Leonics Ulta Series User Manual

- 1 -
SAFETY INSTRUCTIONS 1 INTRODUCTION 4 FRONT AND REAR PANEL 10 INSTALLATION 16 OPERATION 19 UPS STATUS DISPLAY 21 TROUBLE SHOOTING 27 SERVICE 30 BATTERY REPLACEMENT 31 INPUT FUSE REPLACEMENT 33 STORAGE AND PRESERVATION 34 SOFTWARE INSTALLATION 34
SAFETY INSTRUCTIONS
Please read carefully and follow this ULTRA Series UPS guide.
Important :Please keep this user's guide for reference in order to use the UPS properly
and safety. This user's guide contains instructions for installation, operation and specifications.
For product safety, please check this product annually by our service qualified per­sonnel or if there are any symptoms of problems which are not mentioned in this guide or an queries, please contact your LEONICS local distributors,LEONICS Service Center, send e-mail to support@leonics.com or visit www.leonics.com.
For your convenience and quick reference for our service, please fill the requested information in the blanks below. UPS Model : __________________________________ Serial Number : __________________________________ Purchased date : __________________________________ Purchased from : __________________________________
Caution
Risk of electric shock, DO NOT remove cover. No user serviceable part inside, please refer servicing to qualified service personnel.
1.1 Electrical Safety
1.1.1 Do not work alone where there are electrically hazardous conditions.
1.1.2 Contact with live conductors will cause burns and dangerous electric shock.
1.1.3 Only qualified electricians allow to install and wiring this unit and the system.
1.1.4 Periodically check your cable, terminal and power source to make sure that they are in good condition.
1.1.5 To reduce risk from electric shock if you can not find the electrical ground
( ) of the building, unplug the UPS from the AC source before plug in your
load at the rear side of the UPS. Then, plug in the UPS to AC source.
- 2 -
- 3 -
1.1.6Do not touch any metal parts or any electrical connection when UPS is operating.
1.1.7Use ONLY one hand when plugging and unpluging the load in order to avoid electric shock from touching two surfaces with different potential.
1.1.8 It is recommended to connect the UPS to a three wire AC source (two live wires and ground) which connects to a protected circuit such as employs a fuse or circuit breaker.
1.2 CAUTION ! Safety guide for installation and operation
1.2.1 Before installing or using this unit, read all instructions, caution markings on the UPS and all connected load, and all sections of this user guide.
1.2.2 Install this unit in a temperature and humidity controlled indoor area with adequate air flow and away from chemical particles or flammable substances . Avoid installing the unit near radio transmission station, heat dissipation equip­ment and direct sunlight.
1.2.3 This unit has ventilation grills. Ensure that sufficient ventilation is provided. DO NOT block the ventilation grills.
1.2.4 Use insulated tools to reduce your risk of electric shock.
1.2.5 Remove all jewelry or other metal objects such as rings, necklace, bracelets and watches when installing this product.
1.2.6 Properly wiring the cables as shown in the wiring diagram.
1.2.7 Before connecting the communication interface signal cable, Turn off the UPS by pressing the front panel button until the Utility Line OK/Fail ( ) and Overload Alarm ( ) lamps are lit at the same time and the alarm sounds once. Then, release the button.
1.2.8 Turn on the UPS before turn on the load to prevent surge from the loads.
1.2.9 DO NOT connect utility power to the UPS OUTPUT. This may cause the UPS damaged.
1.2.10When heavy rain, avoid using electronic equipments including
UPS to pre
it from lightning.
1.2.11Use soft cloth to clean the UPS when it is turned OFF. DO NOT clean it with solvent.
1.2.12DO NOT use the UPS with life recovery instruments. The failure of UPS may cause life recovery instruments failure or effect to their performance or to the safety system of those instruments.
vent
effect
1.3 Warning ! Battery Safety
1.3.1 Although the UPS is not connected to any power source, its outlets may be energized because it has a battery inside.
1.3.2 The UPS has hazardous voltages inside, do not disassemble any parts of UPS except for the battery. Users are not allowed to repair, recondition or disassemble the UPS. This must be done by Leonics qualified technicians only.
This product contains sealed lead acid battery and must be recycled properly. For recycling please return it to a LEONICS local distributor or LEONICS Service Center or contact your local recycling center for proper disposal information.
1.3.3 Do not dispose of batteries in a fire. They may be exploded.
1.3.4 Do not disassemble batteries. They contains poisonous electrolyte which is harmful to your skin and eyes.
1.3.5 Replace batteries with the same type and rating and follow the proper battery replacement procedure.
1.3.6 When replacing a battery, use tools with insulated handles and remove any watch, rings or other metal objects that you wear in order to avoid electric shock.
1.3.7 If user has to keep the UPS or does not use if for long time, recharge the battery every 3 months in order to preserve the battery. To recharge the battery, connect it to the AC utility and turn on the UPS for 8 hours.
Vocabulary
Load : Any electrical equipment which is connected to the UPS and gets power
from the UPS such as a computer, printer, fax machine or modem. UPS : ULTRA Series UPS VA :The unit of UPS power rating showing its capacity. Option : The additional function or device that is not supply with standard
product.
- 4 -
INTRODUCTION
2.1 General
The ULTRA Series UPS is a compact, light weight and attractively designed uninterruptible power supply for office automation equipment (computers and peripherals such as monitors, modem, printers, fax machines, etc.). Its major function is to eliminate any power problem such as a black out, brown out, sag, surge, spike, noise, etc. that might cause malfuction of the load causing work interruption. With its Advanced Microprocessor Control, when the UPS detects any abnormal conditions, it will respond instantaneously. It also has special features: Power Watcher, a full time load measuring system, Battery Watcher, the battery capacity checking system, Ultra Fast Charger, providing less than 3 hours charging time without shortening battery life and Perfect Ultra Display, which shows the current status of the UPS ( load level, input voltage level, battery level, battery replacement condition and overload condition) and Advanced Load Outlet Management (ALOM), which the user can program to turn off a low priority outlet when there is a low battery or overload condition (for 1050VA or higher only). For the UPS with LED display and EASY display, LED lamps represent the messages or status. For the UPS with LCD display, the messages or symbols show on LCD screen.
The ULTRA Series UPS can be started when there is no power source. It is conve­nient for you to have spare power when the source fails or in an emergency. It also can communicate with a computer through the Easy-Mon X Monitoring and Management Software (sold separately) via USB or RS-232 (for some model) port . This software can monitor the UPS and AC source status on PC that connected directly to UPS. It allow user to schedule on-off the UPS, schedule self-test and data log. It also can monitor the UPS and AC source status of the UPS in the network through Easy-Mon Netview Manager (sold seperately) and alarm the blackout status on computer server to client computer in the network through Easy-Mon Alert (sold seperately).
2.2 ULTRA Series UPS Operation
- 5 -
de
mal mo
ating in the nor er
Op
2.2.1
- 6 -
de
up mo
ating under back er
Op
2.2.2
- 7 -
2.2.1 Operating in the normal mode Normally, UPS is working under line interactive mode in which the path of
current is as follows : When the current first flows into the UPS, it has to pass through a surge protection circuit to filter surges and spikes which may occur from a nearby lightning discharge or load switching by the local power company. Here, the high voltage power will go to the line grounding system and let only the acceptable current pass to the EMI/RFI filter to eliminate EMI and RFI. Then it flows to the automatic voltage regulator (AVR) to regulate the voltage level to approximately your country's standard nominal mains voltage (see product specification, 100, 110, 120, 220, 230 or 240 Volts). If the voltage is too high or too low compared to the standard nominal voltage, it will be adjusted to the safety level for your loads (please refer to the specifications). After that the current will flow to two destinations. The first part goes to the EMI/RFI attenuation then to the Power Watcher and to your connected loads. The Power Watcher provides information about load conditions, whether or not you are overloading your ULTRA Series UPS. (Power Watcher is continuously monitoring in real time both for the stabilizer and inverter modes.) The remaining power flows to the battery charger circuit to charge the batteries and maintain them fully charged.
2.2.2 Operating under backup mode The UPS will transfer to backup mode (inverter mode) when it detects
abnormal situations such as blackouts, brownouts, surges, sags or abnormal frequency. These situations may harm your loads and may be too risky for the UPS to operate in the interactive mode. When an abnormal power mode is detected, the UPS will Immediately transfer to the backup mode with no loss of power to the loads. At this moment, the backup power will begin to be drawn from battery. The current from the battery will flow to the inverter (changing direct current to alternating current). Then, the power flows to the EMI/RFI attenuation, Power Watcher and on to your loads.
You can also monitor the UPS from a PC by using Easy-Mon X Monitoring and Management Software through a connection between the PC and the UPS communication port. For instance, you can set the UPS shutdown time and restart time, this status will be displayed on your PC monitor.
- 8 -
- 9 -
2.3 Features
Advanced LEONICS Microprocessor control: A specially programmed
microprocessor produced only for LEONICS is used as the CPU for the UPS. This makes the ULTRA Series UPS perform faster and more accurately to protect valuable equipment and its peripherals and provides advanced control features. Power Watcher: Full time load power monitoring and battery charge warnings are provided to make sure that your UPS will be able to properly backup power to the PC protected by UPS. "Power Watcher" helps users know in real time that they are not overloading their UPS. With this useful feature you can increase loads as much as you want until the UPS overload warning is shown. (LEONICS suggests that for highest reliability and safety that you should connect loads at no more than 75 % of rated UPS power. This allows for loads that change power level during use and provides for some reserve backup power for some loads.) Battery Watcher (Battery Replacement Indicator): Every time ULTRA Series UPS performs a self-test and when the battery has been fully charged, it will perform a battery condition evaluation to determine whether the battery used by the ULTRA Series UPS is still good or should be replaced. The battery replacement indicator will show when the battery should be replaced. Ultra Fast Charger: This UPS features an advanced, 3 stage charger (Bulk ­Boost - Float) to shorten charging time without harming the battery. Besides fast charging, UPS also maintains the proper charging voltage to preserve the battery from self-discharge and to make sure that it is always fully charged and ready to provide backup power to your PC. Intelligent Battery Management (IBM): The intelligent battery management system will manage charging and discharging to get longer backup times and prolong battery life. Advanced Load Outlet Management (ALOM): This feature allows the user to preset operation of the "Intelligent Channel" via Easy-Mon X Software. The user can preset the intelligent output channel to cut off power to low priority loads when the UPS is overloaded, over temperature or has a low battery (available on 1050 VA or higher model only).
Hot Swappable Battery: The user can replace the battery even when the UPS is running and without turning off the computer as long as mains power is available. Surge Protection for Telephone Line: Surge protection protects equipment data from surges that come from telephone line (RJ11).
Surge Protection for LAN Line (option): Surge protection protects equipment data from surges that come from LAN line. These special sockets can accept either telephone plugs (RJ11) or LAN plugs (RJ45). Perfect LED Display (depend on model): Attractive outlook with full function LED display. It shows load level, input voltage level, battery level, battery replacement condition and overload condition. Perfect LCD Display (depend on model): Attractive outlook with full function LCD display. It shows load level, input voltage level, battery level, battery replacement condition and overload condition. Easy Display (depend on model): Simple outlook with easy function display. It shows utility line status, battery status and load status.
Multi-function switch : Single switch with 4 functions, very convenient to users :
1. Turn on / Turn off UPS
2. Mute audible alarm
3. Self-test switch
4. Switch display mode (For the UPS with LED display only.)
Extend Backup Time (option): It extends the battery unit to increase the duration of UPS backup time. It can protect data with extra effectiveness.
Inverter temperature sensor (option): When the UPS is operating under backup
mode, the inverter temperature sensor will check the temperature inside inverter and
warning when the temperature is too high. You should reduce the load immediately.
Automatic voltage regulator -37% to +30%. buck and double boost (option) :
With it’s especially wide range automatic input voltage regulator, from –37% to +30%,
UPS can lessen backup mode transferred transaction, which helps you save the
battery‘s energy for emergencies, it also prolongs your battery life. (This optional is
special for specific models, please see your features on the side of the carton).