ML180UHA series units are mid-efficiency gas furnaces
used for upflow or horizontal applications only, manufac
tured with Lennox Duralok Plust heat exchangers formed
of aluminized steel. ML180UHA units are available in heat
ing capacities of 69.6 to 139.3 MJ/h and cooling applica
tions 10 to 17 kW. Refer to Engineering Handbook for prop
er sizing.
Units are factory equipped for use with natural gas. Kits are
available for conversion to LP/Propane operation.
ML180UHA model units are equipped with a hot surface
ignition system. All units use a redundant gas valve to as
sure safety shut-off as required.
All specifications in this manual are subject to change. Pro
cedures outlined in this manual are presented as a recom
mendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommended only and do not constitute
code.
Revised 05 /2017
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
TABLE OF CONTENTS
SpecificationsPage 2.............................
Blower DataPage 3..............................
Parts IdentificationPage 5.........................
I Unit ComponentsPage 6........................
ML180UHA
IMPORTANT
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person
al injury or loss of life. Installation and service must
be performed by a qualified installer, service agency
or the gas supplier.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon
nect switch(es). Unit may have multiple
power supplies.
II InstallationPage 14.............................
III Start UpPage 14..............................
IV Heating System Service ChecksPage 15.........
V Typical Operating CharacteristicsPage 19.........
VI MaintenancePage 20..........................
VII Wiring and Sequence of OperationPage 22......
Page 1
WARNING
Sharp edges.
Be careful when servicing unit to avoid sharp edges
which may result in personal injury.
Air Filter and Rack KitHorizontal (end)87L9587L9687L9787L98
Size of lter - mm 356 x 635 x 25 457 x 635 x 25 508 x 635 x 25 635 x 635 x 25
Side ReturnSingle44J2244J2244J2244J22
Ten Pack66K6366K6366K6366K63
Size of lter - mm 406 x 635 x 25 406 x 635 x 25 406 x 635 x 25 406 x 635 x 25
1
Cleanable polyurethane, frame-type lter.
Page 3
Page 3
BLOWER DATA
ML180UH070AP36A PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Various Blower Speeds
HighMediumLow
L/sWattsL/sWattsL/sWatts
0716771589615469468
25687752564597435448
50675724554583430441
75662708547569421430
100649691530554408417
125633672517541393405
150616650503524372387
175595624488514359375
200573608472494324363
225551590447477307346
250523561424454282331
ML180UH090AP48B PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Various Blower Speeds
High
Medium-
High
Medium-
Low
Low
L/s Watts L/s Watts L/s Watts L/s Watts
0890 1085 715892497 598 423493
25849 1050 679855 463577 386481
50849 1016 679831 460565 384464
75831967 676807 456546 369447
100827 937667 773452 526364 434
125816 906660 747439 509349 421
150799 872647 718426 494331 408
175784 845629 691411477308394
200754 808601 642394 460290 383
225722 765577 622359 435256 363
250674 713555 593332 421229 348
ML180UH110AP36C PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Various Blower Speeds
High
Medium-
High
Medium-
Low
Low
L/s Watts L/s Watts L/s Watts L/s Watts
0827 1106 660 884460 574404 478
25800 1063 630 850434 558378 463
50801 1043 631 819432 541369 451
75779984 631807 434 527359438
100773 962624 777 422512 352422
125773 938620 758 408490 3354 11
150761 907609 725 382472 331396
175741 854593 695 383460 319386
200722 832580 659 366441 299372
225699 777554 638 351432 263354
250677 741527 600 3314 11239340
Page 4
ML180UH110AP60C PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Different Blower Speeds
Bottom Return Air, Side Return Air with Optional
Return Air Base, Return Air from Both Sides or Return
Air from Bottom and One Side.
Single Side Return Air − Air volumes in bold require eld
fabricated transition to accommodate 508 x 635 x 25 mm
air lter in order to maintain proper air velocity.
HighMediumLowHighMediumLow
L/sWattsL/sWattsL/sWattsL/sWattsL/sWattsL/sWatts
0116514479641173826987112614529341172794984
25114414089381149803966110414279101150772964
50111513899321121797943108513919021126768943
75110413589221104787926107113568961110756925
100108413339081082773902105913408811079750907
125106313039051079756877103713108691064741890
150104312748881050748865102012828601041731872
175102712498711024738845
100512488391022717852
200100512248499947238159871224821997699831
22598011798359746968009561192801966678808
25094711408079436777759391158789955665786
ML180UH135AP60D PERFORMANCE (Less Filter)
External
Static
Pressure
Pa
Air Volume at Different Blower Speeds
Bottom Return Air, Side Return Air with Optional
Return Air Base, Return Air from Both Sides or Return
Air from Bottom and One Side.
Single Side Return Air − Air volumes in bold require eld
fabricated transition to accommodate 508 x 635 x 25 mm
air lter in order to maintain proper air velocity.
HighMediumLowHighMediumLow
L/sWattsL/sWattsL/sWattsL/sWattsL/sWattsL/sWatts
0115314609581167810967111414699411219786992
25112614259311139788945109114409171196759967
50111814119231125773928107914119131173751950
75108713749151113765914106414028931149743933
100108313448911079752900104813758871130734920
125106713258901066741884103213458661101720899
150103812848621036731869101213228521072708881
175103412698441016712849
99412918341053690860
2001005123983299569782498712718201029663834
225977120480497567781395612387971010650815
25095211737899536407819361220783988627795
BLOWER DATA
Page 5
Pressure Switch
Combustion Air Inducer
Gas Valve
Burner/Manifold Assembly
ML180UHA PARTS ARRANGEMENT
Heat Exchanger
Blower Access Panel
Upper Access Panel
Control Box
Capacitor
Transformer
Limit Switch
IEC Receptacle
(under combustion air inducer)
Blower Assembly
Shipping Pad
ML180UH090AP48B, & ML180UH110AP36C only.
(
Remove prior to operation
)
FIGURE 1
Page 5
Page 6
I-UNIT COMPONENTS
ML180UHA unit components are shown in figure 1.The
gas valve, combustion air inducer and burners can be ac
cessed by removing the upper access panel. Electrical
components are in the control box (figure 2) found in the
blower section.
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box.
The switch provides overcurrent protection to the trans
former (T1). The breaker is rated 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit opera
tion will shutdown. The breaker can be manually reset
by pressing the button on the face. See figure 3.
CAUTION
Electrostatic discharge can affect elec
tronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
1. Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage section of the unit. Transformers on all
models are rated 40VA with a 230V primary and a 24V sec
ondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 230VAC is wired in se
ries with line voltage. When the blower door is removed the
unit will shut down.
CONTROL BOX ML180UHA
Door Interlock Switch
Integrated Control
FIGURE 2
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3
4. Integrated Control (A92)
WARNING
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply re
place entire control.
Can cause injury or death. Unsafe operation will re
sult if repair is attempted.
The hot surface ignition control system consisting of an in
tegrated control (figure 4 with control terminal designa
tions in tables 1 and 2.) sensor and ignitor (figure 6). The
integrated control and ignitor work in combination to en
sure furnace ignition and ignitor durability. The integrated
control, controls all major furnace operations. The inte
grated control also features one LED light (AN1 red) for
troubleshooting and two accessory terminals rated at (1)
one amp. The integrated control also features a (3) amp
fuse for overcurrent protection. See table 3 for trouble
shooting diagnostic codes. The nitride ignitor is made
from a non-porous, high strength proprietary ceramic ma
terial that provides long life and trouble free maintenance.
The integrated control continuously monitors line voltage
and maintains the ignitor power at a consistent level to
provide proper lighting and maximum ignitor life.
Page 6
Page 7
LED
(red)
INTEGRATED CONTROL
TERMINAL DESIGNATIONS
HUM - Humidifier 230VAC
LINE - Input 230VAC
XFMR - Transformer 230VAC
EAC - Electronic Air Cleaner 230VAC
COOL - Cool Speed 230VAC
PARK1, PARK2 - Dead terminals for alternate speed taps
NEUTRALS - Neutral terminals 230VAC
HEAT - Heating Speed 230VAC
FS - Flame Sense
TABLE 1
5-Pin Terminal Designation
PIN #FUNCTION
1Ignitor Line
2
3
4
5
Not Used
Combustion Air Inducer Low
Combustion Air Inducer Neutral
Ignitor Neutral
FIGURE 4
TABLE 2
12-Pin Terminal Designations
PIN #FUNCTION
1Not Used
2Not Used
3Rollout Switch Input
4Ground
5TH 24V Hot
6High Limit Input
7Gas Valve Line
8Gas Valve Common
9TR 24V Return
10Ground
11Rollout Switch Output
12Pressure Switch
Page 7
Page 8
TABLE 3
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
PulseA 1/4 second flash followed by four seconds of off time.
HeartbeatConstant 1/2 second bright and 1/2 second dim cycles.
X + Y
PulsePower on - Standby.
HeartbeatNormal operation - signaled when heating demand initiated at thermostat.
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four
seconds, then repeats.
FLAME CODES
1 + 2Low flame current -- check flame sensor.
1 + 3Flame sensed out of sequence -- flame still present. Flame sensed without gas valve energized.
Reversed line voltage polarity (control will restart if the error recovers). And or no Earth groas valve
faulund
Page 8
Page 9
Electronic Ignition
On a call for heat the integrated control monitors the com
bustion air inducer pressure switch. The control board will
not begin the heating cycle if the pressure switch is closed
(by-passed). Once the pressure switch is determined to be
open, the combustion air inducer is energized. When the
differential in the pressure switch is great enough, the pres
sure switch closes and a 15-second pre-purge begins. If
the pressure switch is not proven within 2-1/2 minutes, the
integrated control goes into Watchguard-Pressure Switch
mode for a 5-minute re-set period.
After the 15-second pre-purge period, the ignitor warms up
for 20 seconds during which the gas valve opens at 19 sec
onds for a 4-second trial for ignition. The ignitor remains
energized for the first 3 seconds during the 4 second trial. If
ignition is not proved during the 4-second period, the inte
grated control will try four more times with an inter purge
and warm-up time between trials of 35 seconds. After a to
tal of five trials for ignition (including the initial trial), the inte
grated control goes into Watchguard-Flame Failure mode.
After a 60-minute reset period, the integrated control will
begin the ignition sequence again.
The integrated control has an added feature of ignitor pow
er regulation to maintain consistent lighting and longer igni
tor life under all line voltage conditions.
Fan Time Control
Heating Fan On Time
The fan on time of 30 seconds is not adjustable.
Heating Fan Off Time
Fan off time (time that the blower operates after the heat
demand has been satisfied) can be adjusted by moving the
jumper to a different setting. The unit is shipped with a fac
tory fan off setting of 60 seconds. For customized comfort,
monitor the supply air temperature once the heat demand
is satisfied. Note the supply air temperature at the instant
the blower is de-energized.
Adjust the fan-off delay to achieve a supply air temperature
between 32° C - 43° C (90° F - 110° F) at the instant the
blower is de-energized. (Longer delay times allow for lower
air temperature, shorter delay times allow for higher air
temperature). See figure 5.
Cooling Fan On Time
The fan on time is 2 seconds and is not adjustable.
Cooling Fan Off Time
The control has a 45 second fan off delay after cooling de
mand has been met. This delay is factory set and not ad
justable.
HEAT FAN‐OFF TIME IN SECONDS
NO JUMPER
To adjust fan-off timing, reposition jumper across pins to
60 Second
off Time
60
90
120
180
achieve desired setting.
90 Second
off Time
60
90
120
180
120 Second
off Time
60
90
120
180
180 Second
off Time
60
90
120
180
FIGURE 5
Page 9
Page 10
Rollout Switches
ML180UHA HEATING COMPONENTS
Flue Transition
Ignitor
Gasket
Pressure Switch
Sensor
Manifold And Gas Valve
FIGURE 6
5. Flame Sensor (Figure 6)
A flame sensor is located on the left side of the burner sup
port. The sensor is mounted on the flame rollout plate and
the tip protrudes into the flame envelope of the left-most
burner. The sensor can be removed for service without re
moving any part of the burners. During operation, flame is
sensed by current passed through the flame and sensing
electrode. The integrated control allows the gas valve to re
main open as long as flame signal is sensed.
6. Flame Rollout Switches (Figure 6) (S47)
Flame rollout switch is a high temperature limit. Each fur
nace is equipped with two identical switches. The limit is a
N.C. SPST manual‐reset limit connected in series with the
integrated control A92. When S47 senses rollout, the inte
grated control immediately stops ignition and closes the
gas valve. If unit is running and flame rollout is detected, the
gas valve will close and integrated control will be disabled.
Rollout can be caused by a blocked heat exchanger, flue or
lack of combustion air. The switch has a factory setpoint of
99°C (210°F) and cannot be adjusted. To manually reset a
tripped switch, push the reset button located on the control.
Orifice Plate
Combustion Air Inducer
Collector Box
7. Primary Limit Control (S10)
The primary limit on ML180UHA units is located in the heating
vestibule panel under the combustion air inducer. See figure 1.
When excess heat is sensed in the heat exchanger, the limit
will open. If the limit is open, the integrated control energizes
the supply air blower and closes the gas valve. The limit auto
matically resets when unit temperature returns to normal. The
switch must reset within three minutes or SureLight
will go into Watchguard for one hour. The switch is factory
set and cannot be adjusted. The switch may have a different
setpoint for each unit model number. If limit switch must be
replaced, refer to Lennox ProductZone repair parts list on
Lennox DaveNet®.
®
control
Page 10
Page 11
8. Ignitor (Figure 6)
The nitride ignitor used on ML180UHA units is made from a
proprietary ceramic material. Ignitor longevity is enhanced
by controlling the voltage to the ignitor. To check ignitor,
measure its resistance and voltage. A value of 300 to 1300
ohms indicates a good ignitor. Voltage to the ignitor should
be 150VAC.
See figure 7 for resistance, and voltage check.
Voltmeter
(set to ohms)
Test 2
Test 1
NOTE - The ML180UHA furnace contains electronic
components that are polarity sensitive. Make sure that
the furnace is wired correctly and is properly grounded.
Test 1 - Remove 5-pin plug
from control. Insert test pins
from meter into plug pin 1 and
5. If reading is correct test is
over. If reading is outside ac
ceptable range move to test 2.
Test 2 - Separate the 2-pin jackplug and again check resistance to
the ignitor. If reading is acceptable
then the problem is the wiring be
tween the jackplug and integrated
control. If reading is acceptable re
place the ignitor.
Voltmeter
(set to AC)
Test - Do not separate 5 pin
jack-plug. Use a true RMS me
ter and carefully insert test pins
in plug pins 1 and 5. Measure
voltage.
FIGURE 7
Page 11
Page 12
9. Gas Valve (Figure 6)
The ML180UHA uses internally redundant gas valve to as
sure safety shut-off. If the gas valve must be replaced, the
same type valve must be used.
24VAC terminals and valve switch are located on the valve. All
terminals on the gas valve are connected to wires from the in
tegrated control. 24V applied to the terminals energizes the
valve.
Inlet and outlet pressure taps are located on the valve. A regu
lator adjustment screw is located on the valve.
LPG changeover kits are available from Lennox. Kits include
burner orifices and a gas valve regulator spring.
10. Combustion Air Inducer (B6)
All ML180UHA units use a combustion air inducer to move
air through the burners and heat exchanger during heating
operation. The blower uses a 230VAC motor. The motor
operates during all heating operation and is controlled by
integrated control A92. The inducer also operates for 15
seconds before burner ignition (pre‐purge) and for 5 sec
onds after the gas valve closes (post‐purge).
A pressure switch connected to the combustion air inducer
orifice plate is used to prove inducer operation. The combus
tion air inducer orifice will be different for each model. See
table 4 for orifice sizes. The switch monitors air pressure in
the inducer housing. During normal operation, the pressure in
the housing is negative. If pressure becomes less negative
(signifying any obstruction in the flue) the pressure switch
opens. When the proving switch opens, the integrated con
trol (A92) immediately de-energizes the gas valve to prevent
burner operation.
TABLE 4
ML180UHA Unit
C.A.I. Orifice Size mm (in)
11. Combustion Air Inducer
Pressure Switch (S18)
ML180UHA series units are equipped with a combustion air
pressure switch located on the combustion air inducer ori
fice bracket. The switch is connected to the combustion air
inducer housing by means of a flexible silicone hose. It mon
itors negative air pressure in the combustion air inducer
housing.
The switch is a single‐pole single‐throw proving switch elec
trically connected to the furnace control. The purpose of the
switch is to prevent burner operation if the combustion air in
ducer is not operating or if the flue becomes obstructed.
On start‐up, the switch senses that the combustion air in
ducer is operating. It closes a circuit to the integrated con
trol when pressure inside the combustion air inducer de
creases to a certain set point. Set points vary depending on
unit size. See table 5. The pressure sensed by the switch is
negative relative to atmospheric pressure. If the flue be
comes obstructed during operation, the switch senses a
loss of negative pressure (pressure becomes more equal
with atmospheric pressure) and opens the circuit to the in
tegrated control and gas valve. A bleed port on the switch
allows relatively dry air in the vestibule to purge switch tub
ing, to prevent condensate build up.
TABLE 5
ML180UHASet Point Pa (in)
070AP36A150 (.60)
090AP48B150 (.60)
110AP36C, 110AP60C150 (.60)
135AP60D150 (.60)
070AP36A35.7 (1.406)
090AP48B42.2 (1.660)
110A36C, 110AP60C47.6 (1.875)
135AP60D55.6 (2.188)
The switch is factory set and is not field adjustable. It is
a safety shut‐down control in the furnace and must not
be by-passed for any reason. If switch is closed or bypassed, the integrated control will not initiate ignition
at start up.
Page 12
Page 13
Multiple Venting
The ML180UHA furnace can vent in multiple positions. See
figure 8.
The make up box may be removed and the combustion air
inducer may be rotated clockwise or counterclockwise 90°
to allow for vertical or horizontal vent discharge in a vertical
or horizontal cabinet position. Remove the four mounting
Vent Pipe
Pressure
Switch
vent pipe
Collector Box
screws, rotate the assembly (assembly consists of orifice
plate, proving switch, gasket and combustion air inducer),
then reinstall the mounting screws. See unit Installation In
structions for more detail.
IMPORTANT
The combustion air pressure switch must be moved
for horizontal discharge air left position.
vent pipe
flue
vent pipe
transition
vent pipe
AIR
FLOW
Collector Box
FLOW
AIR
vent pipe
flue transition
AIR
FLOW
pressure switch
vent pipe
In all positions route the wires away from moving parts and the heat of the inducer
motor to prevent damage to the wires. The pressure switch must be installed above
the CAI to prevent moisture from collecting in the hoses or switch.
FIGURE 8
Page 13
Page 14
SUPPLY AIR BLOWER
AND SECONDARY LIMIT(S)
Left Side
ALIGN AND TIGHTEN SET SCREW WITH
FLAT SIDE OF MOTOR SHAFT
Right Side
SECONDARY
LIMIT (S)
MOTOR/BLOWER
ASSEMBLY
CAPACITOR
To Remove Blower From Unit: Disconnect Power, Remove
Control Box, Remove Bolts and Unplug Motor Wires From
Integrated Control. Then Slide Out Front of Unit.
FIGURE 9
12. Blower Motors and Capacitors
All ML180UHA units use direct drive blower motors. All mo
tors are 230V permanent split capacitor motors to ensure
maximum efficiency. Ratings for capacitors will be on motor
nameplate. If replacing the indoor blower motor or blower
wheel is necessary, placement is critical. The blower wheel
must be centered in the blower housing as shown in figure
10. When replacing the indoor blower motor the set screw
must be aligned and tightened with the motor shaft as
shown in figure 11.
Housing Hub
Set Screw
Motor
Shaft
NOTE - The 5 ton blower will have two flats
and two set screws 90° of each other .
FIGURE 11
13. Secondary Limit Controls
The secondary limit is located in the blower compartment in
the back side of the blower housing. See figure 9. When ex
cess heat is sensed in the blower compartment, the limit will
open. If the limit is open, the furnace control energizes the sup
ply air blower and closes the gas valve. The limit automatically
resets when unit temperature returns to normal. The secon
dary limit cannot be adjusted.
II- PLACEMENT AND INSTALLATION
Make sure unit is installed in accordance with installation
instructions and applicable codes.
III- START‐UP
A- Heating Start‐Up
BLOWER WHEEL REPLACEMENT
Center Blower Wheel
in Blower Housing
FIGURE 10
WARNING
Shock and burn hazard.
ML180UHA units are equipped with a hot surface
ignition system. Do not attempt to light manually.
Gas Valve Operation
MANIFOLD
PRESSURE
OUTLET
PORT
INLET
PRESSURE
PORT
White Rodgers 3600 Gas Valve
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
GAS VALVE SHOWN IN OFF POSITION
FIGURE 12
Page 14
Page 15
1 - STOP! Read the safety information at the beginning of
this section.
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit.
4 - This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 - Remove the upper access panel.
6 - Move gas valve lever to OFF position. Do not for c e .
See figure 12.
7 - Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's instruc
tions. If you do not smell gas go to next step.
8 - Move gas valve lever to ON position. Do not force.
See figure 12.
9 - Replace the upper access panel.
10- Turn on all electrical power to to the unit.
11- Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
12- If the appliance will not operate, follow the instructions
“Turning Off Gas to Unit” and call the gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting.
2 - Turn off all electrical power to the unit if service is to be
performed.
3 - Remove the upper access panel.
4 - Move gas valve lever to OFF position. Do not for c e .
See figure 12.
5 - Replace the upper access panel.
B- Safety or Emergency Shutdown
B- Gas Piping
Gas supply piping should not allow more than 125Pa (13
mm W.C.)drop in pressure between gas meter and unit.
Supply gas pipe must not be smaller than unit gas connec
tion.
Compounds used on gas piping threaded joints should be
resistant to action of liquefied petroleum gases.
C- Testing Gas Piping
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet.
IMPORTANT
In case emergency shutdown is required, turn off
the main shut‐off valve and disconnect the main
power to unit. These controls should be properly
labeled by the installer.
WARNING
Do not exceed 68Nm (50 ft-lbs) torque when attach
ing the gas piping to the gas valve.
When pressure testing gas lines, the gas valve must be dis
connected and isolated. Gas valves can be damaged if
subjected to more than 3.48kPag (0.5psig) See figure 13. If
the pressure is equal to or less than 3.48kPag (0.5psig),
close the manual shut-off valve before pressure testing to
isolate furnace from gas supply.
GAS PIPING TEST PROCEDURE
MANUAL MAIN SHUT-OFF VALVE
WILL NOT HOLD TEST PRESSURE IN EXCESS
OF 3.48kPa (0.5 PSIG 355 mm W.C.)
Disconnect main power to unit. Close manual and main gas
valves.
C- Extended Period Shutdown
Turn off thermostat or set to “UNOCCUPIED” mode. Close
all gas valves (both internal and external to unit) to guaran
tee no gas leak into combustion chamber. Turn off power to
unit. All access panels and covers must be in place and se
cured.
IV-HEATING SYSTEM SERVICE CHECKS
A- Certification
All units are Australian Gas Installation Code (AS/
NZS5601) certified. Refer to the ML180UHA Installation In
struction.
CAP
GAS VALVE
FIELD PROVIDED
LINE PRESSURE TAP
FIGURE 13
When checking piping connections for gas leaks, use pre
ferred means. Kitchen detergents can cause harmful corro
sion on various metals used in gas piping. Use of a specialty
Gas Leak Detector is strongly recommended.
Do not use matches, candles, flame or any other source of
ignition to check for gas leaks.
Page 15
Page 16
D- Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 6
GAS METER CLOCKING CHART
Seconds for One Revolution
Unit
-04580160200400
-07055110136272
-0904182102204
-110336682164
-135275468136
Natural-1000 btu/cu ft LP-2500 btu/cu ft
Furnace should operate at least 5 minutes before check
ing gas flow. Determine time in seconds for two revolu
tions of gas through the meter. (Two revolutions assures a
more accurate time.) Divide by two and compare to time
in table 6 below. If manifold pressure matches table 8 and
rate is incorrect, check gas orifices for proper size and re
striction. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas
appliances connected to meter.
Manifold Pressure Measurement
1 - Remove the threaded plug from the outlet side of the
gas valve and install a field-provided barbed fitting.
Connect to a test gauge to measure manifold pres
sure.
2 - Start unit and allow 5 minutes for unit to reach steady
state.
3 - While waiting for the unit to stabilize, observe the
flame. Flame should be stable and should not lift from
burner. Natural gas should burn blue.
NaturalLP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
4 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
8.
NOTE - Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug. Re-fire unit and
check for gas leaks. Seal any leaks if found.
E- Proper Combustion
Furnace should operate a minimum 15 minutes with cor
rect manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue out
let and compare to the tables below. The maximum carbon
monoxide reading should not exceed 100 ppm.
TABLE 7
ML180UHA
Unit
CO2%
For Nat
CO2%
For L.P.
-070
-090
-110
6.3 - 7.87.0 - 9.0
-135
F- High Altitude
The manifold pressure may require adjustment and com
bustion air pressure switch may need replacing to ensure
proper combustion at higher altitudes. Refer to table 8 for
manifold pressure and table 9 for pressure switch change
and gas conversion kits.
IMPORTANT
For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.
Manifold Pressure Settings at all Altitudes
Model
Input Size
All Models
Gas
Nat0.870.720.670.620.871.133.23
LP/propane2.302.302.192.122.302.753.23
0-610 m*
(0-2000 ft)
* See table 9 for proper high altitude gas conversion kit.
Pressure Switch and Gas Conversion Kits at all Altitudes
Model
Input Size
070
09080W5180W56
11080W5180W56
135No Change80W51
High Altitude Pressure Switch Kit
0-610 m
(0-2000 ft)
No Change
611-1219 m
(2001-4000 ft)
80W5180W56
611-914 m*
(2001-3000 ft.)
1220-1981 m
(4001-6500 ft)
TABLE 8
915-1219 m*
(3001-4000 ft)
1220-1524 m*
(4001-5000 ft.)
1525-1981 m*
(5001-6500 ft)
TABLE 9
High Altitude
Natural Gas Burner
Orifice Kit
1525-1981 m
(5001-6500 ft)
73W3711K1597W0496W95
Natural Gas to LP/Propane
Change Over Kit
0-1524 m
(0-5000 ft)
1525-1981 m
(5001-6500 ft)
Page 16
Line Pressure
kPa
MinMax
LP/Propane to
Natural Gas
Change Over Kit
1-1524 m
(1-5000 ft)
Page 17
G- Flame Signal
A microamp DC meter is needed to check the flame signal
on the integrated control.
Flame (microamp) signal is an electrical current which passes
from the integrated control to the sensor during unit operation.
Current passes from the sensor through the flame to ground to
complete a safety circuit.
To Measure Flame Signal - Integrated Control:
Use a digital readout meter capable of reading DC micro
amps. See figure 14 and table 10 for flame signal check.
1 - Set the meter to the DC amps scale.
2 - Turn off supply voltage to control.
Measuring Flame Signal
3 - Disconnect integrated control flame sensor wire from
the flame sensor.
4 - Connect (-) lead to flame sensor.
5 - Connect (+) lead to the ignition control sensor wire.
6 - Turn supply voltage on and close thermostat contacts to
cycle system.
7 - When main burners are in operation for two minutes, take
reading.
TABLE 10
Flame Signal in Microamps
NormalLowDrop Out
1.50.5 - 1.4 0.4
Flame
Sensor
Flame Sensor
Wire
Integrated
Control
(+)
Flame Sensor
Terminal
(+) To Control
Sensor
Terminal
Remove Sensor Wire from
Integrated Control and
Connect Alligator Clip (−)
to Frame Sensor Lead
DIGITAL METER
Set dial to measure dc microamps
Red Collar
Indicates
Positive Leads
(+)
(-) To
flame
sensor
Remove Sensor Wire from
Integrated Control and
Connect Alligator Clip (+)
to Terminal on Control
FIGURE 14
Page 17
Page 18
H- Proper Ground and Voltage
A poorly grounded furnace can contribute to premature ig
nitor failure. Use the following procedure to check for
ground and voltage to the integrated control.
1 - Measure the AC voltage between Line Neutral (spade
terminals) and “C” terminal (low voltage terminal
block) on the integrated control. See figure 15. A wide
variation in the voltage between Line Neutral and “C”
as a function of load indicates a poor or partial ground.
Compare the readings to the table below. If the read
ings exceed the maximum shown in table 11, make re
pairs before operating the furnace.
2 - In addition, measure the AC voltage from Line Hot to
Line Neutral (spade terminals) on the integrated con
trol. See figure 16. This voltage should be in the range
of 204 to 264VAC.
TABLE 11
Furnace Status
Power On Furnace Idle0.32
CAI / Ignitor Energized0.755
Indoor Blower EnergizedLess than 210
CHECK VOLTAGE BETWEEN LINE NEUTRAL
AND LOW VOLTAGE “C” TERMINAL
Measurement VAC
ExpectedMaximum
CHECK VOLTAGE BETWEEN LINE HOT
AND LINE NEUTRAL
AN2
AN1
GREEN
RED
AN1
RED
AN2
GREEN
FIGURE 16
FIGURE 15
Page 18
Page 19
V-TYPICAL OPERATING CHARACTERISTICS
A-Blower Operation and Adjustment
NOTE- The following is a generalized procedure and
does not apply to all thermostat controls.
1 - Blower operation is dependent on thermostat control
system.
2 - Generally, blower operation is set at thermostat sub
base fan switch. With fan switch in ON position, blower
operates continuously. With fan switch in AUTO position,
blower cycles with demand or runs continuously while
heating or cooling circuit cycles.
3 - Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is in
OFF position.
B-Temperature Rise (Figure 17)
Temperature rise for ML180UHA units depends on unit in
put, blower speed, blower horsepower and static pressure
as marked on the unit rating plate. The blower speed must
be set for unit operation within the range of “TEMP. RISE
°C” listed on the unit rating plate.
C-External Static Pressure
1 - Tap locations shown in figure 18 .
2 - Punch a 6.3 mm (1/4”) diameter hole in supply and re
turn air plenums. Insert manometer hose flush with in
side edge of hole or insulation. Seal around the hose
with permagum. Connect the zero end of the manome
ter to the discharge (supply) side of the system. On
ducted systems, connect the other end of manometer
to the return duct as above.
3 - With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blow
er motor speed to deliver the air desired according to
the job requirements. For heating speed external static
pressure drop must not be more than 125Pa (0.5”). For
cooling speed external static pressure drop must not
be more than 200Pa (0.8” W.C.)
4 - Seal the hole when the check is complete.
EXTERNAL STATIC PRESSURE
Supply Duct Static ________
Return Duct Static + _____
Total Duct Static =
________
(dry coil)
TEMPERATURE RISE
Supply Duct Temperature ________
Return Duct Temperature
Temperature Rise = ________
Supply Air
Return Air
FIGURE 17
_
_____
Supply Air
or
Return Air
FIGURE 18
-+
D-Blower Speed Taps
Blower speed tap changes are made on the integrated con
trol. See figure 4. The heating tap is connected to the
“HEAT” terminal and the cooling tap is connected to the
“COOL” terminal. On all units the continuous blower tap is
the same as the heating tap and unused taps must be se
cured on two dummy terminals labeled ”PARK. To change
out existing speed tap, turn off power and switch out speed
tap with tap connected to “PARK”. See blower speed tap
table on unit diagram for motor tap colors for each speed.
Page 19
Page 20
VI-MAINTENANCE
A-Preliminary and Seasonal Checks
1 - Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2 - Check voltage at disconnect switch. Voltage must be
within range listed on the nameplate. If not, consult the
power company and have voltage condition corrected
before starting unit.
At the beginning of each heating season, the system
should be checked as follows:
B-Filters
Filters should be inspected monthly. Clean or replace the
filters when necessary to ensure that the furnace operates
properly. Replacement filters must be rated for high veloc
ity airflow. See table 12.
TABLE 12
Furnace
Cabinet
Width
A - 338
(14-1/2”)
B- 446
( 17-1/2”)
C - 533
( 21”)
D - 622
(24-1/2”)
Cleaning the Heat Exchanger and Burners
NOTE - Use papers or protective covering in front of the fur
nace during cleaning.
1 - Turn off both electrical and gas power supplies to fur
nace.
2 - Remove flue pipe and top cap (some applications top
cap can remain) from the unit.
3 - Label the wires from gas valve, rollout switches, prima
ry limit switch and make-up box then disconnect them.
4 - Remove the screws that secure the combustion air in
ducer/pressure switch assembly to the collector box.
Carefully remove the combustion air inducer to avoid
damaging blower gasket. If gasket is damaged, it must
be replaced to prevent leakage.
5 - Remove the collector box located behind the combus
tion air inducer. Be careful with the collector box gas
ket. If the gasket is damaged, it must be replaced to
prevent leakage.
Filter Size mm (in) and Quantity
Side ReturnBottom Return
406 X 635 X 25 1
(16 X 25 X 1)
406 X 635 X 25 1
(16 X 25 X 1)
405 X 635 X 25 1
(16 X 25 X 1)
405 X 635 X 25 2
(16 X 25 X 1)
356 X 635 X 25 1
(14 X 25 X 1)
406 X 635 X 25 1
(16 X 25 X 1)
508 X 635 X 25 1
(20 X 25 X 1)
610 X 635 X 25 1
(24 X 25 X 1)
6 - Disconnect gas supply piping. Remove the screw se
curing the burner box cover and remove cover. Re
move the four screws securing the burner manifold as
sembly to the vestibule panel and remove the assem
bly from the unit.
7 - Remove screws securing burner box and remove
burner box.
9 - Remove screws from both sides, top and bottom of
vestibule panel.
10 -Remove heat exchanger. It may be necessary to
spread cabinet side to allow more room. If so, remove
five screws from the left side or right side of cabinet.
See figure 19.
11 - Backwash using steam. Begin from the burner opening
on each clam. Steam must not exceed 135°C (275°F).
12 -To clean burners, run a vacuum cleaner with a soft brush
attachment over the face of burners. Visually inspect in
side the burners and crossovers for any blockage
caused by foreign matter. Remove any blockage.
13 - To clean the combustion air inducer visually inspect and
using a wire brush clean where necessary. Use com
pressed air to clean off debris and any rust.
14 -Reinstall heat exchanger in vestibule. (Replace the
five screws in the cabinet from step 10 if removed).
15 - Reinstall collector box and combustion air assembly.
Reinstall all screws to the collector box and combustion
air inducer. Failure to replace all screws may cause
leaks. Inspect gaskets for any damage and replace if
necessary.
16 - Reinstall burner box, manifold assembly and burner box
cover.
17 -Reconnect all wires.
18 - Reconnect top cap and vent pipe to combustion air in
ducer outlet.
19 -Reconnect gas supply piping.
20 -Turn on power and gas supply to unit.
21 -Set thermostat and check for proper operation.
22 -Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred
means.
Page 20
Page 21
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly af
ter leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
23 -If a leak is detected, shut gas and electricity off and
repair leak.
24 -Repeat steps 23 and 25 until no leaks are detected.
25 -Replace access panel.
Remove 5 screws if necessary
(either side of cabinet)
1
2
3
4
C-Supply Air Blower
1 - Check and clean blower wheel.
2 - Motors used on the Lennox ML180UHA series units
are permanently lubricated and need no further lu
brication.
D-Flue and Chimney
Flue must conform to local codes. Flue pipe deteriorates
from the inside out and must be disconnected in order to
check thoroughly. Check flue pipe, chimney and all con
nections for tightness and to make sure there is no block
age or leaks.
E-Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 240VAC +
3 - Check amp-draw on the blower motor with inner blow
er access panel in place. See figure 20.
Motor Nameplate__________Actual__________
Check Motor AMP Draw
10%
FIGURE 19
5
OFF
P
−
EX
MR
W
3
2
1
kWh
kVAr
COMMV3V1
V2
AMP Meter
FIGURE 20
Page 21
Page 22
VII- Wiring and Sequence of Operation
1
8
2
5
3
4
1 -When there is a call for heat, W1 of the thermostat energizes W of the furnace control with 24VAC.
2 -Integrated control runs a self-check. S10 primary limit, S47 rollout switch and S21 secondary limit contacts are found to be closed. Call for
heat can continue.
3 -Integrated control (A92) energizes combustion air inducer B6. Combustion air inducer runs until combustion air pressure switch closes . Once
it closes, a 15-second pre-purge follows.
4 -Integrated control (A92) energizes ignitor. A 20-second warm-up period begins.
5 -Gas valve opens for a 4-second trial for ignition
6 -Flame is sensed, gas valve remains open for the heat call.