This System Manual addresses to all persons who dimension, install,
commission, and set 9300 servo position controllers.
Together with the System Manual (extension), document number
EDSVS9332P−EXT, and the catalogue, it provides the basis for project
planning for the mechanical engineer and the plant constructor.
The System Manual provides the basis for the description of the 9300 servo
position controller. Together with the System Manual (extension),
document number EDSVS9332P−EXT, a complete System Manual is
available:
ƒ The features and functions are described in detail.
ƒ The parameterisation for typical applications is explained by the use of
examples.
ƒ In case of doubt, the Mounting Instructions supplied with the 9300
servo position controller are always valid.
Contents of System ManualContents of the System Manual (extension)
1 Preface1 Preface
2
Safety−
3 Technical data−
4 Mounting the standard device−
5 Wiring the standard device−
6 Commissioning−
7 Parameter setting−
8
Configuration
8.1 Monitoring
8.2 Monitoring functions2.2 Basic configuration
8.3 Code table2.3 Operating modes
8.4 Selection lists
8.5 Table of attributes
−3 Function library
−4 Application examples
9 Troubleshooting and fault
elimination
10 DC−bus operation−
11 Safety engineering−
12 Accessories−
13 Appendix5 Appendix
2
Configuration
2.1 Configuration with Global Drive Control
−
EDSVS9332P EN 5.0−07/2013
1.1−1
1
1.1
1.1.1
Preface and general information
How to use this System Manual
Information provided by the System Manual
How to find information
Use the System Manual as the basis. It contains references to the
corresponding chapters in the System Manual Supplement:
ƒ Each chapter is a complete unit and comprehensively informs about a
subject.
ƒ The Table of Contents and Index help you to find all information about
a certain topic.
ƒ Descriptions and data of other Lenze products (Drive PLC, Lenze geared
motors, Lenze motors, ...) can be found in the corresponding catalogs,
Operating Instructions and manuals. The required documentation can
be ordered at your Lenze sales partner or downloaded as PDF file from
the Internet.
Tip!
Information and auxiliary devices related to the Lenze products
can be found in the download area at
http://www.Lenze.com
1.1−2
EDSVS9332P EN 5.0−07/2013
Preface and general information
How to use this System Manual
Products to which the System Manual applies
1
1.1
1.1.2
1.1.2Products to which the System Manual applies
This documentation is valid for 9300 servo position controllers from
nameplate data:
Nameplate
EVS 93xx˘ x x Vxx 6x 8x
Product range
EVS =servo controller
Type no. / rated power
400V480 V
9321 = 0.37 kW0.37 kW
9322 = 0.75 kW0.75 kW
9323 = 1.5 kW1.5 kW
9324 = 3.0 kW3.0 kW
9325 = 5.5 kW5.5 kW
9326 = 11 kW11 kW
9327 = 15 kW18.5 kW
3928 = 22 kW30 kW
9329 = 30 kW37 kW
9330 = 45 kW45 kW
9331 = 55 kW55 kW
9332 = 75 kW90 kW
Type
E =panel−mounted unit
C =panel−mounted unit in "cold plate" technology
Model
P =servo position controller
Variant
˘standard
V003 = in "cold plate" technology
V004 = with "safe torque off" function
V100 = for IT systems
V104 = with "safe torque off" function and for IT systems
9300vec112
Hardware version (from 6x)
Software version (from 8.0)
EDSVS9332P EN 5.0−07/2013
1.1−3
1
1.1
1.1.3
Preface and general information
How to use this System Manual
Document history
1.1.3Document history
What is new / what has
changed?
Material numberVersionDescription
.M),5.007/2013TD06 Error corrections
133749934.203/2012TD23 Error correction
133749934.105/2011TD23 Error correction
133749934.004/2011TD23 Extended by functions for software version
004632613.003/2003TD23 Error correction and editorial revision
004061752.002/1999−Types 9321 to 9324 with a double
003976531.005/1997−First edition
8.0
Complete editorial revision and error
correction
Division of the System Manual into 2 parts
(EDSVS9332P and EDSVS9332P−EXT)
overcurrent, new function Automatic
control parameter identification"
1.1−4
EDSVS9332P EN 5.0−07/2013
1.2Legal regulations
Preface and general information
Legal regulations
1
1.2
Identification
Manufacturer
CE conformity
Application as directed
Lenze controllers are unambiguously identified by the contents of the
nameplate.
ƒ may only be operated under the conditions specified in this System
Manual.
ƒ are components
– for open and closed loop control of variable speed drives with PM
synchronous motors, asynchronous standard motors or asynchronous
servo motors.
– for installation in a machine.
– for assembly with other components to form a machine.
ƒ comply with the protection requirements of the EC "Low Voltage"
Directive.
ƒ are not machines for the purpose of the EC "Machinery" Directive.
ƒ are not to be used as domestic appliances, but only for industrial
purposes.
Drive systems with 9300 servo controllers
ƒ comply with the EC "Electromagnetic Compatibility" Directive if they
are installed according to the guidelines of CE−typical drive systems.
ƒ can be used
– for operation on public and non−public mains supplies.
– for operation in industrial premises and residential and commercial
areas.
ƒ The user is responsible for the compliance of the machine application
with the EC Directives.
Any other use shall be deemed inappropriate!
EDSVS9332P EN 5.0−07/2013
1.2−1
1
1.2
Preface and general information
Legal regulations
Liability
Warranty
The information, data and notes given in this System Manual met the state
of the art at the time of printing. Claims on modifications referring to
controllers and components which have already been supplied cannot be
derived from the information, illustrations and descriptions contained in
this manual.
The procedural notes and circuit details given in this System Manual are
suggestions and their transferability to the respective application has to be
checked. Lenze does not take any responsibility for the suitability of the
given procedures and circuit suggestions.
The specifications given in this System Manual describe the product features
without guaranteeing them.
Lenze does not accept any liability for damage and malfunctioning caused
by:
ƒ Disregarding the System Manual
ƒ Unauthorised modifications to the controller
ƒ Operating faults
ƒ Improper working on and with the controller
See terms of sales and delivery of Lenze Automation GmbH.
Warranty claims must be made to Lenze immediately after detecting the
deficiency or fault.
The warranty is void in all cases where liability claims cannot be made.
2.4Safety instructions for the installation according to UL 2.4−3. . . . . . . . . . . .
Safety instructions
Contents
2
EDSVS9332P EN 5.0−07/2013
2−1
2.1General safety information
Safety instructions
General safety information
2
2.1
Scope
For your own safety
The following general safety instructions apply to all Lenze drive and
automation components.
The product−specific safety and application notes given in this
documentation must be observed!
Note for UL−approved systems: UL warnings are notes which only apply to
UL systems. The documentation contains specific notes with regard to UL.
Danger!
Disregarding the following basic safety measures may lead to
severe personal injury and damage to material assets!
ƒ Lenze drive and automation components ...
... must only be used for the intended purpose.
... must never be operated if damaged.
... must never be subjected to technical modifications.
... must never be operated unless completely assembled.
... must never be operated without the covers/guards.
... can − depending on their degree of protection − have live, movable or
rotating parts during or after operation. Surfaces can be hot.
Transport, storage
ƒ All specifications of the corresponding enclosed documentation must
be observed.
This is vital for a safe and trouble−free operation and for achieving the
specified product features.
The procedural notes and circuit details provided in this document are
proposals which the user must check for suitability for his application.
The manufacturer does not accept any liability for the suitability of the
specified procedures and circuit proposals.
ƒ Only qualified skilled personnel are permitted to work with or on Lenze
drive and automation components.
According to IEC 60364 or CENELEC HD 384, these are persons ...
... who are familiar with the installation, assembly, commissioning and
operation of the product,
... possess the appropriate qualifications for their work,
... and are acquainted with and can apply all the accident prevent
regulations, directives and laws applicable at the place of use.
ƒ Transport and storage in a dry, low−vibration environment without
aggressive atmosphere; preferably in the packaging provided by the
manufacturer.
– Protect against dust and shocks
– Comply with climatic conditions according to the technical data.
.
EDSVS9332P EN 5.0−07/2013
2.1−1
2
2.1
Safety instructions
General safety information
Mechanical installation
Electrical installation
ƒ Install the product according to the regulations of the corresponding
documentation. In particular observe the section "Operating
conditions" in the chapter "Technical data".
ƒ Provide for a careful handling and avoid mechanical overload. During
handling neither bend components, nor change the insulation
distances.
ƒ The product contains electrostatic sensitive devices which can easily be
damaged by short circuit or static discharge (ESD). Thus, electronic
components and contacts must not be touched unless ESD measures
are taken beforehand.
ƒ Carry out the electrical installation according to the relevant
regulations (e. g. cable cross−sections, fusing, connection to the PE
conductor). Additional notes are included in the documentation.
ƒ When working on live products, observe the applicable national
regulations for the prevention of accidents (e.g. BGV 3).
ƒ The documentation contains information about EMC−compliant
installation (shielding, earthing, arrangement of filters and laying
cables). The system or machine manufacturer is responsible for
compliance with the limit values required by EMC legislation.
Warning: The controllers are products which can be used in category C2
drive systems as per EN 61800−3. These products may cause radio
interference in residential areas. If this happens, the operator may need
to take appropriate action.
ƒ For compliance with the limit values for radio interference emission at
the site of installation, the components − if specified in the technical
data − have to be mounted in housings (e. g. control cabinets). The
housings have to enable an EMC−compliant installation. In particular
observe that for example control cabinet doors preferably have a
circumferential metallic connection to the housing. Reduce openings or
cutouts through the housing to a minimum.
ƒ Only plug in or remove pluggable terminals in the deenergised state!
Commissioning
Operation
Safety functions
2.1−2
ƒ If required, you have to equip the system with additional monitoring
and protective devices in accordance with the respective valid safety
regulations (e. g. law on technical equipment, regulations for the
prevention of accidents).
ƒ Before commissioning remove transport locking devices and keep them
for later transports.
ƒ Keep all protective covers and doors closed during operation.
ƒ Without a higher−level safety system, the described product must
neither be used for the protection of machines nor persons.
ƒ Certain controller versions support safety functions (e.g. "Safe torque
off", formerly "Safe standstill").
The notes on the safety functions provided in the documentation of the
versions must be observed.
EDSVS9332P EN 5.0−07/2013
Safety instructions
General safety information
2
2.1
Maintenance and servicing
Disposal
ƒ The components are maintenance−free if the required operating
conditions are observed.
ƒ If the cooling air is polluted, the cooling surfaces may be contaminated
or the air vents may be blocked. Under these operating conditions, the
cooling surfaces and air vents must be cleaned at regular intervals.
Never use sharp objects for this purpose!
ƒ Only replace defective fuses in the deenergised state to the type
specified.
ƒ After the system has been disconnected from the supply voltage, live
components and power connections must not be touched immediately
because capacitors may be charged. Please observe the corresponding
notes on the device.
ƒ Recycle metals and plastic materials. Ensure professional disposal of
assembled PCBs.
EDSVS9332P EN 5.0−07/2013
2.1−3
2.2Thermal motor monitoring
From software version 8.0 onwards, the 9300 controllers are provided with
2
an I
xt function for sensorless thermal monitoring of the connected motor.
Note!
2
ƒ I
calculates a thermal motor load from the detected motor
currents.
ƒ The calculated motor load is saved when the mains is
switched.
ƒ The function is UL−certified, i.e. no additional protective
measures are required for the motor in UL−approved systems.
ƒ However, I
influences on the motor load could not be detected as for
instance changed cooling conditions (e.g. interrupted or too
warm cooling air flow).
Safety instructions
Thermal motor monitoring
x t monitoring is based on a mathematical model which
2
x t monitoring is no full motor protection as other
2
2.2
2
x t load of the motor is displayed in C0066.
Die I
The thermal loading capacity of the motor is expressed by the thermal motor
time constant (t, C0128). Find the value in the rated motor data or contact
the manufacturer of the motor.
2
The I
x t monitoring has been designed such that it will be activated after
179 s in the event of a motor with a thermal motor time constant of
5 minutes (Lenze setting C0128), a motor current of 1.5 x I
and a trigger
N
threshold of 100 %.
Two adjustable trigger thresholds provide for different responses.
ƒ Adjustable response OC8 (TRIP, warning, off).
– The trigger threshold is set in C0127.
– The response is set in C0606.
– The response OC8, for instance, can be used for an advance warning.
ƒ Fixed response OC6−TRIP.
– The trigger threshold is set in C0120.
Behaviour of the I2 x t monitoringCondition
The I2 x t monitoring is deactivated.
C0066 is set = 0 % and
MCTRL−LOAD−I2XT is set = 0.00 %.
I2 x t monitoring is stopped.
The current value in C0066 and at the
MCTRL−LOAD−I2XT output is frozen.
I2 x t monitoring is deactivated.
The motor load is displayed in C0066.
When C0120 = 0 % and C0127 = 0 %, set
controller inhibit.
When C0120 = 0 % and C0127 = 0 %, set
controller enable.
Set C0606 = 3 (off) and C0127 > 0 %.
EDSVS9332P EN 5.0−07/2013
Note!
An error message OC6 or OC8 can only be reset if the I2 x t load
falls below the set trigger threshold by 5 %.
2.2−1
2
2.2
2.2.1
Safety instructions
Thermal motor monitoring
Forced ventilated or naturally ventilated motors
2.2.1Forced ventilated or naturally ventilated motors
Parameter setting
Calculate release time and
2
xt load
I
The following codes can be set for I
CodeMeaningValue rangeLenze setting
C0066Display of the I2 x t load of the motor0 ... 250 %−
C0120Threshold: Triggering of error "OC6"0 ... 120 %0 %
C0127Threshold: Triggering of error "OC8"0 ... 120 %0 %
C0128Thermal motor time constant0.1 ... 50.0 min5.0 min
C0606Response to error "OC8"TRIP, warning, offWarning
Formula for release timeInformation
ȡ
t +*(t) ln
ȧ
ȧ
1 *
Ȣ
Formulae for I2 x t loadInformation
2
I
Mot
ǒ
L(t) +
If the controller is inhibited, the I2 x t load is reduced:
Ǔ
100% ǒ1 * e
I
N
L(t) + L
Start
I
Mot
ǒ
I
N
Ǹ
e
z ) 1
2
Ǔ
100
*
*t
t
t
2
x t monitoring:
I
ȣ
ȧ
ȧ
Ȥ
Ǔ
t
Mot
I
r
tThermal motor time constant (C0128)
zThreshold value in C0120 (OC6) or
L(t)Chronological sequence of the I2 x t
I
Mot
IrRated motor current (C0088)
tThermal motor time constant (C0128)
L
Actual motor current (C0054)
Rated motor current (C0088)
C0127 (OC8)
load of the motor
(Display: C0066)
Actual motor current (C0054)
I2 x t load before controller inhibit
Start
If an error is triggered, the value
corresponds to the threshold value set
in C0120 (OC6) or
C0127 (OC8).
Read release time in the
diagram
Diagram for detecting the release times for a motor with a thermal motor
time constant of 5 minutes (Lenze setting C0128):
I = 3 × I
L [%]
MotN
120
100
50
0
0100200300400500600700800900
Fig. 2.2−1I2 × t−monitoring: Release times for different motor currents and trigger
I = 2 × I
MotN
thresholds
I
Actual motor current (C0054)
Mot
I
Rated motor current (C0088)
r
2
LI
TTime
x t load of the motor (display: C0066)
I = 1.5 × I
MotN
I = 1 × I
MotN
t [s]
1000
9300STD105
2.2−2
EDSVS9332P EN 5.0−07/2013
2.2.2Self−ventilated motors
Due to the construction, self−ventilated standard motors are exposed to an
increased heat generation in the lower speed range compared to forced
ventilated motors.
Warnings!
Safety instructions
Thermal motor monitoring
Self−ventilated motors
For complying with the UL 508C standard, you have to set the
speed−dependent evaluation of the permissible torque via code
C0129/x.
2.2.2
2
2.2
Parameter setting
Effect of code C0129/x
The following codes can be set for I2 x t monitoring:
CodeMeaningValue rangeLenze setting
C0066Display of the I2 x t load of the motor0 ... 250 %−
C0120Threshold: Triggering of error "OC6"0 ... 120 %0 %
C0127Threshold: Triggering of error "OC8"0 ... 120 %0 %
C0128Thermal motor time constant0.1 ... 50.0 min5.0 min
C0606Response to error "OC8"TRIP, warning, offWarning
C0129/1S1 torque characteristic I1/I
C0129/2S1 torque characteristics n2/n
I / I
N
1.1
1.0
3
0.9
0.8
0.7
0.6
Fig. 2.2−2Working point in the range of characteristic lowering
0
0
00.1
C0129/1
0.132
C0129/2
1
2
0.20.30.4
rated
rated
10 ... 200 %100 %
10 ... 200 %40 %
n / n
N
9300STD350
EDSVS9332P EN 5.0−07/2013
The lowered speed / torque characteristic (Fig. 2.2−2) reduces the
permissible thermal load of self−ventilated standard motors. The
characteristic is a line the definition of which requires two points:
ƒ Point : Definition with C0129/1
This value also enables an increase of the maximally permissible load.
ƒ Point : Definition with C0129/2
With increasing speeds, the maximally permissible load remains
unchanged (I
Mot
= I
rated
).
In Fig. 2.2−2, the motor speed and the corresponding permissible motor
torque () can be read for each working point (on the
characteristic () ... ). can also be calculated using the values in
Calculate the release time and the I2 x t load of the motor considering the
values in C0129/1 and C0129/2(evaluation coefficient "y").
Formulae for release timeInformation
TRelease time of the I2 x t monitoring
ȡ
I
Mot
ǒ
y I
n
Ǹ
e
z ) 1
2
Ǔ
100
N
n
) C0129ń1
N
t
*
t
T +*(t) ln
ȧ
ȧ
1 *
Ȣ
100% * C0129ń1
y +
Formulae for I2 x t loadInformation
If the controller is inhibited, the I2 x t load is reduced:
L(t) +
C0129ń2
I
Mot
ǒ
y I
L(t) + L
2
Ǔ
100% ǒ1 * e
N
Start
tThermal motor time constant (C0128)
ȣ
InFunction: Natural logarithm
ȧ
ȧ
I
Mot
Ȥ
I
r
zThreshold value in C0120 (OC6) or
yEvaluation coefficient
n
L(t)Chronological sequence of the I2 x t
yEvaluation coefficient
*t
Ǔ
t
I
Mot
IrRated motor current (C0088)
tThermal motor time constant (C0128)
L
Actual motor current (C0054)
Rated motor current (C0088)
C0127 (OC8)
Rated speed (C0087)
rated
load of the motor
(Display: C0066)
Actual motor current (C0054)
I2 x t load before controller inhibit
Start
If an error is triggered, the value
corresponds to the threshold value set
in C0120 (OC6) or
C0127 (OC8).
2.2−4
EDSVS9332P EN 5.0−07/2013
2.3Residual hazards
Safety instructions
Residual hazards
2
2.3
Protection of persons
ƒ According to their enclosure, Lenze controllers (frequency inverters,
servo inverters, DC speed controllers) and their components can carry a
voltage, or parts of the controllers can move or rotate during operation.
Surfaces can be hot.
– If the required cover is removed, the controllers are used
inappropriately or installed or operated incorrectly, severe damage to
persons or material assets can occur.
– For more detailed information please see the documentation.
ƒ There is a high amount of energy within the controller. Therefore
always wear personal protective equipment (body protection,
headgear, eye protection, ear protection, hand guard) when working on
the controller when it is live.
ƒ Before working on the controller, check if no voltage is applied to the
power terminals.
– the power terminals U, V, W, +UG and −UG still carry dangerous
voltage for at least 3 minutes after power−off.
– the power terminals L1, L2, L3; U, V, W, +UG and −UG carry dangerous
voltage when the motor is stopped.
ƒ Before power−off during DC−bus operation, all controllers must be
inhibited and disconnected from the mains.
ƒ The discharge current to PE potential is > 3.5 mA. In accordance with
EN 61800−5−1
– a fixed installation is required.
– the design of the PE conductor has to be double or, in the case of a
single design, must have a cable cross−section of at least 10 mm
ƒ The controller can only be safely disconnected from the mains via a
contactor on the input side.
ƒ During parameter set transfer the control terminals of the controller
can have undefined states.
– Therefore the connectors X5 and X6 must be disconnected from the
controller before the transfer takes place. This ensures that the
controller is inhibited and all control terminals have the defined state
"LOW".
2
.
EDSVS9332P EN 5.0−07/2013
2.3−1
2
2.3
Safety instructions
Residual hazards
ƒ Controllers can cause a DC current in the PE conductor. If a residual
current device (RCD) or a fault current monitoring unit (RCM) is used
for protection in the case of direct or indirect contact, only one
RCD/RCM of the following type can be used on the current supply side:
– Type B for the connection to a three−phase system
– Type A or type B for the connection to a single phase system
Alternatively another protective measure can be used, like for instance
isolation from the environment by means of double or reinforced
insulation, or isolation from the supply system by using a transformer.
Device protection
Motor protection
ƒ Frequent mains switching (e.g. inching mode via mains contactor) can
overload and destroy the input current limitation of the drive
controller:
– At least 3 minutes must pass between switching off and restarting
the devices EVS9321−xP and EVS9322−xP.
– At least 3 minutes must pass between two starting procedures of the
devices EVS9323−xP ... EVS9332−xP.
– Use the "safe torque off" safety function (STO) if safety−related mains
disconnections occur frequently. The drive variants Vxx4 are
equipped with this function.
ƒ For some controller settings, the connected motor may overheat (e.g.
when operating the DC injection brake or a self−ventilated motor at
low speed for longer periods).
– Using an overcurrent relay or a temperature monitoring device
provides a large degree of protection against overload.
– We recommend to use PTC thermistors or thermal contacts for motor
temperature monitoring. (Lenze three−phase AC motors are equipped
with thermal contacts (NC contacts) as standard)
– PTC thermistors or thermal contacts can be connected to the
controller.
2.3−2
ƒ Drives can attain dangerous overspeeds (e.g. setting of high output
frequencies with motors and machines not qualified for this purpose).
EDSVS9332P EN 5.0−07/2013
Loading...
+ 415 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.