Lenox P506640-01, XP16 User Manual

Page 1
INSTALLATION
E20 Lennox Industries Inc.
Dallas, Texas, USA
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
RETAIN THESE INSTRUCTIONS FOR FUTURE
REFERENCE
NOTICE TO INSTALLER
BRAZING LINE SET TO SERVICE VALVES
It is imperative to follow the brazing technique illustrated starting on page 11 to avoid damaging the service valve’s internal seals.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HFCs, and HCFCs) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
INSTRUCTIONS
Elite® Series XP16 Units
HEAT PUMPS
506640−01 12/10 Supersedes 11/10
TABLE OF CONTENTS
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model Number Identification 2. . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . .
Caps and Fasteners Torque Requirements 3. . . . . . . .
Operating Gauge Set and Service Valves 3. . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . .
New Outdoor Unit Placement 6. . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 8. . . . . . . . . . . . . . . . .
Line Set Requirements 9. . . . . . . . . . . . . . . . . . . . . . . . .
Brazing Connections 11. . . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor Refrigerant Metering Device Removal and
Flushing Line Set and Indoor Coil 14. . . . . . . . . . . . . . . .
Installing New Indoor Metering Device 15. . . . . . . . . . . .
Leak Test Line Set and Indoor Coil 16. . . . . . . . . . . . . . .
Evacuating Line Set and Indoor Coil 17. . . . . . . . . . . . .
Electrical Connections 18. . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing and Weighing In Refrigerant for Units
Delivered Void of Charge 24. . . . . . . . . . . . . . . . . . . . . . .
Optimizing System Refrigerant Charge 26. . . . . . . . . . .
System Operation 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Two−Stage Modulation Compressors Checks 40. . . . . .
Maintenance 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checklists 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Litho U.S.A.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox XP16 Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
12/10 506640−01
Page 1
Shipping and Packing List
Check unit for shipping damage. Consult last carrier immediately if damage is found.
1 − Assembled outdoor unit
General
The XP16 outdoor unit uses HFC−410A refrigerant. This unit must be installed with a matching indoor blower coil and line set as outlined in the XP16 Lennox Engineering Handbook. Elite® Series outdoor units are designed for use in check / expansion valve (CTXV) systems only and are not to be used with other refrigerant flow control devices. An indoor coil check / expansion valve approved for use with HFC−410A must be ordered separately and installed prior to operating the unit.
*2P1210* *P506640-01*
Page 2
Model Number Identification
Refrigerant Type
X = R−410A
Unit Type
P = Heat Pump
Series
Unit Dimensions − inches (mm)
C
DISCHARGE AIR
P 16 036
X 05
230
Nominal Cooling Capacity
024 = 2 tons 036 = 3 tons 048 = 4 tons 060 = 5 tons
LIQUID LINE CONNECTION
ELECTRICAL INLETS
VAPOR LINE CONNECTION
4−3/4
4−1/4
(121)
(108)
Minor Revision Number
Voltage
230 = 208/230V−1ph−60hz
B
A
2 (51)
1 (25)
D
E
F
SIDE VIEW
G
K
J
H
XP16 BASE WITH LEGS
UNIT SUPPORT
FEET
8−1/2 (216)
8−3/4 (222)
SIDE VIEW
5−1/2 (140)
13−1/2
(343)
XP16−024 BASE SECTION
9−1/2 (241)
8−1/4 (210)
UNIT SUPPORT FEET
Mode Number A B C D E F G H J K
XP16−024−230 35 (889) 27 (686) 28 (711)
XP16−036−230 39 (991) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)
XP16−048−230 35 (889) 35−1/2 (902)
39−1/2 (1003)
16−7/8 (429) 8−3/4 (222) 3−1/8 (79) 30−3/4 (781) 4−5/8 (117) 3−3/4 (95) 26−7/8 (683)
XP16−060−230 45 (1143 35−1/2 (902)
39−1/2 (1003)
Page 2
Page 3
Typical Unit Parts Arrangement
FOR COIL SENSOR (RT21)
LOCATION SEE DETAIL A
GROUND
SINGLE POLE
LUG AMBIENT
CONTACTOR
(K1)
TEMPERATURE SENSOR (RT13)
DETAIL A
DUAL RUN CAPACITOR (C12) (−024, −036 AND −048 ONLY)
SINGLE RUN CAPACITOR (C1) (−060 ONLY)
DEMAND DEFROST CONTROL (A108)
DISCHARGE LINE
SENSOR (RT28)
REVERSING
VALVE (L1)
TRUE SUCTION
PORT
HIGH PRESSURE
SWITCH (S4)
EXPANSION VALVE
SENSING BULB
LIQUID VALVE AND GAUGE
PORT / LIQUID LINE
CONNECTIONS
VAPOR VALVE AND GAUGE PORT /
SUCTION LINE CONNECTIONS
COMPRESSOR
CHECK / EXPANSION VALV E
LIQUID LINE BI−FLOW FILTER DRIER
LOW PRESSURE SWITCH (S87)
XP16−036
COIL SENSOR − NINTH HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW.
XP16−024
COIL SENSOR −THIRD HAIRPIN DOWN FROM THE TOP ON INSIDE ROW.
Figure 1. Unit Parts Arrangement
Caps and Fasteners Torque Requirements
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes Corp.0807−L5 (C−08−1) for further details and information.
XP16−048
COIL SENSOR − EIGHT HAIRPIN UP FROM THE BOTTOM ON INSIDE ROW.
XP16−060
COIL SENSOR − SIXTH HAIRPIN UP FROM THE BOTTOM
ON INSIDE ROW.
When servicing or repairing HVAC equipment and components, ensure the fasteners are appropriately tightened. Table 1 list torque values for various caps and fasteners.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 N M
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
Page 3
XP16 SERIES
Page 4
Operating Gauge Set and Service Valves
USING MANIFOLD GAUGE SET
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for refrigerant recovery, flushing, leak testing, evacuating, weighing in refrigerant and optimizing system charge.
Each valve is equipped with a service port which has a factory−installed valve core. Figure 2 provides information on how to access and operate both angle− and ball−type service valves.
Operating Angle−Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open the service valve.
SERVICE PORT
CORE
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
When checking the system charge, only use a manifold gauge set that features low−loss anti−blow back fittings.
Manifold gauge set used for HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The manifold gauges should be rated for:
S High side  Pressure range of 0 − 800 pound−force per
square inch gauge (psig)
S Low side  Use with 30" vacuum to 250 psig with
dampened speed to 500 psig
S Manifold gauge set hoses must be rated for use to 800
psig of pressure with a 4000 psig burst rating.
TO INDOOR
UNIT
TO OUTDOOR
UNIT
VALVE STEM
SHOWN
CLOSED
INSERT HEX−HEAD
2
EXTENSION HERE
TO INDOOR
UNIT
TO OUTDOOR UNIT
When service valve is OPEN, the service port is open to line set, indoor and outdoor unit.
STEM CAP
Operating Ball−Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open.
ATo open rotate stem
counterclockwise 90°.
BTo close rotate stem
clockwise 90°.
SERVICE PORT
SERVICE PORT CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
TO INDOOR UNIT
BALL (SHOWN CLOSED)
VALVE STEM
2
REMOVE
1
STEM CAP
When service valve stem is in the CLOSED position, the service port is open to the line set and indoor unit.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
S With torque wrench: Finger tighten and torque cap per table 1. S Without torque wrench: Finger tighten and use an appropriately sized
wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
S With Torque Wrench: Finger tighten and then
torque cap per table 1.
S Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise.
9
10
9
10
8
8
1
11
7
11
7
REMOVE STEM CAP
1/6 TURN
12
1
2
3
4
5
6
1/12 TURN
12
1
2
4
5
6
3
Figure 2. Angle and Ball−Type Service Valves
Page 4
Page 5
Recovering Refrigerant from Existing System
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the disconnect
1
switch and/or main fuse box/breaker panel.
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
3
Remove existing HCFC−22 refrigerant using one of the following procedures:
METHOD 1:
Use Method 1 if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.
Recover all HCFC−22 refrigerant from the existing system using a recovery machine and clean recovery cylinder. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use Method 2 if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system.
Perform the following task: A Start the existing HCFC−22 system in the cooling mode and close the liquid line
valve.
B Use the compressor to pump as much of the existing HCFC−22 refrigerant into
the outdoor unit until the outdoor system is full. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE  It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve. D Check gauges after shutdown to confirm that the valves are not allowing
refrigerant to flow back into the low side of the system.
CONNECT MANIFOLD GAUGE SET
Connect a manifold gauge set, clean recovery cylinder and a
2
recovery machine to the service ports of the existing unit..
NOTE  Use the recovery machine instructions to make the correct manifold gauge set connections for recovery refrigerant. The illustration below is a typical connection.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
METHOD 2 LIMITATIONS
NOTE  When using Method 2, the listed devices below could prevent full system charge recovery into the outdoor unit:
S Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycle the compressor OFF.
S Compressor can stop pumping due to tripped
internal pressure relief valve.
S Compressor has internal vacuum protection that
is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction
pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower pressure due to any of the above mentioned system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
HIGH
Figure 3. Refrigerant Recovery
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
Page 5
XP16 SERIES
Page 6
New Outdoor Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lift­ing heavy objects.
Remove existing outdoor unit prior to placement of new outdoor unit. See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
S Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
S When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 5, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, detail B.
NOTE  If necessary for stability, anchor unit to slab as described in figure 5, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated in figure 5, detail C.
If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) schedule 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2 inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE  Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications. See figure 5, detail F for other roof top mounting considerations.
NOTICE
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
6 (152)
12 (305)
36 (914)
ACCESS PANEL
CONTROL PANEL
ACCESS
LOCATION
30 (762)
LINE SET CONNECTIONS
NOTES:
S Clearance to one of the other three
sides must be 36 inches (914mm).
S Clearance to one of the remaining
two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
MINIMUM CLEARANCE BETWEEN TWO UNITS
24
(610)
Figure 4. Installation Clearances
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
Page 6
Page 7
DETAIL A
Install unit away from windows.
 Outside Unit Placement
DETAIL B
Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure.
 Slab Mounting at Ground Level
BUILDING
STRUCTURE
MOUNTING SLAB
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
Elevated Slab Mounting
DETAIL C
LEG DETAIL
2" (50.8MM) SCH 40
FEMALE THREADED
2" (50.8MM) SCH 40
MALE THREADED
Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.
DETAIL E
using Feet Extenders
ADAPTER
ADAPTER
 Deck Top Mounting
BASE
GROUND LEVEL
DETAIL D
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL  2" WIDTH; HEIGHT AS
#10 1−1/4" LONG HEX HD SCREW
Concrete slab  use two plastic anchors (hole drill 1/4")
Wood or plastic slab  no plastic anchor (hole drill 1/8")
Stabilizing bracket (18 gauge metal  2" (50.8mm) width; height as required); bend to form right angle as exampled below.
DETAIL F
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated.
 Slab Side Mounting
COIL
BASE PAN
REQUIRED)
AND FLAT WASHER
CORNER POST
 Roof Top Mounting
PREVAILING WINTER WINDS
WIND BARRIER
INLET AIR
One bracket per side (minimum). For extra stability, two brackets per side, two inches (51mm) from each corner.
SAME FASTENERS AS SLAB SIDE MOUNTING.
Figure 5. Placement, Slab Mounting and Stabilizing Unit
MINIMUM ONE
PER SIDE
FOR EXTRA
STABILITY
Page 7
INLET AIR
INLET AIR
INLET AIR
XP16 SERIES
Page 8
Removing and Installing Panels
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly.
2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in detail A.
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as possible. Then, in a continuous motion:
1. Slightly rotate and guide the lip of top tab inward as
illustrated in detail A and C; then upward into the top slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes.
4. When panel is correctly positioned and aligned, insert the screws and tighten.
Detail C
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
SCREW
LIP
HOLES
Detail A
Detail B
ROTATE IN THIS DIRECTION;
ANGLE MAY BE TOO EXTREME
THEN DOWN TO REMOVE
HOLD DOOR FIRMLY TO THE HINGED
PANEL
SIDE TO MAINTAIN
FULLY−ENGAGED TABS
PREFERRED ANGLE FOR INSTALLATION
Detail D
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
Figure 6. Removing and Installing Panels
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
Page 8
Page 9
Line Set Requirements
This section provides information on: installation of new or replacement line set.
S Adding Polyol ester oil requirements S New or replacement line set installation S Using existing line set.
ADDING POLYOL ESTER OIL REQUIREMENTS
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil
must be added, it must be a Polyol Ester oil.
The compressor is charged with sufficient Polyol Ester oil (POE) for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. Systems with 20 pounds or less of refrigerant required no oil to be added.
For systems over 20 pounds − add one ounce for every five (5) pounds of HFC−410A refrigerant.
Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.
NEW OR REPLACEMENT LINE SET INSTALLATION
Field refrigerant piping consists of both liquid and vapor lines from the outdoor unit to the indoor coil. Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as specified in table 2.
If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 7 for recommended installation practices.
NOTE  When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following information:
Table 2. Refrigerant Line Set  Inches (mm)
Model
XP16−024−230 3/8" (10 mm) 3/4" (19 mm) 3/8" (10 mm) 3/4" (19 mm) L15−41  15 ft. − 50 ft. (4.6m − 15 m)
XP16−036−230
XP16−048−230
XP16−060−230 3/8" (10 mm) 1−1/8" (29 mm) 3/8" (10 mm) 1−1/8" (29 mm) Field Fabricated
NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter
Liquid Line Suction Line Liquid Line Suction Line L15 Line Set
3/8" (10 mm) 7/8" (22 mm) 3/8" (10 mm) 7/8" (22 mm) L15−65  15 ft. − 50 ft. (4.6 m − 15 m)
Field Connections Recommended Line Set
S Model (XP16) and size of unit (e.g. −036).
S Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
S Number of elbows vertical rise or drop in the piping.
USING EXISTING LINE SET
Things to consider:
S Liquid line that meter the refrigerant, such as RFC1
liquid line, must not be used in this application.
S Existing line set of proper size as listed in table 2 may
be reused.
S If system was previously charged with HCFC−22
refrigerant, then existing line set must be flushed (see Flushing Line Set and Indoor Coil on page 14).
If existing line set is being used, then proceed to Brazing Connections on page 11.
IMPORTANT
Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing Line Set and Indoor Coil on page
13.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
Page 9
XP16 SERIES
Page 10
Line Set Isolation  The following illustrations are examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL STUD
NON−CORROSIVE
METAL SLEEVE
AUTOMOTIVE
MUFFLER-TYPE HANGER
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
VAPOR LINE − WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
VAPOR LINE
SLEEVE
CAULK
LIQUID LINE
NOTE  Similar installation practices should be used if line set is to be installed on exterior of outside wall.
LIQUID LINE
WIRE TIE
INSIDE WALL
STRAP
NON−CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
FLOOR JOIST OR
ROOF RAFTER
Figure 7. Line Set Installation
Page 10
Page 11
Brazing Connections
Use the procedures outline in figures 8 and 9 for brazing line set connections to service valves.
WARNING
Polyol Ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture − Check the high and low pressures before applying heat.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver alloy for copper−to−copper brazing. Use 45% minimum alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex­plosion, that could result in property damage, personal injury or death.
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well−ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
Page 11
XP16 SERIES
Page 12
CUT AND DEBUR
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
CAP AND CORE REMOVAL
Remove service cap and core from
2
both the suction / vapor and liquid line service ports.
SERVICE PORT
CAP
SERVICE
PORT CORE
LIQUID LINE SERVICE
VALV E
SERVICE
PORT
CORE
SERVICE PORT CAP
SUCTION / VAPOR LINE
SERVICE VALVE
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve.
A Connect gauge set low pressure side to
liquid line service valve (service port).
B Connect gauge set center port to bottle of
nitrogen with regulator.
C Remove core from valve in suction / vapor
line service port to allow nitrogen to escape.
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
ATTACH
GAUGES
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
SERVICE
VALV E
VALV E
HIGHLOW
B
OUTDOOR
UNIT
WHEN BRAZING LINE SET TO
A
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
NITROGEN
Figure 8. Brazing Procedures
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Page 12
Page 13
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
5
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections
BRAZE LINE SET
Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water
6
saturated cloths must remain water saturated throughout the brazing and cool−down process.
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT  Allow braze joint to cool. Apply
additional water saturated cloths to help cool brazed joint. Do not remove water saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
LIQUID LINE
WATER SATURATED CLOTH
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE may result if you do not wrap a water
saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
2. Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated. Refer to procedures provided in this supplement.
SUCTION / VAPOR LINE
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both
7
service valves to cool piping. Once piping is cool, remove all water saturated cloths.
SUCTION / VAPOR LINE
SERVICE VALVE
WATER SATURATED CLOTH
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Figure 9. Brazing Procedures (continued)
Page 13
XP16 SERIES
Page 14
Indoor Refrigerant Metering Device Removal and Flushing Line Set and Indoor Coil
Flushing is only required when the existing system used HCFC−22 refrigerant. If the existing system used HFC−410a, then remove the original indoor coil metering device and proceed to Installing New Indoor Metering Device on page 15.
TYPICAL EXISTING FIXED ORIFICE
1A
DISTRIBUTOR
ASSEMBLY
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor as-
sembly.
C Using two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro­cess.
D Remove and discard fixed orifice, valve stem assembly if present and
Teflon® washer as illustrated above.
E Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
TEFLON® RING
FIXED ORIFICE
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE (UNCASED
OR
BRASS NUT
1B
TWO PIECE PATCH PLATE
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
RECOVERY
CYLINDER
LIQUID
VAPOR
OUTDOOR
B
NEW
UNIT
OPENED
C
D
RECOVERY MACHINE
A Inverted HCFC−22 cylinder with clean refrigerant to the vapor service
valve.
B HCFC−22 gauge set (low side) to the liquid line valve. C HCFC−22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.
D Connect recovery tank to recovery machines per machine instructions.
GAUGE
MANIFOLD
LOW HIGH
CLOSED
TANK RETURN
INLET
DISCHARGE
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
®
SENSING
LINE
LIQUID
(UNCASED COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line. D Remove the vapor line sensing bulb. E Disconnect the liquid line from the check expansion valve at the liquid
line assembly. F Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process. G Remove and discard check expansion valve and the two Teflon® rings. H Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
LIQUID LINE
SENSING BULB
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
3
same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
A Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line
B
set and indoor unit coil.
B Invert the cylinder of clean HCFC−22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull down to 0 the system.
D Close the valve on the inverted HCFC−22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
LINE
Figure 10. Removing Indoor Refrigerate Metering Device and Flushing Procedures
Page 14
Page 15
Installing New Indoor Metering Device
This outdoor unit is designed for use in HFC−410A systems that use a check / expansion valve metering device (purchased separately) at the indoor coil.
See the Lennox XP16 Engineering Handbook for approved check / expansion valve kit match−ups. The check / expansion valve device can be installed either internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the check / expansion valve in a manner that will provide access for field servicing of the check / expansion valve (see figure 11).
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS)
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON RING
EQUALIZER LINE
VAPOR
CHECK /
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
LINE
TEFLON
RING
SENSING
BRASS NUT
LIQUID LINE
Sensing bulb insulation is required if mounted external to the coil casing.
EQUALIZER LINE INSTALLATION
Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
®
LINE
A Remove the field−provided fitting that temporarily
reconnected the liquid line to the indoor unit’s distributor assembly.
B Install one of the provided Teflon® rings around the
stubbed end of the check / expansion valve and lightly lubricate the connector threads and expose surface of the Teflon® ring with refrigerant oil.
C Attach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft−lb.
D Place the remaining Teflon® washer around the other
end of the check / expansion valve. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
E Attach the liquid line assembly to the check / expansion
valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft−lb.
SENSING BULB INSTALLATION
A Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and screws provided.
NOTE  Confirm proper thermal contact between vapor line and expansion bulb before insulating the sensing bulb once installed.
B Connect the equalizer line from the check / expansion
valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.
VAPOR LINE
BULB
12
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
BULB
®
1/2 Turn
11
10
9
8
7
1/8 Turn
11
10
9
8
7
12
1
2
3
4
5
6
12
1
2
3
4
5
6
FLARE SEAL CAP
OR
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
VAPOR LINE
VAPOR LINE
12
BULB
NOTE  NEVER MOUNT ON BOTTOM OF LINE.
Figure 11. Installing Indoor Check / Expansion Valve
Page 15
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
XP16 SERIES
Page 16
Leak Test Line Set and Indoor Coil
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
CONNECT GAUGE SET
A Connect an HFC−410A manifold gauge set high pressure hose to the
vapor valve service port.
NOTE  Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of HFC−410A
refrigerant to the center port of the manifold gauge set.
NOTE  Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
NITROGEN
Figure 12. Manifold Gauge Set Connections for Leak Testing
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
1. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC−410A cylinder (vapor only).
2. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the
HFC−410A cylinder and the valve on the high pressure
HFC−410A
B
TO VAPOR
SERVICE VALVE
A
side of the manifold gauge set. Disconnect the HFC−410A cylinder.
3. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
4. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
5. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
6. After leak testing disconnect gauges from service ports.
Page 16
Page 17
Evacuating Line Set and Indoor Coil
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
CONNECT GAUGE SET
NOTE  Remove cores from service valves (if not already done).
1
A Connect low side of manifold gauge set
with 1/4 SAE in−line tee to vapor line service valve
B Connect high side of manifold gauge
set to liquid line service valve
C Connect micron gauge available
connector on the 1/4 SAE in−line tee.
D Connect the vacuum pump (with
vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC−410A and nitrogen containers.
NITROGEN
HFC−410A
VACUUM PUMP
OUTDOOR
UNIT
A
B
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
C
MICRON
GAUGE
MANIFOLD
GAUGE SET
TO VAPOR
SERVICE VALVE
TO LIQUID LINE SERVICE VALVE
D
EVACUATE THE SYSTEM
A Open both manifold valves and start the vacuum pump.
2
B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
S Close manifold gauge valves S Close valve on vacuum pump and turn off vacuum pump S Disconnect manifold gauge center port hose from vacuum pump S Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. S Open manifold gauge valves to break the vacuum in the line set and indoor unit. S Close manifold gauge valves.
D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
G Perform the following:
S Close manifold gauge valves. S Shut off HFC−410A cylinder. S Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
S Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.
RECOMMEND
MINIMUM 3/8" HOSE
10
9
11
8
1/6 TURN
12
7
6
HIGHLOW
1
2
3
4
5
Figure 13. Evacuating Line Set and Indoor Coil
Page 17
XP16 SERIES
Page 18
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
Electrical Connections
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
1
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
MAIN FUSE BOX/ BREAKER PANEL
DISCONNECT
SWITCH
NOTE  Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
2
approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE  24VAC, Class II circuit connections are made in the control panel.
Page 18
Page 19
LOW VOLTAGE CONNECTIONS
3
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.
NOTE − For proper voltages, select thermostat wire (control wires) gauge per table above.
C
CUTOUT WITH
A
Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated. See figures 14 and 15 for typical field connections when connecting unit to either a CBX32MV or CBX40UHV in non−communicating mode. For connections to other Lennox air handlers or furnaces, see the ComfortSense® 7000 installation instruction for further match component wiring illustrations.
GROMMET
24V CONTROL WIRES
B
D
NOTE − Do not bundle any excess 24VAC control wires inside control box.
A Run 24VAC control wires through cutout with grommet. B Run 24VAC control wires through wire tie. C Make 24VAC control wire connections. D Tighten wire tie to security 24V control wiring.
NOTE − Wire tie provides low voltage wire strain relief and to maintain separation of field installed low and high voltage circuits.
TIGHTEN WIRE TIE
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE (24V) FIELD WIRING
HIGH VOLTAGE POWER SUPPLY CONNECTIONS
4
GROUND
NOTE − Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring.
NOTE − To facilitate a conduit, a cutout is lo­cated in the bottom of the control box. Connect conduit to the control box using a proper con­duit fitting.
G
OUTDOOR UNIT
CONTROL BOX
L1
L2
CONDUIT
CUTOUT
CONDUIT
Page 19
XP16 SERIES
Page 20
HEAT PUMP UNIT
(TWO−STAGE)
R
W1
L
Y1
Y2
OUT
BL
CC
CBX32MV
OR
CBX40UHV
RR
W3
W2
W1 W1
2
Y1
G
DS
3
Y2
Figure 14. Typical Field Wiring  Heat Pump Application with CBX32MV or CBX40UHV
COMFORTSENSET
7000
H
W2
1
O. D.
SENSOR
OO
O
(X2658)
L
Y1
Y2Y2
G
D
T
B
T
C
X2658 OUTDOOR SENSOR IS REQUIRED FOR OUTDOOR TEMPERATURE DISPLAY, DEW POINT CONTROL, HEAT PUMP AND
1
DUAL FUEL BALANCE POINTS.
CONNECTED ON UNIT WITH LSOM. RESISTOR KIT (CAT # 47W97)
2
IS REQUIRED WHEN CONNECTING THE COMFORTSENSE 7000 WITH THE LSOM 2.
3
FIELD PROVIDED JUMPER BETWEEN Y2 OUT BL ON HEAT PUMP TO Y2 ON CBX40UHV.
IMPORTANT − USE CARE WHEN CUTTING LINKS TO
PREVENT DAMAGE TO CONTROL. SEE CBX40UHV
INSTALLATION INSTRUCTION FOR FURTHER DETAILS.
CUT ON−BOARD LINK Y1−Y2 FOR TWO−STAGE HP
CUT ON−BOARD LINK R −O.
CUT ON−BOARD LINK R−DS WHEN DEHUMIDIFICATION TERMINAL IS USED.
AIR HANDLER CONTROL
Y1−Y2
2−STAGE
COMPR
R−O
HEAT
PUMP
R−DS
DEHUM
OR
HARMONY
CUT FOR OPTION
OUTDOOR UNIT
RED
FAN RELAY (NOT REQUIRED WITH SINGLE−SPEED OUTDOOR FAN)
PURPLE
BLACK
YELLOW
BLUE
BROWN (NOT USED FOR APPLICATIONS WITHOUT LSOM
BLUE (NOT REQUIRED FOR SINGLE STAGE)
RESISTOR KIT (CAT # 47W97) IS REQUIRED WHEN CONNECTING THE COMFORTSENSE 7000 WITH THE LSOM 2.
CBX32MV OR
CBX40UHV
RED
BLACK
PURPLE
IMPORTANT − USE CARE WHEN CUTTING LINKS TO
PREVENT DAMAGE TO CONTROL. SEE CBX40UHV
INSTALLATION INSTRUCTION FOR FURTHER DETAILS.
CUT ON−BOARD LINK Y1−Y2 FOR TWO−STAGE A/C ONLY
CUT ON−BOARD LINK R−DS WHEN DEHUMIDIFICATION
COMFORTSENSEt 7000 THERMOSTAT
CUT ON−BOARD LINK R −O.
TERMINAL IS USED.
OUTDOOR
SENSOR
T
T
(X2658)
AIR HANDLER CONTROL
Y1−Y2
2−STAGE
COMPR
PUMP
DEHUM
HARMONY
R−O
HEAT
R−DS
OR
CUT FOR OPTION
Figure 15. Heat Pump Application  Humiditrol
CBX32MV or CBX40UHV
Page 20
®
and Second−Stage Outdoor Fan Relay Wiring with
Page 21
Figure 16. Typical Unit Wiring Diagram (−024, −036 and −048 Only)
Page 21
XP16 SERIES
Page 22
Figure 17. Typical Unit Wiring Diagram (−060 Only)
Page 22
Page 23
Figure 18. Typical Factory Wiring Diagram (No Field Modifications)
Unit Start−Up
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
UNIT START−UP
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose connections.
3. Verify that the manifold gauge set is connected as illustrated in figure 21. Use a temperature sensor positioned near the liquid line service port as illustrated in figure 21 which will be required later when using the subcooling method for optimizing the system refrigerant charge.
4. Replace the stem caps and tighten to the value listed in table 1.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you
have consulted with the power company and the voltage condition has been corrected.
6. Open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system.
7. Use figure 19 to determine next step in system preparation.
OPEN BOTH VAPOR AND LIQUID SERVICE
VALVE STEMS TO RELEASE
REFRIGERANT FROM OUTDOOR UNIT TO
GO TO SERVICE AND WEIGH
IN REFRIGERANT CHARGE
FOR OUTDOOR UNITS
DELIVERED VOID OF CHARGE
ON PAGE 24.
SYSTEM.
REFRIGERANT
PRESENT
YESNO
GO TO OPTIMIZING SYSTEM REFRIGERANT CHARGE ON
PAGE 26.
Figure 19. Outdoor Unit Factory Charge
Page 23
XP16 SERIES
Page 24
Service and Weigh In Refrigerant for Outdoor Units Delivered Void of Charge
The following procedures are only required if it has been determine that the new outdoor unit is void of charge. Skip to the next section if refrigerant charge is present.
LEAK CHECK, REPAIR AND EVACUATE
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Leak check system using procedures provided on page 16. Repair any leaks discovered during leak test.
2. Evacuate the system using procedure provided in figure 13.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again using procedure in figure
12.
CONNECT MANIFOLD GAUGE SET AND WEIGH IN CHARGE
After the evacuation procedure, reconnect the manifold gauge set as illustrated in figure 21.
NOTE − Temperature sensor illustrated in figure 21 is not required for initial system weigh in charging.
1. Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.
2. Connect the manifold gauge set’s low pressure side to
the true suction port.
3. Connect the manifold gauge set’s high pressure side
to the liquid line service port.
4. Connect the center hose of the gauge set to a cylinder of HFC−410A and purge the hose. Then, place the cylinder upside down on a scale.
5. Check that fan rotates freely.
6. Inspect all factory− and field−installed wiring for loose connections.
7. Open the high side manifold gauge valve and weigh in liquid refrigerant. Use figure 20 in calculating the correct weigh−in charge.
8. Close manifold gauge valves.
9. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the bi−flow filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future.
10. Continue to Optimizing System Refrigerant Charge
on page 26 to optimize the system charge using subcooling method.
WEIGH−IN CHARGING
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refrigerant charge:
Amount specified on
nameplate
Adjust amount. for variation in line set
length listed on line set length table below.
+
Refrigerant Charge per Line Set Length
LIQUID LINE SET DIAMETER
3/8" (9.5 MM)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE  The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET
Figure 20. Using HFC−410A Weigh In Method
Additional charge specified per indoor
unit match listed on page 28.
+
(4.6 M) LINE SET*
3 OUNCE PER 5’ (85 G PER 1.5 M)
Total Charge
=
Page 24
Page 25
MANIFOLD GAUGE SET
GAUGE SET
CONNECTIONS FOR OPTIMIZING SYSTEM CHARGE
TRUE SUCTION PORT
B
CONNECTION
NOTE  Refrigerant tank should be turned right−side−up to deliver vapor during charge optimizing procedure.
CHARGE IN
LIQUID PHASE
DIGITAL SCALE
D
INSIDE OUTDOOR UNIT
TEMPERATURE SENSOR (USE FOR
SUBCOOLING METHOD)
A Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.
B Connect the manifold gauge set’s low pressure side to the true suction port.
C Connect the manifold gauge set’s high pressure side to the liquid line service port.
D Position temperature sensor on liquid line near liquid line service port (use only for subcooling method).
LOW
REFRIGERANT
TANK
A
TO LIQUID
LINE SERVICE
VALV E
C
HIGH
TEMPERATURE SENSOR
(LIQUID LINE)
OUTDOOR UNIT
Figure 21. Gauge Set Connections for Adding Refrigerant
OUTDOOR UNIT
CHECK / EXPANSION
VALV E
BI−FLOW FILTER / DRIER
LIQUID LINE
SERVICE PORT
MUFFLER
NOTE − Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines and indoor coil. Use true suction port to measure vapor pressure during charging.
DISTRIBUTOR
OUTDOOR
COIL
COMPRESSOR
REVERSING VALVE
TRUE SUCTION PORT
VAPOR
SERVICE
PORT
CHECK / EXPANSION VALVE
Figure 22. Heat Pump Cooling Cycle
NOTE − ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
INDOOR UNIT
INDOOR
COIL
Page 25
XP16 SERIES
Page 26
Optimizing System Refrigerant Charge
This section provides instructions on optimizing the system charge. This section includes:
S Optimizing procedure S Adjusting indoor airflow S Using subcooling method S Approved matched components, targeted subcooling
(SC) values and add charge values
S Normal operating pressures S Temperature pressures
OPTIMIZING PROCEDURE
1. Move the low−side manifold gauge hose from the vapor line service valve to the true suction port (see figure 21).
2. Set the thermostat for either cooling or heating demand. Turn on power to the indoor unit and close the outdoor unit disconnect switch to start the unit.
3. Allow unit to run for five minutes to allow pressures to stabilize.
4. Check the airflow as instructed under Adjusting Indoor Airflow to verify or adjust indoor airflow for maximum
efficiency. Make any air flow adjustments before continuing with the optimizing procedure.
5. Use subcooling method to optimize the system
charge (see figure 24). Adjust charge as necessary.
ADJUSTING INDOOR AIRFLOW
Heating Mode Indoor Airflow Check
(Only use when indoor unit has electric heat)
Indoor blower airflow (CFM) may be calculated by energizing electric heat and measuring:
S Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
S Measuring voltage supplied to the unit, S Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in the following formula to determine CFM:
CFM =
Check airflow using the Delta−T (DT) process using figure
23.
Amps x Volts x 3.41
1.08 x Temperature rise (F)
Cooling Mode Indoor Airflow Check
Temp. of air entering indoor coil ºF
A
Wet−bulb ºF
53º
DRY
BULB
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
Dry−bulb
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
C
Drop
19º
All temperatures are expressed in ºF
ADJUSTING INDOOR AIRFLOW
DT
B
A
72º
air flowair flow
INDOOR COIL
B
64º
WET
BULB
DRY
BULB
Figure 23. Checking Airflow over Indoor Coil Using Delta−T Formula
1. Determine the desired DTMeasure entering air temper-
ature using dry bulb (A) and wet bulb (B). DT is the intersect­ing value of A and B in the table (see triangle).
2. Find temperature drop across coilMeasure the coil’s dry
bulb entering and leaving air temperatures (A and C). Tem­perature Drop Formula: (T
3. Determine if fan needs adjustmentIf the difference between
the measured T +
3º, no adjustment is needed. See examples: Assume DT =
and the desired DT (T
Drop
) = A minus C.
Drop
15 and A temp. = 72º, these C temperatures would necessi­tate stated actions:
T
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
4. Adjust the fan speedSee indoor unit instructions to in-
DT = ºF ACTION
Drop
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck tempera­tures to confirm that the temperature drop and DT are within
3º.
+
DT) is within
Drop
Page 26
Page 27
OPTIMIZE CHARGE USING SUBCOOLING METHOD
1. Check liquid and vapor line pressures. Compare pressures with either second−stage heat or cooling mode normal operating pressures listed in table 7. Table 7 is a general guide and expect minor pressures variations. Significant pressure differences may indicate improper charge or other system problem.
USE
COOLING
MODE
60ºF
(15ºC)
USE
HEATING
MODE
2. Decide whether to use cooling or heating mode based on current outdoor ambient temperature:
A Use COOLING MODE when:
S Outdoor ambient temperature is 60°F (15.5°C) and above. S Indoor return air temperature range is between 70 to 80°F (21−27°C). This
temperature range is what the target subcooling values are base upon in tables 3 through 6.
If indoor return air temperature is not within reference range, set thermostat to cooling mode and a setpoint of 68ºF (20ºC). This should place the outdoor unit into second−stage (high−capacity) cooling mode. When operating and temperature pressures have stabilized, continue to step 3.
B Use HEATING MODE when:
S Outdoor ambient temperature is 59°F (15.0°C) and below. S Indoor return air temperature range is between 65−75°F (18−24°C). This
temperature range is what the target subcooling values are base upon in tables 3 through 6.
If indoor return air temperature is not within reference range, set thermostat to heating mode and a setpoint of 77ºF (25ºC). This should place the outdoor unit into second−stage (high−capacity) heating mode. When operating and temperature pressures have stabilized, continue to step 3.
3. Read the liquid line pressure; then find its corresponding temperature pressure listed in table 8 and record it in the SATº space to the left.
SATº
LIQº
SCº =
4. Read the liquid line temperature; record in the LIQº space to the left.
5. Subtract LIQº temperature from SATº temperature to determine subcooling; record it in SCº space to the left..
6. Compare SCº results with tables 3 through 6 (either Heating or Cooling mode column), also consider any additional charge required for line set lengths longer than 15 feet and/or unit matched component combinations (Add Charge column).
7. If subcooling value is:
A GREATER than shown for the applicable unit match component, REMOVE
refrigerant;
B LESS than shown for the applicable unit match component, ADD refrigerant.
8. If refrigerant is added or removed, repeat steps 3 through 6 to verify charge.
9. Close all manifold gauge set valves and disconnect gauge set from outdoor unit.
10. Replace the stem and service port caps and tighten as specified in Operating Service Valves on page 2.
11. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
Figure 24. Using HFC−410A Subcooling Method  Second Stage (High Capacity)
Page 27
XP16 SERIES
Page 28
APPROVED MATCHED SYSTEM COMPONENTS, TARGETED SUBCOOLING (SC) VALUES AND
ADD CHARGE VALUES
Listed below are the approved matched system components (air handlers and indoor coils), targeted subcooling and add charge values for the XP16. This information is also listed on the unit charging sticker located on the outdoor unit
access panel.
Subcooling values listed in the following tables are based on outdoor ambient air temperature of:
S 60°F (15.5°C) and above for cooling mode S 59°F (15.0°C) and below for heating mode.
Table 3. XP16024230
Heating
Indoor Air Handers and Coils
CBX26UH−024 45 6 0 15
CBX27UH−024−230 20 7 0 9
CBX27UH−030−230 17 7 1 3
CBX32MV−024/030 20 7 0 9
CBX32MV−036 17 7 1 3
CBX40UHV−024 17 7 1 3
CBX40UHV−030 17 7 1 3
CBX40UHV−036 17 7 1 3
CH33−31B 31 8 1 12
CR33−30/36A/B/C 45 4 0 0
CX34−31A/B 24 7 1 11
CX34−38A/B 18 8 1 10
Mode
+5ºF
Subcooling lb. oz.
Table 4. XP16036230
Heating
Indoor Air Handers and Coils
CBX26UH−036 50 5 0 0
CBX27UH−036−230 22 7 0 9
CBX27UH−042−230 24 11 3 0
CBX32M−036 22 7 0 9
CBX32MV−036 22 7 0 9
CBX32MV−048 24 11 3 0
CBX40UHV−030 22 7 0 9
CBX40UHV−036 22 7 0 9
CBX40UHV−042 24 11 3 0
CBX40UHV−048 24 11 3 0
CH33−43B 13 10 2 7
CH33−48C 37 11 2 11
CH33−43C 37 11 2 11
CR33−48B/C 49 7 0 9
CX34−43B/C 29 9 2 11
CX34−50/60C 29 9 2 11
Mode
+5ºF
Subcooling lbs. oz.
Cooling
Mode
+1ºF
Cooling
Mode
+1ºF
*Add Charge
*Add Charge
Indoor Air Handers and Coils
CBX26UH−048−230 10 8 1 4
CBX27UH−048−230 19 9 1 4
CBX27UH−060−230 13 14 3 3
CBX32M−048 19 9 1 4
CBX32M−060 14 9 1 11
CBX32MV−048 19 9 1 4
CBX32MV−060 14 9 1 11
CBX32MV−068 9 8 1 11
CBX40UHV−048 19 9 1 4
CBX40UHV−060 14 9 1 11
CH23−68 24 10 1 12
CH33−49C 19 9 2 5
CH33−50/60C 19 9 2 5
CH33−60D 13 8 0 0
CH33−62D 11 9 1 4
CR33−50/60C 15 7 0 10
CR33−60D 15 7 0 10
CX34−60D 14 8 1 0
CX34−62D 9 9 1 6
CX34−62C 8 9 1 9
Indoor Air Handers and Coils
CBX26UH−060 20 9 4 13
CBX27UH−060−230 10 6 2 3
CBX32M−060 17 6 1 12
CBX32MV−060 17 6 1 12
CBX32MV−068 15 7 2 1
CBX40UHV−060 17 6 1 12
CH23−682 37 9 2 10
CH33−50/60C 33 8 1 0
CH33−62D 15 7 1 4
CR33−50/60C 24 7 0 0
CR33−60D 24 7 0 0
CX34−62C 21 9 2 16
CX34−62D 13 7 1 4
*Amount of charge required in additional to charge shown on unit nameplate. (Remember to consider line set length difference.)
Table 5. XP16048230
Heating
Mode
+5ºF
Subcooling lbs. oz.
Cooling
Mode
+1ºF
Table 6. XP16060230
Heating
Mode
+5ºF
Subcooling lbs. oz.
Cooling
Mode
+1ºF
*Add Charge
*Add Charge
Page 28
Page 29
NORMAL OPERATING PRESSURES
Use the following tables to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Typical pressures only, expressed in psig (liquid +/− 10 and vapor +/− 5 psig); matched indoor component (air handler or coil), indoor air quality, and indoor load will cause the pressures to vary.
Table 7. Normal Operating Pressures*
Normal Operating Pressures − Cooling
XP16 −024 −036 −048 −060
F
(C)**
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
65
(18.3)
75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
50
(10)
60
(15.5)
20
(−7.0)
30
(−1.0)
40
(4.4)
50
(10)
60
(15.5)
** Temperature of air entering outdoor coil.
Liq Vap Liq Vap Liq Vap Liq Vap
First Stage (Low Capacity) Pressure
226 144 220 141 224 143 230 137
260 145 254 144 259 143 267 139
301 148 295 148 302 147 311 141
346 151 340 150 346 149 357 144
396 153 389 153 396 152 398 147
451 156 444 156 450 155 453 149
Second Stage (High Capacity) Pressure
241 140 232 129 238 138 232 131
279 142 269 136 278 140 276 133
321 144 312 140 321 142 320 136
369 146 346 142 372 144 367 138
421 148 409 145 424 147 421 141
480 151 465 148 481 149 479 144
Normal Operating Pressures − Heating
First Stage (Low Capacity) Pressure
312 112 350 115 336 114 385 108
330 130 372 136 363 135 414 126
Second Stage (High Capacity) Pressure
299 64 321 61 289 57 332 59
312 79 347 74 294 69 349 67
325 93 367 90 321 80 361 75
344 110 387 110 341 110 383 85
358 128 395 131 361 128 425 122
TEMPERATURE PRESSURES
Compute subcooling by determining saturated condensing temperature from temperature pressure chart. Subtract from liquid temperature entering TXV.
Table 8. HFC−410A Temperature (°F) −
Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig
32 100.8 63 178.5 94 290.8 125 445.9
33 102.9 64 181.6 95 295.1 126 451.8
34 105.0 65 184.3 96 299.4 127 457.6
35 107.1 66 187.7 97 303.8 128 463.5
36 109.2 67 190.9 98 308.2 129 469.5
37 111.4 68 194.1 99 312.7 130 475.6
38 113.6 69 197.3 100 317.2 131 481.6
39 115.8 70 200.6 101 321.8 132 487.8
40 118.0 71 203.9 102 326.4 133 494.0
41 120.3 72 207.2 103 331.0 134 500.2
42 122.6 73 210.6 104 335.7 135 506.5
43 125.0 74 214.0 105 340.5 136 512.9
44 127.3 75 217.4 106 345.3 137 519.3
45 129.7 76 220.9 107 350.1 138 525.8
46 132.2 77 224.4 108 355.0 139 532.4
47 134.6 78 228.0 109 360.0 140 539.0
48 137.1 79 231.6 110 365.0 141 545.6
49 139.6 80 235.3 111 370.0 142 552.3
50 142.2 81 239.0 112 375.1 143 559.1
51 144.8 82 242.7 113 380.2 144 565.9
52 147.4 83 246.5 114 385.4 145 572.8
53 150.1 84 250.3 115 390.7 146 579.8
54 152.8 85 254.1 116 396.0 147 586.8
55 155.5 86 258.0 117 401.3 148 593.8
56 158.2 87 262.0 118 406.7 149 601.0
57 161.0 88 266.0 119 412.2 150 608.1
58 163.9 89 270.0 120 417.7 151 615.4
59 166.7 90 274.1 121 423.2 152 622.7
60 169.6 91 278.2 122 428.8 153 630.1
61 172.6 92 282.3 123 434.5 154 637.5
62 175.4 93 286.5 124 440.2 155 645.0
Page 29
XP16 SERIES
Page 30
System Operation
IMPORTANT
Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPRESSOR.
This section addresses:
S Unit components (sensors, temperature switch,
pressure switches and demand defrost control)
S Second−stage operation
TEST PINS (P1)
DEFROST TERMINATION
PIN SETTINGS (P1)
SENSOR PLUG IN
(COIL AND
AMBIENT
SENSORS) (P4)
UNIT COMPONENTS
Demand Defrost Control (A108)
The demand defrost control measures differential temperatures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates when the defrost system starts and after each system defrost cycle. The demand defrost control’s: components are shown in figure 25.
S Demand defrost control connections, jumpers and
LED locations are shown in figure 25.
S Demand defrost control connections, jumpers and
LED descriptions are listed on table 9.
S Demand defrost control status, fault and lockout LEDs
are listed in table 10.
LOW AMBIENT THERMOSTAT PINS (P3)
DELAY PINS
(P5)
REVERSING VALVE
(O OUT)
PRESSURE SWITCH
CIRCUIT
CONNECTIONS
DIAGNOSTIC LEDS (DS1 AND DS2)
24V TERMINAL STRIP CONNECTIONS (P2)
Note − Component locations vary by board manufacturer.
Figure 25. Demand Defrost Control (A108)
Page 30
Page 31
Table 9. Demand Defrost Control (A108) Inputs, Outputs and Configurable Settings
Control Locations
P1 TEST Test Mode See Test Mode on page 39 for further details.
P1 50, 70, 90, 100
P2
P3 55, 50, 45, 40
P4
P5 DELAY Delay Mode
P6 TST, PS DF, C, R, O, Y1, Y2 Factory Test Connectors No field use.
DS1 RED LED
DS2 GREEN LED
FAN TWO CONNECTORS Condenser Fan Operation These two connections provide power for the condenser fan.
O OUT O OUT 24 VAC output 24 VAC output connection for reversing valve.
LO−PS LO−PS Low−Pressure Switch
Control Label or Description
W1
C 24VAC Common 24VAC common
L Thermostat Service Light Thermostat service light connection.
R 24VAC 24VAC
Y2 Thermostat Input Controls the second stage operation of the unit.
O Thermostat Input Reversing valve solenoid.
Y1 Thermostat Input Controls the operation of the unit.
DIS−YEL Coil Sensor
AMB−BLACK Ambient Sensor
COIL−BROWN Discharge Sensor No discharge sensor is used; replaced by 10K resistor.
Purpose Function
Defrost Temperature Termination Shunt (Jumper) Pins
24VAC Thermostat Input / Output
Low Ambient Thermostat Pins
Diagnostic LED
The demand defrost control as illustrated in figure 25 has valid selections which are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C).
24VAC input / output from indoor thermostat to indoor unit.
Provides selection of the Y2 compressor lock−in temperature. Valid options are 40, 45, 50 and 55 degrees Fahrenheit.
(P4−5) Ground connection for outdoor coil temperature sensor. (P4−6) Connection for outdoor coil temperature sensor.
(P4−3) Ground connection for outdoor ambient temperature sensor. (P4−4) Connection for outdoor ambient temperature sensor.
The demand defrost control has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTEThe 30 second off cycle is NOT functional when TEST pins on P1 are jumpered.
Valid states for demand defrost control two LEDs are OFF, ON and FLASHING which indicate diagnostics conditions that are described in table 10.
When the low pressure switch trips, the demand defrost control will cycle off the compressor, and the strike counter in the demand defrost control will count one strike. The low pressure switch is ignored under the following conditions:
S during the defrost cycle and 90 seconds after the termination of
defrost
S when the average ambient sensor temperature is below 0°F (−18°C) S for 90 seconds following the start up of the compressor S during TEST mode
Y2 OUT Y2 OUT 24 VAC Output 24 VAC output for second stage compressor solenoid.
Y1 OUT Y1 OUT 24 VAC Common Output 24 VAC common output, switched for enabling compressor contactor.
When the high pressure switch trips, the demand defrost control will cycle
HS−PS HS−PS High−Pressure Switch
L L Service Light Output 24VAC service light output.
24V 24V 24 Volt output
off the compressor, and the strike counter in the demand defrost control will count one strike.
24VAC typically used to supply power to the Lennox System Operation Monitor (LSOM). Not used in this system.
Page 31
XP16 SERIES
Page 32
DEMAND DEFROST CONTROL (A108) DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the demand defrost control (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 10.
Table 10. Demand Defrost Control (A108) Diagnostic LEDs
DS1 and DS2 System Status, Fault and Lockout Codes
DS2 Green
DS1 Red
Type
Condition/Code Possible Cause(s) Solution
OFF OFF Status Power problem
Simultaneous SLOW Flash
Alternating SLOW Flash
Simultaneous FAST Flash
Alternating FAST Flash
ON ON Fault
OFF
SLOW Flash
Status Normal operation
Status 5−minute anti−short cycle delay
Fault Ambient Sensor Problem
Fault Coil Sensor Problem
Demand Defrost Control Failure
Fault Low Pressure Fault
OFF ON Lockout Low Pressure Lockout
SLOW Flash
OFF Fault High Pressure Fault
ON OFF Lockout High Pressure Lockout
1
No power (24V) to demand defrost control terminals R and C or demand defrost control failure.
Unit operating normally or in standby mode.
Initial power up, safety trip, end of room thermostat demand.
Check control transformer power (24V).
2
If power is available to demand defrost con­trol and LED(s) do not light, replace demand defrost control.
None required.
None required (jumper TEST pins to override)
Sensor being detected open or shorted or out of temperature range. Demand defrost control will revert to time/temperature defrost operation. (System will still heat or cool).
Sensor being detected open or shorted or out of temperature range. Demand defrost control will not perform demand or time/temperature defrost operation. (System will still heat or cool).
Indicates that demand defrost control has internal component failure. Cycle 24VAC power to demand defrost control. If code does not clear, replace demand defrost control.
1
1
Restricted air flow over indoor or outdoor coil.
2
Improper refrigerant charge in system.
3
Improper metering device installed or incorrect operation of metering device.
4
Incorrect or improper sensor location or connection to system.
Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using subcooling method.
3
Check system operating pressures and compare to unit subcooling tables in this instruction or located on unit access panel.
4
Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements.
SLOW Flash
ON Fault
Discharge Line Temperature Fault
This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 285ºF (140ºC) during compressor
operation, the demand defrost control will de−energize the compressor contactor FAST Flash
OFF
ON Lockout
Fast Flash
Fault Discharge Sensor Fault
Discharge Line Temperature Lockout
output (and the defrost output if active). The compressor will remain off until the
discharge temperature has dropped below 225ºF (107ºC).
The demand defrost control detects open sensor or out of temperature sensor range.
This fault is detected by allowing the unit to run for 90 seconds before checking
sensor resistance. If the sensor resistance is not within range after 90 seconds, the Fast Flash
OFF Lockout
Discharge Sensor Lockout
demand defrost control will count one fault. After 5 faults, the demand defrost control
will lockout.
(Each fault adds 1 strike to that code’s counter; 5 strikes per code = LOCKOUT)
Page 32
Page 33
High Pressure Switch (S4)
When the high pressure switch trips, the demand defrost control will cycle off the compressor, and the strike counter in the demand defrost control will count one strike. High Pressure (auto reset) − trip at 590 psig, reset at 418.
Low Pressure Switch (S87)
When the low pressure switch trips, the demand defrost control will cycle off the compressor, and the strike counter in the demand defrost control will count one strike. Low pressure switch (auto reset) − trip at 25 psig, reset at 40 psig.
The low pressure switch is ignored under the following conditions:
S During the defrost cycle and 90 seconds after the
termination of defrost
S When the average ambient sensor temperature is
below 15° F (−9°C)
S For 90 seconds following the start up of the
compressor
S During test mode
Ambient Sensor (RT13)
The ambient sensor considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sensor, the demand defrost control will not perform demand defrost operation. The demand defrost control will revert to time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Coil Sensor (RT21)
Coil SensorThe coil temperature sensor considers
outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the coil temperature sensor is detected as being open, shorted or out of the temperature range of the sensor, the demand defrost control will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
High Discharge Temperature Sensor (RT28)
If the discharge line temperature exceeds a temperature of 285°F (140°C) during compressor operation, the demand defrost control will de−energize the compressor contactor output (and the defrost output, if active). The compressor will remain off until the discharge temperature has dropped below 225°F (107°C) and the 5-minute anti−short cycle delay has been satisfied. This sensor has two fault and lockout codes:
1. If the demand defrost control recognizes five high discharge line temperature faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. This code detects shorted sensor or high discharge temperatures. Code on demand defrost control is Discharge Line Temperature Fault and Lockout.
2. If the demand defrost control recognizes five temperature sensor range faults during a single (Y1) compressor demand, it reverts to a lockout mode and displays the appropriate code. The demand defrost control detects open sensor or out-of-temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the demand defrost control will count one fault. After five faults, the demand defrost control will lockout. Code on demand defrost control is Discharge Sensor Fault and Lockout.
The discharge line sensor, which covers a range of 150°F (65°C) to 350°F (176°C), is designed to mount on a ½" refrigerant discharge line.
NOTE − Within a single room thermostat demand, if 5−strikes occur, the demand defrost control will lockout the unit. demand defrost control 24 volt power R must be cycled OFF or the TEST pins on demand defrost control must be shorted between 1 to 2 seconds to reset the demand defrost control.
Crankcase Heater (HR1) and Crankcase Thermostat
Switch (S40)
The reference models are equipped with a 70 watt, belly band type crankcase heater. HR1 prevents liquid from accumulating in the compressor. HR1 is controlled by a thermostat located on the liquid line. When liquid line temperature drops below 50° F the thermostat closes energizing HR1. The thermostat will open, de−energizing HR1 once liquid line temperature reaches 70° F .
Liquid Line Bi−Flow Filter Drier
The unit is equipped with a large−capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of like design and capacity. The replacement filter drier must be suitable for use with HFC−410A refrigerant.
The replacement filter drier must be suitable for use with HFC−410A refrigerant.
SECOND−STAGE OPERATION
If the demand defrost control (A108) receives a call for second−stage compressor operation Y2 in heating or cooling mode and the first-stage compressor output is active, the second-stage compressor solenoid output will be energized.
If first-stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock−in temperature, the second-stage compressor solenoid output will be energized without the Y2 input. If the jumper is not connected to one of the temperature selection pins on P3 (40, 45, 50, 55°F), the default lock−in temperature of 40°F (4.5°C) will be used.
The demand defrost control de−energizes the second-stage compressor solenoid output immediately when the Y2 signal is removed or the outdoor ambient temperature is 5°F above the selected compressor lock−in temperature, or the first-stage compressor output is de−energized for any reason.
Page 33
XP16 SERIES
Page 34
Defrost System
This section addresses:
S Emergency Heat S Defrost System Overview S Defrost Control Connections, Jumper Settings and
Features
S Operational Mode Overview (Calibration, Normal and
Defrost)
S Defrost Cycle Actuation
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of the outdoor unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shutdown, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent compressor slugging.
DEFROST SYSTEM OVERVIEW
The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE − The demand defrost control accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the demand defrost control initiates defrost cycles.
DEFROST CONTROL CONNECTIONS, JUMPERS SETTINGS AND FEATURES
Pressure Switch 5−Strike Lockout
The internal control logic of the demand defrost control counts the pressure switch trips only while the Y1 (Input) line is active. If a pressure switch opens and closes four times during a Y1 (Input), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The 5−strike pressure switch lockout condition can be reset by cycling OFF the 24−volt power to the demand defrost control or by shorting the TEST pins between 1 to 2 seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is engaged, a 5−minute short cycle will occur after the switch closes.
Demand Defrost Control Pressure Switch
Connections
The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the demand defrost control on the LO−PS and HI−PS terminals, respectively.
Demand Defrost Control Sensors
Sensors connect to the demand defrost control through a field-replaceable harness assembly that plugs into the demand defrost control as illustrated in figure 1. Through the sensors, the demand defrost control detects outdoor ambient, coil, and discharge temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes.
Testing Demand Defrost Control Sensors
Sensor resistance values can be checked by ohming across pins shown in table 11.
Table 11. Sensor Temperature /Resistance Range
Temperature
Sensor
Outdoor −35 (−37) to 120 (48) 280,000 to 3750 3 & 4
Coil −35 (−37) to 120 (48) 280,000 to 3750 5 & 6
Discharge (if applicable)
Note: Sensor resistance increases as sensed temperature decreases.
Range °F (°C)
24 (−4) to 350 (176) 41,000 to 103 1 & 2
Resistance values range (ohms)
Pins/W ire Color
(Black)
(Brown)
(Yellow)
Tables 12 and 13 shows how the resistance varies as the temperature changes for various types of sensors.
NOTE − When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 11, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced.
Defrost Temperature Termination Jumper
Settings (P1)
The demand defrost control selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If temperature shunt is not installed, default termination temperature is 90°F (32°C).
Test Pins (P1) Function
Placing the jumper on the field test pins (P1) allows the technician to:
S Clear short cycle lockout S Clear five−strike fault lockout S Cycle the unit in and out of defrost mode S Place the unit in defrost mode to clear the coil
See figure 27 for flowchart of test pin (P1) operations.
Page 34
Page 35
Compressor Delay Mode (P5)
The demand defrost control has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE − The 30 second off cycle is NOT functional when jumpering the TEST pins.
OPERATIONAL MODE OVERVIEW
The demand defrost control has three basic operational modes. Those modes are:
1. Calibration Mode  The demand defrost control is
considered uncalibrated when power is applied to the demand defrost control, after cool mode operation, or if the coil temperature exceeds the termination temperature when it is in heat mode (see figure 26 for further details).
2. Normal Mode  The demand defrost control monitors the O line, to determine the system operating mode (heat/cool), outdoor ambient temperature, coil temperature (outdoor coil) and compressor run time to determine when a defrost cycle is required.
Calibration of the demand defrost control occurs after a defrost cycle to ensure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle.
3. Defrost Mode  The following paragraphs provide a detailed description of the defrost system operation.
DEFROST CYCLE ACTUATION
The demand defrost control initiates a defrost cycle based on either frost detection or time.
1. Frost Detection  If the compressor runs longer than
30 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the demand defrost control, a defrost cycle will be initiated.
2. Time  If six hours of heating mode compressor run
time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
Actuation
When the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the demand defrost control logs the compressor run time. If the demand defrost control is not calibrated, a defrost cycle will be initiated after 30 minutes of heating mode compressor run time. The control will attempt to self−calibrate after this (and all other) defrost cycle(s).
Calibration success depends on stable system temperatures during the 20−minute calibration period. If the demand defrost control fails to calibrate, another defrost cycle will be initiated after 45 minutes of heating mode compressor run time. Once the demand defrost control is calibrated, it initiates a demand defrost cycle when the difference between the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control or after six hours of heating mode compressor run time has been logged since the last defrost cycle.
Termination
The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 30 minutes of run time.
Page 35
XP16 SERIES
Page 36
DEFROST CONTROL (A108) CALIBRATION MODE SEQUENCE
Occurs after power up and cooling operation, or if the coil temperature exceeds
Demand defrost control defaults to 30 minute  Time / Temperature Mode
Reset Compressor Runtime / Reset Three / Five Strike Counter
DEMAND MODE
Accumulate compressor runtime of more than 30 minutes while coil temperature is below 35° F (2°C). When the accumulated compressor time exceeds six (6) hours or if the coil sensor indicates frost is present on coil, go to Defrost.
the termination temperature while in Heat Mode.
THIRTY (30) MINUTE TIME /
TEMPERATURE MODE
Accumulate compressor runtime while coil temperature is below 35° F (2°C). When the accumulated compressor time exceeds 30 minutes go to Defrost.
DEFROST
S Outdoor Fan OFF S Reversing Valve ON S W1 line ON
Monitor coil temperature and
time in defrost mode.
TIME/TEMPERATURE MODE
45 MINUTE
Accumulate compressor runtime while coil temperature is below 35° F (2°C). When the accumulated compressor time exceeds 45 minutes go to Defrost.
HOW DID DEFROST TERMINATE?
Coil temperature was above 35°F (2°C) for four (4) minutes. of the 14−minute defrost OR reached defrost termination temperature.
DEFROST TERMINATION
S Compressor runtime counter RESET S Outdoor Fan ON S Reversing Valve OFF S W1 line OFF
Attempt to Calibration  Temperature measurements are not taken for the first few minutes of each heat demand. This is to allow coil temperatures to stabilize. demand defrost control has a maximum of 20 minutes of accumulated compressor runtime in heat mode to calibrate demand defrost control This may involve more than one heating demand.
YES  Calibration occurred
Was stable coil temperature attained within 20 minutes?
Defrosted for 14−minute without the coil temperature going above 35°F (2°C) for four (4) minutes and coil did not reach termination temperature.
DEFROST TERMINATION
S Compressor runtime counter RESET S Outdoor Fan ON S Reversing Valve OFF S W1 line OFF
NO  Demand defrost control reverts to 45 minute time / temperature.
Figure 26. Defrost Calibration
Page 36
Page 37
Table 12. Ambient (RT13) and Coil (RT21) Sensors Temperature / Resistance Range
Degrees
Fahrenheit
136.3 2680 56.8 16657 21.6 44154 −11.3 123152
133.1 2859 56.0 16973 21.0 44851 −11.9 125787
130.1 3040 55.3 17293 20.5 45560 −12.6 128508
127.3 3223 54.6 17616 20.0 46281 −13.2 131320
124.7 3407 53.9 17942 19.4 47014 −13.9 134227
122.1 3592 53.2 18273 18.9 47759 −14.5 137234
119.7 3779 52.5 18607 18.4 48517 −15.2 140347
117.5 3968 51.9 18945 17.8 49289 −15.9 143571
115.3 4159 51.2 19287 17.3 50074 −16.5 146913
113.2 4351 50.5 19633 16.8 50873 −17.2 150378
111.2 4544 49.9 19982 16.3 51686 −17.9 153974
109.3 4740 49.2 20336 15.7 52514 −18.6 157708
107.4 4937 48.5 20695 15.2 53356 −19.3 161588
105.6 5136 47.9 21057 14.7 54215 −20.1 165624
103.9 5336 47.3 21424 14.1 55089 −20.8 169824
102.3 5539 46.6 21795 13.6 55979 −21.5 174200
100.6 5743 46.0 22171 13.1 56887 −22.3 178762
99.1 5949 45.4 22551 12.5 57811 −23.0 183522
97.6 6157 44.7 22936 12.0 58754 −23.8 188493
96.1 6367 44.1 23326 11.5 59715 −24.6 193691
94.7 6578 43.5 23720 11.0 60694 −25.4 199130
93.3 6792 42.9 24120 10.4 61693 −26.2 204829
92.0 7007 42.3 24525 9.9 62712 −27.0 210805
90.6 7225 41.7 24934 9.3 63752 −27.8 217080
89.4 7444 41.1 25349 8.8 64812 −28.7 223677
88.1 7666 40.5 25769 8.3 65895 −29.5 230621
86.9 7890 39.9 26195 7.7 67000 −30.4 237941
85.7 8115 39.3 26626 7.2 68128 −31.3 245667
84.5 8343 38.7 27063 6.7 69281 −32.2 253834
83.4 8573 38.1 27505 6.1 70458 −33.2 262482
82.3 8806 37.5 27954 5.6 71661 −34.1 271655
81.2 9040 37.0 28408 5.0 72890 −35.1 281400
80.1 9277 36.4 28868 4.5 74147 −36.1 291774
79.0 9516 35.8 29335 3.9 75431 −37.1 302840
78.0 9757 35.2 29808 3.4 76745 −38.2 314669
77.0 10001 34.7 30288 2.8 78090 −39.2 327343
76.0 10247 34.1 30774 2.3 79465
75.0 10496 33.5 31267 1.7 80873
74.1 10747 33.0 31766 1.2 82314
73.1 11000 32.4 32273 0.6 83790
72.2 11256 31.9 32787 0.0 85302
71.3 11515 31.3 33309 −0.5 86852
70.4 11776 30.7 33837 −1.1 88440
69.5 12040 30.2 34374 −1.7 90068
68.6 12306 29.6 34918 −2.2 91738
67.7 12575 29.1 35471 −2.8 93452
66.9 12847 28.6 36031 −3.4 95211
66.0 13122 28.0 36600 −4.0 97016
65.2 13400 27.5 37177 −4.6 98870
64.4 13681 26.9 37764 −5.2 100775
63.6 13964 26.4 38359 −5.7 102733
62.8 14251 25.8 38963 −6.3 104746
62.0 14540 25.3 39577 −6.9 106817
61.2 14833 24.8 40200 −7.5 108948
60.5 15129 24.2 40833 −8.2 111141
59.7 15428 23.7 41476 −8.8 113400
59.0 15730 23.2 42130 −9.4 115727
58.2 16036 22.6 42794 −10.0 118126
57.5 16345 22.1 43468 −10.6 120600
Resistance
Degrees
Fahrenheit
Resistance
Degrees
Fahrenheit
Resistance
Degrees
Fahrenheit
Resistance
Page 37
XP16 SERIES
Page 38
Table 13. High Discharge Sensor (RT28) Temperature / Resistance Range
Degrees
Fahrenheit
303.1 183 186.1 1052 136.8 2656 94.5 6613
298.1 195 185.0 1072 136.0 2698 93.6 6739
293.4 207 183.9 1093 135.2 2740 92.8 6869
289.0 220 182.8 1114 134.5 2783 92.0 7002
284.8 232 181.8 1135 133.7 2827 91.2 7139
280.9 245 180.7 1157 132.9 2872 90.3 7281
277.1 258 179.6 1179 132.2 2917 89.5 7426
273.6 270 178.6 1201 131.4 2963 88.6 7575
270.2 283 177.6 1223 130.6 3010 87.8 7729
267.0 297 176.6 1245 129.9 3057 86.9 7888
263.9 310 175.5 1268 129.1 3105 86.0 8051
260.9 323 174.6 1291 128.4 3154 85.2 8220
258.1 336 173.6 1315 127.6 3204 84.3 8394
255.3 350 172.6 1338 126.8 3255 83.4 8574
252.7 364 171.6 1362 126.1 3307 82.5 8759
250.1 378 170.6 1386 125.3 3359 81.6 8951
247.7 391 169.7 1411 124.6 3413 80.7 9149
245.3 405 168.7 1435 123.8 3467 79.8 9354
243.0 420 167.8 1460 123.1 3523 78.8 9566
240.8 434 166.9 1486 122.3 3579 77.9 9786
238.6 448 165.9 1511 121.6 3637 76.9 10013
236.5 463 165.0 1537 120.8 3695 76.0 10250
234.4 478 164.1 1563 120.1 3755 75.0 10495
232.4 492 163.2 1590 119.3 3816 74.1 10749
230.5 507 162.3 1617 118.5 3877 73.1 11014
228.6 523 161.4 1644 117.8 3940 72.1 11289
226.7 538 160.5 1672 117.0 4005 71.1 11575
224.9 553 159.7 1699 116.3 4070 70.0 11873
223.2 569 158.8 1728 115.5 4137 69.0 12184
221.5 584 157.9 1756 114.8 4205 68.0 12509
219.8 600 157.1 1785 114.0 4274 66.9 12848
218.1 616 156.2 1815 113.2 4345 65.8 13202
216.5 632 155.3 1845 112.5 4418 64.7 13573
214.9 649 154.5 1875 111.7 4491 63.6 13961
213.4 665 153.6 1905 111.0 4567 62.5 14368
211.9 682 152.8 1936 110.2 4644 61.3 14796
210.4 698 152.0 1968 109.4 4722 60.2 15246
208.9 715 151.1 1999 108.7 4802 59.0 15719
207.5 732 150.3 2032 107.9 4884 57.8 16218
206.0 750 149.5 2064 107.1 4968 56.6 16744
204.6 767 148.7 2098 106.4 5054 55.3 17301
203.3 785 147.9 2131 105.6 5141 54.0 17891
201.9 803 147.1 2165 104.8 5231 52.7 18516
200.6 821 146.2 2200 104.0 5323 51.4 19180
199.3 839 145.4 2235 103.3 5416 50.0 19887
198.0 857 144.6 2270 102.5 5512 48.6 20641
196.8 876 143.8 2306 101.7 5610 47.2 21448
195.5 894 143.0 2343 100.9 5711 45.7 22311
194.3 913 142.3 2380 100.1 5814
193.1 932 141.5 2418 99.3 5920
191.9 952 140.7 2456 98.5 6028
190.7 971 139.9 2495 97.7 6139
189.5 991 139.1 2534 96.9 6253
188.4 1011 138.3 2574 96.1 6370
187.2 1031 137.6 2615 95.3 6489
Resistance
Degrees
Fahrenheit
Resistance
Degrees
Fahrenheit
Resistance
Degrees
Fahrenheit
Resistance
Page 38
Page 39
TEST
Placing the jumper on the field test pins (P1) allows the technician to:
S Clear short cycle lockout S Clear five−strike fault lockout S Cycle the unit in and out of defrost mode S Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal operation.
The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.
Y1 Active
Place a jumper on TEST pins for
longer than one second but less than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.
If in COOLING Mode
No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 45 minute test.
INACTIVE
If in HEATING Mode
If no ambient or coil sensor fault exist, unit will go into DEFROST MODE. If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.
NOTE  Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Control.
Figure 27. Test Pin (P1) Functions
If jumper on TEST pins remains in place for more than five seconds.
The unit will return to HEAT MODE uncalibrated with defrost timer set for 34 minutes.
Page 39
If jumper on TEST pins is removed before a maximum of five seconds.
The unit will remain in DEFROST MODE until termination on time or temperature.
XP16 SERIES
Page 40
Two−Stage Modulation Compressors Checks
Use this checklist on page 42 to verify part-load and full-load capacity operation of two-stage modulation compressors.
TOOLS REQUIRED
S Refrigeration gauge set S Digital volt/amp meter S Electronic temperature thermometer S On-off toggle switch
IMPORTANT
This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils, and correct system refrigerant charge. All components in the system must be functioning proper to correctly perform compressor modulation operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings).
PROCEDURE
NOTE − Block outdoor coil to maintain a minimum of 375 psig during testing).
1. Turn main power OFF to outdoor unit.
2. Adjust room thermostat set point 5ºF above the room
temperature.
3. Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor.
4. Turn toggle switch OFF and install switch in series with Y2 wire from room thermostat.
5. Cycle main power ON.
6. Allow pressures and temperatures to stabilize before taking measurements (may take up to 10 minutes).
7. Record all of the readings for the Y1 demand.
8. Close switch to energize Y2 demand. Verify power is going to compressor solenoid.
9. Allow pressures and temperatures to stabilize before taking measurements (may take up to 10 minutes).
10. Record all of the readings with the Y1 and Y2 demand.
11. If temperatures and pressures change in the direction noted in Two−Stage Modulation Compressor Field Operational Checklist on page 42, the compressor is properly modulating from low to high capacity. (If no amperage, pressures or temperature readings change when this test is performed, the compressor is not modulating between low and high capacity and replacement is necessary).
12. After testing is complete, return unit to original set up.
Maintenance
DEALER
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
Outdoor Unit
1. Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre−lubricated and sealed. No further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor. Motor Nameplate:_________ Actual:__________.
7. Inspect drain holes in coil compartment base and clean if necessary.
NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)
S Outdoor Coil  The outdoor coil may be flushed with
a water hose.
S Outdoor Coil (Sea Coast)  Moist air in ocean
locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated and permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor. Motor Nameplate:_________ Actual:__________.
Page 40
Page 41
Indoor Coil
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of oil leaks.
3. Check condensate line and clean if necessary.
HOMEOWNER
Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner.
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its proper operation.
S Please contact your dealer to schedule proper
inspection and maintenance for your equipment.
S Make sure no obstructions restrict airflow to the
outdoor unit.
S Grass clippings, leaves, or shrubs crowding the unit
can cause the unit to work harder and use more energy.
S Keep shrubbery trimmed away from the unit and
periodically check for debris which collects around the unit.
Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit.
Routine Maintenance
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air Filter  Ask your Lennox dealer to show you where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable Filter  Disposable filters should be replaced with a filter of the same type and size.
NOTE If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
3. Reusable Filter  Many indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or grille.
NOTE The filter and all access panels must be in place any time the unit is in operation.
4. Indoor Unit  The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
Thermostat Operation
See the thermostat homeowner manual for instructions on how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics that you should be aware of:
S Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space.
S Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45F (7C). An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
S During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation.
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the EMERGENCY HEAT setting to obtain temporary heat without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the HEAT setting and normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before calling for service:
S Verify room thermostat settings are correct. S Verify that all electrical disconnect switches are ON. S Check for any blown fuses or tripped circuit breakers. S Verify unit access panels are in place. S Verify air filter is clean. S If service is needed, locate and write down the unit
model number and have it handy before calling.
Page 41
XP16 SERIES
Page 42
Accessories
For update−to−date information, see any of the following publications:
S Lennox XP16 Engineering Handbook S Lennox Product Catalog S Lennox Price Book
Checklists
Two−Stage Modulation Compressors Field Operational Checklist
Unit Readings Y1 − First-Stage
Expected results during Y2 demand
COMPRESSOR
Voltage Same
Amperage Higher
OUTDOOR UNIT FAN MOTOR
Amperage Same or Higher
TEMPERATURE
Ambient Same
Outdoor Coil Discharge Air Higher
(Toggle switch On)
Y2 − Second-Stage
Compressor Discharge Line Higher
Indoor Return Air Same
Indoor Coil Discharge Air Lower
PRESSURES
Suction (Vapor) Lower
Liquid Higher
Page 42
Page 43
XP16 Start−Up and Performance
Customer Address
Indoor Unit Model Serial
Outdoor Unit Model Serial
Notes:
START UP CHECKS
Refrigerant Type:
1st Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts
2nd Stage: Rated Load Amps Actual Amps Rated Volts Actual Volts
Outdoor Unit Fan Full Load Amps Actual Amps: 1st Stage 2nd Stage
COOLING MODE
Suction Pressure: 1st Stage: 2nd Stage:
Liquid Pressure: 1st Stage: 2nd Stage:
Supply Air Temperature: 1st Stage: 2nd Stage:
Temperature: Ambient: Return Air:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach tempera­tures.)
Subcooling:
Saturated Condensing Temperature (A) minus Liquid
Line Temperature (B)
Approach:
Liquid Line Temperature (A) minus Outdoor Air
Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
Return Air Temperature (A) minus Supply Air
Temperature (B)
A
A
A
B
=
B
=
B
=
SUBCOOLING
APPROACH
COIL TEMP DROP
Page 43
XP16 SERIES
Loading...