Lennox Hearth 2-EN53-VDLPM User Manual

Page 1
INSTALLATION INSTRUCTIONS
DIRECT VENT
This appliance may be installed in an aftermarket perma­nently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
In the Commonwealth of Massachusetts:
• Installation must be performed by a licensed plumber or gas fitter. See Table of Contents for location of additional Commonwealth of Massachusetts requirements.
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PER­SONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors or liquids in the vicin­ity of this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Portland
US
A French manual is available upon request. Order Form Number 850,043CF.
Ce manuel d’installation est disponible en francais, simplement en faire la demande. Numéro de la pièce 850,043CF.
OTL Report No. 116-F-47-5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
MERIT
VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS P/N 850,043M REV. F 09/2008
MODELS
sledoMtlovilliMsledoMcinortcelE
MN03-VDLPMEN03-VDLPM MP03-VDLPM2-EN53-VDLPM
2-MN53-VDLPMEN04-VDLPM
2-MP53-VDLPMEN54-VDLPM MN04-VDLPM MP04-VDLPM MN54-VDLPM MP54-VDLPM
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d'essence ni d'autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur de gaz:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones se trouvant dans le batiment où vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service dos incendies.
L'installation et service doit être exécuté par un qualifié installeur, agence de service ou le fournisseur de gaz.
1
Page 2
TABLE OF CONTENTS
Packaging........................................ page 2
Introduction..................................... page 2
General Information......................... page 2
Location .......................................... page 4
Appliance and Vent Clearances....... page 5
Requirements for Commonwealth
of Massachusetts .......................... page 5
Vent Termination Clearances ........... page 5
Typical Installation Sequence .......... page 6
Detailed Installation Steps ............... page 6
Step 1. Framing ............................. page 6
Step 2. Routing Gas Line............... page 6
Fireplace Specifications ................... page 9
Step 3. Install the Vent System...... page 10
Vertical Termination Systems .......... page 10
Vent Section Length Chart............... page 11
Vertical Vent Tables and Figures...... page 14
Horizontal Termination System........ page 15
Horizontal Vent Tables and Figures . page 18
Venting Using Flexible Vent Pipe ..... page 21
Step 4. Field Wiring ....................... page 22
Step 5. Connecting Gas Line.......... page 23
Step 6. Installing Logs................... page 24
Step 7. Checking Unit Operation..... page 24
Step 8. Installing Glass Door ......... page 24
Step 9. Burner Adjustments........... page 25
Finishing Requirements................... page 25
Cold Climate Insulation.................... page 26
Installation Accessories................... page 26
Gas Conversion Kits.................. page 28
PACKAGING
The assembled vented gas fireplace heater is packaged with the folowing:
1 - The logs are packaged in a carton located
within the firebox.
2 - One bag of volcanic stones is located in the
bottom compartment.
3 - One envelope containing the litera-
ture package, which consists of the homeowner's manual, installation in­structions, log set supplement, warranty, gas access plate, screws (4) and gasket. The envelope is located in the bottom compartment.
4 - One vent restrictor, to be used as detailed
on page 10.
5 - One hood and one control compartment
cover and one 45 degree starter elbow are strapped to the top of the unit.
INTRODUCTION
These fireplaces are designed, tested and listed for operation and installation with, and only with,
Secure Vent™ Direct Vent System Components, Secure Flex™ Flexible Vent Components manu-
factured by Security Chimneys International and Z-Flex™ Model GA Venting Systems, listed to UL1777 and ULCS635 manufactured by Flex­master Canada Limited. These approved vent system components are labeled for identifica­tion. DO NOT use any other manufacturer's vent components with these appliances.
Millivolt appliances are designed to operate on natural or propane gas. A millivolt gas control valve with piezo ignition system pro­vides safe, efficient operation. There is no optional blower with these units.
Both millivolt and electronic versions of these appliances are listed by Omni-Test Labora­tories for installation in bedrooms and mo­bile homes.
The Installation must conform to local codes or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1/NFPA 54
, or the
Natural Gas and Propane Installa-
tion Code, CSA B149.1
The appliance, when installed, must be elec­trically grounded in accordance with local codes or, in the absence of local codes, with
National Electrical Code, ANSI/NFPA 70
the or the
Canadian Electrical Code, CSA C22.1
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
.
GENERAL INFORMATION
Note: Installation and repair should be per-
formed by a qualified service person. The appli­ance should be inspected annually by a qualified professional service technician. More frequent inspections and cleanings may be required due to excessive lint from carpeting, bedding mate­rial, etc. It is imperative that the control compart­ment, burners and circulating air passage ways of the appliance be kept clean. S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instructions d'installation et d'utilisation qui accompagnent l'appareil.
TYPICAL INSTALLATION
, .
This manual is part of a set of three support­ing this product. Refer to manuals 875,036M for Care & Operations and 750,230M for Log Placement Guide.
Please read and understand these instructions before beginning your
installation.
2
Electronic appliances are designed to operate on natural or propane gas. An electronic inter­mittent pilot ignition system provides safe, ef­ficient operation. External electrical power is recommended to operate these units. If the system operates on line voltage with 3V adapt­ers, two (2) "D" batteries can be used as a backup in case of a power outage. The elec­tronic appliance can be operated solely with two (2) "D batteries.
These appliances comply with National Safety Standards and are tested and listed by Omni­Test Laboratories (Report No. 116-F-47-5) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/ CGA-2.17-M91 in both USA and Canada, as vented gas fireplace heaters.
Figure 1
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 3
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.
These appliances are designed to operate on natural or propane gas only.
Millivolt And Electronic Models -
Millivolt and Electronic models come standard with the manually-modulated gas valve; flame appearance and heat output can be controlled at the gas valve.
Input of millivolt and electronic models is shown in the following table:
htiwsledoMcinortcelEdnAtlovilliM
evlaVsaGdetaludoM-yllaunaM
saGlarutaNsaGenaporP
DLPMV03
DLPMV53
.oNledoM
04VDLPM
54VDLPM
tupnI
etar
)H/UTB(
000,31
ot
000,01 000,91
ot
000,51 000,52
ot
005,81 000,62
ot
02000,
.oNledoM
DLPMV03
DLPMV53
04VDLPM
54VDLPM
tupnI
etar
)H/UTB(
005,11
ot
000,9
000,81
ot
000,41 005,12
ot
005,61 000,52
ot
000,91
All Models -
Maximum manifold pressure is 3.5 in. w.c. (0.87 kPa) for natural gas and 10 in. w.c. (2.49 kPa) for LP/Propane gas.
%seicneiciffE
sledoM
4P
03VDLPM 855636856646 53VDLPM 065636265636 04VDLPM 857646757656 54VDLPM 857656066646
saGlarutaeNnaporP
ydaetS
etatS
EUFA4P
ydaetS
EUFA
etatS
Note: Power venting of direct vent fireplaces may result in the reduction of efficiencies by as much as ten percent. Consider this in making any venting and heating decisions in any installation application.
Installations at Altitudes of 0 to 4500 ft.­Units are tested and approved for elevations of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.­For elevations above 4500 feet (1372 meters), install the unit according to the regulations of the local authorities having jurisdiction and, in the USA, the latest edition of the National Fuel Gas Code (ANSI Z223.1) or, in Canada, the latest edition of the CAN1-B149.1 and .2 codes.
Table 1
shows the units' gas orifice size for
the elevations indicated.
The millivolt appliances are manually controlled and feature a spark ignitor (piezo) that allows the appliance's pilot gas to be lit without the use of matches or batteries. This system provides continued service in the event of a power outage.
noitavelE
teeF
)sretem(
0054-0
)2731-0(
.taN.porP
54#
)"280.0(
14#
)"690.0(
04#
)"890.0(
ezisecifirO
16#
)"930.0(
"840.0
45#
)"550.0(
35#
)"5950.0(
ledoM
.oN
03VDLPM "070.0
53VDLPM
04VDLPM
54VDLPM
Table 1
Do not use these appliances if any part has been under water. Immediately call a qualified, pro­fessional service technician to inspect the ap­pliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas se servir de cet appareil s'il a été plongé dans l'eau, complètement ou en partie. Appeler un technicien qualifié pour inspecter l'appareil et remplacer toute partie du système de contrôle et toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an af­termarket permanently located, manufac­tured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This ap­pliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison préfabriquée (É.-U. seulement) ou mobile déjà installée à demeure si les réglements locaux le permettent. Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique. Ne pas l'utiliser avec d'autres gaz sauf si un kit de con­version certifié est installé.
Test gage connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the inlet and OUT for the manifold side). A 1/8" NPT test gage connec­tion is provided at the inlet and outlet side of the electronic gas control valve.
Minimum inlet gas pressure to these appli­ances is 5.0 inches water column (1.24 kPa) for natural gas and 11 inches water column (2.74 kPa) for propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to these appliances is 10.5 inches water column (2.61 kPa) for natural gas and 13.0 inches water column (3.23 kPa) for propane.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure testing of the gas supply piping sys­tem at test pressures equal to or less than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of 1/2 psig (3.5 kPa).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
These heater rated appliances are intended for use as supplemental heaters only. Using these appliances as a primary heat source may void the manufacturers warranty.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Turn off the gas supply to the appliance and have it serviced by a qualified professional, as it may not be op­erating correctly.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
Page 4
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING INSTRUCTIONS PROVIDED IN THIS DOCUMENT WILL RESULT IN AN IMPROP­ERLY INSTALLED AND OPERATING APPLIANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/ OR ITS OPERATING CONTROLS IS DAN­GEROUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERIOUS INJURY OR DEATH FROM FIRE, BURNS, EXPLOSION OR CARBON MON­OXIDE POISONING.
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES. USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
HORIZONTAL VENT
APPLICATION
HORIZONTAL VENT
Figure 2
APPLICATION
RECESSED
INSTALLATION
VERTICAL VENT
APPLICATION
HORIZONTAL VENT
APPLICATION
03VDLPM )2311(4/344)2311(4/344 53VDLPM )8811(4/364)8811(4/364
HORIZONTAL VENT
APPLICATION
HORIZONTAL VENT
APPLICATION
.oNledoM
54VDLPM/04VDLPM )4131(4/315)4131(4/315
HORIZONTAL VENT (Top Vent Application)
Typical Locations
tneVpoT
tneVeruceSxelFeruceS
VERTICAL VENT (Top Vent Application)
)mm(sehcnithgieHflehS
WARNING: DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIALS ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES ENFANTS. GARDER LES VÊTEMENTS, LES MEUBLES, L'ESSENCE OU AUTRES LIQUIDES À VAPEUR INFLAMMABLES À COTE DE L'APPAREIL.
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. Consideration should be given to traffic ways, furniture, draperies, etc., due to elevated surface temperatures (
The location should also be free of electrical, plumbing or other heating/air conditioning duct­ing. These direct vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace. Utility shelves like these are commonly used for locat­ing television sets and decorative plants.
Figure 2
).
Figure 3
KCAB
SEDIS
SRECAPSPOT)mm0(.ni0
ROOLF)mm0(.ni0
fomottoBmorF
gnilieCottinU
TNEV*)mm4.52(.ni1
TNORF)sretem9.0(.teeF3
Do not insulate the space between the
appliance and the
area above it.
Shelf Height
(
see table)
Shelf Above Fireplace With Top Venting
)mm4.52(.ni1
**)mm4.52(.ni1
*Note: 3 in. (76mm) above any horizontal/ inclined vent component for the MPLDV30
srecaps)mm0(.ni0
in all cases, and for the MPLDV35, MPLDV40 & MPLDV45, when the vent center line is greater than 48" (1219 mm) above the fire-
srecaps)mm0(.ni0
place top wrapper surface. Increase this clearance to 5" (127 mm) for the MPLDV35, MPLDV40 & MPLDV45, when the vent cen­ter line is less than 48" (1219 mm) above the
)mm6261(.ni46
fireplace top wrapper surface. **Note: See page 6, step 1 for clearance
requirements to the nailing flange located at
SECNARAELCECIVRES
each side of the unit and any screw heads adjacent to it.
Table 2
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 5
To provide for the lowest possible shelf surface the venting attached to the top vent should be routed in a way to minimize obstructions to the use of the space above the appliance. Do not
insulate the space between the appliance and the area above it. Refer to
Figure 3
. The
minimum height from the base of the appliance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in the table in
Figure 3
.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materi­als. However, if installed on combustible mate­rials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
APPLIANCE AND VENT CLEARANCES
Refer To Table 2 for approved clearances to combustibles for the models covered in this manual, with the following exception: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is recessed, the side walls surrounding the unit must not extend beyond the front edge of the unit. See
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical vent elements.
Clearances for horizontal vent elements are 1" (25 mm) at the sides and 1" (25 mm) on the bottom. Clearances above horizontal vent elements are 3" (76 mm) for all models and all applications.
Exception: Clearance is 5" (127 mm) for MPLDV35, MPLDV40 & MPLDV45, when the center line of the hori­zontal run is less than 48" (1219 mm) above the fireplace top wrapper surface.
Figure 2
Massachusetts And New York City, NY Requirements
These appliances are approved for installation in the following USA locations listed in the following:
Massachusetts:
These fireplaces are approved for installation in the US state of Massachusetts if the follow­ing additional requirements are met-
Installation and repair must be done by a plumber or gas fitter licensed in the Common­wealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
The individual manual shut-off must be a T­handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori­zontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must
.
comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
New York City, NY:
These fireplaces are approved for installation in New York City in the US state of New York.
VENT TERMINATION CLEARANCES
These instructions should be used as a guide­line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and ­B149.2 in Canada.
Vertical Vent Termination Clearances
Terminate single vent caps relative to building components according to
Figure 4
.
Terminate multiple vent terminations accord­ing to the installation codes listed at the top of
this page.
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
2 FT MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum Clearance to Combustibles
*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT
12
Roof Pitch is X/12
hctiPfooR
Vertical
Wall
X
H
)teef(
21/6ottalF0.1
21/7ot21/6revO52.1 21/8ot21/7revO5.1 21/9ot21/8revO0.2
21/01ot21/9revO5.2
21/11ot21/01revO52.3
21/21ot21/11revO0.4
Figure 4
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any over­head combustible projection of 2-1/2" (64 mm) or less. See ing 2-1/2" (64 mm), see terminations may be located as close as 6" (152mm) to any (non-combustible and com­bustible) exterior sidewall. This distance may be decreased to 2" (51mm) for non-combus­tible exterior sidewalls only, if the SV4.5HT-2 termination is used. For additional vent loca­tion restrictions, refer to
Figure 5.
For projections exceed-
Figure 5
. All horizontal
Figure 8 on page 7
.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
Page 6
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described.
See the page numbers references in the follow­ing steps for detailed procedures.
Step 1. (page 6) Construct the appliance fram­ing. Position the appliance within the framing and secure with nailing brackets.
Step 2. (page 6) Route gas supply line to
appliance location.
Step 3. (page 10) Install the vent system and exterior termination. Install additional restrictor, if needed.
Step 4. (page 21) Field Wiring
a. Millivolt Appliances The operating control
switch is factory installed.
b. Electronic Appliances – Connect 120 Vac electrical power to the appliance receptacle.
Step 5. (page 22) Make connection to gas supply.
Step 6. (page 23) Install the logs and glow­ing embers.
Step 7. (page 23) Checkout appliance operation.
Step 8. (page 23) Install glass door frame
assembly.
Step 9. (page 24) Adjust burner to ensure proper flame appearance.
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired. Re­move the shipping carton, exposing the front glass door. Remove the bottom panel by lifting and pulling it towards the front.
Open the two latches (located under the firebox floor) securing the glass door. Remove the door by tilting it outward at the bottom and lifting it up. Set the door aside protecting it from inadvertent damage.
See Figure 39 on page 23.
Horizontal Vent Termination Clearances
Combustible Projection
inches or less in length
2-1/2
Combustible Projection greater
than 2-1/2 inches in length
Ventilated
Soffit
Unventilated
Soffit
18"
(457 mm)
12"
(305 mm)
3"
(76 mm)
Side Elevation View
Termination Kit
Figure 5 -
Side Elevation View
Step 1. FRAMING
Frame these appliances as illustrated in
on page 8,
in a corner See
unless the appliance is to be installed
.
Figure 10 on page 8
for corner framing installations. All framing details must allow for a minimum clearance to combustible framing mem­bers as shown in
Table 2 on page 4
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed. Headers may be in direct contact with the appli­ance top spacers but must not be supported by them or notched to fit around them. All construc­tion above the appliance must be self supporting, DO NOT use the appliance for structural support.
The fireplace should be secured to the side framing members using the unit's nailing flanges - one top and bottom on each side of the fireplace front. See
Figure 6.
Use 8d nails or their equivalent. Unit Being Secured by Its Nailing
Figure 9
.
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line along the inside of the left side framing as shown in Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a flex­ible gas line connector and 1/2 inch shutoff valve. (See step 6 on page 22).
Figure 7
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible) exterior sidewall. This distance may be decreased to 2” (51mm) for non-­combustible exterior sidewalls only, if the SV4.5HT-2 termination is used.
Side
Framing
Left Side Top Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing flanges, are EXEMPT from the 1” clearance to combustible requirements for the firebox outer wrapper. Combustible framing may be in
direct contact with the nailing flanges and may be located closer than 1” from screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of this manual.
To The Framing
Termination Kit
Nailing Flanges Are Provided At All Four Corners At 5/8”, 1/2” And Flush Settings
Flanges to the Framing
Figure 6
.
Front Corner of
Fireplace Framing
2-1/4"
(57 mm)
4-3/4"
(121 mm)
Unit Nailing Flange
Left Side
(165 mm)
6-1/2"
Figure 7
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 7
V
L
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
*
See Item D in the Text Below.
Exterior Wall
*18”
Horizontal Termination
Inside Corner
B
ytreporpcilbupno
.sgnillewd
NOTE: Local Codes Or Regulations May Require Different Clearances.
of Termination
V
18”
Detail D
F
V
A
X
Center Line
Ventilated Soffit
V
Fixed
Closed
Window
V
C
= Air Supply Inlet
C
C
C
V
Inside
Corner Detail
V
A
B
Operable
V
Window
B
B
= Vent Termination
G
B
= Area where Termination is not Permitted
NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service.
= 9” in U.S.
A
= 12” in Canada
3 ft.
X
A
J
A
3 ft.
.ynoclabro,kced,hcrop,adnarev,edargevobaecnaraelC=A *)mc03(sehcni21**)mc03(sehcni21
.denepoebyamtahtroodrowodniwotecnaraelC=B secnailpparof)mc51(sehcni6
wodniwdesolcyltnenamrepotecnaraelC=C otdednemmocer)mm503(sehcni21
noitasnednocwodniwtneverp
ehtevobadetacoltiffosdetalitnevotecnaraelclacitreV=D
)mm854(sehcni81)mm854(sehcni81
)mm854(sehcni81foecnatsidlatnozirohanihtiwnoitanimret
noitanimretehtfoenilretnecehtmorf
***tiffosdetalitnevnuotecnaraelC=E )mm503(sehcni21)mm503(sehcni21
renrocedistuootecnaraelC=F muminim)mc7.21(sehcni5muminim)mc7.21(sehcni5
renrocedisniotecnaraelC=G muminim)mc2.51(sehcni6muminim)mc2.51(sehcni6
evobadednetxeenilretnecfoedisnihcaeotecnaraelC=H
ylbmessarotaluger/retem
teltuotnevrotalugerecivresotecnaraelC=I *)mc19(teef3**)mc19(teef3
rognidliubottelniylppusrialacinahcemnonotecnaraelC=J
ecnailpparehtoynaottelnirianoitsubmoceht
telniylppusrialacinahcemaotecnaraelC=K *)m38.1(teef6 teef01nihtiwfievoba)mc19(teef3
detacolyaweviddevaproklawedisdevapevobaecnaraelC=L
‡)m31.2(teef7‡)m31.2(teef7
ynoclabrokced,hcrop,adnarevrednuecnaraelC=M ‡*)mc03(sehcni21‡)mc03(sehcni21
)mumixaM(evoclAfohtpeD=N *)m38.1(teef6**)m38.1(teef6
)evoclA(noitanimreTotecnaraelC=O *)mm2.51(sehcni6**)mm2.51(sehcni6
)muminiM(evoclAfohtdiW=P *)mc19(teef3*)mc19(teef3
)evoclA(evobAelbitsubmoCotecnaraelC=Q *)mm754(sehcni81**)mm754(sehcni81
.edoCnoitallatsnIenaporPdnAsaGlanoitaN1.941B-ASCtnerrucehthtiwecnadroccanI*
.sedoCsaGleuFlanoitaN45APFN/1.322ZSISNAtnerucehthtiwecnadroccanI**
.muminim)mc67(sehcni03-lairetamtiffoslynivotderiuqerecnaraelC***
H
I
*noitallatsnInaidanaC**noitallatsnISU
)mc03(sehcni21,)Wk3(hutB000,01<
)Wk3(hutB000,01>secnailpparof
teef51fothgiehanihtiw)mc19(teef3
*ylbmessarotaluger/retemehtevoba
secnailpparof)mc51(sehcni6
)mc03(sehcni21,)Wk3(hutB000,01<
)Wk3(hutB000,01>secnailpparof
:roolfehthtaenebsedis2muminimanonepoyllufsiynoclabrokced,hcrop,adnarevfidettimrepylnO‡*
P
N
Q
M
V
N
O
V
D
V
secnailpparof)mc51(sehcni6
)mc32(sehcni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
otdednemmocer)mm922(sehcni9
noitasnednocwodniwtneverp
teef51fothgiehanihtiw)mc19(teef3
**ylbmessarotaluger/retemehtevoba
secnailpparof)mc51(sehcni6
)mc32(sehcni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
**yllatnoziroh)m3(
htobsevresdnasgnillewdylimafelgnisowtneewtebdetacolsihcihwyawevirddevaproklawedisaevobayltceridetanimrettonllahstnevA
Figure 8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
Page 8
FIREPLACE FRAMING SPECIFICATIONS
Framing should be
constructed of 2 x 4
or larger lumber.
B
1/2 A
A
Inches (mm)
Figure 9
D
C
Framing
10-1/2
(
267
)
5-1/8 (130)
C is the required framing depth
dimension when the finish material
(drywall) thickness is 1/2 in. (13mm).
(178)
.oNledoMABCD
.ni61/9034/3042/16183
03VDLPM
mm6875301914569
*7
**12-1/8
(308)
*9" (229 mm) For MPLDV-35, 40 & 45
**14-1/8" (359 mm) For MPLDV-35, 40 & 45
.ni61/953044/32/16183
53VDLPM
mm3095301914569
.ni61/9044/3542/16134
04VDLPM
mm030126119142901
.ni61/954544/32/16134
54VDLPM
mm751126119142901
.oNledoMABCDE
.ni4/1034/1257346/7418/162
03VDLPM
mm8677231049853466
.ni
53VDLPM
mm
.ni4/1044/126448/5718/113
04VDLPM
mm220118518111844197
.ni
54VDLPM
mm
Note­Venting requirements for corner installations - the horizontal vent length “a” to “b,” must not exceed 28 inches (711 mm)
Note: The appliance 45° collar can be rotated about its axis to align for
corner installation. Remove interfering corner spacer. This spacer is used for shipping only.
May Be
Removed
Back wall of chase/enclosure
(including any finishing materials)
*D
*C
a
A
*B
*These dimensions occur when one 45 degree elbow is connected directly to the appliance collar.
May Be Removed
b
7 (178)
*E
Inches
(millimeters)
8
Figure 10
Corner Framing with Square Termination (SV4.5HT-2)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 9
FIREPLACE SPECIFICATIONS
F
G
6 5/8 (168)
TOP VIEW
4 3/4 (121)
LEFT SIDE VIEW
2 9/32 (58)
13 11/64
(335)
E
3 5/16 (100 mm)
10
(254 mm)
A
C
D
H
B
FRONT VIEW
17
(432)
RIGHT SIDE VIEW
1 (25.4)
Unit Dimensions
Figure 11
.oNledoMABCDEFGH
.ni2/1042/1738/5028/1424/1034/3918/794/172
03VDLPM
mm9201359435316867205152296
.ni2/1042/1738/5028/1924/1534/3428/3214/172
53VDLPM
mm9201359435047598926413296
.ni2/1542/1248/5528/1434/1044/3928/7414/123
04VDLPM
mm651108011567682201657873918
.ni2/1542/1248/5528/1934/1544/3438/3714/123
54VDLPM
mm651108011564999411388144918
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
Page 10
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guide­line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and ­B149.2 in Canada.
These fireplaces are designed, tested and listed for operation and installation with, and only with, Secure Vent Direct Vent System Components, Secure Flex Flexible Vent Components manufactured by Security Chimneys International and Z-FLEXModel GA Venting Systems listed to UL1777 and ULCS635 manufac­tured by Flexmaster Canada Limited. These approved vent system components are labeled for identification. DO NOT use any other manufacturer's vent com­ponents with these appliances.
These fireplaces must be vented directly to the outside.
Determine the venting for the appliance. If the vent run will include at least 8 feet of vertical rise, then install the second restrictor in the appliance collar before connecting any vent (Refer to tor inside the fixed restrictor.
Note: The second restrictor is included within the firebox.
Figure 12
Exhaust Vent
). Place the second restric-
Fixed Restrictor
The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclos­ing wall (such as a chase). There is no require­ment for inspection openings in the enclosing wall at any of the joints in the vent pipe.
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, deter­mine vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section relating to your installation. A list of approved
venting components is shown in the tables on page 26.
VERTICAL TERMINATION SYSTEMS (ROOF)
Figures 13, 17 and 23 through 25 on pages 12, 14 and 15
and their associated Vertical Vent Tables illustrate the various vertical vent­ing configurations that are possible for use with these appliances. Secure Vent pipe ap­plications are shown in these figures; Secure Flex pipe may also be used.
A Vertical Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.
Both these vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is speci­fied in ANSI Z223.1-(latest edition) (In Canada, the current CAN-1 B149 installation code) by major building codes. Always consult your local codes for specific requirements. A gen­eral guide to follow is the Gas Vent Rule (refer to
Figure 4
on page 6 ).
Vertical (Straight) Installation
SV4.5CGV-1
Termination
40' Max. (12.2 M)
6' Min.
(1.8 M)
SV4.5FA OR SV4.5FB Flashing AND SV4.5SC STORM COLLAR
1" (25.4 mm) Minimum Clearance to Combustibles
*SV4.5VF Firestop/Spacer
SV4.5L6/12/24/36/48 Vent Sections
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF
Figure 13
Vertical (Offset) Installation
Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to Vertical Vent Fig- ures and Tables on page 14 and 15 to select the type of vertical installation desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section Length Chart on page 11 for an aid in selecting length combinations. Elbows are available in 90° and 45° configurations. Refer to SV4.5E45 and SV4.5E90 elbow dimensional specifications.
Figure 18
for the
10
Second Restrictor (For Vertical Vent Only)
Figure 12
Determine the number of straight vent sec­tions required. 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 461/2" (1181 mm) net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Refer to the Vent Section Length Chart.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 11
lanimoN
htgneLnoitceS
621426384
)sehcni(
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.91526.1210003
1257.1020002
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
5.94521.4102003
1552.4100012
5.55526.4012003
7557.4001102
6652.5022004
5.76526.5003003
9657.5000202 27 6103004
5.37521.6100203
5.97526.6010203
1857.6000112
095.7021014
5.19526.7002013
3957.7000022 69 8101204
5.79521.8100023
2015.8200024
5.301526.8000303
801 9100304
4115.9020024
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
8315.11000404
5.931526.11000033
5.241578.11100405
T
O
T A L
Q
T Y
TRAHCHTGNELNOITCESTNEV
TRAHCHTGNELNOITCESTNEV
noitceSlanimoN
621426384
)sehcni(htgneL
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
44121100034
0515.21010034
5.451578.21110035
5.061573.31020035
5.271573.41000505
77157.41100506
38152.51010506
6815.51000044
5.091578.51100045
5.691573.61010045
5.502521.71011507
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.232573.91000055
73257.91100056
5.142521.02000707
6425.02100708 25212010708 46222001708 67232000808
97252.32000066
5.082573.32100809
5.382526.32100067
5.982521.42010067
5.103521.52001067
5.013578.52000909
5135.621009001
5.523521.72000077
0335.72100078 63382010078
54357.8200001001
5.943521.9210001011
27313000088
5.673573.13100089
5.973526.1300011011
5.814578.43000099
32452.531000901
56457.8300000101
T O T A L
Q T Y
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1-1/2" (38 mm) to 7-1/2" (191 mm).
The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent sec­tion component) and a plain end with 3 pilot holes. Slip the plain end over the locking channel end of a standard SV4.5 vent com­ponent the required distance and secure with three #8 x 3/8" screws.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical vent elements.
Clearances for horizontal vent elements are 1" (25 mm) at the sides and 1" (25 mm) on the bottom. Clearances above horizontal vent elements are 3" (76 mm) for all models and all applications.
Exception: Clearance is 5" (127 mm) for MPLDV35, MPLDV40 & MPLDV45, when the center line of the hori­zontal run is less than 48" (1219 mm) above the fireplace top wrapper surface.
The starter elbow may not be used if a 45 degree vent run is required directly off of the unit. Refer to
Detail - Figure 17
.
A. Attach Supplied 45 Degree Starter Elbow -
Slip the plain end with 3 mounting holes over the locking channel end of the appliance collar and secure with three screws.
B. Support The Elbows - Support the starter elbow and the vertical portions of the venting system with support bracket as shown in
Figure 23
- Detail A, on page 14. Do not use
the starter elbow anywhere else in the vent system if not used on the appliance collar. SV4.5 rigid and flex components can be used directly off the collar. Do not return to rigid sections after using flex sections in a vent run.
C. Frame ceiling opening - Use a plumb line from the ceiling above the appliance to lo­cate center of the vertical run. Cut and/or frame an opening, 10-1/2" x 10-1/2" (267mm x 267mm) inside dimensions, about this center mark (
Figure 14
).
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
11
Page 12
10 1/2” Min. (267 mm)
10 1/2” Min. (267 mm)
Figure 14
D. Attach vent components to 45 degree starter elbow - Secure Vent SV4.5 direct vent
system components are unitized concentric pipe components featuring positive twist lock connections (
see Figure 15
).
All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent compo­nents fit over the appliance collar to create the positive twist lock connection.
First Vent Component
Align the dimple (four places) with the opening of the locking incline channel on appliance collar. Twist vent component clockwise to engage and seal.
Dimple
Locking Incline Channel
45 degree starter elbow
Vent / 45 Degree Starter
Elbow Connection
Figure 15
To attach a vent component to the 45 degree starter elbow, align the dimpled end over the elbow, adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar
refer to Figure 15
(
).
Push the vent component against the starter elbow until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels.
The unitized design of the Secure Vent com­ponents will engage and seal both the inner and outer pipe without the need for sealant or screws. If desired a #6 x 1/2" screw may be used at the joint, but it is not required as the pipe will securely lock when twisted.
Note: Always use the starter elbow directly at the appliance 45° collar unless rigid straight pipe of flex pipe is used, as shown in Figure 17.
E. Attach vent components to each other - Other
vent sections may be added to the previously installed section in accordance with the require­ments of the vertical vent figures and tables. To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
This seating position is indicated by the alignment of the arrow and dimple as shown in
Figure 16.
F. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF firestop/spacer at ceiling joists; when using Secure Flex, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be installed on the top side of the joist.
Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner. Remember to maintain 1" (25 mm)
clearance to combustibles, framing mem­bers, and attic or ceiling insulation when running vertical chimney sections. Attic insu­lation shield (96K94) may be used to obtain the required clearances indicated here. See installation accessories table on page 25.
G. Support the vertical vent run sections -
Note - Proper venting support is very impor-
tant. The weight of the vent must not be supported by the fireplace in any degree.
Support the vertical portion of the venting system every 8 feet (2.4m) above the fireplace vent outlet. One method of support is by utiliz­ing field provided support straps (conven­tional plumber's tape). Secure the plumber's tape to the framing members with nails or screws.
12
Arrow
Arrow
Figure 16
Align the dimple (four places) of the upper vent section with the opening of the locking incline channel on the lower vent section. Twist vent component clockwise to engage and seal until arrow and dimple align.
Dimple
Locking Incline Channel
Connected
Vent Sections
Vent / Vent Section
Connection
Arrow
Rigid Or Flex Venting Components May Be Connected Directly To The 45 Degree Collar.
Detail
Figure 17
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Blocking
Support Straps
(Plumber’s tape)
8 feet (2.4 m)
Maximum
1 inch
(25.4 mm)
minimum
clearance to
combustibles
Page 13
Loop the tape around the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x 1/2" length may be used to secure the support straps to the vent pipe. Refer to
Figure 17.
H. Change vent direction to horizontal/in­clined run - At transition from or to a horizon-
tal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected vent sections. See
4-13/16"
(122 mm)
Swivel Joint
(360
¡
swivel)
SV4.5E45
(45¡ Elbow)
Figure 18
Swivel Joint
(360
¡
swivel)
SV4.5E90
(90¡ Elbow)
.
8-1/8"
(206 mm)
Figure 18
I. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step E. Install support straps every 5' (1.52 m) along horizontal/ inclined vent runs using conventional plumber’s tape. It is very important that the horizontal/
inclined run be maintained in a straight (no dips) and slightly elevated plane in a direc­tion away from the fireplace 1/4" per foot (20
mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
H. Frame roof opening - Identify location for vent at the roof. Cut and/or frame opening per Roof Framing Chart and
C
Figure 19
D
.
Framing Dimensions for Roof
Pitch C D 0/12 10-1/2 in. 10-1/2 in.
(267 mm) (267 mm)
6/12 10-1/2 in. 12 in.
(267 mm) (305 mm)
12/12 10-1/2 in. 17-3/4 in.
(267 mm) (451 mm)
Figure 19
J. Install the roof flashing - Extend the vent
sections through the roof structure. Install the roof flashing over the vent section and posi­tion such that the vent column rises vertically (use carpenters level) ( perimeter to secure flashing or adjust roofing to overlap the flashing edges at top and sides only and trim where necessary. Seal the top and both sides of the flashing with waterproof caulking.
Figure 20
). Nail along
Storm Collar
Figure 21
L. Install the vertical termination - The final step
involves installation of the SV4.5CGV-1 Vertical Termination. Extend the vent sections to the height as shown in the "Vertical vent termination section" on page 6. The SV4.5CGV-1 Vertical Termination (
Figure 22
same fashion as any other Secure Vent section. Align the termination over the end of the previ­ously installed section, adjusting the radial align­ment until the four locking dimples of the termi­nation are aligned with the inlets of the four incline channels of the last vent section. Push the termination down until it fully engages, then twist the termination clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
) installs in the exact
It is important to maintain the required clear­ances to combustibles at the top and bottom for all horizontal/inclined runs.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical vent elements.
Clearances for horizontal vent elements are 1" (25 mm) at the sides and 1" (25 mm) on the bottom. Clearances above horizontal vent elements are 3" (76 mm) for all models and all applications.
Exception: Clearance is 5" (127 mm) for MPLDV35, MPLDV40 & MPLDV45, when the center line of the hori­zontal run is less than 48" (1219 mm) above the fireplace top wrapper surface.
Figure 20
K. Install the storm collar - Install the storm
collar, supplied with the flashing, over the vent/flashing joint. See
Figure 21.
the storm collar screw. Slide collar down until it meets the top of the flashing. Tighten the adjusting screw. Apply non-combustible caulk­ing or mastic around the circumference of the joint to provide a water tight seal.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Loosen
Figure 22
If the vent system extends more than 5' (1.5 m) above the roof flashing, stabilizers may be necessary. Additional screws may be used at section joints for added stability. Guide wires may be attached to the joint for additional support on multiple joint configurations.
13
Page 14
VERTICAL VENT FIGURES/TABLES
Note: Secure Vent (rigid vent pipe) is shown in the figures; Secure Flex (flexible vent pipe) may
also be used.
WARNING: UNDER NO CIRCUMSTANCES MAY SEPARATE SECTIONS
OF CONCENTRIC FLEXIBLE VENT PIPE BE JOINED TOGETHER.
Note: It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of
1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
Note: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent) or SF4.5HF (Secure Flex) must be used anytime vent pipe passes through a combustible wall. For the MPLDV35/40/45, with a center line lower than 48" (1219 mm) above the fireplace top wrapper surface, use SV4.5HF5 or SF4.5HF5. In all cases the firestop/spacer provided with the termination may be used with the termination, frame to 5" clearance where applicable.
Note: Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting figures for 90 elbows, must be followed if 45 degree elbows are used.
*
Ceiling
Firestop/Spacer
(SV4.5VF)
Detail View
40 feet
(12.2 meters)
Maximum
V
H
*Ceiling
Firestop/Spacer
(SV4.5VF)
**Wall
Firestop/Spacer
TABLE A
H Maximum
(meters)
feet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + H = 40 feet (12.2 m) Max.
H = 20 feet (6.096 meters) Max.
V Minimum
feet
1 2 3 4
(meters)
(0.305) (0.610) (0.914) (1.219)
Support Bracket
*
When using Secure
Flex, use
Firestop/Spacer
SF4.5VF
Note: Install second restrictor in any run
having more than 8 ft. of vertical rise.
Figure 23
- Top Vent - STRAIGHT
14
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF
**Use Firestop/Spacer SV4.5HF or SF4.5HF when using Secure Vent or Secure Flex respectively. Use Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using Secure Vent or Secure Flex on horizontal
vent runs for the MPLDV35/40/45 with a center line lower than 48” (1219 mm) above the fireplace
top wrapper surface. In all cases the firestop/spacer provided with the termination may be used
with the termination, frame to 5” clearance where applicable.
Support Bracket
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical
vent will be required. This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet
of (H) horizontal run, up to a maximum horizontal run of 20 feet.
Figure 24
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
-
Top Vent - TWO 90 DEGREE ELBOWS
Page 15
VERTICAL VENT FIGURES/TABLES
(continued)
TABLE B
H
Maximum
H +
1
feet feet
5 10 15 20
(meters) (meters)
(1.524) (3.048) (4.572) (6.096)
H + H1 = 20 feet (6.096 m) Max.
= 40 ft. (12.192 m) Max.
+ H + H
V
1
V Minimum
1 2 3 4
(0.305) (0.610) (0.914) (1.219)
*Ceiling
H
1
Firestop/Spacer (SV4.5VF)
H
V
**Wall Firestop/Spacer
Example: If 20 feet of (H) horizontal vent run is
needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
Figure 25 -
Top Vent - THREE ELBOWS
HORIZONTAL (OUTSIDE WALL) TERMINATION SYSTEM
Figures 26, and Figures 29 to 32 on pages 18 and 19
and their associated Horizontal Vent
Table illustrate the various horizontal venting configurations that are possible for use with these appliances. Secure Vent pipe applica­tions are shown in these figures; Secure Flex pipe may also be used. A Horizontal Vent Table summarizes each systems minimum and maxi­mum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.
A. Attach Supplied 45 Degree Starter Elbow
- Slip the plain end with 3 mounting holes over
the locking channel end of the appliance collar and secure with three screws.
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF
**Use Firestop/Spacer SV4.5HF or SF4.5HF when using Secure Vent or Secure
Flex respectively. Use Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using
Secure Vent or Secure Flex on horizontal vent runs for the MPLDV35/40/45
with a center line lower than 48” (1219 mm) above the fireplace top wrapper
surface. In all cases the firestop/spacer provided with the termination may
be used with the termination, frame to 5” clearance where applicable.
B. Support The Elbows - Support the starter
elbow and the horizontal portions of the vent­ing system with support bracket as shown in
Figure 29 to 32
.
Both of these horizontal vent systems terminate through an outside wall. Building Codes limit or prohibit terminating in specific areas. Refer to
Figure 8
on page 7 for location guidelines.
Secure Vent SV4.5 direct vent system compo-
nents are unitized concentric pipe compo­nents featuring positive twist lock connection, (
refer to Figure 15 and 16
on page 12). All of the appliances covered in this document are fitted with collars having locking inclined chan­nels. The dimpled end of the vent components fit over the appliance collar to create the posi­tive twist lock connection.
Support Bracket
Detail View
C. Plan the vent run -
Analyze the vent routing and determine the types and quantities of sections required 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Make allowances for elbows as indi­cated in
Figure 18 on page 13
.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical vent elements.
Clearances for horizontal vent elements are 1" (25 mm) at the sides and 1" (25 mm) on the bottom. Clearances above horizontal vent elements are 3" (76 mm) for all models and all applications.
Exception: Clearance is 5" (127 mm) for MPLDV35, MPLDV40 & MPLDV45, when the center line of the hori­zontal run is less than 48" (1219 mm) above the fireplace top wrapper surface.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
15
Page 16
D. Frame exterior wall opening -
Locate the center of the vent outlet on the exterior wall according to the dimensions shown in
Figure 9
on page 8.
Cut and/or frame an opening, 10-1/2" x 12-1/8" (267 mm x 308mm) inside dimensions, about this center.
E. Frame ceiling opening - If the vertical route is to penetrate a ceiling, use plumb line to locate the center above the appliance. Cut and/ or frame an opening, 10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center (refer to
Figure 14
on page 11 ).
Building Support Framing
SV4.5E90
Elbow
Vertical
Rise
Support
Brackets
Ceiling
TYPICAL HORIZONTAL VENT INSTALLATION
Horizontal / Inclined Run
SV4.5L6/12/24/36/48
Vent Sections
Firestop/Spacer
See Figure 17 on page 12 for vertical vent section support.
Support Bracket Spacing Every 5 ft (1.52 m)
SV4.5 HT-2 Termination
Exterior Wall
SV4.5 HT-2 Termination
F. Attach vent components to starter elbow -
To attach a vent component to the the starter elbow, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar (
Figure 15
on page 12).
refer to
Push the vent component against the elbow until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure. Sealant and securing screws are not required.
Note: A 90 or 45 degree elbow may not be directly attached to the appliance elbow collar.
G. Attach vent components to each other -
Other vent sections may be added to the pre­viously installed section in accordance with the requirements of the vent tables.
To add another vent component to a length of vent run, align the dimpled end of the compo­nent over the inclined channel end of the previously installed section, adjusting the ra­dial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section.
Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.This seating
position is indicated by the alignment of the arrow and dimple as shown in
Figure 16 on
page 12.
H. Install firestop/spacer at ceiling -
When using Secure Vent, use SV4.5VF firestop/ spacer at ceiling joists; when using Secure Flex, use SF4.5VF firestop/spacer.
Figure 26
If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
I. Support the vertical run sections -
On the vertical run, support the venting sys­tem every 8 feet (2.4m) above the fireplace vent outlet with field provided support straps (Plumber's tape).
Attach the straps to the vent pipe and secure to the framing members with nails or screws. See
Figure 17 on page 12.
J. Change vent direction - At transition from or to a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist
elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected vent sec­tions. See
Figure 18 on page 13
K. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step F.
If attic space is
.
Fireplace
Exterior Wall
Install support straps every 5 ft. (1.52 m) along horizontal/inclined vent runs using con­ventional plumbers tape. See
Figure 26
very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm per meter) which
is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or
.
near level
Use a carpenters level to measure from a constant surface and adjust the support straps as necessary.
It is important to maintain the required clear­ances to combustibles at the top and bottom for all horizontal/inclined runs.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical vent elements.
Clearances for horizontal vent elements are 1" (25 mm) at the sides and 1" (25 mm) on the bottom. Clearances above horizontal vent elements are 3" (76 mm) for all models and all applications.
Exception: Clearance is 5" (127 mm) for MPLDV35, MPLDV40 & MPLDV45, when the center line of the hori­zontal run is less than 48" (1219 mm) above the fireplace top wrapper surface.
L. Assemble vent run to exterior wall - If not
previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step D. Assemble the vent system to point where the terminus of the last section is within 7 in. (178 mm) to 11-1/4 in. (286 mm) inboard of the exterior surface to which the SV4.5 HT-2 termination is to be attached, see
Figure 28
.
, it is
16
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 17
If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section. For wall thicknesses greater than that shown in
28
, refer to
Table 3 on page 18
Figure
. This table lists the additional venting components needed (in addition to the termination and adapter) for a particular range of wall thicknesses.
M. Attach termination adapter - Attach the adapter (SV4.5RCH - provided with the termi­nation) to the vent section or telescoping vent section), elbow as shown in
Figure 27
in the same manner as any SV4.5 vent component (refer to Step F).
**12-1/8" (308 mm)
5-1/8"
(130 mm)
6 to 48 inch
Vent Section,
Telescopic vent
section on Elbow
**7"
(178)
Firestop/Spacer provided with the termination shown on the exterior
side of the wall. It may also be
installed on the interior side.
10-1/2"
(267 mm)
for MPLDV30/35
1"
(25.4 mm)
SV4.5 HT-2
Termination
**3” (76 mm)
N. Install Firestop/Spacer at exterior wall -
When using the square termination, install the SV4.5HF (Secure Vent) or SF4.5HF (Se­cure Flex) Firestop/Spacer over the open­ing at the exterior side of the framing (long side up) as shown in
Figure 27
, and fasten into place. Ensure 5" clearance is main­tained by framing above the vent run for MPLDV35/40/45 when center line of the run is lower than 48" (12119 mm) above the fireplace top wrapper surface.
(The Firestop/Spacer may also be installed over the opening at the interior side of the framing.)
O. Install the desired termination -
1. Install the square termination (SV4.5HT-2)-
For the last step , from outside the exterior wall, slide the collars of the termination onto the adapter (the outer over the outer and the inner inside the inner) until the termination seats against the exterior wall surface to which it will be attached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The horizontal
termination must not be recessed into the exterior wall or siding by more than the 1-1/4"
(32 mm) as shown in
Figure 28
.
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
Adapter
SV4.5RCH
**Increase these dimensions by 2” (51mm) for MPLDV35/40/45
with horizontal vent runs with center lines lower than 48”
(1219mm) above the fireplace for wrapper surface.
Figure 27
*Use silicone caulking to seal the top and sides of the termination, up to the underlayment, stucco, or masonry wall surface.
*Caulk
*Caulk
Stucco
Installing the Square Horizontal Termination (SV4.5HT-2)
Maximum Extent of
Siding
Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section. Use Telescopic Vent Section (SV4.5LA), If Necessary
SV4.5HT-2
Square Termination
**For thicknesses greater than 10”, see Table 3.
the Frame Opening.
Interior Surface of
Finished Wall
Adapter
SV4.5RCH
See Figure 9 on page 8
for Min. Distance to Base
of Appliance.
Base of Appliance
Maximum wall thickness
10 in.(254 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to 9-1/4 in.
(152 to 235 mm)**
Square Termination
1-1/4" Maximum Recess of Square Termination into Exterior Finishing Material
SV4.5HT-2
SVHRK Snorkel Cap –The snorkel cap is de-
signed to be fitted into a basement window box. The SVHRK cap is for use with flex vent. The vertical distance between the inlet and outlet of the cap is 28 in. (711 mm). pipe.
IMPORTANT: The vent termination is hot while in operation and for a period of time following use of the fireplace. To prevent contact with hot surfaces, we recommend the use of a Termination Guard. This can be purchased at your local dealer.
Venting Connection and Exterior Wall Recessing of the
Horizontal Square Termination (SV4.5HT-2).
Figure 28
Horizontal terminations have been designed to perform in a wide range of weather conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination where water from eaves and adjoining rooflines may create a heavy flow of cascading water onto the termination cap. If the cap must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the use of silicone caulking where required.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
17
Page 18
HORIZONTAL VENT FIGURES/TABLES
Note: Secure Vent components (rigid vent pipe and terminal) are
shown in the figures; Secure Flex components (flexible vent pipe and terminal) may also be used.
Note: Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting figures for 90 degree elbows, must be followed if 45 degree elbows are used.
Note: It is very important that the horizontal/inclined run be main­tained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of
foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
Note: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. Lennox MPLDV35"/40" & 45" models require 5" clearances to combustibles above horizontal vent runs when the centerline of the horizontal vent run is at or below 48" (1219 mm) above the fireplace top wrapper. In all other instances, with these three models and with the MPLDV30 in all instances, the clearance to combustibles above horizon­tal vent runs is 3". Please note that to facilitate the 5" clearance when required, we have two 5" clearance firestops. The SV4.5HF5 is for use with rigid (Secure Vent ) and the SF4.5HF5 is for use with (Secure Flex ). These firestops should be used whenever horizontal vent runs meeting the use requirements detailed above, penetrate walls separating occupied rooms in a house.
1/4" rise per
The SV4.5HF or SF4.5HF firestop provided with each termination can be used as shown in Figure 29 when fitted at the exterior wall adjacent to the termination.
WARNING: UNDER NO CIRCUMSTANCES MAY SEPA­RATE SECTIONS OF CONCENTRIC FLEXIBLE VENT PIPE BE JOINED TOGETHER.
3ELBAT
llaWroiretxEsuoiraVrofderiuqeRstnenopmoCgnitneV
)2-TH5.4VS(noitanimreTerauqSehTgnisUnehW,sessenkcihT
deriuqeRstnenopmoCgnitneV
ylnOtiKnoitanimreT4/1-9ot6)532ot251(
tneV.ni6dnatiKnoitanimreT
)6L5.4VS(noitceS
2/1-01)943ot762(4/3-31ot
tneV.ni21dnatiKnoitanimreT
)21L5.4VS(noitceS
cipocseleTdnatiKnoitanimreT
).ni21-7ot2AL5.4VS(noitceS
)6L5.4VS(noitcestnev.ni6&
ssenkcihTllaWroiretxE
)mm(sehcni
)205ot914(4/3-91ot2/1-61
)205ot972(4/3-91ot11
Each of our horizontal terminations are shipped with a standard 3" clearance horizontal firestop. In ALL cases this firestop may be used at the exterior wall regardless of any circumstances that may require the 5" clearance to combustibles above the horizontal vent component. The firestop provided with the termination is not specific for use with any particular clearance height.
SV4.5HF/SF4.5HF
Firestop
Stud Framing
Top Spacer
3”
1”
1”
1”
SV4.5HF/SF4.5HF Firestop
Stud Framing
Top
5”
1”
1”
1”
Spacer
18
Figure 29
3” Clearance
5” Clearance
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 19
TABLE C
H Maximum
(meters)
feet feet
(1.524)
5
V Minimum
(meters)
1 (0.305) 10 (3.048) 2 (0.610) 15 (4.572) 3 (0.914) 20 (6.096) 4 (1.219)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
Example: If 20 feet of (H)
horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
H
*Use Firestop/Spacer SV4.5HF or SF4.5HF
when using Secure Vent or Secure Flex
respectively. Use Firestop/Spacer SV4.5HF5
or SF4.5HF5 when using Secure Vent or
Secure Flex on horizontal vent runs for the
MPLDV35/40/45 with a center line lower than
48” (1219 mm) above the fireplace top
wrapper surface. In all cases the
firestop/spacer provided with the termination
may be used with the termination, frame to
5” clearance where applicable.
H
**Wall
Firestop/Spacer
*When using Secure Flex, use
Firestop/Spacer SF4.5VF
**Use Firestop/Spacer SV4.5HF or SF4.5HF when using
Secure Vent or Secure Flex respectively. Use
Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using
Secure Vent or Secure Flex on horizontal vent runs for
the MPLDV35/40/45 with a center line lower than 48”
(1219 mm) above the fireplace top wrapper surface.
In all cases the firestop/spacer provided with the
termination may be used with the termination, frame
to 5” clearance where applicable.
*Ceiling
Firestop/Spacer
(SV4.5VF)
Square termination (SV4.5HT-2) shown.
Table 3
See
as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Figure 30
-
Top Vent - ONE 90 DEGREE ELBOW - ELBOW
CONNECTION NOT DIRECTLY AT APPLIANCE
Support Bracket
V
*Wall
Firestop/Spacer
Support Bracket
H = 28 inches (711 mm) Maximum
Square termination (SV4.5HT-2) shown.
Figure 31
-
Top Vent - ONE 90 DEGREE ELBOW -
CONNECTION DIRECTLY AT APPLIANCE
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
19
Page 20
HORIZONTAL VENT FIGURES/TABLES (CONTINUED)
**Wall
Firestop/Spacer
H
1
***Note - When using
Secure Flex, use
Firestop/Spacer SF4.5VF
**Use Firestop/Spacer SV4.5HF or SF4.5HF when using Secure Vent or Secure Flex respectively. Use Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using
Secure Vent or Secure Flex on horizontal vent runs
for the MPLDV35/40/45 with a center line lower than
48” (1219 mm) above the fireplace top wrapper
surface. In all cases the firestop/spacer provided
with the termination may be used with the
termination, frame to 5” clearance where applicable.
Square termination (SV4.5HT-2) shown.
See
Table 3 on page 18
as an aid in venting component selection for a particular range
of exterior wall thicknesses.
Figure 32
-
Top Vent - TWO 90 DEGREE ELBOWS - ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
Firestop/Spacer
H
**Wall
***Ceiling
Firestop/Spacer
(SV4.5VF)
Support Bracket
*
To Top Surface Of
Fireplace
V*
TABLE D
+ H
H
Maximum
1
(meters)
feet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V +H+ H1 = 40 feet (12.2 m) Max.
+ H1 = 20 ft. (6.096 m) Max.
H
V Minimum
(meters)
feet
1 (0.305) 2 (0.610)
(0.914)
3
(1.219)
4
Example: If 20 feet of (H) horizontal vent run
is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
H
1
***Wall
Firestop/Spacer
***Use Firestop/Spacer SV4.5HF
or SF4.5HF when using Secure
Vent or Secure Flex respectively.
Use Firestop/Spacer SV4.5HF5
or SF4.5HF5 when using Secure Vent or Secure Flex on horizontal vent runs for the MPLDV35/40/45 with a center line lower than 48”
(1219 mm) above the fireplace top wrapper surface. In all cases the firestop/spacer provided with the termination may be used with
the termination, frame to 5” clearance where applicable.
**When using Secure Flex, use
Firestop/Spacer SF4.5VF
+ H
H
1
feet
**Ceiling
Firestop/Spacer
(SV4.5VF)
5 10 15
H
20
H
V
1
V*
+ V +H+ H = 40 ft. (12.192 m) Max.
V
Example: If 20 feet of (H) horizontal vent
run is needed, then 4 feet minimum of (V)
TABLE E
Maximum
(meters)
(1.524) (3.048) (4.572) (6.096)
+ H1 = 20 feet (6.096 m) Max.
11
+ V
V Minimum
1
(meters)
feet
(0.305)
1
(0.610)
2
(0.914)
3
(1.219)
4
vertical vent will be required. This table shows a 1 (V) to 5 (H) ratio. For
every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maxi-
***Wall
Firestop/Spacer
**Ceiling
Firestop/Spacer
(SV4.5VF)
mum horizontal run of 20 feet.
Support Bracket
*To Top Surface
Of Fireplace
20
Square termination (SV4.5HT-2) shown.
Table 3 on page 18
See
Figure 33
-
Top Vent - THREE 90 DEGREE ELBOWS - ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
as an aid in venting component selection for a particular range of exterior wall thicknesses.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 21
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX
KITS AND COMPONENTS
Secure Flex venting kits and components may
be used in any venting application where rigid Secure Vent (SV4.5) direct vent components can be used. All restrictions, clearances and allowances that pertain to the rigid piping apply to the flexible venting.
Secure Flex
kits may not be modified; also, under no circumstances may separate sections of flex pipe be joined together. Secure Flex kits may be added to the
end of a vent run made up of rigid Secure Vent (SV4.5) vent sections provided that doing so does not violate any of the venting length, height, routing, horizontal to vertical ratio re­quirements or clearance considerations de­tailed in this manual.
Secure Flex kits come with an included adapter that can be fitted to the appliance collar or the inclined channel end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent section. Align the dimpled end of the adapter over the previously installed section or appli­ance collar, adjusting the radial alignment until the four locking dimples of the adapter are aligned with the inlets of the four incline chan­nels of the last vent section or collar. Push on the adapter until it fully engages, then twist the adapter clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Attach the flexible vent to the adapter as follows
(also see Figure 34 )
:
A. Install the Inner Flex Pipe -
1. Install the small gear clamp loosely around the
inner flexible vent pipe, push it back out of the way.
2. Apply a bead of Mill-Pac Black (700
°F)
high temperature sealant - Catalog No. 10K81) to the inner adapter collar, approxi-
mately 1/2 inch from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adapter
collar. Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1³⁄₄ inches from the end, and that it is free from damage or tears.
5. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adapter inner collar approximately 3/4 inch from the end of the flex.
6. Install three screws 120 degrees apart through the flexible vent pipe and into the adapter collar just below the gear clamp to provide additional security to the connection.
B. Install the Outer Flex Pipe -
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out of the way.
NOTE: OUTER PIPE IS PULLED AWAY TO SHOW THE DETAIL OF THE INNER PIPE
Apply ONLY MIL-PAC BLACK HIGH TEMPERATURE SEALANT (Catalog No. 10K81) to the outside surface of both collars of the adapter (be especially careful to fill the grooves of the outer collar to be covered by the flexible pipe) and slide flexible pipe over inner and outer adapter collars.
1-3/4 in. (44 mm) Flexible Pipe and
Adapter Outer Collar Overlap
Adapter
(SV4.5RF)
Attach Adapter to Appliance
Collar, or Secure Vent Sections
Figure 34
2. Apply a bead of Mill-Pac Black (700 temperature sealant - Catalog No. 10K81) to
the outer adapter collar; to the grooves of the collar which extend approximately 1 inch from the end and to the flat surface, approximately 1­3/8 inches from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adapter
collar. Ensure the flexible vent pipe com­pletely engages the adapter collar to a dis­tance of 1-3/4 inches from the end, and that it is free from damage or tears.
5. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adapter outer collar approximately 3/4 inch from the end of the flex.
6. Install three screws 120 degrees apart through the flexible vent pipe and into the adapter collar just below the gear clamp to provide additional security to the connection.
C. Route Flex Vent -
Ensure that the flex vent is properly routed to provide the required clearance. Do Not allow the flexible vent to bend in a radius tighter than 5" (127 mm). Refer to
Figure 35
horizontal sections of flex with metal straps at 2 foot (0.61 m) intervals.
D. Install Firestop/Spacers at ceilings and walls -
When Secure Flex penetrates a wall or ceil­ing, a firestop/spacer is required: use SV4.5 (Secure Vent), SF4.5 (Secure Flex) firestop/ spacer anytime vent pipe passes through a combustible floor or ceiling.
°F) high
. Support
FLEX VENT
SECURING SCREW
(3 PLACES EQUIDISTANT
JUST BELOW GEAR CLAMP)
GEAR CLAMPS
1-3/4 in. (44 mm) Flexible Pipe and
Adapter Inner Collar Overlap
SECURING SCREW
(3 PLACES EQUIDISTANT
JUST BELOW GEAR CLAMP)
SV4.5HF (Secure Vent) or SF4.5HF (Secure Flex) must be used anytime vent pipe passes through a combustible wall. For the MPLDV35/40/45 with a center line lower than 48" (1219 mm) above the fireplace top wrap­per surface use SV4.5HF5 or SV4.5HF5. In all cases the firestop/spacer provided with the termination may be used with the termina­tion, frame to 5" clearance where applicable.
See the appropriate sections and figures shown throughout the venting section for their installation requirements.
Flexible Vent Section
5" (127 mm)
Radius Minimum
Figure 35
E. Attach Flex Vent to Termination ­Secure Flex components can be purchased
separately and attached to bulk lengths of Secure Flex flexible tubing cut to size at the job site. Secure the flexible vent to the Secure
Flex terminations in the same manner (see
Figure 34)
as it was attached to the adapter.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
21
Page 22
Note:
Secure Flex
Secure Flex
substitute
Secure Vent
nents. The collars of
vent must be attached to
terminations only. DO NOT
Secure Vent
adapter for
terminations or the
Secure Flex
Secure Flex
compo-
termina­tions and adapters have a different circum­ference than that used with the pipe. Additionally,
Secure Flex
Secure Vent
components have an extended length center tube for use in attaching the flexible vent.
Step 4. FIELD WIRING
Caution: Label all wires prior to disconnec­tion when servicing controls. Wiring errors can cause improper and dangerous opera­tion. Verify proper operation after servicing.
Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and pre-wired at the factory on both models.
A. Millivolt Wiring
1. Appliance-mounted ON/OFF burner control
switch (rocker switch) is factory installed be­hind the bottom panel. Optional wall-mounted switch, thermostat, or one of the optional remote control kits may also be used.
2. If wall-mounted ON/OFF control or thermo­stat is selected mount it in a convenient loca­tion on a wall near the fireplace.
3. Wire the control switch within the millivolt control circuit using the 15 feet of 2 conductor wire supplied with the unit.
Note: The supplied 15 feet of 2 conductor wire has one end of each conductor con­nected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
(See Figure 36 )
4.If an optional control switch is installed, turn
the appliance-mounted ON/OFF burner con­trol switch to the OFF position.
B. Electronic Wiring (See
Figure 37 )
Note: The electronic appliance must be con-
nected to the main power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power supply to the appliance junction box.
2. Remove the electrical inlet cover plate from the side of the unit by removing the plate's securing screws.
See Figure 11 on page 9.
3. Remove the cover plate's knockout and then
feed the power supply wire through the knock­out opening and into the unit junction box.
4. Connect the black power supply wire to the lower outlet's red pigtail lead and the white
power supply wire to the common terminal of the outlet as shown in
Figure 37.
5. Connect the ground supply wire to the pigtail lead attached to outlet's green ground screw.
6. Appliance-mounted ON/OFF burner control
switch (rocker switch) is factory installed be­hind the bottom panel.
120 VAC
BK
GR
W
JUNCTION BOX
TRANSFORMER 3V
INTERMITTENT ELECTRONIC WIRING DIAGRAM
GR
W
BK
IGNITOR MODULE
Optional wall-mounted switch, thermostat, or one of the optional remote control kits may also be used. The appliance mounted ON/OFF switch needs to be relocated onto the optional style view door, if used.
7. If wall-mounted ON/OFF control or thermo­stat is to be used, mount it in a convenient location on a wall near the fireplace.
8. If an optional control is to be used, wire it in the low voltage circuit as shown in
Figure 37.
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom com­partment.
9. If an optional control switch is installed, turn the appliance-mounted ON/OFF burner control switch to the OFF position.
10. After the wiring is complete, replace the cover plate.
Note: No batteries to be installed in the battery holder until a power outage, or if the appliance is to be operated solely with two (2) "D" batteries.
SPARK TO PILOT IGNITOR
3V
BLACK (IGNITOR)
BLACK (SENSOR)
Caution: Do Not connect the optional wall switch to a 120V power supply.
WIRING DIAGRAM MILLIVOLT GAS VALVES
THERMOPILE
APPLIANCE- MOUNTED ON/OFF SWITCH
BK/W(1)
WALL-MOUNTED ON/OFF SWITCH (OPTIONAL) THERMOSTAT (OPTIONAL)
BK/W(1)
TP-TH
TP TH
GAS VALVE
Figure 36
22
TO WALL SWITCH OR THERMOSTAT
BROWN
Figure 37
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
BLACK
BATTERY BACK-UP
RED
BROWN
ORANGE (THTP)
BLACK (TP)
GREEN (TH)
TP
HI
LO
TH
OUT
VENT
PILOT
IN
IN
TH
TP
Page 23
IMPORTANT: Ground supply lead must be connected to the wire attached to the green ground screw located on the out­let box. See
Figure 37
. Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70­(latest edition). (In Canada, the current CSA C22-1 Canadian Electrical Code.)
Gas Line Access Plate Not Installed At The Factory. It Is Included In The Installation Instruction Bag.
Step 5. CONNECTING GAS LINE
All codes require a shut-off valve mounted in the supply line. The orientation of the shut­off valve should face the front, as shown in
Figure 39. Figure 38
for connecting the gas supply. The flex-line method is acceptable in the U.S.,
however, Canadian requirements vary depend­ing on locality. Installation must be in compli­ance with local codes.
These appliances are equipped with a gas flex line for use in connecting the unit to the gas line. A gas flex line is provided to aid in attaching the direct vent appliance to the gas supply.
The gas flex line can only be used where local codes permit. See description. The flex line is rated for both natural and propane gas. A manual shut off valve is also provided with the flex line.
The gas control valve is located in the lower control compartment.
illustrates the method
Figure 38
for flex line
Gas
Supply
Line
Shut-Off Valve (Orientation
ON/OFF Switch
As Shown)
Piezo Ignitor
Figure 39
These appliances come from the factory with the gas line access plate removed to provide full access to the end of the gas flex line.
As designed, the glass door needs to be opened to access the open gas access area. Route a hard pipe from the left to a spot directly below the access plate opening.
Bring the shutoff valve on the end of the flex line over to the hard pipe and tighten with wrenches from above through the firebox opening.
If required, access the valve by removing the lower control compartment panel (
39
) by lifting and pulling the panel forward. The millivolt and electronic control valve has a 3/8" (10 mm) NPT thread inlet port.
see Figure
Gas Valve
Air Shutter Adjustment Arm
Secure all joints tightly using appropriate tools and sealing compounds (ensure pro­pane resistant compounds are used in pro­pane applications).
Turn on gas supply and test for gas leaks, using a gas leak test solution (also referred to as bubble leak solution).
Note: Using a soapy water solution (50% dish soap, 50% water) is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/ fittings can result in corrosion over time. Never
use an open flame to check for leaks. A. Light the appliance (refer to the lighting
instructions label in the control compartment or in the Homeowner's Care and Operation Instructions).
Gas Stub
Figure 38 -
1/2" x 3/8" Flare
Shut-Off Valve
GAS CONNECTION
Flex Line Connector
3/8" NPT x 3/8"
Flare Fitting
3/8" Flex Tubing
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Gas Valve
B. Brush all joints and connections with the
gas leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the OFF posi­tion. Either tighten or refasten the leaking connection and retest as described above.
C. When the gas lines are tested and leak free, be sure to rinse off the leak testing solution.
D. When the gas lines are tested and leak free, observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
23
Page 24
Door Assembly
Gas Line Access Panel
Bottom Panel
Burner Assembly
Step 6. INSTALLING THE LOGS, GLOW­ING EMBERS AND VOLCANIC STONES
Remove the gas line access plate and gasket from the provided plastic bag and install them over the opening, using the provided screws (4) as shown in
Refer to for the venturi air shutter. Manually actuate the air shutter through several cycles. Set the air shutter to 3/32" before placing the logs.
The logs are packaged in a carton located within the firebox. One plastic bag of glowing embers and volcanic stones are located in the bottom compartment. Refer to the Log Set Placement Supplement for detailed place­ment instructions for the logs, glowing em­bers and volcanic stones.
Proper log and twig placement is critical to encourage outstanding flame appearance and prevent sooting. These fires are designed to provide a rich orange/red glow on the logs. Ensure the bottom of the rear log is fully seated and pulled as far forward as the pins will al­low. Refer to the Log Set Placement
Supplement for detailed instructions.
Figure 39
Figure 43
.
and loosen the set screw
Note: Log setup is by design asymmetric. The fire is intentionally positioned off center to provide a natural fire look.
Step 7. CHECKING APPLIANCE OPERATION
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.
The top 3/8" (10 mm) at the pilot generator (thermopile) and the top 1/8" min (tip) of the quick drop out thermocouple should be en­gulfed in the pilot flame.
The flame should project 1" (25 mm) beyond the hood at all three ports place logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall switch and rotate the gas valve control knob counterclockwise to the “ON” position (“ON” will be at the bottom side of the valve).
MILLIVOLT Thermocouple
Pilot Nozzels
Thermopile
(Figure 40 ).
Hood Ignitor Rod
3/8" Min (9 mm)
Re-
Figure 40
Step 8. INSTALLING THE GLASS DOOR AND OPTIONAL HOOD
To access the glass door securing latches, first open the lower control compartment door (
Figure 42
bottom panel forward. Retrieve the glass door. Visually inspect the
gasket on the backside of the frame. Gasket surface must be clean, free of irregularities and seated firmly.
Position the door in front of the firebox opening with the bottom of the door held away from the fireplace the door frame over the top of the firebox frame. Let the bottom of the door frame swing gently in towards the fireplace ensuring that the gas­ket seats evenly as the door frame draws shut. Fasten the two latches located underneath the firebox floor to the door's vee-flange. Close both the latches securely.
If desired, install the optional hood. Note the location of the three clips inside the top air channel above the door. The clips are equally spaced on the top surface of the air channel opening. Use a screwdriver to open the clips slightly if needed. Engage the back edge of the eyebrow into the clips to secure.
(Figure 42 )
) by lifting and pulling the
. Hook the top flange of
With gas line installed run initial system check­out before closing up the front of the unit. Follow the pilot lighting instructions provided in the Homeowner's Care and Operation In­structions. For piezo ignitor location see
ure 39 on page 23
(millivolt appliances only).
Fig-
Note: Lighting Instructions are also found on the literature tag tied to the gas piping next to the gas valve. To access the tag, open the lower control compartment door (Figure 39 on page 23 ) by pulling the panel forward.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lighting of the appliance will not require such purg­ing. Inspect the pilot flame (remove logs, if necessary, handling carefully).
Electronic Appliance Checkout
To light the burner, turn ON the unit mounted On/Off switch or the optional remote wall switch. Ensure the ignitor lights the pilot. The pilot flame should engulf the flame rod as shown in
Figure 41
ELECTRONIC
Sensor
Ignitor
.
Pilot Hood
Figure 41
Figure 42
-
INSTALLING THE GLASS DOOR
WARNING: HANDLE THIS GLASS WITH EXTREME CARE! THE GLASS PANEL IS SUSCEPTIBLE TO DAMAGE — DO NOT SCRATCH WHILE HANDLING OR WHILE RE-INSTALLING THE GLASS DOOR FRAME.
24
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 25
Combustible Finished Wall Materials
This Area Must Remain Clear of Combustible Materials
Top of Appliance
3-1/2" Min (89 mm)
Spacer
Combustible
materials not
allowed
below this
point on
the face of the
appliance.
Optional Hood
Top of Door Frame
10" Min
(254 mm)
WARNING: DO NOT OPERATE APPLI­ANCE WITH THE GLASS FRONT RE­MOVED, CRACKED OR BROKEN. RE­PLACEMENT OF THE GLASS SHOULD BE DONE BY A LICENSED OR QUALIFIED SERVICE TECHNICIAN.
Step 9. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a matter of taste. Generally, most people prefer the warm glow of a yellow to orange flame. Appliances operated with air shutter openings that are too large will exhibit flames that are blue and transparent. These weak, blue and transparent flames are termed anemic. If the air shutter opening is too small sooting may develop.
CAUTION: THE AIR SHUTTER DOOR AND NEARBY APPLIANCE SURFACES ARE HOT. EXERCISE CAUTION TO AVOID INJURY WHILE ADJUSTING FLAME APPEARANCE.
To adjust the flame, rotate the lever arm up or down (rod located in the lower control area). Position the air shutter to the factory setting as shown in the table in burner to operate for at least 20 minutes.
Air Shutter Rod
Venturi
Figure 43
. Allow the
Air
Adjustment
Arm
The adjustment rod and associated adjustable air shutter is patented technology. Flame ad­justments can be made quickly and accurately to taste without the need of disassembling the appliance and waiting for 30 minutes after each adjustment.
Propane models may exhibit a flame pattern that may candle or appear stringy. If this is problematic or persists as the appliance is continually operated, adjust the air shutter closed as described in the previous paragraphs. Operate the appliance for a period of time as the effect diminishes, ensuring that the appliance does not develop sooty flames.
When satisfied that the appliance operates properly, proceed to finish the installation. Leave the control knob in the ON position and the remote switch OFF. Close the lower control compartment door.
Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior sur­faces adjacent to the vent termination. Sooting is caused by incomplete combustion in the flames and lack of combustion air entering the air shutter opening. To achieve a warm yellow to orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
No smoke or soot should be present. These logs are designed to be involved in the fire. Flames will impinge the top tips of the right and left logs.
If the logs are properly positioned and sooting conditions exist, the air shutter opening on the main burner tube should be adjusted. Normally, the more offsets in the vent system, the greater the need for the air shutter to be opened further.
Burner Adjustment
WARNING: AIR SHUTTER ADJUST­MENT SHOULD ONLY BE PER­FORMED BY A QUALIFIED PROFES­SIONAL SERVICE TECHNICIAN.
IMPORTANT: ENSURE THAT THE FRONT GLASS PANEL IS IN PLACE AND SEALED DURING ADJUSTMENT.
Valve
RENRUBNIAM
GNITTESGNINEPORETTUHSYROTCAF
sledoM
saGlarutaN
)mm(sehcni
saGenaporP
)mm(sehcni
03VDLPM)83.2(23/3)67.4(61/3 53VDLPM)6.1(61/1)53.6(4/1 04VDLPM)53.6(4/1)5.9(8/3 54VDLPM)53.6(4/1)7.21(2/1
Figure 43
CAUTION: DO NOT BEND THE AIR SHUTTER ROD. MAKE SURE THE AIR SHUTTER MOVES WHEN THE LEVER ARM IS OPERATED.
Note: When first operating the air shutter
adjustment lever arm observe the air shutter. If it is not moving, open the glass, ensure the air shutter screw is loose and adjust by hand through a couple of cycles, to break the adhe­sion of paint, if required. Close door and adjust with the lever as needed.
Observe the flame continuously. If it appears weak or sooty as previously described, adjust the air shutter by rotating the adjustment arm up or down ( appearance is as desired.
refer to Figure 39
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
) until the flame
FINISHING REQUIREMENTS Wall Details
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thick­ness of the finished wall (
Figure 44
)
Figure 44
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
25
Page 26
Note: Combustible wall finish materials and/or surround materials must not be allowed to be placed in direct contact with the area defined by the appliance front face (black sheet metal). Never allow combustible materials to overlap the appliance front face. See Figure 44 on page 25. Combustible mantle materials may be placed in front of non-combustible facing materials, as shown in Figure 45.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must not cover any portion of the glass or hood; they may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel up to the installed hood.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See
Figure 45
. Mantels constructed of non-
combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the hood.
Combustible materials may project beyond the sides of the fireplace opening as long as they are kept within the shaded areas illustrated in
Figure 46
Combustible Materials Allowed In Shaded Area “Safe Zone”
17"
.
Side Wall
12"
14"
Top View Of
45°
Side Wall
5"
8-1/4"
Min. Distance To Unprotected Side Wall
Fireplace
Min. Distance To Protected Side Wall
18
(457)
16
(406)
14
(356)
MANTEL CLEARANCES
Inches (mm)
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
4 (102) MANTEL
12
(305)
10
(254)
8
(203)
2 (51) MANTEL
TOP OF APPLIANCE
Figure 46
Figure 45
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation. In cold climates, if the fireplace is being installed on a cement slab, a sheet of plywood or other raised platform can be placed underneath to prevent conducting cold up into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
INSTALLATION ACCESSORIES
detsiL xelFeruceS stnenopmoC
.taC
.oN
18K01 04L98
ledoM
.oN
PMFS
21-PMFS 66L196-4CG-FSrof)mm411(.ni5.4pmalCraeG 76L196-7CG-FS)mm5.091(.ni5.7pmalCraeG
8422HFH5.4FSkcaP01-recapS/potseriF 9422HFV5.4FSkcaP01-recapS/potseriF
noitpircseD
tnalaeS
)seceip6(xelF
)seceip6(xelFrof
.oN.taC.oNledoMnoitpircseD
01L49**SSTH5.4VSerauqSllamSlatnoziroH
72L89**LSSTH5.4VS-erauqSllamSlatnoziroH
**May be used with 30" and 35" models only.
26
detsiL tneVeruceS stnenopmoC
t
n
a
l
a
e
htiwnoitanimreT
S
)08K69(recapS/potseriF
)16L47(retpadAdna
htiwnoitanimreTgnoL
)08K69(recapS/potseriF
)16L47(retpadAdna
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
erutarepmeT-iHkcalBcaPliM erutarepmeT-iHkcalBcaPliM
21kcaPkluB-tnalaeS
)gnicaps1-1-3(latnoziroH
)gnicaps1-1-1(lacitreV
Page 27
INSTALLATION ACCESSORIES CONTINUED
detsiL tneVeruceS stnenopmoC
.oN.taC.oNledoMnoitpircseD
8691H2-TH5.4VSnoitanimreTerauqSlatnoziroH
2512H1-VGC5.4VSnoitanimreTlacitreV
7864H 6174H 7174H
STC5.4VS B-STC5.4VS CT-STC5.4VS
07L776L5.4VSnoitceStneV)mm251(hcni6 17L7721L5.4VS
27L7742L5.4VS 37L7763L5.4VS 47L7784L5.4VS
57L77AL5.4VSnoitceScipocseleT 67L7754E5.4VSwoblEeergeD54
77L7709E5.4VSwoblEeergeD09
87L77F5.4VSgnihsalFfooRtalF 97L77AF5.4VSgnihsalF.tsujdA21/7ot21/1 08L77BF5.4VSgnihsalF.tsujdA21/21ot21/7 18L776CS5.4VS)xob/sralloc6(sralloCmrotS
3816H5FH5.4VSlatnoziroHrecapS/potseriF 4816H5FH5.4FSlatnoziroHxelFrecapS/potseriF 7422HFV5.4VSkcaP01-recapS/potseriF 39K69US5.4VSpartStroppuS
49K69ASR5.4VSdleihSnoitalusnIcittA
29K69PS5.4VSetalPtroppuS
detsiL xelFeruceS stnenopmoC
.taC
.oN
)08K69(recapS/potseriFhtiw
)16L47(retpadAdna
9691H2-TH5.4FSnoitanimreTerauqSlatnoziroH
ledoM
.oN
noitpircseD
.retpadaxelfdnaspmalcraeg,recaps/potserifedulcnistiknoitanimretesehT
xelFtuohtiw
78L7721TIKFS.ni21htiw.mreTerauqSxelF
xelFdesserpmoc*fomm503(
88L7781TIKFS.ni81htiw.mreTerauqSxelF
erauqS.mreTpoTesahC
klB,erauqS.mreTpoTesahC
noitanimreTattoCarreT
98L7742TIKFS.ni42htiw.mreTerauqSxelF 09L7763TIKFS.ni63htiw.mreTerauqSxelF
xelFdesserpmoc*fo)mm754( xelFdesserpmoc*fo)mm016( xelFdesserpmoc*fo)mm419(
tneV)mm503(hcni21
noitceS
tneV)mm016(hcni42
noitceS
tneV)mm419(hcni63
noitceS
tneV)mm9121(hcni84
noitceS
19L7784TIKFS.ni84htiw.mreTerauqSxelF
xelFdesserpmoc*fo)mm9121(
47L6503TVFSottalf(xelFrof.nimreTlacitreV
noitces,retpadAxelFhtiw)21/6
ralloctroppusfoor,tnevdigirfo
dnagnihsalffoor,ylbmessa
.rallocmrots
57L6554TVFSot21/6(xelFrof.nimreTlacitreV
noitcesretpadAxelFhtiw)21/21
ralloctroppusfoor,tnevdigirfo
dnagnihsalffoor,ylbmessa
.rallocmrots 01L0681-FSxelFdesserpmoc*)m94.5(.tf81 30K8921-FSxelFdesserpmoc*)m66.3(.tf21
.rallocmrotsahtiwdegakcapemocsgnihsalfgniwollofehT
.oN.taC.oNledoMnoitpircseD
.retpadaxelfdnaspmalcraeg,recaps/potserifedulcnistiknoitanimretesehT
90L49**SSTH-FSerauqSllamSlatnoziroH
xelFtuohtiwnoitanimreT
40L49**SS21TIKFShtiw.mreTerauqSllamSxelF
fomm503(.ni21
xelFdesserpmoc*
50L49**SS81TIKFShtiw.mreTerauqSllamSxelF
)gnicaps1-1-5(
fo)mm754(.ni81
xelFdesserpmoc*
)gnicaps1-1-5(
60L49**SS42TIKFShtiw.mreTerauqSllamSxelF
fo)mm016(.ni42
)gnicaps1-1-1(lacitreV
70L49**SS63TIKFShtiw.mreTerauqSllamSxelF
xelFdesserpmoc*
fo)mm419(.ni63
xelFdesserpmoc*
80L49**SS84TIKFShtiw.mreTerauqSllamSxelF
fo)mm9121(.ni84
xelFdesserpmoc*
.oN.taC.oNledoMnoitpircseD
20L785.4VS
30L99 20L99
drauGnoitanimreT
SGH
8891H 5891H
33-ASTC
33-OSTC
,tiKduorhSpoTesahC
3x3poThcrA
,tiKduorhSpoTesahC
3x3poTnepO
7891H
63KRH5.4VS 41KRH5.4VS
"63tiKresiRlatnoziroH "41tiKresiRlatnoziroH
6891H
44-OSTC 64-OSTC
,tiKduorhSpoTesahC
4x4poTnepO
,tiKduorhSpoTesahC
6x4poTnepO
0285H
KSTH5.4
tiKduorhSnoitanmreT
*All compressed flex vents can be expanded up to two times. **May be used with 30" and 35" models only.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
27
Page 28
Burner Assembly
Gas Valve
Assembly
Orifice
Air Adjustment Arm
GAS CONVERSION KITS
WARNING: THIS CONVERSION KIT SHALL BE INSTALLED BY A QUALIFIED SERVICE AGENCY IN ACCORDANCE WITH THE MANUFACTURER'S IN­STRUCTIONS AND ALL APPLICABLE CODES AND REQUIREMENTS OF THE AUTHORIZED HAVING JURISDICTION. IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE, EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. THE INSTALLATION IS NOT PROPER AND COM­PLETE UNTIL THE OPERATION OF THE CONVERTED APPLIANCE IS CHECKED AS SPECIFIED IN THE OWNER INSTRUCTIONS SUPPLIED WITH THE KIT. THE QUALIFIED SERVICE AGENCY PERFORMING THIS INSTALLATION ASSUMES RESPONSIBILITY FOR THIS CONVERSION.
In Canada: THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 AND .2 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN1­B149.1 ET.2.
03VDLPMtlovillim3616H 53VDLPMtlovillim5796H 04VDLPMtlovillim95L58 54VDLPMtlovillim96L58 03VDLPMcinortcele6616H 53VDLPMcinortcele3796H 04VDLPMcinortcele8616H 54VDLPMcionrtcele9616H
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SERVICE CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET TOUTES EXIGENCES ET CODES APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION. SI L'INFORMATION DANS CETTE INSTRUCTION N'EST PAS SUIVIE EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE PERSONNELLE DE VIE. L'AGENCE QUALIFIÉE DE SERVICE EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.
Millivolt Appliances
tiKnoisrevnoCsaGenaporPoTlarutaN
Step 4. SIT Systems - Refer to
.oNsledoMepyTtinU.oNgolataC
page 29
the kit. Using a Torx T20, remove and discard the three pressure regulator mounting screws. Remove the pressure regulator, spring, pop­pet, diaphragm and bushing. Discard all removed components.
Ensure the rubber gasket installed on the back of the replacement pressure regulator is prop­erly positioned and install the new pressure regulator using the new screws supplied with the kit. Tighten screws to 25 In. lb. torque.
and the instructions provided with
Figure 48 on
28
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the neces­sary components needed to complete the task including labeling that must be affixed to en­sure safe operation.
Kit part numbers are listed here and the following steps detail the conversion procedure.
Step 1. Turn off the gas supply to the appliance. Step 2. Carefully remove the logs. Exercise
care so as not to break the logs. Step 3. Refer to
Remove the burner assembly with attached venturi tube.
Figure 47
.
tiKnoisrevnoCsaGlarutaNotenaporP
.oNledoMepyTtinU.oNgolataC
03VDLPMtlovillim5616H 53VDLPMtlovillim8696H 04VDLPMtlovillim7716H 54VDLPMtlovillim26L58 03VDLPMcinortcele0716H 53VDLPMcinortcele4796H 04VDLPMcinortcele2716H 54VDLPMcinortcele3716H
Figure 47
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 29
Pressure
.oNledoM
ezisecifirO
larutaNenaporP
03-VDLPM"070.0
16#
)"930.0(
53-VDLPM
54#
)"280.0(
"840.0
04-VDLPM
14#
)"640.0(
45#
)"550.0(
54-VDLPM
04#
)"890.0(
35#
)"595.0(
Regulator
Figure 48
Remove These Components
Ground
(TP)
Gas Outlet
To Burner
Pilot Stage Terminal
TP
Pressure-Tap (Inlet)
TH
TP
LO
TH
IN
HI
OUT
VENT
Pilot Gas Outlet
PILOT
Supply Gas
IN
Inlet
Step 5. Attach manometer to the manifold
side pressure test fitting and verify manifold pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
Step 6. Refer to
Figure 49
and remove the pilot hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the one provided with the kit.
Pilot
Orifice
Figure 49
Electronic Appliances Step 7. Dexen Electronic Valves -
See
Figure 50
with the kit. Remove and discard the two pressure regulator mounting screws. Re­move the pressure regulator and diaphragm. Discard all removed components. Ensure the provided diaphragm is installed properly onto the replacement pressure regulator and install the new pressure regulator using the new screws supplied with the kit. Tighten screws.
See
Figure 51
as follows: Remove pilot hood assembly to access the phillipped pilot orifice. Remove and replace the orifice with the one pro­vided with the kit. Exercise extreme care
to prevent damage to or breakage of the ignitor assembly.
and the instructions provided
and replace the pilot orifice
Burner Stage Terminal
Regulator Mounting Screw
Figure 50
ELECTRONIC
Sensor
Pilot Hood
Ignitor
Note: If the ignitor is damaged, a replacement kit is available, order Catalog Number 87L54.
Figure 51
All Models Step 8. (Refer to
A. Remove the orifice from the manifold and
replace it with the one provided in the kit. See the following table for orifice sizes for natural and propane models orifice.
B. Retrieve the burner and slide the venturi tube over the orifice. Set the shutter adjusting opening as shown in
Figure 47 on page 28
. Figure 52
Figure 43
illustrates the
, page 25.
)
Pressure-Tap (Manifold)
Figure 52
Step 9. Reassemble the remaining compo-
nents by reversing the procedures outlined in the preceding steps. Use pipe joint compound or Teflon tape on all pipe fittings before install­ing (ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds on flare fittings).
Step 10. Attach the conversion label provided in the conversion kit to the rating plate on the appliance.
Step 11. Turn on gas supply and test for gas leaks.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
29
Page 30
30
NOTE: THIS PAGE INTENTIONALLY LEFT BLANK.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Page 31
NOTE: THIS PAGE INTENTIONALLY LEFT BLANK.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
31
Page 32
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2007 by Lennox Hearth Products
P/N 850,043M REV. F 09/2008
32
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
1110 West Taft Avenue • Orange, CA 92865
Loading...