Lennox International Inc. SA13 User Manual

Page 1
INSTALLATION AND
MAINTENANCE INSTRUCTIONS
(2,4)SA13 Series
Electric Cooling Package Unit
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer or service agency.
WARNING
Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical compo­nents. Only trained and qualified service personnel should install or service this equip­ment. Installation and service performed by unqualified persons can result in property damage, personal injury, or death.
WARNING
If this unit is to be installed in a mobile or manu­factured home application, the ductwork must be sized to achieve static pressures within the manufacturer’s guidelines. All other installation guidelines must also be followed. Failure to do so may result in equipment damage, personal injury, and improper performance of the unit.
*48392M005*
WARNING
Sharp metal edges can cause injury. When installing the unit, use care to avoid sharp edges.
TABLE OF CONTENTS
INSTALLATION ...................................... 2
OPERATION .......................................... 7
MAINTENANCE..................................... 8
WIRING DIAGRAM ................................ 9
WARRANTY ........................................ 10
Manufactured By
A.A.C.
A Lennox International Inc. Company
421 Monroe Street
Bellevue, OH 44811
CAUTION
The installation of this appliance must conform to the requirements of the National Fire Protection Association; the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
# 48392M005 Page 1
Save these instructions for future reference
Page 2
INSTALLATION
Location
These instructions explain the recommended method of installation of the SA electric cooling unit and associated electrical wiring.
This unit is designed and approved for use as a self­contained air-to-air air conditioning system.
The units are factory equipped with a transformer and blower control for applications without auxiliary heat. Electric heat accessory kits (PHK) can be ordered for field installation of additional heat where required.
These instructions, and any instructions packaged with mating components and/or accessories, should be care­fully read prior to beginning installation. Note particularly any CAUTIONS or WARNINGS in these instructions and all labels on the units.
These instructions are intended as a general guide only, for use by qualified personnel and do not supersede any national or local codes in any way. Compliance with all local, state, provincial, or national codes pertaining to this type of equipment should be determined prior to installation.
IMPORTANT: This product has been designed and manufac­tured to meet ENERGY STAR criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and air flow instructions. Failure to confirm
proper charge and airflow may reduce energy effi­ciency and shorten equipment life.
The unit is designed to be located outdoors with sufficient clearance for free entrance to the air inlet and discharge air openings. The location must also allow for adequate service access.
The unit must be installed on a solid foundation that will not settle or shift. Adequate structural support must be pro­vided. Maintain minimum clearances as shown in Figure 1 and Table 1 and install the unit in level position. Isolate the base from the building structure to avoid possible transmis­sion of sound or vibration into the conditioned space.
Using Accessory Lift Kit
Spreaders
(Field Supplied)
Lifting Bracket
Accessory
Sheet Metal Screw
To avoid possible damage to unit panels from lifting clevis, place packing material between clevis and panels before lifting unit.
Inspection of Shipment
Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier’s freight bill. Take special care to examine the unit inside the carton if the carton is damaged. File a claim with the transportation company.
If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT, as claim may be denied.
Check the unit rating plate to confirm specifications are as ordered.
Limitations
The unit should be installed in accordance with all national and local safety codes.
Limitations of the unit and appropriate accessories must also be observed.
The unit must not be installed with any ductwork in the outdoor air stream. The outdoor fan is not designed to operate against any additional static pressure.
Figure 1
Avoid placing the unit near quiet areas such as sleeping quarters or study rooms. Normal operating
sound levels may be objectionable if the unit is placed near certain rooms.
Do not permit overhanging structures or shrubs to obstruct condenser air discharge inlet or outlet.
For improved start-up performance, the indoor coil should be washed with suitable detergent to remove any residue from manufacturing processes.
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. An accessory lift kit can be purchased to aid in rigging (see Figure 1). Spreaders whose length exceed the largest dimension across the unit must be used across the top of the unit. Recommended spreader length: 3 ton and smaller package units – 44", 3.5 ton and larger units – 54".
Page 2 # 48392M005
Page 3
Unit
Drain Connection
Positive Liquid Seal Required
3.00" Min.
1.00" Min.
12.00" Max.
Minimum Clearance Requirements
oT
elbitsubmoC
lairetaM
tnorF"0"84"3
roF
ecivreS
roF
Clearances
All units require certain clearances for proper operation and service. Refer to Table 1 for the minimum clearances to combustibles as well as minimum clearances necessary
reporP
noitarepO
for servicing and proper unit operation.
In the U.S., units may be installed on combustible floors made from wood or class A, B, or C roof covering material. In Canada, units may be installed on combustible floors.
raeR "0 "42 "3
resnednoC
dnE
rewolB
dnE
poT"0"63"63
"0"42"3
"0 "03 "0
Table 1
Units may also be moved or lifted with a forklift while still in the factory-supplied packaging. The lengths of the
forks of the forklift must be a minimum of 42".
CAUTION
Before lifting a unit, make sure that the weight is distributed equally on the cables so that it will lift evenly.
Service Access
Access to all serviceable components is provided by four removable panels: filter compartment, blower compart­ment, heater compartment, and top panel.
Condensate Drain
The SA package unit is equipped with a 3/4" FPT coupling for condensate line connection. Plumbing must conform to local codes. Use a sealing compound on male pipe threads.
The condensate drain line must be properly trapped and routed to a suitable drain. See Figure 3 for proper
drain arrangement. The drain line must pitch to an open drain or pump to prevent clogging of the line. Seal around the drain connection with suitable material to prevent air leakage into the return air system.
Typical Condensate Drain Connection
Roof Curb Installation
If a roof curb is used, follow the manufacturers Installation Instructions and be sure that all required clearances are observed (see following Clearances section).
Roof Curb Assembly
Figure 3
Ductwork
Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA).
# 48392M005 Page 3
Figure 2
A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. It is recommended that supply and return duct connections at the unit be made with flexible joints.
Page 4
The supply and return air duct systems should be de­signed for the CFM and static requirements of the job.
They should not be sized by matching the dimensions of the duct connections on the unit.
Outdoor ductwork must be insulated and waterproofed.
clean or replaced. Dirty filters will reduce the airflow of the unit. Filters should be sized in accordance with Table 2.
Minimum Required Surface Area
for Disposable Filters
Equipment is shipped for side ductwork connection. The unit can be converted to bottom ductwork connection by removing the duct covers located over the bottom duct openings and placing these covers over the side duct openings (see Figure 4).
To remove the bottom duct cover over supply opening:
1. Remove screw on cover nearest side opening.
2. Lift end of cover slightly and push to slide back screw/ pin free from duct flange.
3. Slide duct cover out the side duct opening.
Removing Bottom Duct Covers
2
1
1. Remove screw and lift.
2. Slide cover to free back pin.
Base
Figure 4
CAUTION
gnilooClanimoN
000,4276.2
000,03 33.3
000,6300.4
000,24 76.4
000,8433.5
000,06 76.6
aerAretliF
).tf.qs(
Table 2
Electrical Wiring
WARNING
Line voltage is present at all components when unit is not in operation on units with single pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies. Failure to disconnect all power supplies could result in personal injury or death.
When fastening ductwork to side duct flanges on unit, insert screws through duct flanges only; do not insert screws through casing. If using bottom duct work, do not use screws to secure ductwork to bottom duct opening under drain pan side. Using screws to secure bottom duct may damage drain pan.
Filters
All wiring should be done in accordance with the National Electrical Code, ANSI/NFPA No. 70 (latest edition); Canadian Electrical Code Part 1, CSA C22.1 (latest edition); or local codes where they prevail. Use
wiring with a temperature limitation of 75°C minimum. Run the 208 or 230 volt, 60 hertz electric power supply through a fused disconnect switch to the connection box of the unit and connect as shown in the wiring diagram located on the inside of the control access panel.
CAUTION
Air filters are to be used with this heating/cooling unit. Filters are not factory supplied in the unit. However, a filter frame accessory is available from the manufacturer that allows filters to be installed within the unit. If the filter frame accessory is not used, a filter must be installed in the duct work by the installer. Filters must always be installed ahead of the evaporator coil and must be kept
Page 4 # 48392M005
When connecting electrical power and control wiring to the unit, waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation.
Page 5
WARNING
Unit must be grounded in accordance with national and local codes. Failure to ground unit properly can result in personal injury or death.
Electrical Access
Heater Power Entry
Power supply to the unit must be N.E.C. Class 1, and must comply with all applicable codes. A fused disconnect switch should be field provided for the unit. The switch must be separate from all other circuits.
If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram. Electrical wiring must be sized to carry minimum circuit ampacity marked on the unit. Use copper conduc- tors only. Each unit must be wired with a separate branch circuit and be properly fused.
Typical Wiring Connections
THERMOSTAT
ECONOMIZER
NOT
INSTALLED
CAUTION
Do not connect connections except when
required by the indoor thermostat. Refer to the
C
thermostat installation instructions.
RR
W
G G
OUTDOOR UNIT
CC
YY Y1
W1
W2
Thermostat
Thermostat
The room thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow the
THERMOSTAT
CC
W
GG
Y2
OUTDOOR UNIT
RR
Y
W1
W2
Entry
Line Voltage
ECONOMIZER
BLUE
WHITE
YELLOW
GREEN
BLACK
Entry
Figure 5
CAUTION
Do not connect connections except when
required by the indoor thermostat. Refer to the
C
thermostat installation instructions.
L2 L1
POWER WIRING
208/230-1-60
POWER WIRING
24V CONTROL WIRING
(NEC CLASS 2)
* W1, W2 CAN BE USED TO STAGE ELECTRIC
HEAT ACCESSORY ON MODELS.15 & 20 KW
* 5 & 10 KW HEATER ACCESSORY FUNCTION
W1 ONLY.OFF
TYPICAL WIRING CONNECTION
(90°C MIN. WIRE)
1 PHASE
GROUND SCREW
POWER WIRING
200/230-3-60, 460/575-3-60
(90°C MIN. WIRE)
POWER WIRING
24V CONTROL WIRING
(NEC CLASS 2)
* W1, W2 CAN BE USED TO STAGE ELECTRIC
HEAT ACCESSORY ON 15 & 20 KW MODELS.
* 10 KW HEATER ACCESSORY FUNCTION OFF
W1 ONLY.
TYPICAL WIRING CONNECTION
3 PHASE
L1L2L3
GROUND SCREW
Figure 6
# 48392M005 Page 5
Page 6
manufacturer’s instructions enclosed with thermostat for general installation procedure. Color-coded insulated wires (#18 AWG) should be used to connect thermostat to unit. Four wires are required for cooling.
Compressor
Heater Kit Accessory Installation
Units are shipped with compressor mountings factory­adjusted and ready for operation. Caution: Do not loosen
compressor mounting bolts.
Heater Kit Accessory (if used)
The unit is fully equipped for cooling operation without auxiliary heat. A heater kit accessory may also be used.
To install the heater kit accessory (see Figure 7):
1. Disconnect the power and remove the heater compart­ment access panel.
2. Disconnect the plug separating the high voltage wire harness. Remove the high voltage wire harness plug and discard.
3. Remove the heater blockoff by removing the four screws holding it in place.
4. Insert the heater into the control panel and fasten in the same mounting holes.
5. Plug the heater wiring harness into the wire harness on the control assembly. Field wiring of the auxiliary heater is separate from the unit power supply. Wire the power supply wiring for the heater to the appropriate connections on the heater kit.
6. Replace the heater compartment access panel and reconnect the power.
Removal of Unit from Common Venting System
When an existing furnace is removed from a common venting system serving other appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted with each appliance while the other appliances connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
Heater
Blockoff
Heater
Compartment
Access
Panel
Heater Kit
Figure 7
are located and other spaces in the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Following the lighting instructions, place the unit being inspected in operation. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft control relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
6. Follow the preceding steps for each appliance con­nected to the common venting system.
7. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other fuel burning appliance to their previous condition of use.
8. If improper venting is observed during any of the above tests, the common venting system must be corrected. See National Fuel Gas Code, ANSI
Z223.1 (latest edition) or CAN/CGA B149.1 & .2 Canadian Installation Codes to correct improper operation of common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no block­age or restriction, leakage, corrosion, or other deficien­cies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows between the space in which the appliances remaining connected to the common venting system
Page 6 # 48392M005
Page 7
OPERATION
Sequence of Operation
Cooling
Upon cooling demand, the thermostat closes circuit R and Y. Closing R and Y closes the unit contactor, starting the compressor and outdoor fan. The thermostat automatically closes R to G circuit which also brings on the indoor blower at the same time. Upon satisfying cooling demand, the thermo­stat will open the above circuits and open the main contactor, stopping the compressor and outdoor fan. If the unit is equipped with a delay timer, the blower will continue to operate for 90 seconds which improves system efficiency.
Circulating Air Blower
The circulating air blower is controlled by a timing circuit in the blower control. Timings are not adjustable.
There is no blower “on” delay after a call for heating or cooling. Blower “off” delay is 90 seconds after the thermo­stat is satisfied.
Cooling System Performance
For maximum performance of the cooling system, operat­ing temperatures and pressure should be checked. Super­heat should be determined at Standard ARI test conditions of 82°F outdoor and 80°F indoor dry bulb/67°F wet bulb. If superheat measured deviates from values found in Table 3, refrigerant charge should be adjusted accordingly for maximum performance.
Suction Superheat
taehrepuSnoitcuS
snoitidnoCIRA@
eziS
22R A014
4251
03 °02 °51
6021
24 °02 °21
BWDI°76/BDDI°08-DO°28
06,8001
Table 3
# 48392M005 Page 7
Page 8
MAINTENANCE
Owner Record
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in dangerous operation, serious injury, death, or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to unit.
When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
Periodic inspection and maintenance normally consists of changing or cleaning the filters and cleaning the outdoor coil. On occasion, other components may also require cleaning.
Model # _________________________________
Serial # _________________________________
Installation Date ___________________________
Installed by:
Dealer __________________________________
Address _________________________________
Telephone # ______________________________
License # ________________________________
Filters
Filters should be checked at least every 6 weeks. Dispos­able filters should be replaced when dirty, and cleanable filters should be cleaned regularly. It is important to keep the air filters clean, as dirty filters can restrict airflow and the blower motor depends upon sufficient air flowing across and through it to keep from overheating.
Motors
Indoor and outdoor fan and vent motors are permanently lubricated and require no maintenance.
Outdoor Coil
Dirt and debris should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Clean­ing should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure the power to unit is shut off prior to cleaning. Care should be used
when cleaning the coil so that the coil fins are not damaged.
Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.
Page 8 # 48392M005
Page 9
P-6
WHT
W1
GRN
G
RED
R
YEL
Y
THERMOSTAT
BLU
C
S1
P-5
Settings
Factory Shipped
YEL
W1 & W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 15 & 20KW MODELS.
5, 7.5 & 10KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY.
ELECTRIC SHOCK HAZARD. UNIT MUST BE GROUNDED
IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
WARNING-
NOTE:
YEL
Unit
42 LOW
36 HIGH
30 MED
24 LOW
Cooling Input (BLK)
48 MED
60 HIGH
BLOWER SPEED CHART
S4
SWITCH
(IF USED)
HIGH PRESSURE
YEL
BLU
K1
24V
BLK
BLU
GRN
G
FUSE
XFMR-R
BLU
YEL
CONDENSER
BLK
H
RED
A15
C
XFMR-C
B4
FAN MOTOR
RED
BLOWER
CONTROL
BLU
BLU
WHT
COMPRESSOR
CONTACTOR
T2
RED
R
T1
TRANSFORMER
INDOOR
BLOWER
B3
T1
MOTOR
L
C
M
H
C4
CAPACITOR
BRN
PUR
F
C
C12
DUAL
CAPACITOR
BLK
208/230V-1-60
S
C
B1
YEL
R
COMPRESSOR
CONTACTOR
RED
LINE VOLTAGE FIELD INSTALLED.
BLK
BLK
P-3
RED
NC
NO
P-1
240V
208V
A15
CONTROL
BLOWER
C
BLK
SEE CHART
FOR WIRING
CHM
K1-1
COMPRESSOR
L
MOTOR
SPEED TAPS
L1
IF ANY OF THE ORIGINAL WIRE IS REPLACED,
THE SAME SIZE AND TYPE WIRE MUST BE USED.
USE COPPER CONDUCTOR ONLY, MIN 75°C WIRE.
CONTACTOR
L1
K1-2
L2
P-2
P-4
P/N 48396-001
Wiring Diagram
L2
# 48392M005 Page 9
Figure 9
Page 10
Limited Warranty
August 1, 1997
This warranty gives you specific legal rights and you may have other rights
which vary from state/province to state/province.
Subject to the limitations stated in this warranty, we warrant to the first buyer for use the residential heating, cooling, or heat pump unit, when installed, operated, and maintained as required by this warranty, to be free of defects in workmanship or material for a period of 5 years in residential installations (1 year in non-residential installations) from the time of installation. We will replace any defective component without cost or expense to you except for the costs of delivery and labor for removal and replacement of the defective component.
These (2/4)SA13 package cooling units carry a 5-year limited warranty on the compressor. Limited warranties apply to the original owner in private owner-occupied residences.
Warranty Begins
The warranty period begins when the installation is complete and the product is ready to operate. You must be able to verify this date whenever a warranty claim is made. Original bill of sale, installer’s invoice, or other similar document will suffice. If the beginning date cannot be verified, we will consider warranty coverage to begin 6 months after the date the product was shipped from our factory.
Limitations on Implied Warranties
Implied warranties of merchantability or, to the extent applicable, fitness for a particular purpose are limited to 5 years, the same duration as the basic limited written warranty provided herein. Some states/provinces do not allow limitations on how long an implied warranty of merchantability or fitness lasts, so the above limitations or exclusions may not apply to you.
Only Warranty
This written Limited Warranty is the only warranty made by the warrantor; this warranty is in lieu of and excludes all other warranties, express or implied. The warrantor does not authorize any person to provide any other warranty or to assume for it any further obligation in connection with the warranted product.
What is NOT Covered
1. Cabinets or cabinet pieces.
2. Normal maintenance items such as filters, fan belts, fuses, or other consumable items.
3. Damage caused by misuse, failure to maintain properly, accidents, or acts of God.
4. External wiring, piping, venting, or attachment of accessory products not integral to our product, including without limitation, humidifier, air cleaner, vent damper, thermostat, or other mechanical devices not manufactured by the warrantor.
5. Products that have been operated in a corrosive atmosphere where a concentration of acids, halogenated hydrocarbons, or other corrosive elements causes deterioration to metal surfaces or integral components. NOTE: Operation in a corrosive atmosphere is considered abuse and voids this warranty.
6. Products that have NOT been installed in accordance with our published installation instructions, applicable local, state/ provincial, or national codes, ACCA published standards.
7. Products that have NOT been installed by competent, qualified installers.
8. Products that have been moved from their original place of installation.
Warranty on Replacement Components
Any replacement component furnished by us will assume the remaining (unused) portion of the Limited Warranty.
Consequential Damages
The warrantor shall not be responsible for any consequential damages caused by any defect in the product. Some state/provinces do not allow the exclusion or limitations of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This product must be installed, used, and cared for in accordance with the instruction manual. You are responsible for required periodic maintenance or service, such as changing or cleaning of air filters and lubrication or cleaning of components. Failure to properly install, operate, or maintain your unit voids this warranty.