Lennox Hearth 2-EN53-VDLPM User Manual

INSTALLATION INSTRUCTIONS
DIRECT VENT
This appliance may be installed in an aftermarket perma­nently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
In the Commonwealth of Massachusetts:
• Installation must be performed by a licensed plumber or gas fitter. See Table of Contents for location of additional Commonwealth of Massachusetts requirements.
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PER­SONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors or liquids in the vicin­ity of this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Portland
US
A French manual is available upon request. Order Form Number 850,043CF.
Ce manuel d’installation est disponible en francais, simplement en faire la demande. Numéro de la pièce 850,043CF.
OTL Report No. 116-F-47-5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
MERIT
VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS P/N 850,043M REV. F 09/2008
MODELS
sledoMtlovilliMsledoMcinortcelE
MN03-VDLPMEN03-VDLPM MP03-VDLPM2-EN53-VDLPM
2-MN53-VDLPMEN04-VDLPM
2-MP53-VDLPMEN54-VDLPM MN04-VDLPM MP04-VDLPM MN54-VDLPM MP54-VDLPM
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d'essence ni d'autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur de gaz:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones se trouvant dans le batiment où vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service dos incendies.
L'installation et service doit être exécuté par un qualifié installeur, agence de service ou le fournisseur de gaz.
1
TABLE OF CONTENTS
Packaging........................................ page 2
Introduction..................................... page 2
General Information......................... page 2
Location .......................................... page 4
Appliance and Vent Clearances....... page 5
Requirements for Commonwealth
of Massachusetts .......................... page 5
Vent Termination Clearances ........... page 5
Typical Installation Sequence .......... page 6
Detailed Installation Steps ............... page 6
Step 1. Framing ............................. page 6
Step 2. Routing Gas Line............... page 6
Fireplace Specifications ................... page 9
Step 3. Install the Vent System...... page 10
Vertical Termination Systems .......... page 10
Vent Section Length Chart............... page 11
Vertical Vent Tables and Figures...... page 14
Horizontal Termination System........ page 15
Horizontal Vent Tables and Figures . page 18
Venting Using Flexible Vent Pipe ..... page 21
Step 4. Field Wiring ....................... page 22
Step 5. Connecting Gas Line.......... page 23
Step 6. Installing Logs................... page 24
Step 7. Checking Unit Operation..... page 24
Step 8. Installing Glass Door ......... page 24
Step 9. Burner Adjustments........... page 25
Finishing Requirements................... page 25
Cold Climate Insulation.................... page 26
Installation Accessories................... page 26
Gas Conversion Kits.................. page 28
PACKAGING
The assembled vented gas fireplace heater is packaged with the folowing:
1 - The logs are packaged in a carton located
within the firebox.
2 - One bag of volcanic stones is located in the
bottom compartment.
3 - One envelope containing the litera-
ture package, which consists of the homeowner's manual, installation in­structions, log set supplement, warranty, gas access plate, screws (4) and gasket. The envelope is located in the bottom compartment.
4 - One vent restrictor, to be used as detailed
on page 10.
5 - One hood and one control compartment
cover and one 45 degree starter elbow are strapped to the top of the unit.
INTRODUCTION
These fireplaces are designed, tested and listed for operation and installation with, and only with,
Secure Vent™ Direct Vent System Components, Secure Flex™ Flexible Vent Components manu-
factured by Security Chimneys International and Z-Flex™ Model GA Venting Systems, listed to UL1777 and ULCS635 manufactured by Flex­master Canada Limited. These approved vent system components are labeled for identifica­tion. DO NOT use any other manufacturer's vent components with these appliances.
Millivolt appliances are designed to operate on natural or propane gas. A millivolt gas control valve with piezo ignition system pro­vides safe, efficient operation. There is no optional blower with these units.
Both millivolt and electronic versions of these appliances are listed by Omni-Test Labora­tories for installation in bedrooms and mo­bile homes.
The Installation must conform to local codes or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1/NFPA 54
, or the
Natural Gas and Propane Installa-
tion Code, CSA B149.1
The appliance, when installed, must be elec­trically grounded in accordance with local codes or, in the absence of local codes, with
National Electrical Code, ANSI/NFPA 70
the or the
Canadian Electrical Code, CSA C22.1
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
.
GENERAL INFORMATION
Note: Installation and repair should be per-
formed by a qualified service person. The appli­ance should be inspected annually by a qualified professional service technician. More frequent inspections and cleanings may be required due to excessive lint from carpeting, bedding mate­rial, etc. It is imperative that the control compart­ment, burners and circulating air passage ways of the appliance be kept clean. S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instructions d'installation et d'utilisation qui accompagnent l'appareil.
TYPICAL INSTALLATION
, .
This manual is part of a set of three support­ing this product. Refer to manuals 875,036M for Care & Operations and 750,230M for Log Placement Guide.
Please read and understand these instructions before beginning your
installation.
2
Electronic appliances are designed to operate on natural or propane gas. An electronic inter­mittent pilot ignition system provides safe, ef­ficient operation. External electrical power is recommended to operate these units. If the system operates on line voltage with 3V adapt­ers, two (2) "D" batteries can be used as a backup in case of a power outage. The elec­tronic appliance can be operated solely with two (2) "D batteries.
These appliances comply with National Safety Standards and are tested and listed by Omni­Test Laboratories (Report No. 116-F-47-5) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/ CGA-2.17-M91 in both USA and Canada, as vented gas fireplace heaters.
Figure 1
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.
These appliances are designed to operate on natural or propane gas only.
Millivolt And Electronic Models -
Millivolt and Electronic models come standard with the manually-modulated gas valve; flame appearance and heat output can be controlled at the gas valve.
Input of millivolt and electronic models is shown in the following table:
htiwsledoMcinortcelEdnAtlovilliM
evlaVsaGdetaludoM-yllaunaM
saGlarutaNsaGenaporP
DLPMV03
DLPMV53
.oNledoM
04VDLPM
54VDLPM
tupnI
etar
)H/UTB(
000,31
ot
000,01 000,91
ot
000,51 000,52
ot
005,81 000,62
ot
02000,
.oNledoM
DLPMV03
DLPMV53
04VDLPM
54VDLPM
tupnI
etar
)H/UTB(
005,11
ot
000,9
000,81
ot
000,41 005,12
ot
005,61 000,52
ot
000,91
All Models -
Maximum manifold pressure is 3.5 in. w.c. (0.87 kPa) for natural gas and 10 in. w.c. (2.49 kPa) for LP/Propane gas.
%seicneiciffE
sledoM
4P
03VDLPM 855636856646 53VDLPM 065636265636 04VDLPM 857646757656 54VDLPM 857656066646
saGlarutaeNnaporP
ydaetS
etatS
EUFA4P
ydaetS
EUFA
etatS
Note: Power venting of direct vent fireplaces may result in the reduction of efficiencies by as much as ten percent. Consider this in making any venting and heating decisions in any installation application.
Installations at Altitudes of 0 to 4500 ft.­Units are tested and approved for elevations of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.­For elevations above 4500 feet (1372 meters), install the unit according to the regulations of the local authorities having jurisdiction and, in the USA, the latest edition of the National Fuel Gas Code (ANSI Z223.1) or, in Canada, the latest edition of the CAN1-B149.1 and .2 codes.
Table 1
shows the units' gas orifice size for
the elevations indicated.
The millivolt appliances are manually controlled and feature a spark ignitor (piezo) that allows the appliance's pilot gas to be lit without the use of matches or batteries. This system provides continued service in the event of a power outage.
noitavelE
teeF
)sretem(
0054-0
)2731-0(
.taN.porP
54#
)"280.0(
14#
)"690.0(
04#
)"890.0(
ezisecifirO
16#
)"930.0(
"840.0
45#
)"550.0(
35#
)"5950.0(
ledoM
.oN
03VDLPM "070.0
53VDLPM
04VDLPM
54VDLPM
Table 1
Do not use these appliances if any part has been under water. Immediately call a qualified, pro­fessional service technician to inspect the ap­pliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas se servir de cet appareil s'il a été plongé dans l'eau, complètement ou en partie. Appeler un technicien qualifié pour inspecter l'appareil et remplacer toute partie du système de contrôle et toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an af­termarket permanently located, manufac­tured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This ap­pliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison préfabriquée (É.-U. seulement) ou mobile déjà installée à demeure si les réglements locaux le permettent. Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique. Ne pas l'utiliser avec d'autres gaz sauf si un kit de con­version certifié est installé.
Test gage connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the inlet and OUT for the manifold side). A 1/8" NPT test gage connec­tion is provided at the inlet and outlet side of the electronic gas control valve.
Minimum inlet gas pressure to these appli­ances is 5.0 inches water column (1.24 kPa) for natural gas and 11 inches water column (2.74 kPa) for propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to these appliances is 10.5 inches water column (2.61 kPa) for natural gas and 13.0 inches water column (3.23 kPa) for propane.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure testing of the gas supply piping sys­tem at test pressures equal to or less than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of 1/2 psig (3.5 kPa).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
These heater rated appliances are intended for use as supplemental heaters only. Using these appliances as a primary heat source may void the manufacturers warranty.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Turn off the gas supply to the appliance and have it serviced by a qualified professional, as it may not be op­erating correctly.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING INSTRUCTIONS PROVIDED IN THIS DOCUMENT WILL RESULT IN AN IMPROP­ERLY INSTALLED AND OPERATING APPLIANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/ OR ITS OPERATING CONTROLS IS DAN­GEROUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERIOUS INJURY OR DEATH FROM FIRE, BURNS, EXPLOSION OR CARBON MON­OXIDE POISONING.
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES. USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
HORIZONTAL VENT
APPLICATION
HORIZONTAL VENT
Figure 2
APPLICATION
RECESSED
INSTALLATION
VERTICAL VENT
APPLICATION
HORIZONTAL VENT
APPLICATION
03VDLPM )2311(4/344)2311(4/344 53VDLPM )8811(4/364)8811(4/364
HORIZONTAL VENT
APPLICATION
HORIZONTAL VENT
APPLICATION
.oNledoM
54VDLPM/04VDLPM )4131(4/315)4131(4/315
HORIZONTAL VENT (Top Vent Application)
Typical Locations
tneVpoT
tneVeruceSxelFeruceS
VERTICAL VENT (Top Vent Application)
)mm(sehcnithgieHflehS
WARNING: DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIALS ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES ENFANTS. GARDER LES VÊTEMENTS, LES MEUBLES, L'ESSENCE OU AUTRES LIQUIDES À VAPEUR INFLAMMABLES À COTE DE L'APPAREIL.
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. Consideration should be given to traffic ways, furniture, draperies, etc., due to elevated surface temperatures (
The location should also be free of electrical, plumbing or other heating/air conditioning duct­ing. These direct vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace. Utility shelves like these are commonly used for locat­ing television sets and decorative plants.
Figure 2
).
Figure 3
KCAB
SEDIS
SRECAPSPOT)mm0(.ni0
ROOLF)mm0(.ni0
fomottoBmorF
gnilieCottinU
TNEV*)mm4.52(.ni1
TNORF)sretem9.0(.teeF3
Do not insulate the space between the
appliance and the
area above it.
Shelf Height
(
see table)
Shelf Above Fireplace With Top Venting
)mm4.52(.ni1
**)mm4.52(.ni1
*Note: 3 in. (76mm) above any horizontal/ inclined vent component for the MPLDV30
srecaps)mm0(.ni0
in all cases, and for the MPLDV35, MPLDV40 & MPLDV45, when the vent center line is greater than 48" (1219 mm) above the fire-
srecaps)mm0(.ni0
place top wrapper surface. Increase this clearance to 5" (127 mm) for the MPLDV35, MPLDV40 & MPLDV45, when the vent cen­ter line is less than 48" (1219 mm) above the
)mm6261(.ni46
fireplace top wrapper surface. **Note: See page 6, step 1 for clearance
requirements to the nailing flange located at
SECNARAELCECIVRES
each side of the unit and any screw heads adjacent to it.
Table 2
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
To provide for the lowest possible shelf surface the venting attached to the top vent should be routed in a way to minimize obstructions to the use of the space above the appliance. Do not
insulate the space between the appliance and the area above it. Refer to
Figure 3
. The
minimum height from the base of the appliance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in the table in
Figure 3
.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materi­als. However, if installed on combustible mate­rials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
APPLIANCE AND VENT CLEARANCES
Refer To Table 2 for approved clearances to combustibles for the models covered in this manual, with the following exception: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is recessed, the side walls surrounding the unit must not extend beyond the front edge of the unit. See
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical vent elements.
Clearances for horizontal vent elements are 1" (25 mm) at the sides and 1" (25 mm) on the bottom. Clearances above horizontal vent elements are 3" (76 mm) for all models and all applications.
Exception: Clearance is 5" (127 mm) for MPLDV35, MPLDV40 & MPLDV45, when the center line of the hori­zontal run is less than 48" (1219 mm) above the fireplace top wrapper surface.
Figure 2
Massachusetts And New York City, NY Requirements
These appliances are approved for installation in the following USA locations listed in the following:
Massachusetts:
These fireplaces are approved for installation in the US state of Massachusetts if the follow­ing additional requirements are met-
Installation and repair must be done by a plumber or gas fitter licensed in the Common­wealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
The individual manual shut-off must be a T­handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori­zontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must
.
comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
New York City, NY:
These fireplaces are approved for installation in New York City in the US state of New York.
VENT TERMINATION CLEARANCES
These instructions should be used as a guide­line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and ­B149.2 in Canada.
Vertical Vent Termination Clearances
Terminate single vent caps relative to building components according to
Figure 4
.
Terminate multiple vent terminations accord­ing to the installation codes listed at the top of
this page.
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
2 FT MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum Clearance to Combustibles
*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT
12
Roof Pitch is X/12
hctiPfooR
Vertical
Wall
X
H
)teef(
21/6ottalF0.1
21/7ot21/6revO52.1 21/8ot21/7revO5.1 21/9ot21/8revO0.2
21/01ot21/9revO5.2
21/11ot21/01revO52.3
21/21ot21/11revO0.4
Figure 4
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any over­head combustible projection of 2-1/2" (64 mm) or less. See ing 2-1/2" (64 mm), see terminations may be located as close as 6" (152mm) to any (non-combustible and com­bustible) exterior sidewall. This distance may be decreased to 2" (51mm) for non-combus­tible exterior sidewalls only, if the SV4.5HT-2 termination is used. For additional vent loca­tion restrictions, refer to
Figure 5.
For projections exceed-
Figure 5
. All horizontal
Figure 8 on page 7
.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described.
See the page numbers references in the follow­ing steps for detailed procedures.
Step 1. (page 6) Construct the appliance fram­ing. Position the appliance within the framing and secure with nailing brackets.
Step 2. (page 6) Route gas supply line to
appliance location.
Step 3. (page 10) Install the vent system and exterior termination. Install additional restrictor, if needed.
Step 4. (page 21) Field Wiring
a. Millivolt Appliances The operating control
switch is factory installed.
b. Electronic Appliances – Connect 120 Vac electrical power to the appliance receptacle.
Step 5. (page 22) Make connection to gas supply.
Step 6. (page 23) Install the logs and glow­ing embers.
Step 7. (page 23) Checkout appliance operation.
Step 8. (page 23) Install glass door frame
assembly.
Step 9. (page 24) Adjust burner to ensure proper flame appearance.
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired. Re­move the shipping carton, exposing the front glass door. Remove the bottom panel by lifting and pulling it towards the front.
Open the two latches (located under the firebox floor) securing the glass door. Remove the door by tilting it outward at the bottom and lifting it up. Set the door aside protecting it from inadvertent damage.
See Figure 39 on page 23.
Horizontal Vent Termination Clearances
Combustible Projection
inches or less in length
2-1/2
Combustible Projection greater
than 2-1/2 inches in length
Ventilated
Soffit
Unventilated
Soffit
18"
(457 mm)
12"
(305 mm)
3"
(76 mm)
Side Elevation View
Termination Kit
Figure 5 -
Side Elevation View
Step 1. FRAMING
Frame these appliances as illustrated in
on page 8,
in a corner See
unless the appliance is to be installed
.
Figure 10 on page 8
for corner framing installations. All framing details must allow for a minimum clearance to combustible framing mem­bers as shown in
Table 2 on page 4
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed. Headers may be in direct contact with the appli­ance top spacers but must not be supported by them or notched to fit around them. All construc­tion above the appliance must be self supporting, DO NOT use the appliance for structural support.
The fireplace should be secured to the side framing members using the unit's nailing flanges - one top and bottom on each side of the fireplace front. See
Figure 6.
Use 8d nails or their equivalent. Unit Being Secured by Its Nailing
Figure 9
.
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line along the inside of the left side framing as shown in Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a flex­ible gas line connector and 1/2 inch shutoff valve. (See step 6 on page 22).
Figure 7
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible) exterior sidewall. This distance may be decreased to 2” (51mm) for non-­combustible exterior sidewalls only, if the SV4.5HT-2 termination is used.
Side
Framing
Left Side Top Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing flanges, are EXEMPT from the 1” clearance to combustible requirements for the firebox outer wrapper. Combustible framing may be in
direct contact with the nailing flanges and may be located closer than 1” from screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of this manual.
To The Framing
Termination Kit
Nailing Flanges Are Provided At All Four Corners At 5/8”, 1/2” And Flush Settings
Flanges to the Framing
Figure 6
.
Front Corner of
Fireplace Framing
2-1/4"
(57 mm)
4-3/4"
(121 mm)
Unit Nailing Flange
Left Side
(165 mm)
6-1/2"
Figure 7
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
V
L
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
*
See Item D in the Text Below.
Exterior Wall
*18”
Horizontal Termination
Inside Corner
B
ytreporpcilbupno
.sgnillewd
NOTE: Local Codes Or Regulations May Require Different Clearances.
of Termination
V
18”
Detail D
F
V
A
X
Center Line
Ventilated Soffit
V
Fixed
Closed
Window
V
C
= Air Supply Inlet
C
C
C
V
Inside
Corner Detail
V
A
B
Operable
V
Window
B
B
= Vent Termination
G
B
= Area where Termination is not Permitted
NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service.
= 9” in U.S.
A
= 12” in Canada
3 ft.
X
A
J
A
3 ft.
.ynoclabro,kced,hcrop,adnarev,edargevobaecnaraelC=A *)mc03(sehcni21**)mc03(sehcni21
.denepoebyamtahtroodrowodniwotecnaraelC=B secnailpparof)mc51(sehcni6
wodniwdesolcyltnenamrepotecnaraelC=C otdednemmocer)mm503(sehcni21
noitasnednocwodniwtneverp
ehtevobadetacoltiffosdetalitnevotecnaraelclacitreV=D
)mm854(sehcni81)mm854(sehcni81
)mm854(sehcni81foecnatsidlatnozirohanihtiwnoitanimret
noitanimretehtfoenilretnecehtmorf
***tiffosdetalitnevnuotecnaraelC=E )mm503(sehcni21)mm503(sehcni21
renrocedistuootecnaraelC=F muminim)mc7.21(sehcni5muminim)mc7.21(sehcni5
renrocedisniotecnaraelC=G muminim)mc2.51(sehcni6muminim)mc2.51(sehcni6
evobadednetxeenilretnecfoedisnihcaeotecnaraelC=H
ylbmessarotaluger/retem
teltuotnevrotalugerecivresotecnaraelC=I *)mc19(teef3**)mc19(teef3
rognidliubottelniylppusrialacinahcemnonotecnaraelC=J
ecnailpparehtoynaottelnirianoitsubmoceht
telniylppusrialacinahcemaotecnaraelC=K *)m38.1(teef6 teef01nihtiwfievoba)mc19(teef3
detacolyaweviddevaproklawedisdevapevobaecnaraelC=L
‡)m31.2(teef7‡)m31.2(teef7
ynoclabrokced,hcrop,adnarevrednuecnaraelC=M ‡*)mc03(sehcni21‡)mc03(sehcni21
)mumixaM(evoclAfohtpeD=N *)m38.1(teef6**)m38.1(teef6
)evoclA(noitanimreTotecnaraelC=O *)mm2.51(sehcni6**)mm2.51(sehcni6
)muminiM(evoclAfohtdiW=P *)mc19(teef3*)mc19(teef3
)evoclA(evobAelbitsubmoCotecnaraelC=Q *)mm754(sehcni81**)mm754(sehcni81
.edoCnoitallatsnIenaporPdnAsaGlanoitaN1.941B-ASCtnerrucehthtiwecnadroccanI*
.sedoCsaGleuFlanoitaN45APFN/1.322ZSISNAtnerucehthtiwecnadroccanI**
.muminim)mc67(sehcni03-lairetamtiffoslynivotderiuqerecnaraelC***
H
I
*noitallatsnInaidanaC**noitallatsnISU
)mc03(sehcni21,)Wk3(hutB000,01<
)Wk3(hutB000,01>secnailpparof
teef51fothgiehanihtiw)mc19(teef3
*ylbmessarotaluger/retemehtevoba
secnailpparof)mc51(sehcni6
)mc03(sehcni21,)Wk3(hutB000,01<
)Wk3(hutB000,01>secnailpparof
:roolfehthtaenebsedis2muminimanonepoyllufsiynoclabrokced,hcrop,adnarevfidettimrepylnO‡*
P
N
Q
M
V
N
O
V
D
V
secnailpparof)mc51(sehcni6
)mc32(sehcni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
otdednemmocer)mm922(sehcni9
noitasnednocwodniwtneverp
teef51fothgiehanihtiw)mc19(teef3
**ylbmessarotaluger/retemehtevoba
secnailpparof)mc51(sehcni6
)mc32(sehcni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
**yllatnoziroh)m3(
htobsevresdnasgnillewdylimafelgnisowtneewtebdetacolsihcihwyawevirddevaproklawedisaevobayltceridetanimrettonllahstnevA
Figure 8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
FIREPLACE FRAMING SPECIFICATIONS
Framing should be
constructed of 2 x 4
or larger lumber.
B
1/2 A
A
Inches (mm)
Figure 9
D
C
Framing
10-1/2
(
267
)
5-1/8 (130)
C is the required framing depth
dimension when the finish material
(drywall) thickness is 1/2 in. (13mm).
(178)
.oNledoMABCD
.ni61/9034/3042/16183
03VDLPM
mm6875301914569
*7
**12-1/8
(308)
*9" (229 mm) For MPLDV-35, 40 & 45
**14-1/8" (359 mm) For MPLDV-35, 40 & 45
.ni61/953044/32/16183
53VDLPM
mm3095301914569
.ni61/9044/3542/16134
04VDLPM
mm030126119142901
.ni61/954544/32/16134
54VDLPM
mm751126119142901
.oNledoMABCDE
.ni4/1034/1257346/7418/162
03VDLPM
mm8677231049853466
.ni
53VDLPM
mm
.ni4/1044/126448/5718/113
04VDLPM
mm220118518111844197
.ni
54VDLPM
mm
Note­Venting requirements for corner installations - the horizontal vent length “a” to “b,” must not exceed 28 inches (711 mm)
Note: The appliance 45° collar can be rotated about its axis to align for
corner installation. Remove interfering corner spacer. This spacer is used for shipping only.
May Be
Removed
Back wall of chase/enclosure
(including any finishing materials)
*D
*C
a
A
*B
*These dimensions occur when one 45 degree elbow is connected directly to the appliance collar.
May Be Removed
b
7 (178)
*E
Inches
(millimeters)
8
Figure 10
Corner Framing with Square Termination (SV4.5HT-2)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
FIREPLACE SPECIFICATIONS
F
G
6 5/8 (168)
TOP VIEW
4 3/4 (121)
LEFT SIDE VIEW
2 9/32 (58)
13 11/64
(335)
E
3 5/16 (100 mm)
10
(254 mm)
A
C
D
H
B
FRONT VIEW
17
(432)
RIGHT SIDE VIEW
1 (25.4)
Unit Dimensions
Figure 11
.oNledoMABCDEFGH
.ni2/1042/1738/5028/1424/1034/3918/794/172
03VDLPM
mm9201359435316867205152296
.ni2/1042/1738/5028/1924/1534/3428/3214/172
53VDLPM
mm9201359435047598926413296
.ni2/1542/1248/5528/1434/1044/3928/7414/123
04VDLPM
mm651108011567682201657873918
.ni2/1542/1248/5528/1934/1544/3438/3714/123
54VDLPM
mm651108011564999411388144918
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guide­line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and ­B149.2 in Canada.
These fireplaces are designed, tested and listed for operation and installation with, and only with, Secure Vent Direct Vent System Components, Secure Flex Flexible Vent Components manufactured by Security Chimneys International and Z-FLEXModel GA Venting Systems listed to UL1777 and ULCS635 manufac­tured by Flexmaster Canada Limited. These approved vent system components are labeled for identification. DO NOT use any other manufacturer's vent com­ponents with these appliances.
These fireplaces must be vented directly to the outside.
Determine the venting for the appliance. If the vent run will include at least 8 feet of vertical rise, then install the second restrictor in the appliance collar before connecting any vent (Refer to tor inside the fixed restrictor.
Note: The second restrictor is included within the firebox.
Figure 12
Exhaust Vent
). Place the second restric-
Fixed Restrictor
The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclos­ing wall (such as a chase). There is no require­ment for inspection openings in the enclosing wall at any of the joints in the vent pipe.
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, deter­mine vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section relating to your installation. A list of approved
venting components is shown in the tables on page 26.
VERTICAL TERMINATION SYSTEMS (ROOF)
Figures 13, 17 and 23 through 25 on pages 12, 14 and 15
and their associated Vertical Vent Tables illustrate the various vertical vent­ing configurations that are possible for use with these appliances. Secure Vent pipe ap­plications are shown in these figures; Secure Flex pipe may also be used.
A Vertical Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.
Both these vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is speci­fied in ANSI Z223.1-(latest edition) (In Canada, the current CAN-1 B149 installation code) by major building codes. Always consult your local codes for specific requirements. A gen­eral guide to follow is the Gas Vent Rule (refer to
Figure 4
on page 6 ).
Vertical (Straight) Installation
SV4.5CGV-1
Termination
40' Max. (12.2 M)
6' Min.
(1.8 M)
SV4.5FA OR SV4.5FB Flashing AND SV4.5SC STORM COLLAR
1" (25.4 mm) Minimum Clearance to Combustibles
*SV4.5VF Firestop/Spacer
SV4.5L6/12/24/36/48 Vent Sections
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF
Figure 13
Vertical (Offset) Installation
Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to Vertical Vent Fig- ures and Tables on page 14 and 15 to select the type of vertical installation desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section Length Chart on page 11 for an aid in selecting length combinations. Elbows are available in 90° and 45° configurations. Refer to SV4.5E45 and SV4.5E90 elbow dimensional specifications.
Figure 18
for the
10
Second Restrictor (For Vertical Vent Only)
Figure 12
Determine the number of straight vent sec­tions required. 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 461/2" (1181 mm) net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Refer to the Vent Section Length Chart.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Loading...
+ 22 hidden pages