Lennox International Inc. GWB8-075IE-2, GWB8-042IE-2, GWB8-187IE-2, GWB8-150IE-2, GWB8-112IE-2, GWB8-225IE-2 User Manual
PRODUCT LITERATURE
Lennox Industries Inc.
Dallas, Texas
INSTALLATION
INSTRUCTIONS
GWB8-042IE-2, GWB8-075IE-2
GWB8-112IE-2, GWB8-150IE-2
GWB8-187IE-2, GWB8-225IE-2
GAS FIRED BOILER
RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE
These instructions must be affi xed on
or adjacent to the boiler .
!
WARNING
Improper installation, adjustment, alteration,
service, or maintenance could result in death
or serious injury. Refer to this manual for
assistance. For additional information consult
a qualifi ed installer, service agency, or the gas
supplier.
This boiler cannot be used with all types of
chimneys. Read these instructions carefully
before installing.
C.S.A. Certifi ed
For Natural Gas Or Propane
Tested For 50 psi.
ASME
Working Pressure
GAS-FIRED HOT WATER BOILERS
These Gas-Fired Water boilers are low pressure,
sectional cast iron boilers Design Certifi ed by
CSA (Canadian Standards Association) for
use with Natural and Propane Gases. They
are constructed and hydrostatically tested for
maximum working pressure of 50 psi (pounds
per square inch) in accordance with A.S.M.E.
(American Society of Mechanical Engineers)
Boiler and Pressure Vessel Code Section IV
Standards for Cast Iron Heating Boilers.
A.9 Intermittent Pilot ................................ 30
WARNING
!
Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
WARNING
!
Keep boiler area clear and free from combustible
materials, gasoline and other fl ammable vapors
and liquids.
DO NOT obstruct air openings to boiler room.
Modifi cation, substitution or elimination of factory
equipped, supplied or specifi ed components may
result in personal injury or loss of life.
TO THE OWNER - Installation and service of this
boiler must be performed by a qualifi ed installer.
TO THE INSTALLER - Leave all instructions with
boiler for future reference.
When this product is installed in Commonwealth of
Massachusetts installation must be performed by
Licensed Plumber or Licensed Gas Fitter.
2
BOILER RATINGS & CAPACITIES
Table 1 RATINGS NATURAL AND PROPANE GASES
**Net
Model
GWB8-042IE-242.5363184.443
GWB8-075IE-275.0635583.443
GWB8-112IE-2112.5948283.043
GWB8-150IE-2150.012510982.743
GWB8-187IE-2187.515513582.344
GWB8-225IE-2225.018616282.044
* MBH = 1,000 Btuh = British Thermal Unit Per Hour. Boilers are equipped for altitudes up to 2,000 feet only.
Input
*Mbh
Heating
Capacity
*Mbh
AHRI
Rating
Water
*Mbh
AFUE
Vent Diameter (Inches)
To Chimney
(Category I)
Horizontal Vent
(Category III)
• U.S.A. Only - For altitudes above 2,000 feet, ratings should be reduced at the rate of 4% for each
1,000 feet above sea level.
• Canada Only - Boilers may be used at high altitude (2,000-4500 feet/640-1350m) by using a certifi ed
fi eld conversion kit, resulting in a 10% de-rate. Contact Provincial authority having jurisdiction for
installations above 4500 ft (1350m)above sea level.+ Heating Capacity based on D.O.E. (Department
of Energy) test procedure.
** Net AHRI Water Ratings i
ndicate amount of remaining heat input that can be used to heat the radiation
or terminal units. Net AHRI Ratings shown are based on an allowance of 1.15 Selection of
boiler size should be based upon “Net AHRI Rating” being equal to or greater than calculated
heat loss of building.
Manufacturer should be consulted before selecting a boiler for installations having unusual piping
and pickup requirements.
New York City MEA Number 484-84-E Vol. IV.
This boiler cannot be used with all types of chimneys. Read these instructions carefully before installing.
These Gas-Fired Hot Water Boilers are low pressure, sectional cast iron boilers Design Certifi ed by C.S.A. (Canadian Standards
Association) for use with Natural and Propane Gases. Constructed and hydrostatically tested for maximum working pressure of 50 psi in
accordance with A.S.M.E. Boiler and Pressure Vessel Code Section IV Standards for cast iron heating boilers.
Boilers must stand on noncombustible fl oor. If installed on combustible fl oor, please refer to Repair Parts manual for appropriate
Combustible Floor Base part number.
Boilers For Use At High Altitude
Boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes above 2,000 feet above sea level,
input ratings are reduced by change in main burner orifi ce size.
U.S.A. Only - For altitudes above 2,000 feet above sea level, input ratings should be reduced at rate of 4% for each 1,000 feet above
sea level. Consult National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1,
or manufacturer for correct orifi ce sizing information.
Canada Only - For altitudes in the range of 2,000-4,500 feet (610 - 1350m) above sea level, boilers may be fi eld equipped for use
at high altitude by using a certifi ed fi eld conversion kit. The change in main burner orifi ce size results in the boiler’s input rating
being reduced by 10%.The conversion shall be carried out by a manufacturer’s authorized representative, in accordance with the
requirements of the manufacturer, provincial or territorial authorities having jurisdiction and in accordance with the requirements of
CSA-B149 Natural Gas and Propane Installation Code. The certifi ed fi eld conversion kit includes a conversion data plate, which must be
attached to the boiler adjacent to the rating plate, indicating that the boiler has been converted for high altitude use. The conversion
data plate must be fi lled in with the correct conversion information.
For altitudes over 4500 feet (1350m), contact Provincial authority having jurisdiction.
Improper installation, adjustment, alteration, service
or maintenance could result in death or serious
injury
.
1.
The installation must conform to the requirements of
the authority having jurisdiction or, in the absence
of such requirements, to the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane
Installation Code, CAN/CSA B149.1
2.
Where required by authority having jurisdiction,
installation must conform to the Standard for Controls
and Safety Devices for Automatically fi red Boilers,
ANSI/ASME CSD-1.
3.
This boiler series is classifi ed as a Category I. Vent
installation shall be in accordance with “Venting of
Equipment ,” of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or “Venting Systems and Air Supply
for Appliances,” of the Natural Gas and Propane
Installation Code, CAN/CSA B149.1, or applicable
provisions of the local building codes.
4.
Boiler has met safe lighting and other performance
criteria with gas manifold and control assembly on
boiler per latest revision of ANSI Z21.13/CGA 4.9.
5.
Install such that gas ignition system components are
protected from water (dripping, spraying, rain, etc.)
during appliance operation and service, (circulator
replacement, condensate trap, control replacement,
etc.).
6.
Locate boiler on level, solid base as near chimney as
possible and centrally located with respect to heat
distribution system as practical.
7.
Verify you have the right size boiler before starting
installation. See rating and capacity table.
8.
When installed in utility room, door should be wide
enough to allow largest boiler part to enter, or to
permit replacement of another appliance such as water
heater.
9.
Boiler installed in building under construction, take
care to insure clean combustion air supply during
construction process. Airborne particulates such as
from drywall dust and from fi berglass insulation can
clog burner ports and cause incomplete combustion and
sooting.
!
WARNING
Fire hazard. Do not install boiler on combustible
fl ooring or carpeting. Failure to follow these
instructions could result in death or serious injury.
NOTICE
Follow local regulations with respect to installation
of CO detectors.
10.
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY - For installation on combustible
fl ooring special base must be used. (See Replacement
Parts Section.) Do Not Install Boiler on carpeting.
11.
Verify boiler is supplied with correct type of gas, fresh
air for combustion, and suitable electrical supply.
Figure 1 - Minimum Clearances To Combustible
Construction
6”
8”
Rear
Opposite Side
6”
Boiler
Front
18”
Table 2 - BOILER MINIMUM CLEARANCE TO
COMBUSTIBLES
Unit
Top6” (152mm)
Rear6” (152mm)
Control Side8” (203mm)
Opposite Side6” (152mm)
Front (Alcove)18” (457mm)
Flue/Vent Connector6” (152mm)
Near Boiler Piping1/2” (13mm)
Control Side
8”
Minimum
Clearances
Set unit on concrete or other noncombustible material base or
fl oor. DO NOT INSTALL ON CARPETING.
5
VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance
with the section “Air for Combustion and Ventilation,” of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation
Code, CAN/CSA B149.1, or applicable provisions of local
building codes.
Provide make-up air where exhaust fans, clothes dryers,
and kitchen ventilation equipment interfere with proper
operation.
National Fuel Gas Code recognizes several methods
of obtaining adequate ventilation and combustion air.
Requirements of the authority having jurisdiction may
override these methods.
• Engineered Installations. Must be approved by
authority having jurisdictions.
• Mechanical Air Supply. Provide minimum of 0.35
cfm per Mbh for all appliances located within space.
Additional requirements where exhaust fans installed.
Interlock each appliance to mechanical air supply
system to prevent main burner operation when
mechanical air supply system not operating.
• All Indoor Air. Calculate minimum volume for all
appliances in space. Use a different method if
minimum volume not available.
о Standard Method. Cannot be used if known air
National Gas and Propane Installation Code Requires
providing air supply in accordance with:
infi ltration rate is less than 0.40 air changes per
hour. See Table 3 for space with boiler only. Use
equation for multiple appliances.
3
Volume ≥ 50 ft
x Total Input [Mbh]
о Known Air Infi ltration Rate. See Table 3 for
space with boiler only. Use equation for multiple
appliances. Do not use an air infi ltration rate
(ACH) greater than 0.60.
Volume ≥ 15 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
• All Outdoor Air. Provide permanent opening(s)
communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second
opening commencing within 12 inches of bottom
enclosure.
Direct communication with outdoors or
communicating through vertical ducts. Provide
minimum free area of 1 in
2
per 4 Mbh of total
input rating of all appliances in enclosure.
Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2
Mbh of total input rating of all appliances in
enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure.
Provide minimum clearance of 1 inch on sides
and back and 6 inches on front of boiler (does not
supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements
for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for application information.
• Section 8.2 and 8.3 when combination of appliances
has a total input of up to and including 400 Mbh (120
kW).
о Does not have draft control device.
• Section 8.4 when combination of appliances has total
input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code
for specifi c air supply requirements for enclosure
or structure where boiler is installed, including air
supply openings and ducts.
Table 3- Air Infi ltration Rate
Input Mbh
Standard
Method
Known Air Infi ltration Rate Method (Air Changes Per Hour)
0.10.20.30.40.50.6
42.52125637531882125159412751063
7537501125056253750281322501875
112.556251687584385625421933752813
150750022500112507500562545003750
187.5937528125140639375703156254688
22511250337501687511250843867505625
6
INSTALLATION SYSTEM PIPING
!
WARNING
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns,
scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:
• connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum
distance from fl oor or allowable safe point of discharge.
• be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge
line;
• have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or
place any obstruction in discharge line.
• terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;
• allow complete drainage of the valve and the discharge line;
• be independently supported and securely anchored to avoid applied stress on the relief valve;
• be as short and straight as possible;
• terminate with plain end (not threaded);
• be constructed of material suitable for exposure to temperatures of 375° F; or greater.
Refer to local codes and appropriate ANSI/ASME Boiler and Pressure Vessel Code, Section IV, or Boiler,
Pressure Vessel and Pressure Piping Code, CSA B51 for additional installation requirements.
1.
Refer to local codes and appropriate ASME Boiler
and Pressure Vessel Code for additional installation
requirements.
2.
Install relief valve on 3/4” pipe nipple in tapped boiler
opening.
A. Pipe discharge line following guidelines in preceding
Warning. See Figure 2.
B. Discharge line pipe size shall be equal or greater
than that of relief valve outlet over entire length
of discharge line with no intervening shutoff valve
between safety relief valve and discharge to
atmosphere.
C. Discharge line shall terminate with plain end to
atmosphere where any discharge will be clearly
visible and is at no risk of freezing.
D. Discharge line shall be independently supported to
avoid applied stress on relief valve.
E. Installation shall allow complete drainage of relief
valve and discharge line.
3.
Install Drain Valve on lower left side of boiler as
marked.
4.
Install Temperature and Pressure Gauge into ¼”
bushing threaded in tee furnished with supply piping.
See
Figures 3 and 4
5.
Connect Supply and Return Lines to boiler. Figure 3 &
4. Connections may require certain additional fi ttings
and parts.
.
Figure 2 - Safety Relief Valve Discharge Piping
RELIEF VALVE
DISCHARGE
PIPING
Check local codes
for maximum
distance from
fl oor or other
allowable safe
point of discharge
7
INSTALLATION SYSTEM PIPING
Figure 3 -
Forced Hot Water Typical Piping
Figure 4 - Forced Hot Water Typical Piping
With Zone Control Valve
8
INSTALLATION SYSTEM PIPING
• Install radiation units (panels, radiators or cabinets) and
supply and return mains fi rst then make connections at
boiler.
• Verify clean water supply is available when connecting
cold water supply to water valve. Install sand strainer at
pump when water supply is from well or pump.
• Provide low water cutoff device when boiler is installed
above radiation level or as required by the Authority
having jurisdiction, either provide as part of boiler
or at time of boiler installation. Periodic inspection
is necessary, as is fl ushing of fl oat type devices, per
manufacturers specifi c instructions.
• Boiler used in connection with refrigeration systems shall
be installed so chilled medium is piped in parallel with
heating boiler with appropriate valves to prevent chilled
medium from entering heating boiler. See
• Boiler connected to heating coils located in air handling
units exposed to refrigerated air circulation, piping
system shall be equipped with fl ow control valves or
other automatic means to prevent gravity circulation of
boiler water during cooling cycle.
Figure 5
.
Low Design Water Temperature Systems (Below
140°F) And Large Water Content Systems
Condensation is corrosive and can eventually cause severe
damage to boiler and venting system.
• Minimum design return water temperature to prevent
• Boiler used in heating systems where design water
• Boiler connected to system having large water content
condensation in boiler and venting is 120°F. Minimum
high limit setting is 140°F.
temperatures below 140°F are desired (e.g. radiant fl oor
heating), a 3-way or 4-way mixing valve or suitable
alternative is required to prevent low temperature return
water from entering boiler. When using mixing valve,
follow manufacturer’s installation instructions.
(such as former gravity system), suggest use of bypass
piping. See
Figure 6
.
Figure 5
- Piping Arrangements For Boiler When
Used In Connection With Refrigeration
System
Figure 6
- Bypass Piping
9
VENT INSTALLATION
Check Your Chimney
Chimney must be clean, right size, properly constructed
and in GOOD CONDITION.
1.
Installation must conform to requirements of the
authority having jurisdiction or, in absence of such
requirements, to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or of the Natural Gas and Propane
Installation Code, CAN/CSA B149.1, or applicable
provisions of the local building codes..
2.
Boiler’s induced draft blower has 3” outlet. 3” X
4” increaser fi tting is included in parts bag. Locate
increaser fi tting on outlet of induced draft blower, and
secure gas-tight with bead of furnished silicone sealant.
Increaser fi tting is required on this boiler for Category I
venting, and 4” is minimum permissible vent diameter.
This does not imply vent connector is intended to be 4”
diameter pipe. Vent connector shall be sized according
to appropriate venting tables in the National Fuel
Gas Code and may be required to be larger than 4”
diameter.
NOTICE
Boiler installation for chimney venting is not complete
unless increaser fi tting is located and secured.
3.
These are high effi ciency boilers with low stack or
exhaust temperature.
4.
Venting into masonry chimney without liner, line
chimney from top to bottom with either:
A. Listed Type B vent pipe
B. Listed fl exible vent liner
C. Poured ceramic liner.
11.
Fasten sections of vent pipe with sheet metal screws to
make piping rigid. Use stovepipe wires to support pipe
from above.
12.
Do not connect to fi replace fl ue.
13.
Do not install damper on this boiler.
Minimum Vent Pipe Clearance
• Use Type B vent pipe through crawl space. Where vent
pipe passes through combustible wall or partition, use
ventilated metal thimble. Thimble should be 4 inches
larger in diameter than vent pipe.
• Boiler installed with single wall vent, must have 6”
clearance between its surface and any combustible
material. New Type B gas vent or fl exible liner must be
installed in accordance with instructions furnished with
vent. Maintain clearances as specifi ed for vent pipe.
• Verify vent pipe is fi re-stopped where it goes through fl oor or ceiling. It should have approved vent cap with
clearances from roof. If clearances are less than shown
in have vent checked by local authorities. See Figure 7,
Page 11.
• Vent connectors serving appliances vented by natural
draft shall not be connected into any portion of
mechanical draft systems operating under positive
pressure.
5.
Outside chimneys should not be used unless they are
(choose one of the following):
A. Enclosed in a chase
B. Lined with Type B vent pipe
C. Use listed fl exible vent liner
D. Use certifi ed chimney lining system
6.
Vent connector from boiler to chimney should run as
directly as possible with as few elbows as possible.
7.
Where possible, it is recommended to common vent
water heater and boiler. Consult appropriate Vent
Sizing Tables in National Fuel Gas Code for specifi c
requirements of multiple appliance venting.
8.
Boiler is only appliance connected to vent, Type B vent
pipe is recommended for vent connector.
9.
Slope pipe up from boiler to chimney not less than 1/4”
per foot (21mm/m).
10.
End of vent pipe must be fl ush with inside face of
chimney fl ue. Use sealed-in thimble for chimney
connection.
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.