selected while configuring the fieldbus gateway
(see chapter 9 "Configuration").
The exact specifications for the individual Leuze end devices can be found in the following
sections and in the device description.
The corresponding serial command is sent to the Leuze end device in Command mode. To
send the corresponding command to the RS 232 device after activating the Command
mode in byte 0 (control bit 0.0), set the corresponding bit in byte 2.
The Leuze end device also responds to most commands by sending data, such as the bar
code contents, NoRead, device version, etc., back to the gateway. The answer is not evaluated by the gateway, but is instead passed on to the PLC.
For the BPS 8, BPS 300i and hand-held scanners, a number of specific features are to be
noted.
16.1Standard setting, KONTURflex (S4 switch position 0)
This switch position can be used with almost all devices, since a data frame is transmitted
along with it if necessary. A 00h in the data range of the control is interpreted as the end of
a telegram/invalid, however.
The distance between two successive telegrams (without frame) must be more than 20ms
in this switch position, since there is otherwise no clear separation between them. If necessary, the settings have to be adjusted on the device.
Leuze measuring sensors with RS 232 interface (such as a KONTURflex Quattro RS) do not
necessarily use a telegram frame, which is why these are also operated in switch position 0.
Specifications for the serial interface
Default parameterStandard
Baud rate9600
Data mode8N1
Handshakeno
Protocolframing protocol without acknowledgment
Frame<Data>
Data Mode transparent
Notice!
The data frame is specified via the switch position.Only the data mode and the baud rate
can also be set via the "Configuration assembly"/ EDS file.
In the factory setting, the S4 switch position is 0. Resetting the settings to these is possible
in S4 switch position F. The procedure for doing this is described in chapter 16.13.
Leuze electronicMA 258i97
TNT 35/7-24V
Specifications for Leuze end devices
KONTURflex specifications
Settings on the MA 258i
• EtherNet address is freely selectable
• Device selection switch at position "0"
EtherNet settings
• Produced/Consumed data settings:
Dependent on number of beams used, but at least "20 bytes In/4 bytes Out"
• User parameters:
"Transparent mode", "Use ESD settings", baud rate 38400, "4 data bits",
"No parity", "2 stop bits"
KONTURflex settings
First, the following settings are to be performed on the device using KONTURFlex-Soft:
• Either "Autosend (fast)" or "Autosend with data in Modbus format"
• Repeat time "31.5ms"
• Autosend baud rate "38.4KB"
• 2 stop bits, no parity
98MA 258iLeuze electronic
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.