Leuze electronic AMS 200 Technical Description

AMS 200
Optical Laser Measurement System
GB 01-03/08 50104729
TECHNICAL DESCRIPTION
© All rights reserved, especially the right of reproduction, distribution and translation. Copying or
reproductions in any form require the written consent of the manufacturer. Product names are used without warranty of unrestricted applicability. Changes reflecting technical improvements may be made.
Table of contents
1 General information ........................................................................................................... 4
1.1 Explanation of symbols........................................................................................................ 4
1.2 Declaration of conformity ..................................................................................................... 4
1.3 Description of AMS 200…functions ..................................................................................... 5
1.4 Nomenclature....................................................................................................................... 5
2 Safety notices..................................................................................................................... 6
2.1 General safety notices ......................................................................................................... 6
2.2 Safety standards.................................................................................................................. 6
2.2.1 Intended use.................................................................................................................................. 6
2.3 Working safely .....................................................................................................................7
3 Commissioning steps at a glance ....................................................................................9
4 Specifications................................................................................................................... 12
4.1 General specifications........................................................................................................ 12
4.2 Dimensioned drawing of AMS 200..................................................................................... 14
4.3 Electrical connection.......................................................................................................... 15
4.3.1 PWR - Voltage supply and input/output.......................................................................................16
4.3.2 BUS IN - (PROFIBUS DP IN) ......................................................................................................16
4.3.3 BUS OUT - (PROFIBUS DP OUT) ..............................................................................................16
4.3.4 BUS IN - (Interbus) ...................................................................................................................... 17
4.3.5 BUS OUT - (Interbus) .................................................................................................................. 17
4.3.6 SSI interface ................................................................................................................................17
4.3.7 SERVICE - (RS 232) ...................................................................................................................18
5 Reflectors ......................................................................................................................... 19
5.1 General information ........................................................................................................... 19
5.2 Specifications of reflectors.................................................................................................19
5.3 Selecting reflector sizes..................................................................................................... 20
5.4 Dimensioned drawing of reflectors..................................................................................... 20
5.5 Mounting the reflector ........................................................................................................ 21
5.5.1 General information .....................................................................................................................21
5.5.2 Mounting the reflector.................................................................................................................. 22
5.5.3 Table ofreflector pitches ..............................................................................................................22
6 Control panel display AMS 200… ................................................................................... 23
6.1 Structure of the control panel............................................................................................. 23
6.2 Status display and operation.............................................................................................. 23
6.2.1 Control buttons ............................................................................................................................23
6.2.2 Status displays............................................................................................................................. 24
6.3 Operation ........................................................................................................................... 26
6.3.1 The 5 main menus.......................................................................................................................26
6.3.2 Parameter - Main menu...............................................................................................................27
6.3.3 Language selection - Main menu.................................................................................................30
6.3.4 Service - Main menu....................................................................................................................30
Leuze electronic AMS 200 1
Table of contents
7 Mounting........................................................................................................................... 31
7.1 Mounting the AMS 200…................................................................................................... 31
7.1.1 Optional mounting bracket ...........................................................................................................32
7.1.2 Mounting distances ......................................................................................................................33
7.2 Mounting the reflector ........................................................................................................ 33
7.3 Mounting with deflector unit ............................................................................................... 34
7.3.1 General information......................................................................................................................34
7.3.2 Mounting the US AMS 01 deflector unit with integrated mounting bracket..................................34
7.3.3 Dimensioned drawing of US AMS 01 deflector unit .....................................................................35
7.3.4 Mounting the US 1 OMS deflector unit without mounting bracket................................................36
7.3.5 Aligning the laser light spot in the centre of the reflector..............................................................37
8 Device parameters and interfaces.................................................................................. 38
8.1 PROFIBUS......................................................................................................................... 38
8.1.1 General information......................................................................................................................38
8.1.2 PROFIBUS - Electrical connection...............................................................................................39
8.1.3 PROFIBUS address .....................................................................................................................40
8.1.4 General information on the GSD file ............................................................................................42
8.1.5 Overview of the GSD modules.....................................................................................................43
8.1.6 Detail description of the modules.................................................................................................45
8.2 SSI ..................................................................................................................................... 80
8.2.1 General information about the transmission procedure ...............................................................80
8.2.2 SSI - Electrical connection ...........................................................................................................82
8.2.3 Notice regarding software parameters .........................................................................................83
8.2.4 Default settings of the SSI interface.............................................................................................83
8.2.5 Changing the SSI default settings via the display ........................................................................84
8.2.6 SSI parameter display..................................................................................................................84
8.3 Interbus.............................................................................................................................. 85
8.3.1 General information......................................................................................................................85
8.3.2 Activation/deactivation of the Interbus interface on the AMS 200................................................85
8.3.3 Indicator LEDs..............................................................................................................................86
8.3.4 Interbus - Electrical connection....................................................................................................86
8.3.5 Ident number of the AMS 200/xxx-20-(H).....................................................................................88
8.3.6 Data format - 32-bit input data .....................................................................................................88
8.3.7 Default settings of the AMS 200/…-20… .....................................................................................90
8.3.8 Configuration via the control panel/display...................................................................................91
8.4 RS 232...............................................................................................................................92
8.4.1 General information......................................................................................................................92
8.4.2 Activation/deactivation of the RS 232 interface on the AMS 200.................................................92
8.4.3 RS 232 - Electrical connection .....................................................................................................93
8.4.4 Configuration via the control panel/display...................................................................................94
8.4.5 Communication protocol (binary protocol)....................................................................................96
9 Diagnostics and troubleshooting ................................................................................... 98
9.1 General errors causes ....................................................................................................... 98
9.2 Status displays on the AMS 200… display ........................................................................ 98
9.3 PROFIBUS errors .............................................................................................................. 98
9.4 SSI interface errors............................................................................................................ 99
9.5 RS 232 interface errors...................................................................................................... 99
9.6 Interbus interface errors..................................................................................................... 99
2 AMS 200 Leuze electronic
Table of contents
10 Type overview and accessories ................................................................................... 101
10.1 Overview of AMS 200…types .......................................................................................... 101
10.2 Overview of reflector types .............................................................................................. 101
10.3 Accessory mounting bracket............................................................................................ 101
10.4 Accessory deflector unit................................................................................................... 101
10.5 Accessory PROFIBUS terminating resistor...................................................................... 102
10.6 Accessory connectors...................................................................................................... 102
10.7 Accessory ready-made cables for voltage supply............................................................ 102
10.7.1 Contact assignment of PWR connection cable..........................................................................102
10.7.2 Technical data for voltage supply cable.....................................................................................102
10.7.3 Order codes for voltage supply cables ......................................................................................102
10.8 Accessory ready-made cables for interface connection................................................... 103
10.8.1 General information ................................................................................................................... 103
10.8.2 Contact assignment for PROFIBUS connection cable KB PB… ...............................................103
10.8.3 Contact assignment for SSI/Interbus connection cable KB SSI/IBS…...................................... 104
10.8.4 Technical data of interface connection cable.............................................................................104
10.8.5 Order codes for interface connection cables ............................................................................. 105
11 Maintenance ................................................................................................................... 106
11.1 Cleaning........................................................................................................................... 106
11.2 Repairs and maintenance ................................................................................................ 106
12 Appendix......................................................................................................................... 107
12.1 EU Declaration of Conformity .......................................................................................... 107
Index................................................................................................................................ 108
Leuze electronic AMS 200 3
General information

1 General information

1.1 Explanation of symbols

The symbols used in this technical description are explained below.
Attention!
This symbol precedes text messages which must strictly be observed. Failure to comply with this information can result in injuries to personnel or damage to the equipment.
Attention Laser!
This symbol warns of possible danger caused by hazardous laser radiation.
Notice!
This symbol indicates text passages containing important information.

1.2 Declaration of conformity

The AMS 200… absolute measuring optical laser measurement system was designed and manufactured in accordance with applicable European directives, standards and guidelines.
Notice!
A copy of all declarations of conformity available for this product can be found in the appen­dix of this handbook (chapter 12.1 on page 107).
The manufacturer of this product, Leuze electronic GmbH + Co. KG in D-73277 Owen/Teck, uses a certified quality assurance system in accordance with ISO 9001.
U
L
C
US
LISTED
4 AMS 200 Leuze electronic

1.3 Description of AMS 200…functions

The AMS 200… optical laser measurement system measures distances to stationary as well as moving plant components. The measurement principle is based on the measurement of the propagation time of the radiated light. The light emitted by the laser diode is reflected onto the receiving element of the laser measurement system by a reflector. The AMS 200… calculates the distance to the reflector based on the propagation time of the radiated light. The high absolute measurement accuracy of the laser measurement system as well as the fast integration time are designed for position control applications.

1.4 Nomenclature

AMS 200 = Absolute Measurement System 200.
General information
Leuze electronic AMS 200 5
TNT 35/7-24V
Safety notices

2 Safety notices

2.1 General safety notices

Documentation
All entries in this technical description must strictly be observed, in particular those in the "Safety notices" section. Keep this technical description in a safe place. It should be acces­sible at all times.
Repair
Repairs must only be carried out by the manufacturer or an authorised representative.
Attention!
The device must not be opened. Failure to comply will render the guarantee void. Warranted features cannot be guaranteed after the device has been opened.

2.2 Safety standards

The AMS 200… absolute measuring optical laser measurement system was developed, manufactured and tested in accordance with the applicable safety standards. It corresponds to the state of the art.

2.2.1 Intended use

The AMS 200… device series is an absolute measurement system based on laser tech­nology. The devices use a visible optical laser to measure distances of up to 200 m contact­lessly. The laser is designed so that position measurements are made against a reflector.
Attention!
The protection of personnel and the device cannot be guaranteed if the device is operated in a manner not complying with its intended use.
Areas of application
The AMS 200… is suitable for the following areas of application:
• Distance measurements for determining the position of automated, moving plant components such as:
• Travel and lifting axes of high-bay storage devices
• Gantry crane bridges and their trolleys
• Repositioning units
• Lifts
6 AMS 200 Leuze electronic

2.3 Working safely

Attention!
Access to or changes on the device, except where expressly described in this operating manual, are not authorised. The device must not be opened. Failure to comply will render the guarantee void. Warranted features cannot be guaranteed after the device has been opened.
Safety regulations
Observe the locally applicable legal regulations and the rules of the employer's liability insur­ance association.
Attention! The AMS 200… is not a safety module acc. to EU machine guidelines.
Qualified personnel
Mounting, commissioning and maintenance of the device may only be carried out by quali­fied personnel. Electrical work must be carried out by a certified electrician.
Attention, laser radiation!
The AMS 200… operates with a red light laser of class 2 acc. to EN 60825-1. If you look into the beam path over a longer time period, the retina of your eye may be damaged!
Never look directly into the beam path!
Safety notices
Do not point the laser beam of the AMS 200… at persons!
When mounting and aligning the AMS 200… take care to avoid reflections of the laser beam off reflective surfaces!
Heed the laser safety regulations according to DIN EN 60825-1 in their most current version! The output power of the laser beam at the reading window is at most 4.0 mW acc. to EN 60825-1. The average laser power is less than 1 mW in accordance with la­ser class 2 as well as CDRH class 2.
The AMS 200… uses a laser diode with low power in the visible red light range with an emitted wavelength of 650 … 690 nm.
Attention! CAUTION! The use of operating and adjusting devices other than those specified here
or carrying out of differing procedures may lead to dangerous exposure to radiation.
Leuze electronic AMS 200 7
TNT 35/7-24V
Safety notices
A
D
A Hazard warning & logotype B Aperture label C Warning label and certification label D Name plate with part no., version no., date of manufacture and serial no.
B
C
or
The housing of the AMS 200… is provided with the following labels:
Figure 2.1: Attachment of the stick-on labels at the AMS 200…
8 AMS 200 Leuze electronic
Commissioning steps at a glance

3 Commissioning steps at a glance

Notice!
Below you will find a short description for the initial commissioning of the laser meas­urement system. Detailed explanations for all listed points can be found throughout the handbook.
Mechanical design
The AMS 200… and the corresponding reflector are mounted on two opposing, plane­parallel, flat and vertical walls or plant components.
For error-free position measurement there must be unobstructed visual contact between the AMS 200… and the reflector.
Mounting the device
The laser is mounted on a vertical wall using 4 screws (M5).
Alignment is performed using 2 adjustment screws. (Laser light spot centred on the reflector.) Once aligned, the device is secured in place with the knurled nut and locked using the M5 nut.
chapter 7.1 on page 31
Mounting the reflector
The reflector is mounted on a vertical wall using 4 screws (M5). The reflector is angled using the included shims. For specific information please refer to chapter 5 (Reflectors). AMS 200… and reflector oppose each other such that the laser light spot is positioned in the centre of the reflector.
chapter 5 on page 19
Attention!
For position calculation purposes the laser beam must reach the reflector without interrup­tion. Ensure that the laser beam is always incident on the reflector when the system is mov­ing.
Connecting PWR, PROFIBUS, Interbus, SSI or RS 232
The laser measurement system is connected using M 12 connectors.
The voltage supply is connected via the PWR M 12 connection.
The PROFIBUS/Interbus is connected via BUS IN or, in the case of a continuing network, via BUS OUT.
PROFIBUS:
I
NTERBUS
SSI:
RS 232:
If BUS OUT is not used, the PROFIBUS must be terminated at this point with a M 12 termi­nator plug (see chapter 10.5 "Accessory PROFIBUS terminating resistor"PROFIBUS).
:
The Interbus does not require a terminator plug at the BUS OUT connection.
The SSI interface is connected via the SSI M 12 connection.
The RS 232 interface is connected via the SERVICE M 12 connection.
chapter 4.3 on page 15
Leuze electronic AMS 200 9
TNT 35/7-24V
Commissioning steps at a glance
Display
When the laser measurement system is supplied with voltage, the device status as well as the measured position value can be read. The display automatically switches to the display of the measurement values.
Use the Up and Down buttons at the left of the display to read and change a variety of data and parameters. For the PROFIBUS the network address of the AMS 200… must be configured on the display.
PROFIBUS:
SSI:
I
NTERBUS
The green PWR LED indicates that the device is ready for operation. The green BUS LED indicates correct configuration and correct bus connection. The configured PROFIBUS address appears on the display.
The default settings can be used when using the device as an SSI device. The PROFIBUS is deactivated via the display to prevent the BUS LED from signalling a missing PROFIBUS. If other SSI adjustments are desired, they can also be changed via the display.
:
The green PWR LED indicates that the device is ready for operation. The BUS LED is not active and is permanently off. While the Interbus is in an activated state, appears on the display.
chapter 6 on page 23
The AMS 200… on the PROFIBUS
Install the GSD file associated with the AMS 200… in the PROFIBUS manager of your control. Activate the desired modules (at least module 1 - position value).
Store the slave address for the AMS 200… in the PROFIBUS manager. Ensure that the address is the same as the address configured in the device. The SSI and RS 232 interfaces available on the AMS 200 can be used simultaneously with the PROFIBUS interface.
chapter 8.1 on page 38
10 AMS 200 Leuze electronic
Commissioning steps at a glance
The AMS 200… on the Interbus
The laser measurement system is delivered with preset Interbus parameters (see chapter 8.3.7 "Default settings of the AMS 200/…-20…" on page 90). The AMS 200 is clas­sified with Ident-Code 32 BUS IN M 12 connection or, in the case of a continuing network, via BUS OUT. The RS 232 interface available on the AMS 200 can be used simultaneously with the Interbus interface.
chapter 8.3 on page 85
The SSI interface of the AMS 200…
The laser measurement system is delivered with preset SSI parameters (see chapter 8.2.4 "Default settings of the SSI interface"). Should it be necessary to adapt the parameters to the control/regulator, these settings are made directly via the display, or, during operation, on the PROFIBUS using the GSD file (see chapter 6 "Control panel display AMS 200…" and see chapter 8.1.6.17 "Module 17: SSI interface").
chapter 8.2 on page 80
Notice!
You can find additional information on maintaining the laser measurement system in chapter 9 "Diagnostics and troubleshooting".
, which is stored in the control. The AMS 200 is connected via the
H
TNT 35/7-24V
Leuze electronic AMS 200 11
Specifications

4 Specifications

4.1 General specifications

Measurement data AMS 200/40-…-(H) AMS 200/120-…-(H) AMS 200/200-…-(H)
Measurement range 0.2 … 40 m 0.2 … 120 m 0.2 … 200 m Accuracy ± 2 mm ± 2 mm ± 3 mm Consistency Measurement value output 1.6 ms Measurement value calculation time / integration time Resolution adjustable, PROFIBUS/Interbus default: 1 mm,
Temperature drift 0.1 mm/K Ambient temperature sensitivity 1 ppm/K Air pressure sensitivity 0.3 ppm/hPa Traverse rate 10 m/s
Electrical data
Supply voltage VIN Current consumption without optics heating: 250 mA / 24 V DC
Optical data
Transmitter laser diode, red light, wavelength 650 … 690 nm Laser class 2 acc. to EN 60825-1, CDRH Laser life expectancy
Light spot diameter 40 mm (at 40 m) 100 mm (at 120 m) 150 mm (at 200 m)
Interfaces
PROFIBUS DP acc. to V SSI 50 kHz … max. 800 kHz Interbus 500 kBit/s RS 232 19.2 kBit/s … 115.2 kBit/s
Operating and display elements
Keyboard 4 buttons Display monochromatic graphical display, 128 x 64 pixels LED 2 LEDs, two-colour
Inputs/outputs
Quantity 2, programmable Input low: 0 … 2 V DC, high: 18 … 30 V DC
Output low: 0 … 2 V DC, high: VIN - 2 V DC
1)
0.3 mm 0.5 mm 0.7 mm
approx. 8 ms
SSI/RS 232 default : 0.1 mm
2)
18 … 30 V DC
with optics heating: 500 mA / 24 V DC
3)
average temperature / year
50 °C: 23.000 h 25 °C: 60.000 h 20 °C: 75.000 h 10 °C: 120.000 h
, V
0
1
12 Mbit/s
protected against polarity reversal
max. 100 mA, short-circuit proof,
protection against overvoltage, transients, excess temperature
12 AMS 200 Leuze electronic
Specifications
Mechanical data
Housing diecast zinc Optics glass Weight approx. 2.8 kg Protection class IP 65 acc. to EN 60529
Environmental conditions
Operating temperature without optics heating: -5 °C … +50 °C
with optics heating: -30 °C … +50 °C Storage temperature -30°C … +70°C Air humidity max. 90% rel. humidity, non-condensing Vibrations acc. to EN 60068-2-6 Noise acc. to EN 60068-2-64 Shock acc. to EN 60068-2-27, EN 60068-2-29 EMC acc. to EN 61000-6-2:2005 and EN 61000-6-4:2007
1) statistical error 1 sigma, minimum switch-on time 2 min.
2) For UL applications: only for use in Class 2 circuits according to NEC.
3) Switching off the laser diode during system downtime can considerably extend the life expectancy of the device. The laser life expectancy is calculated using a failure rate of 1 %.
4) with screwed-on M 12 connectors or mounted caps
5) see "EU Declaration of Conformity" on page 107.
Table 4.1: Specifications
4)
5)
Leuze electronic AMS 200 13
TNT 35/7-24V
Specifications
A M5 screw for alignment B Knurled nut and M5 nut for securing C Optical axis D Measured distance

4.2 Dimensioned drawing of AMS 200

Figure 4.2: Dimensioned drawing of AMS 200…
14 AMS 200 Leuze electronic

4.3 Electrical connection

The AMS 200… is connected using M 12 connectors.
For the locations of the individual device connections please refer to the device detail shown below.
The corresponding mating connectors and ready-made cables are available as accessories for all connections (see chapter 10 "Type overview and accessories").
Attention!
Connection of the device and maintenance work while under voltage must only be carried out by a qualified electrician.
If faults cannot be cleared, the device should be switched off from operation and protected against accidental use.
Before connecting the device please ensure that the supply voltage matches the value print­ed on the nameplate.
The AMS 200… is designed in accordance with safety class III for supply with PELV (pro­tective extra-low voltage with reliable disconnection). For UL applications use is permitted solely in Class 2 circuits according to NEC (National Electrical Code).
Please ensure that the protective conductor is connected correctly. Trouble-free operation is only guaranteed if the device is properly earthed.
Specifications
Figure 4.3: Location and designation of the electrical plug connections
Attention!
Protection class IP 65 is achieved only if the connectors and caps are screwed into place!
Leuze electronic AMS 200 15
TNT 35/7-24V
Specifications
M 12-plug
(A-coded)
M 12 plug
(B-coded)
BUS OUT
VCC
1
2
3
4
A (N)
B (P)
GND
FE
5
M 12 socket
(B-coded)

4.3.1 PWR - Voltage supply and input/output

PWR - I/O
PWR (5-pin plug, A-coded)
PWR
I/O 1
2
GND VIN
3
FE
5
4
I/O 2
1
For configuring the input/output, see Display, PROFIBUS or Interbus chapters.

4.3.2 BUS IN - (PROFIBUS DP IN)

PROFIBUS:
BUS IN
A (N)
2
N.C.
FE
3
5
B (P)
N.C.
1
4
Pin Name Remarks
1VINPositive supply voltage +18 … +30 V DC
2 I/O 1 Input/output 1 (see also modules 4/5)
3 GND Negative supply voltage 0 V DC
4 I/O 2 Input/output 2 (see also modules 4/5)
5FEFunctional earth
Thread FE Functional earth (housing)
BUS IN (5-pin plug, B-coded)
Pin Name Remarks
1N.C.Not used
2A (N)Receive/transmit data A-line (N)
3 N.C. Not used
4B (P)Receive/transmit data B-line (P)
5SHIELDShield or functional earth
Thread FE Functional earth (housing)

4.3.3 BUS OUT - (PROFIBUS DP OUT)

PROFIBUS:
BUS OUT (5-pin socket, B-coded)
Pin Name Remarks
1VCC
2A (N)Receive/transmit data A-line (N)
3 GND Data reference potential
4B (P)Receive/transmit data B-line (P)
16 AMS 200 Leuze electronic
5SHIELDShield or functional earth
Thread FE Functional earth (housing)
Supply voltage +5V (termination)

4.3.4 BUS IN - (Interbus)

M 12 plug
(B-coded)
M 12 socket
(B-coded)
SSI
CLK+
3
2
1
4
FE
DATA-
CLK-
DATA+
5
M 12 plug
(B-coded)
I
NTERBUS
:
BUS IN
/DO
2
DI
Data GND
3
5
/DI
DO
1
4

4.3.5 BUS OUT - (Interbus)

I
NTERBUS
:
BUS OUT
/DO
2
DO
1
/DI
DI
3
5
4
Data GND
Specifications
BUS IN (5-pin plug, B-coded)
Pin Name Remarks
1DOFrom the Interbus master
2/DOFrom the Interbus master - inverted
3 DI To the Interbus master
4/DITo the Interbus master - inverted
5Data GNDData Ground
Thread SHIELD Shield via RC element on the housing
BUS OUT (5-pin socket, B-coded)
Pin Name Remarks
1DOFrom the Interbus master
2/DOFrom the Interbus master - inverted
3 DI To the Interbus master
4/DITo the Interbus master - inverted
5 Data GND Data Ground
Thread SHIELD Shield directly on the housing

4.3.6 SSI interface

SSI
SSI (5-pin plug, B-coded)
Pin Name Remarks
1DATA++ Data line SSI (output)
2DATA-- Data line SSI (output)
3 CLK+
4CLK-
5FEFunctional earth
Leuze electronic AMS 200 17
Thread FE Functional earth (housing)
+ Clock line SSI
(input electrically insulated)
- Clock line SSI (input electrically insulated)
TNT 35/7-24V
Specifications
SERVICE
1
2
3
4
+3.3 V
NC
RS232-RX
RS232-TX
GND
5
M 12 socket
(A-coded)

4.3.7 SERVICE - (RS 232)

RS 232
Notice!
The shown connections, specifically the assignment of connectors or sockets, describe the M 12 connections of the AMS 200.
SERVICE (5-pin socket, A-coded)
Pin Name Remarks
1+3.3V Voltage supply 3.3 V DC
2RS232-TX
Transmission line for RS232/service data
3 GND Voltage supply 0 V DC
4RS232-RX Receiving line for RS232/service data
5NCNot used
Thread FE Functional earth (housing)
18 AMS 200 Leuze electronic

5 Reflectors

5.1 General information

The laser measurement system measures distances against a reflective tape (reflector). The reflective tape is available pre-mounted on an aluminium plate or as self-adhesive tape. Different sizes of reflective tape are available for various measurement distances and instal­lation sites.
Notice!
On the front side of the reflector is a stick-on label with the designation "TOP". Particularly for measurement distances greater than 120 m, it is important to always mount the reflector with the reflector side labelled with "TOP" so that it has the same alignment as the M 12 connections of the AMS 200:
• M 12 connections of the AMS 200 on top–> TOP on reflector on top !
• M 12 connections of the AMS 200 on side–> TOP on reflector on side !
• M 12 connections of the AMS 200 on bottom–> TOP on reflector on bottom !
Attention!
The range, accuracy and consistency specified in the technical data for the laser measure­ment system are achieved only when using the reflective tape specified by Leuze electronic.

5.2 Specifications of reflectors

The reflective tape consists of a white, microprism-based reflective material. The beam reflection system is located under a hard, highly transparent, protective coating. The adhe­sive tape is covered with a protective foil.
Reflectors
Specifications
Recommended application temperature for adhesive tape Temperature resistance (affixed) Mounting surface the mounting surface must be clean, dry and free of grease Cutting the tape with sharp tools always on the side of the tape with the prism
Cleaning do not use any abrasive agents Cleaning agents warm water with commercially available household deter-
Cleaning method rinse with clear water and wipe Storage store in a cool, dry place
Attention!
For applications in low-temperature areas less than -10 °C, the max. distance may be affect­ed when measuring distances greater than 120 m. For distances greater than 120 m we rec­ommend "floating" mounting of the reflective tape, i.e. the edge of the foil may only be fastened or secured with an additional adhesive tape. For measurement distances greater than 120 m avoid full-surface adhesive mounting.
Leuze electronic AMS 200 19
+5°C … +25°C
-40°C … +80°C
structure.
gent
TNT 35/7-24V
Reflectors
Always align the TOP marking with the AMS connections! (chapter 5.1)

5.3 Selecting reflector sizes

Depending on the system design, the reflector may either be mounted on the moving vehicle or in a stationary location.
Attention!
The reflector sizes shown below are recommended by Leuze electronic for mounting the AMS 200 on a vehicle. The system supplier must always perform a check to determine whether a larger reflector than the one recommended has to be used by reason of mechan­ical travel tolerances. This applies, in particular, when the laser measurement system is mounted on a vehicle. The laser beam must not leave the reflector during travel. For station­ary mounting of the AMS 200, a small 200 x 200 mm reflector will be adequate for all meas­urement distances.
Recommended reflector sizes
Laser measurement system (range in m)
AMS 200/40… (max. 40 m) 200 x 200 mm
AMS 200/120… (max. 120 m) 500 x 500 mm
AMS 200/200… (max. 200 m)
Recommended reflector size (H x W)
749 x 914 mm 914 x 914 mm
Type designation …-S = Self-adhesive …-M = Mounted
Reflective tape 200x200-S Reflective tape 200x200-M
Reflective tape 500x500-S Reflective tape 500x500-M
Reflective tape 749x914-S Reflective tape 914x914-M Reflective tape 914x914-S
Part No.
50104361 50104364
50104362 50104365
50104363 50104366 50108988

5.4 Dimensioned drawing of reflectors

Figure 5.1: Dimensioned drawing of reflectors
20 AMS 200 Leuze electronic
Part Reflective tape Reflector plate
Pitch 1 °
Spacer rings
Reflective tape 200x200-S 200 200 N/A N/A
Reflective tape 500x500-S 500 500 N/A N/A
Reflective tape 749x914-S 914 749 N/A N/A
Reflective tape 914x914-S 914 914 N/A N/A
Reflective tape 200x200-M 200 200 250 250
Reflective tape 500x500-M 500 500 550 550
Reflective tape 914x914-M 914 914 946 946

5.5 Mounting the reflector

5.5.1 General information

The reflective tape of the "Reflective tape …x…-S“ – self-adhesive – series must be affixed to a flat, clean and grease-free mounting surface. We recommend using a separate metal plate, which is to be provided on-site.
The reflective tape must be angled as described in Table 5.4.
The reflective tape of the "Reflective tape …x…-M" – mounted on aluminium plate – series is provided with appropriate mounting holes. Spacer rings are provided in the packet for achieving the necessary pitch angle. For further information see Table 5.4.
Reflectors
xL(mm) yL(mm) XL(mm) YL(mm)
Figure 5.2: Pitch of the reflector
Leuze electronic AMS 200 21
TNT 35/7-24V
Reflectors
Pitch 1 °
Direct reflection from the
triad structure
Deflected surface reflection due to
the pitch of the reflective tape

5.5.2 Mounting the reflector

The combination of laser measurement system and reflective tape is mounted in such a way that the laser light spot hits the reflective tape as centred as possible and without interrup­tion.
For this purpose use the provided adjustment elements on the AMS 200… (see chapter 7 "Mounting"). If necessary, remove the protective foil from the reflector.
Notice!
The reflector must be angled. To do this, use the spacer rings. Angle the reflectors so that the surface reflections of the foil seal are deflected to the left, right or upwards. Avoid a downward pitch, as additional reflections may occur on the running rails. The chapter 5.5.3 gives the correct pitch with respect to the reflector size and thus the length of the spacer rings.
Figure 5.3: Reflector mounting

5.5.3 Table ofreflector pitches

Reflector type
Reflective tape 200x200-S Reflective tape 200x200-M
Reflective tape 500x500-S Reflective tape 500x500-M
1)
1)
Pitch by spacer rings
4 mm
10 mm
Reflective tape 749x914-S 20 mm
Reflective tape 914x914-S Reflective tape 914x914-M
1) Spacer rings are included in the delivery contents of the reflective tape…-M
1)
20 mm
Table 5.4: Reflector pitch by spacer rings
22 AMS 200 Leuze electronic
1)

6 Control panel display AMS 200…

Status display
Distance measurement value
Control buttons
Bar graph Bus/interface info
LEDLED

6.1 Structure of the control panel

Figure 6.1: Structure of the control panel using the PROFIBUS device model as an exam-
ple
Control panel display AMS 200…

6.2 Status display and operation

6.2.1 Control buttons

Up Navigate upward/laterally.
Down Navigate downward/laterally.
ESC
ESC Exit menu item.
ENTER Confirm/enter value, change menu levels.
Leuze electronic AMS 200 23
TNT 35/7-24V
Control panel display AMS 200…

6.2.2 Status displays

6.2.2.1 LED PWR
off device OFF
flashes green device ok, initialisation phase
green continuous light device ok
flashes red device ok, warning set
red continuous light device error
- no supply voltage
- no measurement value output
- voltage connected
- self test running
- initialisation running
- parameter download running
- booting
- measurement value output
- self test successfully finished
- device monitoring active
- measurement value output
- light beam interruption detected
- plausibility error detected
- no measurement value output
- for details see status displays on the display
6.2.2.2 BUS LED (for PROFIBUS only; no function for Interbus)
off no supply voltage
- PROFIBUS deactivated (SSI interface only)
green continuous light bus ok
- device active on PROFIBUS ("data exchange")
flashes red bus error
- configuration failed ("parameter failure")
- DP error
- no data exchange
red continuous light bus error
- no DP protocol established to the master ("no data exchange")
24 AMS 200 Leuze electronic
6.2.2.3 Status displays on the display
Input 1 or output 1 active:
Function dependent on configuration (see also modules 4/5).
Input 2 or output 2 active: Function dependent on configuration (see also modules 4/5).
Warning laser prefailure message: Laser diode aged, device still functional; have replaced or repaired.
Temperature monitoring warning:: Above/below permissible internal device temperature.
Plausibility error: Implausible measurement value. Possible causes: light beam interruption, outside of measurement range, permissible internal device temperature considerably exceeded or traverse rate >10m/s.
Depending on the configuration, either zero or the last valid measurement value is output at the interfaces.
Received signal warning : Laser emission window or reflector dirty. Clean surfaces.
Internal hardware error: The device must be sent in for inspection.
6.2.2.4 Bar graph
Indicates the strength of the received laser light.
The middle line represents the ATT warning threshold. The distance value remains valid and is output at the interfaces.
If no bar graph is available, the PLB status information appears at the same time. The measurement value has thus been assessed as being implausible. Depending on the configuration, either zero or the last valid measurement value is output at the interfaces.
Control panel display AMS 200…
6.2.2.5 Bus/interface info
Displays the set PROFIBUS address (default 126). If the PROFIBUS is deactivated, this field is suppressed.
Displays the activated SSI interface. If the SSI interface is deactivated, this field is suppressed.
Displays the activated Interbus interface. If the Interbus interface is deactivated, this field is suppressed.
Displays the activated RS 232 interface. If the RS 232 interface is deactivated, this field is suppressed.
6.2.2.6 Measured position value
The measured position value is displayed in the configured unit of measurement.
In the metric setting, the measurement value is always displayed in m with 3 decimal places.
In the inch setting, the measurement value is always displayed in in with 1 decimal place.
Leuze electronic AMS 200 25
TNT 35/7-24V
Control panel display AMS 200…
Device information - main menu
• General information regarding the device
Measurement window - main menu
• Status information
• Measured position value
Parameter - main menu
• Access to all device parameters
Language selection - main menu
• Display language selection
Service - main menu
• Various service functions
PROFIBUS Interbus
dependent
on
device
version

6.3 Operation

6.3.1 The 5 main menus

After voltage has been applied to the laser, device information will be displayed for several seconds. The display then shows the measurement window with all status information.
The main menus are selected with the up/down buttons .
The selected main menu is activated with the enter button .
Use the ESC button to exit an activated main menu or submenu.
When one of the buttons is actuated, the display illumination is activated for 10 min.
ESC
Figure 6.2: The 5 main menus
26 AMS 200 Leuze electronic

6.3.2 Parameter - Main menu

Notice! Included in the front cover of this handbook is a fold-out page with the complete param-
eter menu structure. The parameters are briefly described and the respective default val-
ues are listed.
Control panel display AMS 200…
PROFIBUS:
A detailed description of the individual PROFIBUS parameters can be found in the descrip­tion of the PROFIBUS GSD modules (chapter 8.1.6 on page 45). Parameter handling is described in the following chapter.
I
NTERBUS
:
An extensive description of the default settings for Interbus can be found in chapter 8.3 on page 85.
Parameter handling is described in the following chapter.
6.3.2.1 Parameter handling menu item
Viewing and editing parameters
During normal operation parameters can only be viewed. If parameters need to be changed, the ON menu item in the Parameter enabling display mask must be activated (see figure
6.3).
Notice!
If a password was set, parameter enabling cannot be accessed until this password has been entered, see "Password for parameter enabling" on page 29.
The entire display of the AMS 200… is inverted as long as parameter enabling is activated.
Attention!
Depending on the device version the bus system or interface is deactivated upon activation of parameter enabling:
PROFIBUS:
The laser measurement system is deactivated on the PROFIBUS when parameter enabling is activated via the display. The device is reactivated on the PROFIBUS after parameter en­abling is exited.
TNT 35/7-24V
SSI:
The SSI interface remains active even during parameter enabling. Changes to parameters have an immediate effect.
I
NTERBUS
:
The Interbus interface remains active even during parameter enabling. Changes to param­eters have an immediate effect.
RS 232:
The RS 232 interface remains active even during parameter enabling. Changes to parame­ters have an immediate effect.
Leuze electronic AMS 200 27
Control panel display AMS 200…
Parameter enabling
ESC
Figure 6.3: Parameter enabling
Notice!
If the AMS 200… is operated on a PROFIBUS network, configuration is performed exclu­sively via the PROFIBUS.
PROFIBUS:
PROFIBUS:
SSI:
Parameters set via the display are overwritten by the parameters set in the GSD modules when operating the laser measurement system on the Profibus. For GSD modules which are not actively used on the PROFIBUS, the default settings of the laser measurement system apply, see "Detail description of the modules" on page 45. Thus the PROFIBUS presets values to all parameters.
Attention!
If parameters are changed via the display during bus operation, the laser measurement sys­tem is separated from the PROFIBUS when parameter enabling is activated via the display. Parameters set via the PROFIBUS are moved to the background, and changes to parame­ters can then be made via the display. When parameter enabling is exited, the laser meas­urement system is automatically reconnected to the PROFIBUS. Upon connection to the PROFIBUS, the laser measurement system receives all parameters from the PROFIBUS master.
Changes made via the display are overwritten!
Device settings for operating the laser measurement system on the PROFIBUS are managed and configured exclusively by the PROFIBUS master.
If the PROFIBUS is deactivated and the laser measurement system transmits its data via the SSI interface, it may be necessary to adjust the laser parameters via the integrated dis­play. In this operating mode the PROFIBUS default parameters have no effect; the SSI de­fault parameter set applies (see chapter 8.2.4). Settings made on the display apply permanently. As the parameters are only stored in the device in this operating mode, the parameters must be reset on the replacement device if device replacement is required.
ESC
ESC
28 AMS 200 Leuze electronic
6.3.2.2 Password for parameter enabling
The password query is deactivated by default. To protect against unwanted changes the password query can be activated. The preset password is 0000 and can be changed as necessary (see figure 6.4).
Notice!
In order to enter the password parameter enabling must be activated.
A selected password is saved with .
ESC
Control panel display AMS 200…
ESC
ESC
ESC
Figure 6.4: Changing the password
If the password is not known, the master password 2301 can always be used to enable the device.
Attention!
When operating the laser measurement system on the PROFIBUS, the password entered on the display has no effect. The PROFIBUS overwrites the password with the default set­tings.
PROFIBUS:
If a password is desired for PROFIBUS operation, it must be configured via module 18 d, e (see page 78).
Leuze electronic AMS 200 29
TNT 35/7-24V
Control panel display AMS 200…

6.3.3 Language selection - Main menu

Figure 6.5: Language selection - Main menu
PROFIBUS:

6.3.4 Service - Main menu

Notice!
When operating the laser measurement system on the PROFIBUS, the language configured in the GSD file is displayed.
Figure 6.6: Service - Main menu
Diagnosis
Selecting the Diagnosis menu item displays the following values:
• current measurement value.
• minimum value measured after diagnosis activation.
• maximum value measured after diagnosis activation.
Actuate the Up or Down button to reset the min./max. memory to the current meas- urement value.
In the Min/Max diagnosis window, displayed and stored device messages, such as ATT,
PLB, TMP etc., are reset by pressing any button or with Power ON/Power OFF.
Status messages
This menu item is used exclusively for service purposes by Leuze electronic.
30 AMS 200 Leuze electronic

7 Mounting

A M5 Allen screws for
aligning
B Knurled nut and
M5 nut for securing
C Optical axis D Must not be
adjusted!

7.1 Mounting the AMS 200…

Figure 7.1: Mounting the device
The AMS 200… and the corresponding reflector should be mounted on two opposing, plane-parallel, flat walls or plant components. For error-free position measurement there must be unobstructed line of sight between the AMS 200… and the reflector.
Use the M5 screws to mount the laser measurement system. Secure the screws with a toothed lock washer to protect against loosening caused by vibrations.
The laser light spot has to be aligned so that it always hits the centre of the opposing reflector, both at close range as well as at the maximum measurement distance. Use the two M5 hexagon socket screws to align the device ("A" in figure 7.1). When aligning please ensure that the knurled nut and the M5 lock nut ("B" in figure 7.1) are opened wide.
Mounting
TNT 35/7-24V
Attention!
To prevent the laser measurement system from becoming misaligned during continuous op­eration, then hand-tighten the knurled nut and securely lock into place with the M5 nut ("B" in figure 7.1). Knurled nut and M5 nut must not be tightened until after aligning.
Attention!
The device must not be opened. Failure to comply will render the guarantee void. Warranted features cannot be guaranteed after the device has been opened.
Leuze electronic AMS 200 31
Mounting

7.1.1 Optional mounting bracket

An optional mounting bracket is available as an accessory for mounting the AMS 200 on a flat, horizontal surface.
Type designation: MW OMS/AMS 01
Part No.: 50107255
Figure 7.2: Optional mounting bracket
32 AMS 200 Leuze electronic

7.1.2 Mounting distances

Reflector 1 Reflector 2
Minimum parallel distance to adjacent AMS 200
The smallest possible parallel distance to an adjacent AMS 200 is determined by the maximum measured distance as well as the characteristics of the reflector. To prevent adja­cent devices from interfering with each other the parallel distance of the laser light spots on the reflector is crucial.
Figure 7.3: Minimum parallel distance X to adjacent AMS 200
Min. parallel distance of the laser light spot X = 100 mm + (max. measurement distance in mm • 0.01)
Notice!
Please note that travel tolerances could cause the two laser light spots to move towards each other.
Mounting
X
If both AMS 200 devices are optically separated from each other, e.g. if mounted in different shelf alleys, the parallel distance can be chosen somewhat smaller, as there is no interfer­ence in this case.
Minimum distance to an adjacent DDLS 200 optical data transmission device
The DDLS 200 series optical data transceivers and the AMS 200 do not interfere with each other. Depending on the size of the used reflector, the optical data transceiver can be mounted with a minimum mounting spacing of 100 mm to the AMS 200. The mounting spacing is independent of the distance.

7.2 Mounting the reflector

The combination of laser measurement system and reflective tape or reflector is mounted in such a way that the laser light spot hits the reflective tape as centred as possible and without interruption.
Notice!
For further information on mounting the reflector please refer to chapter 5 "Reflectors".
Leuze electronic AMS 200 33
TNT 35/7-24V
Mounting

7.3 Mounting with deflector unit

7.3.1 General information

The two available deflector units are used for the 90 ° deflection of the laser beam, see "Accessory deflector unit" on page 101.
Attention!
The deflector units are designed for a maximum range of 40 m. Longer distances on request.

7.3.2 Mounting the US AMS 01 deflector unit with integrated mounting bracket

For this purpose the laser measurement system is screwed onto the body of the US AMS 01 deflector unit. For stand mounting the mirror can be mounted for 3 different directions of deflection:
1. Upward beam deflection
2. Beam deflection to the left
3. Beam deflection to the right
The deflector unit is mounted on plane-parallel, flat and vertical walls or plant components. For error-free position measurement there must be unobstructed line of sight between the AMS 200… and the deflection mirror as well as between the mirror and the reflector.
Use the M5 screws to mount the deflector unit. Secure the screws with a toothed lock washer to protect against loosening caused by vibrations.
Figure 7.4: Mounting variants of the US AMS 01 deflector unit
34 AMS 200 Leuze electronic

7.3.3 Dimensioned drawing of US AMS 01 deflector unit

A Laser beam
Mounting
Figure 7.5: Dimensioned drawing of US AMS 01 deflector unit
Leuze electronic AMS 200 35
TNT 35/7-24V
Mounting
A Mirror

7.3.4 Mounting the US 1 OMS deflector unit without mounting bracket

The US 1 OMS deflector unit and the AMS 200 are mounted separately from one another.
Notice!
When mounting please ensure that the laser light spot of the AMS 200 is positioned in the centre of the deflection mirror.
Figure 7.6: Photo and dimensioned drawing of the US 1 OMS deflector unit
Alignment of the laser light spot on the reflector is performed as described in chapter 7.3.5.
36 AMS 200 Leuze electronic

7.3.5 Aligning the laser light spot in the centre of the reflector

Using the alignment screws of the laser measurement system the laser light spot is aligned in the centre of the reflector via the deflector mirror. When adjusting please ensure that the knurled nut and the M5 lock nut are opened wide.
When the laser is aligned, hand-tighten the knurled nut and lock it securely into place using the M5 nut (see chapter 7.1 "Mounting the AMS 200…").
Mounting
Leuze electronic AMS 200 37
TNT 35/7-24V
Device parameters and interfaces
Measurement window with activated PROFI-
Display of the PROFIBUS address
Default: ON

8 Device parameters and interfaces

8.1 PROFIBUS

8.1.1 General information

The AMS 200… is designed as a PROFIBUS-DP device. For this purpose the functionality of the laser is defined via GSD parameter sets. The max. baud rate of the data to be trans­ferred is 12 Mbit/s.
PROFIBUS, SSI and RS 232 interfaces can be used simultaneously as fully-fledged interfaces. PROFIBUS and SSI interfaces are activated by default.
Notice!
The PROFIBUS interface can be activated/deactivated via the display. When the PROFIBUS is activated, the address set is visible on the display.
ESC
ESC
Figure 8.1: PROFIBUS activation
38 AMS 200 Leuze electronic

8.1.2 PROFIBUS - Electrical connection

M 12 plug
(B-coded)
M 12 socket
(B-coded)
BUS IN (5-pin plug, B-coded) BUS OUT (5-pin socket, B-coded)
Pin Name Remarks Pin Name Remarks
1N.C.Not used 1VCC
Supply voltage +5V (termination)
2A (N)
Receive/transmit data A-line (N)
2A (N)
Receive/transmit data A-line (N)
3 N.C. Not used 3 GND Data reference potential
4B (P)
Receive/transmit data B-line (P)
4B (P)
Receive/transmit data B-line (P)
5SHIELDShield or functional earth 5SHIELDShield or functional earth
Thread FE Functional earth (housing) Thread FE Functional earth (housing)
Device parameters and interfaces
N.C.
3
FE
BUS IN
A (N)
2
5
4
B (P)
N.C.
1
VCC
BUS OUT
A (N)
2
1
5
4
B (P)
GND
3
FE
Figure 8.2: PROFIBUS - Electrical connection
Notice!
For connecting BUS IN and BUS OUT we recommend our ready-made PROFIBUS cables (see chapter 10.8 "Accessory ready-made cables for interface connection" on page 103).
TNT 35/7-24V
Attention!
The laser measurement system can be used to branch out the PROFIBUS network. The continuing network is connected via BUS OUT. If the laser measurement system is the last subscriber in the network, the BUS OUT con­nection must be connected to a terminator plug, see "Accessory PROFIBUS terminating re­sistor" on page 102.
Leuze electronic AMS 200 39
Device parameters and interfaces

8.1.3 PROFIBUS address

Notice!
For basic operation of the display please refer to chapter 6.3.2. To set the address parameter enabling must be activated. The display is inverted.
Attention!
The laser measurement system is deactivated on the PROFIBUS when parameter enabling is activated via the display. The device is reactivated on the PROFIBUS after parameter en­abling is exited.
The PROFIBUS-DP address is entered via the display.
To do this proceed as follows:
Enable parameter handling.
ª
ª
Select the PROFIBUS submenu (figure 8.3).
ª
Select the Address [ ] menu item (figure 8.3).
ª
Enter the PROFIBUS address of the laser measurement system; set to a value between 1 and 126 (default: 126, figure 8.3).
ª
Reset parameter enabling.
40 AMS 200 Leuze electronic
Device parameters and interfaces
Make entry with the buttons
Use ’save’ to conclude address entry
ESC
ESC
ESC
ESC
Figure 8.3: Setting the PROFIBUS address
Leuze electronic AMS 200 41
TNT 35/7-24V
Device parameters and interfaces

8.1.4 General information on the GSD file

If the AMS 200… is operated in a PROFIBUS network, configuration must be performed exclusively via the PROFIBUS. The functionality of the laser measurement system is defined via modules. The parameters and their functions are structured in the GSD file using modules. A user-specific configuration tool is used during PLC program creation to integrate the required modules and configure them appropriately for the measurement application.
During operation of the laser measurement system on the PROFIBUS all parameters are set to default values. If these parameters are not changed by the user, the device functions using the default settings supplied by Leuze electronic. For the default settings of the device please refer to the following module descriptions.
Notice!
A least one module in the GSD file must be activated in the configuration tool for the control, usually the Position value module.
Notice!
Some controls make available a so-called "universal module". This module must not be ac­tivated for the AMS 200…
Attention!
The AMS 200… makes available a PROFIBUS, an SSI and an RS 232 interface. All inter­faces can be operated in parallel. If the laser is operated via the PROFIBUS, the SSI/RS 232 parameters must also be changed via the PROFIBUS/SSI/RS 232 modules if they differ from the default settings. SSI/RS 232 parameters which are only changed via the display are overwritten by the PROFIBUS manager with the SSI/RS 232 default values stored in the GSD file.
Notice!
For test purposes parameters can be changed via the display on a laser measurement sys­tem operated on the PROFIBUS. As soon as parameter enabling is activated on the display, the device is deactivated on the PROFIBUS. All parameters set via PROFIBUS modules re­main effective. Parameter changes can now be made via the display for test purposes. If pa­rameter enabling is deactivated via the display, only the parameters set in the PROFIBUS modules and the PROFIBUS default settings are in effect.
Parameter changes made via the display are no longer in effect on the PROFIBUS!
Attention!
The laser measurement system does not permanently store parameters changed via the PROFIBUS. Following Power OFF/ON the currently configured parameters are downloaded by the PROFIBUS manager. If no PROFIBUS manager is available following Power OFF/ ON, the parameters set on the display apply.
42 AMS 200 Leuze electronic
Notice! All input and output modules described in this documentation are described from the per-
spective of the control: Described inputs (I) are inputs of the control. Described outputs (O) are outputs of the control. Described parameters (P) are parameters of the GSD file in the control.
Notice!
The current GSD file for the AMS 200… can be found on our homepage under:
www.leuze.com -> Download -> Identify -> Optical distance measuring and positioning ->
GSD files AMS 200

8.1.5 Overview of the GSD modules

Device parameters and interfaces
Module Module name Module contents
(I) Position value
(P) = Parameter, (O) = Output, (I) = Input
(P) Sign
M1
page 46
Position value
(P) Unit (P) Resolution (P) Count direction (P) Offset
M2
page 48
M3
page 49
Static preset
Dynamic preset
(P) Preset value (O) Preset teach (O) Preset reset (O) Preset value (O) Preset teach (O) Preset reset (P) Output or input defined (P) Level/edge input/output
M4
page 50
I/O 1
(P) Function for output wiring (P) Function for input wiring (I) Signal level input/output (O) Output activated (P) Output or input defined (P) Level/edge input/output
M5
page 53
I/O 2
(P) Function for output wiring (P) Function for input wiring (I) Signal level input/output (O) Output activated
M6
page 56
M7
page 58
M8
page 59
Status and control
Position limit value 1 (P) Upper and lower position limit value
Position limit value 2 (P) Upper and lower position limit value
(I) Diagnosis and status of AMS 200 (O) Laser control ON/OFF
TNT 35/7-24V
Leuze electronic AMS 200 43
Device parameters and interfaces
M9
page 60
M10
page 62
M11
page 64
M12
page 66
M13
page 68
M14
page 70
M15
page 72
M16
page 73
M17
page 75
Error handling
procedures
Velocity
Velocity
Limit value 1
Velocity
Limit value 2
Velocity
Limit value 3
Velocity
Limit value 4
Velocity
Limit value
Dynamic
Velocity status (I) Status of velocity monitoring
SSI interface
(P) Position value in case of error (P) Position error message delay ON/OFF (P) Position error message delay (P) Velocity value in case of error (P) Velocity error message delay ON/OFF (P) Velocity error message delay (I) Velocity value (P) Velocity value resolution (P) Velocity integration time (P) Monitoring for over/under values (P) Monitoring direction dependent yes/no (P) Velocity limit value 1 (P) Hysteresis of velocity limit value (P) Start of velocity monitoring range (P) End of velocity monitoring range (P) Monitoring for over/under values (P) Monitoring direction dependent yes/no (P) Velocity limit value 2 (P) Hysteresis of velocity limit value (P) Start of velocity monitoring range (P) End of velocity monitoring range (P) Monitoring for over/under values (P) Monitoring direction dependent yes/no (P) Velocity limit value 3 (P) Hysteresis of velocity limit value (P) Start of velocity monitoring range (P) End of velocity monitoring range (P) Monitoring for over/under values (P) Monitoring direction dependent yes/no (P) Velocity limit value 4 (P) Hysteresis of velocity limit value (P) Start of velocity monitoring range (P) End of velocity monitoring range (O) Release/lock limit value control (P) Monitoring for over/under values (P) Monitoring direction dependent yes/no (O) Dynamic velocity limit value (O) Hysteresis of velocity limit value (O) Start of velocity monitoring range (O) End of velocity monitoring range
(P) Gray/Binary coding (P) Number of data bits (P) Resolution (P) Update rate (P) Function of the error bit
44 AMS 200 Leuze electronic
(P) Display language selection
a
zabdd
M18
page 78
M19
page 79
Table 8.4: Overview of the GSD modules
Other
RS 232 interface
(P) Display illumination (P) Display contrast (P) Activate/inhibit password (P) Password (P) Address (P) Baud rate (P) Format (P) Output cycle (P) Position resolution (P) Velocity resolution

8.1.6 Detail description of the modules

Notice!
In the following detailed descriptions of the modules you will find in the last column of the tables cross references (CR) to parameters and input/output data of other modules which are directly related to the described parameter. These cross references must abso­lutely be observed during configuration.
Device parameters and interfaces
The individual modules are numerically labelled from 1 … 18. The parameters and input/output data within a module are alphanumerically labelled from … .
Example:
The preset parameter in module 2 becomes active only when the preset teach occurs via module 2 , 4
Leuze electronic AMS 200 45
or 5.
TNT 35/7-24V
Device parameters and interfaces
a
bcd
0m +100m
8.1.6.1 Module 1: Position value
Description
Outputs the current position value.
The parameters for sign, unit, resolution, count direction and offset remain adjustable.
Parameter
Parameter Description Rel.
Output mode of the sign.
Sign
Measure­ment unit
Resolution
Count direction
Sign affects position and velocity output.
Selection of the measurement
1)
unit
. The parameter applies to all val­ues with measurement units. The parameter applies to all interfaces. Resolution of the position value applies only to the PROFIBUS output. The resolution does not apply to:
- Static preset
- Dynamic preset
- Offset
The SSI interface has a separate parameter for the resolution.
Count direction positive
Count direction negative
0m
The parameter applies to all interfaces. The count direction changes the sign during velocity measure­ment. For the SSI interface, no negative position values can be trans­ferred. In this case, the value 0 is output at the SSI interface. A suitable offset is to be selected so that only positive values are transferred.
-
addr.
100m
Data
type
0.0 Bit
0.1 Bit
0.2 …
0.4
0.5 Bit
0: two's complement
1: sign + quantity
0: metric
1: inch (in)
001=1: 0.001 010=2: 0.01
Bit
011=3: 0.1
100=4: 1
101=5: 10
0: positive
1: negative
Val ue Default Unit CR to
metr. inch
0 ––
0 ––
4 mm in/100
0 ––
module
46 AMS 200 Leuze electronic
Output value=measurement
e
f
value+offset. The parameter applies to all interfaces. Attention: If the preset is activated, it has priority over the offset. Preset and offset are not offset against
Offset
Parameter length: 6 bytes
each other. The resolution of the offset value is independent of the resolution selected in module 1. The entered offset applies imme­diately without any further release.
1) see following notice!
Notice! If the unit of measurement is changed from metric to inch (or vice versa), previously
entered numerical values (e.g. for offset, preset, limit values etc.) are not automatically converted. This must be performed manually!
1 - 4
Device parameters and interfaces
sign
-999999 … +999999 0 mm in/100
32 bit
Example: Preset = 10000 mm -> Change from metric to inch -> Preset = 10000 inch/100
Hex coding of the "position value" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
Sign
Unit
Resolution
Count direction
01 10 00 00 00 00
Input data
Input data Description Rel.
Position value
Input data length: 4 bytes consistently
Output of the current position. 0
addr.
Output data
none
Offset
Data type
sign
32 bit
Value Default Unit CR to
-999999 … +999999 scaled 9a
metr. inch
TNT 35/7-24V
module
Leuze electronic AMS 200 47
Device parameters and interfaces
a
b
c
8.1.6.2 Module 2: Static preset
Description
With this module, a preset value can be specified. The specified preset value becomes active in the position in which preset teaching is performed.
Notice!
In the event of a device change the preset value is retained in the PROFIBUS manager. The activation of the preset value (preset teach) at the intended position must, however, be per­formed again.
Parameter
Parameter Description Rel.
Preset value. The value is accepted during a corresponding teach event (see output data).
Preset
Parameter length: 4 bytes
The parameter applies to all interfaces. The resolution of the preset value is independent of the resolution selected in module 1.
addr.
Hex coding of the "preset value" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
Preset value
02 00 00 00 00
Input data
none
Output data
Output
data
Preset teach
Preset reset
Output data length: 1 byte
Read in the preset value. 0.0 Bit 0Æ1 Preset teach
Preset value is deactivated. 0.1 Bit 0Æ1 Preset reset
Description Rel.
addr.
Data
type
sign
0
32 bit
Data
type
Val ue Default Unit CR to
metr. inch
-999999 … +999999 0 mm
Val ue Default Unit CR to
metr. inch
in/
100
module
2b 4d 5d
module
4d 5d
4d 5d
48 AMS 200 Leuze electronic
8.1.6.3 Module 3: Dynamic preset
abc
Description
With this module, a preset value can be specified. The specified preset value becomes active in the position in which preset teaching is performed. The preset value can be adjusted within the control to meet plant requirements without intervening in the static parameter structure.
Parameter
none
Input data
none
Output data
Device parameters and interfaces
Output
data
Preset teach
Preset reset
Preset
Output data length: 5 bytes
Description Rel.
Read in the preset value. 0.0 Bit 0Æ1 Preset teach
Preset value is deactivated. Output value=measurement value+offset.
The value is accepted during a corresponding teach event, The output data apply to all inter­faces. The resolution of the pre­set value is independent of the resolution selected in module 1.
Data
addr.
type
0.1 Bit 0Æ1 Preset reset
sign
1
32 bit
Value Default Unit CR to
metr. inch
-999999 … +999999 mm in/1003a4d
modul
e
4d 5d
4d 5d
5d
TNT 35/7-24V
Leuze electronic AMS 200 49
Device parameters and interfaces
a
b
c
8.1.6.4 Module 4: I/O 1 Input/Output
Description
The module defines the mode of operation of the digital input/output I/O 1.
Parameter
Parameter Description Rel.
The parameter defines whether
Function
Activation
Output
I/O 1 functions as an input or as
an output. The parameter defines the level
of the output when the "output" event is received. If I/O 1 is con­figured as an input, the response is edge-controlled. The parameter defines which event triggers activation of the output. The individual functions are OR-linked to one another.
Position limit value 1
If the position value lies outside of configured limit range 1, the output is set.
Position limit value 2
If the position value lies outside of configured limit range 2, the output is set.
Velocity limit value
If the velocity value lies outside of the configured values, the output is set. Monitoring from modules 11 to 15 is OR-linked.
Intensity (ATT)
If the intensity of the received signal is less than the warning threshold, the output is set.
Temperature (TMP)
If the internal device temperature exceeds the set limit value, the output is set.
Laser (LSR)
Laser prefailure message.
Plausibility (PLB)
If implausible measurement val­ues are diagnosed, the output is set.
addr.
Data
type
0.0 Bit
0.1 Bit
1.0 Bit
1.1 Bit
1.2 Bit
1.3 Bit
1.4 Bit
1.5 Bit
1.6 Bit
Val ue Default Unit CR to
metr. inch
0: Input
1: Output
0: Low
1-0 transition
1: High
0-1 transition
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
1 –4cd
0 ––
0
0
0
0
0
0
1
module
4a
50 AMS 200 Leuze electronic
Device parameters and interfaces
c
d
Hardware (ERR)
If a hardware error is diagnosed,
Output
Input
Parameter length: 4 bytes
the output is set.
Pseudodynamic output
If bit 0.0 is set in the output data, the output is set.
Preset
The HW input is used as preset teach input (valid for static or dynamic preset).
Laser
The HW input is used as laser OFF.
Hex coding of the "I/O 1 input/output" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
04 01 00 C0 00
Function
Activation
Position limit value 1
1.7 Bit
2.0 Bit
3.0
3.2
Position limit value 2
Velocity limit value
Intensity (ATT)
0 = OFF
1 = ON 0 = OFF
1 = ON
000 = HW input no
Unsig
001 = HW input as pre-
n8Bit
010 = HW input as laser
Temperature (TMP)
Laser (LSR)
Plausibility (PLB)
Hardware (ERR)
Pseudodynamic output
function
set teach function
OFF function
Input Preset / Laser
1
4a
0
000 –4a
Notice!
Behaviour of the AMS 200 on laser ON/OFF:
TNT 35/7-24V
If the laser light spot is positioned on the reflector when the laser diode is switched on, the AMS 200 returns valid measurement values after approx. 330 ms.
If the laser light spot is not positioned on the reflector when the laser diode is switched on, the AMS 200 cannot calculate any distance values. If the laser beam hits the reflector at a later point in time while switched-on, the AMS 200 returns valid measurement values after the following time span:
t = (measurement distance / 20 m) sec.
Example: Corridor change of a high-bay storage device during which the laser diode is not
switched off while travelling around curves. Measurement distance 100 m –> t = 5 sec., measurement distance 200 m –> t = 10 sec.
Leuze electronic AMS 200 51
Device parameters and interfaces
e
f
Input data
Input data Description Rel.
Signal state of the input or out-
State
Input data length: 1 byte
put.
addr.
Output data
Output
data
The output can be activated/ deactivated with this bit. The cor-
State
Output data length: 1 byte
responding release is performed in module 4, output parameter bit 2.0.
Description Rel.
addr.
Data
type
0.0 Bit
Data
type
0.0 Bit
Val ue Default Unit CR to
0: Input/Output at sig-
nal level not active
1: Input/Output at sig-
nal level active
Val ue Default Unit CR to
0: Output at signal level
not active
1: Output at signal level
active
metr. inch
––
metr. inch
–4c
module
module
52 AMS 200 Leuze electronic
8.1.6.5 Module 5: I/O 2 Input/Output
a
b
c
Description
The module defines the mode of operation of the digital input/output I/O 2.
Parameter
Device parameters and interfaces
Parameter Description Rel.
The parameter defines whether
Function
Activation
Output
I/O 2 functions as an input or as
an output. The parameter defines the level
of the output when the "output" event is received. If I/O 2 is con­figured as an input, the response is edge-controlled. The parameter defines which event triggers activation of the output. The individual functions are OR-linked to one another.
Position limit value 1
If the position value lies outside of configured limit range 1, the output is set.
Position limit value 2
If the position value lies outside of configured limit range 2, the output is set.
Velocity limit value
If the velocity value lies outside of the configured values, the output is set. Monitoring from modules 11 to 15 is OR-linked.
Intensity (ATT)
If the intensity of the received signal is less than the warning threshold, the output is set.
Temperature (TMP)
If the internal device temperature exceeds the set limit value, the output is set.
Laser (LSR)
Laser prefailure message.
Plausibility (PLB)
If implausible measurement val­ues are diagnosed, the output is set.
addr.
Data type
0.0 Bit
0.1 Bit
1.0 Bit
1.1 Bit
1.2 Bit
1.3 Bit
1.4 Bit
1.5 Bit
1.6 Bit
Value Default Unit CR to
metr. inch
0: Input
1: Output
0: Low
1-0 transition
1: High
0-1 transition
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = ON
1 –5cd
0 ––
0
0
0
1
1
1
0
module
5a
TNT 35/7-24V
Leuze electronic AMS 200 53
Device parameters and interfaces
c
d
Hardware (ERR)
If a hardware error is diagnosed,
Output
Input
Parameter length: 4 bytes
the output is set.
Pseudodynamic output
If bit 0.0 is set in the output data, the output is set.
Preset
The HW input is used as preset teach input (valid for static or dynamic preset).
Laser
The HW input is used as laser OFF.
Hex coding of the "I/O 2 input/output" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
05 01 00 38 00
Function
Activation
Position limit value 1
1.7 Bit
2.0 Bit
3.0 …
3.2
Position limit value 2
Velocity limit value
Intensity (ATT)
Temperature (TMP)
0 = OFF
1 = ON
0 = OFF
1 = ON
000 = HW input no
001 = HW input as pre-
Unsign
8Bit
010 = HW input as
Laser (LSR)
Plausibility (PLB)
Hardware (ERR)
Pseudodynamic output
function
set teach func­tion
laser OFF func­tion
Input Preset / Laser
0
5a
0
000 –5a
Notice!
Behaviour of the AMS 200 on Laser ON/OFF:
If the laser light spot is positioned on the reflector when the laser diode is switched on, the AMS 200 returns valid measurement values after approx. 330 ms.
If the laser light spot is not positioned on the reflector when the laser diode is switched on, the AMS 200 cannot calculate any distance values. If the laser beam hits the reflector at a later point in time while switched-on, the AMS 200 returns valid measurement values after the following time span:
t = (measurement distance / 20 m) sec.
Example: Corridor change of a high-bay storage device during which the laser diode is not
switched off while travelling around curves. Measurement distance 100 m –> t = 5 sec., measurement distance 200 m –> t = 10 sec.
54 AMS 200 Leuze electronic
Input data
e
f
Device parameters and interfaces
Input data Description Rel.
Signal state of the input or out-
State
Input data length: 1 byte
put.
addr.
Output data
Output
data
State
Output data length: 1 byte
Description Rel.
The output can be activated/ deactivated with this bit. The cor­responding release is performed in module 5, output parameter bit 2.0.
addr.
Data type
0.0 Bit
Data type
0.0 Bit
Value Default Unit CR to
0: Input/Output at sig-
nal level not active
1: Input/Output at sig-
nal level active
Value Default Unit CR to
0: Output at signal level
not active
1: Output at signal level
active
metr. inch
––
metr. inch
–5c
module
module
TNT 35/7-24V
Leuze electronic AMS 200 55
Device parameters and interfaces
abcde
f
g
h
i
j
k
8.1.6.6 Module 6: Status and control
Description
This module supplies various AMS 200… status information to the PROFIBUS master. The laser can be controlled via the master's output data.
Parameter
none
Input data
Input data Description Rel.
Laser status
Preset status
Preset teach
Overflow
Intensity (ATT)
Tempera­ture (TMP)
Laser (LSR)
Plausibility (PLB)
Hardware (ERR)
Lower posi­tion limit value 1
Upper posi­tion limit value 1
Signals the laser status. 1.0 Bit
Status of the preset value. 1.1 Bit
This bit toggles on each teach event of a preset value.
The output value has exceeded the maximum value which can be represented by the SSI inter­face. In the event of an overflow the SSI interface data are set to 0xFF.
If the intensity of the received signal is less than the warning threshold, the status bit is set.
If the internal device tempera­ture exceeds or drops below the set limit value, the status bit is set.
Laser prefailure message. 1.6 Bit
If implausible measurement val­ues are diagnosed, the status bit is set.
If a hardware error is diagnosed, the status bit is set.
Signals that the value is less than lower limit value 1.
Signals that the value is greater than upper limit value 1.
Data
addr.
type
1.2 Bit 0 or 1 ––
1.3 Bit
1.4 Bit
1.5 Bit
1.7 Bit
0.0 Bit
0.4 Bit
0.5 Bit
Val ue Default Unit CR to
0: Laser ON
1: Laser OFF 0: Preset not active
1: Preset active
0: OK
1: Overflow
0: OK
1: Warning 0: OK
1: Temperature above/
below limit
0: OK
1: Laser warning 0: OK
1: Implausible meas-
urement value
0: OK
1: Hardware error
0: OK
1: Value less than limit
0: OK
1: Value greater than
limit
metr. inch
––
––
––
––
––
––
––
––
––
––
module
56 AMS 200 Leuze electronic
Device parameters and interfaces
l
m
n
Lower posi­tion limit value 2
Upper posi­tion limit value 2
Input data length: 2 bytes
Signals that the value is less than lower limit value 2.
Signals that the value is greater than upper limit value 2.
0.6 Bit
0.7 Bit
Output data
Output data Description Rel.
Laser
Output data length: 2 bytes
Controls the laser. 0.0 Bit
addr.
0: OK
1: Value less than limit
0: OK
1: Value greater than
limit
Data type
0: Laser ON
1: Laser OFF
––
––
Value Default Unit CR to
metr. inch
––
module
TNT 35/7-24V
Leuze electronic AMS 200 57
Device parameters and interfaces
a
b
8.1.6.7 Module 7: Position limit value range 1
Description
The position limit value range 1 parameter defines a distance range with lower and upper limits. If the measured value lies outside of the configured range, the corresponding bit is set in module 6 or, if configured, an output is set.
Parameter
Parameter Description Rel.
Lower pos. limit 1
Upper pos. limit 1
Parameter length: 8 bytes
Specifies the lower position limit.
Specifies the upper position limit.
addr.
0…3
4…7
Hex code of the "position limit value range 1" parameter
The value listed in this table shows the hex coding of the default settings:
pos. limit 1
Module address
Lower
07 00 00 00 00 00 00 00 00
Input data
none
Output data
none
Data
type
sign
32 bit
sign
32 bit
pos. limit 1
Upper
Val ue Default Unit CR to
-999999 … +999999 0 mm
-999999 … +999999 0 mm
metr. inch
in/
100
in/
100
module
58 AMS 200 Leuze electronic
8.1.6.8 Module 8: Position limit value range 2
a
b
Description
The position limit value range 2 parameter defines a distance range with lower and upper limits. If the measured value lies outside of the configured range, the corresponding bit is set in module 6 or, if configured, an output is set.
Parameter
Device parameters and interfaces
Parameter Description Rel.
Lower pos. limit 2
Upper pos. limit 2
Parameter length: 8 bytes
Specifies the lower position limit.
Specifies the upper position limit.
addr.
0…3
4 … 7sign
Hex code of the "position limit value range 2" parameter
The value listed in this table shows the hex coding of the default settings:
pos. limit 2
Module address
Lower
08 00 00 00 00 00 00 00 00
Input data
none
Output data
none
Data type
sign
32 bit
32 bit
pos. limit 2
Upper
Value Default Unit CR to
-999999 … +999999 0 mm
-999999 … +999999 0 mm
metr. inch
in/
100
in/
100
module
TNT 35/7-24V
Leuze electronic AMS 200 59
Device parameters and interfaces
abc
def
8.1.6.9 Module 9: Error handling procedures
Description
The module makes parameters available to handle any errors should they occur.
In the event of a temporary error in the value/velocity calculation (e.g. plausibility error caused by light beam interruption) the laser measurement system transmits the last valid measurement value for a length of time xx which is to be configured.
If the configured time is exceeded, the error display or the faulty measurement value output is activated.
Parameter
Parameter Description Rel.
Specifies which position value is
Position value in the case of error
Suppress position status
Error delay (position)
Error delay time (posi­tion)
Velocity in the case of error
Suppress velocity status
to be output in the event of an error after the position suppres­sion time has elapsed.
No function. 0.1 Bit Always 0 0 –– Specifies whether the PLB sta­tus bit is set immediately in the event of an error or if it is sup­pressed for the configured posi­tion suppression time. Specifies in the event of an error whether the position value immediately outputs the value of the "position value in the case of error" parameter or outputs the last valid position value for the duration of the configured "error delay time". Errors which occur are sup­pressed for the configured time. If no valid position value can be ascertained during the config­ured time, the last valid position value is output. If the error per­sists after the time elapses, the value stored in the "position value in the case of error" parameter is output. Specifies which velocity is to be output in the event of an error after the velocity suppression time has elapsed. No function. 3.1 Bit Always 0 0 –– Specifies whether the PLB sta­tus bit is set immediately in the event of an error or if it is sup­pressed for the configured velocity suppression time.
addr.
1…2
Data
type
0.0 Bit
0.2 Bit
0.3 Bit
unsign
16 bit
3.0 Bit
3.2 Bit
Val ue Default Unit CR to
metr. inch
0: Last valid value
1: Zero
0: OFF
1: ON
0: OFF
1: ON
100 … 1000 100 ms
0: Last valid value
1: Zero
0: OFF
1: ON
1 mm
1 ––
1 ––
1 ––
1 ––
in/
100
module
60 AMS 200 Leuze electronic
Specifies in the event of an error
g
h
whether the velocity immedi­ately outputs the value of the
Error delay (velocity)
Error delay time (velocity)
Parameter length: 6 bytes
"velocity in the case of error" parameter or outputs the last valid velocity for the duration of the configured "error delay time". Errors which occur are sup­pressed for the configured time. If no velocity position value can be ascertained during the con­figured time, the last valid veloc­ity value is output. If the error persists after the time elapses, the value stored in the "velocity in the case of error" parameter is output.
Hex code of the "Error handling procedures" parameter (position and velocity)
The value listed in this table shows the hex coding of the default settings:
3.3 Bit
unsign
4…5
16 bit
Device parameters and interfaces
0: OFF
1: ON
200 … 1000 200 ms
1 ––
Module address
Position value in the case of error
Suppress position status
Error delay (position)
Position suppression time
09 C0 00 64 C0 00 C8
Velocity output in the case of error
Suppress velocity status
Error delay (velocity)
Velocity suppression time
TNT 35/7-24V
Input data
none
Output data
none
Leuze electronic AMS 200 61
Device parameters and interfaces
a
b
8.1.6.10 Module 10: Velocity
Description
Outputs the current velocity with the configured resolution. The unit (metric or inch) is set in module 1 (position value) and also applies to the velocity. If module 1 is not configured, the AMS 200… operates with the default unit (metric).
The sign of the velocity is dependent on the count direction in module 1d.
In the default setting a positive velocity is output when the reflector moves away from the AMS 200… When the reflector moves towards the AMS 200…, negative velocities are output. If the "negative" count direction is configured in module 1, the velocity signs are reversed.
Measurement value preparation averages all velocity values calculated during the selected period to yield a velocity value.
Parameter
Parameter Description Rel.
Velo city resolution
Average
Parameter length: 2 bytes
The parameter specifies the res­olution for the velocity value.
The parameter specifies the inte­gration time (averaging time) of the calculated velocity values.
addr.
0.0…
Hex coding of the "velocity" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
0A 00 19
Velocity resolution
Average
0.2
0.3
0.5
Data
type
Bit
Bit
Val ue Default Unit CR to
metr. inch
001=1: 1
010=2: 10 011=3: 100 100=4: 1000
000=0: 2 001=1: 4 010=2: 8
011=3: 16
100=4: 32 101=5: 64 110=6: 128
1 mm/s
3 ms
module
(in/
100)/s–
62 AMS 200 Leuze electronic
Input data
c
Device parameters and interfaces
Input data Description Rel.
Vel ocit y
Input data length: 4 bytes consistently
Current velocity 0
addr.
Output data
none
Data type
sign
32 bit
Value Default Unit CR to
metr. inch
-999999 … +999999 0 scaled
module
TNT 35/7-24V
Leuze electronic AMS 200 63
Device parameters and interfaces
a
bcdef
8.1.6.11 Module 11: Static velocity limit value 1
Description
The static velocity limit value 1 function compares the current velocity with a velocity stored in the configuration. This occurs in the configured range, which is defined by range
start and range end.
Notice!
If range start and range end are identical, velocity monitoring is not activated.
If a direction-dependent limit value check is activated via the direction selection parameter, the values of range start and range end also define the direction. The check is always performed from range start to range end. For example, if the range start is "5500" and the range end is "5000", the direction-dependent check is only performed in the direction from "5500" to "5000". The limit value is not active in the opposite direction.
If the check is independent of direction, the order of range start and range end is irrelevant. Depending on the selected switching mode, if the value is above or below the defined limits, the limit value status in module 16 is set and, if configured, the output is appropriately set via module 4 or 5.
Parameter
Parameter Description Rel.
Condition for the "velocity limit
Switching mode
Direction selection
Velo city limit value 1
Velo city hysteresis 1
Limit value 1 range start
Limit value 1 range end
Parameter length: 13 bytes
value 1" signal, which applies to the output (module 4/5) and the status bit (module 16).
Selection of direction-depend­ent or direction-independent limit value checking.
Limit value is compared to the current velocity.
Relative shift to prevent signal bouncing.
The velocity limit value is moni­tored beginning at this position.
The velocity limit value is moni­tored up to this position.
addr.
0.0 Bit
0.1 Bit
1…2
3…4
5…8
9 … 12
Data
type
unsign
16 bit
unsign
16 bit
sign
32 bit
sign
32 bit
Val ue Default Unit CR to
0: Value greater than
limit
1: Value less than limit
0: Direction inde-
pendent
1: Direction dependent
0 … 20000 0 mm/s
0 … 20000 100 mm/s
-999999 … +999999 0 mm
-999999 … +999999 0 mm
metr. inch
0 ––
0 ––
module
(in/
100)/s16d
(in/
100)/s–
in/
100
in/
100
64 AMS 200 Leuze electronic
Device parameters and interfaces
Hex code of the "static velocity limit value 1" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
Switching mode
Direction selection
Velocity limit value 1
Velocity hysteresis 1
Limit value 1 range start
0B 00 00 00 00 64 00 00 00 00 00 00 00 00
Input data
none
Output data
none
Limit value 1 range end
TNT 35/7-24V
Leuze electronic AMS 200 65
Device parameters and interfaces
a
bcdef
8.1.6.12 Module 12: Static velocity limit value 2
Description
The static velocity limit value 2 function compares the current velocity with a velocity stored in the configuration. This occurs in the configured range, which is defined by range
start and range end.
Notice!
If range start and range end are identical, velocity monitoring is not activated.
If a direction-dependent limit value check is activated via the direction selection parameter, the values of range start and range end also define the direction. The check is always performed from range start to range end. For example, if the range start is "5500" and the range end is "5000", the direction-dependent check is only performed in the direction from "5500" to "5000". The limit value is not active in the opposite direction.
If the check is independent of direction, the order of range start and range end is irrelevant. Depending on the selected switching mode, if the value is above or below the defined limits, the limit value status in module 16 is set and, if configured, the output is appropriately set via module 4 or 5.
Parameter
Parameter Description Rel.
Condition for the "velocity limit
Switching mode
Direction selection
Velo city limit value 2
Velo city hysteresis 2
Limit value 2 range start
Limit value 2 range end
Parameter length: 13 bytes
value 2" signal, which applies to the output (module 4/5) and the status bit (module 16).
Selection of direction-depend­ent or direction-independent limit value checking.
Limit value is compared to the current velocity.
Relative shift to prevent signal bouncing.
The velocity limit value is moni­tored beginning at this position.
The velocity limit value is moni­tored up to this position.
addr.
0.0 Bit
0.1 Bit
1…2
3…4
5…8
9 … 12
Data
type
unsign
16 bit
unsign
16 bit
sign
32 bit
sign
32 bit
Val ue Default Unit CR to
0: Value greater than
limit
1: Value less than limit
0: Direction inde-
pendent
1: Direction dependent
0 … 20000 0 mm/s
0 … 20000 100 mm/s
-999999 … +999999 0 mm
-999999 … +999999 0 mm
metr. inch
0 ––
0 ––
module
(in/
100)/s16e
(in/
100)/s–
in/
100
in/
100
66 AMS 200 Leuze electronic
Device parameters and interfaces
Hex code of the "static velocity limit value 2" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
Switching mode
Direction selection
Velocity limit value 2
Velocity hysteresis 2
Limit value 2 range start
0C 00 00 00 00 64 00 00 00 00 00 00 00 00
Input data
none
Output data
none
Limit value 2 range end
TNT 35/7-24V
Leuze electronic AMS 200 67
Device parameters and interfaces
a
bcdef
8.1.6.13 Module 13: Static velocity limit value 3
Description
The static velocity limit value 3 function compares the current velocity with a velocity stored in the configuration. This occurs in the configured range, which is defined by range
start and range end.
Notice!
If range start and range end are identical, velocity monitoring is not activated.
If a direction-dependent limit value check is activated viathe direction selection parameter, the values of range start and range end also define the direction. The check is always performed from range start to range end. For example, if the range start is "5500" and the range end is "5000", the direction-dependent check is only performed in the direction from "5500" to "5000". The limit value is not active in the opposite direction.
If the check is independent of direction, the order of range start and range end is irrelevant. Depending on the selected switching mode, if the value is above or below the defined limits, the limit value status in module 16 is set and, if configured, the output is appropriately set via module 4 or 5.
Parameter
Parameter Description Rel.
Condition for the "velocity limit
Switching mode
Direction selection
Velo city limit value
3
Velo city hysteresis
3
Limit value 3 range start
Limit value 3 range end
Parameter length: 13 bytes
value 3" signal, which applies to the output (module 4/5) and the status bit (module 16).
Selection of direction-depend­ent or direction-independent limit value checking.
Limit value is compared to the current velocity.
Relative shift to prevent signal bouncing.
The velocity limit value is moni­tored beginning at this position.
The velocity limit value is moni­tored up to this position.
addr.
0.0 Bit
0.1 Bit
1…2
3…4
5…8
9 … 12
Data
type
unsign
16 bit
unsign
16 bit
sign
32 bit
sign
32 bit
Val ue Default Unit CR to
0: Value greater than
limit
1: Value less than limit
0: Direction inde-
pendent
1: Direction dependent
0 … 20000 0 mm/s
0 … 20000 100 mm/s
-999999 … +999999 0 mm
-999999 … +999999 0 mm
metr. inch
0 ––
0 ––
module
(in/
100)/s16f
(in/
100)/s–
in/
100
in/
100
68 AMS 200 Leuze electronic
Device parameters and interfaces
Hex code of the "static velocity limit value 3" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
Switching mode
Direction selection
Velocity limit value 3
Velocity hysteresis 3
Limit value 3 range start
0D 00 00 00 00 64 00 00 00 00 00 00 00 00
Input data
none
Output data
none
Limit value 3 range end
TNT 35/7-24V
Leuze electronic AMS 200 69
Device parameters and interfaces
a
bcdef
8.1.6.14 Module 14: Static velocity limit value 4
Description
The static velocity limit value 4 function compares the current velocity with a velocity stored in the configuration. This occurs in the configured range, which is defined by range
start and range end.
Notice!
If range start and range end are identical, velocity monitoring is not activated.
If a direction-dependent limit value check is activated via the direction selection parameter, the values of range start and range end also define the direction. The check is always performed from range start to range end. For example, if the range start is "5500" and the range end is "5000", the direction-dependent check is only performed in the direction from "5500" to "5000". The limit value is not active in the opposite direction.
If the check is independent of direction, the order of range start and range end is irrelevant. Depending on the selected switching mode, if the value is above or below the defined limits, the limit value status in module 16 is set and, if configured, the output is appropriately set via module 4 or 5.
Parameter
Parameter Description Rel.
Condition for the "velocity limit
Switching mode
Direction selection
Velo city limit value 4
Velo city hysteresis 4
Limit value 4 range start
Limit value 4 range end
Parameter length: 13 bytes
value 4" signal, which applies to the output (module 4/5) and the status bit (module 16).
Selection of direction-depend­ent or direction-independent limit value checking.
Limit value is compared to the current velocity.
Relative shift to prevent signal bouncing.
The velocity limit value is moni­tored beginning at this position.
The velocity limit value is moni­tored up to this position.
addr.
0.0 Bit
0.1 Bit
1…2
3…4
5…8
9 … 12
Data
type
unsign
16 bit
unsign
16 bit
sign
32 bit
sign
32 bit
Val ue Default Unit CR to
0: Value greater than
limit
1: Value less than limit
0: Direction inde-
pendent
1: Direction dependent
0 … 20000 0 mm/s
0 … 20000 100 mm/s
-999999 … +999999 0 mm
-999999 … +999999 0 mm
metr. inch
0 ––
0 ––
module
(in/
100)/s16 g
(in/
100)/s–
in/
100
in/
100
70 AMS 200 Leuze electronic
Device parameters and interfaces
Hex code of the "static velocity limit value 4" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
Switching mode
Direction selection
Velocity limit value 4
Velocity hysteresis 4
Limit value 4 range start
0E 00 00 00 00 64 00 00 00 00 00 00 00 00
Input data
none
Output data
none
Limit value 4 range end
TNT 35/7-24V
Leuze electronic AMS 200 71
Device parameters and interfaces
a
bcdef
g
8.1.6.15 Module 15: Dynamic velocity limit value
Description
The dynamic velocity limit value compares the current velocity with a stored velocity within the defined range. If the value is above or below the limit value, the dynamic limit value status in module 16 is set and, if configured, the output is appropriately set. Limit value, hysteresis, range start and range end are transferred with the output data of this module by the PROFIBUS master. The transferred values are activated by Bit 0.0, i.e. if this bit is set, the AMS 200… compares the current velocity with the new limit value conditions.
Notice! If range start and range end are identical, velocity monitoring is not activated.
Parameter
none
Input data
none
Output data
Output
data
Limit value control
Switching mode
Direction selection
Velo city limit value
Velo city hysteresis
Limit value range start
Limit value range end
Output data length: 13 bytes consistently
Description Rel.
Controls internal processing of the transferred dynamic limit value parameters.
Condition for the signal change of the output/status bit.
Selection of direction-depend­ent or direction-independent limit value checking.
Limit value is compared to the current velocity.
Relative shift to prevent signal bouncing.
The velocity limit value is moni­tored beginning at this position.
The velocity limit value is moni­tored up to this position.
addr.
0.0 Bit
0.1 Bit
0.2 Bit
1…2
3…4
5…8
9 … 12
Data
type
unsign
16 bit
unsign
16 bit
sign
32 bit
sign
32 bit
Val ue Default Unit CR to
0: Do not process
1: Process
parameter
0: Value greater than
limit
1: Value less than limit 0: Direction independ-
ent
1: Direction dependent
0 … +20000 mm/s
0 … +20000 mm/s
-999999 … +999999 0 mm
-999999 … +999999 0 mm
metr. inch
––
––
––
module
(in/
100)/s16 h
(in/
100)/s–
in/
100
in/
100
72 AMS 200 Leuze electronic
8.1.6.16 Module 16: Velocity status
abcde
fgh
ijk
Description
This module supplies the PROFIBUS master with various status information for velocity measurement.
Parameter
none
Input data
Device parameters and interfaces
Input data Description Rel.
Vel ocit y measure­ment error
Movement status
Movement direction
Vel ocit y limit value status 1
Vel ocit y limit value status 2
Vel ocit y limit value status 3
Vel ocit y limit value status 4
Dynamic velocity limit value status
Vel ocit y comparison limit value 1
Vel ocit y comparison limit value 2
Vel ocit y comparison limit value 3
Signals that no valid velocity could be ascertained.
Signals whether a movement >0.1 m/s is currently being detected.
When the movement status is activated, this bit indicates the direction.
Signals that limit value 1 has been exceeded.
Signals that limit value 2 has been exceeded.
Signals that limit value 3 has been exceeded.
Signals that limit value 4 has been exceeded.
Signals that the dynamic limit value has been exceeded.
Signals whether the current velocity is compared with this limit value.
Signals whether the current velocity is compared with this limit value.
Signals whether the current velocity is compared with this limit value.
addr.
1.0 Bit
1.1 Bit
1.2 Bit
1.3 Bit
1.4 Bit
1.5 Bit
1.6 Bit
1.7 Bit
0.3 Bit
0.4 Bit
0.5 Bit
Data type
0: OK
1: Error
0: No movement
1: Movement 0: Positive direction
1: Negative direction 0: Limit value
maintained
1: Limit value violated 0: Limit value
maintained
1: Limit value violated 0: Limit value
maintained
1: Limit value violated 0: Limit value
maintained
1: Limit value violated
0: Limit value
maintained
1: Limit value violated
0: Comparison not
active
1: Comparison active 0: Comparison not
active
1: Comparison active 0: Comparison not
active
1: Comparison active
Value Default Unit CR to
metr. inch
––
––
––
11c
12c
–13c
14c
15bd
––
––
––
module
TNT 35/7-24V
Leuze electronic AMS 200 73
Device parameters and interfaces
l
m
Velo city comparison limit value 4
Dynamic velocity comparison
Input data length: 2 bytes
Signals whether the current velocity is compared with this limit value.
Signals whether the current velocity is compared with this limit value.
Output data
none
0.6 Bit
0.7 Bit
0: Comparison not
active
1: Comparison active 0: Comparison not
active
1: Comparison active
––
––
74 AMS 200 Leuze electronic
8.1.6.17 Module 17: SSI interface
Description
The module defines the parameters for the SSI interface.
Attention! The SSI interface can only represent positive distance values. If negative output val-
ues are ascertained due to the offset or count direction, a zero value is output at the SSI interface! In the event of a number overflow, all data bits are set to "1".
The unit, offset and count direction parameters of module 1 also apply to the SSI inter­face.
Notice! If the SSI interface is not configured via module 17 (SSI interface) in PROFIBUS oper-
ation, the SSI interface is deactivated.
If the SSI interface is operated without PROFIBUS (PROFIBUS OFF/SSI ON), configuration is performed via the display.
Device parameters and interfaces
Leuze electronic AMS 200 75
TNT 35/7-24V
Device parameters and interfaces
a
b
cde
Parameter
Parameter Description Rel.
The parameter defines the cod-
Coding
Mode
Resolution
Update rate
Error bit
Attention! The attached error bit always has the follow­ing signifi­cance:
0: No
error
1: Error
Parameter length: 2 bytes
ing of the SSI data.
The parameter defines the number of data bits.
The parameter defines the reso­lution of the SSI position value.
The parameter defines the update rate of the measurement values at the SSI interface. The measurement value is updated independent of the clock fre­quency.
Error bit off/on
The parameter defines the meaning of the error bit. If the error bit = OFF, no bit is attached to the data. The remaining bits 1 to 6 activate the various events which apply to the error bit. The bits are OR­linked to each other.
Overflow
Output value exceeds the maxi­mum value which can be repre­sented. In the event of an overflow, all data bits are set to 1.
Intensity (ATT)
If the intensity of the received signal is less than the warning threshold, the bit is set.
Temperature (TMP)
Maximum internal device tem­perature exceeded.
Laser (LSR)
Laser prefailure message.
Plausibility (PLB)
Plausibility error.
Hardware (ERR)
Hardware error.
addr.
Data
type
0.0 Bit
0.1 …
0.2
0.3
0.5
0.6 Bit
1.0 Bit
1.1 Bit
1.2 Bit
1.3 Bit
1.4 Bit
1.5 Bit
1.6 Bit
Bit
Bit
Val ue Default Unit CR to
0: Binary
1: Gray 00=0: 24Bit
01=1: 25Bit 10=2: 26Bit
001=1: 0.001 010=2: 0.01
011=3: 0.1
100=4: 1 101=5: 10
0: 1.6 ms
1: 0.2 ms
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: ON 0: OFF
1: ON
0: OFF
1: ON
metr. inch
1 ––
0 ––
3 mm
0 ms
1 ––
0 ––
0 ––
0 ––
0 ––
1 ––
1 ––
module
in/
1001b6d
76 AMS 200 Leuze electronic
Device parameters and interfaces
Hex coding of the "SSI interface" parameter
The value listed in this table shows the hex coding of the default settings:
Module address
Coding
Mode
Resolution
Update rate
Error bits
11 19 61
Input data
none
Output data
none
Notice! Resolution and maximum position value which can be represented:
SSI setting Max. distance which can be
24-bit; resolution 0.1 1,677 m 16,777 in 24-bit; resolution 0.01 167 m 1,677 in 24-bit; resolution 0.001 16 m 167 in 25-bit; resolution 0.1 3,355 m 33,554 in 25-bit; resolution 0.01 335 m 3,355 in 25-bit; resolution 0.001 33 m 335 in 26-bit; resolution 0.1 6,710 m 67,108 in 26-bit; resolution 0.01 671 m 6,710 in 26-bit; resolution 0.001 67 m 671 in
represented
Metric
Max. distance which can be
represented
Inches (in)
1,704 m
426 m
42 m
4 m
852 m
85 m
8 m
170 m
17 m
Table 8.5: SSI interface - resolution and maximum position value which can be
represented
Leuze electronic AMS 200 77
TNT 35/7-24V
Device parameters and interfaces
abc
d
e
8.1.6.18 Module 18: Other
Description
Parameters for general operation are set in this module.
Parameter
Parameter Description Rel.
Language selection for the dis­play.
Language selection
Display illumina­tion
Display contrast
Password protection
Password
Parameter length: 4 bytes
A language which was selected via the display is overwritten by this parameter.
Off after 10 min. or always on. 0.3 Bit
Contrast setting of the display. The contrast changes under extreme ambient temperatures and can be adjusted with this parameter.
Password protection on/off. 0.7 Bit
Specifies the password. Password protection must be on.
addr.
1…2
Hex coding of the "other" parameter
The value listed in this table shows the hex coding of the default settings:
0.0
0.2
0.4
0.5
Data
type
Bit
Bit
unsign
16 bit
Val ue Default Unit CR to
000=0: English
001=1: German 010=2: Italian 011=3: Spanish 100=4: French
0: Off after 10 min.
1: Always on
000=0: Weak
001=1: Medium
010=2: Strong
0: OFF
1: ON
0000 … 9999 0000 ––
metr. inch
0 ––
0 ––
1 ––
0 ––
module
Module address
Language
Display illumination
Display contrast
Password protection
Password
12 10 00
Input data
none
Output data
none
78 AMS 200 Leuze electronic
8.1.6.19 Module 19: RS 232 interface
a
b
cde
f
Description
The parameters of the RS 232 interface can be set in this module. The Unit, Offset and Count direction parameters from module 1 also apply to the RS 232 interface.
If module 19 is not configured via the PROFIBUS, i.e. not integrated into the configuration, the RS 232 interface is deactivated by default. If the AMS 200 is operated without PROFIBUS only on the RS 232 interface, the interface must be activated via the display (RS 232 parameter menu item).
Parameter
Device parameters and interfaces
Parameter Description Rel.
Address of the AMS 200 for
Address
Baud rate
Format
Output cycle
Position resolution
Vel ocit y resolution
Parameter length: 4 bytes
serial communication
Transmission rate on the RS 232 interface.
Data format of RS 232 communication.
Output cycle on the RS 232 interface in multiples of the AMS 200 measurement cycle = approx. 1.7 ms.
Resolution of the RS 232 position value.
Resolution of the RS 232 velocity value.
addr.
0.0
0.3
0.4
0.7
1.0
1.3
3.0
3.2
3.3
3.4
Hex coding of the "RS 232 interface" parameter
The value listed in this table shows the hex coding of the default settings:
Module
address
Address
Baud rate
Format
13 90 06 01 0B
Data type
Bit 0 … 15 0 ––
Bit
Bit
unsign
2
8 bit
Bit
Bit
Output
cycle
Value Default Unit CR to
metr. inch
8: 19.2
9: 38.4
10: 57.6 11: 115.2
6: 8, n, 1
8: 8, e, 1 10: 8, o, 1
1 … 20 1 ––
2: 0.01
3:0.1
4: 1 5: 10
1: 1
2: 10 3:100
Position
resolution
Velo city
resolution
9 kBit/s
6 ––
3 mm in/100
mm/s(in/100)
1
/s
module
TNT 35/7-24V
Input data
none
Output data
none
Leuze electronic AMS 200 79
Device parameters and interfaces

8.2 SSI

8.2.1 General information about the transmission procedure

Data communication of the SSI interface is based on differential transmission as used for RS 422 interfaces. Transmission of the position value, beginning with the MSB (most signif­icant bit), is thus synchronised with a clock cycle (CLOCK) specified by the control.
In the quiescent state both the clock line as well as the data line are at HIGH level. At the first HIGH-LOW edge (point it is ensured that the data cannot change during serial transmission.
When the next clock signal change from LOW to HIGH level (point transmission of the position value begins with the most significant bit (MSB). With each successive change of the clock signal from LOW to HIGH level the next least-significant bit is transmitted on the data line. After the least significant bit (LSB) has been output, the clock signal switches from LOW to HIGH for one last time and the data line switches to LOW level (end of transmission).
A monoflop retriggered by the clock signal determines the time span before the SSI interface can be called for the next transmission. This results in the minimum pause time between two successive clock cycles. If time t cent level (HIGH) (point that the device is again ready for transmission.
Notice!
If the off-cycle of data transmission is interrupted for longer than t will begin with a completely new transmission cycle with a newly calculated value.
in figure 8.6) the data in the internal register are stored. Thus
= 20 µs has elapsed, the data line is returned to the quies-
m
in figure 8.6). This signals completed data communication and
in figure 8.6) occurs
= 20 µs, the next cycle
m
If a new transmission cycle is started before time t
has elapsed, the previous value is out-
m
put again.
Attention! The SSI interface can only represent positive distance values. If negative output val-
ues are ascertained due to the offset or count direction, a zero value is output at the SSI interface! In the event of a number overflow, all data bits are set to "1".
80 AMS 200 Leuze electronic
8.2.1.1 SSI sequence diagram
Clock sequence
Complete transmission cycle
Figure 8.6: SSI data transmission sequence diagram
Notice! In the default setting the LSB bit is the error bit.
Attention! Significance of the error bit:
By default a 25th error bit (LSB) is appended to the 24-bit measurement value. The error bit is not included in the Gray coding of the measurement value. The error bit is 1 = active, 0 = not active.
Device parameters and interfaces
Notice!
The data can be read out with a clock rate between 80 kHz and 800 kHz.
Attention! Updating the measurement values on the SSI interface of the AMS 200:
The measurement value on the SSI interface of the AMS 200 is updated every 1.6 ms (de­fault) independent of the clock frequency. The update rate on the interface can be reduced to 0.2 ms via the display under the SSI menu item or in PROFIBUS module 17. The shorter update rate is only valid for the SSI interface and has no influence on the PROFIBUS DP interface.
Leuze electronic AMS 200 81
TNT 35/7-24V
Device parameters and interfaces
SSI connector (5-pin plug, B-coded)
Pin Name Remarks
1DATA+ + Data line SSI (output)
2DATA- - Data line SSI (output)
3 CLK+ + Clock line SSI (input electrically insulated)
4CLK- - Clock line SSI (input electrically insulated)
5FE Functional earth
Thread FE Functional earth (housing)
8.2.1.2 Cable length as a function of the data rate
Only shielded and twisted pair lines (pin 1 with 2 and pin 3 with 4) are permitted as data
lines for the SSI interface (see chapter 8.2.2 "SSI - Electrical connection").
ª
The shielding must be connected at both ends.
ª
Do not lay the cable parallel to power cables.
The maximum possible cable length is dependent on the cable used and the clock rate:
Data rate 80 kBit/s 100 kBit/s 200 kBit/s 300 kBit/s 400 kBit/s 500 kBit/s 1,000 kBit/s
Max. cable length (typical) 500 m 400 m 200 m 100 m 50 m 25 m 10 m
Table 8.7: Max. cable length as a function of the clock rate

8.2.2 SSI - Electrical connection

SSI
DATA-
2
CLK+
FE
3
5
CLK-
DATA+
1
4
Figure 8.8: SSI - electrical connection
Notice!
To connect the SSI interface we recommend our ready-made SSI cables, see "Order codes for interface connection cables" on page 105.
82 AMS 200 Leuze electronic

8.2.3 Notice regarding software parameters

Attention! Using the PROFIBUS and SSI interface simultaneously:
The SSI interface settings are performed by the PROFIBUS. If settings which differ from the default settings for the parameters, are to be used, they must be configured via module 17 (SSI interface).
Device parameters and interfaces
Using the SSI interface without PROFIBUS:
For this operating mode deactivate the PROFIBUS via the display (PROFIBUS = OFF). Default parameters are stored in the laser measurement system for the sole use of the SSI interface. The preset default parameters can be changed at any time via the display. This also applies when using parameters which do not relate directly to the SSI interface (for example: I/O 1 or I/O 2, position value or others). The SSI interface remains active even during parameter enabling. Changes to parameters have an immediate effect.

8.2.4 Default settings of the SSI interface

Default parameters which apply only to the SSI interface. SSI activation ON Measurement value coding Gray Transmission mode 24-bit measurement value + 1-bit error (error: 1 = active), error bit = LSB Resolution 0.1 mm Default error bit Plausibility error or hardware error Update rate 1.6 ms
Default parameters which apply to both PROFIBUS and SSI. Measurement unit Metric Count direction Positive (the SSI interface cannot represent negative values) I/O 1 Output – plausibility error or hardware error I/O 2 Output – temperature error, intensity error or laser prefailure message Static preset +000.000 Dynamic preset +000.000 Position limit value range 1 Lower limit and upper limit: both 0 Position limit value range 2 Lower limit and upper limit: both 0 Error handling procedures Position output: 0
Suppress position status: active Position suppression time: 100 ms
Display language English Display illumination OFF after 10 min. Display contrast Medium Password protection Off Password 0000
Table 8.9: Default settings of the SSI interface
TNT 35/7-24V
Leuze electronic AMS 200 83
Device parameters and interfaces
ESC
ESC
ESC
ESC
ESC
ESC ESC
ESC
Activation of SSI interface ON/OFF
Default: ON
Data coding: Gray or binary
Default: Gray coding
Transmission mode: 24-bit, 25-bit or 26-bit measurement value
Default: 24-bit
Measurement value resolution:
0.001 mm, 0.01 mm, 0.1 mm, 1 mm or 10 mm
Default: 0.1 mm
Error bit: ON or OFF, default: ON Error bit is set in the event of overflow or intensity (ATT) or excess temperature (TMP) or laser prefailure warning (LSR) or plausibility error (PLB) or hardware error (ERR).
Default: Plausibility error (PLB) or hardware error (ERR).
Update rate:
0.2 ms or 1.6 ms (independent of the clock frequency!)
Default: 1.6 ms

8.2.5 Changing the SSI default settings via the display

Notice!
For basic operation of the display please refer to chapter 6.3.2. In order to change the parameters please activate parameter enabling. The SSI interface remains active even during parameter enabling. Changes to parameters have an immediate effect.

8.2.6 SSI parameter display

Figure 8.10: SSI parameter display
84 AMS 200 Leuze electronic
Device parameters and interfaces
ESC
ESC
Measurement window with activated Interbus and RS 232 interface:
Display IBS: Interbus activated (default: ON)
Default: ON
Display RS232:RS 232 interface activated
(default: OFF)

8.3 Interbus

8.3.1 General information

The AMS 200/xxx-20-(H) is designed as an Interbus device. The functionality of the AMS 200 is thereby permanently defined by default settings.
The baud rate of the data to be transferred is 500 kbit/s.
The RS 232 interface available on the AMS 200 can be used simultaneously with the Interbus interface. The SSI interface cannot be used.

8.3.2 Activation/deactivation of the Interbus interface on the AMS 200

Notice!
The Interbus interface can be activated/deactivated via the display. With the Interbus acti­vated, the IBS lettering is visible on the display. By default the Interbus interface is activated and the RS 232 interface is deactivated.
If Interbus "OFF" is switched, the IBS lettering is also deactivated on the display.
Continuing participants are addressed even with the Interbus deactivated.
A deactivated AMS 200 can be recognised on the process data monitor of the Interbus master by means of the data double word 80 00 00 00
.
H
Figure 8.11: Interbus activation
Leuze electronic AMS 200 85
TNT 35/7-24V
Device parameters and interfaces
PWR LED:
States as described
in chapter 6.2.2.2
BUS LED:
No function with Interbus (perma-
nently deactivated) !
BUS OUT
DO
1
2
3
4
/DO
/DI
DI
Data GND
5
BUS IN
DI
3
2
1
4
Data GND
/DO
/DI
DO
5
M 12 plug
(B-coded)
M 12 socket
(B-coded)
BUS IN (5-pin plug, B-coded) BUS OUT (5-pin socket, B-coded)
Pin Name Remarks Pin Name Remarks
1DOFrom the Interbus master 1DOFrom the Interbus master
2/DO
From the Interbus master
- inverted
2/DO
From the Interbus master
- inverted
3 DI To the Interbus master 3 DI To the Interbus master
4/DI
To the Interbus master ­inverted
4/DI
To the Interbus master ­inverted
5
Data GND
Data Ground 5
Data GND
Data Ground
Thread SHIELD
Shield via RC element on the housing
Thread SHIELD
Shield directly on the housing

8.3.3 Indicator LEDs

Figure 8.12: Indicator LEDs of Interbus version

8.3.4 Interbus - Electrical connection

8.3.4.1 BUS IN and BUS OUT connections
86 AMS 200 Leuze electronic
Figure 8.13: Interbus - BUS IN and BUS OUT electrical connections
Notice!
PWR
I/O 2
I/O 1
3
2
1
4
5
GND VIN
FE
M 12-plug
(A-coded)
PWR (5-pin plug, A-coded)
Pin Name Remarks
1VINPositive supply voltage +18 … +30 V DC
2 I/O 1
Input/output 1, by default: Input: low (0 V) = laser on,
high (VIN) = laser off
3 GND Supply voltage 0 V DC
4 I/O 2
Input/output 2, by default: Output: low (0 V) = velocity limit value exceeded
high (VIN) = below velocity limit value
5FEFunctional earth
Thread FE Functional earth (housing)
For connecting BUS IN and BUS OUT we recommend our ready-made Interbus cables (see chapter 10.8 "Accessory ready-made cables for interface connection" on page 103).
Attention! The laser measurement system can be used to branch out the Interbus network. The con-
tinuing network is connected via BUS OUT.
The integrated SUPI (Serial Universal Peripheral Interface) automatically detects whether additional participants are connected to BUS OUT. Termination of BUS OUT is not neces­sary.
8.3.4.2 Shielding and grounding concept
The cable shielding must be concentric and have the largest possible surface area on the M 12 connector (thread).
The M 12 thread for BUS IN is connected to the functional earth (FE) inside the AMS 200 via an RC element (1MΩ || 15nF).
The M 12 thread for BUS OUT is conductively connected to the housing and is thus directly connected to the functional earth (FE).
8.3.4.3 PWR connection
Device parameters and interfaces
Leuze electronic AMS 200 87
Figure 8.14: Interbus - electrical connection PWR
TNT 35/7-24V
Device parameters and interfaces
Notice!
Input I/O 1 (pin 2) - laser ON/OFF:
If the laser diode of the AMS 200 is deactivated, the data double word A0 00 00 00 ferred. In this case, bit 31 is permanently set to logic 1 and message "PLB" is transferred; the values of the four bytes are thus A0 00 00 00 input data").

8.3.5 Ident number of the AMS 200/xxx-20-(H)

The AMS 200 is classified with Interbus Ident-Code No. 32H.
The classification describes the AMS 200 as a remote bus participant with 32-bit input data.

8.3.6 Data format - 32-bit input data

byte 0 byte 1 byte 2 byte 3
76543210765432107654321076543210
is trans-
H
(see chapter 8.3.6 "Data format - 32-bit
H
ATT
PLB
ERR
"1" level
313029282726252423222120191817161514131211109876543210
MSB LSB
LSR
TMP
Reserved
Reserved
Sign
MSB measurement value
Measurement value, Gray coded, resolution 1 mm
Table 8.15: Interbus data format - 32-bit input data
The AMS 200 makes available 32-bit input data. The breakdown of the 32 bits is shown in the above table.
88 AMS 200 Leuze electronic
LSB measurement value
Device parameters and interfaces
The data format in detail:
Bit 0 … Bit 22 Measurement value:
Representation of the measured distance, Gray coded with a resolution of 1 mm. The coding of the measurement value can be switched from Gray (default) to binary. The setting can be found in the Parameter -> Inter-
bus -> Coding menu.
Bit 23 Sign of the measured distance:
0 = positive distance value 1 = negative distance value (e.g. through the use of the offset function)
Bit 24 … Bit 25 Reserved, statically set to binary 0
Bit 26 TMP - Temperature monitoring warning.
Above/below permissible internal device temperature.
Bit 27 LSR - Warning laser prefailure message.
Laser diode aged, device still functional, please initiate replacement or repair.
Bit 28 ATT - Received signal warning.
Laser emission window or reflector dirty.
Bit 29 PLB - Plausibility error.
Implausible measurement value. Possible causes:
• Light beam interruption
• Measurement range exceeded
• Internal device temperature considerably above/below limit
• Traverse rate >10m/s.
Bit 30ERR - Internal hardware error.
The device must be sent in for inspection.
Bit 31 Statically set to binary 1
TNT 35/7-24V
Notice!
The AMS 200 makes a new 32-bit long data set available every 1.6 ms. Depending on the number of configured participants and the quantity of data to be transferred by the partici­pants, the baud rate of 500 kbit/s can result in the same data set of the AMS 200 being read multiple times in succession.
With the Interbus deactivated (Interbus OFF via control panel/display), bit 31 remains stati­cally set to binary 1. Bit 30 … bit 0 are statically set to binary 0.
A deactivated AMS 200 can be recognised on the process data monitor of the Interbus mas­ter by means of the data double word 80 00 00 00
.
H
Continuing participants are addressed even with the Interbus deactivated.
Leuze electronic AMS 200 89
Device parameters and interfaces

8.3.7 Default settings of the AMS 200/…-20…

Default parameters of the AMS 200/xxx-20-(H) Interbus activation RS232 activation
1)
1)
OFF
ON
Ident-Code 32H Number of data bits 32
Data breakdown
Measurement value represen-
1)
tation
1)
Unit Resolution Count direction I/O 1 I/O 2 Static preset Dynamic preset
1)
1)
1)
1)
1)
1)
Pos. limit value range 1 Pos. limit value range 2
Error handling procedures
Display language Display illumination Display contrast Password protection Password
1)
1)
1)
1)
1)
23-bit measurement value, 1-bit sign, 2-bit reserved, 3-bit pre-failure mes­sages, 2-bit errors, 1-bit statically set to binary 1
Gray
Metric 1mm Posi tive Input LOW = laser on, HIGH = laser off Velocity monitoring output set to > 0.2m/s (configurable) + 000.000 + 000.000
1)
Lower and upper limit, both 000.000
1)
Lower and upper limit, both 000.000 Position output: 000.000
1)
Position status suppression: active Error delay time: 100ms
English Off after 10 min. medium Off 0000
1) Parameter can be changed via the control panel/display
Table 8.16: Default settings of the Interbus interface
Notice! The AMS 200 cannot be configured via the Interbus.
The settings labelled with footnote 1) can only be changed via the display. Changed param­eters are stored in the AMS 200 and are reactivated following power off/on.
90 AMS 200 Leuze electronic
Device parameters and interfaces
ESC
ESC
ESC

8.3.8 Configuration via the control panel/display

First, you must activate parameter enabling (ON).
Figure 8.17: Parameter enabling
After enabling the parameters (display is inverted) the parameters shown in the following image can be changed.
Figure 8.18: Interbus parameter
An overview of the parameter menu is included in the fold-out page behind the cover page of this technical description.
Leuze electronic AMS 200 91
TNT 35/7-24V
Device parameters and interfaces
Measurement window when RS 232 interface is activated:
Default: OFF
Display RS232:RS 232 interface activated
(default: OFF)

8.4 RS 232

8.4.1 General information

The AMS 200 offers the option of using the SERVICE M 12 connection to communicate with other devices via an RS 232 interface. The RS 232 interface can be used as a full-fledged interface in parallel with the PROFIBUS, the SSI interface or the Interbus interface.
On delivery, the RS 232 interface is deactivated.
PROFIBUS
I
NTERBUS
SSI

8.4.2 Activation/deactivation of the RS 232 interface on the AMS 200

If the RS 232 is used simultaneously with the PROFIBUS interface, activation is performed via the GSD file in module 19.
If the RS 232 is used simultaneously with the Interbus or with the SSI interface, activation is performed via the display.
Notice! Upon consultation with Leuze electronic, a MA… connector unit can be used to convert
to the RS 485 or RS 422 interfaces.
ESC
ESC
Figure 8.19: RS 232 activation
Notice!
92 AMS 200 Leuze electronic
With the RS 232 interface activated the RS232 lettering appears on the display.

8.4.3 RS 232 - Electrical connection

RS 232 socket (5-pin socket, A-coded)
Pin Name Remarks
1
1)
1) Must not be connected/used!
+3.3V 1)Voltage supply 3.3 V DC
1)
2RS232-TX Transmission line RS 232 interface
3 GND Voltage supply 0 V DC
4RS232-RX Receiving line RS 232 interface
5N.C.Not used
Thread FE Functional earth (housing)
Device parameters and interfaces
SERVICE
RS232-TX
2
Figure 8.20: RS 232 - electrical connection
Attention!
The RS 232 interface is not electrically insulated. Line length should not exceed 10 m.
+3.3 V
1
RS232-RX
GND
3
5
4
NC
TNT 35/7-24V
Leuze electronic AMS 200 93
Device parameters and interfaces

8.4.4 Configuration via the control panel/display

Attention!
Simultaneous use of PROFIBUS and RS232
The settings of the RS 23 2 interface are performed by the PROFIBUS. For this purpose, module 19 must be activated. If parameters other than those specified in the default settings are used, they must be configured via module 19 (RS 232 interface).
Using the RS 232 interface without PROFIBUS
For this operating mode, default parameters are stored for the RS 232 interface by the laser measurement system. The preset default parameters can be changed at any time via the control panel/display.
This also applies when using parameters that do not directly affect the RS 232 interface. This RS 232 interface is also active during parameter enabling. Changes to parameters have an immediate effect.
Default settings of the RS232 interface
Designation Default setting Value rang e
Activation of the RS232OFF
Address 0 0 … 15
Baud rate 38.4kbit/s
Format (number of data bits, parity none/even/odd, number of stop bits)
Output cycles (Value range 1 … 20) x 1.7 ms
Position resolution Unit mm
Unit inch (in/100)
Velocity resolution Unit mm/s
Unit inch/s (in/100)/s
8,n,1
1 1 … 20
0.1 mm
1 mm/s
ON OFF
19.2 kbit/s
38.4 kbit/s
57.6 kbit/s
115.2 kbit/s 8,n,1
8,e,1 8, o, 1
0.01
0.1 1 10 1 10 100
94 AMS 200 Leuze electronic
Device parameters and interfaces
Activation of the RS 232 interface
Default: OFF
Address of the RS 232 interface
Default: 0
Baud rate of the RS 232 interface
Default: 38.4 kbit/s
Transmission format of the RS 232 interface
Default: 8,n,1 (8 data bits,
parity none, 1 stop bit)
Resolution of position values:
0.01 mm, 0.1 mm or 1 mm
Default: 0.1 mm
Output cycle of the data
Default: 1 (1 • 1.7 ms)
Resolution of speed values: 1 mm/s, 10 mm/s or 100 mm/s
Default: 1 mm/s
Changing the RS 232 default settings via the control panel/display
Notice!
For basic operation of the display please refer to chapter 6.3.2. In order to change the pa­rameters please activate parameter enabling. The RS 232 interface remains active even during parameter enabling. Changes to parameters have an immediate effect.
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ESC
Figure 8.21: Display - RS 232 parameters
Leuze electronic AMS 200 95
TNT 35/7-24V
Device parameters and interfaces

8.4.5 Communication protocol (binary protocol)

8.4.5.1 Querying AMS data (request)
The transfer of the measured distances, the speed or the control of the laser diode (ON/ OFF) is controlled by a protocol which is 3-byte long.
Request structure
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 1 1 0 0 ADR ADR ADR ADR 1 CMD CMD CMD CMD CMD CMD CMD CMD 2 XOR XOR XOR XOR XOR XOR XOR XOR
Function byte 0
ADR = address
Function byte 1
CMD = command
Bit coding Hex coding Function
1111 0001
1111 0010
1111 0011
1111 0100
1111 0101
1111 0110
1111 0111
F1
H
F2
H
F3
H
F4
H
F5
H
F6
H
F7
H
Function byte 2
XOR link of byte 0 and byte 1
Transfer individual position value (single shot) Cyclically transfer position values
(note output cycle parameter!) Stop cyclical transfer
Laser diode on
Laser diode off
Transfer single speed value Cyclically transfer speed values
(note output cycle parameter!)
96 AMS 200 Leuze electronic
Loading...