Lenoxx Electronics G41UF User Manual

E 2002 Lennox Industries Inc.
Dallas, Texas, USA
504,646M 2/2003
G41UF
SERIES
GAS FURNACE
FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exactĆ ly could result in serious injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other apĆ pliance.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
02/03
*2P0203*
Litho U.S.A.
WARNING
WHAT TO DO IF YOU SMELL GAS:
D Do not try to light any appliance. D Do not touch any electrical switch; do not
use any phone in your building.
D Leave the building immediately. D Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's instructions.
D If you cannot reach your gas supplier, call
the fire department.
504,646M
*P504646M*
G41UF Parts Identification
TOP CAP
COMBUSTION AIR
PROVING
(PRESSURE) SWITCH
UPPER ACCESS
PANEL
DURALOK
EXCHANGER
ASSEMBLY
TM
HEAT
BURNERS
CABINET
GAS VALVE AND
MANIFOLD
FLUE
COLLAR
COMBUSTION AIR
INDUCER
SURELIGHTt
CONTROL BOARD
BLOWER ACCESS
PANEL
FIGURE 1
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of CalĆ ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379-9900
NOTE - This manual must be left with the equipment user.
BLOWER
MOTOR
CONTROL BOX
WARNING
Do not set thermostat below 60°F (16°C) in heating mode. Setting thermostat below 60°F (16°C) reduces the number of heating cycles. Damage to the unit may occur that is not covered by the warranty.
WARNING
If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the furnace before shutting off electrical supply.
CAUTION
Before attempting to perform any service or mainteĆ nance, turn the electrical power to unit OFF at the disconnect switch.
Page 2
WARNING
Do not use this furnace if any part has been underĆ water. A flood-damaged furnace is extremely danĆ gerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified serĆ vice technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
IMPORTANT
Any additions, changes, or conversions required in order for the appliance to satisfactorily meet the apĆ plication needs must be made by a Lennox service technician using factory specified and approved parts.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personĆ al injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Safety Instructions
1 - Keep the furnace area clear and free of combustible
material, gasoline, and other flammable vapors and liquids. If it is installed in an insulated area, the furnace must be kept free of insulating material. Insulating maĆ terial may be combustible.
2 - DO NOT obstruct air flow to unit. Unit must receive an
unobstructed flow of combustion and ventilating air. DO NOT block or obstruct air openings on the furnace or air openings to the area in which the furnace is installed. Take care to maintain established clearĆ ances surrounding the furnace.
3 - DO NOT store chlorine or fluorine products near unit
or introduce these products into the combustion air. These products can cause furnace corrosion.
4 - DO NOT draw return air from a room where this furĆ
nace, or any other gas appliance (ie., a water heatĆ er), is installed. When return air is drawn from a room,
a negative pressure is created in the room. If a gas apĆ pliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
WARNING
The blower door must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into the living space resulting in personal injury or death.
Your furnace is a gas appliance. It is critical that the gas
supplied to the unit be completely burned to avoid the proĆ duction of carbon monoxide gas. Complete combustion of the gas requires, but is not limited to, correct gas pressure and gas flow rate, adequate combustion, air, and proper venting.
WARNING
Carbon monoxide gas is invisible, odorless and toxic.
Exposure to carbon monoxide gas can cause personal injuĆ ry and even death to all occupants, including pets. Any item that is powered by or gives off heat from a combustion proĆ cess (including lawn mowers, automobiles, and fireplaces) has the potential to produce carbon monoxide gas. Because of this, Lennox recommends the use of a carbon monoxĆ
ide detector in your home, even if you do not own gas appliances. Reliable detectors are available at reasonable
retail prices. Contact your Lennox dealer for more details about this investment in your safety.
Your furnace is designed to meet standards set by nationĆ al agencies, and to operate safely when properly installed and maintained. However, the unit's performance can be greatly impacted by the individual installation and the opĆ erating environment. It is your responsibility to ensure that this appliance is maintained. Proper maintenance is critiĆ cal for your safety and the satisfactory operation of the product. Lennox strongly recommends annual inĆ spection and maintenance of this appliance. Contact your Lennox dealer for an inspection by a qualified service technician.
Lighting Information & Operation
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
Page 3
The gas valve on the G41UF will be equipped with either a gas control knob or lever. Use only your hand to turn the gas control knob or push the gas lever. Never use tools. If the knob or lever will not move by hand, do not try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Placing the G41UF furnace into operation:
G41UF units are equipped with a SureLightt ignition sysĆ tem. Do not attempt to manually light burners on these furĆ naces. Each time thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with the SureLightt ignition sysĆ tem.
Operating the Gas Valve (Figures 3, 4 and 5)
1 - STOP! Read the safety information at the beginning of
this section.
2 - Set the thermostat to the lowest setting. See figure 2.
3 - Turn off all electrical power to the unit.
White Rodgers 36E Series Gas Valve
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
GAS VALVE SHOWN IN OFF POSITION
FIGURE 3
White Rodgers 36F Series Gas Valve
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
THERMOSTATS
FIGURE 2
4 - This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the burners by hand.
5 - Remove the upper access panel.
6 - White Rodgers 36E/36F Gas Valve - Switch gas
valve lever to OFF. Honeywell VR8205 Gas Valve - Turn knob on gas
valve clockwise
to OFF. Do not force. See figure
5.
7 - Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instrucĆ tions. If you do not smell gas go to next step.
8 - White Rodgers 36E/36F Gas Valve - Switch gas valve leĆ
ver to ON. See figure 3 for the White Rodgers 36E va l v e and figure 4 for the Wh i te Rodgers 36F valve.
Honeywell VR8205 Gas Valve - Turn knob on gas valve counterclockwise
to ON. Do not force.
GAS VALVE SHOWN IN OFF POSITION
FIGURE 4
Honeywell VR8205 Series Gas Valve
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
ON
OFF
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
OUTLET
FIGURE 5
9 - Replace the upper access panel.
10 - Turn on all electrical power to to the unit.
11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12- If the appliance will not operate, follow the section
Turning Off Gas to the Unit" and call your service techĆ nician or gas supplier.
Turning Off Gas to the Unit
1 - Set the thermostat to the lowest setting. 2 - Turn off all electrical power to the unit if service is to be
performed.
3 - Remove the upper access panel.
Page 4
4 - White Rodgers 36E/36F Gas Valve - Switch gas
Furnace
valve lever to OFF.
Honeywell VR8205 Gas Valve - Turn knob on gas valve clockwise
5 - Replace the upper access panel.
to OFF. Do not force.
Filters
All G41UF filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure proper furnace operation. ReĆ placement filters must be rated for high velocity airflow. Table 1 lists recommended filter sizes. A filter must be in place whenever the unit is operating.
TABLE 1
Furnace
Cabinet Size
17-1/2" 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21" 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24-1/2" 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Side Return Bottom Return
Filter Size
Maintenance
A qualified service technician should inspect the complete system each season (heating and cooling). The following maintenance procedures should only be conducted by a qualified service technician. Do not attempt to service
the unit in any way.
Annually (before heating season) inspect furnace venting system, vent cap, heat exchanger, and burners for corroĆ sion, deterioration, or deposits of debris. Remove any obĆ structions.
Inspect the furnace for obvious signs of deterioration.
Inspect the furnace venting system to make sure it is in place, physically sound, and without holes, corrosion, or blockage.
Vent pipe must be clear and free of obstructions and must slope upward away from the furnace.
Inspect the furnace return air duct connection to ensure duct is sealed to the furnace and terminates outside the space containing the furnace.
Inspect the physical support of the furnace to guarantee that it is sound without sagging, cracks or gaps around base and it maintains seal between base and support.
Inspect and clean the condensate trap and drain.
During a seasonal check the service technician will inspect the indoor blower, burner flames and electrical connections along with the venting system.
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operaĆ tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to disĆ connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
Venting System
WARNING
Asphyxiation Hazard
The exhaust vent for this furnace must be securely connected to the furnace flue collar at all times.
For your safety and to fulfill the terms of the limited warranty, a qualified service technician must annualĆ ly inspect this furnace and its vent system.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injuĆ ry or death.
Burner Flame
CAUTION
To ensure proper operation, a qualified technician should annually check the burner flame.
Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating).
3 - Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
Page 5
Service Reminder
Call your Lennox service technician if the unit will not operĆ ate. Before calling, always check the following to be sure service is required:
1 - Check that electrical disconnect switches are ON. 2 - Check room thermostat for proper setting. 3 - Replace any blown fuses or reset circuit breakers. 4 - Gas valve should be ON. 5 - Air filter should not be plugged, which will limit air flow. 6 - Is gas turned on at meter? 7 - Is manual main shut-off valve open? Record the model and serial number of the furnace. These
numbers are on the unit nameplate, which is located on the blower deck below the combustion air inducer.
Serial Number __________________
Model Number __________________
Safety Precautions
If you discover any of the following, shut down your unit, and contact a Lennox dealer for an inspection by a qualified technician.
D If you repeatedly hear any new or unfamiliar sounds
while your unit is operating, there may be a problem. For example, poorly performing burners can produce unfaĆ miliar noises.
D If you smell any unusual odors, your unit may be operatĆ
ing improperly. For example, units can give off unfamilĆ iar odors if components are required to operate in abĆ normal conditions.
D Look for visible signs of a malfunctioning unit. Examples
include unusual amounts of condensate on windows inĆ side your house, visibly burnt components or unusual dirt or rust accumulations on the vent pipe or in the unit.
D If you experience headache, nausea, fatigue, or dizziĆ
ness, the cause could be exposure to carbon monoxide gas. This is often misdiagnosed as the flu because symptoms are similar. If you suffer from flu-like sympĆ toms that are exaggerated at home, but seem to subĆ side while you are away from the house, exposure to carbon monoxide could be the cause.
Your vigilance may pay off in early detection of a problem before either personal injury or property damage occurs. Do not hesitate to contact a qualified service technician as an investment in your well being.
Planned Service
You should expect a service technician to check the followĆ ing items during an annual inspection. Power to the unit must be shut off for the service technician's safety.
Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) - Must be open and unobĆ structed to provide combustion air.
Burners - Must be inspected for rust, dirt, or signs of water.
Vent pipe - Must be inspected for signs of water, damaged
or sagging pipe, or disconnected joints.
Unit appearance - Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.
Blower access door - Must be properly in place and proĆ vide a seal between the return air and the room where the furnace is installed.
Return air duct - Must be properly attached and provide an air seal to the unit.
Operating performance - Unit must be observed during operation to monitor proper performance of the unit and the vent system.
Combustion gases - Flue products must be analyzed and compared to the unit specifications.
Problems detected during the inspection may make it necĆ essary to temporarily shut down the furnace until the items can be repaired or replaced.
Pay attention to your furnace. Situations can arise beĆ tween annual furnace inspections that may result in unsafe operation. For instance, items innocently stored next to the furnace may obstruct the combustion air supply. This could cause incomplete combustion and the production of carĆ bon monoxide gas.
Page 6
Repair Parts List
The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA nameplate -- Example: G41UF-24A-045-1.
Cabinet Parts
Upper access panel Blower access panel Top Cap
Control Panel Parts
Transformer SureLight ignition board Door interlock switch Circuit Breaker
Blower Parts
Blower wheel Motor Motor mounting frame Motor capacitor Blower housing cutoff plate
Heating Parts
Flame Sensor
Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster Main burner orifices Pressure switch Ignitor Primary limit control Secondary limit Flame rollout switch
Page 7
Loading...