Lenovo 55948KX, 55948PX, RT11kVA, RT8kVA, 55949KX Product Manual

...
RT8kVA and RT11kVA 6U Rack or Tower Uninterruptible Power Supplies
Product Guide
The RT8kVA and RT11kVA 6U Rack or Tower Uninterruptible Power Supply (UPS) offerings provide extended power protection with increased efficiency and simplified power management to safeguard high­availability of System x® and ThinkServer® server environments. With efficiency ratings of up to 98%, these compact 6U rack or tower designs can help reduce energy usage without compromising performance or reliability.
The 6U Rack or Tower UPS units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required.
The 6U Rack UPS unit (RT8kVA or RT11kVA) is shown in Figure 1.
Figure 1. RT8kVA or RT11kVA 6U Rack UPS unit (Power module (top) and Battery module (bottom))
Did you know?
6U Rack or Tower UPS units feature Advanced Battery Management (ABM) technology that uses a unique three-stage charging technique that significantly extends battery service life and optimizes recharge time, compared to traditional charging methods.
6U Rack or Tower UPS units come standard with the Maintenance Bypass module, which enhances system availability by providing service continuity during UPS maintenance and upgrades.
6U Rack or Tower UPS units come standard with UPS Manager software that integrates seamlessly with the major virtualization platforms, which enables you to view and manage your entire power system from your current dashboard. It also triggers live migration during power outages and avoids data loss by gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.
RT8kVA and RT11kVA 6U Rack or Tower Uninterruptible Power Supplies 1
Ordering information
Table 1 shows the part numbers and feature codes for the 6U Rack or Tower UPS models and options.
Table 1. Part numbers and feature codes
Description Part number Feature code (MTM 5594-RU8)
UPS units
IBM RT8kVA 6U Rack or Tower UPS (200-240VAC) 55948KX A543
IBM RT8kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC) 55948PX A546
IBM RT11kVA 6U Rack or Tower UPS (200-240VAC) 55949KX A544
IBM RT11kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC) 55949PX A547
Extended Battery Modules (EBMs)
8kVA/11kVA 3U Rack or Tower Extended Battery Module 55949BX A545
Options
Environmental Monitoring Probe 46M4113 6146
The RT8kVA and RT11kVA 6U Rack or Tower UPS models are shipped standard with the Network Management Card (NMC) installed and include the following items:
A power module
A battery module
A Maintenance Bypass module (MBP) with the hardwired MBP detection cable and two hardwired power cables for connections to the power module's terminal block
An accessory kit that contains the following items:
Rack-mount kit Rack installation instructions Tower kit Serial cable: 3.7 m (12 ft) USB cable Remote On/Off (ROO) and Remote Power Off (RPO) connector Battery power cable Battery detection cable
A documentation kit that contains the following items:
Warranty flyer Important Notices Manual Documentation CD Software CD, which contains UPS Manager power management software
The Extended Battery Modules are shipped with the following items:
An accessory kit that contains the following items:
Rack-mount kit Tower kit EBM power cable EBM detection cable
A documentation kit that contains the following items:
Warranty flyer Important Notices Manual Documentation CD
The RT8kVA and RT11kVA 6U Rack or Tower UPS units have a hardwired terminal block connector for AC input power.
RT8kVA and RT11kVA 6U Rack or Tower Uninterruptible Power Supplies 2
All 6U Rack or Tower UPS models come standard with a NMC installed. The NMC provides convenient, over-the-network UPS remote monitoring and management through a standard web browser or UPS Power Manager UPM software. Figure 2 shows the UPS NMC.
Figure 2. UPS Network Management Card
The NMC includes the following features:
Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH
Simultaneous shutdown of protected servers
Configuration of automatic email messages in response to UPS alarms and to transmit reports
Customizable actions, including automatic shutdown if there is an extended power failure with standard UPS Power Protector software
Control of UPS on/off switching with a web browser
Adjustment and control of load segments through the HTML interface, including sequential starting of the installation and optimization of backup time by shutting down non-priority systems
Automatic date and time adjustment through an NTP server
Dual stack IP v4/IP v6
Recording of events and measurements in the card log
Data and event logging in the nonvolatile memory
Card firmware update through the network
10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
Measurement of humidity and temperature with the optional Environmental Monitoring Probe (EMP)
An optional EMP (part number 46M4113) is used to report local temperature and humidity values and make that information available to management tools. The EMP connects to the UPS via the NMC. The EMP is shown in Figure 3.
Figure 3. Environmental Monitoring Probe
The Environmental Monitoring Probe has the following features:
Monitors temperature, humidity, and status of two user-provided contact devices or sensors
RT8kVA and RT11kVA 6U Rack or Tower Uninterruptible Power Supplies 3
Connects to an NMC through an RJ-45 CAT5 Ethernet cable (1 m cable that is included with the EMP)
Can be located up to 20 m (65.6 ft) from the UPS
Measures ambient temperatures between 0 - 80 °C (32 - 176 °F), with an accuracy of ±1 °C (33.8° F)
Measures relative humidity between 10 - 90%, with an accuracy of ±5%
Displays temperature, humidity, and contact closure status through a Web browser
Supports user-defined alarm thresholds for temperature, humidity, and contact closure status
Stores events in the NMC's event log
Sends SNMP alarms to network management systems
Sends email notifications through SMTP
Features
A UPS is a device that acts as a defensive barrier between electronic equipment and incoming power problems. It conditions, regulates, and filters out power disturbances to ensure a clean power source for IT equipment. A UPS also provides battery backup if there is a power failure.
In today’s high availability server environments, unplanned power outages or line quality irregularities can have a considerable financial impact on all sized businesses. The typical utility power is 99.9% available, but that means that there can be almost 9 hours of downtime a year, not to mention brownouts and other power quality problems. Selecting the right UPS can help protect against these potentially costly issues.
The RT8kVA and RT11kVA 6U Rack or Tower UPS units protect against the following power problems: power failures, power sags, power surges, under-voltage, electrical line noise, over-voltage, frequency variation, switching transients, and harmonic distortion.
The RT8kVA and RT11kVA 6U Rack or Tower UPS models offer the following features:
High-efficiency protection delivers more real power (Watts) in a compact tower or 6U rack design, which lowers power and cooling consumption
Graphical Liquid Crystal Display (LCD) provides intuitive configuration, management, and monitoring capabilities in the following languages to reduce management complexity:
English French German Spanish Russian Portuguese Italian
Hot-swappable batteries for maximum uptime, availability, and ease of maintenance
Standard UPS Power Manager software provides effective local or remote power monitoring and management for servers and virtual machines, and allows for graceful remote system shutdown
ABM technology significantly extends battery service life and optimizes recharge time
Optional external battery modules (EBMs) provide extra run time to critical systems during a prolonged power outage
Standard NMC provides enhanced UPS monitoring and control over-the-network through a standard web browser
Optional Environmental Monitoring Probe provides thermal management requirements (temperature and humidity)
Standard Maintenance Bypass enhances availability by providing service continuity during UPS
RT8kVA and RT11kVA 6U Rack or Tower Uninterruptible Power Supplies 4
maintenance and upgrades
Provides dual channel communication through the USB or RS-232 port and an NMC at the same time to maximize communications flexibility
Flash upgrades firmware for both the UPS and the NMC, which makes it an ideal solution for remote locations
Includes ROO and RPO connectors to control power of the UPS unit through a wired remote switch
Technical specifications
Table 2 lists the technical specifications for the 8kVA and 11kVA 6U Rack or Tower UPS models.
Table 2. Technical specifications
Specification
RT8kVA 6U Rack or Tower UPS (200-240VAC)
RT8kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC)
RT11kVA 6U Rack or Tower UPS (200­240VAC)
RT11kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC)
General
Part number 55948KX 55948PX 55949KX 55949PX
Form factor 6U Rack or Tower 6U Rack or Tower 6U Rack or Tower 6U Rack or Tower
Topology Online, double conversion, sinewave output
VA/Watts rating 8000 VA
7200 W
8000 VA 7200 W
11000 VA 10000 W
11000 VA 10000 W
Efficiency (on utility power)
Online mode: Up to 94.5%
High efficiency mode: Up to 98%
Transfer time Online mode: 0 ms (no break)
High efficiency mode: 10 ms maximum (due to loss of utility power)
Energy Star compliant Yes No Yes No
Electrical input
Input voltage 200 - 240 V AC, 1-
Phase
380 - 415 V AC, 3­Phase
200 - 240 V AC, 1­Phase
380 - 415 V AC, 3­Phase
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Max input amperage 40 A 40 A 50 A 50 A
Input connector Hardwired terminal block
Input line cord Onsite wiring required
Electrical output
Output voltage settings 200/208/220/230/240 V AC 200/208/220/230/240 V AC
Output frequency 50/60 Hz 50/60 Hz
Output power capacity 200 - 240 V AC: 8000 VA/7200 W 200-208 V AC: 10000 VA/9000 W
220 V AC: 11000 VA/9900 W
230-240 V AC: 11000 VA/10000 W
Output connectors 4x IEC 320-C19 (16 A) (on the MBP) 4x IEC 320-C19 (16 A) (on the MBP)
Batteries
Battery type Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed, leak-proof
RT8kVA and RT11kVA 6U Rack or Tower Uninterruptible Power Supplies 5
Battery management ABM technology or temperature-compensated charging method (user selectable),
automatic battery test and deep discharge protection, and automatic recognition of external battery units
Battery replacement Hot-swap standard and extended battery modules
External battery support
Up to 4 (PN 55949BX)
Typical backup times See Table 3
Communications and management
USB port (Type B) Yes Yes Yes Yes
RS-232 serial port (RJ-
45)
Yes Yes Yes Yes
10/100 Mbps Ethernet port (RJ-45)
Yes (on the Network Management Card)
Environmental monitoring
Optional with Environmental Monitoring Probe, 46M4113 (connects to the Network Management Card)
Management software UPS Power Manager and UPS Power Protector
Control panel Intelligent 5-button graphical LCD
LED indicators Online, On Battery, Bypass, and Fault
Remote On/Off and Power Off
Remote On/Off and Remote Power Off terminal block connectors
Specification
RT8kVA 6U Rack or Tower UPS (200-240VAC)
RT8kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC)
RT11kVA 6U Rack or Tower UPS (200­240VAC)
RT11kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC)
Table 3 lists the expected period that the 6U Rack or Tower UPS models operates only on batteries, depending on the load.
Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, and temperature.
Table 3. 6U Rack or Tower UPS runtime chart
Load Run time, Minutes
Percentage Watts Standard battery module 1x EBM 2x EBMs 3x EBMs 4x EBMs
RT8kVA 6U Rack or Tower UPS (1-phase or 3-phase)
25% 1800 W 35 85 140 173 220
50% 3600 W 16 36 65 86 118
75% 5400 W 9 23 36 53 72
100% 7200 W 5 16 27 36 50
RT11kVA 6U Rack or Tower UPS (1-phase or 3-phase)
25% 2500 W 25 60 97 136 163
50% 5000 W 10 25 42 61 79
75% 7500 W 5.5 15 25 37 48
100% 10000 W 3 10 18 25 34
RT8kVA and RT11kVA 6U Rack or Tower Uninterruptible Power Supplies 6