These Gas-Fired Water Boilers are low
pressure, sectional cast iron boilers Design
Certified by CSA (Canadian Standards
Association) for use with Natural and
Propane Gases. They are constructed
and hydrostatically tested for a maximum
working pressure of 50 psi (pounds per
square inch) in accordance with A.S.M.E.
(American Society of Mechanical Engineers)
Boiler and Pressure Vessel Code Section IV:
Rules for Construction of Heating Boilers.
WARNING
Improper installation, adjustment,
alteration, service, or maintenance can
cause injury or property damage. Refer
to this manual. For assistance or additional
information consult a qualifi ed installer,
service agency, or the gas supplier.
Checking and Adjusting ................................................................................................. 25
Cleaning Your Boiler ...................................................................................................... 27
Maintaining Your Boiler .................................................................................................. 28
Service Hints ............................................................................................................... 30
Repair Parts ................................................................................................................. 31
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
GSB8-E
GAS-FIRED STEAM BOILER
GSB8-S
GAS-FIRED STEAM BOILER
H
2
SAFETY SYMBOLS
The following defi ned symbols are used throughout this
manual to notify the reader of potential hazards of varying
risk levels.
DANGER
!
Indicates a hazardous situation which, if
not avoided, WILL result in death or serious
injury.
WARNING
!
Indicates a hazardous situation which, if
not avoided, could result in death or serious
injury.
CAUTION
!
Indicates a hazardous situation which, if not
avoided, may result in minor or moderate
injury.
READ ALL INSTRUCTIONS BEFORE INSTALLING.
WARNING
Keep boiler area clear and free from
combustible materials, gasoline and other
fl ammable vapors and liquids.
DO NOT obstruct air openings to the boiler
room.
Modifi cation, substitution or elimination
!
of factory equipped, supplied or specifi ed
components may result in property damage,
personal injury or the loss of life.
To owner: Installation and service of this
boiler must be performed by qualifi ed installer.
When this product is installed in the
Commonwealth of Massachusetts the
installation must be performed by a Licensed
Plumber or Licensed Gas Fitter.
NOTICE
Indicates information which should be
followed to ensure proper installation and
operation.
To installer: Leave all instructions with boiler for
future reference.
WARNING
All installations of boilers and venting should
be done only by a qualifi ed expert and in
accordance with the appropriate Installation,
Operation and Maintenance manual.
!
Installing or venting a boiler or any other gas
appliance with improper methods or materials
may result in serious injury or death due to
fi re or to asphyxiation from poisonous gases
such as carbon monoxide which is odorless
and invisible.
Installation shall conform to requirements of
authority having jurisdiction or in absence of
such requirements:
United States
•
National Fuel Gas Code, ANSI Z223.1/NFPA 54•
National Electrical Code, NFPA 70.•
Canada •
Natural Gas and Propane Installation Code, •
CAN/CSA B149.1.
.
Canadian Electrical Code, Part I, Safety Standard •
for Electrical Installations, CSA C22.1
3
Figure 1 - Dimensions
BOILER RATINGS AND CAPACITIES
BOILER SPECIFICATIONS
Natural gasPropane
Model No.
Type of Ignition
Input *MBH (KW)
GSB8-075EElectronic
GSB8-075SStanding Pilot81.1
GSB8-112EElectronic
GSB8-112SStanding Pilot78.8
GSB8-150EElectronic
GSB8-150SStanding Pilot79.2
GSB8187EElectronic
GSB8187SStanding Pilot79.6
GSB8-225EElectronic
GSB8-225SStanding Pilot80.1
GSB8-262EElectronic
GSB8-262SStanding Pilot80.5
GSB8-299EElectronic
GSB8-299SStanding Pilot80.9
75,000
(22.0)
112,500
(33.0)
105,000
(44.0)
187,000
(54.8)
225,000
(65.9)
262,000
(76.9)
299,000
(87.6)
*MBH (KW)
Heating Capacity
62,000
(18.5)
91,000
(26.7)
122,000
(35.7)
153,000
(44.8)
183,000
(53.6)
214,000
(62.7)
245,000
(71.8)
(KW)
Net I=B=R *MBH
47,000
(14.7)
68,000
(19.9)
92,000
(27.0)
115,000
(33.7)
137,000
(40.1)
161,000
(47.2)
184,000
(53.9)
sq.ft. Radiation
Net I=B=R Rating
196
(18.2)
283
(26.3)
383
(35.6)
479
(44.5)
571
(53.0)
671
(62.3)
767
(71.3)
Input *MBH (KW)
70,000
(20.0)
105,000
(30.8)
140,000
(41.0)
175,000
(51.3)
210,000
(61.5)
245,000
(71.8)
280,000
(82.0)
Heating Capacity
58,000
(16.1)
85,000
(24.9)
114,000
(33.4)
143,000
(41.9)
171,000
(50.1)
200,000
(58.6)
229,000
(67.1)
Net I=B=R
*MBH (KW)
*MBH(KW)
44,000
(13.0)
64,000
(18.6)
86,000
(25.2)
107,000
(31.4)
128,000
(37.5)
150,000
(44.0)
172,000
(50.4)
(17.0)
(24.8)
(33.3)
(41.4)
(51.4)
(58.1)
(66.7)
sq.ft. Radiation
Net I=B=R Rating
82.7
183
80.4
267
80.6
358
80.9
446
81.1
553
81.3
625
81.5
717
AFUE %
Number of Sections
3
4
5
6
7
8
9
round
Diameter in. (mm)
Flue Size Connection
5
(12.7)
(15.2)
(15.2)
(17.8)
(17.8)
325
(147)
6
404
(183)
6
483
(219)
7
564
(256)
649
(294)
719
7
(326)
800
(363)
(kg) Package
Sipping Weight Lbs.
tion NPT in. (mm)
Supply & Return Connec-
2-1/2
(64.0)
in. (mm)
Drain Connection NPT
3/4
(19.0)
* MBH = 1,000 Btuh. Btuh = British Thermal Unit Per Hour.
** Add 5½" to height for Vent Damper
† For altitudes above 2,000 ft. reduce input rate 4% for each 1,000 ft. above sea level.
Heating Capacity is based on DOE (Department of Energy) test procedure.
(1) Add model number suffi x 'P' for Propane Gas.
4
BEFORE YOU START
Net I=B=R steam Ratings shown are based on piping and
pickup allowance of 1.333.
Base selection of boiler size on "Net I=B=R Rating"
being equal to or greater than installed radiation in
square feet. Consult manufacturer before selecting a
boiler for installations having unusual piping and pickup
requirements,such as intermittent system operation,
exhaust piping systems, etc.
Specifi cations and dimensions are subject to change
without notice.
For elevations above 2000 ft. (600m):
USA - Reduce input rate 4% for each 1,000 ft (300m) •
above sea level.
Canada - Boiler certifi ed for altitudes of 0-2000 ft •
(610m) above sea level. Reduce input rate 10% for
altitudes 2000-4500 ft (610-1350) above sea level.
Contact Provincial authority having jurisdiction for
installations above 4500 feet (1350 m) above sea level.
Verify you have right size boiler before starting installation.
See rating and capacity table on previous page. Verify boiler
is for type of gas you are using. Check rating plate on right
side of boiler.
Verify boiler is supplied with correct type of gas, fresh air for
combustion, and suitable electrical supply. Also, boiler must
be connected to suitable venting system and adequate piping
system. Finally, thermostat, properly located, is needed
for control of heating system. If you have any doubts as to
various requirements, check with local authorities and obtain
professional help where needed. Take time to complete all
steps for SAFE and PROPER operation of heating system.
If this boiler is installed in building under construction, special
care must be taken to insure clean combustion air supply
during construction process. Airborne particulates such as
from drywall dust and from fi berglass insulation can clog
burner ports and cause incomplete combustion and sooting.
Boilers are designed for use in closed heating systems
where all steam is returned to boiler as condensate and
amount of make-up water required is minimal. Boilers are
not designed for or intended for use in open systems of
process applications using 100% make-up water. Damage
to boiler resulting from such use shall not be covered
under warranty.
Installation shall conform to requirements of authority having
jurisdiction or in absence of such requirements:
Where required by authority having jurisdiction, installation
shall conform to Standard for Controls and Safety Devices
for Automatically Fired Boilers, ANSI/ASME CSD-1.
Following steps are all necessary for proper installation and
safe operation of your boiler.
1. LOCATING THE BOILER 5. GAS SUPPLY PIPING
2. FRESH AIR FOR COMBUSTION 6. ELECTRICAL WIRING
3. INSTALLATION - SYSTEM PIPING 7. CHECKING & ADJUSTING
4. CHIMNEY & VENT PIPE CONNECTION
LOCATING THE BOILER
Select level location as centralized with piping system,
1.
and as near chimney as possible.
Place crated boiler at selected location, remove crate
2.
by pulling crate sides from top and bottom boards.
Combustible fl oors: When boiler is to be installed on
combustible fl oor, Special Base Plate must be used -
146-14-031 (2-6 Section) or 146-14-032 (7-9 Section).
This boiler must not be installed on carpeting.
Boiler is to be level. Metal shims may be used under
3.
base legs for fi nal leveling.
Equipment shall be installed in location in which
4.
facilities for ventilation permit satisfactory combustion
of gas, proper venting, and maintenance of ambient
temperature at safe limits under normal conditions of
use. Equipment shall be located so as not to interfere
with proper circulation of air. When normal infi ltration
does not provide necessary air, outside air shall be
introduced (See Page 6 - “Fresh Air for Combustion”).
Advise owner to keep air passages free of obstructions.
5.
Ventilating and combustion air must enter boiler room
without restrictions.
6.
5
United States •
National Fuel Gas Code, ANSI Z223.1/NFPA 54. •
National Electrical Code, NFPA 70.•
Canada •
Natural Gas and Propane Installation Code, •
CAN/CSA B149.1.
Canadian Electrical Code, Part I, Safety Standard for •
Electrical Installations, CSA C22.1
Install boiler such that automatic gas ignition system
components are protected from water (dripping,
spraying, rain, etc.) during appliance operation and
service (condensate trap, control replacement, etc.).
Table - 1 Minimum Clearance
Dimensions
Top6" (16 cm)
Rear6" (16 cm)
Control Side7" (18 cm)
Opposite Side6" (16 cm)
FrontAlcove
Flue/Vent Connector6" (16 cm)
Near Boiler Piping1" (2.5 cm)
Unit must be set on concrete or other
non-combustible material base or
fl oor.
FRESH AIR FOR COMBUSTION
WARNING
!
Air openings to combustion area must not
be obstructed. Following instructions below,
adequate combustion air can be maintained.
Provide combustion air and ventilation air in accordance
with the section “Air for Combustion and Ventilation,” of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation
Code, CAN/CSA B149.1, or applicable provisions of local
building codes.
Provide make-up air where exhaust fans, clothes dryers,
and kitchen ventilation equipment interfere with proper
operation.
National Fuel Gas Code recognizes several methods
of obtaining adequate ventilation and combustion air.
Requirements of the authority having jurisdiction may
override these methods.
Engineered Installations. Must be approved by •
authority having jurisdiction.
Mechanical Air Supply. Provide minimum of 0.35 •
cfm per Mbh for all appliances located within space.
Additional requirements where exhaust fans installed.
Interlock each appliance to mechanical air supply
system to prevent main burner operation when
mechanical air supply system not operating.
All Indoor Air. Calculate minimum volume for all •
appliances in space. Use a different method if
minimum volume not available.
Standard Method. Cannot be used if known air A.
infi ltration rate is 0.40 air changes per hour. See
Table 1 for space with natural gas boiler only. Use
equation for multiple appliances and/or propane.
Volume ≥ 50 ft
Known Air Infi ltration Rate. See Table 1 for B.
space with boiler only. Use equation for multiple
appliances. Do not use an air infi ltration rate
(ACH) greater than 0.60.
Volume ≥
Refer to National Fuel Gas Code for opening C.
requirements between connected indoor spaces.
All Outdoor Air. Provide permanent opening(s) •
communicating directly or by ducts with outdoors.
Two Permanent Opening Method. Provide opening A.
commencing within 12 inches of top and second
opening commencing within 12 inches of bottom of
enclosure.
Direct communication with outdoors or
communicating through vertical ducts. Provide
minimum free area of 1 in² per 4 Mbh of total
input rating of all appliances in enclosure.
Communicating through horizontal ducts.
Provide minimum free area of 1 in² per 2
Mbh of total input rating of all appliances in
enclosure.
One Permanent Opening Method. Provide opening B.
commencing within 12 inches of top of enclosure.
Provide minimum clearance of 1 inch on sides/back
and 6 inches on front of boiler (does not supersede
clearance to combustible materials).
Refer to National Fuel Gas Code for additional C.
requirements for louvers, grilles, screens and air
ducts.
Combination Indoor and Outdoor Air. Refer to National •
Fuel Gas Code for application information.
3
x Total Input [Mbh]
21 ft3⁄ACH x Total Input [Mbh]
Table 3 - Minimum Room Volume, Indoor Air Only*
Input Mbh
Standard
Method
0.10.20.30.40.50.6
Known Air Infi ltration Rate Method (Air Changes Per Hour)
* Table values based on boiler only. Add volume for any additional appliances.
6
INSTALLATION - SYSTEM PIPING
WARNING
Burn and scald hazard. Safety valve could
!
discharge steam or hot water during
operation. Install discharge piping per these
instructions
Near boiler piping, that is the piping around boiler, must be
considered as part of boiler for proper water level control,
and to produce dry steam. Correct near boiler piping is
crucial to the proper operation of the boiler and the heating
system. Follow these recommendations carefully.
Place boiler in selected location, as near chimney as
1.
possible.
Install safety valve, using furnished 3/4” coupling, into
2.
3/4” pipe nipple on top of boiler.
Install safety valve with spindle in vertical position.•
Do no install shutoff valve between boiler and safety •
valve.
Install discharge piping from safety valve. See Figure •
2.
Use 3/4" or larger pipe.•
3.
Use pipe suitable for temperatures of 375°F (191°C) •
or greater.
Individual boiler discharge piping shall be •
independent of other discharge piping.
Size and arrange discharge piping to avoid reducing •
safety valve relieving capacity below minimum relief
valve capacity stated on rating plate.
Run pipe as short and straight as possible to location •
protecting user from scalding and properly drain
piping.
Install union, if used, close to safety valve outlet.•
Install elbow(s), if used, close to safety valve outlet •
and downstream of union (if used).
Terminate pipe with plain end (not threaded).•
This boiler is equipped with two 2-1/2” supply
connections and two 2-1/2” return connections, one
each on both the left and right sides of the boiler.
Unused connections must be plugged with the 2-1/2”
plugs (furnished).
Figure 2 - Recommended Near Boiler Piping Using One Supply Tapping
7
INSTALLATION - SYSTEM PIPING
Recommended near boiler piping for gravity return
4.
systems is shown in Figure 5. This confi guration uses
one supply and one return tapping. This setup can be
used on any size boiler in this series. The supply and
return connections may be piped both into the same
side (either left or right) or one into each side of the
boiler.
5.
For installers choosing to use both supply tappings,
Figure 6A shows the correct way to pipe this system.
Figure 6B shows the wrong way to pipe a header with
two risers.
Headers must be fi tted with header offsets or swing •
joints, or be equipped with expansion joints, so that
thermal expansion and contraction of the header will
not damage the boiler. Headers shall not be welded.
System takeoffs from the header must be between •
the equalizer and the riser to the header nearest the
equalizer. System takeoffs must never be between
two risers.
Figure 3A - Recommended Near Boiler Piping Using One Supply Tapping
System takeoffs from the header must never be bull-
6.
headed. If the steam main goes in two directions, there
must be two takeoffs from
main.
All boilers in gravity return systems
7.
with a Hartford Loop as shown in Figures 2 and 3A.
When piping the vertical risers from the boiler to the
8.
header, the bottom of the header must be a minimum
of 24 inches above the water level line on the right side
of the boiler.
Steam riser(s) and header shall be 2-1/2” pipe size.
9.
Equalizer line shall be minimum 1-1/2” pipe size.
10.
The near boiler piping shall include a 2-1/2” tee with a
11.
plug located on the supply line as shown for skimming
(i.e. surface blowdown).
The near boiler piping shall include a 1-1/2 ball valve
12.
in the return piping as shown for bottom blowdown and
draining.
the header, one for each
must be equipped
8
INSTALLATION - SYSTEM PIPING
For gravity return systems, the bottom of the lowest
13.
steam carrying pipe, be it a dry return, or the end of the
steam main, must be at least 28” above the normal water
level line on the right side of the boiler. This is known as
“Dimension A.”
For pumped return systems, follow the condensate
14.
pump or boiler feed pump manufacturer’s instructions
for proper installation and hookup.
In connecting the cold water supply to the water inlet
15.
valve, make sure that a clean water supply is available.
When the water supply is from a well or pump, a sand
strainer should be installed at the pump.
FOR USE WITH COOLING UNITS
The boiler, when used in connection with a A.
refrigeration system, must be installed so the chilled
medium is piped in parallel with the boiler with
appropriate valves to prevent the chilled medium
from entering the boiler. See Figure 4.
Figure 3B - Common Near Boiler Piping Mistakes
Figure 4 - Chilled Water Piping
VALVES A & B OPEN FOR HEATING; CLOSE FOR COOLING
VALVES C & D CLOSE FOR HEATING; OPEN FOR COOLING
9
CHIMNEY AND VENT PIPE CONNECTION
For boilers for connection to gas vents or chimneys, vent
installations shall be in accordance with National Fuel
Gas Code, ANSI Z223.1/NFPA 54, or "Venting Systems
and Air Supply for Appliances," of the Natural Gas and
Propane Installation Code, CAN/CSA B149.1, or applicable
provisions of the local building codes.
CHECK YOUR CHIMNEY
This is a very important part of your heating system. It
must be clean, the right size, properly constructed and in
GOOD CONDITION. No boiler can function properly with
a bad chimney. Inspect the chimney and verify that the
construction and size of the chimney meets all applicable
provisions of the National Fuel Gas Code and local building
codes. Figure 4 gives you an idea how a boiler might be
vented to a chimney. Note that the height (HT) is measured
from the vent pipe to the top.
CONNECTING THE VENT DAMPER AND VENT
CONNECTOR
Refer to Fig. 1 and Table 1 for the size and location of the
vent (fl ue opening). Use a 28 gauge (minimum) galvanized
pipe to connect to the chimney.
IMPORTANT - The damper blade on the furnished vent
damper has a 1/2 square inch hole (approximately 3/4”
diameter). On boilers equipped with standing pilot, the hole
must be left open. On boilers equipped with intermittent
ignition, the hole should be plugged by using the plug
supplied with the vent damper.
1.
Position furnished vent damper on top of fl ue outlet
collar. Fasten damper securely to fl ue outlet collar
with sheet metal screws. Make sure damper blade has
clearance to operate inside of diverter. Do not modify
draft diverter or vent damper
As An Option
The damper may be installed in any horizontal or
vertical position, closer to the fl ue outlet collar
preferred. Follow the diagrams - Figures 6, 7 and 8.
Install the vent damper to service only the single boiler
2.
for which it is intended. The damper position indicator
shall be in a visible location following installation.
Locate the damper so that it is accessible for servicing.
The damper must be in the open position when
3.
appliance main burners are operating.
The boiler is equipped with a factory wired harness
4.
that plugs into the vent damper. The thermostat
must be connected to the black wires marked 24 volt
thermostat on the boiler.
Vent pipe must be same size as the fl ue outlet collar.
5.
Slope pipe up from boiler to chimney not less than 1/4”
6.
per foot.
Run pipe as directly as possible with as few elbows as
7.
possible.
Do not connect to fi replace fl ue.
8.
9.
10.
The sections of vent pipe should be fastened with sheet
metal screws to make the piping rigid. Horizontal portions
of the vent system must be supported to prevent sagging.
Use stovepipe wires every 5’ to support the pipe from above.
If the vent pipe must go through a crawl space, double wall
vent pipe should be used. Where vent pipe passes through a
combustible wall or partition, use a ventilated metal thimble.
The thimble should be 4 inches larger in diameter than the
vent pipe.
MINIMUM VENT PIPE CLEARANCE
Wood and other combustible materials must not be closer
than 6” from any surface of single wall metal vent pipe.
Listed Type B vent pipe or other listed venting systems shall
be installed in accordance with their listing.
REMOVING EXISTING BOILER FROM COMMON
VENTING SYSTEM
When an existing boiler is removed from a common venting
system, the common venting system is likely to be too large
for proper venting of the appliances remaining connected to
it.
At the time of removal of an existing boiler, the following steps
shall be followed with each appliance remaining connected
to the common venting system placed in operation, while
the other appliances remaining connected to the common
venting system are not in operation.
1.
2.
3.
4.
5.
10
End of vent pipe must be fl ush with inside face of
chimney fl ue. Use a sealed-in thimble for the chimney
connection.
Horizontal run should not be longer than 3/4 the
chimney height (HT) (Fig.5).
Seal any unused openings in the common venting
system.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other defi ciencies
which could cause an unsafe condition.
Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. Close fi replace dampers.
Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the fl ame of
a match or candle, or smoke from a cigarette, cigar or
pipe.
CHIMNEY AND VENT PIPE CONNECTION
6.
After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fi replace dampers and
any other gas-burning appliance to their previous
conditions of use.
7.
Any improper operation of the common venting system
should be corrected so the installation conforms with
the National Fuel gas Code, ANSI Z223.1/NFPA 54,
and/or the Natural Gas and Propane Installation Code,
CAN/CSA B149.1. When re-sizing any portion of the
common venting system, the common venting system
should be re-sized to approach the minimum size
determined using the appropriate tables in Chapter 13
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
and/or the Natural Gas and Propane Installation Code,
CAN/CSA B149.1.
Vent connectors serving appliances vented by natural
draft shall not be connected into any portion of mechanical
draft systems operating under positive pressure.
Figure 5 - Typical Masonry Chimney Requirements
Figure 6 - Horizontal Installation
VENT DAMPER OPERATION
Figure 7 - Alternate Vent Damper Installation
TYPICAL INSTALLATION FOR VENT DAMPER
NOTE CAUTION AND FOOTNOTES
Install the vent damper to service only the single
1.
appliance for which it is intended. If improperly
installed, a hazardous condition, such as an explosion
or carbon monoxide poisoning, could result.
Do not install the vent damper on vent pipe curve.
2.
Do not run wires near high temperature surfaces.
3.
Use stand-off brackets if necessary.
11
VENT DAMPER OPERATION
For safe, effi cient operation, the vent damper and all
fl ue product carrying areas of the appliance must be
checked annually by you, with particular attention
given to deterioration from corrosion or other
sources. If you see corrosion or other deterioration,
contact your heating contractor for repairs. Check
vent damper operation as follows:
When the boiler is off, check that the vent damper
1.
positions indicator points to the closed position, Fig.
8.
Turn the thermostat or controller up to call for heat
2.
and check the vent damper indicator points to the open
position, Fig. 8.
Turn the thermostat or controller down again and check
3.
that the damper position indicator returns to the closed
position.
If you have central air conditioning, set the thermostat
4.
to COOL and turn it down to call for cooling. Cooling
system should operate.
Return thermostat to desired position.
5.
The vent damper must be inspected at least
once a year by a trained, experienced service
technician. The name of the person who
originally installed your vent damper is shown
on the installation label.
DO NOT turn damper open manually or motor
damage will result. Set switch to “AUTOMATIC
OPERATION” to close vent damper during burner off
cycle.
For further information, and for a vent damper
troubleshooting guide, refer to the manual that was
packaged with the vent damper.
Figure 8 - Vent Damper Position Indicator
MANUAL OPERATION OF THE VENT DAMPER
The vent damper may be placed in the open position
to permit burner operation by using the “HOLD
DAMPER OPEN” switch, located on the damper
controller. The thermostat will control the burner
fi ring as before, while the damper will remain open.
GAS SUPPLY PIPING
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.•
Do not touch any electrical switch; do not use •
!
General
Use piping materials and joining methods acceptable •
to authority having jurisdiction. In absence of such
requirements:
any phone in your building.
Immediately call your gas supplier from a •
neighbor’s phone. Follow gas supplier’s
instructions.
If you cannot reach your gas supplier, call the •
fi re department.
USA - National Fuel Gas Code, ANSI Z223.1/NFPA •
54
Canada - Natural Gas and Propane Installation Code, •
CAN/CSA B149.1
Install fi eld sourced manual main shutoff valve and
•
ground joint union.
Size and install gas piping system to provide
•
suffi cient gas supply to meet maximum input at not
less than minimum supply pressure. See Table 4a &
4b.
NOTICE
Use two (2) wrenches when installing pipe to
gas valve. Boiler's gas valve can be damaged
if subjected to excessive torque.
Support piping with hooks straps, bands, brackets,
•
hangers, or building structure components to prevent
or dampen excessive vibrations and prevent strain on
gas connection.
Use thread (joint) compound (pipe dope) suitable for
•
liquefi ed petroleum gas.
12
GAS SUPPLY PIPING
Provide sediment trap up stream of gas valve.
•
Propane Installation
Connections by licensed propane dealer only.
•
Use two stage regulator provided by propane
•
supplier.
Propane supplier should check piping.
•
Leak Check Gas Piping
Pressure test boiler and gas connection before placing
boiler in operation.
•
Pressure test over 1/2 psig (3.5 kPa). Disconnect
boiler and its individual gas shutoff valve from gas
supply system.
Pressure test at 1/2 psig (3.5 kPa) or less. Isolate
•
boiler from gas supply system by closing manual
gas shutoff valve.
Locate leakage using gas detector, noncorrosive
•
detection fl uid, or other leak detection method
acceptable to authority having jurisdiction. Do
not use matches, candles, open fl ames, or other
methods providing ignition source.
Figure 9 - Gas Piping At Boiler
Correct leaks immediately and retest.
•
Table - 4a Gas Pipe Sizes - Natural Gas
Length of
Pipe - Ft.
2092,000190,000350,000625,000
4063,000130,000245,000445,000
6050,000105,000195,000365,000
Table - 4b Gas Pipe Sizes - Propane Gas
Length of
Pipe - Ft.
20131,000216,000189,000393,000
4090,000145,000129,000267,000
6072,000121,000103,000217,000
* Outside diameter
Length of pipe or tubing should be measured from the gas meter
or propane second stage regulator.
Pipe Capacity - BTU Per Hour Input
Includes Fittings
1/2"3/4"1"1 -1/4"
Pipe Capacity - BTU Per Hour Input
Includes Fittings
5/8"3/4"1/2"3/4"
13
ELECTRICAL WIRING
ELECTRIC POWER SUPPLY
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to:
USA- National Electrical Code, ANSI/NFPA 70.•
Canada - Canadian Electrical Code, Part I, CSA C22.1: •
Safety Standard for Electrical Installations.
Run separate 115 volt circuit from separate overcurrent
protective device in your electrical service entrance panel.
This should be 15 ampere circuit. Locate shut-off switch
at boiler. It must be turned off during any maintenance.
Connect 115 volt electrical supply to primary leads on 24
volt transformer. Solder and tape or securely fasten these
connections with wire nuts.
Boiler, when installed, must be electrically grounded in
accordance with requirements of the authority having
jurisdiction or, in absence of such requirements, with
National Electrical Code, ANSI/NFPA No. 70 and/or
Canadian Electrical Code, Part I, CSA C22.1: Safety
Standard for Electrical Installations. Run 14 gauge or
heavier copper wire from boiler to grounded connection in
service panel or properly driven and electrically grounded
ground rod.
WARNING
!
Turn off electrical power at fuse box before
making any line voltage connections. Follow
local electrical codes.
Set heat anticipator at 0.4 amps for boilers equipped
with standing pilot, and at 0.6 amps for boilers equipped
with intermittent ignition. Connect 24 volt thermostat
leads to two wires tagged “24 volt thermostat” on boiler.
For boilers with 67D-1 fl oat type low water cut-off, two
wires are black. One wire is located on secondary of 24
volt transformer, second wire is located on pressure limit
control. For boilers with PS-802 probe type low water
cut-off, one wire is green and is located on terminal B of
PS-802, second wire is black and located on pressure limit
control.
ELECTRONIC THERMOSTATS
Certain types of electronic thermostats may lose their
memory or shut down. With 67D-1 fl oat type low water
cutoffs, this may occur each time thermostat calls for heat,
due to internal circuit in vent damper. With PS-802 probe
type low water cut off’s, this may occur each time low
water cut off detects low water condition. If this is case,
isolation relay is required for thermostat circuit. 24 volt
single pole single throw (SPST) normally open (N.O.) relay
is required, such as Honeywell R8222A or equivalent. Wire
as shown in Fig. 10A or Fig. 10B.
VENT DAMPER
Boiler is equipped with factory wired harness with 4 pin
molex plug, that plugs into 4 pin molex receptacle inside
vent damper operator.
Vent damper must be connected for boiler to operate.
Wiring diagrams follow for various different models.
INSTALL YOUR THERMOSTAT
Thermostat location has important effect on
operation of your boiler system. BE SURE TO FOLLOW
INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT.
Locate thermostat about fi ve feet above fl oor on inside
wall. It may be mounted directly on wall or on vertically
mounted outlet box. It should be sensing average room
temperature, avoid following:
DEAD SPOTS:
Behind doors
Corners and alcoves
HOT SPOTS:
Concealed pipes
Fireplace
TV sets
Radios
Lamps
Direct sunlight
Kitchens
COLD SPOTS:
Concealed pipes or ducts
Stairwells - drafts
Doors – drafts
Unheated rooms on other side of wall
CAUTION
Label all wires prior to disconnection when
!
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
14
ELECTRICAL WIRING
Figure 10A - Isolation Relay Wiring For Steam
Boilers With Float Type Low Water Cut Off And Using
An Electronic Thermostat
Figure 10B - Isolation Relay Wiring For Steam
Boilers With Probe Type Low Water Cut Off And
Using An Electronic Thermostat
15
ELECTRICAL WIRING
Figure 11 - Wiring Diagrams For Boilers With PS-802 Probe Type Low Water Cut-Off
INTERMITTENT IGNITION
If any of the original wire as supplied with this appliance must be replaced, it must be replaced with type 105°C
Thermoplastic wire or its equivalent.
16
ELECTRICAL WIRING
Figure 12 - Wiring Diagrams For Boilers With PS-802 Probe Type Low Water Cut-Off
STANDING PILOT
If any of the original wire as supplied with this appliance must be replaced, it must be replaced with type 105°C
Thermoplastic wire or its equivalent.
17
ELECTRICAL WIRING
Figure 13 - Wiring Diagrams For Boilers With 67D-1 Float Type Low Water Cut-Off
INTERMITTENT IGNITION
If any of the original wire as supplied with this appliance must be replaced, it must be replaced with type 105°C
Thermoplastic wire or its equivalent.
18
ELECTRICAL WIRING
Figure 14 - Wiring Diagrams For Boilers With 67D-1 Float Type Low Water Cut-Off
STANDING PILOT
If any of the original wire as supplied with this appliance must be replaced, it must be replaced with type 105°C
Thermoplastic wire or its equivalent.
19
CONTROLS AND ACCESSORIES
SAFETY VALVE
The safety valve should open automatically if the boiler
steam pressure exceeds the pressure rating of the valve
(15 psig). Should it ever fail to open under this condition,
shut down your boiler. If valve discharge occurs, or valve
fails to open as described above, contact an authorized
contractor or qualifi ed service technician to replace the pop
safety valve and inspect the heating system to determine
the cause, as this may indicate an equipment malfunction.
STEAM PRESSURE GAUGE
Every system should have a pressure gauge installed in the
boiler. This gauge enables you to monitor the pressure in
the system. If the safety devices fail to shut off your boiler
at the proper settings, notify your serviceman immediately.
WATER LEVEL GAUGE
The water level in the boiler can be seen through the glass
tube in the water level gauge at side of boiler. Correct
cold boiler water level is stamped on side jacket panel.
The water level should be checked regularly for the proper
level.
On the right side jacket panel of the boiler, there are
three holes for the glass water level gauge. The top hole
is common for both types of low water cut off, and is used
for the upper gauge glass fi tting. The middle hole, 9” down
from the top hole, is used for the bottom gauge glass fi tting
for the Model 67D-1 and 47-2 fl oat type low water cut off.
The lowest hole, 12
1
/4” down from the top hole, is used for
the bottom gauge glass fi tting for the Model PS-802 probe
type low water cut off. The hole that is not being used is
covered with a sheet metal knockout.
STEAM PRESSURE CONTROL
The steam pressure limit control (pressuretrol) shuts off
the gas to the main burners when the steam pressure in
the boiler reaches the cut-off setpoint (i.e. the sum of the
cut-in and the differential setpoints). Burners refi re when
the steam pressure drops to the cut-in setpoint. System
pressure requirements are based on the size and condition
of the pipes, and the load.
LOW WATER CUT-OFF
1. Model 67D-1
This is a fl oat operated switch which shuts down the gas
burner if water falls below the visible bottom of the gauge
glass.
2. Model PS-802
This is an electronic probe type LWCO. The probe is located
inside the boiler. The LWCO will shut down the burners if
the water loses contact with the probe for a period of 10
seconds.
Refer to manufacturer’s instructions (enclosed) for more
information.
WATER FEEDER (Optional)
The Model WF-2U-24 water feeder maybe used with either
of the available low water cutoffs. The water feeder’s job is
to maintain a safe minimum water level. It’s used to keep
the boiler running by compensating for minor evaporative
steam leaks, and to prevent freeze-ups if the homeowners
are away and a return line should spring a leak.
McDonnell and Miller Model 101 water feeders may be
used, however the water feed rates are too high and need
to be regulated or throttled and wiring will have to be
revised. Consult the boiler manufacturer before using these
or any other non-standard types of controls.
The automatic water feeder is a safety device, not a
convenience item. It is not designed to maintain a “normal”
water line. The water feeder does not take the place of a
responsible person monitoring and maintaining the normal
water line. Steam boilers require personal attention.
VENT DAMPER
This is an automatic, motorized stack damper that has
been developed to increase the effi ciency of heating
systems by reducing standby losses from the boiler and the
conditioned air space. The damper closes the chimney vent
when the burner is off and fully opens it when combustion
is required.
ROLLOUT SWITCH
(FLAME ROLLOUT SAFETY SHUTOFF)
The rollout switch is a temperature-sensitive fuse link
device. It is located on the boiler base just outside the
fi re box. In the event of heat exchanger fl ueway blockage
causing fl ame to roll out of the fi re box, the fuse will blow,
shutting down the fl ow of gas to the main burners. The
fuse does not change in appearance when blown.
If the rollout switch blows, it must be replaced with an
exact replacement. Check heat exchanger fl ueways for
blockage when restoring system to operating condition. Do
not operate system without a rollout switch.
20
CONTROLS AND ACCESSORIES
SPILL SWITCH
(BLOCKED VENT SAFETY SHUTOFF)
The spill switch is a manual reset disc thermostat with
a fi xed setpoint (280° F), and normally closed contacts.
It is located at the relief opening of the draft diverter. In
the event of chimney or venting system blockage causing
products of combustion to spill out of the relief opening, the
spill switch disc heats up and the spill switch contacts will
open, shutting down the fl ow of gas to the main burners by
removing power to the gas valve.
In the event that the spill switch contacts open, the reset
button on the back of the switch will pop up. The spill
switch must be reset manually, after the switch has cooled
off, by pushing the reset button down. Check the venting
system and chimney for blockage when restoring the
system to operating condition. DONOT operate the boiler
without a spill switch.
21
OPERATING INSTRUCTIONS
For Your Safety Read Before Operating
WARNING
!
If you do not follow these instructions exactly,
a fi re or explosion may result causing property
damage, personal injury or loss of life.
Some boilers are equipped with an intermittent ignition A.
device which automatically lights the pilot. Do not try
to light the pilot by hand.
Some boilers are equipped with a continuous pilot and
must be manually lighted. (See lighting instructions on
page 23.) A match holder is included in the parts bag.
BEFORE OPERATING smell all around the appliance B.
area for gas. Be sure to smell next to the fl oor because
some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.•
Do not touch any electric switch; do not use any phone •
in your building.
Use only your hand to push in or turn the gas control C.
knob. Never use tools. If the knob will not push in or
turn by hand, don’t try to repair it, call a qualifi ed ser-
vice technician. Force or attempted repair may result in
a fi re or explosion.
Do not use this appliance if any part has been under D.
water. Immediately call a qualifi ed service technician
to inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.
Immediately call your gas supplier from a neighbor’s •
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fi re •
department.
INTERMITTENT IGNITION BOILER - VR8204A/VR8304M GAS VALVE OPERATING INSTRUCTIONS
STOP! Read the safety information on this page.
1.
Set the thermostat to lowest setting.
2.
Turn off all electric power to the appliance.
3.
This appliance is equipped with an ignition device which
4.
automatically lights the pilot. Do not try to light the
pilot by hand.
Remove lower front panel.
5.
Rotate the gas control knob clockwise
6.
to“OFF”.
Wait fi ve (5) minutes to clear out any gas. Then smell
7.
for gas, including near the fl oor. If you smell gas,
STOP! Follow “B” in the safety information on this page
If you don’t smell gas, go to next step.
Rotate the gas control knob counterclockwise
8.
to “ON.”
Replace lower front panel.
9.
Turn on all electric power to the appliance.
10.
Set thermostat to desired setting.
11.
If the appliance will not operate, follow the instructions
12.
“To Turn Off Gas To Appliance” and call your service
technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
Set the thermostat to lowest setting.
1.
Turn off all electric power to the appliance if service is
2.
to be performed.
Push in gas control knob slightly and turn clockwise
3.
to “OFF” Do not force.
22
CONTINUOUS PILOT BOILER - VR8200A/VR8300A GAS VALVE OPERATING INSTRUCTIONS
Figure 15 - Lighting Pilot
Figure 16 - VR8200A /VR8300A Automatic Gas Valve
1.
2.
3.
4.
5.
6.
7.
STOP! Read the safety information on page 22.
Set the thermostat to lowest setting.
Turn off all electric power to the appliance.
Remove lower front panel.
Rotate gas control knob slightly and turn clockwise
to “OFF”
Wait fi ve (5) minutes to clear out any gas. Then smell
for gas, including near the fl oor. If you smell gas,
STOP! Follow “B” in the safety information on page 22
If you don’t smell gas, go to next step.
Find pilot - follow metal tube from gas control. The pilot
is between two burner tubes as shown in Fig. 15.
8.
9.
Figure 17 - VR8204A /VR8304A Automatic Gas Valve
10.
11.
12.
13.
TO TURN OFF GAS TO APPLIANCE
1.
2.
3.
Turn knob on gas control counterclockwise
“PILOT”
Rotate the gas control knob counterclockwise
to “PILOT” Push down and hold the red reset button
while you light pilot burner with a match.
After about one minute, release reset button. Pilot
should remain lit. If it goes out, turn gas control knob
clockwise to OFF To relight, repeat steps 5-9.
If button does not pop up when released, stop and •
immediately call your service technician or gas
supplier.
If the pilot will not stay lit after several tries, turn •
the gas control knob to “OFF” and call your service
technician or gas supplier.
After pilot remains lit when red reset button is released,
turn gas control knob counterclockwise to “ON.”
Replace lower front panel.
Turn on all electric power to the appliance.
Set thermostat to desired setting.
Set the thermostat to lowest setting.
Turn off all electric power to the appliance if service is
to be performed.
Push in gas control knob slightly and turn clockwise
to “OFF” Do not force.
to
23
OPERATING YOUR BURNER
HOW A STEAM SYSTEM OPERATES
The water in the boiler is heated until it reaches the boiling point. As the water boils it turns into steam. The steam
rises from the top of the water through the supply main to
the radiation units. As it passes through the radiators it releases its heat and condenses into water. The water returns
to the boiler through the return main. Most residential sys-
tems operate at less than 1 pound steam pressur
FILLING SYSTEM WITH WATER
On steam heating systems the boiler is partially fi lled with
water. It is very important to the proper operation of the
entire system that your boiler be fi lled to the proper level.
The correct water level is about halfway up the glass water
level gauge as marked on the boiler jacket. To fi ll:
Close the boiler drain valve.
1.
Open the valves at the top and bottom of the glass
2.
water level gauge. Also open the drain valve at the
bottom of the gauge.
Open the fi ll valve and allow water to run into the
3.
boiler.
e.
THERMOSTAT
Keep it set at a desired room temperature. If windows
are to be opened or heat is not needed, move thermostat
pointer to a lower setting.
NOTICE
In the event of failure of any component,
the system will not operate or will go into
safety lockout. The system is completely
self-checking. On every call for heat, each
component must be functioning properly
to permit operation. On safety lockout
the system has to be reset by turning the
thermostat to the lowest setting for one
minute, then back to the normal setting.
!
WARNING
Never run water Into a hot empty boiler.
Allow boiler to fi ll until water runs out the gauge drain
4.
valve. Then close the gauge drain valve.
Continue to fi ll boiler until water reaches the indicated
5.
water line. This is about halfway up the glass tube.
WATER LEVEL
The normal water level is shown on the right side of the
boiler and is 24” above the fl oor. The normal water level
is determined when the boiler is off and cold, i.e. when
all of the water in the system is inside the boiler and the
return piping below the water line, and everything above
the water line is air, no steam. When the boiler is making
steam, the water level will drop two to three inches below
the normal water line.
AUTOMATIC GAS VALVE
The Automatic Gas Valve opens or closes according to the
heat requirements of the thermostat and temperature limit
control. It closes if the pilot goes out. Each individual control must be operating correctly before any gas can pass to
the burners. Any one control can hold the gas supply from
burner regardless of the demand of any other control.
24
CHECKING AND ADJUSTING
ADJUST PILOT BURNER
Pilot fl ame should surround 3/8” to 1/2” of the pilot sensor.
Refer to Fig. 19. If fl ame needs adjusting, do it as follows:
Remove screw cover over pilot adjusting screw.
1.
Insert small screwdriver and adjust fl ame as needed.
2.
Turn screw counterclockwise to increase fl ame, clock-
wise to decrease.
Replace screw cover over pilot adjusting screw.
3.
MAIN BURNER(S)
The main burners do not require primary air adjustment
and are not equipped with primary air shutters. Main burner fl ames should form sharp blue inner cones in a softer
blue outer mantel, with no yellow. Puffs of air from blowing
on the fl ame or stamping on the fl oor will cause the fl ames
to turn orange momentarily. This is not unusual. Remain
still when observing the main burner fl ames. If the fl ame
appearance is not correct, check main burner orifi ces and
the burner throat and fl ame ports for dust and lint obstruc-
tion. It may be necessary to remove the rollout shield to
observe the main burner fl ames. Replace rollout shield after
observation. Refer to Figure 18.
Figure 18 - Main Burner
GAS VALVE SAFETY SHUTDOWN TEST
Ignition System Safety Shutoff device must be tested after
placing boiler in operation.
For boilers equipped with continuous pilot, with main
1.
burners fi ring, disconnect the thermocouple from the
gas valve. The gas valve should immediately shut off
the main burners and the pilot.
For boilers equipped with intermittent ignition, with
2.
main burners fi ring, disconnect the ignition cable from
the intermittent pilot control box. The gas valve should
shut off the main burners. TURN OFF ELECTRIC POWER
to boiler before reconnecting ignition cable, to prevent
electric shock.
ADJUST STEAM PRESSURE CONTROL
The steam pressure limit control (pressuretrol) shuts off
the gas to the main burners when the steam pressure in
the boiler reaches the cut-off setpoint (i.e. the sum of the
cut-in and the differential setpoints). Burners refi re when
the steam pressure drops to the cut-in setpoint. System
pressure requirements are based on the size and condition
of the pipes, and the load.
For good system operation, the cut-in setting of the pres-
suretrol should never be less than twice the system pressure drop. In a typical single family residence with a clean
one pipe heating system and cast iron radiation, this means
that the cut-in will usually be set at the minimum setting,
i.e. 1/2 psi.
Steam radiation is usually sized based on square feet of
equivalent direct radiation (EDR). This is based on a steam
pressure in the radiator of just less than 1 psi. Therefore, in
our example system from above, we would set the differential adjustment at 1 psi, i.e. the steam pressure required
in the radiators. This will give us a cut-off setpoint of 1-1/2
psi.
The above is an example of a typical one pipe system.
For larger systems or other types of systems such as two
pipe systems, or systems with convectors or fan coil units,
the pressuretrol settings will need to be determined on a
system-by-system basis.
The cut-in setpoint is determined by the system pressure
drop to the furthest radiator or terminal unit. Double the
system pressure drop as a safety factor, resulting in the
rule that the cut-in setting should never be less than twice
the system pressure drop.
The differential setpoint is the steam pressure required at
the terminal heating units.
Now your boiler will operate in the correct pressure range.
It will maintain enough steam pressure to send the steam
out to the furthest radiator, and not go over the optimum
steam pressure that is required at the radiators.
CHECKING CONTROLS
To check the Low Water Cut-Off, turn off power to the boiler
or turn the thermostat down to the lowest setting. Drain
water to below the visible bottom of the water gauge glass.
Turn power on and turn the thermostat to call for heat.
When the boiler is equipped with the fl oat type LWCO the
gas valve should not open on a call for heat when the water
is low. When the boiler is equipped with a probe type LWCO
the gas control should be powered for approximately 10
seconds (the time delay on the probe type LWCO), then the
gas valve will close and the red indicator will illuminate on
the LWCO.
25
CHECKING AND ADJUSTING
If your boiler is equipped with the optional WF-2U-24
water feeder, continue to keep the thermostat calling for
heat after the low water cut off recognizes the low water
condition. After a one minute time delay, the water feeder
should start feeding water to the boiler. The feeder should
feed for one minute, and then go into another one minute
waiting period. This cycle of alternately waiting and feeding
should repeat until:
1.
For Model 67D-1 fl oat type low water cutoffs
water level raises the fl oat above the burner cut off
switch level, the burners should ignite. The water
feeder remains powered until the water level raises the
fl oat to the water feeder switch level, satisfying the
water feeder.
For Model PS-802 probe type low water cutoffs
2.
water level will rise until water in the boiler makes
contact with the probe, satisfying the water feeder, and
igniting the burners.
In either case, there should be between one and two inches
of water visible in the gauge glass when both the water
feeder is satisfi ed, and the burners are allowed to ignite.
The time delays in the feed cycles are designed to prevent
the boiler from fl ooding due to slow return lines.
To check the pressure limit, run the boiler until the pressure reaches system demand. Then turn the pressure
screw and drop the pressure setting until the boiler shuts
down. This will show that the pressure limit is operating
properly.
Refer to control manufacturer’s instructions (enclosed) for
more information.
Check thermostat operation. When set above temperature
indicated on the thermometer, boiler should ignite. Make
certain the thermostat turns off the boiler when room temperature reaches the selected setting and starts the boiler
operating when room temperature falls a few degrees.
Finally, set the thermostat for the desired temperature.
Special conditions in your home and the location of the
thermostat will govern this setting.
- as the
- the
Figure 19 - Igniter
26
CLEANING YOUR BOILER
It is very important to clean a new steam boiler after it has
been installed and put into continuous operation. This must
be done to remove any accumulation of oil, grease, sludge,
etc., that may have been present in the system. These
substances may cause the boiler water to foam and surge,
thus producing a very unsteady water line, throwing water
into the steam header, and possibly preventing steam
generation. Follow these steps in order to remove these
contaminants.
SKIMMING AND SLOWDOWN
New boilers must be skimmed at the time of installation to
remove threading oil and other impurities that fl oat on the
surface of the water.
1.
Remove the plug from the skimmer tapping and pipe to
a fl oor drain or bucket.
Raise the water level to the skimmer tapping.
2.
Fire the boiler to maintain a water temperature of 180-
3.
200 degrees.
Feed water to the boiler to maintain the water level.
4.
Adjust the water feed rate to keep water continuously
fl owing out of the skimmer tapping without the water
level going above or falling below the tapping. Cycle
the burners to prevent boiling.
Continue skimming until the water runs clear. This may
5.
take several hours.
Float type low water cutoffs must be blown down after
6.
skimming. The fl oat chamber of the low water cut off
must be fl ushed clean and maintained clear of sediment
to allow free movement of the fl oat. This must be done
frequently during initial operation of the boiler, and at
least once a week thereafter. Follow the instructions on
the tag attached to the control. Probe type low water
cutoffs require no maintenance at this time.
After blowing down the low water cut off and before
7.
blowing down the boiler, fi ll the boiler to the water line.
Fire the burners and allow normal steam pressure to
build up. Run a connection from the boiler blowdown
valve to a nearby sewer or fl oor drain or to a safe
discharge point outside. Shut off the gas burners, open
the blowdown valve, and allow all of the water in the
boiler to drain out. Close the blowdown valve. Allow
the boiler to cool thoroughly, and then slowly refi ll the
boiler to the water line. Repeat this step as many times
as necessary until the blowdown water is clear.
Following the fi nal blow down, allow the boiler to thor-
8.
oughly cool, and then add fresh water slowly up to the
normal water line. Start the burners and maintain at
least 180 degrees for 15 minutes to remove dissolved
gasses from the fresh water. Shut off burners
Now, let the boiler steam for a few days, to give the majority
of the system dirt a chance to work its way back to the
boiler. Then check the water in the gauge glass. The gauge
glass should be dry above the water line. The water line
should not bounce more than one inch when the boiler is
steaming. If you see water droplets carrying over from the
top of the gauge glass, or excessive bouncing of the water
line, the boiler needs further cleaning. Take a water sample
and boil it on the stove, to see if it foams. If it does, this also
indicates the boiler needs to be cleaned.
If cleaning is necessary, repeat the skimming and blow down
procedure from above. Usually, a long skim will be all you
need to clean the boiler.
In more troublesome cases it may be desirable to fl ush the
system as well. This is accomplished by closing the gate
valve in the Hartford Loop, and opening the drain(s) at the
end of the wet return(s). Run a hose from the drain valve
on the wet return to a nearby fl oor drain or bucket. Run the
boiler at two pounds of steam pressure. Feed just enough
water to compensate for the waste condensate going down
the drain, and to keep the boiler from going off on low water
cut off. Run the boiler until all waste condensate runs clear.
In very extreme cases it may be necessary to chemically
clean and fl ush the heating system. Consult the boiler
manufacturer before introducing any chemicals into the
boiler.
NOTICE
Boiler cleaners and chemical cleaning
additives are not recommended. If used
and not rinsed properly, they will do more
harm than good. The cleaning procedures
laid out above will clean out the typical oils
and impurities found in new boilers and in
residential heating systems. The best thing for
your boiler and heating system is clean water
with no additives.
27
MAINTAINING YOUR BOILER
Keep boiler area clear and free from combustible materials,
gasoline and other fl ammable vapors and liquids. Keep
boiler are clear and free of obstructions to fl ow of
combustion and ventilation air.
Check the water level every day or two. Verify the water
line shown by operating the drain valve on the gauge. BE
SURE TOP AND BOTTOM VALVES ON GAUGE ARE ALWAYS
OPEN SO THAT ACTUAL WATER LEVEL WILL BE SHOWN AT
ALL TIMES.
The gauge glass should be dry above the water line. The
water line should not bounce more than about one inch
when the boiler is steaming. If you see water droplets
carrying over through the top of the gauge glass, or
excessive bouncing of the water line, the boiler needs to
be cleaned. Follow the instructions under “Cleaning Your
Boiler.”
SAFETY VALVE
Before testing, make certain discharge pipe is properly
connected to valve outlet and arranged to contain and
safely dispose of boiler discharge. Under normal operating
conditions a “try lever test” must be performed every
month. A “try lever test” must also be performed at the
end of any non-service period. Test at normal system
operating pressure by holding the test lever fully open
for at least fi ve seconds to fl ush the valve seat free of
sediment and debris. Then release lever and permit the
valve to snap shut. If lift lever does not activate, or there
is no evidence of discharge, turn off boiler immediately and
contact a licensed contractor or qualifi ed service personnel.
too. As fl oat drops with falling water level, burners will shut
off. After valve is closed and normal operating conditions
are restored, burners will resume fi ring. For probe type
Low Water Cutoffs, check action of the Low Water Cut-Off
monthly to make sure it is providing the proper protection.
See “Checking and Adjusting” on page 19. Low Water CutOff remote probes must be removed for periodic inspection
and cleaning, preferably at the beginning of each heating
season. More frequent cleaning may be required on boilers
requiring constant or very frequent additions of make up
water.
BURNERS
A visual check of the pilot and main burner fl ames should
be made at least once each year, preferably at the beginning of the heating season. See page 19.
BOILER FLUE PASSAGES
Under normal operating conditions, with the burners
properly adjusted, it should not be necessary to clean the
boiler fl ue gas passages. However, to assure trouble-free
operation, we recommend that you have the fl ue passages,
burner adjustment,
and operation of the controls checked once each year by a
competent Service Technician.
Before the start of each season (or whenever system has
been shut down for some time) recheck the whole system for leaks . . . and recheck the boiler and vent pipe for
leaks.
LOW WATER CUT-OFF
The Low Water Cut-Off will interrupt the electrical current
to the burner when the water line in the boiler drops to a
low level.
On fl oat type low water cutoffs, it is very important to
keep the fl oat chamber free from sediment, a condition
essential to dependability. To keep any accumulation from
interfering with fl oat action is to “BLOW DOWN” or fl ush out
the control regularly. This must be done two to three times
during the fi rst week after installation and once a week
thereafter during the heating season. Do it while the boiler
is in operation. First note water level in gauge glass. Open
blow-off valve at bottom of control; water will pour out,
fl ushing away sediment. Drain until water is clear, about a
pailful, then close valve. If water level in gauge glass has
dropped, add water to boiler to restore level. Consult low
water cut-off manufacturer’s instructions included with
boiler.
VENT PIPE
The venting of this unit is very important and the piping
should be checked at least once a season. If the vent piping shows any sign of leaking, replace it immediately.
CLEANING YOUR BOILER FLUE PASSAGES AND
BURNERS
Flue Passages between sections should be examined yearly
and cleaned, if necessary. To clean, remove burners, pilot,
and vent pipe. Remove top and front jacket panels. Remove
the two screws attaching the intermediate front panel to
the left and right side jacket panels. Remove the draft
diverter and intermediate front panel as a unit. Carefully
remove the cerafelt gasket strips. Clean passageways
between sections with a fl exible handle wire brush. Remove
dirt from bottom of boiler and from between sections by
vacuuming. Make sure all fl ame ports in burners are open
and clear. Shake out or blow out all loose dirt in burners.
Reseal seams between adjacent sections as necessary with
400F RTV silicone sealant. Reassemble all parts. Be sure to
check tightness of pilot connections and condition of burner
fl ames after reassembly (see Figures 18 and 19).
Be sure vent pipe connections to chimney are secure and
no obstructions are present.
28
MAINTAINING YOUR BOILER
FOAMING, PRIMING OR SURGING
These terms are used to describe a fl uctuating water line -
when water leaves the boiler with the steam.
It is caused by any combination of the following:
Threading oil and organic matter in the boiler water.
1.
(Mineral oil, or core sand does not cause surging.)
Follow instructions under “Cleaning Your Boiler.”
Faulty quick vents that do not release air until a
2.
sizeable pressure is built up - if old style, replace - if
dirty, clean so you can easily blow through valve.
Improper header design - when steam fl ows in opposite
3.
direction of equalizer line on “Hartford Loop.” Generally
a 15” horizontal run between riser and main takeoff
will allow entrained water to fall out of the steam vapor
so it can return to boiler. (See Figures 2, 3A & 3B on
pages 7 and 8).
Adjustment of steam limit control to a wide differential
4.
increases diffi culty if quick vents are old style, slow-
releasing type or dirty. Always set steam limit control
differential as low as possible.
Soap and detergents in the boiler water cause extreme
5.
surging. Boiler cleaners and chemical cleaning additives
are not recommended. If used and not rinsed properly,
they will do more harm than good. The cleaning
procedures laid out in these instructions will clean out
the typical oils and impurities found in new boilers
and in residential heating systems. The best thing for
your boiler and heating system is clean water with no
additives.
BOILER WATER TREATMENT (Other Than Cleaners) In
steam systems where the system is tight, free from leaks,
and all the steam is returned to the boiler as condensate,
the amount of make up water is small. Water treatment is
generally not required.
In steam systems with less than 90% of the steam being
returned as condensate, or with very hard or corrosive
make up water, treatment may be desirable. Follow the
recommendations of your local boiler water treatment
specialist.
BETWEEN HEATING SEASONS
Boilers should not be drained between heating seasons.
Steam boilers should be entirely fi lled with water during the
summer months to exclude air.
CAUTION
!
Never refi ll a hot boiler with cold water - the
danger of thermal shock may crack a section.
29
SERVICE HINTS
You may avoid inconvenience and service calls by checking these points before you call for service.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
1. Do Not try to light any appliance.
2. Do not touch any electric switch, do not use the
phone.
3. Leave the building immediately, then call your
gas supplier.
4. If you cannot reach the gas supplier, call the fi re
department.
IF YOUR SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT . . .
Possible CauseWhat to do
Thermostat is not set correctlyReset thermostat above room temperature.
Check fl ame. If it is yellow, the burner is not getting enough air.
Burner is not operating properly
No electric power to boiler
Controls out of adjustment
Radiators not heating
Poor electrical contact
Or, if fl ame is blue and noisy and seems to lift off the burner, the burner is
getting too mush air. Contact your service technician
Check over current protection. Check to be sure electric power supply
circuit is “ON”.
Reset according to instructions.
Steam air vents not operting properly. Check fl ow control valve (if used) - may be
in closed position.
Check all control terminals and wire joints.
Rollout switch blown
Chimney fl ue is blocked
Vent damper not operating
Have your service technician check heat exchanger for blockage.
Spill switch contacts open, requiring manual reset of spill switch. Have your service
technician check and correct chimney problem.
Consult troubleshooting guide, packaged with vent damper.
IF BURNER IS NOISY . . .
Gas input amount is incorrectContact your service technician.
IF WALLS OR WINDOWS SWEAT . . .
Not enough ventilationContact your service technician
Chimney fl ue is blockedHave your service technician check and correct, if necessary
IF RADIATORS ARE NOISY . . .
Air in systemrefer to "Radiators Not Heating" above
SAFETY VALVE LEAKING . . .
Dirt on seatOpen valve manually. Allow steam to blow and clear valve seat.
HAVE YOUR SERVICE TECHNICIAN CHECK ANY PROBLEM YOU ARE UNABLE TO CORRECT.
30
REPAIR PARTS
31
REPAIR PARTS
32
REPAIR PARTS
33
REPAIR PARTS
34
DateService PerformedCompany Name & Tech InitialsCompany Address & Phone #
35
PRODUCT LITERATURE
Lennox Industries Inc.
Dallas, Texas
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.