ML180UHA series units are mid-efficiency gas furnaces
used for upflow or horizontal applications only, manufac
tured with Lennox Duralok Plust heat exchangers formed
of aluminized steel. ML180UHA units are available in heat
ing capacities of 69.6 to 139.3 MJ/h and cooling applica
tions 10 to 17 kW. Refer to Engineering Handbook for prop
er sizing.
Units are factory equipped for use with natural gas. Kits are
available for conversion to LP/Propane operation.
ML180UHA model units are equipped with a hot surface
ignition system. All units use a redundant gas valve to as
sure safety shut-off as required.
All specifications in this manual are subject to change. Pro
cedures outlined in this manual are presented as a recom
mendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommended only and do not constitute
code.
Revised 05 /2017
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
TABLE OF CONTENTS
SpecificationsPage 2.............................
Blower DataPage 3..............................
Parts IdentificationPage 5.........................
I Unit ComponentsPage 6........................
ML180UHA
IMPORTANT
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person
al injury or loss of life. Installation and service must
be performed by a qualified installer, service agency
or the gas supplier.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon
nect switch(es). Unit may have multiple
power supplies.
II InstallationPage 14.............................
III Start UpPage 14..............................
IV Heating System Service ChecksPage 15.........
V Typical Operating CharacteristicsPage 19.........
VI MaintenancePage 20..........................
VII Wiring and Sequence of OperationPage 22......
Page 1
WARNING
Sharp edges.
Be careful when servicing unit to avoid sharp edges
which may result in personal injury.
Air Filter and Rack KitHorizontal (end)87L9587L9687L9787L98
Size of lter - mm 356 x 635 x 25 457 x 635 x 25 508 x 635 x 25 635 x 635 x 25
Side ReturnSingle44J2244J2244J2244J22
Ten Pack66K6366K6366K6366K63
Size of lter - mm 406 x 635 x 25 406 x 635 x 25 406 x 635 x 25 406 x 635 x 25
1
Cleanable polyurethane, frame-type lter.
Page 3
BLOWER DATA
ML180UH070AP36A PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Various Blower Speeds
HighMediumLow
L/sWattsL/sWattsL/sWatts
0716771589615469468
25687752564597435448
50675724554583430441
75662708547569421430
100649691530554408417
125633672517541393405
150616650503524372387
175595624488514359375
200573608472494324363
225551590447477307346
250523561424454282331
ML180UH090AP48B PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Various Blower Speeds
High
Medium-
High
Medium-
Low
Low
L/s Watts L/s Watts L/s Watts L/s Watts
0890 1085 715892497 598 423493
25849 1050 679855 463577 386481
50849 1016 679831 460565 384464
75831967 676807 456546 369447
100827 937667 773452 526364 434
125816 906660 747439 509349 421
150799 872647 718426 494331 408
175784 845629 691411477308394
200754 808601 642394 460290 383
225722 765577 622359 435256 363
250674 713555 593332 421229 348
ML180UH110AP36C PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Various Blower Speeds
High
Medium-
High
Medium-
Low
Low
L/s Watts L/s Watts L/s Watts L/s Watts
0827 1106 660 884460 574404 478
25800 1063 630 850434 558378 463
50801 1043 631 819432 541369 451
75779984 631807 434 527359438
100773 962624 777 422512 352422
125773 938620 758 408490 3354 11
150761 907609 725 382472 331396
175741 854593 695 383460 319386
200722 832580 659 366441 299372
225699 777554 638 351432 263354
250677 741527 600 3314 11239340
ML180UH110AP60C PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Different Blower Speeds
Bottom Return Air, Side Return Air with Optional
Return Air Base, Return Air from Both Sides or Return
Air from Bottom and One Side.
Single Side Return Air − Air volumes in bold require eld
fabricated transition to accommodate 508 x 635 x 25 mm
air lter in order to maintain proper air velocity.
HighMediumLowHighMediumLow
L/sWattsL/sWattsL/sWattsL/sWattsL/sWattsL/sWatts
0116514479641173826987112614529341172794984
25114414089381149803966110414279101150772964
50111513899321121797943108513919021126768943
75110413589221104787926107113568961110756925
100108413339081082773902105913408811079750907
125106313039051079756877103713108691064741890
150104312748881050748865102012828601041731872
175102712498711024738845
100512488391022717852
200100512248499947238159871224821997699831
22598011798359746968009561192801966678808
25094711408079436777759391158789955665786
ML180UH135AP60D PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Different Blower Speeds
Bottom Return Air, Side Return Air with Optional
Return Air Base, Return Air from Both Sides or Return
Air from Bottom and One Side.
Single Side Return Air − Air volumes in bold require eld
fabricated transition to accommodate 508 x 635 x 25 mm
air lter in order to maintain proper air velocity.
HighMediumLowHighMediumLow
L/sWattsL/sWattsL/sWattsL/sWattsL/sWattsL/sWatts
0115314609581167810967111414699411219786992
25112614259311139788945109114409171196759967
50111814119231125773928107914119131173751950
75108713749151113765914106414028931149743933
100108313448911079752900104813758871130734920
125106713258901066741884103213458661101720899
150103812848621036731869101213228521072708881
175103412698441016712849
99412918341053690860
2001005123983299569782498712718201029663834
225977120480497567781395612387971010650815
25095211737899536407819361220783988627795
BLOWER DATA
Pressure Switch
Combustion Air Inducer
Gas Valve
Burner/Manifold Assembly
ML180UHA PARTS ARRANGEMENT
Heat Exchanger
Blower Access Panel
Upper Access Panel
Control Box
Capacitor
Transformer
Limit Switch
IEC Receptacle
(under combustion air inducer)
Blower Assembly
Shipping Pad
ML180UH090AP48B, & ML180UH110AP36C only.
(
Remove prior to operation
)
FIGURE 1
Page 5
I-UNIT COMPONENTS
ML180UHA unit components are shown in figure 1.The
gas valve, combustion air inducer and burners can be ac
cessed by removing the upper access panel. Electrical
components are in the control box (figure 2) found in the
blower section.
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box.
The switch provides overcurrent protection to the trans
former (T1). The breaker is rated 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit opera
tion will shutdown. The breaker can be manually reset
by pressing the button on the face. See figure 3.
CAUTION
Electrostatic discharge can affect elec
tronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
1. Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage section of the unit. Transformers on all
models are rated 40VA with a 230V primary and a 24V sec
ondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 230VAC is wired in se
ries with line voltage. When the blower door is removed the
unit will shut down.
CONTROL BOX ML180UHA
Door Interlock Switch
Integrated Control
FIGURE 2
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
4. Integrated Control (A92)
WARNING
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply re
place entire control.
Can cause injury or death. Unsafe operation will re
sult if repair is attempted.
The hot surface ignition control system consisting of an in
tegrated control (figure 4 with control terminal designa
tions in tables 1 and 2.) sensor and ignitor (figure 6). The
integrated control and ignitor work in combination to en
sure furnace ignition and ignitor durability. The integrated
control, controls all major furnace operations. The inte
grated control also features one LED light (AN1 red) for
troubleshooting and two accessory terminals rated at (1)
one amp. The integrated control also features a (3) amp
fuse for overcurrent protection. See table 3 for trouble
shooting diagnostic codes. The nitride ignitor is made
from a non-porous, high strength proprietary ceramic ma
terial that provides long life and trouble free maintenance.
The integrated control continuously monitors line voltage
and maintains the ignitor power at a consistent level to
provide proper lighting and maximum ignitor life.
Page 6
LED
(red)
INTEGRATED CONTROL
TERMINAL DESIGNATIONS
HUM - Humidifier 230VAC
LINE - Input 230VAC
XFMR - Transformer 230VAC
EAC - Electronic Air Cleaner 230VAC
COOL - Cool Speed 230VAC
PARK1, PARK2 - Dead terminals for alternate speed taps
NEUTRALS - Neutral terminals 230VAC
HEAT - Heating Speed 230VAC
FS - Flame Sense
TABLE 1
5-Pin Terminal Designation
PIN #FUNCTION
1Ignitor Line
2
3
4
5
Not Used
Combustion Air Inducer Low
Combustion Air Inducer Neutral
Ignitor Neutral
FIGURE 4
TABLE 2
12-Pin Terminal Designations
PIN #FUNCTION
1Not Used
2Not Used
3Rollout Switch Input
4Ground
5TH 24V Hot
6High Limit Input
7Gas Valve Line
8Gas Valve Common
9TR 24V Return
10Ground
11Rollout Switch Output
12Pressure Switch
Page 7
TABLE 3
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
PulseA 1/4 second flash followed by four seconds of off time.
HeartbeatConstant 1/2 second bright and 1/2 second dim cycles.
X + Y
PulsePower on - Standby.
HeartbeatNormal operation - signaled when heating demand initiated at thermostat.
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four
seconds, then repeats.
FLAME CODES
1 + 2Low flame current -- check flame sensor.
1 + 3Flame sensed out of sequence -- flame still present. Flame sensed without gas valve energized.
Reversed line voltage polarity (control will restart if the error recovers). And or no Earth groas valve
faulund
Page 8
Electronic Ignition
On a call for heat the integrated control monitors the com
bustion air inducer pressure switch. The control board will
not begin the heating cycle if the pressure switch is closed
(by-passed). Once the pressure switch is determined to be
open, the combustion air inducer is energized. When the
differential in the pressure switch is great enough, the pres
sure switch closes and a 15-second pre-purge begins. If
the pressure switch is not proven within 2-1/2 minutes, the
integrated control goes into Watchguard-Pressure Switch
mode for a 5-minute re-set period.
After the 15-second pre-purge period, the ignitor warms up
for 20 seconds during which the gas valve opens at 19 sec
onds for a 4-second trial for ignition. The ignitor remains
energized for the first 3 seconds during the 4 second trial. If
ignition is not proved during the 4-second period, the inte
grated control will try four more times with an inter purge
and warm-up time between trials of 35 seconds. After a to
tal of five trials for ignition (including the initial trial), the inte
grated control goes into Watchguard-Flame Failure mode.
After a 60-minute reset period, the integrated control will
begin the ignition sequence again.
The integrated control has an added feature of ignitor pow
er regulation to maintain consistent lighting and longer igni
tor life under all line voltage conditions.
Fan Time Control
Heating Fan On Time
The fan on time of 30 seconds is not adjustable.
Heating Fan Off Time
Fan off time (time that the blower operates after the heat
demand has been satisfied) can be adjusted by moving the
jumper to a different setting. The unit is shipped with a fac
tory fan off setting of 60 seconds. For customized comfort,
monitor the supply air temperature once the heat demand
is satisfied. Note the supply air temperature at the instant
the blower is de-energized.
Adjust the fan-off delay to achieve a supply air temperature
between 32° C - 43° C (90° F - 110° F) at the instant the
blower is de-energized. (Longer delay times allow for lower
air temperature, shorter delay times allow for higher air
temperature). See figure 5.
Cooling Fan On Time
The fan on time is 2 seconds and is not adjustable.
Cooling Fan Off Time
The control has a 45 second fan off delay after cooling de
mand has been met. This delay is factory set and not ad
justable.
HEAT FAN‐OFF TIME IN SECONDS
NO JUMPER
To adjust fan-off timing, reposition jumper across pins to
60 Second
off Time
60
90
120
180
achieve desired setting.
90 Second
off Time
60
90
120
180
120 Second
off Time
60
90
120
180
180 Second
off Time
60
90
120
180
FIGURE 5
Page 9
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.