Figure 5.6:"High Density" reading field curve for line scanner (with/without deflection mirror)............... 46
Figure 5.7:"High Density" reading field curve for oscillating-mirror scanners......................................... 47
Figure 5.8:Lateral "High Density" reading field curve for oscillating-mirror scanners ............................. 47
Figure 5.9:"Medium Density" reading field curve for line scanner (with/without deflection mirror) ......... 48
Figure 5.10:"Medium Density" reading field curve for oscillating-mirror scanners ................................... 49
Figure 5.11:Lateral "Medium Density" reading field curve for oscillating-mirror scanners........................ 49
Figure 5.12:"Low Density" reading field curve for line scanner (with/without deflection mirror) ............... 50
Figure 5.13:"Low Density" reading field curve for oscillating-mirror scanners ......................................... 51
Figure 5.14:Lateral "Low Density" reading field curve for oscillating-mirror scanners.............................. 51
Figure 5.15:"Ultra Low Density" reading field curve for line scanner without deflection mirror................. 52
Figure 5.16:"Ultra Low Density" reading field curve for oscillating-mirror scanners ................................. 53
Figure 5.17:Lateral "Ultra Low Density" reading field curve for oscillating-mirror scanners...................... 53
Figure 5.18:"High Density" reading field curve for line scanner with heating (without deflection mirror) .. 54
Figure 5.19:"High Density" reading field curve for line scanner with heating (with deflection mirror) ....... 55
Figure 5.20:"High Density" reading field curve for oscillating-mirror scanners with heating..................... 56
Figure 5.21:Lateral "High Density" reading field curve for oscillating-mirror scanners with heating ......... 56
Figure 5.22:"Medium Density" reading field curve for line scanner with heating (without deflection mirror) ... 57
Figure 5.23:"Medium Density" reading field curve for line scanner with heating (with deflection mirror).. 58
Figure 5.24:"Medium Density" reading field curve for oscillating-mirror scanners with heating ............... 59
Figure 5.25:Lateral "Medium Density" reading field curve for oscillating-mirror scanners with heating.... 59
Figure 5.26:"Low Density" reading field curve for line scanner with heating (without deflection mirror)... 60
6BCL 558iLeuze electronic
Page 10
Figures and tables
Figure 5.27:"Low Density" reading field curve for line scanner with heating (with deflection mirror) ........61
Figure 5.28:"Low Density" reading field curve for oscillating-mirror scanners with heating...................... 62
Figure 5.29:Lateral "Low Density" reading field curve for oscillating-mirror scanners with heating.......... 62
Figure 5.30:"Ultra Low Density" reading field curve for line scanner with heating (without deflection mirror). 63
Figure 5.31:"Ultra Low Density" reading field curve for oscillating-mirror scanners with heating .............64
Figure 5.32:Lateral "Ultra Low Density" reading field curve for oscillating-mirror scanners with heating.. 64
Figure 6.1:Device name plate BCL 558i ................................................................................................. 65
Figure 6.2:Fastening options using M 4x6 threaded holes....................................................................... 66
The symbols used in this technical description are explained below.
Attention!
This symbol precedes text messages which must strictly be observed. Failure to comply with
this information results in injuries to personnel or damage to the equipment.
Attention Laser!
This symbol warns of possible danger caused by hazardous laser radiation.
Notice!
This symbol indicates text passages containing important information.
1.2Declaration of conformity
The bar code readers of the BCL 500i series have been developed and manufactured in
accordance with the applicable European standards and directives.
The BCL 500i series is "UL LISTED" according to American and Canadian safety standards,
and fulfills the requirements of Underwriter Laboratories Inc. (UL).
Notice!
You can find the Declaration of Conformity of the devices in the appendix of the manual on
page 182.
The manufacturer of the product, Leuze electronic GmbH & Co. KG in D-73277 Owen,
possesses a certified quality assurance system in accordance with ISO 9001.
Leuze electronicBCL 558i9
TNT 35/7-24V
Page 13
2Safety notices
2.1General safety notices
Documentation
All entries in this technical description must be heeded, in particular the present chapter
"Safety notices". Keep this technical description in a safe place. It should be available at all
times.
Safety regulations
Observe the locally applicable regulations and the rules of the employer's liability insurance
association.
Repair
Repairs must only be carried out by the manufacturer or an authorized representative.
2.2Safety standards
The bar code readers of the BCL 500i series were developed, manufactured and tested in
accordance with the applicable safety standards. They correspond to the state of the art.
2.3Approved purpose
Attention!
The protection of personnel and the device cannot be guaranteed if the device is operated
in a manner not complying with its intended use.
Bar code readers of the BCL 500i series are conceived as stationary, high-speed scanners
with integrated decoders for all current bar codes used for automatic object detection.
In particular, unauthorized uses include:
• In rooms with explosive atmospheres
• Operation for medical purposes
Areas of application
The bar code readers of the BCL 500i series are especially designed for the following areas
of application:
• Storage and conveying technologies, in particular for object identification on fastmoving conveyor belts
• Pallet transportation applications
• Automobile sector
• Omnidirectional reading
10BCL 558iLeuze electronic
Page 14
2.4Working safely
Attention!
Access to or changes on the device, except where expressly described in this operating
manual, are not authorized.
Safety regulations
Observe the locally applicable legal regulations and the rules of the employer's liability
insurance association.
Qualified personnel
Mounting, commissioning and maintenance of the device must only be carried out by
qualified personnel.
Electrical work must be carried out by a certified electrician.
Attention, laser radiation!
If you look into the beam path over a longer time period, the retina of your eye may
be damaged!
Never look directly into the beam path!
Do not point the laser beam of the BCL 558i at persons!
When mounting and aligning the BCL 558i, avoid reflections of the laser beam off
reflective surfaces!
The BCL 558i bar code readers comply with safety standards EN 60825-1 for a class
2 product. They also comply with the U.S. 21 CFR 1040.10 regulations for a class II
laser product except for deviations pursuant to Laser Notice No. 50, dated July 26,
2001.
Radiant Energy: The BCL 558i uses a low power visible laser diode. The emitted wavelength is 655nm. The average laser power is less than 1mW in accordance with the
definition of class 2 lasers.
Adjustments: Do not attempt any adjustments to or alterations of this product.
Do not remove the protective housing of the bar code reader. There are no userserviceable parts inside.
The scanner window is the only aperture through which light may be observed on this
product. A failure of the scanner motor, while the laser diode continues to emit a laser
beam, may cause emission levels to exceed those for safe operation. The bar code
reader has safeguards to prevent this occurrence. If, however, a stationary beam is
emitted, the failing bar code reader should be disconnected from its power source
immediately.
TNT 35/7-24V
CAUTION: Use of controls or adjustments or performance of procedures other than
specified herein may result in hazardous light exposure.
Leuze electronicBCL 558i11
Page 15
The use of optical instruments or devices in combination with the device increases
The housing of the BCL 558i is provided with warning notices B and C above and next
to the reading window as shown in the following figure:
Figure 2.1:Attachment of the stick-on labels with warning notices at the BCL 558i
Notice!
It is important that you attach the stick-on labels supplied to the device (A in figure 2.1)! If
the signs would be covered due to the installation situation of the BCL 558i, attach them
instead in the immediate vicinity of the BCL 558i in such a way that it is not necessary to
look into the laser beam when reading the notices.
12BCL 558iLeuze electronic
Page 16
3Fast commissioning / operating principle
Below you will find a short description for the initial commissioning of the BCL 558i. Detailed
explanations for all listed points can be found throughout this technical description.
3.1Mounting the BCL 558i
The BCL 558i bar code readers can be mounted in 3 different ways:
• Using two M4x6 screws on the rear of the device or using four M4x6 screws on the
bottom of the device.
• Using a BT 56 mounting device on the two fastening grooves.
3.2Device arrangement and selection of the mounting location
In order to select the right mounting location, several factors must be considered:
• Size, orientation, and position tolerance of the bar codes on the objects to be
scanned.
• The reading field of the BCL 558i in relation to the bar code module width.
• The resulting minimum and maximum reading distance from the respective reading
field (see chapter 5.5 "Reading field curves / optical data").
• The permissible cable lengths between the BCL 558i and the host system depending
on which interface is used.
• The correct time for data output. The BCL 558i should be positioned in such a way
that, taking into consideration the time required for data processing and the conveyor
belt speed, there is sufficient time to e.g. initiate sorting operations on the basis of the
read data.
• The display and control panel should be very visible and accessible.
• For configuring and commissioning with the webConfig tool, the USB interface should
be easily accessible.
For specific information, please refer to chapter 4.4.
Notice!
The beam exits the BCL 558i as follows for the respective devices:
- line scanner parallel to the housing base
- oscillating mirror and deflection mirror perpendicular to the housing base
The black areas in figure 6.1 are the housing base. The best read results are obtained when:
• The BCL 558i is mounted in such a way that the scanning beam is incident on the bar
code at an angle of inclination greater than ±10° … 15° to vertical.
• The reading distance lies in the middle area of the reading field.
• The bar code labels are of good print quality and have good contrast ratios.
• You do not use high-gloss labels.
• There is no direct sunlight.
Leuze electronicBCL 558i13
TNT 35/7-24V
Page 17
3.3Electrical connection BCL 558i
SW IN/OUT
VOUT
1
2
3
4
SWIO_1
SWIO_2
GND
FE
5
HOST / BUS IN
TD+
1
2
3
4
RD+
RD-
TD-
SERVICE
2134
GND D+ D-
U
B
PWR
SWIO_4
SWIO_3
3
2
1
4
5
GNDVIN
FE
BUS OUT
TD+
1
2
3
4
RD+
RD-
TD-
USB socket
Type A
M12 socket
(A-coded)
M12 socket
(D-coded)
M12 socket
(D-coded)
M12 plug
(A-coded)
The BCL 558i is equipped with four M 12 plugs/sockets which are A- and D-coded, and an
USB socket of Type A.
Figure 3.1:Connections of the BCL 558i
Voltage supply and switching inputs/outputs
The voltage supply (10 … 30 VDC) is connected at the PWR M12 connector.
Available at both the PWR M12 connector as well as at the SW IN/OUT M12 socket are
four freely programmable switching inputs/outputs for custom adaptation to the respective application. Detailed information on this topic can be found in chapter 7.2.
Standalone operation in Ethernet network
During stand-alone operation of the BCL 558i, the host interface of the superior system is
connected to HOST/BUS IN. Thus, a star structure (Ethernet structure) is possible. Please
be certain to select the correct protocol for the connected components.
Network operation in Ethernet network
In network operation, the superior system (PC/PLC) is connected to the host interface of
the BCL 558i. With the aid of the "switch" integrated in the BCL 558i, the bus connection
to the next participant, e.g. another BCL 558i, can occur directly via the BUS OUT socket!
Notice!
The BCL 558i does not have its own built-in DHCP server. Please make certain that each
participant in the Ethernet has its own unique IP address. This can be set by a DHCP server
in the primary system or through manual address assignment.
14BCL 558iLeuze electronic
Page 18
3.4Starting the device
Connect the supply voltage +10 … 30VDC (typ. +24 VDC); the BCL 558i starts up and
the bar code reading window appears on the display:
As a first step, you need to set the communication parameters of the BCL 558i.
You can make the necessary settings via the display or via the webConfig tool. Provided
here is only a brief description of the settings via the webConfig tool; detailed information
can be found in chapter 10.
ENIP
3.4.1BCL 558i on EtherNet/IP
Commissioning on the EtherNet/IP is performed according to the following scheme:
1.Address assignment
• automatic via DHCP, BootP or
• manual via webConfig (with a USB connection)
2.Configuration of the participant depending on the version of the control software:
• either with the generic Ethernet module or
• installation of the EDS file
3.Transferring the data to the control
4.Adapting the device parameters via webConfig
5.Use explicit messaging services
Notice!
On delivery, the automatic address assignment via DHCP server is defined as the standard
setting of the BCL 558i and the IP address is set to 0.0.0.0.
The BCL 558i can be configured in the planning tool/control using the EDS file (Electronic
Data Sheet) if the control supports this. PLC software RSLogix 5000 from Rockwell offers
EDS support for EtherNet/IP from software version 20.00 and up.
Without PLC support of the EDS integration, the settings are made via the generic Ethernetmodule. In this case, the respective configuration must be entered and adapted manually
for each device. The parameter download from the control to the BCL 558i is performed
during every establishment of connection. Since the parameters are stored centrally in the
control, this helps during device exchange.
By default, parameter enabling is deactivated and you
cannot change any settings. If you wish to carry out the
configuration via the display, you must activate parameter
enabling. Further information can be found in chapter
"Parameter enabling" on page 103.
TNT 35/7-24V
Leuze electronicBCL 558i15
Page 19
3.4.2Manually setting the IP address
If your system does not include a DHCP server or if the IP addresses of the devices are to
be set permanently, proceed as follows:
• Have the network administrator specify the data for IP address, net mask and gateway address of the BCL 558i.
• Set the IP address manually via the BootP/DHCP server tool and deactivate the
DHCP operation in the BCL 558i. The BCL 558i automatically adopts these settings.
A restart is not required.
Figure 3.2:Manually setting the IP address
Alternatively, you can set the IP address manually via the webConfig tool. Proceed as
follows:
• Have the network administrator specify the data for IP address, net mask and
gateway address of the BCL 558i.
• Connect the BCL 558i to your computer using the service cable.
• Set these values on the BCL 558i. Via webConfig:
Configuration -> Communication -> Ethernet interface.
Notice!
If the IP address is set via the webConfig tool, then it becomes active after transfer to the
device. A restart is not required.
16BCL 558iLeuze electronic
Page 20
3.4.3Configure the participant
Configuration with the generic Ethernet module
In the RSLogix 5000 configuration tool (up to software version 20.00), a so-called generic
Ethernet module is created under the Communication path for the BCL 558i.
Figure 3.3:Generic Ethernet module
The input mask for the generic module describes the following parameters to be set:
• The name of the participant (can be selected freely; e.g. BCL 558i)
• The format of I/O data (data - SINT = 8 bits)
• The IP address of the participant
• The address and length of the input assembly (instance 100, instance 101 or instance
102; min 1 byte - up to max. 266 bytes for the default input assembly of the read
results)
• The address and length of the output assembly (instance 120, instance 121 or
instance 122; min 1 byte - up to max. 263 bytes for the default output assembly)
• The address and length of the configuration assembly (instance 190; 3 bytes)
For the exact description of the assemblies for input/output and configuration, please refer
to chapter 10.
TNT 35/7-24V
Leuze electronicBCL 558i17
Page 21
Configuration of the participant using the EDS file
From software version 20.00 and up, proceed as follows in the RSLogix 5000 configuration
tool to create the BCL 558i as an EtherNet/IP participant in your system:
• First, load the EDS file for the device via EDS wizard into the PLC database.
Notice!
You can find the EDS file at: www.leuze.com.
• After it has downloaded, select the device from the device list.
• Open the input dialog for setting the address and additional parameters by
double-clicking on the device symbol and make the desired entries here.
• Finally, transmit the values to the control via download.
3.4.4Transferring the data to the control (RSLogix 5000 specific)
• Activate online mode
• Select the Ethernet communication port
• Select the processor onto which the project is to be transferred
• Set the control to PROG
• Start the download
• Set the control to RUN
3.5Further settings
After the basic configuration of the operating mode and the communication parameters, you
need to carry out further settings:
• Decoding and processing the read data
Define at least one code type with the desired settings.
• Via webConfig:
Configuration -> Decoder
• Control of the decoding
Configure the connected switching inputs according to your requirements. To do
this, first set the I/O mode to Input and then configure the switching behavior:
With the aid of the "Action menu", you can instruct the BCL 558i to read a bar code.
Actions
o Start decoding
o Start alignment
o Start auto-setup
o Start teach-in
To test, you can use the following bar code in the 2/5 Interleaved format. The bar code
module here is 0.5:
The read information appears in the display and is simultaneously passed on to the superior
system (PLC or PC).
Please check the incoming data of the bar code information there.
Alternatively, you can connect a photoelectric sensor or a 24 V DC switching signal to the
SW IN/OUT socket for read activation. To do this, however, you must appropriately
configure the switching input (see chapter 7.2.3 "SW IN/OUT – Switching input/switching
output").
In the main menu, use the buttons to select the
Actions menu item. Activate the Actions menu with .
Then select Start decoding with and press
again to start the bar code reading operation.
Leuze electronicBCL 558i19
TNT 35/7-24V
Page 23
4Device description
Line scanner
Oscillating-mirror scanner /
Line scanner with deflection mirror
4.1About the bar code readers of the BCL 500i series
Bar code readers of the BCL 500i series are high-speed scanners with integrated decoder
for all commonly used bar codes, e.g. 2/5 Interleaved, Code 39, Code 128, EAN 8/13 etc.,
as well as codes from the GS1 DataBar family.
Bar code readers of the BCL 500i series are available in various optics models as well as
line scanners, line scanners with deflection mirrors, oscillating mirrors and also optionally
as heated models.
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam
exit) is currently not available.
Figure 4.1:Line scanner, line scanner with deflection mirror and oscillating-mirror scanner
The extensive options for device configuration via display or software enable adaptation to
a multitude of reading tasks. Due to the large reading distance combined with the great
depth of field and a very compact construction, the device is ideally suited for package and
20BCL 558iLeuze electronic
pallet transportation systems. In general, the bar code readers of the BCL 500i series are
designed for the conveyor and storage technology market.
The interfaces (RS 232, RS 485 and RS 422) integrated in the various device models and
the fieldbus systems (PROFIBUS DP, PROFINET-IO, Ethernet TCP/IP / UDP and
EtherNet/IP) of the BCL 500i series bar code readers offer optimum connection to the superior host system.
Page 24
4.2Characteristics of the bar code readers of the BCL 500i series
Performance features:
• Integrated fieldbus connectivity = i -> Plug-and-Play fieldbus coupling and easy
networking
• Numerous interface variants facilitate connection to the superior systems
• RS 232, RS 422 as well as with integrated multiNet plus master
• RS 485 and multiNet plus slave
alternatively, various fieldbus systems, such as
•PROFIBUS DP
•PROFINET-IO
• Ethernet TCP/IP and UDP
• EtherNet/IP
• Integrated code fragment technology (CRT) enables the identification of soiled or damaged bar codes
• Maximum depth of field and reading distances from 200 mm to 2400mm
• Large optical opening angle and, thus, large reading field width
• High scanning rate from 800 - 1200 scans/s for fast reading tasks
• Intuitive, backlit, multi-language display with user-friendly menu navigation
•Integrated USB 1.1 service interface
• Adjustment of all device parameters with a web browser
• Connection options for an external parameter memory
• Easy alignment- and diagnosis functions
• M 12 connections with Ultra-Lock™ technology
• Four freely programmable switching inputs/outputs for the activation or signaling of
states
• Automatic monitoring of the read quality with autoControl
• Automatic recognition and setting of the bar code type using autoConfig
• Reference code comparison
• Optional heating models to -35°C
• Heavy-duty housing of protection class IP 65
Notice!
Information on technical data and characteristics can be found in chapter 5.
TNT 35/7-24V
General information
The integrated fieldbus connectivity = i contained in the bar code readers of the BCL 500i
series facilitates the use of identification systems which function without connector unit or
gateways. The integrated fieldbus interface considerably simplifies handling. The Plug-andPlay concept enables easy networking and very simple commissioning: Directly connect the
respective fieldbus and all configuration is performed with no additional software.
For decoding bar codes, the bar code readers of the BCL 500i series make available the
proven CRT decoder with code fragment technology:
Leuze electronicBCL 558i21
Page 25
The proven code fragment technology (CRT) enables bar code readers of the BCL 500i
series to read bar codes with a small bar height, as well as bar codes with a damaged or
soiled print image.
With the aid of the CRT decoder, bar codes can also be read without problem in other
demanding situations, such as with a large tilt angle (azimuth angle or even twist angle).
Figure 4.2:Possible bar code orientation
The BCL 558i can be operated and configured using the integrated webConfig tool via the
USB service interface; alternatively, the bar code readers can be adjusted using configuration commands via the host/service interface.
The BCL 558i needs a suitable activation to start a read process as soon as an object is in
the reading field. This opens a time window ("reading gate") in the BCL 558i for the read
process during which the bar code reader has time to detect and decode a bar code.
In the basic setting, triggering takes place through an external reading cycle signal.
Alternative activation options include online commands via the host interface and the
autoReflAct function.
Through the read operation, the BCL 558i collects additional useful pieces of data for diagnosis which can also be transmitted to the host. The quality of the read operation can be
inspected using the alignment mode which is integrated in the webConfig tool.
A multi-language display with buttons is used to operate the BCL 558i as well as for visualization purposes. Two LEDs provide additional optical information on the current operating
state of the device.
The four freely configurable switching inputs/outputs "SWIO 1 … SWIO 4" can be assigned
various functions and control e.g. activation of the BCL 558i or external devices, such as a
PLC.
System, warning and error messages provide assistance in setup/troubleshooting during
commissioning and read operation.
22BCL 558iLeuze electronic
Page 26
4.3Device construction
USB interface
M12 connection
technology
Reading window
Dovetail mounting and
4 mounting threads
Dovetail mounting and
2 mounting threads
Display, LEDs
and buttons
Figure 4.3:Device construction
Leuze electronicBCL 558i23
TNT 35/7-24V
Page 27
4.4Reading techniques
4.4.1Line scanner (single line)
A line (scan line) scans the label. Due to the opt. opening angle, the reading field width is
dependent on the read distance. Through the movement of the object, the entire bar code
is automatically transported through the scan line.
The integrated code fragment technology permits twisting of the bar code (tilt angle) within
certain limits. These are dependent on the transport speed, the scanning rate of the scanner
and the bar code properties.
Areas of application of the line scanner
The line scanner is used:
• when the bars of the bar code are printed in the conveying direction ('ladder arrangement').
• with bar codes having very short bar lengths.
• when the ladder code is turned out of the vertical position (tilt angle).
• when the scanning distance is large.
Figure 4.4:Deflection principle for the line scanner
24BCL 558iLeuze electronic
Page 28
4.4.2Line scanner with oscillating mirror
The oscillating mirror deflects the scan line additionally to both sides across the scan direction at a randomly adjustable oscillation frequency. In this way, the BCL 558i can also scan
larger areas or spaces for bar codes. The reading field height (and the scan line length useful
for evaluation) depends on the reading distance due to the optical beam width of the oscillating mirror.
Areas of application of the line scanner with oscillating mirror
For line scanners with oscillating mirror, oscillation frequency, start/stop position etc. are
adjustable. It is used:
• when the position of the label is not fixed, e.g. on pallets – various labels can, thus,
be detected at various positions.
• when the bars of the bar code are printed perpendicular to the conveying direction
('picket fence arrangement').
• when reading stationary objects.
• when the bar code is turned out of the horizontal position.
• when the scanning distance is large.
• when a large reading field (reading window) has to be covered.
Figure 4.5:Deflection principle for the line scanner with oscillating mirror add-on
Leuze electronicBCL 558i25
TNT 35/7-24V
Page 29
4.4.3Omnidirectional reading
In order to read arbitrarily oriented bar codes on an object, at least 2 bar code readers are
necessary. If the bar code is not printed over-square, i.e. bar length > code length, bar code
readers with integrated code fragment technology are necessary.
Figure 4.6:Principle arrangement for omnidirectional reading
26BCL 558iLeuze electronic
Page 30
4.5Fieldbus systems
Various product variants of the BCL 500i series are available for connecting to different
fieldbus systems such as PROFIBUS DP, PROFINET-IO, Ethernet and EtherNet/IP.
4.5.1EtherNet/IP
The BCL 558i is designed as an EtherNet/IP device (acc. to IEEE 802.3) with a standard
baud rate of 10/100 Mbit. EtherNet/IP makes use of the Common Industrial Protocol (CIP)
as an application layer for the user. The functionality of the device is defined via parameter
sets which are clustered in objects, classes and instances. These are contained in an EDS
file which, depending on the version of the control software, can be used to configure and
integrate the BCL 558i into the system. A fixed MAC ID is assigned to each BCL 558i by the
manufacturer; this ID cannot be changed.
The BCL 558i automatically supports the transmission rates of 10 Mbit/s (10Base T) and
100 Mbit/s (100Base TX), as well as auto-negotiation and auto-crossover.
The electrical connection of the supply voltage, the interface and the switching inputs/
outputs on the BCL 558i is performed via several M12 connectors.
Additional information on the electrical connection can be found in chapter 7.
The BCL 558i supports the following protocols and services:
• EtherNet/IP
•DHCP
•HTTP
•ARP
•PING
• Telnet
• BootP
Notice!
The BCL 558i communicates via the Common Industrial Protocol (CIP).
CIP Safety, CIP Sync and CIP Motion are not supported by the BCL 558i.
Further information on commissioning can be found in chapter 10.
Leuze electronicBCL 558i27
TNT 35/7-24V
Page 31
4.5.2Ethernet – star topology
PC / PLC host interface
Other network participants
BCL 558i
192.168.60.xxx
BCL 558i
192.168.60.yyy
The BCL 558i can be operated as a single device (stand-alone) in an Ethernet star topology
with individual IP address.
The address can either be manually set permanently via the BootP/webConfig tool or
assigned dynamically via a DHCP server.
Figure 4.7:Ethernet with star topology
Notice!
The BCL 558i does not support the DLR (Device Level Ring) ring structure determined by
the ODVA.
28BCL 558iLeuze electronic
Page 32
4.5.3Ethernet – linear topology
PC / PLC host interface
BCL 558i
192.168.60.xxx
to other network participants
BCL 558i
192.168.60.yyy
BCL 558i
192.168.60.zzz
The innovative further development of the BCL 558i with integrated switch functionality
offers the option of connecting multiple bar code readers of type BCL 558i to one another
without direct connection to a switch. In addition to the classic "star topology", a "linear
topology" is thus also possible.
Figure 4.8:Ethernet with linear topology
Each participant in this network requires its own unique IP address which is assigned to it
via the DHCP process. Alternatively, the address can be permanently assigned to it manually via BootP or webConfig tool.
The maximum length of a segment (connection from the hub to the last participant) is limited
to 100m.
Notice!
The BCL 558i does not support the DLR (Device Level Ring) ring structure determined by
the ODVA.
Leuze electronicBCL 558i29
TNT 35/7-24V
Page 33
4.6Heater
USB memory stick
For low-temperature applications to min. -35°C (e.g. in cold storage), the bar code readers
of the BCL 558i series can optionally be permanently fitted with a built-in heating and these
bar code readers purchased as separate device models.
4.7External parameter memory
The optionally available external parameter memory –
based on a USB memory stick (compatible with
version 1.1) – is housed in an external hood with
integrated connectors which cover the USB service
interface when installed (IP 65).
By having available a copy of the current parameter
set of the BCL 558i, the external parameter memory
makes it easy and reduces the time needed to replace
the BCL 558i on site. A manual configuration of the
exchanged device is thereby omitted.
The procedure for transferring the configuration with
the aid of the external parameter memory is described
on page 152.
The delivery contents of the external parameter memory include the hood with integrated
connectors with unscrewable cover and the USB memory stick.
Figure 4.9:External parameter memory
Notice!
To mount, the cover of the service interface must be unscrewed. Then take the USB memory
stick and plug it into the USB connection on the BCL 558i. Then, take the connector hood
of the USB memory stick and screw this over the plugged-in USB memory stick to the service
interface to close the system and ensure protection class IP 65.
30BCL 558iLeuze electronic
Page 34
4.8autoReflAct
AutoReflAct stands for Automatic Reflector Activation and permits an activation without
additional sensors. This is achieved by directing the scanner with reduced scanning beam
towards a reflector mounted behind the conveyor path. As long as the scanner is targeted
at the reflector, the reading gate remains closed. If, however, the reflector is blocked by an
object such as a container with a bar code label, the scanner activates the read procedure,
and the label on the container is read. When the path from the scanner to the reflector has
cleared, the read procedure has completed and the scanning beam is reduced and again
directed onto the reflector. The reading gate is closed.
Notice!
You will find a matching reflector in Accessories, and more are available on request.
Figure 4.10: Reflector arrangement for autoReflAct
The autoReflAct function uses the scanning beam to simulate a photoelectric sensor and
thus permits an activation without additional sensory mechanism.
Leuze electronicBCL 558i31
TNT 35/7-24V
Page 35
4.9Reference codes
The BCL 558i offers the possibility of storing one or two reference codes.
It is possible to store the reference codes by means of teach-in (display command), via the
webConfig tool or via online commands.
The BCL 558i can compare read bar codes with one and/or both reference codes and
execute user-configurable functions depending on the comparison result.
4.10autoConfig
With the autoConfig function, the BCL 558i offers the user who only wishes to simultaneously read one code type (symbology) with one number of digits an extremely simple and
convenient configuration option.
After starting the autoConfig function via the display, switching input or from a superior
control, it is sufficient to position a bar code label with the desired code type and number
of digits in the reading field of the BCL 558i.
Afterward, bar codes with the same code type and number of digits are recognized and
decoded.
32BCL 558iLeuze electronic
Page 36
5Specifications
5.1General specifications of the bar code readers
5.1.1Line scanner
TypeBCL 558i
EtherNet/IP
TypeLine scanner without heating
Optical data
Light sourceLaser diode = 650 nm / 655nm (red light)
Beam exitFront
Scanning rate1000 scans/s (adjustable in the range 800 … 1200 scans/s)
Beam deflectionby means of rotating polygon wheel
Useful opening angleMax. 60 °
Optics models / resolutionHigh Density (N): 0.25 … 0.5mm
Medium Density (M): 0.35 … 0.8mm
Low Density (F): 0.5 … 1.0mm
Ultra Low Density (L): 0.7 … 1.0mm
Read distanceSee reading field curves
Laser safety class2 acc. to EN 60825-1,
Switching inputs/outputs are protected against polarity reversal!
Operating voltage10 … 30VDC (Class II, Safety Class III)
Power consumptionMax. 10W
Operating and display elements
DisplayMonochromatic graphical display, 128 x 64 pixel, with background
lighting
Keyboard4 buttons
LEDs2 LEDs for power (PWR) and bus state (NET), two-colored (red/green)
Mechanical data
Protection classIP 65 (with screwed-on M12 connectors or mounted caps)
Weight1.1kg
Dimensions (WxHxD)63 x 123.5 x106.5 mm
HousingDiecast aluminum
Environmental data
Operating temperature range 0 °C … +40°C
Storage temperature range-20°C … +70°C
Air humidityMax. 90% rel. humidity, non-condensing
VibrationIEC 60068-2-6, test FC
ShockIEC 60068-2-27, test Ea
Continuous shockIEC 60068-2-29, test Eb
Electromagnetic compatibility EN 55022;
IEC 61000-6-2 (contains IEC 61000-4-2, -3, -4, -5 and -6)
1)
Table 5.1:Specifications of the BCL 558i line scanners without heating
1) This is a Class A product. In a domestic environment this product may cause radio interference, in
which case the operator may be required to take adequate measures.
34BCL 558iLeuze electronic
Page 38
Attention!
For UL applications, use is permitted exclusively in Class 2 circuits according to NEC
(National Electric Code).
The BCL 558i bar code readers are designed in accordance with safety class III for supply
by PELV (protective extra-low voltage with reliable disconnection).
5.1.2Oscillating-mirror scanner
Specifications are the same as for line scanner without heating with the following differences:
TypeBCL 558i
EtherNet/IP
TypeOscillating-mirror scanner without heating
Optical data
Beam exitLateral zero position at an angle of 90°
Beam deflectionVia rotating polygon wheel (horizontal) and stepping motor with mirror
(vertical)
Oscillation frequency0 … 10Hz
(adjustable, max. frequency is dependent on set swivel angle)
Max. swivel angle±20°(adjustable)
Reading field heightSee reading field curves
Electrical data
Power consumptionMax. 14 W
Mechanical data
Weight1.5kg
Dimensions (Wx HxD)84 x173 x147mm
Table 5.2:Specifications of the BCL 558i oscillating-mirror scanners without heating
5.1.3Line scanner with deflection mirror
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam exit) is
currently not available.
Specifications are the same as for line scanner without heating with the following differences:
TNT 35/7-24V
Leuze electronicBCL 558i35
Page 39
TypeBCL 558i
EtherNet/IP
TypeLine scanner with deflection mirror without heating
Optical data
Beam exitLateral zero position at an angle of 90°
Beam deflectionVia rotating polygon wheel (horizontal) and deflection mirror (vertical)
Max. optical adjustment
range of the beam exit
Electrical data
Power consumptionMax. 11W
Mechanical data
Weight1.4kg
Dimensions (WxHxD)84 x173 x147 mm
Table 5.3:Specifications of the BCL 558i deflection mirror scanners without heating
±10° (adjustable via display or software)
5.2Heating models of the bar code readers
The BCL 558i bar code readers are optionally available as models with integrated heating.
In this case, heating is permanently installed ex works. Self-installation on-site by the user
is not possible!
Features
• Integrated heating (permanently installed)
• Extends the application range of the BCL 558i to -35 °C
• Supply voltage 24VDC ±20 %
• BCL 558i enabling through an internal temperature switch
(switch-on delay about 30 min for 24V DC and minimum ambient temperature of -35 °C)
• Necessary conductor cross-section for the voltage supply: at least 0.75mm²; the use
of ready-made cables is, thus, not possible.
Construction
The heating consists of two parts:
• The front cover heater
• The housing heater
Function
When the 24V DC supply voltage is applied to the BCL 558i, a temperature switch initially
only connects the heating to electrical power (front cover heater and housing heater). During
the heating phase (around 30min), when the inside temperature rises above 15°C, the
temperature switch connects the BCL 558i to the supply voltage. This is followed by the
self test and the changeover to read operation. The "PWR" LED lights up showing overall
readiness for operation.
36BCL 558iLeuze electronic
Page 40
When the inside temperature reaches approximately 18 °C, another temperature switch
turns the housing heater off and, if necessary, back on again (if the inside temperature drops
below 15°C). This does not interrupt the read operation. The front cover heater remains activated until an inside temperature of 25°C is reached. At temperatures above this, the front
cover heater switches off and, with a switching hysteresis of 3°C, back on again at an inside
temperature below 22 °C.
Electrical connection
The required core cross-section of the connection cable for the voltage supply must be at
least 0.75 mm².
Attention!
The voltage supply must not be looped through from one device to the next.
Power consumption
The energy requirement depends on the model:
• the line scanner with heating typically consumes 40 W and a maximum of 50W power.
• the line scanner with oscillating mirror and heating typically consumes 60W and a
maximum of 75W.
These values are based on operation with unconnected switching outputs.
5.2.1Line scanner with heating
Specifications are the same as for line scanner without heating with the following
differences:
TypeBCL 558i
TypeLine scanner with heating
Electrical data
Operating voltage24V DC ±20%
Power consumptionMax. 50 W
Structure of the heatingHousing heating and separate heating of the optics glass
Warmup timeMin. 30min at +24 VDC and an ambient temperature of -35°C
Min. conductor
cross-section
Environmental data
Operating temperature range -35°C … +40 °C
Storage temperature range -20°C … +70 °C
Table 5.4:Specifications of the BCL 558i line scanners with heating
Leuze electronicBCL 558i37
Conductor cross-section of at least 0.75mm² for the supply-voltage
supply line.
Wiring through of the voltage supply to multiple heating devices is not
permissible.
Standard, M12 ready-made cable not usable
(insufficient cable cross-section)
EtherNet/IP
TNT 35/7-24V
Page 41
5.2.2Oscillating-mirror scanner with heating
Specifications are the same as for line scanner without heating with the following differences:
Operating voltage24 VDC ±20%
Power consumptionMax. 75W
Structure of the heatingHousing heating and separate heating of the optics glass
Warmup timeMin. 30min at +24VDC and an ambient temperature of -35°C
Min. conductor
cross-section
Environmental data
Operating temperature range -35°C … +40°C
Storage temperature range -20 °C … +70°C
Table 5.5:Specifications of the BCL 558i oscillating-mirror scanners with heating
Conductor cross-section of at least 0.75mm² for the supply-voltage
supply line.
Wiring through of the voltage supply to multiple heating devices is not
permissible.
Standard, M12 ready-made cable not usable
(insufficient cable cross-section)
38BCL 558iLeuze electronic
Page 42
5.2.3Line scanner with deflection mirror and heating
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam exit) and
heating is currently not available.
Specifications are the same as for line scanner without heating with the following differences:
TypeBCL 558i
TypeDeflection mirror scanner with heating
Optical data
Useful opening angleMax. 50 °
Max. adjustment range±10°(adjustable via display or software)
Electrical data
Operating voltage24V DC ±20%
Power consumptionMax. 75 W
Structure of the heatingHousing heating and separate heating of the optics glass
Warmup timeMin. 30min at +24 VDC and an ambient temperature of -35°C
Min. conductor
cross-section
Environmental data
Operating temperature range -35°C … +40 °C
Storage temperature range -20°C … +70 °C
Table 5.6:Specifications of the BCL 558i deflection mirror scanners with heating
Conductor cross-section of at least 0.75mm² for the supply-voltage
supply line.
Wiring through of the voltage supply to multiple heating devices is not
permissible.
Standard, M12 ready-made cable not usable
(insufficient cable cross-section)
EtherNet/IP
TNT 35/7-24V
Leuze electronicBCL 558i39
Page 43
5.3Dimensioned drawings
deepdeep
deep
A – Optical axis
5.3.1Line scanner with / without heating
Figure 5.1:Dimensioned drawing BCL 558i line scanner S…102
40BCL 558iLeuze electronic
Page 44
5.3.2Deflection mirror scanner with / without heating
deep
deep
A – Optical axis
B – Optical adjustment range
C – Opening angle
The opening angle is reduced on devices with heating, see "Reading field curves for heating devices"
on page 54.
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam exit) is
BCL 558i SN 102Line scanner, beam exit at the front50122787
BCL 558i ON 100Oscillating-mirror scanner50122776
BCL 558i SN 102 HLine scanner, beam exit at the front, with heating50122788
BCL 558i ON 100 HOscillating-mirror scanner with heating50122780
Medium Density Optics (m = 0.35 … 1.0mm)
BCL 558i SM 102Line scanner, beam exit at the front50122785
BCL 558i OM 100Oscillating-mirror scanner50122773
BCL 558i SM 102 HLine scanner, beam exit at the front, with heating50122786
BCL 558i OM 100 HOscillating-mirror scanner with heating50122775
Low Density Optics (m = 0.5 … 1.0mm)
BCL 558i SF 102Line scanner, beam exit at the front50122781
BCL 558i OF 100Oscillating-mirror scanner50122769
BCL 558i SF 102 HLine scanner, beam exit at the front, with heating50122782
BCL 558i OF 100 HOscillating-mirror scanner with heating50122770
Ultra Low Density Optics (m = 0.7 … 1.0mm)
BCL 558i SL 102Line scanner, beam exit at the front50122783
BCL 558i OL 100Oscillating-mirror scanner50122771
BCL 558i SL 102 HLine scanner, beam exit at the front, with heating50122784
BCL 558i OL 100 HOscillating-mirror scanner with heating50122772
Table 5.7:Type overview BCL 558i
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam
exit) is currently not available.
Leuze electronicBCL 558i43
TNT 35/7-24V
Page 47
5.5Reading field curves / optical data
M = Module: The narrowest line or space of a bar code in mm
Z
B
= Wide element: Wide lines and spaces are a multiple (ratio) of the
module.
Module x Ratio = Z
B
(Normal Ratio 1 : 2.5)
B
Z
= Quiet zone: The quiet zone should be at least 10 times the
module, but not less than 2.5mm.
L= Code length: The length of the bar code in mm including the start
and stop characters. The quiet zone is included depending on the
code definition.
S
L
= Bar length: Height of the elements in mm
Bar code characteristics
Notice!
Please note that the size of the bar code module influences the maximum reading distance
and the width of the reading field. Therefore, when selecting a mounting location and/or the
bar code label, take into account the different reading characteristics of the scanner with
various bar code modules.
Figure 5.4:The most important characteristics of a bar code
The range in which the bar code can be read by the BCL 558i (the so-called reading field)
depends on the quality of the printed bar code and its dimensions.
Therefore, above all, the module of a bar code is decisive for the size of the reading field.
Notice!
A rule of thumb: The smaller the module of the bar code is, the smaller the maximum reading
distance and reading field width will be.
44BCL 558iLeuze electronic
Page 48
5.6Reading field curves
Zero position
Distance acc. to reading field curves
Notice!
Please notice that the real reading fields are also influenced by factors such as labeling
material, printing quality, scanning angle, printing contrast etc., and may thus deviate from
the reading fields specified here.
The zero position of the reading distance always refers the front edge of the housing of the
beam exit and is shown in figure 5.5 for the two housing types of the BCL 558i.
Figure 5.5:Zero position of the reading distance
Reading conditions for the reading field curves
Bar code type2/5 Interleaved
Ratio1:2,5
Leuze electronicBCL 558i45
ANSI specificationclass A
Reading rate> 75%
Table 5.8:Reading conditions
TNT 35/7-24V
Page 49
5.6.1High Density (N) Optics: BCL 558i SN 100/102
Read distance [mm]
Reading field width [mm]
400
300
200
100
-100
-200
-300
-400
0-1002001003004005006007008009001000
BCL 5xxi SN 100/102
m = 0,25
m = 0,3
m = 0,35
m = 0,25
m = 0,3
m = 0,35
m = 0,5
m = 0,5
Figure 5.6:"High Density" reading field curve for line scanner (with/without deflection mirror)
The reading field curve applies for the reading conditions stated in table 5.8.
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam
exit) is currently not available.
46BCL 558iLeuze electronic
Page 50
5.6.2High Density (N) Optics: BCL 558i ON 100
0-1001002003004005006007008009001000
100
200
300
400
-100
-200
-300
-400
BCL 5xxi ON 100
m = 0,25
m = 0,3
m = 0,35
m = 0,5
m = 0,35
m = 0,3
m = 0,25
m = 0,5
Read distance [mm]
Reading field width [mm]
Read distance [mm]
Reading field height [mm]
Figure 5.7:"High Density" reading field curve for oscillating-mirror scanners
400
300
200
100
-100
-200
-300
-400
-100
0100
2003004005006007008009001000
BCL 5xxi ON 100
m = 0,25
m = 0,3
m = 0,35
m = 0,25
m = 0,3
m = 0,35
m = 0,5
m = 0,5
Figure 5.8:Lateral "High Density" reading field curve for oscillating-mirror scanners
The reading field curves apply for the reading conditions stated in table 5.8.
Leuze electronicBCL 558i47
TNT 35/7-24V
Page 51
5.6.3Medium Density (M) Optics: BCL 558i SM 100/102
Read distance [mm]
Reading field width [mm]
BCL 5xxi SM 100/102
m = 0,35
m = 0,5
m = 0,8 … 1,0
m = 0,35
m = 0,5
m = 0,8
…
m = 1,0
-100
-200
-300
-400
400
300
200
100
100200-100030040050060070080090010001100
Figure 5.9:"Medium Density" reading field curve for line scanner (with/without deflection mirror)
The reading field curves apply for the reading conditions stated in table 5.8.
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam
exit) is currently not available.
48BCL 558iLeuze electronic
Page 52
5.6.4Medium Density (M) Optics: BCL 558i OM 100
0-10010020030040050060070080090010001100
100
200
300
400
-100
-200
-300
-400
BCL 5xxi OM 100
m = 0,35
m = 0,5
m = 0,8
…
m = 1,0
m = 0,5
m = 0,35
m = 0,8 … 1,0
Read distance [mm]
Reading field width [mm]
0100
-100
20030040050060070080090011001000
100
200
300
400
-100
-200
-300
-400
BCL 5xxi OM 100
m = 0,35
m = 0,5
m = 0,8
…
m = 1,0
m = 0,5
m = 0,35
m = 0,8 … 1,0
Read distance [mm]
Reading field height [mm]
Figure 5.10: "Medium Density" reading field curve for oscillating-mirror scanners
Figure 5.11: Lateral "Medium Density" reading field curve for oscillating-mirror scanners
The reading field curves apply for the reading conditions stated in table 5.8.
Figure 5.16: "Ultra Low Density" reading field curve for oscillating-mirror scanners
m = 0,7
m = 0,8
m = 1,0
m = 1,0
Figure 5.17: Lateral "Ultra Low Density" reading field curve for oscillating-mirror scanners
The reading field curves apply for the reading conditions stated in table 5.8.
Leuze electronicBCL 558i53
TNT 35/7-24V
Page 57
5.7Reading field curves for heating devices
100200-10003004005006007008009001000
100
200
300
400
-100
-200
-300
-400
BCL 5xxi SN 102 H
m = 0,25
m = 0,3
m = 0,35
m = 0,5
m = 0,35
m = 0,3
m = 0,25
m = 0,5
Read distance [mm]
Reading field width [mm]
The reading field curves of the heating devices differ to some extent from the normal reading
curves due to the optics heating and are somewhat reduced in the reading field width as
well as in the reading field height!
• The maximum opening angle for all oscillating and deflection mirror devices
(BCL 558i…100 H) is reduced to ±28° (without heating = ±30°).
• In addition, the maximum swivel range for all oscillating mirror devices
(BCL 558i O…100 H) is reduced to ±12° (without heating = ±20°). The deflection
mirror models (BCL 558i S…100 H) are not affected by this limitation.
• The reading field curves and opening angles are unchanged for all line scanners with
heating (BCL 558i S…102 H).
For details, please refer to the following reading field curves for the heating devices.
5.7.1High Density (N) Optics: BCL 558i SN 102 H
Figure 5.18: "High Density" reading field curve for line scanner with heating (without deflection mirror)
The reading field curve applies for the reading conditions stated in table 5.8.
54BCL 558iLeuze electronic
Page 58
5.7.2High Density (N) Optics: BCL 558i SN 100 H
100200-10003004005006007008009001000
100
200
300
400
-100
-200
-300
-400
BCL 5xxi SN 100 H
m = 0,25
m = 0,3
m = 0,35
m = 0,5
m = 0,35
m = 0,3
m = 0,25
m = 0,5
Read distance [mm]
Reading field width [mm]
Figure 5.19: "High Density" reading field curve for line scanner with heating (with deflection mirror)
The reading field curve applies for the reading conditions stated in table 5.8.
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam
exit) is currently not available.
Leuze electronicBCL 558i55
TNT 35/7-24V
Page 59
5.7.3High Density (N) Optics: BCL 558i ON 100 H
Read distance [mm]
Reading field width [mm]
0100
-100
2003004005006007008009001000
100
200
300
400
-100
-200
-300
-400
BCL 5xxi ON 100 H
m = 0,25
m = 0,3
m = 0,35
m = 0,5
m = 0,35
m = 0,3
m = 0,25
m = 0,5
= ±12˚
Read distance [mm]
Reading field height [mm]
BCL 5xxi ON 100 H
m = 0,3
m = 0,35
m = 0,25
m = 0,5
-100
-200
-300
-400
400
300
200
100
1000-1002003004005006007008009001000
Figure 5.20: "High Density" reading field curve for oscillating-mirror scanners with heating
m = 0,25
m = 0,3
m = 0,35
m = 0,5
Figure 5.21: Lateral "High Density" reading field curve for oscillating-mirror scanners with heating
56BCL 558iLeuze electronic
The reading field curves apply for the reading conditions stated in table 5.8.
Page 60
5.7.4Medium Density (M) Optics: BCL 558i SM 102 H
100200-100030040050060070080090010001100
100
200
300
400
-100
-200
-300
-400
BCL 5xxi SM 102 H
m = 0,35
m = 0,5
m = 0,8
…
m = 1,0
m = 0,5
m = 0,35
m = 0,8 … 1,0
Read distance [mm]
Reading field width [mm]
Figure 5.22: "Medium Density" reading field curve for line scanner with heating (without deflection mirror)
The reading field curves apply for the reading conditions stated in table 5.8.
Leuze electronicBCL 558i57
TNT 35/7-24V
Page 61
5.7.5Medium Density (M) Optics: BCL 558i SM 100 H
Read distance [mm]
Reading field width [mm]
BCL 5xxi SM 100 H
m = 0,35
m = 0,5
m = 0,8 … 1,0
m = 0,35
m = 0,5
m = 0,8
…
m = 1,0
-100
-200
-300
-400
400
300
200
100
100200-100030040050060070080090010001100
Figure 5.23: "Medium Density" reading field curve for line scanner with heating (with deflection mirror)
The reading field curves apply for the reading conditions stated in table 5.8.
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam
exit) is currently not available.
58BCL 558iLeuze electronic
Page 62
5.7.6Medium Density (M) Optics: BCL 558i OM 100 H
1000-10020030040050060070080090010001100
100
200
300
400
-100
-200
-300
-400
BCL 5xxi OM 100 H
m = 0,35
m = 0,5
m = 0,8
…
m = 1,0
m = 0,5
m = 0,35
m = 0,8 … 1,0
Read distance [mm]
Reading field width [mm]
0100
-100
20030040050060070080090011001000
100
200
300
400
-100
-200
-300
-400
BCL 5xxi OM 100 H
m = 0,35
m = 0,5
m = 0,8
…
m = 1,0
m = 0,5
m = 0,35
m = 0,8 … 1,0
= ±12˚
Read distance [mm]
Reading field height [mm]
Figure 5.24: "Medium Density" reading field curve for oscillating-mirror scanners with heating
Figure 5.25: Lateral "Medium Density" reading field curve for oscillating-mirror scanners with heating
The reading field curves apply for the reading conditions stated in table 5.8.
Figure 5.31: "Ultra Low Density" reading field curve for oscillating-mirror scanners with heating
Figure 5.32: Lateral "Ultra Low Density" reading field curve for oscillating-mirror scanners with heating
64BCL 558iLeuze electronic
The reading field curves apply for the reading conditions stated in table 5.8.
Page 68
6Installation and mounting
6.1Storage, transportation
Attention!
When transporting or storing, package the device s o that it is prot ected against collision and
humidity. Optimum protection is achieved when using the original packaging. Heed the
required environmental conditions specified in the technical data.
Unpacking
Check the packaging for any damage. If damage is found, notify the post office or shipping
agent as well as the supplier.
Check the delivery contents using your order and the delivery papers:
• Delivered quantity
• Device type and model as indicated on the nameplate
• Laser warning signs
• Brief manual
The name plate provides information as to what BCL type your device is. For specific information, please refer to chapter 5.
Name plates of the bar code readers of the BCL 500i series
Figure 6.1:Device name plate BCL 558i
Save the original packaging for later storage or shipping.
If you have any questions concerning your shipment, please contact your supplier or your
local Leuze electronic sales office.
Observe the applicable local regulations when disposing of the packaging materials.
Leuze electronicBCL 558i65
TNT 35/7-24V
Page 69
6.2Mounting the BCL 558i
The BCL 558i bar code readers can be mounted in two different ways:
• Using two M 4x6 screws on the rear of the device or using four M4x6 screws on the
bottom of the device.
• Using a BT 56 mounting device on the two fastening grooves.
6.2.1Fastening with M4 x 6 screws
Figure 6.2:Fastening options using M 4x6 threaded holes
66BCL 558iLeuze electronic
Page 70
6.2.2BT 56 mounting device
Clamping jaws for
mounting on the
BCL 558i
Clamp profile for
mounting to round or
oval pipes
Ø16…20mm
A Rod holder, turnable 360°
B Rods Ø 16 … 20mm
All dimensions in mm
The BT 56 mounting device is available for mounting the BCL 558i using the fastening
grooves. It is designed for rod installation (Ø 16mm to 20mm). For ordering instructions,
please refer to chapter "Type overview and accessories" on page 175.
BT 56 mounting device
Figure 6.3:BT 56 mounting device
Leuze electronicBCL 558i67
TNT 35/7-24V
Page 71
Figure 6.4:Mounting example of BCL 558i with BT 56
68BCL 558iLeuze electronic
Page 72
6.2.3BT 59 mounting device
Clamping jaws for mounting
on the BCL 558i
A Holder, turnable 360°
B ITEM joint, angle adjustable ±90°
C M 8x16 screw cylinder, M 8 wave washer, M 8
sliding block, connectors for ITEM profile (2x)
All dimensions in mm
The BT 59 mounting device offers you an additional fastening option. For ordering instructions, please refer to chapter "Type overview and accessories" on page 175.
BT 59 mounting device
Figure 6.5:BT 59 mounting device
Notice!
When mounting, ensure that the scanning beam is not reflected directly back to the scanner
by the label which is being read. For further information, see the notices in chapter 6.3!
Please refer to chapter 5.6 for the permissible minimum and maximum distances between
the BCL 558i and the labels to be read.
Leuze electronicBCL 558i69
TNT 35/7-24V
Page 73
6.3Device arrangement
6.3.1Selecting a mounting location
In order to select the right mounting location, several factors must be considered:
• Size, orientation, and position tolerance of the bar codes on the objects to be scanned.
• The reading field of the BCL 558i in relation to the bar code module width.
• The resulting minimum and maximum reading distance from the respective reading
field (see chapter 5.5 "Reading field curves / optical data").
• The permissible cable lengths between the BCL 558i and the host system depending
on which interface is used.
• The correct time for data output. The BCL 558i should be positioned in such a way
that, taking into consideration the time required for data processing and the conveyor
belt speed, there is sufficient time to e.g. initiate sorting operations on the basis of the
read data.
• The display and control panel should be very visible and accessible.
• For configuring and commissioning with the webConfig tool, the USB interface should
be easily accessible.
For specific information, please refer to chapter 4.4.
Notice!
The beam exits the BCL 558i as follows for the respective devices:
- line scanner parallel to the housing base
- oscillating mirror and deflection mirror perpendicular to the housing base
The black areas in figure 6.1 are the housing base. The best read results are obtained when:
• The BCL 558i is mounted in such a way that the scanning beam is incident on the bar
code at an angle of inclination greater than ±10° … 15° to vertical.
• The reading distance lies in the middle area of the reading field.
• The bar code labels are of good print quality and have good contrast ratios.
• You do not use high-gloss labels.
• There is no direct sunlight.
70BCL 558iLeuze electronic
Page 74
6.3.2Avoiding total reflection – Line scanner
Z
e
r
o
p
o
s
i
t
i
o
n
D
i
s
t
a
n
c
e
a
c
c
.
t
o
r
e
a
d
i
n
g
f
i
e
l
d
c
u
r
v
e
s
Bar code
The BCL 558i should be mounted in such a way that the
scanning beam is incident on the bar code at an angle of
inclination greater than ±10° … 15° to vertical.
±
1
0
…
1
5
°
The bar code label must be positioned at an angle of inclination greater than ±10° … 15°
from vertical in order to avoid total reflection of the laser beam (see figure 6.6)!
Total reflection occurs whenever the laser light of the bar code reader is directly incident
on the surface of the bar code at an angle of 90°. The light directly reflected by the bar code
may overload the bar code reader and thereby cause non-readings!
Figure 6.6:Total reflection – line scanner
6.3.3Avoiding total reflection – oscillating/deflection-mirror scanner
For the BCL 558i with oscillating/deflection mirror, the laser beam exits at an angle of 90°
to vertical.
For the BCL 558i with deflection mirror, it is also possible to use software to adjust the
direction of the beam by ±10°.
For the BCL 558i with oscillating mirror, the swivel range of ±20° (±12° for devices with
heating) is to be taken into account.
This means that in order to be on the safe side and to avoid total reflection, the BCL 558i
with oscillating/deflection mirror must be inclined upward or downward 20° … 30°!
Notice!
Mount the BCL 558i with oscillating/deflection mirror in such a way that the outlet window
of the bar code reader is parallel to the object. This will result in an angle of inclination of
approx. 25°.
TNT 35/7-24V
Leuze electronicBCL 558i71
Notice!
Please note: the BCL 558i line scanner with deflection mirror (perpendicular beam exit) is
currently not available.
Page 75
Figure 6.7:Total reflection – BCL 558i with oscillating/deflection mirror
Z
e
r
o
p
o
s
i
t
i
o
n
D
i
s
t
a
n
c
e
a
c
c
.
t
o
r
e
a
d
i
n
g
f
i
e
l
d
c
u
r
v
e
s
Bar code
±
2
5
°
The BCL 558i should be mounted in such a way that the scanning
beam is incident on the bar code at an angle of inclinatio n greater
than ±25° to vertical.
6.3.4Mounting location
When selecting a mounting location, pay attention to:
• Maintaining the required environmental conditions (temperature, humidity).
• Possible soiling of the reading window due to liquids, abrasion by boxes, or packaging
material residues.
• Lowest possible chance of damage to the BCL 558i by mechanical collision or jammed
parts.
• Possible extraneous light (no direct sunlight or sunlight reflected by the bar code).
6.3.5Devices with integrated heating
For devices with integrated heating, also observe the following points:
• Mount the BCL 558i in a way which provides maximum thermal isolation, e.g. using
rubber-bonded metal.
• Mount in such a way that the device is protected from draft and wind; mount additional
shields if necessary.
Notice!
When installing the BCL 558i in a protective housing, it must be ensured that the scanning
beam can exit the protective housing without obstruction.
72BCL 558iLeuze electronic
Page 76
6.3.6Possible read angles between BCL 558i and bar code
The optimum alignment of the BCL 558i is accomplished when the scan line scans the code
bars almost at a right angle (90°). All read angles that are possible between the scan line
and bar code must be taken account (figure 6.8).
Figure 6.8:Reading angle for the line scanner
Tilt
Angle of inclination (Pitch)
Skew
In order to avoid total reflection, the skew should be greater than 10°
6.4Attaching laser warning sign
Attention Laser!
Follow the safety notices in chapter 2.
It is important that you attach the sticky labels supplied to the device (laser warning signs
and laser emission symbol)! If the signs would be covered due to the installation situation
of the BCL 558i, attach them instead in the immediate vicinity of the BCL 558i in such a
way that it is not necessary to look into the laser beam when reading the notices!
6.5Cleaning
Clean the glass window of the BCL 558i with a soft cloth after mounting. Remove all p ack-
aging remains, e.g. carton fibers or Styrofoam balls. In doing so, avoid leaving fingerprints
on the front cover of the BCL 558i.
Attention!
Do not use aggressive cleaning agents such as thinner or acetone for cleaning the device.
Leuze electronicBCL 558i73
TNT 35/7-24V
Page 77
7Electrical connection
The bar code readers of the BCL 500i series are connected using variously coded M12
connectors. This ensures unique connection assignments.
The additional USB interface is used for configuring the device.
For the locations of the individual device connections, please refer to the device detail shown
below.
Notice!
The corresponding mating connectors and ready-made cables are available as accessories
for all connections. For additional information, refer to chapter chapter 13.
Figure 7.1:Location of the electrical connections
74BCL 558iLeuze electronic
Page 78
7.1Safety notices for the electrical connection
Attention!
Do not open the device yourself under any circumstances! There is otherwise a risk of
uncontrolled emission of laser radiation from the device. The housing of the BCL 558i contains no parts that need to be adjusted or maintained by the user.
Before connecting the device, be sure that the supply voltage agrees with the value printed
on the name plate.
Connection of the device and cleaning must only be carried out by a qualified electrician.
Ensure that the functional earth (FE) is connected correctly. Unimpaired operation is only
guaranteed when the functional earth is connected properly.
If faults cannot be corrected, the device should be removed from operation and protected
against possible use.
Attention!
For UL applications, use is permitted exclusively in Class 2 circuits according to NEC
(National Electric Code).
The bar code readers of the BCL 500i series are designed in accordance with safety class
III for supply by PELV (protective extra-low voltage with reliable disconnection).
Notice!
Protection class IP 65 is achieved only if the connectors and caps are screwed into place!
Leuze electronicBCL 558i75
TNT 35/7-24V
Page 79
7.2Electrical connection of the BCL 558i
SW IN/OUT
VOUT
1
2
3
4
SWIO_1
SWIO_2
GND
FE
5
HOST / BUS IN
TD+
1
2
3
4
RD+
RD-
TD-
SERVICE
2134
GND D+ D-
U
B
PWR
SWIO_4
SWIO_3
3
2
1
4
5
GNDVIN
FE
BUS OUT
TD+
1
2
3
4
RD+
RD-
TD-
USB socket
Type A
M12 socket
(A-coded)
M12 socket
(D-coded)
M12 socket
(D-coded)
M12 plug
(A-coded)
As a network participant, the BCL 558i is equipped with four M12 plugs / sockets which
are A- and D-coded.
The voltage supply (PWR) as well as the four freely configurable switching inputs/outputs
(SW IN/OUT and PWR) are connected there.
"HOST / BUS IN" is available as an Ethernet interface for connecting to the host system.
By means of the implemented switch function in the BCL 558i, an additional second
"BUS OUT" Ethernet interface is available for creating a scanner network (linear topology).
A USB connection serves as a "SERVICE" interface.
Figure 7.2:Connections of the BCL 558i
Described in detail in the following are the individual connections and pin assignments.
76BCL 558iLeuze electronic
Page 80
7.2.1PWR – Voltage supply and switching input/outputs 3 and 4
PWR
SWIO_4
SWIO_3
3
2
1
4
5
GNDVIN
FE
M12 plug
(A-coded)
PWR (5-pin plug, A-coded)
PinNameRemark
1VINPositive supply voltage +10 … +30VDC
2SWIO_3 Configurable switching input / output 3
3GNDNegative supply voltage 0V DC
4SWIO_4 Configurable switching input / output 4
5FEFunctional earth
ThreadFEFunctional earth (housing)
Table 7.1:Pin assignment PWR
Supply voltage
Attention!
For UL applications, use is permitted exclusively in Class 2 circuits according to NEC
(National Electric Code).
The bar code readers of the BCL 500i … series are designed in accordance with safety class
III for supply by PELV (protective extra-low voltage with reliable disconnection).
Connecting functional earth FE
Ensure that the functional earth (FE) is connected correctly. Unimpaired operation is only
guaranteed when the functional earth is connected properly. All electrical disturbances
(EMC couplings) are discharged via the functional earth connection.
Leuze electronicBCL 558i77
Switching input/output
The bar code readers of the BCL 500i series are equipped with four freely programmable,
opto-decoupled switching inputs and outputs SWIO_1 … SWIO_4.
The switching inputs can be used to activate various internal functions of the BCL 558i
(decoding, autoConfig, …). The switching outputs can be used to signal the state of the
BCL 558i and to implement external functions independent of the superior control.
The two switching inputs/outputs SWIO_1 and SWIO_2 are located on the SW IN/OUT M12
socket and are described in chapter 7.2.3. The other two (SWIO_3 and SWIO_4) of the four
freely configurable switching inputs/outputs are located on the PWR M12 connector.
TNT 35/7-24V
Page 81
Notice!
Switching input
Switching output
from controller
(deactivated)
Switching input
to controller
Switching output
Switching output
from controller
Switching input
to controller
(deactivated)
The respective function as input or output can be set via the display or with the aid of the
webConfig tool!
Described in the following is the external wiring for use as a switching input or output; the
respective function assignments to the switching inputs/outputs can be found in chapter 10.
Function as switching input
Figure 7.3:Switching input connection diagram SWIO_3 and SWIO_4
If you use a sensor with a standard M12 connector, please note the following:
• Pins 2 and 4 must not be operated as switching outputs if sensors which function as
inputs are also connected to these pins.
If, for example, the inverted sensor output is connected to pin 2, and pin 2 of the bar code
reader is, at the same time, configured as an output (and not as an input), the switching
output malfunctions.
Each configured switching output is short-circuit proof! Do not load the respective switching
output of the BCL 558i with more than 60mA at +10 … +30VDC in normal operation!
78BCL 558iLeuze electronic
Page 82
Notice!
SERVICE
2134
GND D+ D-
U
B
Both switching inputs/outputs SWIO_3 and SWIO_4 are configured by default in such a way
that:
• Switching input SWIO_3 activates the reading gate.
• Switching output SWIO_4 switches by default on "No Read".
7.2.2SERVICE – USB interface (type A)
SERVICE – USB interface (type A)
PinNameRemark
1VBPositive supply voltage +5V DC
2D-Data -
3D+Data +
4GNDGround
Table 7.2:Pin assignments of SERVICE – USB interface
Attention!
Maximum load of the +5 VDC supply voltage of the Service - USB interface is 200mA!
Ensure adequate shielding.
The entire connection cable must absolutely be shielded acc. to the USB specifications.
Cable length must not exceed 3m.
Use the Leuze specific USB service cable (see chapter 13 "Type overview and acces-
sories") for the connection and use a service PC to configure.
Notice!
IP 65 is achieved only if the connectors and caps are screwed into place. Alternatively, a
parameter memory in the form of a USB memory stick certified by
Leuze electronic GmbH + Co. can be connected to the provided USB service interface. With
this Leuze memory stick, protection class IP 65 is also ensured. For further information,
please refer to chapter 4.7 and chapter 10.10.2 of this documentation!
Leuze electronicBCL 558i79
TNT 35/7-24V
Page 83
7.2.3SW IN/OUT – Switching input/switching output
SW IN/OUT
VOUT
1
2
3
4
SWIO_1
SWIO_2
GND
FE
5
M12 socket
(A-coded)
Diffuse reflection light scanner
Switching output
from controller
(deactivated)
Switching input
to controller
Output
SW IN/OUT (5-pin socket, A-coded)
PinNameRemark
1VOUT
Voltage supply for sensors
(VOUT identical to VIN at PWR IN)
2SWIO_1 Configurable switching input / output 1
3GNDGND for the sensors
4SWIO_2 Configurable switching input / output 2
5FEFunctional earth
ThreadFEFunctional earth (housing)
Table 7.3:Pin assignment SW IN/OUT
The bar code readers of the BCL 500i series are equipped with four freely programmable,
opto-decoupled switching inputs and outputs SWIO_1 … SWIO_4.
The two switching inputs/outputs SWIO_1 and SWIO_2 are located on the SW IN/OUT M12
socket. The other two (SWIO_3 and SWIO_4) of the four freely configurable switching inputs/
outputs are located on the PWR M12 connector and are described in chapter 7.2.1.
Described in the following is the external wiring for use as a switching input or output; the
respective function assignments to the switching inputs/outputs can be found in chapter 10.
Function as switching input
Figure 7.5:Switching input connection diagram SWIO_1 and SWIO_2
If you use a sensor with a standard M12 connector, please note the following:
• Pins 2 and 4 must not be operated as switching outputs if sensors which function as
inputs are also connected to these pins.
If, for example, the inverted sensor output is connected to pin 2, and pin 2 of the bar code
reader is, at the same time, configured as an output (and not as an input), the switching
output malfunctions.
Each configured switching output is short-circuit proof! Do not load the respective switching
output of the BCL 558i with more than 60mA at +10 … +30VDC in normal operation!
Notice!
Both switching inputs/outputs SWIO_1 and SWIO_2 are configured by default in such a way
that they function as switching inputs:
• Switching input SWIO_1 activates the start reading gate function
• Switching input SWIO_2 activates the reference code teach-in function
The functions of the individual switching inputs/outputs are programmed via the display or
via configuration in the webConfig tool under the Switching input or Switching output
heading.
For further information, see also "Commissioning and configuration" on page 110.
Leuze electronicBCL 558i81
TNT 35/7-24V
Page 85
7.2.4HOST / BUS IN for BCL 558i
M12 socket
(D-coded)
45
+
(3)
)
Twisted pair
Twisted pair
The BCL 558i makes either the Ethernet interface available as host interface.
HOST / BUS IN (4-pin socket, D-coded)
HOST / BUS IN
RD+
2
TD+
1
RD-
TD-
3
4
ThreadFEFunctional earth (housing)
Table 7.4:Pin assignment HOST / BUS IN BCL 558i
For the host connection of the BCL 558i, the "KB ET - … - SA-RJ45" ready-made cables
are preferred, see table 13.9 "Bus connection cables for the BCL 558i" on page 180.
Ethernet cable assignments
BCL508 HOST / BUS INRJ
RD+
2
4
RD-
TD-
3
TD+
1
PinNameRemark
1TD+Transmit Data +
2RD+Receive Data +
3TD-Transmit Data -
4RD-Receive Data -
TD+ (1)
TD- (2)
RD
RD- (6
1
8
Figure 7.7:HOST / BUS IN cable assignments on RJ-45
Notice for connecting the Ethernet interface!
Ensure adequate shielding. The entire connection cable must be shielded and earthed. The
RD+/RD- and TD+/TD- wires must be stranded in pairs.
Use CAT 5 cable for the connection.
82BCL 558iLeuze electronic
Page 86
7.2.5BUS OUT for the BCL 558i
M12 socket
(D-coded)
To set up an Ethernet network with other participants with linear topology, the BCL 558i
makes available another Ethernet interface. The use of this interface drastically reduces the
cabling requirements, as only the first BCL 558i requires a direct connection to the switch,
via which it can communicate with the host. All other BCL 558i are connected in series to
the first BCL 558i, see figure 7.9.
BUS OUT (4-pin socket, D-coded)
BUS OUT
RD+
2
TD+
1
Table 7.5:Pin assignment BUS OUT
For the connection of two BCL 558i, the "KB ET - … - SSA" ready-made cables are
preferred, see table 13.9 "Bus connection cables for the BCL 558i" on page 180.
If you use user-configurable cables, note the following:
Notice!
Ensure adequate shielding. The entire connection cable must be shielded and earthed. The
signal lines must be stranded in pairs.
Use CAT 5 cable for the connection.
4
RD-
TD-
3
PinNameRemark
1TD+Transmit Data +
2RD+Receive Data +
3TD-Transmit Data -
4RD-Receive Data -
ThreadFEFunctional earth (housing)
Notice!
For the BCL 558i as standalone device or as the last participant in a linear topology,
termination on the BUS OUT socket is not mandatory!
Leuze electronicBCL 558i83
TNT 35/7-24V
Page 87
7.3Ethernet topologies
PC / PLC host interface
Other network participants
BCL 558i
192.168.60.xxx
PC / PLC host interface
BCL 558i
192.168.0.xxx
to other network participants
BCL 558i
192.168.0.yyy
BCL 558i
192.168.0.zzz
I/O
PWR
I/O
PWR
I/O
PWR
The BCL 558i can be operated as a single device (stand-alone) in an Ethernet star topology
with individual IP address.
The IP address can either be set permanently via the display or webConfig tool or assigned
dynamically via a DHCP server.
Figure 7.8:Ethernet with star topology
The innovative further development of the BCL 558i with integrated switch functionality
offers the option of networking multiple bar code readers of type BCL 558i with one another.
In addition to the classic "star topology", a "linear topology" is thus also possible.
This makes wiring the network easy and inexpensive as slaves are looped through to one
another in parallel.
The maximum length of a segment (connection from the hub to the last participant) is limited
to 100m.
Figure 7.9:Ethernet with linear topology
Up to 254 bar code readers can be networked. For this purpose, each participating BCL 558i
is assigned the respective network address via the display and the control panel or the
webConfig tool. This address must be specified by the network administrator. Alternatively,
the BCL 558i can also be configured as a DHCP client and then automatically receive its
address from a DHCP server.
Information on the necessary configuration steps can be found in chapter 10.
84BCL 558iLeuze electronic
Page 88
7.3.1Ethernet wiring
A Cat. 5 Ethernet cable should be used for wiring.
For the connection on the BCL 558i, a "KDS ET M12 / RJ 45 W - 4P" adapter is available
into which the standard network cable can be plugged.
If no standard network cables are to be used (e.g. due to lacking IP… protection class), you
can use the "KB ET - … - SA" user-configurable cable on the BCL 558i, see table 13.9 "Bus
connection cables for the BCL 558i" on page 180.
The individual BCL 558i devices in a linear topology are connected with the
"KB ET - … - SSA" cable, see table 13.9 "Bus connection cables for the BCL 558i" on
page 180.
For unavailable line lengths, you can configure your cables yourself. When doing so, make
certain that you connect TD+ on the M12 connector with RD+ on the RJ-45 connector and
TD- on the M12 connector with RD- on the RJ-45 connector, respectively, etc.
Notice!
Use the recommended connectors / sockets or the ready-made cables (see chapter 13
"Type overview and accessories").
7.4Cable lengths and shielding
Observe the following maximum cable lengths and shielding types:
ConnectionInterfaceMax. cable lengthShielding
BCL – service
BCL – host
Network from the
first BCL to the
last BCL
BCL – power
supply unit
Switching input
Switching output
Table 7.6:Cable lengths and shielding
USB3m
Ethernet100 m
The max. segment length must
not exceed 100m for 10Base-T
Ethernet
twisted pairs (min. Cat. 3) and
100Base-TX twisted pair
(min. Cat. 5)
30mnot necessary
10mnot necessary
10mnot necessary
shielding absolutely
necessary acc. to USB
specifications
absolutely required,
shielded
absolutely required,
shielded
TNT 35/7-24V
Leuze electronicBCL 558i85
Page 89
8Display and control panel
LED
LED
Control buttons
Read result
Bar graph
Status displayEtherNet/IP status
USB interface
8.1Structure of the control panel
IO1 IO2 IO3
IO4 ATT ERR
Figure 8.1:Structure of the control panel
8.2Status display and operation
8.2.1Indicators in the display
Status displays of the switching inputs/outputs
IO1
Switching input or switching output 1 active (function dependent on set configuration).
Default: Switching input with the "Reading gate activation" function
IO2
Switching input or switching output 2 active (function dependent on set configuration).
Default: Input with the "Teach-in" function
IO3
Switching input or switching output 3 active (function dependent on set configuration).
Default: Switching input with the "Reading gate activation" function
IO4
Switching input or switching output 4 active (function dependent on set configuration).
ATTWarning (Attention)
ERR Internal device error (Error) -> The device must be sent in for inspection
Bar graph
The read quality is described on a scale of 0 - 100%. The quality is evaluated based on the
"Equal Scans" of the read result configured in the bar code reader.
Default: Switching output with the "No read" function
ENIP
USB
MS
12345678
NET
86BCL 558iLeuze electronic
Page 90
Status display of the USB interface
USB The BCL 558i is connected to a PC via the USB interface.
MS An external parameter memory is properly connected to the USB interface of the
BCL 558i.
Read result
The read bar code information is displayed.
EtherNet/IP status
ENIP EtherNet/IP interface is activated.
8.2.2LED status indicators
PWR LED
offDevice OFF
flashes greenDevice ok, initialization phase
green continuous light Device ok
- no supply voltage
- no bar code reading possible
- voltage connected
- self test running
- initialization running
- bar code reading possible
- self test successfully finished
- device monitoring active
orange continuous light Service mode
- bar code reading possible
- configuration via the USB service interface
- configuration via the display
- no data on the host interface
flashes redDevice ok, warning set
- bar code reading possible
- temporary operating fault
red continuous lightDevice error / parameter enable
- no bar code reading possible
Leuze electronicBCL 558i87
TNT 35/7-24V
Page 91
NET LED
ESC
offNo supply voltage
flashes greenInitialization
green continuous light Operation ok
flashes redCommunication error
red continuous lightNetwork error
green/red flashingSelf test
8.2.3Control buttons
- no communication possible
- no IP address assigned
- self test running
- no EtherNet/IP communication present
- BCL 558i is not assigned to any master
- BCL 558i bus communication ok
- self test running
- time-out in bus communication
- double IP address
- self test running
UpNavigate upward/laterally.
DownNavigate downward/laterally.
ESCExit menu item.
ENTERConfirm/enter value, change menu levels.
Navigating within the menus
The menus within a level are selected with the up/down buttons .
The selected menu item is activated with the enter button .
Press the ESC button to move up one menu level.
ESC
When one of the buttons is actuated, the display illumination is activated for 10min.
88BCL 558iLeuze electronic
Page 92
Setting values
If input of a value is possible, the display looks like this:
0000|
<-|0123456789 save
Standard ----- Unit
0000 | |
Use the and buttons to set the desired value. An accidental, incorrect entry can be
corrected by selecting
<-| and then pressing .
Then use the buttons to select save and save the set value by pressing .
Selecting options
If options can be selected, the display looks like this:
o OFF
ON
Standard ----- Unit
OFF | |
Select the desired option with the buttons. Activate the option by pressing .
Leuze electronicBCL 558i89
TNT 35/7-24V
Page 93
8.3Menu description
ENIP
After voltage is applied to the bar code reader, a startup screen is displayed for several
seconds. The display then shows the bar code reading window with all status information.
8.3.1The main menus
BCL558i SF 102
Leuze electronic
GmbH & Co. KG
SW: V 1.3.1 HW:1
SN: 0704-081894 001
Parameter handling
Decoder table
Digital SWIO
EtherNet/IP
Language selection
oDeutsch
o English
o Español
o Français
o Italiano
Device information - main menu
This menu item contains detailed information on
• Device type
• Software version
• Hardware version
• Serial number
Network settings - main menu
• Display of the network settings
See "EtherNet/IP" on page 99.
Bar code reading window - main menu
• Visualization of the read bar code information
• Status overview of the switching inputs/outputs
• Bar graphs for read quality of the current bar code
See "Indicators in the display" on page 86.
Parameter - main menu
• Configuration of the bar code reader
See "Parameter menu" on page 92.
Language selection - main menu
• Selection of the display language
See "Language selection menu" on page 100.
90BCL 558iLeuze electronic
Page 94
Ser vice
Diagnostics
Status messages
Service - main menu
• Scanner diagnosis and status messages
See "Service menu" on page 100.
Actions
o Start decoding
o Start alignment
o Start auto-setup
o Start teach-in
Actions - main menu
• Various functions for scanner configuration and manual operation
See "Actions menu" on page 101.
Notice!
The rear cover of this manual includes a fold-out page with the complete menu structure.
It describes the menu items in brief.
The display offers only limited configuration options. The configurable parameters are
described here in chapter 8.3.
Only the webConfig tool provides complete configuration options and is largely self-explanatory. The use of the webConfig tool is described inchapter 9. Notes on commissioning via
the webConfig tool can be found in chapter 10.
TNT 35/7-24V
Leuze electronicBCL 558i91
Page 95
8.3.2Parameter menu
Parameter handling
The Parameter handling submenu is used to lock and release the parameter input via the
display and for resetting to default values.
The standard setting (
changes.
If parameter enabling is activated (
manually.
By pressing the enter button after selecting
Parameters to default
standard settings without any further security prompts.
In this case, English is selected as the display language.
OFF
Table 8.1:Parameter handling submenu
) prevents unintended parameter
ON
), parameters can be changed
, all parameters are reset to their
Standard
OFF
92BCL 558iLeuze electronic
Page 96
Decoder table
In the Decoder table submenu, 4 different code type definitions can be stored. Bar codes
that have been read can only be decoded if they correspond to one of the definitions stored
here.
Depending on the symbology (code type)
selected for the decoder, further calculation
algorithms can be selected here.
Check digit method used for the decoding of
the bar code that has been read.
Standard
If
intended for the respective code type is
used.
Not standard
Specifies whether the check digit is
transmitted. Standard means that the
transmission matches the standard
intended for the respective code type.
Determines the function of switching
input/output 1.
In the case of passive, the connection is
on 0V if the
to
parameter is set to
OFF
function upon high level at the switching
input
ON
function upon low level at the switching
input.
Time in milliseconds for which the input
signal must be present and stable.
Time in milliseconds between the end of
the debounce time and activation of the
function configured below.
Minimum activation time in milliseconds
for the function configured below.
Time in milliseconds for which the function configured below remains activated
after the switching input signal is deactivated and the pulse duration has
expired.