Indicates dangers that may result in property damage if the measures for danger avoidance are not followed.
Table 1.2:Other symbols
Symbol for tips
Text passages with this symbol provide you with further information.
About this document
Table 1.3:Terms and abbreviations
BCLBar code reader
CRTCode reconstruction technology
Symbol for action steps
Text passages with this symbol instruct you to perform actions.
Leuze electronicBCL 600i/BCL 601i6
2Safety
This sensor was developed, manufactured and tested in line with the applicable safety standards. It corresponds to the state of the art.
2.1Intended use
The device is designed as a stationary high-speed scanner with integrated decoder for all common bar
codes for automatic object detection.
Areas of application
The device is specially designed for the following areas of application:
• Object identification on fast-moving conveyor lines
• Omnidirectional reading
CAUTION
Comply with conditions and regulations!
Observe the locally applicable legal regulations and the rules of the employer's liability insurance asso-
ciation.
Safety
2.2Foreseeable misuse
Any use other than that defined under “Intended use” or which goes beyond that use is considered
improper use.
In particular, use of the device is not permitted in the following cases:
• in rooms with explosive atmospheres
• in circuits which are relevant to safety
• for medical purposes
CAUTION
Do not modify or otherwise interfere with the device!
Do not carry out modifications or otherwise interfere with the device.
The device must not be tampered with and must not be changed in any way.
The device must not be opened. There are no user-serviceable parts inside.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
2.3Competent persons
Connection, mounting, commissioning and adjustment of the device must only be carried out by competent
persons.
Prerequisites for competent persons:
• They have a suitable technical education.
• They are familiar with the rules and regulations for occupational safety and safety at work.
• They are familiar with the technical description of the device.
• They have been instructed by the responsible person on the mounting and operation of the device.
Certified electricians
Electrical work must be carried out by a certified electrician.
Due to their technical training, knowledge and experience as well as their familiarity with relevant stan-
dards and regulations, certified electricians are able to perform work on electrical systems and independently detect possible dangers.
In Germany, certified electricians must fulfill the requirements of accident-prevention regulations BGV A3
(e.g. electrician foreman). In other countries, there are respective regulations that must be observed.
Leuze electronicBCL 600i/BCL 601i7
2.4Exemption of liability
Leuze electronic GmbH + Co. KG is not liable in the following cases:
• The device is not being used properly.
• Reasonably foreseeable misuse is not taken into account.
• Mounting and electrical connection are not properly performed.
• Changes (e.g., constructional) are made to the device.
2.5Laser safety notices
2.5.1Laser safety notices– laser class 2
ATTENTION, LASER RADIATION – LASERCLASS2
Never look directly into the beam!
The device satisfies the requirements of IEC 60825-1:2007 (EN 60825-1:2007) safety regulations for a
product of laser class 2 as well as the U.S. 21 CFR 1040.10 regulations with deviations corresponding
to “Laser Notice No. 50” from June 24, 2007.
Never look directly into the laser beam or in the direction of reflected laser beams!
If you look into the beam path over a longer time period, there is a risk of injury to the retina.
Do not point the laser beam of the device at persons!
Interrupt the laser beam using a non-transparent, non-reflective object if the laser beam is accidentally
directed towards a person.
When mounting and aligning the device, avoid reflections of the laser beam off reflective surfaces!
CAUTION! The use of operating or adjusting devices other than those specified here or carrying out
of differing procedures may lead to dangerous exposure to radiation.
Observe the applicable statutory and local laser protection regulations.
The device must not be tampered with and must not be changed in any way.
There are no user-serviceable parts inside the device.
Repairs must only be performed by Leuze electronic GmbH + Co. KG.
Safety
CAUTION
Affix laser information and warning signs!
Laser information and warning signs attached to the device(see figure 2.1). Also included with the device
are self-adhesive laser warning and laser information signs (stick-on labels) in multiple languages (see
figure 2.3).
Affix the laser information sheet to the device in the language appropriate for the place of use.
When using the device in the U.S.A., use the stick-on label with the “Complies with 21 CFR 1040.10”
notice.
Affix the laser information and warning signs near the device if no signs are attached to the device (e.g.
because the device is too small) or if the attached laser information and warning signs are concealed
due to the installation position.
Affix the laser information and warning signs so that they are legible without exposing the reader to the
laser radiation of the device or other optical radiation.
Leuze electronicBCL 600i/BCL 601i8
1Laser aperture
LASER RADIATION
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
EN 60825-1:2007
Maximum Output (peak):
Pulse duration:
Wavelength:
2 mW
<150 µs
405 nm
AVOID EXPOSURE – LASER RADIATION
IS EMITTED FROM THIS APERTURE
23
1
LASER RADIATION
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
EN 60825-1:2007
Maximum Output (peak):
Pulse duration:
Wavelength:
2 mW
<150 μs
405 nm
AVOID EXPOSURE – LASER RADIATION
IS EMITTED FROM THIS APERTURE
23
1
2Laser warning sign
3Laser information sign with laser parameters
Figure 2.1:Laser aperture, laser warning and information signs - line scanner
Safety
1Laser aperture
2Laser warning sign
3Laser information sign with laser parameters
Figure 2.2:Laser aperture, laser warning and information signs - oscillating-mirror scanner
Potencia máx. (peak):
Duración del impulso:
Longitud de onda:
RADIAÇÃO LASER
NÃO OLHAR FIXAMENTE O FEIXE
EQUIPAMENTO LASER CLASSE 2
EN 60825-1:2007
Potência máx. (peak):
Período de pulso:
Comprimento de onda:
LASER RADIATION
DO NOT STARE INTO BEAM
CLASS 2 LASER PRODUCT
IEC 60825-1:2007
Complies with 21 CFR 1040.10
Maximum Output (peak):
Pulse duration:
Wavelength:
䉏⏘戟⺓
▎䦃展⏘㧮
伊䉏⏘ℶ❐
GB7247.1-2012
㦏⮶戢⒉᧤⽿⋋᧥
厘⑁㖐兼㢅梃
㽱栎
2 mW
<150 µs
405 nm
2 mW
<150 µs
405 nm
2 mW
<150 µs
405 nm
2 mW
<150
µ
s
405 nm
2 mW
<150 µs
405 nm
2 mW
<150 µs
405 nm
2 mW
<150 µs
405 nm
2 mW
<150 µs
405 nm
50127630
Figure 2.3:Laser warning and information signs – supplied stick-on labels
Leuze electronicBCL 600i/BCL 601i10
3Device description
2
1
3.1Device overview
Bar code readers of the BCL 600i series are high-speed scanners with integrated decoder for all
commonly used bar codes, e.g. 2/5 Interleaved, Code 39, Code 128, EAN 8/13 etc., as well as codes from
the GS1 DataBar family.
Bar code readers of the BCL 600i series are available in various optics models as well as line scanners
and oscillating mirrors and also optionally as heated models.
Device description
1Line scanner
2Oscillating-mirror scanner
Figure 3.1:Line scanner and oscillating-mirror scanner
The extensive options for device configuration via display or software enable adaptation to a multitude of
reading tasks. Due to the large reading distance combined with the great depth of field and a very compact
construction, the device is ideally suited for package and pallet transportation systems. In general, the bar
code readers of the BCL 600i series are designed for the conveyor and storage technology market.
The interfaces (RS 232, RS 485 and RS 422) integrated in the various device models and the fieldbus
systems (Profibus DP , PROFINET -IO, Ethernet TCP/IP / UDP and E thernet/IP) of the BCL 600i series bar
code readers offer optimum connection to the superior host system.
3.2Performance characteristics
• Integrated fieldbus connectivity = i -> Plug-and-Play fieldbus coupling and easy networking
• Numerous interface variants facilitate connection to the superior systems
• RS 232, RS 422 as well as with integrated multiNet plus master
• RS 485 and multiNet plus slave
• Alternatively, various fieldbus systems, such as
PROFIBUS DP
PROFINET-IO
Ethernet TCP/IP and UDP
Ethernet/IP
Leuze electronicBCL 600i/BCL 601i11
Device description
• Integrated code reconstruction technology (CRT) enables the identification of soiled or damaged bar
codes
• Maximum depth of field and reading distances from 400 mm to 1450 mm
• Large optical opening angle and, thus, large reading field width
• High scanning rate of 800 / 1000 scans/s for fast reading tasks
• Intuitive, backlit, multi-language display with user-friendly menu navigation
• Integrated USB 1.1 service interface
• Adjustment of all device parameters with a web browser
• Connection options for an external parameter memory
• Easy alignment- and diagnostics functions
• M 12 connections with Ultra-Lock ™ technology
• Four freely programmable switching inputs/outputs for the activation or signaling of states
• Automatic monitoring of the read quality with autoControl
• Automatic recognition and setting of the bar code type using autoConfig
• Reference code comparison
• Optional heating models to -35 °C
• Heavy-duty housing of degree of protection IP 65
Leuze electronicBCL 600i/BCL 601i12
3.3Device construction
1
1
2
3
5
6
4
66
Device description
1Reading window
2Control panel with display, LEDs and buttons
3M 12 connection technology
4USB interface
5Dovetail mounting
6M4 mounting thread
Figure 3.2:Device construction
3.4Connection technology
The bar code readers are connected using variously coded M 12 connectors. This ensures unique connection assignments.
Leuze electronicBCL 600i/BCL 601i13
Device description
345
2
1
3
2
1
4
5
6
The additional USB interface is used for configuring the device.
The two product series BCL 600i and BCL 601i differ in their interfaces and in their function as multiNet
plus master or slave.
Table 3.1: BCL 600i/BCL 601i interfaces
HOST / BUS INBUS OUT
BCL 600i
(Stand alone or multiNet plus Master)
BCL 601i
(multiNet plus slave)
RS 232 / RS 422RS 485
RS 485RS 485
For the locations of the individual device connections, please refer to the device detail shown below.
1Service, USB socket, type A
2SW IN/OUT, M 12 socket (A-coded)
3Bus OUT, M 12 socket (D-coded)
4HOST/BUS IN, M 12 socket (D-coded)
5PWR, M 12 connector (A-coded)
Figure 3.3:Location of the electrical connections
3.5Display elements
3.5.1Structure of the control panel
1PWR LED
2NET LED
3Navigation buttons
4Escape button
5Enter button
6Display
Figure 3.4:Structure of the control panel
Leuze electronicBCL 600i/BCL 601i14
3.5.2Status display and operation
Indicators in the display
Table 3.2:Status displays of the switching inputs/outputs
IO1Switching input or switching output 1 active (function dependent on set configuration).
Default: Switching input with the “Reading gate activation”
IO2Switching input or switching output 2 active (function dependent on set configuration).
Default: Input with the “Teach-in”
IO3Switching input or switching output 3 active (function dependent on set configuration).
Default: Switching input with the “Reading gate activation”
IO4Switching input or switching output 4 active (function dependent on set configuration).
Default: Switching output with the “No read”
ATTWarning (Attention)
ERRInternal device error (Error) -> The device must be sent in for inspection
Table 3.3:Status display of the USB interface
Device description
USBThe device is connected to a PC via the USB interface.
MSAn external parameter memory is properly connected to the USB interface of the device.
Read result
The read bar code information is displayed.
3.5.3LED indicators
PWR LED
OffDevice OFF
Flashes greenDevice ok, initialization phase
Green,
continuous light
Orange,
continuous light
• No supply voltage
• No bar code reading possible
• Voltage connected
• Self test running
• Initialization running
Device ok
• Bar code reading possible
• Self test successfully finished
• Device monitoring active
Service mode
• Bar code reading possible
• Configuration via the USB service interface
• Configuration via the display
• No data on the host interface
Flashes redDevice ok, warning set
• Bar code reading possible
• Temporary operating fault
Red,
continuous light
Leuze electronicBCL 600i/BCL 601i15
Device error / parameter enable
• No bar code reading possible
NET LED
OffNo supply voltage
• No communication possible
Flashes greenInitialization
• Of the device, establishing communication
Device description
Green,
Operation ok
continuous light
Flashes redCommunication error
Red,
continuous light
Network error
No communication (protocol) to IO controller established (no data exchange)
3.6Operational controls
Navigating within the menus
Use the navigation buttons to move through the menu. Activate the desired selection with the enter
button .
Press the escape button to move up one menu level.
When one of the buttons is actuated, the display illumination is activated for 10 min.
Setting values
Set the desired value with the navigation buttons and the enter button .
An accidental incorrect entry can be corrected by selecting the left arrow button and then pressing the
enter button.
Then use the navigation buttons to select save and save the set value by pressing the enter button.
• Network mode ok
• Parameterization or configuration failed (parameter failure)
•IO error
• No data exchange
ESC
Selecting options
Set the desired option with the navigation buttons and the enter button .
3.7External parameter memory
The optionally available external parameter memory – based on a USB memory stick (compatible with
version 1.1) – is housed in an external hood with integrated connectors which cover the USB service interface when installed (IP 65).
The external parameter memory makes it easy and reduces the time needed to replace a device on site
by providing a copy of the current parameter set of the device. This eliminates the need to configure the
exchanged device manually.
The delivery contents of the external parameter memory include the hood with integrated connectors with
unscrewable cover and the USB memory stick.
For transferring the configuration with the aid of the external parameter memory see chapter 6.2.
Leuze electronicBCL 600i/BCL 601i16
4Functions
General information
The integrated fieldbus connectivity = i contained in the bar code readers of the BCL 600i series facilitates
the use of identification systems which function without connection unit or gateways. The integrated
fieldbus interface considerably simplifies handling. The Plug-and-Play concept enables easy networking
and very simple commissioning: Directly connect the respective fieldbus and all configuration is performed
with no additional software.
For decoding bar codes, the bar code readers of the BCL 600i series make available the proven CRT
decoder with code reconstruction technology:
The proven code reconstruction technology (CRT) enables bar code readers of the BCL 600i series to read
bar codes with a small bar height, as well as bar codes with a damaged or soiled print image.
With the aid of the CRT decoder, bar codes can also be read without problem in other demanding situations, such as with a large tilt angle (azimuth angle or even twist angle).
Functions
Figure 4.1:Possible bar code orientation
The BCL 600i / BCL 601i can be operated and configured using the integrated webConfig tool via the USB
service interface; alternatively, the bar code readers can be adjusted using configuration commands via
the host/service interface.
The device needs a suitable activation to start a read process as soon as an object is in the reading field.
This opens a time window (reading gate) in the device for the read process during which the bar code
reader has time to detect and decode a bar code.
In the basic setting, triggering takes place through an external reading cycle signal. Alternative activation
options include online commands via the host interface and the autoReflAct function. Through the read
operation, the device collects additional useful pieces of data for diagnosis which can also be transmitted
to the host. The quality of the read operation can be inspected using the alignment mode which is integrated in the webConfig tool.
A multi-language display with buttons is used to operate the device as well as for visualization purposes.
Two LEDs provide additional optical information on the current operating state of the device.
The four freely configurable switching inputs/outputs SWIO 1 … SWIO 4 can be assigned various functions and control e.g. activation of the device or external devices, such as a PLC.
Leuze electronicBCL 600i/BCL 601i17
System, warning and error messages provide assistance in setup/troubleshooting during commissioning
and read operation.
4.1autoReflAct
autoReflAct st a nds for automatic Reflector Activation and permits an activation without additional sensors.
This is achieved by directing the scanner with reduced scanning beam towards a reflector mounted behind
the conveyor path. As long as the scanner is targeted at the reflector, the reading gate remains closed. If,
however, the reflector is blocked by an object such as a container with a bar code label, the scanner activates the read procedure, and the label on the container is read. When the path from the scanner to the
reflector has cleared, the read procedure has completed and the scanning beam is reduced and again
directed onto the reflector. The reading gate is closed.
You will find a matching reflector in Accessories, and more are available on request.
Functions
Figure 4.2:Reflector arrangement for autoReflAct
The autoReflAct function uses the scanning beam to simulate a photoelectric sensor and thus permits an
activation without additional sensors.
4.2Reference codes
The device offers the possibility of storing one or two reference codes.
It is possible to store the reference codes by means of teach-in (display command), via the webConfig tool
or via online commands.
The device can compare read bar codes with one and/or both reference codes and execute user-config-
urable functions depending on the comparison result.
4.3autoConfig
With the autoConfig function, the device offers an extremely simple and convenient configuration option
to users who only want to read one code type (symbology) with one number of digits at a time.
Leuze electronicBCL 600i/BCL 601i18
After starting the autoConfig function via the display, switching input or from a superior control, it is sufficient to position a bar code label with the desired code type and number of digits in the reading field of the
device.
Afterward, bar codes with the same code type and number of digits are recognized and decoded.
4.4Stand-alone connection
The bar code readers of the BCL 600i series can be operated as single “stand-alone” devices. The device
features multiple M 12 connectors / sockets for the electrical connection of the supply voltage, the interface
and the switching inputs and outputs.
1Switching inputs/outputs
2Supply voltage
3PC / PLC host interface
Figure 4.3:Stand-alone connection
Functions
1
2
3
4.5Networking - Leuze multiNet plus
In the Leuze multiNet plus network, up to 32 bar code readers can be networked together. The respective
network devices transmit the read data when requested to by the BCL 600i (or MA 31) network master.
For this purpose, each device is assigned its own station address, which is set using the display of the
corresponding device.
The master then transmits the data of all network devices via its host interface to a superior PLC control
system or a computer, i.e. it “collects” the scanner data in the network and transmits it to an interface on
the host computer. This reduces interface costs (CPs) and time spent programming the software.
1
1
2
345
6
1BCL 600i master
2To PC/PLC
3BCL 601i slave 1
4BCL 601i slave 2
5BCL 601i slave n
6Terminating resistor on the last slave
Figure 4.4:Networking possibilities using the multiNet plus
Leuze electronicBCL 600i/BCL 601i19
Two-wire RS 485
The Leuze multiNet plus is optimized for fast transmission of scanner data to a primary host computer. The
multiNet plus consists physically of a two-wire RS 485 interface through which the Leuze multiNet plus
software protocol is controlled. This makes wiring the network easy and inexpensive as slaves are looped
through to one another in parallel.
In principle, networking occurs via a parallel connection of the individual RS 485 interfaces of the respective bar code scanners. Shielded, twisted pair conductors should be used for the Leuze multiNet plus. This
allows a total network length of up to 1200m.
4.6Leuze multiScan
The multiScan operating mode is based on Leuze multiNet plus and links individual bar code readings from
multiple bar code scanners into a single decoding result. This is used, for example, on a packet conveyor
system on which the label can be affixed on either the right or left side, thereby requiring two read stations.
To prevent the host from having to always process two readings for a single packet, i.e. a decoding result
and a No Read, a multiScan arrangement is used which transmits only one reading from the two read
stations to the host; this single reading is transmitted by the multiScan master.
Thus, from the perspective of the host, the scanner network appears to be just a single bar code
reader!
Functions
For this purpose one multiScan master and one or more multiScan slaves are connected together via the
RS 485 interface.
Figure 4.5:Scanner arrangement with the multiScan function
The multiScan function on the RS 485 interface is possible for minimum of 2 and a maximum of
32 devices!
The protocol set on the RS 485 interface is the multiNet protocol. As a result, during multiScan operation
on the RS 485 interface, the multiNet master also functions as the multiScan master and the
multiNet slaves function as multiScan slaves (thus, all multiNet slave are included in multiScan operation).
4.7Heater
For low-temperature applications to min. -35°C (e.g. in cold storage), the bar code readers of the BCL 600i
series can optionally be permanently fitted with a built-in heating and these bar code readers purchased
as separate device models.
Leuze electronicBCL 600i/BCL 601i20
5Reading techniques
5.1Line scanner (single line)
A line (scan line) scans the label. Due to the opt. opening angle, the reading field width is dependent on
the read distance. Through the movement of the object, the entire bar code is automatically transported
through the scan line.
The integrated code reconstruction technology permits twisting of the bar code (tilt angle) within certain
limits. These are dependent on the transport speed, the scanning rate of the scanner and the bar code
properties.
Areas of application of the line scanner
The line scanner is used:
• when the bars of the bar code are printed in the conveying direction ('ladder arrangement').
• with bar codes having very short bar lengths.
• when the ladder code is turned out of the vertical position (tilt angle).
• when the reading distance is large.
Reading techniques
Figure 5.1:Deflection principle for the line scanner
5.2Line scanner with oscillating mirror
The oscillating mirror deflects the scan line additionally to both sides across the scan direction at a
randomly adjustable oscillation frequency. In this way, the device can also scan larger areas or spaces for
bar codes. The reading field height (and the scan line length useful for evaluation) depends on the reading
distance due to the optical opening angle of the oscillating mirror.
Leuze electronicBCL 600i/BCL 601i21
Reading techniques
Areas of application of the line scanner with oscillating mirror
For line scanners with oscillating mirror, oscillation frequency, start/stop position etc. are adjustable. It is
used:
• when the position of the label is not fixed, e.g. on pallets – various labels can, thus, be detected at
various positions.
• when the bars of the bar code are printed perpendicular to the conveying direction (“picket fence
arrangement”).
• when reading stationary objects.
• when the bar code is turned out of the horizontal position.
• when the reading distance is large.
• when a large reading field (reading window) has to be covered.
Figure 5.2:Deflection principle for the line scanner with oscillating mirror add-on
5.3Omnidirectional reading
In order to read arbitrarily oriented bar codes on an object, at least 2 bar code readers are necessary. If
the bar code is not printed over-square, i.e. bar length > code length, bar code readers with integrated code
reconstruction technology are necessary.
Leuze electronicBCL 600i/BCL 601i22
Figure 5.3:Principle arrangement for omnidirectional reading
Reading techniques
Leuze electronicBCL 600i/BCL 601i23
6Mounting
The bar code readers can be mounted in different ways:
• Using two M4x6 screws on the rear of the device or using four M4x6 screws on the bottom of the
device (see figure 3.2).
• Using a BT 56 mounting device on the two fastening grooves (see figure 15.3).
• Using a BT 59 mounting device on the two fastening grooves (see figure 15.4).
6.1Device arrangement
6.1.1Selecting a mounting location
In order to select the right mounting location, several factors must be considered:
• Size, orientation, and position tolerance of the bar codes on the objects to be scanned.
• The reading field of the device in relation to the bar code module width.
• The resulting minimum and maximum reading distance from the respective reading field (see
chapter 15.5 "Reading field curves / optical data").
• The permissible cable lengths between the device and the host system depending on which interface
is used.
• The correct time for data output. The device should be positioned in such a way that, taking into consideration the time required for data processing and the conveyor belt speed, there is sufficient time
to e.g. initiate sorting operations on the basis of the read data.
• The display and control panel should be very visible and accessible.
• For configuring and commissioning with the webConfig tool, the USB interface should be easily
accessible.
• Maintaining the required environmental conditions (temperature, humidity).
• Possible soiling of the reading window due to liquids, abrasion by boxes, or packaging material residues.
• Lowest possible chance of damage to the device by mechanical collision or jammed parts.
• Possible extraneous light (no direct sunlight or sunlight reflected by the bar code).
Mounting
With the line scanner, the beam exits the device parallel to the housing base; with the oscillating
mirror, the beam exits perpendicular to the housing base. The housing base is the black surface.
The best read results are obtained when:
• The device is mounted in such a way that the scanning beam is incident on the bar code at an angle
of inclination greater than ±10° … 15° to vertical.
• The reading distance lies in the middle area of the reading field.
• The bar code labels are of good print quality and have good contrast ratios.
• You do not use high-gloss labels.
• There is no direct sunlight.
6.1.2Avoiding total reflection – Line scanner
The bar code label must be positioned at an angle of inclination greater than ±10° … 15° from vertical in
order to avoid total reflection of the laser beam (see figure 6.1)!
Total reflection occurs whenever the laser light of the bar code reader is directly incident on the surface of
the bar code at an angle of 90°. The light directly reflected by the bar code may overload the bar code
reader and thereby cause non-readings!
Leuze electronicBCL 600i/BCL 601i24
1Zero position
x
1
2
x
1
2
2Bar code
xDistance acc. to reading field curves
±10 … 15°
Figure 6.1:Total reflection – line scanner
6.1.3Avoiding total reflection – oscillating-mirror scanner
For the device with oscillating mirror, the laser beam exits at an angle of 90° to vertical.
In addition, the swivel range of ±20° is to be taken into account.
This means that in order to be on the safe side and to avoid total reflection, the device with oscillating mirror
must be inclined upward or downward 20° … 30°!
Mounting
1Zero position
2Bar code
xDistance acc. to reading field curves
±25°
6.1.4Possible read angles between device and bar code
The optimum alignment of the device is accomplished when the scan line scans the bar code bars almost
at a right angle (90°). All reading angles that are possible between the scan line and bar code must be
taken account (see figure 6.3).
Leuze electronicBCL 600i/BCL 601i25
Mounting
Azimuth angle (tilt)
Inclination angle (pitch)
Angle of rotation (skew)
In order to avoid total reflection, the skew should be greater than 10 °
Figure 6.3:Reading angle for the line scanner
6.2Installing the external parameter memory
Remove the cover of the USB connection on the device.
Insert the USB memory stick into the USB connection and then cover it with the connector hood to
ensure degree of protection IP 65.
The USB memory stick can be inserted regardless of whether or not the device is connected to supply
voltage.
• After the USB memory stick has been inserted and supply voltage applied, the following message
appears on the display.
Memory stick connected: Export internal configuration?
Use the navigation buttons to select OK and activate with the enter button .
The configuration is now transferred to the external parameter memory and is from now on updated imme-
diately when the configuration is changed via display or online commands.
• The display of MS under the device address indicates that the USB memory stick is correctly connected and functional.
Replacing a defective device
Uninstall the defective device.
Remove the external parameter memory from the defective device by unscrewing the protection hood.
Mount the external parameter memory on the new device.
Install and start up the new device.
The following message appears on the display again:
Use the navigation buttons to select Cancel and activate with the enter button .
Make sure you select Cancel. Otherwise, the configuration in the external parameter memory is
lost!
The configuration is now imported from the external parameter memory and the device is immediately
operational without any further configuration.
Leuze electronicBCL 600i/BCL 601i27
7Electrical connection
345
2
1
CAUTION
Do not open the device yourself under any circumstances! There is otherwise a risk of uncontrolled
emission of laser radiation from the device. The housing of the device contains no parts that need to
be adjusted or maintained by the user.
Before connecting the device, be sure that the supply voltage agrees with the value printed on the
name plate.
Connection of the device and cleaning must only be carried out by a qualified electrician.
Ensure that the functional earth (FE) is connected correctly. Unimpaired operation is only guaranteed
when the functional earth is connected properly.
If faults cannot be cleared, the device should be switched off and protected against accidental use.
CAUTION
For UL applications, use is only permitted in Class 2 circuits in accordance with the NEC (National
Electric Code). The bar code readers are designed in accordance with protection class III for supply by
PELV (protective extra-low voltage with reliable disconnection).
Electrical connection
CAUTION
Degree of protection IP 65 is achieved only if the connectors and caps are screwed into place!
7.1Overview
As a “stand-alone” device, or multiNet plus “master” participant or network slave participant, the device is
equipped with four M 12 plugs/sockets which are A- and B-coded.
The voltage supply (PWR) as well as the four freely configurable switching inputs/outputs (SW IN/OUT and
PWR) are connected there.
An RS 232 or optionally RS 422 interface is available as “HOST / BUS IN” interface for connecting to the
host system. An RS 485 is available as a second physical “BUS OUT” interface for setting up the
Leuze multiNet plus scanner network. The device is suitable for use in the Leuze multiNet plus as network
master/multiScan master.
An USB connection is used as a SERVICE interface.
1Service, USB socket, type A
2SW In/Out, M 12 socket (A-coded)
3Bus Out RS 485, M 12 socket (B-coded)
4HOST/BUS in, M 12 connector (B-coded)
5PWR, M 12 connector (A-coded)
Figure 7.1:Connections of the device
Described in detail in the following are the individual connections and pin assignments.
Leuze electronicBCL 600i/BCL 601i28
7.2PWR – Voltage supply and switching inputs/outputs 3 and 4
2
3
1
4
5
FE
Figure 7.2:PWR, M 12 connector (A-coded)
Table 7.1:Pin assignments - PWR
PinNameComment
1VINPositive supply voltage +10 ... +30 V DC
2SWIO_3 Configurable switching input / output 3
3GNDNegative supply voltage 0 V DC
4SWIO_4 Configurable switching input / output 4
5FEFunctional earth
Electrical connection
ThreadFEFunctional earth (housing)
Supply voltage
CAUTION
For UL applications, use is only permitted in Class 2 circuits in accordance with the NEC (National
Electric Code).
CAUTION
The bar code readers of the BCL 600i series are designed in accordance with protection class III for
supply by PELV (protective extra-low voltage with reliable disconnection).
Connecting functional earth FE
Ensure that the functional earth (FE) is connected correctly. Unimpaired operation is only guaranteed
when the functional earth is connected properly. All electrical disturbances (EMC couplings) are discharged via the functional earth connection.
Switching input/output
The device is equipped with four freely programmable, opto-decoupled switching inputs and outputs
SWIO_1 … SWIO_4.
The switching inputs can be used to activate various internal functions of the device (decoding, autoConfig,
…). The switching outputs can be used to signal the state of the device and to implement external functions
independent of the superior control.
The two switching inputs/outputs SWIO_1 and SWIO_2 are located on the SW IN/OUT M 12 socket (see
chapter 7.4). The other two (SWIO_3 and SWIO_4) of the four freely configurable switching inputs/outputs
are located on the PWR M 12 connector.
The respective function as input or output can be set via the display or with the aid of the
“webConfig” configuration tool!
The external wiring as switching input and switching output is described in the following. For the respective
function assignment to the switching inputs/outputs see chapter 10.
Leuze electronicBCL 600i/BCL 601i29
Function as switching input
1
2
3
Electrical connection
1
2
3
1Switching input
2Switching output from controller (deactivated)
3Switching input to controller
Figure 7.3:Switching input connection diagram SWIO_3 and SWIO_4
If you use a sensor with a standard M 12 connector, please note the following:
Pins 2 and 4 must not be operated as switching outputs if sensors which function as inputs are also
connected to these pins.
If, for example, the inverted sensor output is connected to pin 2, and pin 2 of the bar code reader is, at
the same time, configured as an output (and not as an input), the switching output malfunctions.
CAUTION
The maximum input current must not exceed 8 mA!
Function as switching output
1Switching output
2Switching input from controller
3Switching output to controller (deactivated)
Each configured switching output is short-circuit proof! Do not load the respective switching output of the
device with more than 60 mA at +10 … +30 V DC in normal operation!
By default, the two switching inputs/outputs SWIO_3 and SWIO_4 are configured so that switch-
ing input SWIO_3 activates the reading gate and switching output SWIO_4 switches on
“No Read”.
Leuze electronicBCL 600i/BCL 601i30
7.3SERVICE – USB interface (type A)
4
3
1
2
1
3
2
4
5
FE
Figure 7.5:Service, USB, type A
Table 7.2:Pin assignments of SERVICE – USB interface
PinNameComment
1VBPositive supply voltage +5 V DC
2D-Data -
3D+Data +
4GNDGround
NOTICE
Maximum load of the +5 V DC supply voltage of the USB interface is 200 mA!
Ensure adequate shielding.
The entire interconnection cable must absolutely be shielded acc. to the USB specifications. Cable
length must not exceed 3 m.
Use the Leuze-specific USB service cable (see chapter 16 "Ordering information and accessories") for
the connection and use a service PC to configure.
Electrical connection
NOTICE
IP 65 is achieved only if the connectors and caps are screwed into place. Alternatively, a parameter
memory in the form of a USB memory stick certified by Leuze electronic GmbH + Co. can be connected
to the provided USB service interface. With this Leuze memory stick, degree of protection IP 65 is also
ensured.
7.4SW IN/OUT – Switching input/switching output
Figure 7.6:SW IN/OUT, M 12 socket (A-coded)
Table 7.3:Pin assignment SW IN/OUT
PinNameComment
1VOUTVoltage supply for sensor system (VOUT identical to VIN at PWR IN)
2SWIO_
1
Configurable switching input / output 1
3GNDGND for the sensor system
Leuze electronicBCL 600i/BCL 601i31
PinNameComment
1
2
3
4
Electrical connection
4SWIO_
Configurable switching input / output 2
2
5FEFunctional earth
ThreadFEFunctional earth (housing)
The device is equipped with four freely programmable, opto-decoupled switching inputs and outputs
SWIO_1 … SWIO_4.
The two switching inputs/outputs SWIO_1 and SWIO_2 are located on the SW IN/OUT M 12 socket. The
other two (SWIO_3 and SWIO_4) of the four freely configurable switching inputs/outputs are located on
the PWRsee chapter 7.4 M 12 connector.
The external wiring as switching input and switching output is described in the following. For the respective
function assignment to the switching inputs/outputs see chapter 10.
Function as switching input
1Output
2Switching output from controller (deactivated)
3Switching input to controller
4Diffuse reflection sensor
Figure 7.7:Switching input connection diagram SWIO_1 and SWIO_2
NOTICE
If you use a sensor with a standard M 12 connector, please note the following: Pins 2 and 4 must not be
operated as switching outputs if sensors which function as inputs are also connected to these pins. If, for
example, the inverted sensor output is connected to pin 2, and pin 2 of the bar code reader is, at the same
time, configured as an output (and not as an input), the switching output malfunctions.
NOTICE
The maximum input current must not exceed 8 mA!
Leuze electronicBCL 600i/BCL 601i32
Function as switching output
3
1
2
4
FE
5
Electrical connection
1
2
3
1Switching output
2Switching output from controller
3Switching input to controller (deactivated)
Each configured switching output is short-circuit proof! Do not load the respective switching output of the
device with more than 60 mA at +10 … +30 V DC in normal operation!
By default, the two switching inputs/outputs SWIO_1 and SWIO_2 are configured so that they
function as switching inputs. Switching input SWIO_1 activates the start reading gate function
and switching input SWIO_2 activates the reference code teach-in function.
The functions of the individual switching inputs/outputs are programmed via the display or via configuration
in the webConfig tool under the Switching input or Switching output heading (see chapter 10 "Starting up
the device - Configuration").
7.5HOST / BUS IN
HOST / BUS IN for BCL 600i
The BCL 600i makes either the RS 232 or RS 422 interface available as host interface. This is selected
via the display or the “webConfig” configuration software. The pin assignments change depending on the
selected interface type (see table 7.4, see figure 7.10 and see figure 7.11).
Figure 7.9:HOST/BUS IN, M 12 connector (B-coded)
Table 7.4:Pin assignment HOST / BUS IN for BCL 600i
PinNameComment
1CTS /
RX+
CTS signal (RS 232) / RX+ (RS 422)
2TxD /
TXD signal (RS 232) / TX- (RS 422)
Tx-
3GND_H Reference potential 0V for RS 232 / RS 422
Leuze electronicBCL 600i/BCL 601i33
PinNameComment
3
1
2
4
FE
5
Electrical connection
4RTS/
RTS signal (RS 232) / TX+ (RS 422)
Tx+
5RxD /
RxD signal (RS 232) / Rx- (RS 422)
Rx-
ThreadFEFunctional earth (housing)
RS 232 interface
2
1
RXD
TXD
GND
CTS
RTS
GND_H
3
1Host
2Shield
3Max. 10 m
Figure 7.10: Pin assignments - HOST / BUS IN as RS 232
RXD/RX-
TXD/TX-
3
5
RTS/TX+
2
CTS/RX+
1
4
NOTICE
Ensure adequate shielding. The entire interconnection cable must be shielded and earthed. The cables
for RTS and CTS must only be connected if RTS/CTS hardware handshake is used.
RS 422 interface
1
RX-
TX-
GND
RX+
TX+
2
TXD/TX-
2
GND_H
RXD/RX-
3
RTS/TX+
CTS/RX+
1
5
4
2
1Host
2Twisted pair
Figure 7.11: Pin assignments - HOST / BUS IN as RS 422
NOTICE
Ensure adequate shielding. The entire interconnection cable must be shielded and earthed. The signal
lines must be stranded in pairs.
HOST / BUS IN for BCL 601i
The BCL 601i makes available an RS 485 as HOST / BUS IN interface for the connection to the host
system. This interface is physically looped through to the BUS OUT RS 485 socket.
With its RS 485 interface, the BCL 601i is suitable for use in the Leuze multiNet plus scanner network.
Leuze electronicBCL 600i/BCL 601i34
Figure 7.12: HOST/BUS IN, M 12 connector (B-coded)
Table 7.5:Pin assignment HOST / BUS IN for BCL 601i
1
3
2
4
5
PinNameComment
1N.C.Reserved
2RS 485 BRS 485 B - signal line
Electrical connection
3GND
4RS 485 ARS 485 A - signal line
5FEFunctional earth / shield
ThreadFEFunctional earth (housing)
7.6BUS OUT
To set up the Leuze multiNet plus network with additional participants, the device makes available another
interface in the form of an RS 485.
Figure 7.13: M 12 socket (B-coded)
Table 7.6:Pin assignment BUS OUT
PinNameComment
Reference ground RS 485 - potential equalization
485
1VCC485+5VDC for bus termination
2RS 485 BRS 485 B - signal line
3GND
Reference ground RS 485 - potential equalization
485
4RS 485 ARS 485 A - signal line
5FEFunctional earth / shield
ThreadFEFunctional earth (housing)
NOTICE
Ensure adequate shielding. The entire interconnection cable must be shielded and earthed. The signal
lines must be stranded in pairs.
Termination of the RS 485 interface on the master (BCL 600i)
The RS 485 interface must always be terminated externally on the master via a T-connector and a termi-
nating resistor (see chapter 16 "Ordering information and accessories").
Termination of the RS 485 interface on the slave (BCL 600i)
On the last network participant, the Leuze multiNet plus network (RS 485 interface) should be terminated
with a terminating resistor on the BUS OUT socket (see chapter 16 "Ordering information and accessories").
Leuze electronicBCL 600i/BCL 601i35
The BCL 600i can only participate as a slave in the Leuze multiNet plus on the BUS OUT socket
and via an external M 12 T-connector (see chapter 7.8.3 and see figure ).
Termination of the RS 485 interface (BCL 601i)
The device operates as slave in the Leuze multiNet plus network. On the last physical participant, the
Leuze multiNet plus network (RS 485 interface) must be terminated with a terminating resistor (see
chapter 16 "Ordering information and accessories"). This prevents reflections on the Leuze multiNet plus
and improves the immunity to interference.
7.7Cable lengths and shielding
Observe the following maximum cable lengths and shielding types:
Table 7.7:Cable lengths and shielding
ConnectionInterfaceMax. cable lengthShielding
BCL – serviceUSB3 mShielding absolutely
Electrical connection
necessary acc. to USB
specifications
BCL – hostRS 232
Network from the first
BCL to the last BCL
BCL – power supply
unit
Switching input10 mNot necessary
Switching output10 mNot necessary
7.8Leuze multiNet plus
The Leuze multiNet plus is optimized for fast transmission of scanner data to a primary host computer. The
multiNet plus consists physically of a two-wire RS 485 interface through which the multiNet plus software
protocol is controlled.
This makes wiring the network easy and inexpensive as slaves are looped through to one another in
parallel.
10 m
RS 422
RS 485
RS 4851200 mshielding absolutely
1200 m
1200 m
30 mNot necessary
shielding absolutely
required
RS 422/485 conductors, stranded in pairs
required
RS 485 conductors,
stranded in pairs
Leuze electronicBCL 600i/BCL 601i36
1
1
2
345
1BCL 600i master
2To PC/PLC
3BCL 601i slave 1
4BCL 601i slave 2
5BCL 601i slave n
6Terminating resistor on the last slave
Figure 7.14: Leuze multiNet plus system topology
Electrical connection
6
With the aid of a BCL 600i network master, up to 31 bar code readers can be networked. For this purpose,
each participating device is assigned the respective station address via the display and the control panel.
The devices are networked by connecting the individual RS 485 interfaces in parallel.
In the Leuze multiNet plus network, the individual network devices sequentially transfer their data to the
BCL 600i network master when requested.
The BCL 600i master then transmits the data of all network devices via its host interface (either an RS 232
or RS 422) to a superior PLC control or to a computer, i.e. it “collects” the scanner data in the network and
transmits it to an interface on the host computer. This reduces interface costs (CPs) and time spent
programming the software.
7.8.1Wiring the multiNet plus
Leuze multiNet plus connection hints
Shielded, twisted pair conductors should be used for the Leuze multiNet plus. This allows a total network
length of up to 1200 m.
Recommended network cable (e.g. LiYCY 2x0.2 mm
• Twisted pairs, shielded
• Cross section: min. 0.2 mm
• Copper resistance <100 W/km
When wiring the network, note the following points:
The RS 485A, RS 485B and GND cables are looped through in the network and must not in any case
be misconnected; the Leuze multiNet plus network is otherwise not functional. It is recommended to wire
through the GND of the RS 485 interface of the participants.
Connect the shielding to the slaves on one side with FE.
The maximum cable length in the network is 1200m.
The (physically) last slave in the network should be equipped with a terminating resistor of 220
between RS 485A and RS 485B. This prevents reflections on the multiNet plus and improves the immunity to interference.
²
):
²
W
Leuze electronicBCL 600i/BCL 601i37
Use the recommended connectors / sockets or the ready-made cables and terminating resistors
(see chapter 16 "Ordering information and accessories").
7.8.2The BCL 600i as network master
Master operation
The BCL 600i bar code readers are specially designed for master operation in a network. They manage
the data of the slaves in multiNet plus and establish the connection to the superior host computer. Only a
few parameters need to be set for master operation. Network commissioning can thus be performed in
very little time (see chapter 10 "Starting up the device - Configuration").
Last slave address
Unlike the slaves, the display of the BCL 600i is not used to set the network address (the master always
has the address 00), but the last slave address, i.e. the number of the most significant slave. This “informs”
the BCL 600i master of the number of slaves operating on the network, without requiring you to call up the
webConfig tool. If the network is expanded at a later time, you only need to change the number of slaves
(last slave address) accordingly via the display.
Start-up / timeout messages
During the initialization phase, i.e. after switching on the operating voltage, the master searches for the set
number of slaves. If a slave is found, the master generates a start-up message “S” for the respective
address found, e.g. “04S” -> Slave with the address 04 has responded correctly.
If a slave is not found or does not respond, the master generates a “timeout” (response timeout) at this
address.
The slave address and a “T” are output on the host interface. For example, “08T” means that no slave
responded at the network address 08. The network is still operational with one or several reported
“timeouts”, however, a slave, for which a timeout was generated, can no longer be addressed.
Electrical connection
BCL 600i master mounting location
Ensure that the BCL 600i is mounted in an easily accessible and visible place in your system. Once the
network has been put into operation, you can set (configure) every scanner in the network centrally via the
USB service or host interface of the BCL 600i, without having to connect a PC/terminal to the individual
read stations.
7.8.3The BCL 600i as network slave
Alternatively, the bar code readers of the BCL 600i series can also operate as slave participants in the
network mode. They now transmit data to the multiNet master (e.g. BCL 600i) only after the master
prompts them to do so, and, using an external M 12 T-connector, they establish the continuing connection
via the BUS OUT socket to the slaves which follow (order information see chapter 16.3 "Accessories").
The last network participant must be terminated with a terminating resistor.
Leuze electronicBCL 600i/BCL 601i38
1
1
2
345
1BCL 600i master
2To PC/PLC
3BCL 600i slave 1
4BCL 600i slave 2
5BCL 600i slave n
6Terminating resistor on the last slave
Figure 7.15: Leuze multiNet plus system topology with BCL 600i as slave
Electrical connection
6
Only a few parameters need to be set for slave operation. Network commissioning can thus be performed
in very little time (see chapter 10 "Starting up the device - Configuration").
Slave address
The BCL 600i display has an important function for setting the network address. The network address, i.e.
the corresponding station number of the slave, is set via the display. The address which is set must be > 0
since the master always has address 0 (Adr.00).
Each network device with an address > 0 is thereby automatically informed that it is a slave in the
Leuze multiNet plus with this address and that it is initialized and queried by the network master. No other
settings are necessary for commissioning in the Leuze multiNet plus.
Other settings
The parameters necessary for the reading task, such as the code ty p e s to be read and the number of di g i t s
of the code, must be set. This can be done via the display, as well as with the help of the webConfig tool.
7.8.4The BCL 601i as network slave
The BCL 601i bar code readers are specially designed for slave operation in a network. They transmit data
to the multiNet master only after the master prompts it to do so and establish the continuing connection
via the BUS OUT socket to the slaves which follow. Only a few parameters need to be set for slave operation. Network commissioning can thus be performed in very little time (see chapter 10 "Starting up the
device - Configuration").
The connection is performed as described above (see figure 7.14).
Slave address
With the BCL 601i, the network address, i.e. the corresponding station number of the slave, is set via the
display. The address which is set must be > 0 since the master always has address 0 (Adr.00).
Each network device with an address > 0 is thereby automatically informed that it is a slave in the
Leuze multiNet plus with this address and that it is initialized and queried by the network master. No other
settings are necessary for commissioning in the Leuze multiNet plus.
Other settings
The parameters necessary for the reading task, such as the code ty p e s to be read and the number of di g i t s
of the code, must be set. This can be done via the display, as well as with the help of the webConfig tool.
Leuze electronicBCL 600i/BCL 601i39
8Menu description
After voltage is applied to the bar code reader, a startup screen is displayed for several seconds. The
display then shows the bar code reading window with all status information.
8.1The main menus
Use the navigation buttons to move through the menu. Activate the desired selection with the enter
button .
Device informationThis menu item contains detailed information on
Menu description
• Device type
• Software version
• Hardware version
• Serial number
Network settings
Bar code reading
window
Parameter
Language selection
Service
Actions
The display offers only limited configuration options. The configurable parameters are described
in this chapter. Only the webConfig tool provides complete configuration options and is largely
self-explanatory. For the use of webConfig tool see chapter 9. Notes on commissioning via the
webConfig tool see chapter 10.
8.2Parameter menu
Parameter handling
The Parameter handling submenu is used to lock and release the parameter input via the display and for
resetting to default values.
• Display of the network settings
• Visualization of the read bar code information
• Status overview of the switching inputs/outputs
• Bar graphs for read quality of the current bar code.
Further information see chapter "Indicators in the display".
• Configuration of the bar code reader
Further information see chapter 8.2 "Parameter menu".
• Selection of the display language
Further information see chapter 8.3 "Language selection menu".
• Scanner diagnosis and status messages
Further information see chapter 8.4 "Service menu".
• Various functions for scanner configuration and manual operation
Further information see chapter 8.5 "Actions menu".
Parameters to defaultBy pressing the enter button after selecting
Description
The standard setting (OFF) prevents unintended parameter
changes.
If parameter enabling is activated (ON), parameters can be
changed manually.
Parameters to default, all parameters are reset to their standard settings without any further security prompts.
In this case, English is selected as the display language.
Standard
OFF
Decoder table
In the Decoder table submenu, 4 different code type definitions can be stored. Bar codes that have been
read can only be decoded if they correspond to one of the definitions stored here.
Value between 0 and 64
The value set here specifies the maximum number of labels that
should be detected for each reading gate.
No code
Code 2/5 Interleaved
Code 39
Code 32
Code UPC
Code EAN
Code 128
EAN Addendum
Codabar
Code 93
GS1 DataBar Omnidirectional
GS1 DataBar Limited
GS1 DataBar Expanded
If No code is configured, the current and all subsequent decoders
are deactivated.
With the ON setting, the values in digits 1 and 2 define a range of
character numbers that are to be read.
First decodable number of characters or lower range limit.
Second decodable number of characters or upper range limit.
Third decodable number of characters.
Standard
1
Code 2/5i
OFF
10
0
0
Number of digits 40 to 64 characters
Number of digits 50 to 64 characters
Reading reliabilityValue from 2 to 100
Check digit methodStandard
Check digit transmission
Fourth decodable number of characters.
Fifth decodable number of characters.
Number or scans required to reliably detect a label.
No check
Depending on the symbology (code type) selected for the decoder,
further calculation algorithms can be selected here.
Check digit method used for the decoding of the bar code that has
been read.
If Standard is set, the check digit method intended for the respective code type is used.
Standard
Not standard
Specifies whether the check digit is transmitted. Standard means
that the transmission matches the standard intended for the
respective code type.
Determines the function of switching input/output 1.
In the case of passive, the connection is on 0 V if the
Inverted parameter is set to OFF, and on +UB if the
Inverted parameter is set to ON.
OFF = activation of the switching input function upon high
level at the switching input
ON = activation of the switching input function upon low
level at the switching input
Time in milliseconds for which the input signal must be
present and stable.
Time in milliseconds between the end of the debounce
time and activation of the function configured below.
Minimum activation time in milliseconds for the function
configured below.
Time in milliseconds for which the function configured
below remains activated after the switching input signal is
deactivated and the pulse duration has expired.
Reading gate start/stop
Reading gate stop
-Reading gate start
Teach reference code
Autoconfig start/stop
The function set here is carried out after the switching input
is activated.
OFF = activated switching output upon high level
ON = activated switching output upon low level
Time in milliseconds between activation function and
switching of the switching output.
Switch-on time of the switching output in milliseconds. If
the Pulse duration is set to 0, the switching output is
switched on via the Activation function and switched off via
the Deactivation function.
If the Pulse duration is greater than 0, the Deactivation
function has no effect.
Reading gate start
Reading gate end
Positive reference code comparison 1
Negative reference code comparison 1
Valid read result
Invalid read result
Device ready
Device not ready
Data transmission active
Data transmission not active
AutoCont. good quality
AutoCont. bad quality
Reflector detected
Reflector not detected
External event, pos. edge
External event, neg. edge
Device active
Device standby
No device error
Device error
Positive reference code comparison 2
Negative reference code comparison 2
The function set here specifies which event activates the
switching output.
Standard
OFF
0
400
No function
Deactivation function 1 See Activation function 1 for selection options
7N2
7E1
7E2
7O1
7O2
8N1
8N2
8E1
8E2
8O1
8O2
9N1
The data format is specified in:
Number of bits (7,8,9)
Parity (N=none, E=even, O=odd)
Number of stop bits (1,2)
RTS CTS
XON XOFF
RS422
RS485
b)
Postfix 1 ... 3
BCC mode
Control character definition for transmit data
Postfix 1 ... 3
BCC mode
Control character definition for received data
Standard
8N1
None
RS232
STX, NULL,
NULL
CR, LF, NULL
None
STX, NULL,
NULL
CR, LF, NULL
None
Address format No address
AddressValue from 0 to 310
BUS OUTmultiNet Master Maximum num-
multiNet SlaveSlave addressValue from 0 to 31
ber of slaves
a) If the device is configured as stand-alone device or network master, the framing protocol defines how data is exchanged
between the BCL 600i and the host. The framing protocol is a character-b ase d pro tocol for the trans missi on of ASCII
characters. It groups the characters to be transmitted into a datablock and frames the block with control characters. Var-
ious block checking methods are optionally available for protecting the integrity of the data.
b) Enter the decimal value of the desired ASCII character here. For example, enter "13" for the "CR" character (Carriage
Return) (see chapter 18.1).
8.3Language selection menu
Currently, there are 6 display languages available:
• German
• English
• Spanish
• French
• Italian
• Chinese
The display language and the language of the webConfig user interface are synchronized. The setting in
the display affects the webConfig tool and vice versa.
Binary address
ASCII address
Automatic address
Value from 0 to 31
If the BCL 600i was configured as network master in the Operating mode
menu item, the maximum number of slaves managed by the master must
be entered here.
If the BCL 600i was configured as network slave in the Operating mode
menu item, the slave address must be entered here.
No address
1
1
Leuze electronicBCL 600i/BCL 601i46
8.4Service menu
Diagnostics
This menu item is used exclusively for service purposes by Leuze electronic.
Status messages
This menu item is used exclusively for service purposes by Leuze electronic.
8.5Actions menu
Start decoding
Here, you can perform a single reading via the display.
Activate the single reading with the enter button and hold a bar code in the reading field of the device.
The laser beam is switched on and the following display appears:
zzzzzzzzz
Once the bar code is detected, the laser beam is switched off again. The read result zzzzzzzzz is shown
directly in the display for about 1 s. After that, the Actions menu is displayed again.
Start alignment
The alignment function makes it easy to align the device by optically displaying the read quality.
Activate the alignment function with the enter button and hold a bar code in the reading field of the
device.
At first, the laser beam is switched on continuously, enabling you to position the bar code securely in the
reading field. Once the bar code is read, the laser beam is switched off briefly and the following display
appears:
Menu description
xxzzzzzz
xxRead quality in % (scans with info)
zzzzzzContents of the decoded bar code
Once the bar code has been detected, the laser beam starts to flash.
The flash frequency provides visual information on the read quality. The faster the laser beam flashes, the
higher the read quality.
Start auto-setup
The auto-setup function provides an easy option for configuring the code type and number of digits of
Decoder 1.
Use the enter button to activate the auto-setup function and hold an unknown bar code in the reading
beam of the device.
The following display appears:
xxyyzzzzzz
The following information is displayed:
xxCode type of the detected code (sets the code type of Decoder 1)
012/5 Interleaved
02Code 39
06UPC (A, E)
07EAN
Leuze electronicBCL 600i/BCL 601i47
Menu description
08Code 128, EAN 128
10EAN Addendum
11Codabar
yyNumber of digits of the detected code (sets the number of digits of Decoder 1)
zzzzzzContents of the decoded label. A appears if the label was not correctly read.
Start teach-in
The teach-in function can be used to conveniently read reference code 1.
Use the enter button to activate the teach-in function and hold a bar code which contains the content
that you wish to store as the reference code in the reading beam of the device.
The following display appears:
RC13xxzzzzzz
RC13Means that ReferenceCode number 1 is stored in RAM. This is always output
xxDefined code type (see auto-setup)
zDefined code information (1 … 63 characters)
8.6Operation
Shown here is an example describing important operating procedures in detail.
Parameter enable
During normal operation parameters can only be viewed. If parameters need to be changed, the ON menu
item in the Parameter enabling menu must be activated.
Use the navigation buttons to move through the menu. Activate the desired selection with
the enter button .
In the Parameter menu, select Parameter handling.
Press the enter button to enter the menu.
Select the Parameter enable menu item.
Press the enter button to enter the menu.
Select the ON menu item.
Press the enter button to enter the menu.
The PWR LED lights up red. You can now set individual parameters via the display.
Press the Escape button twice to return to the main menu.
Network configuration
For information on network configuration see chapter 10 "Starting up the device - Configuration".
Leuze electronicBCL 600i/BCL 601i48
Commissioning – Leuze electronic webConfig tool
9Commissioning – Leuze electronic webConfig tool
With the Leuze webConfig tool, an operating-system independent, web-technology based, graphical user
interface is available for configuring bar code readers of the BCL 600i series.
Through the use of HTTP as communication protocol and by using only standard technologies on the client
side (HTML, JavaScript and AJAX), which are supported by all commonly used, modern browsers (e.g.
Mozilla Firefox beginning with Version 4, Internet Explorer beginning with Version 8.0 and Microsoft Edge),
it is possible to operate the Leuze webConfig tool on any internet-ready PC.
9.1Connecting the service USB interface
The connection to the SERVICE USB interface of the device is established via the PC-side USB interface
using a special USB cable with 2 type A/A plugs.
9.2Installation
9.2.1System requirements
Operating system:
Windows 2000
Windows XP (Home Edition, Professional)
Windows Vista
Windows 7
Windows 8
Windows 10
Computer:
PC with USB interface version 1.1 or higher
Graphics card:
Min. 1024 x 768 pixels or higher resolution
Required disk capacity:
Approx. 10 MB
It is recommended to update the operating system regularly and to install the current Windows
service packs.
9.2.2Installing the USB driver
In order for the device to be automatically detected by the connected PC, the USB driver must be installed
once on your PC. To do this, you must have administrator privileges.
Please proceed according to the following steps.
Start your PC with administrator privileges and log on.
Load the CD included in the delivery contents of your device in the CD drive and start the setup.exe
program.
Alternatively, you can also download the setup program from the internet at www.leuze.com.
Follow the instructions provided by the setup program.
Upon successful installation of the USB driver, an icon automatically appears on the desktop.
To check: In the Windows device manager, a device called “Leuze electronic, USB Rem o te NDIS Network
Device” appears under the “Network adapter” device class following successful USB registration.
If the installation failed, contact your network administrator: The settings of the firewall used may
need to be adjusted.
Leuze electronicBCL 600i/BCL 601i49
9.3Starting the webConfig tool
To start the webConfig tool, click the icon located on the desktop. Make certain that the device is
connected to the PC via the USB interface and that voltage is connected.
Or alternatively: Open a browser on your PC and enter the following address: 192.168.61.100.
This is the default Leuze service address for communication with bar code readers of the BCL 600i series.
In both cases, the following start page appears on your PC.
Commissioning – Leuze electronic webConfig tool
Figure 9.1:The start page of the webConfig tool
The webConfig tool is completely contained in the firmware of the device. Depending on firmware
version, the start page may vary from that shown above.
The individual parameters are – where useful – graphically displayed in order to better illustrate the
meaning of the what are often perceived as abstract parameters.
The result is an easy-to-use and practically-oriented user interface!
9.4Short description of the webConfig tool
The webConfig tool has five main menus:
•Home
With information on the connected device as well as on installation. This information corresponds to
the information in this handbook.
• Alignment
For manually starting read processes and for aligning the bar code reader. The results of the read
processes are displayed immediately. As a result, this menu item can be used to determine the optimum installation location.
• Configuration
For adjusting decoding, for data formatting and output, switching inputs/outputs, communication
parameters and interfaces, etc. …
• Diagnostics
For event logging of warnings and errors.
• Maintenance
For updating the firmware.
The user interface of the webConfig tool is largely self-explanatory.
Leuze electronicBCL 600i/BCL 601i50
9.5Module overview in the Configuration menu
The adjustable parameters of the device are clustered in modules in the Configuration menu.
Commissioning – Leuze electronic webConfig tool
Figure 9.2:Module overview in the webConfig tool
The webConfig tool is completely contained in the firmware of the device. Depending on firmware
version, the module overview may vary from that shown above.
The individual modules and their relationships to one another are graphically displayed in the module overview. The display is context sensitive, i.e. click a module to directly access the corresponding submenu.
An overview of the modules:
• Decoder
Definition of code types, code-type features and number of digits of the labels that are to be decoded
• Data processing
Filtering and processing of the decoded data
• Output
Sorting of the processed data and comparison with reference codes
• Communication
Formatting of the data for output via the communication interfaces
• Control
Activation/deactivation of decoding
• Switching input
Activation/deactivation of read processes
• Switching output
Definition of events which activate/deactivate the switching output
• Display
Formatting of the data for output on the display
This chapter describes basic configuration steps which you can carry out either via the webConfig tool or
the display.
Via the webConfig tool
The most convenient way to configure the device is via the webConfig tool. Only the webConfig tool gives
you access to all settings of the device. To use the webConfig tool, you need to establish a USB connection between the device and a PC/laptop.
Notes on use see chapter 9 "Commissioning – Leuze electronic webConfig tool".
Via display
The display offers basic configuration options for the device. Configuration via the display is appropriate if
you want to configure simple reading tasks and you cannot or do not want to set up a USB connection
between the device and a PC/laptop.
Notes on use see chapter 3.5.2 "Status display and operation".
Starting up the device - Configuration
10.1Measures to be performed prior to the initial commissioning
Before commissioning, familiarize yourself with the operation and configuration of the device.
Before connecting the supply voltage, recheck all connections and ensure that they have been properly
made.
Check the applied voltage. It must be in the range between +10V … 30 V DC.
Connecting functional earth FE
Ensure that the functional earth (FE) is connected correctly.
NOTICE
Unimpaired operation is only guaranteed when the functional earth is connected properly. All electrical
disturbances (EMC couplings) are discharged via the functional earth connection.
10.2Starting the device
Connect the +10 … 30 V DC supply voltage (typ. +24 V DC); the device starts up and the bar code read-
ing window appears on the display.
By default, parameter enabling is deactivated and you cannot change any settings. If you wish to carry out
the configuration via the display, you must activate parameter enabling (see chapter 8.6 "Operation",
Parameter enable).
10.3BCL 600i operation
As a first step, you need to set the communication parameters of the device. The BCL 600i can be oper-
ated as stand-alone device, multiNet plus master or multiNet plus slave.
You can make the necessary settings via the display or via the webConfig tool. The settings made by
means of the webConfig tool are described here only briefly.
10.3.1 Operation as stand-alone device
Operation of the BCL 600i is factory-set to stand-alone device.
If you want to operate the BCL 600i as stand-alone device, you can skip the following points. For further
settings see chapter 10.5.
10.3.2 Selecting the operating mode
To operate the BCL 600i as multiNet master or slave, you must set the corresponding operating mode.
Leuze electronicBCL 600i/BCL 601i52
Starting up the device - Configuration
In the webConfig tool
In the main menu, select Configuration -> Communication -> Overview.
Or alternatively in the display
Use the navigation buttons to move through the menu. Activate the desired selection with
the enter button .
In the main menu, select the Parameter menu.
Select the Com menu item.
Press the enter button to enter the menu.
Select the Operating mode menu item.
Press the enter button to enter the menu.
Select the desired menu item: Stand-alone device, Network master or Network slave.
Press the enter button to activate the operating mode.
webConfig tool or display
Set one of the following three operating modes:
• Stand-alone device:
BCL 600i in stand-alone operation (see chapter 10.5)
• Network Master:
BCL 600i as master in multiNet plus. Further settings are required for master operation (see
chapter 10.3.3).
• Network Slave:
BCL 600i as slave in multiNet plus. Further settings are required for slave operation. The configuration of the BCL 600i as multiNet slave corresponds to the configuration of the BCL 601i (see
chapter 10.4).
10.3.3 Operation as multiNet plus master
For operation as multiNet plus master, you must inform the BCL 600i of the maximum number of slaves
to be managed. This is done via the Maximum number of slaves parameter.
Set the Maximum number of slaves parameter to the desired value:
Via webConfig:
Configuration -> Communication -> BUS OUT -> Protocol
Or, alternatively, via the display:
BCL 600i as slave in multiNet plus. Further settings are required for slave operation. The configuration of
the BCL 600i as multiNet slave corresponds to the configuration of the BCL 601i (see chapter 10.4).
In the main menu, select the Parameter menu.
Select the Com menu item.
Press the enter button to enter the menu.
Select the BUS OUT menu item.
Press the enter button to enter the menu.
Select the multiNet master menu item.
Press the enter button to enter the menu.
Press the enter button to enter the menu for setting the maximum number of slaves.
Displayed in the following screen is the preset number 1, which you can now change.
Select the desired number of slaves. An accidental, incorrect entry can be corrected by selecting <-| and
then pressing the enter button.
Select Save.
Press the enter button in order to save the set number of slaves.
Leuze electronicBCL 600i/BCL 601i53
Starting up the device - Configuration
Furthermore, you must configure the BCL 600i in such a way that it can communicate with the superior
host:
Interface standard and communication parameters of the host interface:
Select the desired interface standard (RS 232 / RS 422) and set the associated parameters:
Via webConfig:
Configuration -> Communication -> HOST/BUS IN -> Data transmission
Or, alternatively, via the display:
In the main menu, select the Parameter menu.
Select the Com menu item.
Press the enter button to enter the menu.
Select the HOST/BUS IN menu item.
Press the enter button to enter the menu.
Select the Interface menu item.
Press the enter button to enter the menu.
Press the enter button to enter the menu for setting the interface parameters.
Displayed in the following screen is the preset number 1, which you can now change.
Successively select the parameters available and set the values you require. For a description of the
various configuration options see table 8.4.
Communication protocol of the host interface:
Select the desired protocol and set the associated parameters:
Via webConfig:
First select:
Configuration -> Communication-> HOST/BUS IN -> Protocol
Then select:
Configuration -> Communication-> HOST/BUS IN -> Framing protocol
Or, alternatively, via the display:
First select:
Parameter -> Com -> HOST/BUS IN -> Protocol type
Then select:
Parameter -> Com -> HOST/BUS IN -> Framing protocol
Proceed with the device configuration (see chapter 10.5).
10.4BCL 601i operation
The communication parameters of the HOST/BUS IN and BUS OUT interfaces are permanently set for
operation of the device as multiNet plus slave. To enable communication of the BCL 600i/BCL 601i with
the multiNet plus master, you only need to set the device address.
The BCL 601i always automatically starts as slave participant in multiNet plus. The default
address is 1.
The Leuze multiNet plus permits an address range from 0 to 31. Address 31 must not be used for data
communication. It may only be used temporarily for commissioning.
Set the parameter of the slave address to a value > 0 and < 31. Start with address 01 for the first slave
and assign the following addresses in ascending order and without gaps.
Via webConfig:
Configuration -> Communication -> BUS OUT -> Protocol
Or, alternatively, via the display:
In the main menu, select the Parameter menu.
Leuze electronicBCL 600i/BCL 601i54
Starting up the device - Configuration
Select the Com menu item.
Press the enter button to enter the menu.
Select the BUS OUT menu item.
Press the enter button to enter the menu.
Select the multiNet Slave menu item.
Press the enter button to enter the menu.
Press the enter button to enter the menu for setting the slave address.
Displayed in the following screen is the preset slave address 1, which you can now change.
Select the desired number of slaves. An accidental, incorrect entry can be corrected by selecting <-| and
then pressing the enter button.
Select Save.
Press the enter button in order to save the set number of slaves.
Permissible values for the network address in the Leuze multiNet plus are 0 … 31. Make certain
that a different address is assigned to each multiNet plus participant.
From the hardware address (device address > 0), the BCL 601i detects that networking is
required. It automatically switches to the Leuze multiNet plus network and waits for initialization
by the master.
10.5Further settings
After the basic configuration of the operating mode and the communication parameters, you need to carry
out further settings:
• Decoding and processing the read data
• Control of the decoding
• Control of the switching outputs
10.5.1 Decoding and processing the read data
The device offers the following possibilities:
• Setting the number of labels to be decoded for each reading gate (0 … 64). This is done via the Max.
no. of labels parameter.
• Definition of up to 8 different code types (4 different types if configured via the display). Labels that
match one of the defined code types are decoded. Further parameters can be set for each code
type:
• Code type (symbology)
• Number of digits: either up to 5 different numbers of digits (e.g., 10, 12, 16, 20, 24), or a range
(Interval mode) and up to three additional numbers of digits (e.g., 2 … 10, 12, 16, 26)
• Reading reliability: the set value specifies how many times a label must be read and decoded with
the same result before the result is accepted as valid.
• Activation of the code reconstruction technology (CRT, in the webConfig tool only)
• Additional code type specific settings (in the webConfig tool only)
• Check digit method used for decoding as well as the type of check digit transmission for the output
of the read result. The two possibilities for the latter are Standard (corresponds to the standard for
the selected code type/symbology) and not Standard.
Define at least one code type with the desired settings.
In the webConfig tool: Configuration -> Decoder
Or alternatively in the display: Parameter -> Decoder table
Leuze electronicBCL 600i/BCL 601i55
Data processing via the webConfig tool
In the Data and Output submenus of the Configuration main menu, the webConfig tool provides extensive
data processing options to adapt the functionality of the device to the specific reading task:
• Data filtering and segmentation in the Data submenu:
• Data filtering according to characteristics for handling identical bar code information
• Data segmentation for differentiating between identifier and content of the read data
• Data filtering according to content and/or identifier in order to suppress the output of bar codes
with specific content/identifiers
• Completeness inspection of the read data
• Sorting and formatting the output data in the Output submenu:
• Configuration of up to 3 different sorting criteria. Sorting by physical data and content of the read
bar codes.
• Formatting of the data output for the HOST.
• Formatting of the data output for the display.
10.5.2 Control of the decoding
In general, decoding is controlled via one or more of the configurable switching inputs/outputs. For this
purpose, the respective connection to the SW IN/OUT and POWER interfaces must be configured as a
switching input.
Starting up the device - Configuration
Via a switching input, you can:
• Start decoding
• Stop decoding
• Start decoding and then stop decoding after a configurable time period
• Read a reference code
• Start the automatic code type configuration (AutoConfig)
Connect the required control devices (photoelectric sensor, proximity switch, etc.) to the device (see
chapter 7).
Configure the connected switching inputs according to your requirements. To do this, first set the I/O
mode to Input and then configure the switching behavior.
In webConfig: Configuration -> Device -> Switching inputs/outputs
Or alternatively in the display: Parameter -> Digital SWIO -> Switching input/output 1-4
Alternatively, one can also activate decoding via the online command + and deactivate it via the
online command ’-’. For further information on the online commands, see chapter 11 "Online
commands".
Advanced decoder control in the webConfig tool
The webConfig tool provides advanced functions, in particular for deactivating decoding. These may be
accessed via the Control submenu of the Configuration main menu. You can:
• Activate decoding automatically (delayed)
• Stop decoding after a maximum reading gate time
• Stop decoding via the completeness mode, if:
• the maximum number of bar codes to be decoded has been decoded
• a positive reference code comparison has taken place.
10.5.3 Control of the switching outputs
By using the switching inputs/outputs of the device, external event-controlled functions can be implemented without assistance from the superior process control. For this purpose, the respective connection
at the SW IN/OUT and POWER interfaces must be configured as a switching output.
Leuze electronicBCL 600i/BCL 601i56
A switching output can be activated:
• At the start/end of the reading gate
• Depending on the read result:
• Reference code comparison positive/negative
• Read result valid/invalid
• Depending on the state of the device:
• Ready/not ready
• Data transmission active/not active
• Active/standby
• Error/no error
•etc.
Connect the required switching outputs (see chapter 7).
Configure the connected switching outputs according to your requirements. To do this, first set the I/O
mode to Output and then configure the switching behavior.
In webConfig: Configuration -> Device -> Switching inputs/outputs
Or alternatively in the display: Parameter -> Digital SWIO -> Switching input/output 1-4
10.6Transmitting configuration data
Instead of going through the tedious task of configuring every parameter of the device individually, you can
also conveniently transfer configuration data.
Starting up the device - Configuration
In general, there are two possibilities for transferring configuration data between two bar code readers:
• Storage in a file and transfer using the webConfig tool
• Using the external parameter memory
10.6.1 Via the webConfig tool
With the webConfig tool, you can store entire configurations of the device on data carriers and transfer
them from these to the device.
This storage of configuration data is especially useful if you want to store basic configurations which will
require only minor changes.
In the webConfig tool, you store the configuration data via the buttons in the upper part of the middle
window of all submenus of the Configuration main menu.
10.6.2 With the external parameter memory
The use of the external parameter memory permits the easy replacement of a defective device on site.
This requires an external parameter memory to be installed permanently to the USB connection of the
device.
The device stores a copy of the current configuration in the external parameter memory. This copy is
immediately updated when the configuration is changed via the display or by a superior host system (PC/
PLC) via online commands.
Leuze electronicBCL 600i/BCL 601i57
11Online commands
Online commands can be used to send commands directly to the device for control and configuration.
For this purpose, the device must be connected to a host- or service computer via the interface. The
commands described can be sent either via the host or the service interface.
Online commands
With the commands, you can:
• control/decode.
• read/write/copy parameters.
• carry out an automatic configuration.
• teach-in/set reference codes.
• call up error messages.
• call up statistical device information.
• carry out a software reset in order to reinitialize the device.
Syntax
Online commands consist of one or two ASCII characters followed by command parameters. No separa-
tion characters may be entered between the command and the command parameter(s). Both small and
capitalized letters can be used.
Example:
Online commands
Command CA:autoConfig function
Parameter +:Activation
Transmitted is:CA+
Most online commands are acknowledged by the device and any requested data returned. For commands
that are not acknowledged, command execution can be observed or monitored directly on the device.
11.1General online commands
Software version number
CommandV
DescriptionRequests device version information
ParameterNo
AcknowledgmentBCL 600i SM 100 V 1.3.8 2008-02-15
The first line contains the device type, followed by the device version number
and version date. (The data which is actually displayed may vary from the values given here.)
This command returns the major release number of the software packet. This major release
number also appears on the display during start-up.
This command can be used to check whether the connected host or service computer is properly
connected and configured. If you do not receive an acknowledgment, please check interface
connections, protocol and service switches.
Leuze electronicBCL 600i/BCL 601i58
Online commands
Software reset
CommandH
DescriptionCarries out a software reset. The device is restarted and reinitialized, leaving
it in the same state as when the supply voltage is switched on
ParameterNo
AcknowledgmentS (start signal)
Code recognition
CommandCC
DescriptionDetects an unknown bar code and outputs number of digits, code type, and
code information to the interface, without storing the bar code in the parameter memory.
ParameterNo
Acknowledgmentxx yy zzzzzz
xx:Number of digits of the read code
yy:Code type of the read code
012/5 Interleaved
02Code 39
06 UPC (A, E)
07EAN
08Code 128, EAN 128
10EAN Addendum
11Codabar
zzzzzzContents of the decoded label. A
↑ appears if the label was not
correctly read
autoConfig
CommandCA
DescriptionActivates or deactivates the autoConfig function. Certain label reading param-
eters are programmed automatically in the setup by the labels which the
device reads while the autoConfig function is active.
Parameter+Activates autoConfig
/Rejects the last code read
-Deactivates autoConfig and stores the decoded data in the cur-
rent parameter set
Leuze electronicBCL 600i/BCL 601i59
CommandCA
AcknowledgmentCSx
xStatus
0Valid CA command
1Invalid command
2autoConfig could not be activated
3autoConfig could not be deactivated
4Result could not be deleted
Descriptionxx yy zzzzzz
xxNumber of digits of the read code
yyCode type of the read code
012/5 Interleaved
Online commands
02Code 39
06UPC (A, E)
07EAN
08Code 128, EAN 128
10EAN Addendum
11Codabar
zzzzzzContents of the decoded label. A
↑ appears if the label was not
correctly read
Alignment mode
CommandJP
DescriptionThis command simplifies mounting and alignment of the device. After activat-
ing the function with JP+, the device continuously supplies status information
to the serial interfaces.
With this online command, the scanner is set to terminate the decoding after
100 successfully decoded labels and output the status information. Subsequently, the read process is reactivated automatically.
In addition to the output of the status information, the laser beam is used to
display the reading quality. Depending on how many read results could be
extracted, the duration of the laser's off time increases.
If the reading quality is high, the laser beam flashes in brief, regular intervals.
The worse the decoder decodes, the longer the pauses become during which
the laser is switched off. The flashing intervals become more and more irregular because the laser may, in total, be active for longer to extract more labels.
The duration of the pauses has been stepped in such a way that they can be
distinguished by the eye.
Parameter+Starts the adjustment mode.
-Ends the adjustment mode.
Leuze electronicBCL 600i/BCL 601i60
Online commands
CommandJP
Acknowledgmentyyy_zzzzzz
yyyRead quality in %. A high process availability is ensured at read
qualities > 75 %.
zzzzzzBar code information.
Manual definition of the reference code
CommandRS
DescriptionThis command can be used to define a new reference code in the device by
means of direct input via the serial interface. The data is saved in the parameter set according to your input under reference code 1 through 2 and stored in
the working buffer for direct further processing.
ParameterRSyvxxzzzzzzzz
y, v, x and z are placeholders (variables) for the actual input.
DescriptionThis command enables a reference code to be defined quickly by reading an
example label.
Leuze electronicBCL 600i/BCL 601i61
Online commands
CommandRT
ParameterRTy
yFunction
1Defines reference code 1
2Defines reference code 2
+Activates the definition of reference code 1 up to the value of
Parameter no_of_labels
-Ends the teach event
AcknowledgmentThe device first responds with the command RS and corresponding status
(see command RS). After a bar code has been read, it sends the result in the
following format:
RCyvxxzzzzz
y, v, x and z are placeholders (variables) for the actual input.
yDefined reference code no.
1(code 1)
2(code 2)
vStorage location for reference code
0RAM+EEPROM,
3RAM only
xxDefined code type (see command CA)
zDefined code information (1 … 63 characters)
With this function, only code types are recognized that are identified using the autoConfig func-
tion or which were set in the set-up.
After each reading via an RTy command, explicitly switch off the function again since failure to do so
will interfere with other commands as well as prevent execution of a new RTx command.
Reading a reference code
CommandRR
DescriptionThe command reads out the reference code defined in the device. If no
parameters are specified, all defined codes are output.
Parameter<reference code number>
1 … 2 value range of reference code 1 to 2
Leuze electronicBCL 600i/BCL 601i62
Online commands
CommandRR
AcknowledgmentIf no reference codes are defined, the device responds with the RS command
and corresponding status (see command RS). For valid codes, the output corresponds to the following format:
RCyvxxzzzzzz
y, v, x and z are placeholders (variables) for the actual input.
yDefined reference code no.
1(code 1)
2(code 2)
vStorage location for reference code
0RAM+EEPROM,
3RAM only
xxDefined code type (see command CA)
zDefined code information (1 … 63 characters)
11.2Online commands for system control
Activating sensor input
Command+
DescriptionThe command activates decoding. This command is used to activate the
reading gate. It remains active until it is deactivated by one of the following criteria:
• Deactivation by a manual command
• Deactivation by a switching input
• Deactivation upon reaching the specified read quality (equal scans)
• Deactivation by timeout
• Deactivation upon reaching a preset number of scans without informa-
tion.
ParameterNo
AcknowledgmentNone
Deactivating sensor input
CommandDescriptionThe command deactivates decoding. This command can be used to deacti-
vate the reading gate. Following deactivation, the read result is output.
Because the reading gate was manually deactivated and, thus, no GoodRead
criterion was met, a NoRead is output.
ParameterNo
AcknowledgmentNone
Leuze electronicBCL 600i/BCL 601i63
11.3Online commands for the parameter set operations
Copying parameter set
CommandPC
DescriptionThis command can only be used to copy parameter sets in their entirety. This
can be used to replicate the three parameter sets default, permanent and
operating parameters on the basis of one another. In addition, this command
also be used to restore the factory settings.
ParameterPC<Source type><Target type>
Online commands
<Source
type>
Parameter data set that is to be copied,
unit [dimensionless]
0Parameter data set in permanent memory
2Default or factory parameter set
3 Operating parameter data set in volatile memory
<Target
type>
Parameter set into which the data is to be copied,
unit [dimensionless]
0 Parameter data set in permanent memory
3 Operating parameter data set in volatile memory
Permissible combinations here include:
03Copying the data set from the permanent memory to the operat-
ing parameter data set
30Copying the operating parameter data set to the permanent
parameter set memory
20Copying the default parameters to the permanent memory and to
the main memory
AcknowledgmentPS=<aa>
<aa> Status acknowledgment,
00Ok
01Syntax error
02Impermissible command length
03Reserved
04Reserved
05Reserved
06Impermissible combination, source type - target type
unit [dimensionless]
Leuze electronicBCL 600i/BCL 601i64
Online commands
Requesting parameter data set from device
CommandPR
DescriptionThe parameters of the device are grouped together in a parameter set and
permanently stored in memory. There is one parameter set in permanent
memory and one operating parameter set in volatile memory; in addition,
there is a default parameter set (factory parameter set) for initialization. This
command can be used to edit the first two parameter sets (in permanent and
volatile memory). A check sum can be used for reliable parameter transfer.
<BCC type>Check-digit function during transmission,
unit [dimensionless]
0Not used
3BCC mode 3
<PS type>Memory from which the values are to be read,
unit [dimensionless]
0Parameter values stored in the flash memory
1Reserved
2 Default values
3 Operating values in RAM
<Address> Relative address of the data within the data set
aaaa Four-digit,
unit [dimensionless]
<Data length> Length of the parameter data to be transferred
bbbbFour-digit,
unit [length in bytes]
<BCC>Check sum calculated as specified under BCC type
Leuze electronicBCL 600i/BCL 601i65
CommandPR
Online commands
Acknowledgment
positive
PT<BCC type><PS type><Status><Start>
<Parameter value - address><Parameter value - address+1>…
[;<Address><Parameter value - address>][<BCC>]
<BCC type>Check-digit function during transmission,
unit [dimensionless]
0Not used
3BCC mode 3
<PS type> Memory from which the values are to be read,
unit [dimensionless]
0Parameter values stored in the flash memory
2 Default values
3 Operating values in RAM
<Status>Mode of parameter processing,
unit [dimensionless]
0 No further parameters
1 Additional parameters follow
Acknowledgment
negative
<Start> Relative address of the data within the data set,
aaaa Four-digit,
unit [dimensionless]
<P.value A.> Parameter value of the parameter stored at this address; the
parameter set data 'bb' is converted from HEX format to a
2-byte ASCII-format for transfer.
<BCC> Check sum calculated as specified under BCC type
PS=<aa>
Parameter reply:
<aa> Status acknowledgment,
unit [dimensionless]
01Syntax error
02Impermissible command length
03Impermissible value for checksum type
04Invalid check sum received
05Impermissible number of data requested
06Requested data does not (any longer) fit in the transmission
buffer
07Impermissible address value
08Read access after end of data set
09Impermissible QPF data set type
Leuze electronicBCL 600i/BCL 601i66
Online commands
Determining parameter set difference to default parameters
CommandPD
DescriptionThis command outputs the difference between the default parameter set and
the operating parameter set or the difference between the default parameter
set and the permanent parameter set.
Comment:
The reply supplied by this command can e.g. be directly used for programming a device with factory settings, whereby this device receives the same
configuration as the device on which the PD-sequence was executed.
ParameterPD<P.set1><P.set2>
<P.set1>Parameter data set that is to be copied,
unit [dimensionless]
0Parameter data set in permanent memory
2Default or factory parameter set
<P.set2> Parameter set into which the data is to be copied,
unit [dimensionless]
0Parameter data set in permanent memory
3Operating parameter data set in volatile memory
Permissible combinations here include:
20Output of the parameter differences between the default and the
permanently saved parameter set
23Output of the parameter differences between the default parame-
ter set and the operating parameter set saved in volatile memory
03Output of the parameter differences between the permanent
parameter set and the operating parameter set saved in volatile
memory
<Addr.> Relative address of the data within the data set
aaaa Four-digit,
unit [dimensionless]
<P.value> Parameter value of the -bb- parameter stored at this address.
The parameter set data is converted from HEX format to a
2-byte-ASCII format for transfer.
Acknowledgment
PS=<aa>
negative
<aa> Status acknowledgment,
unit [dimensionless]
0No difference
1Syntax error
2Impermissible command length
6Impermissible combination, parameter set 1 and parameter set 2
8Invalid parameter set
Writing parameter set
CommandPT
DescriptionThe parameters of the device are grouped together in a parameter set and
permanently stored in memory. There is one parameter set in permanent
memory and one operating parameter set in volatile memory; in addition,
there is a default parameter set (factory parameter set) for initialization. This
command can be used to edit the first two parameter sets (in permanent and
volatile memory). A check sum can be used for reliable parameter transfer.
- Switching input: 10 … 30 V DC depending on
supply voltage, I max. = 8 mA
- Switching output: 10 … 30 V DC depending on
supply voltage, I max. = 60 mA (short-circuit proof)
Switching inputs/outputs protected against polarity
reversal!
Operating voltage10 … 30 V DC (Class II, protection class III)
Power consumptionMax. 10 W
Table 15.5: Operating and display elements
DisplayMonochromatic graphical display, 128 x 64 pixel,
with background lighting
Keyboard4 buttons
LEDs2 LEDs for power (PWR) and bus state (NET), two-
colored (red/green)
Table 15.6:Mechanical data
Degree of protectionIP 65 (with screwed-on M 12 connectors or
mounted caps)
Weight1.1 kg
Dimensions (H x W x D)63 x 123.5 x 106.5 mm
HousingDiecast aluminum
Table 15.7: Environmental data
Operating temperature range0 C … +40 °C
Storage temperature range-20 °C … +70 °C
Air humidityMax. 90% rel. humidity, non-condensing
VibrationIEC 60068-2-6, test Fc
ShockIEC 60068-2-27, test Ea
Continuous shockIEC 60068-2-29, test Eb
Electromagnetic compatibilityEN 55022;
IEC 61000-6-2 (contains IEC 61000-4-2, -3, -4, -5
and -6)
a) This is a Class A product. In a domestic environment this product may cause radio interference, in which case the oper-
ator may be required to take adequate measures.
Leuze electronicBCL 600i/BCL 601i75
a)
15.1.2 Oscillating-mirror scanner
Specifications are the same as for line scanner with the following differences:
Table 15.8: Optics
Beam exitLateral zero position at an angle of 90°
Beam deflectionVia rotating polygon wheel (horizontal) and step-
Oscillation frequency0 … 10 Hz (adjustable, max. frequency is depen-
Max. swivel angle±20° (adjustable)
Reading field heightsee chapter 15.5 "Reading field curves / optical
Table 15.9: Electrical equipment
Power consumptionMax. 14 W
Technical data
ping motor with mirror (vertical)
dent on set swivel angle)
data"
Table 15.10: Mechanical data
Weight1.5 kg
Dimensions (H x W x D)84 x 173 x 147 mm
15.2Heating models of the bar code readers
The devices of the BCL 600i series are optionally available as models with integrated heating. In this case,
heating is permanently installed ex works. Self-installation on-site by the user is not possible!
Features
• Integrated heating (permanently installed)
• Extends the application range of the device to -35 °C
• Supply voltage 24 V DC ±20%
• Enabling the device through an internal temperature switch (switch-on delay about 30 min for
24 V DC and minimum ambient temperature of -35 °C)
• Necessary conductor cross-section for the voltage supply: at least 0.75 mm
cables is, thus, not possible
Structure
The heating consists of two parts:
• The front cover heater
• The housing heater
²
; the use of ready-made
Function
When the 24 V DC supply voltage is applied to the device, a temperature switch initially only connects the
heating to electrical power (front cover heater and housing heater). During the heating phase (around
30 min), when the inside temperature rises above 15 °C, the temperature switch connects the device to
the supply voltage. This is followed by the self test and the changeover to read operation. The “PWR” LED
lights up showing overall readiness for operation.
When the inside temperature reaches approx. 18 °C, another temperature switch turns the housing heater
off and, if necessary, back on again (if the inside temperature drops below 15 °C). This does not interrupt
the read operation. The front cover heater remains activated until an inside temperature of 25 °C is
reached. At temperatures above this, the front cover heater switches off and, with a switching hysteresis
of 3 °C, back on again at an inside temperature below 22 °C.
Leuze electronicBCL 600i/BCL 601i76
Electrical connection
The required core cross-section of the connection cable for the voltage supply must be at least 0.75 mm
CAUTION
The voltage supply must not be looped through from one device to the next.
Power consumption
The energy requirement depends on the model:
• the line scanner with heating typically consumes 40 W and a maximum of 50 W power.
• the line scanner with oscillating mirror and heating typically consumes 60 W and a maximum of
75 W.
These values are based on operation with unconnected switching outputs.
15.2.1 Line scanner with heater
Technical data same as for line scanner without heating, however with the following differences:
Table 15.11:Specifications of the line scanners with heating
Technical data
²
.
TypeBCL 600i
Stand alone or multiNet plus
BCL 601i
multiNet plus slave
master
DesignLine scanner with heater
Electrical data
Operating volt-
24 V DC ±20 %
age
Power
Max. 50 W
consumption
Structure of the
Housing heating and separate heating of the optics glass
heating
Warmup timeMin. 30 min at +24 V DC and an ambient temperature of -35 °C
Min. conductor
cross section
Conductor cross section of at least 0.75 mm
through of the voltage supply to multiple heating devices is not permissible. Standard,
²
for the supply-voltage line. Wiring
M 12 ready-made cable is not usable (insufficient cable cross-section)
Environmental data
Operating tem-
-35 °C … +40 °C
perature range
Storage temper-
-20 °C … +70 °C
ature range
Leuze electronicBCL 600i/BCL 601i77
15.2.2 Oscillating-mirror scanner with heating
Technical data same as for line scanner without heating, however with the following differences:
Table 15.12:Specifications of the oscillating-mirror scanners with heating
Technical data
TypeBCL 600i
Stand alone or multiNet plus
BCL 601i
multiNet plus slave
master
DesignOscillating-mirror scanner with heating
Optical data
Useful opening
Max. 50°
angle
Max. swivel
±12°(adjustable)
angle
Electrical data
Operating volt-
24 V DC ±20%
age
Power con-
Max. 75 W
sumption
Structure of the
Housing heating and separate heating of the optics glass
heating
Warmup timeMin. 30 min at +24 V DC and an ambient temperature of -35 °C
Min. conductor
cross section
Environmental data
Operating tem-
perature range
Storage temper-
ature range
Conductor cross section of at least 0.75 mm
²
for the supply-voltage line. Wiring
through of the voltage supply to multiple heating devices is not permissible. Standard,
M 12 ready-made cable not usable (insufficient cable cross-section).
-35 °C … +40 °C
-20 °C … +70 °C
Leuze electronicBCL 600i/BCL 601i78
15.3Dimensioned drawings
1
1
23
Technical data
1Optical axis
2M4, 7 mm deep
3M4, 6 mm deep
Figure 15.1: Dimensioned drawing - line scanner
Leuze electronicBCL 600i/BCL 601i79
Technical data
1
2
3
4
5
1Optical axis
2Optical swivel range
3Opening angle
4M4, 7 mm deep
5M4, 6 mm deep
Please note that the size of the bar code module influences the maximum reading distance and
the width of the reading field. Therefore, when selecting a mounting location and/or the bar code
label, take into account the different reading characteristics of the scanner with various bar code
modules.
MModule: The narrowest line or space of a bar code in mm
BWide character: Wide bars and gaps are a multiple (ratio) of the module. Module x Ratio = ZB
Z
(Normal Ratio 1 : 2.5)
ZQuiet zone: The quiet zone should be at least 10 times the module, but not less than 2.5 mm.
B
LCode length: The length of the bar code in mm including the start and stop characters. The quiet
zone is included depending on the code definition.
LBar length: height of the elements in mm
S
Figure 15.5: The most important characteristics of a bar code
Technical data
The range in which the bar code can be read by the device (the so-called reading field) depends on the
quality of the printed bar code and its dimensions.
Therefore, above all, the module of a bar code is decisive for the size of the reading field.
A rule of thumb: The smaller the module of the bar code is, the smaller the maximum reading
distance and reading field width will be
15.6Reading field curves
Please notice that the real reading fields are also influenced by factors such as labeling material,
printing quality, reading angle, printing contrast etc., and may thus deviate from the reading fields
specified here.
The zero position of the reading distance always refers to the front edge of the housing of the beam exit
and is shown for the two housing types of the device (see figure 15.6).
Leuze electronicBCL 600i/BCL 601i82
Technical data
x
1
1
1Zero position
xDistance acc. to reading field curves
Figure 15.6: Zero position of the reading distance
Reading conditions for the reading field curves
Table 15.13:Reading conditions
Bar code type2/5 Interleaved
Ratio1:2.5
ANSI specificationClass A
Reading rate> 75%
Leuze electronicBCL 600i/BCL 601i83
15.6.1 Medium Density (M) - optics
2003000100400500600700800900100011001200
100
200
300
400
-100
-200
-300
-400
1
2
3
y
x
2003000100-100400500600700800900100011001200
100
200
300
400
-100
-200
-300
-400
123
z
x
Technical data
xReading field distance [mm]
yReading field width [mm]
1Module = 0.25 mm: 450 mm - 750 mm (300 mm depth of field)
2Module = 0.3 mm: 400 mm - 800 mm (400 mm depth of field)
3Module = 0.35 mm: 400 mm - 900 mm (500 mm depth of field)
Figure 15.7: Medium Density reading field curve for line scanner
xReading field distance [mm]
zReading field height [mm]
aSwivel range, ± 20°
1Module = 0.25 mm: 450 mm - 750 mm (300 mm depth of field)
2Module = 0.3 mm: 400 mm - 800 mm (400 mm depth of field)
3Module = 0.35 mm: 400 mm - 900 mm (500 mm depth of field)
Figure 15.8: Lateral reading field curve - Medium Density for oscillating-mirror scanner
xReading field distance [mm]
yReading field width [mm]
1Module = 0.3 mm: 600 mm - 1050 mm (450 mm depth of field)
2Module = 0.35 mm: 500 mm - 1200 mm (700 mm depth of field)
3Module = 0.5 mm: 450 mm - 1450 mm (1000 mm depth of field)
Figure 15.9: Reading field curve - Low Density for line scanner
xReading field distance [mm]
zReading field height [mm]
aSwivel range, ± 20°
1Module = 0.3 mm: 600 mm - 1050 mm (450 mm depth of field)
2Module = 0.35 mm: 500 mm - 1200 mm (700 mm depth of field)
3Module = 0.5 mm: 450 mm - 1450 mm (1000 mm depth of field)
Figure 15.10:Lateral reading field curve - Low Density for oscillating-mirror scanner
15.7Reading field curves for heating devices
The reading field curves of the heating devices differ to some extent from the normal reading curves due
to the optics heating and are somewhat reduced in the reading field width as well as in the reading field
height!
• The maximum opening angle for all oscillating mirror devices of the BCL 600i series is reduced to
±28° (without heating = ±30°).
• In addition, the maximum swivel range for all oscillating mirror devices of the BCL 600i series is
reduced to ±12° (without heating = ±20°).
• The reading field curves and opening angles are unchanged for all line scanners with heating of the
series BCL 600i.
For details, please refer to the following reading field curves for the heating devices.
x
Leuze electronicBCL 600i/BCL 601i86
15.7.1 Medium Density (M) - optics: (with heating)
y
400
300
200
100
Technical data
2
-100
-200
-300
-400
2003000100400500600700800900100011001200
xReading field distance [mm]
yReading field width [mm]
1Module = 0.25 mm: 450 mm - 750 mm (300 mm depth of field)
2Module = 0.3 mm: 400 mm - 800 mm (400 mm depth of field)
3Module = 0.35 mm: 400 mm - 900 mm (500 mm depth of field)
Figure 15.11:“Medium Density” reading field curve for line scanner with heating
The reading field curve applies for the reading conditions stated above (see table 15.13).
15.7.2 Medium Density (M) - optics: (with heating)
y
400
1
3
x
300
2
200
100
1
-100
-200
-300
-400
xReading field distance [mm]
yReading field width [mm]
1Module = 0.25 mm: 450 mm - 750 mm (300 mm depth of field)
2Module = 0.3 mm: 400 mm - 800 mm (400 mm depth of field)
3Module = 0.35 mm: 400 mm - 900 mm (500 mm depth of field)
Figure 15.12:“Medium Density” reading field curve for oscillating-mirror scanners with heating
2003000100400500600700800900100011001200
3
x
Leuze electronicBCL 600i/BCL 601i87
Technical data
2003000100-100400500600700800900100011001200
100
200
300
400
-100
-200
-300
-400
1a23
z
x
xReading field distance [mm]
yReading field width [mm]
aSwivel range, ± 12°
1Module = 0.25 mm: 450 mm - 750 mm (300 mm depth of field)
2Module = 0.3 mm: 400 mm - 800 mm (400 mm depth of field)
3Module = 0.35 mm: 400 mm - 900 mm (500 mm depth of field)
Figure 15.13:Lateral “Medium Density” reading field curve for oscillating-mirror scanners with heating
The reading field curve applies for the reading conditions stated above (see table 15.13).
xReading field distance [mm]
yReading field width [mm]
1Module = 0.3 mm: 600 mm - 1050 mm (450 mm depth of field)
2Module = 0.35 mm: 500 mm - 1200 mm (700 mm depth of field)
3Module = 0.5 mm: 450 mm - 1450 mm (1000 mm depth of field)
Figure 15.14:“Low Density” reading field curve for line scanner with heating
The reading field curve applies for the reading conditions stated above (see table 15.13).
xReading field distance [mm]
yReading field width [mm]
1Module = 0.3 mm: 600 mm - 1050 mm (450 mm depth of field)
2Module = 0.35 mm: 500 mm - 1200 mm (700 mm depth of field)
3Module = 0.5 mm: 450 mm - 1450 mm (1000 mm depth of field)
Figure 15.15:“Low Density” reading field curve for oscillating-mirror scanners with heating
xReading field distance [mm]
yReading field width [mm]
aSwivel range, ± 12°
1Module = 0.3 mm: 600 mm - 1050 mm (450 mm depth of field) 2/5l
2Module = 0.35 mm: 500 mm - 1200 mm (700 mm depth of field) 2/5l
3Module = 0.5 mm: 450 mm - 1450 mm (1000 mm depth of field) 2/5l
Figure 15.16:Lateral “Low Density” reading field curve for oscillating-mirror scanners with heating
The reading field curve applies for the reading conditions stated above (see table 15.13).
A list with all available device types can be found on the Leuze electronic website at
www.leuze.com.
16.2Type overview
Table 16.2:BCL 600i / BCL 601i part numbers
Part no.Part designationDescription
50112757BCL 600i SM 102Line scanner, front beam exit, Medium Density
50132844BCL 600i OM 100Oscillating-mirror scanner, Medium Density
N: High Density (close)
M: Medium Density (medium distance)
F: Low Density (large distance)
L: Ultra Low Density (very large distances)
0 = Perpendicular
2 = Front
50132845BCL 600i SM 102 HLine scanner, beam exit at the front, with heating,
Medium Density
50132846BCL 600i OM 100 HOscillating-mirror scanner with heating,
Medium Density
50132847BCL 600i SF 102Line scanner, front beam exit, Low Density
Leuze electronicBCL 600i/BCL 601i92
Part no.Part designationDescription
50132848BCL 600i OF 100Oscillating-mirror scanner, Low Density
50132849BCL 600i SF 102 HLine scanner, beam exit at the front with heating,
50132850BCL 600i OF 100 HOscillating-mirror scanner with heating,
16.3Accessories
Table 16.3:Accessories
Part no.Part designationDescription
Voltage supply connection cables
50104557K-D M12A-5P-5m-PVCM 12 socket for PWR, axial connector, open cable
50104559K-D M12A-5P-10m-PVCM 12 socket for PWR, axial connector, open cable
Ordering information and accessories
Low Density
Low Density
end, cable length 5 m
end, cable length 10 m
BUS IN connection cables, M 12 connector, axial cable outlet, open cable end
50104181KB PB-2000-BACable length 2 m
50104180KB PB-5000-BACable length 5 m
50104179KB PB-10000-BACable length 10 m
50104178KB PB-15000-BACable length 15 m
50104177KB PB-20000-BACable length 20 m
50104176KB PB-25000-BACable length 25 m
50104175KB PB-30000-BACable length 30 m
BUS OUT connection cables, M 12 connector, axial cable outlet, open cable end
50104188KB PB-2000-SACable length 2 m
50104187KB PB-5000-SACable length 5 m
50104186KB PB-10000-SACable length 10 m
50104185KB PB-15000-SACable length 15 m
50104184KB PB-20000-SACable length 20 m
50104183KB PB-25000-SACable length 25 m
50104182KB PB-30000-SACable length 30 m
BUS OUT connection cables, M 12 connector + M 12 socket, axial cable outlets
50104096KB PB-1000-SBACable length 1 m
50104097KB PB-2000-SBACable length 2 m
50104098KB PB-5000-SBACable length 5 m
50104099KB PB-10000-SBACable length 10 m
50104100KB PB-15000-SBACable length 15 m
Leuze electronicBCL 600i/BCL 601i93
Ordering information and accessories
Part no.Part designationDescription
50104101KB PB-20000-SBACable length 20 m
50104174KB PB-25000-SBACable length 25 m
50104173KB PB-30000-SBACable length 30 m
Connector
50020501KD 095-5AM 12 socket for voltage supply
50040155KS 095-4AM 12 connector for SW IN/OUT
50038538KD 02-5-BAM 12 socket for HOST or BUS IN
50038537KD 02-5-SAM 12 connector for BUS OUT
50109834KDS BUS OUTM 12 T-connector for BUS OUT
Terminating resistor
50038539TS 02-4-SA M 12M 12 connector with integrated terminating
resistor for BUS OUT
USB cables
50107726KB USB-ServiceUSB service cable
External parameter memory
50108833USB Memory SetExternal USB parameter memory
Mounting devices
50027375BT 56Mounting device for rod
50111224BT 59Mounting bracket
Leuze electronicBCL 600i/BCL 601i94
17EC Declaration of Conformity
The bar code readers of the BCL 600 series have been developed and manufactured in accordance with
the applicable European standards and directives.
The manufacturer of the product, Leuze electronic GmbH + Co. KG in D-73277 Owen, possesses a certified quality assurance system in accordance with ISO 9001.
EC Declaration of Conformity
Leuze electronicBCL 600i/BCL 601i95
18Appendix
18.1ASCII character set
ASCIIDec.Hex.Oct.DesignationMeaning
NUL0000ZEROZero
SOH1011START OF HEADINGStart of heading
STX2022START OF TEXTStart of text characters
ETX3033END OF TEXTLast character of text
EOT4044END OF TRANSMISS.End of transmission
ENQ5055ENQUIRYRequest for data trans.
ACK6066ACKNOWLEDGEPositive acknowledgment
BEL7077BELLBell signal
BS80810BACKSPACEBackspace
Appendix
HT90911HORIZ. TABULATORHorizontal tabulator
LF100A12LINE FEEDLine feed
VT110B13VERT. TABULATORVertical tabulator
FF120C14FORM FEEDForm feed
CR130D15CARRIAGE RETURNCarriage return
SO140E16SHIFT OUTShift out
SI150F17SHIFT INShift in
DLE161020DATA LINK ESCAPEData link escape
DC1171121DEVICE CONTROL 1Device control character 1
DC2181222DEVICE CONTROL 2Device control character 2
DC3191323DEVICE CONTROL 3Device control character 3
DC4201424DEVICE CONTROL 4Device control character 4
NAK211525NEG. ACKNOWLEDGENegative acknowledge
SYN221626SYNCHRONOUS IDLESynchronization
ETB2317 27EOF TRANSM. BLOCK End of data transmission block
CAN241830CANCELInvalid
EM251931END OF MEDIUMEnd of medium
SUB261A32SUBSTITUTESubstitution
ESC271B33ESCAPEEscape
FS281C34FILE SEPARATORFile separator
GS291D35GROUP SEPARATORGroup separator
RS301E36RECORD SEPARATORRecord separator
Leuze electronicBCL 600i/BCL 601i96
ASCIIDec.Hex.Oct.DesignationMeaning
US311F37UNIT SEPARATORUnit separator
SP322040SPACESpace
!332141EXCLAMATION POINTExclamation point
" 342242QUOTATION MARKQuotation mark
# 352343NUMBER SIGN Number sign
$ 362444DOLLAR SIGNDollar sign
%372545PERCENT SIGNPercent sign
& 382646AMPERSANDAmpersand
’392747APOSTROPHEApostrophe
(402850OPEN. PARENTHESISOpen parenthesis
)412951CLOS. PARENTHESISClosed parenthesis
Appendix
*422A52ASTERISKAsterisk
+ 432B53PLUSPlus sign
, 442C54COMMAComma
-452D55HYPHEN (MINUS)Hyphen
.462E56PERIOD (DECIMAL)Period (decimal)
/ 472F57SLANTSlant
0 4830600Number
1 4931611Number
2 5032622Number
3 5133633Number
4 5234644Number
5 5335655Number
6 5436666Number
7 5537677Number
8 5638708Number
9 5739719Number
: 583A72COLONColon
;593B73SEMICOLONSemicolon
<603C74LESS THANLess than
= 613D75EQUALSEquals
>623E76GREATER THANGreater than
?633F77QUESTION MARKQuestion mark
@6440100COMMERCIAL ATCommercial AT
Leuze electronicBCL 600i/BCL 601i97
ASCIIDec.Hex.Oct.DesignationMeaning
A 6541101ACapital letter
B 6642102BCapital letter
C 6743103CCapital letter
D 6844104DCapital letter
E 6945105ECapital letter
F 7046106FCapital letter
G 7147107GCapital letter
H 7248110HCapital letter
I7349111I Capital letter
J744A112JCapital letter
K754B113KCapital letter
Appendix
L764C114LCapital letter
M774D115MCapital letter
N784E116NCapital letter
O794F117OCapital letter
P 8050120PCapital letter
Q 8151121QCapital letter
R 8252122RCapital letter
S 8353123SCapital letter
T 8454124TCapital letter
U 8555125UCapital letter
V 8656126VCapital letter
W8757 127WCapital letter
X 8858130XCapital letter
Y 8959131YCapital letter
Z905A132ZCapital letter
[915B133OPENING BRACKETOpening bracket
\925C134REVERSE SLANTReverse slant
]935D135CLOSING BRACKETClosing bracket
^945E136CIRCUMFLEXCircumflex
_955F137UNDERSCOREUnderscore
‘9660140GRAVE ACCENTGrave accent
a9761141aLower case letter
b9862142bLower case letter
Leuze electronicBCL 600i/BCL 601i98
ASCIIDec.Hex.Oct.DesignationMeaning
c9963143cLower case letter
d10064144dLower case letter
e10165145eLower case letter
f10266146fLower case letter
g10367147gLower case letter
h10468150hLower case letter
i10569151iLower case letter
j1066A152jLower case letter
k1076B153kLower case letter
l1086C154lLower case letter
m1096D155mLower case letter
Appendix
n1106E156nLower case letter
o1116F157oLower case letter
p11270160pLower case letter
q11371161qLower case letter
r11472162rLower case letter
s11573163sLower case letter
t11674164tLower case letter
u11775165uLower case letter
v11876166vLower case letter
w11977167wLower case letter
x12078170xLower case letter
y12179171yLower case letter
z1227A172zLower case letter
{1237B173OPENING BRACEOpening brace
|1247C174VERTICAL LINEVertical line
}1257D175CLOSING BRACEClosing brace
~1267E176TILDETilde
DEL1277F177DELETE (RUBOUT)Delete
Leuze electronicBCL 600i/BCL 601i99
18.2Bar code samples
18.2.1 Module 0.3
Figure 18.1: Code type 01: Interleaved 2 of 5
Figure 18.2: Code type 02: Code 39
Appendix
Figure 18.3: Code type 06: UPC-A
Figure 18.4: Code type 07: EAN 8
Figure 18.5: Code type 08: EAN 128
Figure 18.6: Code type 10: EAN 13 Add-on
Leuze electronicBCL 600i/BCL 601i100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.