Lenoxx G1D91BU, G1D93BC, G1D93BT, G1D91BT, G1D93BU Installation Instructions Manual

INSTALLATION INSTRUCTIONS
G1D91BU, G1D91BT, G1D93BU, G1D93BT & G1D93BC
High Efficiency 90+ Condensing Gas Furnace
With System Sentry™ Control System
Save these instructions for future reference
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency , or the gas supplier.
W ARNING
Do not store combustible materials, including gasoline and other flammable vapors and liquids, near the furnace, vent pipe, or warm air ducts. The homeowner should be cautioned that the furnace area must not be used as a broom closet or for any other storage purposes. Such uses may result in actions that could cause property damage, personal injury, or death.
W ARNING
This furnace is not approved for installation in a mobile home. Do not install this furnace in a mobile home. Installation in a mobile home could result in actions that could cause property damage, personal injury , or death.
T ABLE OF CONTENTS
SAFETY ...............................................................2
INSTALLATION ....................................................3
START-UP..........................................................26
OPERATION ......................................................27
MAINTENANCE .................................................30
CONTROL SYSTEM DIAGNOSTICS.................32
WIRING DIAGRAMS..........................................33
Manufactured By
Allied Air Enterprises Inc.
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
*506305-01*
The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1/NFPA No. 54 (latest edition) and the National Electrical Code, ANSI/NFP A No. 70 (latest edition) in the United States; CSA B149.1 (latest edition) Natural Gas and Propane Installation Codes and the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws, local ordinances (including plumbing or wastewater codes), or local gas utility requirements. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
506305-01 Page 1 of 36Issue 0938
WARNING
IMPORT ANT SAFETY INFORMA TION
The following is a list of safety rules and precautions that must be followed when installing this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the Location section on page 3 of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in the Combustion and Ventilation Air section on page 4 of these instructions.
4. Adequate clearance must be provided around the vent­air intake terminals as specified in the Venting section beginning on page 5 of these instructions.
5. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only , as specified in the Venting section beginning on page 5 of these instructions.
6. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in Gas Supply and Piping beginning on page 22 of these instructions.
7. Always install furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in Temperature Rise on page 28 of these instructions. See furnace rating plate.
8. When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See Circulating Air Supply on page 22 of these instructions.
9. A gas-fired furnace for installation in a residential garage must be installed as specified in the Location section on page 3 of these instructions.
10. The furnace is permitted to be used for temporary heating of buildings or structures under construction as specified in the Location section beginning on page 3 of these instructions.
In the State of Massachusett s:
This product must be installed by a licensed Plumber or Gas Fitter. When flexible connectors are used, the maximum length shall not exceed 36". When lever­type gas shutoffs are used, they shall be T-handle type.
506305-01Page 2 of 36 Issue 0938
INSTALLATION
These instructions must be placed on or near the furnace in a conspicuous place.
The furnace design is certified by CSA International as a Category IV furnace in compliance with the latest edition of American National Standard Z21.47/CSA Standard 2.3 for Gas-Fired Central Furnaces, for operation with natural gas or propane. Consult the rating plate on the furnace for gas type before installing.
The maximum hourly heat loss of space shall be calculated in accordance with the procedure described in the current manuals of Air Conditioning Contractors of America, or by any other recognized method which is suitable for local conditions, provided the results obtained are in substantial agreement with, and not less than, those obtained using the procedure described in the manuals.
Location
T o provide proper operation and satisfactory performance, care must be taken in choosing the location for this furnace. The atmosphere in which the furnace operates must be free of contaminants such as chlorides and sulfates.
The furnace must be installed so that electrical components are protected from water. Unit must be level for proper condensate drainage.
WARNING
The condensate drain on this furnace is incorporated within the furnace and must be primed before start-up. The condensate system must not be exposed to temperatures under 32°F. Use of heat tape is permissible provided the rate temperature of the tape does not exceed 155°F.
G1D91BU and G1D93BU models shall be installed only as upflow furnaces. G1D93BC models shall be installed only as counterflow (downflow) furnaces.
G1D91BT and G1D93BT models may be installed as up flow or horizontal right to left or left to right airflow furnaces. When installed horizontally , the inst aller must install a sheet metal screw to retain the upper door as shown in Figure 1.
Never install any furnace on its back.
Horizontal Installations
HORIZONTAL RIGHT TO LEFT AIRFLOW SHOWN
Figure 1
Inspection of Shipment
This furnace is shipped in one package, completely assembled and wired. The thermostat is shipped in a separate carton when ordered.
Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier’s freight bill. Damage claims should be filed with the carrier immediately . Claims of shortages should be filed with the seller within 5 days.
To avoid property damage caused by condensate drain blockage, install a field-fabricated auxiliary drain pan with a separate drain line to the outside under the entire furnace and drain system. Install according to local codes.
All models are suitable for closet or utility room installation. The furnace is suitable for installation in buildings constructed
on-site. The furnace should be centralized in respect to the heat distribution system as much as practicable. When installed in a utility room, the door should be wide enough to allow the largest part of the furnace to enter, or permit the replacement of another appliance, such as a water heater.
A gas-fired furnace for installation in a residential garage must be installed so the burner(s) and the ignition source are located not less than 18" above the floor. The furnace is to be located or protected to avoid physical damage by vehicles.
This furnace is not recommended to be used as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors, and operation of the unit with clogged or misplaced filters will damage the unit.
The furnace may be used for heating of buildings or structures under construction, if the following conditions are met:
The vent system must be permanently installed per these
installation instructions.
A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to the
furnace.
506305-01 Page 3 of 36Issue 0938
Return air temperature range between 60°F and 80°F must be maintained.
Air filters must be installed in the system and must be maintained during construction.
Air filters must be replaced upon construction completion.
The input rate and temperature rise must be set per the furnace rating plate.
One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following the instructions provided on this page in the Combustion and Ventilation Air section regarding confined space with air from outside.
The furnace heat exchanger, component s, duct system, air filters, and evaporator coils must be thoroughly cleaned following final construction cleanup.
All furnace operating conditions (including ignition, input rate, temperature rise, and venting) must be verified according to these installation instructions.
G1D91BU, G1D91BT , G1D93BU and G1D93BT models may be installed on wood flooring but shall not be installed directly on carpeting, tile, or any other combustible material.
G1D93BC counterflow models are certified for installation on combustible flooring provided a special base assembly is used. (Refer to the Duct Connection – Counterflow Models section on page 22 for more information on using the special base assembly .)
When a counterflow unit is installed on a combustible floor , 1" clearance must be provided between the supply duct and the floor.
Combustion and Ventilation Air
Adequate provisions for combustion air and ventilation of furnace must be made. Refer to Section 5.3, “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA54 (latest edition), Sections 7.2, 7.3, or
7.4 of CSA B149.1 Natural Gas and Propane Installation Codes (latest editions), or applicable provisions of the local building codes.
WARNING
If the furnace is to be installed in an attic or other insulated space, it must be kept free and clear of insulating materials.
Clearances
All servicing and cleaning of the furnace can be performed from the front. If installed in a closet or utility room, provide 18" clearance in front for service if the door to the room is not in line with the front of the furnace.
Refer to T able 1 for the minimum clearances to combustibles required for construction and proper unit operation.
Accessibility clearances must take precedence over fire protection clearances.
Minimum Clearances to Combustibles
Table 1
Insufficient combustion air can cause headaches, nausea, dizziness, or asphyxiation. When considering combustion air requirements, enough air must also be provided to meet the needs of all fuel-burning appliances and exhaust fans.
W ARNING
Air openings in the front of the furnace must be kept free of obstructions. Any obstruction may cause improper operation that can result in a fire hazard or carbon monoxide injury .
Unconfined Space
An unconfined space is defined as “a space whose volume is more than 50 cubic feet per 1000 BTU per hour of the combined input rating of all appliances installed in that space.” When a furnace is installed in an unconfined space in a building, it can be assumed that the infiltration will be sufficient to supply the required air . If the furnace is installed in a ventilated attic or crawl space, it is assumed that the infiltration is sufficient to supply the required air . However , in a building of unusually tight construction, additional outdoor air should be provided.
506305-01Page 4 of 36 Issue 0938
Confined Space
A confined sp ace is defined as “a space whose volume is less than 50 cubic feet per 1000 BTU per hour of the combined input rating of all appliances installed in that space.”
If the furnace is installed in a confined space within the building and combustion air is taken from a heated space, the combustion air and ventilating air must enter and leave the space through two permanent openings of equal area. One opening shall be located within 12" of the ceiling and the other within 12" of the floor, each having a free area of 1 square inch per 1000 BTU/HR of total input rating of all appliances within the space and not less than 100 square inches each.
If the furnace is installed in a space within a building of tight construction, makeup air must be supplied from outdoors. In this case, one opening shall be within 12" of the ceiling and one opening within 12" of the floor. If combustion ducts are vertical, each opening shall have a free area of 1 square inch per 4000 BTU/HR of the total input rating of all appliances within the enclosure. If horizontal combustion ducts are run, 1 square inch per 2000 BTU/HR is required.
Contaminated Combustion Air
Excessive exposure to contaminated combustion air will result in safety and performance related problems. The recommended source of combustion air is outdoor air. However, the use of indoor air in most applications is acceptable if the following guidelines are followed:
1. If the furnace is installed in a confined space, it is
recommended that the necessary combustion air come from the outdoors by way of an attic, crawl space, air duct, or direct opening.
2. If indoor combustion air is used, there must be no exposure
to the substances listed in item 5.
3. All provisions for indoor combustion air must meet the
requirements for combustion air indicated in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition), and/or any applicable local codes. In Canada, see CSA B149.1, Natural Gas and Propane Installation Codes (latest edition).
4. The following types of installation may require outdoor air for combustion, due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage areas
5. Exposure to the following substances in the combustion air supply may also require outdoor air for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine-based swimming pool chemicals
Water softening chemicals
Deicing salts or chemicals
Carbon tetrachloride
Halogen-type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Chlorinated laundry products
Hydrochloric acid
Venting
The high efficiency of this furnace is accomplished by the removal of both sensible and latent heat from the flue gases. The removal of latent heat results in the condensation of moisture in the flue gases. This condensation occurs in the secondary heat exchanger and in the vent system. Therefore, this furnace requires special venting considerations and the instructions must be followed to insure proper operation. All venting must be in accordance with the codes having jurisdiction in the area and these instructions.
G1D91BU, G1D91BT , G1D93BU, G1D93BT and G1D93BC models can be installed as either direct vent or non-direct vent units. A direct vent (two pipe) installation requires that all the air necessary for combustion be supplied from outside the dwelling through an air intake pipe. A non-direct vent (one pipe) installation uses air from inside the dwelling for combustion.
The furnace is shipped with the air inlet pipe terminated to the top panel for either inside or outside combustion air . An inlet air restrictor plate (see Figure 2) is supplied with this furnace and can be found in the plastic bag containing these Installation Instructions and the User’s Information Manual. The inlet
restrictor plate must be used in all installations using inside air for combustion (non-direct vent).
Inlet Air Restrictor Plate
The inlet air restrictor plate must be installed in all installations using inside air for combustion (non-direct vent).
Flue Pipe Screen
The flue pipe screen should be installed at the termination of the flue pipe in all installations.
506305-01 Page 5 of 36Issue 0938
Figure 2
The inlet restrictor plate must be installed in the air inlet in one of three ways:
Restrictor plate in inlet collar: Install the restrictor plate in the inlet pipe collar in the top panel of the furnace. Insert a 3" to 36" section of PVC pipe (field supplied) into the collar. Use high temperature RTV sealant to attach PVC pipe to collar. A 90° elbow (field supplied) may be attached to the PVC pipe, but the elbow is not required. Use high temperature RTV sealant to attach elbow to PVC pipe (if applicable).
Restrictor plate in inlet pipe: Insert a 3" to 36" section of PVC pipe (field supplied) into the collar. Use high temperature RTV sealant to attach PVC pipe to collar. Install the restrictor plate in the end of the inlet pipe just installed. Attach either a field-supplied coupler or 90° elbow to the end of the PVC pipe to keep the restrictor plate in place. Use high temperature RTV sealant to attach the coupler or elbow to PVC pipe.
Restrictor plate in elbow: Insert a 3" to 36" section of PVC pipe (field supplied) into the collar. Use high temperature RTV sealant to attach PVC pipe to collar. Attach a 90° elbow (field supplied) to the PVC pipe. Use high temperature RTV sealant to attach elbow to PVC pipe. Install the restrictor plate into the elbow .
When a furnace is installed as direct vent, provisions for ventilation air should follow the same requirements as if installed as non-direct vent. Proper ventilation air is necessary to maintain furnace component temperatures within acceptable limits.
All vents passing through floors, ceilings, and walls must be installed in accordance with National Fuel Gas Code, ANSI Z223.1/NFP A 54 (latest edition).
The length of flue pipe exposed to outdoor conditions should be kept to a minimum. When the installation requires more than 3 feet of flue pipe be exposed to outdoor conditions, insulating the exposed flue pipe with 1/2” Armaflex or equivalent is recommended. In climates with design temperatures below zero degrees (F), 3/4” Armaflex or equivalent is recommended.
Materials
All pipe, fittings, primer, and solvent cement must conform with American National S tandard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no lumps, undissolved particles, or any foreign matter that adversely affects the joint strength or chemical resistance of the
Two dif ferent sized inlet restrictor plates are supplied with the furnace (2" and 3"). Use the proper restrictor plate for the furnace model.
W ARNING
If at any time in the future the installation of this furnace is changed to require outside fresh air for combustion, the inlet air restrictor plate must be removed. Failure to remove the inlet air restrictor could cause improper operation that can result in a fire hazard or carbon monoxide injury .
Also included in the plastic bag containing the inlet air restriction plate is a flue pipe screen (see Figure 2). In all installations, this screen sould be installed at the termination of the flue pipe and is designed to keep objects out of the flue pipe.
For either type of installation (direct or non-direct vent), special venting considerations must be followed. Refer to the proper section in pages 11 – 17 for the type of furnace and venting being installed.
The venting system must be supported with mounting straps to prevent any weight load from being applied to the vent blower. Horizontal vent pipe must be supported every 5' and vertical pipe should be supported every 10' to prevent sagging and provide rigid support.
Piping and Fitting Specifications
Piping & Fitting
Material
Schedule 40 PVC
(Pipe)
Schedule 40 PVC
(Cellular Core Pipe)
Schedule 40 PVC
(Fittings)
SDR-26
(Pipe)
SDR-26 CPVC
(Pipe)
Schedule 40 ABS
Cellular Core
DWV (Pipe)
Schedule 40 ABS
(Pipe)
Schedule 40 ABS
(Fittings)
Schedule 40 & 80 CPVC
(Pipe)
Schedule 40 & 80 CPVC (Fittings)
ABS-DWV
Drain Waste & Vent
(Pipe & Fittings)
PVC-DWV
Drain Waste & Vent
(Pipe & Fittings)
Specification
D1785
D2665
T able 2
ASTM
F891
D2466
D2241
F442
F628
D1527
D2468
F441
F438
D2661
506305-01Page 6 of 36 Issue 0938
cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring.
Refer to Table 2 for approved piping and fitting materials. Canadian Applications Only: PVC pipe, fittings, primer
and solvent cement used to vent this applicance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved venting system. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection. Models that may be installed as a horizontal furnace include a horizontal drain kit. In Canada this drain kit must be replaced by a locally available IPEX Drain Kit # 196014. For Local IPEX Canadian Customer
Service Center and Kit abailability call IPEX at 1-866-473-
9462.
The primers and solvents used must also meet ASTM specifications. PVC primer is specified in ASTM F656. Use PVC solvent as specified in ASTM D2564 and ABS solvent cement as specified ASTM D2235. Low temperature solvent cement is recommended. Metal or plastic strapping may be used for vent pipe hangers.
When making ABS joint s, pieces can be prepared with a clean dry cloth to clean inside socket surface of fitting and male end of pipe to depth of socket. Refer to procedure specified in ASTM D3138. When joining ABS to PVC materials, use transition solvent.
Preferred fittings are DWV style or long sweep. Seal all joints gas tight with appropriate cement. In areas where vent and air intake pipes are exposed to abnormal stress or are subject to damage, schedule 80 pipe should be used.
Category IV Furnace Limitations
This furnace shall not be connected to any Type B, BW, or L vent or vent connector and shall not be connected to any portion of a factory-built or masonry chimney . This furnace is not to
be common vented with any other appliance. The vent pipe must not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
Concentric Vent Kit
A concentric vent kit (see Accessories section on p age 31 for correct kit) is available for use when installing this furnace as a direct vent furnace and the air intake and vent pipe are to be run through the same hole, whether horizontally through the wall or vertically through the roof (see Figure 3). Refer to the instructions included with the concentric vent kit for installation specifics.
Vent Pipe Size and Length
The vent pipe and air intake pipe (in direct vent installations) should be sized in accordance with the information found in the appropriate table in Figure 4. One 90° elbow is equivalent to 5' of pipe. Two 45° elbows are equivalent to one 90° elbow. The minimum length certified for use with this furnace is 5' and one elbow, not including the vent and air intake terminals.
In the event that the pipe length is in between the lengths listed in the table, use the next larger length listed. For example, if a length of pipe needed to install the furnace is 27', use the diameter values for the 30' row in the tables. For direct vent installations, if the vent and air intake pipe are not equal in length and number of elbows, then determine the minimum pipe diameter for both the vent and air intake. If the results indicate different diameters, use the larger of the two for both the vent and air intake. Under no
circumstances should the vent and air intake pipe size be different in diameter. For installation details, refer to
the appropriate section in pages 11 – 17 for the unit model and type of installation.
High Altitude Installation: 2” pipe not recommended at altitude above 4,000 feet. 3” pipe required for altitude above 5,000 feet.
Horizontal Venting
The vent for this appliance shall not terminate over public walkways; or near soffit vents or crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or cause property damage; or where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.
Concentric Vent Kit Dimensions
Figure 3
506305-01 Page 7 of 36Issue 0938
See Figures 5 and 6 on pages 9 and 10 for additional information on where the horizontal vent terminal can and cannot terminate.
For Massachusetts Installations: The installation must comply with Massachusetts
248 CMR 5.08 Modifications to
sections of NFP A-54, Chapter10. (See p ages 35 and 36 )
Vent Tables *
(numbers in inches unless specified otherwise)
Minimum Pipe Diameter
45,000 – 75,000 BTU/HR Models
Vent Pipe Length (ft.)
5 10 20
30
40
50 60 70 80
90
Vent Pipe Length (ft.)
5
10
20
30
40
50
60
70
80
90
0123456789
1.5
1.5
1.5 2
2222222
22 222
2
2
2.5
2.52.5
2.5
2.5
2.52.5
90,000 – 100,000 BTU/HR Models
0123456789
NR
222222
2 222 333
2NR2
2.5
2.5
2.5 3333 33 33
Number of 90° Elbows
22222222 222222222
22222222
2.5 2.5
2.5
2
2.5 2.5
2.5 33333
2.5 2.5 2.5 2.5
2.5 2.5
2.52.52.5
3
3
2.5
2.5
2.5 3333 33
NR
3
3
2.5 2.5
2.5
NR NR
NR
Minimum Pipe Diameter
Number of 90° Elbows
2.5
2222222
2
2
2.5
2.5
3 3
3
NR NR NR
22
2.5 2.5 2.5 2.5
2.5 3
3
NR
2.5 2.5 2.5 2.5
2.5
3 3
33333
3
3
3
NR
NR
NR
NR
NR
NR
2.5 2.5
3
2.5
2.5
3
NR NR NR
NR NR
NRNR
NRNRNR
2.5
2.5
32.5 2.5
3
3
NR
NR
2.5
2.5 3
33
NR
NR
NR
Minimum Pipe Diameter
112,000 – 125,000 BTU/HR Models
Vent Pipe Length (ft.)
5
10
20 30
40
50
60
0123456789
2.5
2.5
2.5
2.5 2.5
2.5 2.5
2.5 3
Number of 90° Elbows
2.5
2.52.5
2.5
2.5
2.5
33
3
2.5
2.5
NR
2.5
2.5 2.5
2.5 NR
NR
2.5
2.52.52.5
2.5
2.5
2.5
NR
3
NR
NR
NR NR
2.52.52.5
2.5 2.5
2.5 33
NR NR NR NR
NR
NR
NR
NR = Not Recommended * 2” not recommended at altitude above 4,000 feet 3” required for altitude above 5,000 feet
Figure 4
2.52.5
3
2.5 3
3
NR
NRNR
NR
NR NR NR
NR
.
NR
506305-01Page 8 of 36 Issue 0938
Sidewall Vent Terminal Clearances (Direct Vented Furnaces)
A ** Minimum 12” (30 cm) above grade or 12” (30 cm) above average snow accumulation.
V
Vent Terminal
Air Supply Inlet
X
Area Where Terminal Is Not Permitted
1
In accordance with the current CSA B149.1, Natural Gas and
Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National
Fuel Gas Code
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
506305-01 Page 9 of 36Issue 0938
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, the following statement shall be included: “Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.”
Figure 5
Sidewall Vent Terminal Clearances (Non-Direct Vented Furnaces)
A ** Minimum 12” (30 cm) above grade or 12” (30 cm) above average snow accumulation.
V
X
Area Where Terminal Is Not Permitted
Vent Terminal
Air Supply Inlet
1
In accordance with the current CSA B149.1, Natural Gas and
Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National
Fuel Gas Code
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, the following statement shall be included: “Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.”
Figure 6
506305-01Page 10 of 36 Issue 0938
G1D91BU, G1D91BT, G1D93BU and G1D93BT Upflow Models – Direct Vent Installation
An inlet air restrictor plate (see Figure 2 on page 5) is supplied with this furnace and can be found in the plastic bag containing these Installation Instructions and the User’s Information Manual. This
restrictor plate is to be used only in non-direct vent applications. See pages 5 and 6 for more information on installing
the restrictor plate in non-direct vent applications. The flue pipe screen (see Figure 2 on page 5) should be
installed at the termination of the flue pipe and is designed to keep objects out of the flue pipe. An additional screen should not be placed in the intake termination. If a screen is installed, the air intake may freeze shut.
For horizontal venting, refer to Figure 7. For vertical venting, refer to Figure 8. It is permissible to run the vent vertically through the roof and terminate it as shown in Figure 8, and to run the combustion air intake pipe horizontally through a side wall and terminate as shown in Figure 7. The vent pipe on horizontal runs must slope upward, away from the furnace, at a minimum pitch of 1/4" per foot of run, to prevent accumulation of condensate.
Do not cement air intake into the connector on burner box. Use high temperature RTV silicone sealant so intake pipe can be removed if service is required.
In horizontal venting applications, the vent and air int ake pipe must be installed on the same side of the house within the parameters shown in Figure 7.
Prime the trap system by slowly pouring 1 cup of water down the vent pipe. On initial start-up of the unit, some of the water used to prime the trap system may run down into the combustion blower and cause noise.
Upflow Direct V ent – Vertical Venting
(G1D91BU, G1D91BT, G1D93BU & G1D93BT Only)
Upflow Direct Vent – Horizontal Venting
(G1D91BU, G1D91BT, G1D93BU & G1D93BT Only)
* Maintaining a vertical separation
between the flue outlet and the air intake of at least 18” is highly recommended to minimize the chance of flue gases recirculating and freezing in the air intake pipe. This distance may be reduced in milder climates or where wind is unlikely to blow flue products to the intake pipe, but should not be less than 6”.
Overhead View
FLUE PIPE
INTAKE PIPE
IS OPTIONAL.
3” MIN. - 48”MAX.
THIS PIECE
Figure 8
Figure 7
506305-01 Page 11 of 36Issue 0938
Loading...
+ 25 hidden pages